Oct 13, 2015
Operating Manual
Controller B 150 (Mb 1)
Read the operating manual before commissioning the Controller.
www.nabertherm.com
B 150
wait time 2time 1
Temp.
timemin
T1
+
-
startstop
P
Info
2Short instructions
Switch the Controller on
Call in the program
Input program
Start the program
or
time 1 T1 time 2...
Confirm entry with
Confirm numerical entry with and
B 150 U 2.01
P = 1P + -
+ -
3Table of contents Short instructions .................................................. 2Display ................................................................. 4Keyboard ............................................................... 4General information ............................................... 4Features ................................................................ 5Safety ................................................................... 5Switching the Controller on .................................... 5Input of program ..................................................... 5Storing the program ............................................... 6Starting the program .............................................. 6Aborting the program .............................................. 7Locking of keys ..................................................... 7Info menu .............................................................. 7Data interface (optional) ........................................ 8Customized settings/configuration ......................... 8Opening the configuration menu ............................. 9Setting the kilowatt-hour meter .............................. 9Setting the interface address ............................... 10Switch-over F ..................................................... 10Automatic optimization ........................................ 10Error messages .................................................... 12Power failure behaviour ........................................ 13Technical specifications ...................................... 13Trouble shooting .................................................. 14Replacement instructions .................................... 14Electrical connection ........................................... 16Notes .................................................................. 18
4Display
1
3
2
4 5 6 7 8 9
1 Temperature indication2 Display of units3 Status field heat heater ON4 not applicable5 Status field rel2 additional relay 2 (option)
6 Status field key key locking7 Status field error error message8 Status field end program End9 Status field com communication with PC
1 Program selection2 +/-3 Scroll4 Programm Start/Stop5 Info menu6 Key locking7 Save
Mains switch/control current switchThe mains switch / control current switch is locatedunder the Controller.
First terminate active heating programs, then switch offthe furnace at the mains switch.
Switch the mains switch to position 0 and pull themains plug before starting work on the electricalequipment!
Some parts in the furnace may be live even when themains switch is switched off!
Work on the electrical equipment may only be carriedout by specialists!
Keyboard
1
3 4
5
6
7
2
General information
5Features The Controller B 150 is an electronic temperatureregulator with the following features:
The Controller is provided with a number of electronicsafety equipment. If a fault occurs, the furnace switchesitself off automatically and an error message appears onthe LC display. You can find more detailed informationin the chapter Error messages.
Switch mains switch to position I. Type and version ofthe Controller appear on the display. Then the Controlleris ready to operate. All necessary settings for properfunctioning were already made at the factory.
Setting or changing programs/delay timeThe program has a ramp and a holding time: A linear rise in temperature (slow heating) is set in
the ramp via segment temperature T1 and segmenttime time 1.
In holding time 2 you can define how long thetemperature set in T1 is to be maintained. Duringthe program run the holding time can be changed byactuating the key, selecting the time valuetime 2 and keeping the +/- button pressed.
The values can be changed with the +/- key. Byactuating the key repeatedly, the value is changed by1 C (1 F) or by one minute.Keep the key pressed to change the value more quickly.If this key is operated once
Input of program
Safety
wait time 2time 1
T1
Switching the Controller on
Overtemperature protection 9Control of circulation motor -
Delay time 9Number of programs 1
Automatic optimization 9Kilowatt-hour meter 9Operating hours counter 9RS 422 interface optional
6for less than 2 seconds by 10 C/s (F/s), or by 10min/sfor less than 5 seconds by 100 C/s (F/s), or by 1 h/s
Confirm the entry in T or time by actuating the key. If this key is not pressed, the changes arediscarded and the previously set value remains valid.
To ensure that old program values are not retrieved in anewly generated program, you should first call in theprogram 0.
The unit of the expected value C/F or h:mm is shownon the display.Input the time in hours and minutes, e.g. enter 06:30 forsix hours and 30 minutes.Skip values that are not to be changed with .Changed settings are first of all only stored temporarily(please see also Saving programs).
After a program has been input or changed, the modifiedvalues are saved in a volatile memory.If you want to store the program changes permanently,actuate the storage key twice. The program canthen be called from memory location 1.
If the storage key is not pressed a second timewithin 10 seconds the Controller displays againthe furnace temperature. In this case the programis not stored.
Program locations that are already occupied areoverwritten without further notice and can no longer berecovered.
Stored programs remain in the memory even when thesystem is switched off.
Call the stored program with the P key and check theprogram by actuating the button.
After input of a heating program the process can bestarted with start/stop . After the program has been
Segment Time value Comment
time 1 00:00 fast heating-up to T1
time 2 99:59 execute the segment for an
infinitely long period of time
Storing programs
Starting the program
7started the diode of the respective active segment time1or time 2 lights up during the program run. The settemperature profiles are automatically controlled by theController and the status field heat starts flashingduring the heating cycle.
When a delay time has been defined the diode waitlights up and the remaining delay time is counted downon the display. The status field heat flashes onlywhen the program has been started.
To abort a program press the start/stop key again.The heater is switched off and the status field endflashes.
The program can be aborted at any desired time.
However, it is not possible to abort a program onlytemporarily.
To prevent unintentional or prohibited access to the pro-gram run, the keyboard can be blocked by means of thekey lock after the program has been started.
The key lock can only be released when the Con-troller is switched off and then on again (behaviourduring switching off, please refer to Power failurebehaviour)!
By actuating the info key, the following processinformation can be displayed:
Pr selected programSP temperature set valuePt program runtime of the activated/last program in
minutesE power consumption of the activated/last program
in kW/htt total operating hoursOP heater output in %F1 fault memory of last errorF2 fault memory of last but one error
Aborting the program
Info menu
Locking of keys
8Ht highest program temperature of the activated/last program
tA maximum furnace temperature
The info menu is not automatically switched over to thetemperature display to prolong the time for viewing data!
Scroll the complete info menu by actuating the Infokey until the furnace temperature is again displayed!In case of a power failure all values are lost except thehighest program temperature Ht and the total operatinghours tt .
The Controller B150 can be equipped with an RS 422data interface, that is optionally realized via a 9-pin D-Sub plug connection. This interface can be used to sendand receive control functions as well as archive data. Adata transmission is indicated on the display by com(communication with PC).The interface is immediately ready for operation; e.g. forthe Nabertherm furnace supervision software Control-therm (see also Setting of the interface address.)
To operate several Controllers/furnaces on one datanetwork the interface address might have to be changed(see Setting of the interface address).
If the data connection line between the furnace and thePC/notebook is longer than 20 m, communication errorsmay occur if an interface power supply that is availableas option is not used.
Special settings that affect the operational behaviour ofthe Controller are to be made in the configuration menu.The configuration menu is divided into 2 access levelsthat can be called via different passwords.
Possibilities of settings at configuration level 1(password 0):rt switching temperature relay 2 in operating mode
temp.-dependent relay function (option)setting range 0 to Tmax +20C
Data interface (optional)
Customizedsettings/configuration
9Ad address of the RS 422 interfacesetting range 0 to 99
PF furnace output to calculate the power consumption(see also kilowatt-hour meter)setting range 0 to max. 2000 (max. 200 kW)
F switch-over C/Fsetting range 0= >C; 1=>F
Possibilities of settings at configuration level 2(password 2):PA activated parameter set
setting range 0 to 4 (please see also Automaticoptimization)
TU automatic optimization (tune)setting range 1 (Start)
P1 proportional band XP of the first parameter setsetting range from 0 to 100%
i1 reset time Tn of the first parameter setsetting range 0 to 5000 s
d1 derivative time Tv of the first parameter setsetting range 0 to 250 sfollowing parameter sets 2-4P2, i2, d2 ... P4, i4, d4
Keep the Info key pressed and actuate the ----- keybriefly, then release the Info key again. Co 0 isdisplayed and the system is waiting for the password.Actuate +/- to enter the code for the desiredconfiguration level and confirm by pressing the storage key. Scroll the screen with to display theparameters one after the other as described above.
Changed settings must be stored by pressing the storage key. During write operation the value is flashingbriefly on the display.
Changing the control parameters may affect thefunction of the control system considerably.
To calculate the power consumption in kW/h in the infomenu, the furnace performance which is indicated on therating plate must be input. In general these settings werealready defined by Nabertherm. Otherwise selectparameter PF at configuration level 0 and input the
Opening the configuration menu
Setting the kilowatt-hour meter
10
capacity on the rating plate x 10.e.g. furnace performance 3.6kW * 10 = input 36.Acknowledge the settings with .
When several Controllers are operated within a datanetwork, different addresses are to be set at the Control-lers.
Select parameter Adat configuration level 0, inputa new addresss (1...99) and confirm by actuating the storage key.
Select parameter Fat configuration level 0, set to1 and acknowledge with .The safety cut-out in the Controller is automaticallyconverted, all the other temperature settings mustsubsequently be changed to F, if necessary.The preset heating programs are always programmed inC and must be adapted manually if the temperatureunits are changed.
The control parameters of the Controllers are already setfor an optimum regulation of the furnace at the factory. Ifthis control behaviour should be inappropriate for yourprocess, you can improve it by automatic optimization.The Controller has four different parameter sets, thatwere preset for different furnace models.
The preset parameter set is indicated in parameter PA(please see also Configuration).When the automatic optimization is carried out the controlparameters of the selected parameter set are determinedand stored by a special measuring method.
Start the automatic optimization only when the furnacehas cooled down (T < 60 C) since otherwise wrongparameters will be determined for the controlled process!
First input a program in which the temperature to beoptimized is programmed in T1. Set all time displaystime to 00:00.
Setting the interface address
Switch-over C/F
Automatic optimization
11
Select parameter tu at configuration level 2, set to1 and confirm by pressing the key. The automaticoptimization is now started and tune and the furnacetemperature appear alternately in the display.When the optimization is finished the status field Endis flashing. The determined parameters are stored by theController in the parameter set for the correspondingtemperature range.
In any case the automatic optimization is carried out atappr. 70% of the value set in T1 in order to preventdestroying the furnace, e.g. when the maximumtemperature is optimized.The automatic optimization can take more than 3 hoursfor some models, dependent on the furnace type and thetemperature range.
The control behaviour may deteriorate in other temperatureranges when an automatic optimization was executed.Nabertherm rejects all liability for damages which arecaused by manual or automatic changes of the controlparameters (please see also Temperature-dependentparameter sets)!
Temperature-dependent parameter setsIf 0 is set in parameter PA, all 4 parameter sets areavailable to control the furnace. The parameter sets arethen divided as follows:Parameter set 1 T = 0 -250 C (0 -482 F)Parameter set 2 T = 251 -500 C (483 -932 F)Parameter set 3 T = 501 -1000 C (933 -1832 F)Parameter set 4 T > 1000 C (>1832 F)
Read out the parameter set selected in PA before youactivate the temperature-dependent parameters. Thenset the same P-, I- and D-values in all parameter sets.You can then search special parameters for a certaintemperature range which do not affect the remainingtemperature ranges.
Carry out an automatic optimization for all temperatureranges, if necessary.
12
If an error occurs one of the following error messages isdisplayed:
Error code Reason
F 10 The furnace does not reach the settemperature
F 30-32 Error of thermocouple or measuringcircuit
F 40 Thermocouple has reverse polarity (e.g.after replacement of thermocouple -change polarity)
F 50 Temperature or time entry incorrect(correct entry)
F 60-61 Controller system errorF 62 Ambient temperature too low
70CF 64-69 Controller system errorF 70 Furnace temperature has exceeded the
permissible Tmax valueF 90 Voltage failure (displayed after the
voltage has recovered)
Error messages can be reset by switching the mainsswitch off and on. Leave the equipment switched off forat least 5 seconds.Recirculation motors (if installed) remain switched on,even in case of an error. The heater is in any caseswitched off.
If the error message does not reappear within one minuteafter the system is switched on, the Controller is againready for operation. If the error message reappears, informNabertherm service.
When contacting Nabertherm service, please have therating plate data available.
Error messages
13
Supply voltage ~85-250V 50/60Hz
Power consumption 3.5W
Sensor input type S, K, R
Heater output 12 V, max. 130 mA
Safety relay ~250 V /16 A
Additional relay (option) ~250 V /3 A
Protection class: I (protective earth)
Enclosure rating: membrane keypad IP 65
attached casing IP 20
Furnace/switchgear (see Operating Instructions of furnace)
Interface (option) RS 422 insulated
Measuring accuracy: +/- 3C
Lowest possible rate: 0.25 C/h
Ambient conditions
Storage temperature: - 20C to + 75C
Working temperature: 0 - 40C, ensure sufficient circulation of air
Relative humidity: 5-90% non-condensing
Power failure behaviour
Technical specifications
wait: program is aborted with error message F90
time1: program is continued
time2: program is aborted at a time period below 99:59
time2: program is continued at a time period of 99:59
14
Only a qualified electrican may carry out work onthe electrical system.
Make sure that the mains switch is in position 0!Pull the mains plug before you open the housing!If the furnace is not equipped with a mains plug, switchthe mains connection voltage-free!
Removal Loosen the 4 fastening screws at the front side of the
Controller. Tilt the Controller carefully out of the housing from
the top Loosen the plug - if installed - of the flat ribbon cable
for the interface Loosen the protective conductor connections Loosen both plug connectors
Do not pull the Controller at the cables by force out ofthe housing.
Replacement instructions
Trouble shooting
Error Cause Corrective action
Controller does not light up Controller switched off Switch mains switch to I
No voltage Power plug plugged in?
Check house fuse
Furnace does not heat Door/cover open Close door/cover
Door contact switch actuated Check door contact switch
wait flashes Set delay time to 00:00
No temperature input Check temperatures T1/T2
Program does not change to The holding time is infinite Set holding time < 99:59
the next segment in time2 / time4
The regulator does not heat No temperature was set The temperature to be optimized
during optimization in T1 must be input in T1
Please contact Nabertherm service if the fault cannot be eliminated.
When contacting Nabertherm service, please have the rating plate data available.
15
Insertion Plug the two plug connectors on the new Controller Attach the protective conductor connection to the
Controller Check the earth connection of the orange and grey
measuring line Attach the plug of the interface line (if installed) Check that the protective conductor is properly
connected before you install the Controller Position the Controller in the mounting frame Make sure that no cables protrude or are squeezed Screw in the 4 fastening screws.
Fasten the fastening screws only finger-tight to avoiddamaging the membrane keypad!The replacement must be carried out by a specialist!
16
Electrical connection
TE- - ++
SAFL1
Extra
1
X10.1 X10.2
X20
X21
X9. X11.2
S11
1a
Extra
2
OP 12V
11 22 33 445678910
2(N)1(P)
~=
gr
or - Typ S
gn - Typ K
TE- - ++
SAFL1
Extra
1
X10.1 X10.2
X20
X21
X9. X11. 2(N) 1(P)
S11
11
1a
12
2
21
ON
COM
2a
22
Extra
2
OP 12V
11 22 33 445678910
2(N)1(P)
~=
K1
or - Typ S
gn - Typ K
Controlof specialfunctions
(option)
Voltagesupply P/N
Door contact
Heater connectionsee operating instructions of
furnace
Thermocouple
Controlof specialfunctions(option)
Voltagesupply P/N
ThermocoupleSafetycontactor
Output12V semi-conductorrelay
Furnaces up to 3.6kW
Furnaces > 3.6kW with semi-conductor relay
17
TE- - ++
SAFL1
Extra
1
X10.1 X10.2
X20
X21
X9. X11.2
S11
1a
Extra
2
OP 12V
11 22 33 445678910
2(N)1(P)
~=
gr
or - Typ S
gn - Typ K
Controlof specialfunctions(option)
Voltagesupply P/N
ThermocoupleSafetycontactor
Output
Furnaces > 3.6kW with heater contactor
18
Notes
19
Notes
Reg.
No.
B 2
.7 (e
nglis
ch),
Augu
st 2
004
Headquarters: No responsibility is accepted for the correctness of this information, we reserve the right to make technical alterations
Nabertherm GmbH Bahnhofstr. 20 28865 Lilienthal/Bremen, Germany Tel. +49 (04298) 922-0, Fax -129 [email protected] www.nabertherm.com
/ColorImageDict > /JPEG2000ColorACSImageDict > /JPEG2000ColorImageDict > /AntiAliasGrayImages false /DownsampleGrayImages true /GrayImageDownsampleType /Bicubic /GrayImageResolution 300 /GrayImageDepth 8 /GrayImageDownsampleThreshold 1.50000 /EncodeGrayImages true /GrayImageFilter /FlateEncode /AutoFilterGrayImages false /GrayImageAutoFilterStrategy /JPEG /GrayACSImageDict > /GrayImageDict > /JPEG2000GrayACSImageDict > /JPEG2000GrayImageDict > /AntiAliasMonoImages false /DownsampleMonoImages true /MonoImageDownsampleType /Bicubic /MonoImageResolution 1200 /MonoImageDepth -1 /MonoImageDownsampleThreshold 1.50000 /EncodeMonoImages true /MonoImageFilter /CCITTFaxEncode /MonoImageDict > /AllowPSXObjects false /PDFX1aCheck false /PDFX3Check false /PDFXCompliantPDFOnly false /PDFXNoTrimBoxError true /PDFXTrimBoxToMediaBoxOffset [ 0.00000 0.00000 0.00000 0.00000 ] /PDFXSetBleedBoxToMediaBox true /PDFXBleedBoxToTrimBoxOffset [ 0.00000 0.00000 0.00000 0.00000 ] /PDFXOutputIntentProfile () /PDFXOutputCondition () /PDFXRegistryName (http://www.color.org) /PDFXTrapped /Unknown
/Description >>> setdistillerparams> setpagedevice