HIGH POWER LABORATORY CENTRAL POWER RESEARCH INSTITUTE, P. B.NO. 8066, SADASmV ANAGAR SUB P.O PROF. SIR.C.V. RAMAN ROAD, BANGALORE-560 080, INDIA PHONE: + 9]- (0) 80-23600574, FAX: + 91 (0) 80-23601213 CPRI ch. Test Report Number Name & Address of the Customer Name & Address of the Manufacturer Particulars of sample tested Sample Type Designation Serial number Number of samples tested Date(s) of Test(s) CPRI Sample Code No. Condition of sample on receipt Particulars of tests conducted Test in accordance with Standard/Specification Sampling Plan Customer's requirement Deviation if any Name of the witnessing persons Customer's representative NABL ACCREDITED LABORATORY Certificate No. TOOlO Sheet No.1 of 8 TEST REPORT : HPL07077 Dated: 26/06/2007 : Mis. Supreme Power Equipment Pvt Ltd., No: 55, S1DCOIndustrial Estate, Thirumazhisai, Chennai-602107. : Mis. Supreme Power Equipment Pvt Ltd., No: 55, SIDCO Industrial Estate, Thirumazhisai, Chennai-602107. : 16 MV A, 33 kV / 11kV, 3phase Transformer : Conventional Type, Oil cooled. : Power Transformer : SPEL/2081 : One : 10thApril 2007 : HPL07S0089 : New : Dynamic ability to withstand short-circuit test. : 1S:2026 - Part-l (1977) :Nil :Nil : Nil : Mr. B. Sivaramakrishnan, Sr. Manager(QA) : Mr. G. Sundaresan Other than Customer's representative Test subcontracted with address of the laboratory : No load loss, load loss measurement, Induced over voltage test and separate source voltage withstand test conducted at Mls.Supreme Power Equipment Pvt. Ltd., Chennai. - 602 107. Documents constituting this report (In words) Number of sheets : Eight Number of oscillograms : Nine Number of photographs : Three Number of test circuit diagrams : One Number of sample drawings : Four ~rr4~ (G.Sengupta) ADDJTIONAL DIRECTOR AUTHOR]SED SIGNA TORIES
3
Embed
NABL ACCREDITED LABORATORY Certificate No. … Reports Scanned/16 MVA SC TestRpt… · Documents constituting this report (In words) Number of sheets :Eight ... NABL ACCREDITED LABORATORY
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
HIGH POWER LABORATORYCENTRAL POWER RESEARCH INSTITUTE,P. B.NO. 8066, SADASmV ANAGAR SUB P.O
Particulars of sample testedSampleTypeDesignationSerial numberNumber of samples testedDate(s) of Test(s)CPRI Sample Code No.Condition of sample on receipt
Particulars of tests conductedTest in accordance withStandard/SpecificationSampling PlanCustomer's requirementDeviation if anyName of the witnessing persons
: 16 MVA, 33 kV / 11kV, 3phase Transformer: Conventional Type, Oil cooled.: Power Transformer: SPEL/2081: One
: 10thApril 2007: HPL07S0089: New
: Dynamic ability to withstand short-circuit test.
: 1S:2026- Part-l (1977):Nil:Nil: Nil
: Mr. B. Sivaramakrishnan, Sr. Manager(QA): Mr. G. Sundaresan
Other than Customer's representativeTest subcontracted with address of
the laboratory : No load loss, load loss measurement, Induced overvoltage test and separate source voltage withstand testconducted at Mls.Supreme Power Equipment Pvt. Ltd.,
Chennai. - 602 107.Documents constituting this report (In words)
Number of sheets : EightNumber of oscillograms : NineNumber of photographs : ThreeNumber of test circuit diagrams : OneNumber of sample drawings : Four
~rr4~(G.Sengupta)
ADDJTIONAL DIRECTORAUTHOR]SED SIGNATORIES
HIGH POWER LABORATORYCENTRAL POWER RESEARCH INSTITUTE,P. B.NO. 8066, SADASHIVANAGAR SUB P.O