HIGH POWER LABORATORY CENTRAL POWER RESEARCH INSTITUTE, P. B.NO. 8066, SADASmV ANAGAR SUB P.O PROF. SIR.C.V. RAMAN ROAD, BANGALORE-560 080, INDIA PHONE: + 9]- (0) 80-23600574, FAX: + 91 (0) 80-23601213 CPRI ch. Test Report Number Name & Address of the Customer Name & Address of the Manufacturer Particulars of sample tested Sample Type Designation Serial number Number of samples tested Date(s) of Test(s) CPRI Sample Code No. Condition of sample on receipt Particulars of tests conducted Test in accordance with Standard/Specification Sampling Plan Customer's requirement Deviation if any Name of the witnessing persons Customer's representative NABL ACCREDITED LABORATORY Certificate No. TOOlO Sheet No.1 of 8 TEST REPORT : HPL07077 Dated: 26/06/2007 : Mis. Supreme Power Equipment Pvt Ltd., No: 55, S1DCOIndustrial Estate, Thirumazhisai, Chennai-602107. : Mis. Supreme Power Equipment Pvt Ltd., No: 55, SIDCO Industrial Estate, Thirumazhisai, Chennai-602107. : 16 MV A, 33 kV / 11kV, 3phase Transformer : Conventional Type, Oil cooled. : Power Transformer : SPEL/2081 : One : 10thApril 2007 : HPL07S0089 : New : Dynamic ability to withstand short-circuit test. : 1S:2026 - Part-l (1977) :Nil :Nil : Nil : Mr. B. Sivaramakrishnan, Sr. Manager(QA) : Mr. G. Sundaresan Other than Customer's representative Test subcontracted with address of the laboratory : No load loss, load loss measurement, Induced over voltage test and separate source voltage withstand test conducted at Mls.Supreme Power Equipment Pvt. Ltd., Chennai. - 602 107. Documents constituting this report (In words) Number of sheets : Eight Number of oscillograms : Nine Number of photographs : Three Number of test circuit diagrams : One Number of sample drawings : Four ~rr4~ (G.Sengupta) ADDJTIONAL DIRECTOR AUTHOR]SED SIGNA TORIES
3

NABL ACCREDITED LABORATORY Certificate No. … Reports Scanned/16 MVA SC TestRpt… · Documents constituting this report (In words) Number of sheets :Eight ... NABL ACCREDITED LABORATORY

Apr 04, 2018

Download

Documents

truongdan
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: NABL ACCREDITED LABORATORY Certificate No. … Reports Scanned/16 MVA SC TestRpt… · Documents constituting this report (In words) Number of sheets :Eight ... NABL ACCREDITED LABORATORY

HIGH POWER LABORATORYCENTRAL POWER RESEARCH INSTITUTE,P. B.NO. 8066, SADASmV ANAGAR SUB P.O

PROF. SIR.C.V. RAMAN ROAD, BANGALORE-560 080, INDIAPHONE: + 9]- (0) 80-23600574, FAX: + 91 (0) 80-23601213

CPRIch.

Test Report Number

Name & Address of the Customer

Name & Address of the Manufacturer

Particulars of sample testedSampleTypeDesignationSerial numberNumber of samples testedDate(s) of Test(s)CPRI Sample Code No.Condition of sample on receipt

Particulars of tests conductedTest in accordance withStandard/SpecificationSampling PlanCustomer's requirementDeviation if anyName of the witnessing persons

Customer's representative

NABL ACCREDITEDLABORATORY

Certificate No. TOOlO

Sheet No.1 of 8

TEST REPORT

: HPL07077 Dated: 26/06/2007

: Mis. Supreme Power Equipment Pvt Ltd.,No: 55, S1DCOIndustrial Estate,Thirumazhisai, Chennai-602107.

: Mis. Supreme Power Equipment Pvt Ltd.,No: 55, SIDCO Industrial Estate,Thirumazhisai, Chennai-602107.

: 16 MVA, 33 kV / 11kV, 3phase Transformer: Conventional Type, Oil cooled.: Power Transformer: SPEL/2081: One

: 10thApril 2007: HPL07S0089: New

: Dynamic ability to withstand short-circuit test.

: 1S:2026- Part-l (1977):Nil:Nil: Nil

: Mr. B. Sivaramakrishnan, Sr. Manager(QA): Mr. G. Sundaresan

Other than Customer's representativeTest subcontracted with address of

the laboratory : No load loss, load loss measurement, Induced overvoltage test and separate source voltage withstand testconducted at Mls.Supreme Power Equipment Pvt. Ltd.,

Chennai. - 602 107.Documents constituting this report (In words)

Number of sheets : EightNumber of oscillograms : NineNumber of photographs : ThreeNumber of test circuit diagrams : OneNumber of sample drawings : Four

~rr4~(G.Sengupta)

ADDJTIONAL DIRECTORAUTHOR]SED SIGNATORIES

Page 2: NABL ACCREDITED LABORATORY Certificate No. … Reports Scanned/16 MVA SC TestRpt… · Documents constituting this report (In words) Number of sheets :Eight ... NABL ACCREDITED LABORATORY

HIGH POWER LABORATORYCENTRAL POWER RESEARCH INSTITUTE,P. B.NO. 8066, SADASHIVANAGAR SUB P.O

PROF. SIR.C.V. RAMAN ROAD, BANGALORE-560 080, INDIAPHONE: + 91- (0) 80-23600574, FAX: + 91 (0) 80-23601213

CPRITest Report No. HPL07077

NABL ACCREDITEDLABORATORY

Certificate No.TOOIO

Sheet No.2 of 8

DESCRIPTION OF SAMPLE TESTED

(As assigned by the manufacturer)

Sample

Rated power MVA

Rated voltage HV (volts)

LV (volts)

Rated current HV (Amps)

LV (Amps)

Number of phases

Connection symbol

Type of cooling

Rated frequency (Hz)

Temperature rise of oil (OC)

Tapping range

Tap No.

% tap variation

% impedance

X/R Ratio

App"arentshort circuit power

behind transformer (MYA)

Winding material

Insulation level

HV WindingLV Winding

Guaranteed no-load loss

(on principal tapping in watts)

: Power Transformer

: 16

: 33000

: 11000

: 279.9

: 839.8

: Three

: Dynl1

:ONAF

: 50

: 50

: + 5% to -15 % in steps of 1.25%

17

-15

10.40

25.79

: 1000

: Copper

: 170kVPeak/70 kVrms: 75 kV Peak I 28 kV rms

: 9900(Max)

Guaranteed load loss at 75°C(on principal tapping in watts) : 59700

Guaranteed % impedance at 75° C

(on principal tapping) : 1O%:t 10%

\\Ux\LU!9' /(S.Suafi'akaraRedd~TEST ENGINEER .

: 1 5

: +5 0

:9.38 9.61

: 27.25 26.30

Page 3: NABL ACCREDITED LABORATORY Certificate No. … Reports Scanned/16 MVA SC TestRpt… · Documents constituting this report (In words) Number of sheets :Eight ... NABL ACCREDITED LABORATORY

HIGH POWER LABORATORYCENTRAL POWER RESEARCH INSTITUTE,P. B.NO. 8066, SADASHIVANAGAR SUB P.O

PROF. SIR.C.V. RAMAN ROAD, BANGALORE-560 080, INDIAPHONE: + 91- (0) 80-23600574, FAX: + 91 (0) 80-23601213

NABL ACCREDITEDLABORATORY

Certificate No.TOOIO

CPRITest Report No HPL07077 Sheet No.3 of 8

SUMMARY OF TEST

1.0 Test conducted : Dynamic ability to withstand short-circuit test.

2.0 Rating for which tested

Tapping position I % Z at75° C

X/R

: Short-circuit currents determined as per clause 9.1.2 ofIS: 2026 - Part-I (1977

Required short-circuit current on LV (phase)with rated voltage a lied to HV*kA eak kA rms.

19.28 7.5618.58 7.2916.42 6.44

9.389.61

10.40

27.2526.3025.79

* Considering the source impedance based on 1000 MYA and voltage of 36 kV

3.0 Schedule of short-circuit test results : As per sheet no. 5 of 8

4.0 Schedule of routine test results : As per sheet no. 6 of 8 & sheet no. 7 of 8

5.0 Oscillogram numbers : HPL07077.s002, S003, S004,

HPL07077.S006, S007, S008,

HPL07077.S01O,SOII& SO12.

6.0 Test circuit number : CRTL/HPLffR12