Top Banner

of 51

Na20 Mb0 Manual Pr 0250

Apr 03, 2018

Download

Documents

scozans
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
  • 7/28/2019 Na20 Mb0 Manual Pr 0250

    1/51

    PRON NA20-MB0

    MODBUS PROTOCOL USER GUIDE 2.50

    Modbus Communication Protocol User Guide

    PRON NA20-MB0

  • 7/28/2019 Na20 Mb0 Manual Pr 0250

    2/51

    PRON NA20-MB0

    Contents

    Contents ........................................................................................................................................................................21 Modbus RTU communication................................................................................................................................3

    1.1 Serial port settings........................................................................................................................................31.2 Transmission mode ......................................................................................................................................31.3 Data Types ...................................................................................................................................................31.4 Supported functions .....................................................................................................................................41.5 Exceptions....................................................................................................................................................4

    1.6 Modbus/TCP ................................................................................................................................................51.7 Network setting.............................................................................................................................................51.8 NTP synchronization ....................................................................................................................................5

    2 Logical organization of the protections data ........................................................................................................62.1 Basic Data Type ...........................................................................................................................................6

    2.1.1 BIT............................................................................................................................................................62.1.2 BYTE........................................................................................................................................................72.1.3 UBYTE .....................................................................................................................................................72.1.4 WORD......................................................................................................................................................8

    2.1.5 UWORD ...................................................................................................................................................82.1.6 LONG.......................................................................................................................................................92.1.7 ULONG ....................................................................................................................................................92.1.8 ARR........................................................................................................................................................102.1.9 STR........................................................................................................................................................112.1.10 CMD.......................................................................................................................................................11

    3 How to read the Address Data Table..................................................................................................................123.1 Address Data Table....................................................................................................................................12

    3.1.1 VAR........................................................................................................................................................123.1.2 REF........................................................................................................................................................123.1.3 IDX .........................................................................................................................................................123.1.4 DIM.........................................................................................................................................................133.1.5 TYPE......................................................................................................................................................133.1.6 UM..........................................................................................................................................................133.1.7 Kv 133.1.8 ENUM.....................................................................................................................................................14

    3.2 Common properties....................................................................................................................................143.2.1 Input state ..............................................................................................................................................143.2.2 Output state............................................................................................................................................14

    4 Examples ............................................................................................................................................................154.1 Example 1. How to read a variable ............................................................................................................154.2 Example 2. How to read a BIT data type ...................................................................................................164.3 Example 3. How to execute a command....................................................................................................16

    5 Glossary..............................................................................................................................................................176 Appendix A. Address Data Table........................................................................................................................18

  • 7/28/2019 Na20 Mb0 Manual Pr 0250

    3/51

    PRON NA20-MB0

    Introduction

    This Protocol Manual is for use with Thytronic Protective Relays, such as the DMC, NTG and PRO-N series thatsupport Modbus RTU and Modbus TCP communication protocol.

    1 Modbus RTU communication

    The Thytronic Protective Relay (TPR) uses a communication protocol called Modbus. A company called Modicon,for use with their programmable controllers, developed the Modbus protocol. Since that time Modbus has evolvedinto common communication protocol in industry and its now a de-facto standard.

    The communication method involves using a master-slave technique, in which there is one master and severalslaves. The TPR is a slave device. Only the master can initiate queries. These queries are directed to an individualslave device and the appropriate slave responds with the requested data.There are two transmission modes. These modes are known as RTU (Remote Terminal Unit) and ASCII (AmericanStandard Code for Information Interchange).The TPR can be setup in a network of up to 247 slave devices. Each device must have a different address (1-247).The TPR can be set for RTU mode only.

    The MODBUS protocol documentation can be found online at www.modicon.com or www.modbus.org

    (document PDI-MBUS-300 REV J).

    1.1 Serial port settings

    To communicate with a TPR, the serial port of the Master has to be configured with the following settings:

    Address Baud Rate Parity Stop bits Data bits1 19200 No 1 8

    Table 1 Serial port settings

    Remark: Every TPR has a default MODBUS Slave Address set to 1.

    1.2 Transmission mode

    The transmission mode supported by TPR is RTU.The ASCII transmission mode is not supported.

  • 7/28/2019 Na20 Mb0 Manual Pr 0250

    4/51

    PRON NA20-MB0

    1.4 Supported functions

    TPR supports the following Modbus functions:

    Code Name0x010x020x030x040x05

    0x060x0F0x10

    Read Coil StatusRead Input StatusRead Holding RegistersRead Input RegistersForce Single Coil

    Preset Single RegisterForce Multiple CoilPreset Multiple Registers

    Table 3 Supported Modbus functions

    The smallest data that can be exchanged within a Modbus message is the Modbus Register.A Modbus Register is a 16 bit data in the Big Endian representation, called WORD (W)

    W = BH BL

    1.5 Exceptions

    When a TPR receives a request that can not handle (e.g. the data address doesnt exists, the function is notsupported, etc.), a special response called Exception is returned to the Master. This message contains theinformation needed to recognize the error occurred.

    In an Exception message the most significant bit (msb) of the Function field is set to 1.

    Function Code field: in case of exception, the msb is set to 1.

    Data field: this field contains a value related to the kind of error generated by the request.

    An example of request with exception response could be the following:

    04 07 A5 50 00 02 - -TX

    S F ADR DIM CRC

    04 87 01 - -RX

    S F DATA CRC

    S = Slave AddressF = Function CodeADR M db D Add

  • 7/28/2019 Na20 Mb0 Manual Pr 0250

    5/51

    PRON NA20-MB0

    The next table describes all the exceptions handled by the TPRs.

    Code Name Description

    01 ILLEGAL FUNCTIONThe function code received in the query is not an allowable action forthe slave.

    02 ILLEGAL DATA ADDRESSThe data address received in the query is not an allowable address forthe slave

    03 ILLEGAL DATA VALUEA value contained in the query data field is not an allowable value forthe slave

    04 SLAVE DEVICE FAILUREAn unrecoverable error occurred while the slave was attempting toperform the requested action.

    05 ACKNOWLEDGEThe slave has accepted the request and is processing it, but a longduration of time will be required to do so. This response is returned toprevent a timeout error from occurring in the master.

    06 SLAVE DEVICE BUSYThe slave is engaged in processing a long-duration program command.The master should retransmit the message later when the slave is free.

    1.6 Modbus/TCPModbus/TCP, an extension of Modbus/RTU, defines how Modbus/RTU and Modbus/ASCII messages are encoded

    within and transported over TCP/IP-based networks. Modbus/TCP is just as simple to implement and flexible toapply as the original Modbus/RTU. The specification can be found online at www.modicon.com

    1.7 Network settingEvery device connected to the TCP/IP network including the TPRs must have a unique IP address. Every TPR has

    the following default IP address:

    Default IP Address = 200.1.1.135

    1.8 NTP synchronization

    T h i h R l Ti Cl k f h i h i h NTP i i il bl

    Transaction

    Identifier

    Protocol

    IdentifierLength Field Modbus Frame TCP FRAMECHECKSUM

    S F DATAMODBUS FRAME

  • 7/28/2019 Na20 Mb0 Manual Pr 0250

    6/51

    PRON NA20-MB0

    2 Logical organization of the protections data

    Each TPR has some data that can be read and/or written. These data are grouped in 4 data table.Data with 1 bit of information (e.g. the state of an output), can be placed in the Discrete Inputs table or in the Coilstable, while data with more than 1 bit of information (e.g. the value of a current), can be placed in the Registertable, sometimes fitting more than one register as described in the following example.

    1x, Discrete Input 3x, Input Registersn var n var6 I> Start 157 Power frequeny

    7 I> Trip 158 Phase current IL1 value Word L8 I> Block1 159 Phase current IL1 value Word H

    160 Phase current IL2 value Word L

    161 Phase current IL2 value Word H

    Table 4. Example of data structures

    Example: lets read the value of the variable I> Start. This variable is the first one in the Discrete Input data table.To read this kind of data the Modbus function 0x02 has to be used. As described in the standard the Modbusaddress to access the data is given by IDX-1 = 5 in this case.To read the data from the Slave address 1 the next request has to be sent:

    01 02 00 05 00 01 - -TX

    S F ADR DIM CRC

    2.1 Basic Data Type

    In this chapter all the basic TPR data type and their relationship with the Modbus data type will be described.

    2.1.1 BITDescription:Variable with 1 bit of information.

    Relationship with Modbus:The information corresponds to the least significant bit (lsb) of the first data byte addressed in the query.

  • 7/28/2019 Na20 Mb0 Manual Pr 0250

    7/51

    PRON NA20-MB0

    2.1.2 BYTE

    Description:Signed variable with 1 byte (8 bit) of information. Range: -128 +127

    Relationship with Modbus:A BYTE data type is always placed in the Least Significant Byte (LSB) of a Modbus Register (DIM=1).

    B 00 BByte

    ModbusRegister

    Example:relationship between the data BYTE whose value is 13 (0x0D) and its Modbus representation:

    0D 00 0D

    ByteModbus

    Register

    2.1.3 UBYTE

    Description:Unsigned variable with 1 byte (8 bit) of information. Range: 0 +255

    Relationship with Modbus:A BYTE data type is always placed in the Least Significant Byte (LSB) of a Modbus Register (DIM=1).

    B 00 BUByte Modbus

    Register

    Example:relationship between the data BYTE whose value is 13 (0x0D) and its Modbus representation:

    0D 00 0D

    ByteModbusRegister

  • 7/28/2019 Na20 Mb0 Manual Pr 0250

    8/51

    PRON NA20-MB0

    2.1.4 WORD

    Description:Signed variable with 2 byte (16 bit) of information. Range: -32.768 +32.767

    Relationship with Modbus:A WORD data type is always placed in a Modbus Register (DIM=1) keeping the representation (Big Endian).

    BH BL BH BL

    WordModbusRegister

    Example:relationship between the data WORD whose value is 3073 (0x0C01) and its Modbus representation:

    0C 01 0C 01Word

    ModbusRegister

    2.1.5 UWORD

    Description:

    Unsigned variable with 2 byte (16 bit) of information. Range: 0

    +65.535

    Relationship with Modbus:A UWORD data type is always placed in a Modbus Register (DIM=1) keeping the representation (Big Endian).

    BH BL BH BL

    UWordModbusRegister

    Example:relationship between the data UWORD whose value is 3073 (0x0C01) and its Modbus representation:

    0C 01 0C 01

    UWordModbusRegister

  • 7/28/2019 Na20 Mb0 Manual Pr 0250

    9/51

    PRON NA20-MB0

    2.1.6 LONG

    Description:Signed variable with 4 byte (32 bit) of information. Range: -2.147.483.648 +2.147.483.647

    Relationship with Modbus:A LONG data type is placed in two Modbus Registers (DIM=2). The Least Significant Word of the LONG data typeis placed in the first Modbus register while the Most Significant Word of the LONG data type is placed in the second

    Modbus register.

    BHH BHL BLH BLL BLH BLL BHH BHLWH WL WL WH

    Long Modbus Registers

    Example:relationship between the data LONG 66536 (0x103E8) and its value in the Modbus protocol domain:

    00 01 03 E8 03 E8 00 01Long Modbus Registers

    2.1.7 ULONG

    Description:Unsigned variable with 4 byte (32 bit) of information. Range: -0 +4.294.967.295

    Relationship with Modbus:A ULONG data type is placed in two Modbus Registers (DIM=2). The Least Significant Word of the ULONG datatype is placed in the first Modbus register while the Most Significant Word is placed in the second Modbus register.

    LHH LHL LLH LLL LLH LLL LHH LHLWH WL WL WH

    ULong Modbus Registers

    Example:relationship between the ULONG data whose value is 66536 (0x103E8) and its Modbus representation:

    00 01 03 E8 03 E8 00 01ULong Modbus Registers

  • 7/28/2019 Na20 Mb0 Manual Pr 0250

    10/51

    PRON NA20-MB0

    2.1.8 ARR

    Description:Array of BYTE.

    Relationship with Modbus:An ARR data type of length n is placed in N Modbus Registers (N= ceil(n/2)

    ) keeping the byte ordering. If odd n,

    the last byte of ARR is placed in the MSB of the last Modbus register, while the LSB is set to 0

    If even n:

    B1 B2 Bn B1 B2 Bn-1 Bn1 2 n 1 N

    Array[n] Modbus RegistersN = ceil(n/2)

    If odd n:

    B1 B2 Bn B1 B2 Bn 01 2 n 1 N

    Array[n] Modbus RegistersExample:Lets consider an array with 3 bytes whose values are: (0x01, 0x3A, 0x1F). This array can be placed inN=ceil(3/2)=ceil(1.5)=2 Modbus registers.

    01 3A 1F 01 3A 1F 001 2 3 1 2

    Array[3] Modbus Registers

  • 7/28/2019 Na20 Mb0 Manual Pr 0250

    11/51

    PRON NA20-MB0

    2.1.9 STR

    Description:String data type. Its represented by an array of BYTE. Every byte represents the hexadecimal ASCII codeassociated with the character of the string

    Relationship with Modbus:An STR data type of length n is placed in N Modbus Registers (N= ceil(n/2)

    ) keeping the byte ordering. If odd n,

    the last byte is placed in the MSB of the last Modbus register. A zero padding operation (with char \0) is necessaryfor every writing operation where the length of the string is lower than the number of bytes contained in the Modbusregisters.

    If even n:

    C1 C2 Cn C1 C2 Cn-1 Cn1 2 n 1 N

    String[n] Modbus Registers

    N = ceil(n/2)If odd n:

    C1 C2 Cn C1 C2 Cn \01 2 n 1 N

    String[n] Modbus Registers

    Example:Lets assume Relay reference name is a STRING variable whose length is 8 characters, its Modbus address is

    0x0029 and its dimension is 4 Modbus registers. Lets set its value to NAxx.

    First of all the ASCII code in hexadecimal notation for each character of the string NA10 is equal to 0x4E417878An example of write request could be the following:

    01 10 00 29 00 05 10 4E 41 78 78 00 00 00 00 - -TX

    S F ADR DIM B DATA1 DATA2 DATA3 DATA4 CRCN A x x \0 \0 \0 \0

    Remark. A zero padding operation is necessary because the length of the string DMC901 is lower than the lengthof the RACK_TYPE variable.

    2.1.10 CMDDescription:Thi t f d t t d

  • 7/28/2019 Na20 Mb0 Manual Pr 0250

    12/51

    PRON NA20-MB0

    3 How to read the Address Data Table

    All the information necessary to read/write data from/to a TPR is contained in the Address Data Table (seeAppendix A).

    3.1 Address Data Table

    Now a description of all the Address Data Tables fields is given:

    3.1.1 VAR

    The VAR field contains the description of the variable.An example of VAR fields could be: Relay phase nominal current - In , Relay reference name or I> Trip.

    3.1.2 REF

    The REF field tells which data table the variable is stored in.The REF field can assume one of the following values:

    0x: data stored in the COIL table

    1x: data stored in the DISCRETE INPUT table

    3x: data stored in the INPUT REGISTER table

    4x: data stored in the HOLDING REGISTER table

    3.1.3 IDX

    The IDX field represents the position of the table (specified by REF) in which the variable VAR is stored.The IDX value is related to the Modbus address of the variable. The relationship between IDX and Modbus addressis the following:

    MB address = IDX - 1

    E l l id h f ll i Add D T bl

    VAR REF IDX DIM TYPE UM KV ENUM

    Table 5. Address Data Tables field

  • 7/28/2019 Na20 Mb0 Manual Pr 0250

    13/51

    PRON NA20-MB0

    3.1.4 DIM

    The DIM field is the number of Modbus registers necessary to contain the VAR data.

    Example: lets read the value of the variable Relay phase nominal current - In.From the previous table we see that the reference is 4x for which the function 0x03 has to be used for reading.The Modbus address is IDX-1=50-1=49.The request for reading is the following:

    01 03 00 31 00 01 - -TX

    S F ADR DIM CRC

    3.1.5 TYPE

    The TYPE field specifies the basic data type associated with VAR, as described in chapter 2.1.

    3.1.6 UM

    The UM field specifies the Unit of Measure of the variable.If UM is empty, it means that the Unit is just a number.

    3.1.7 Kv

    The Kv field contains the scale factor that has to be applied to the variable to obtain the real value. If Kv is notequal to 1, the value of the variable must be divided by Kv.

    Example: lets consider the following address data table

    VAR REF IDX DIM TYPE UM KV ENUM

    Phase current IL1 - Value 3x 159 2 LONG In 16000

    Lets read the Phase current IL1 - Value from the Slave address 1.

    01 04 00 9E 00 02 - -TX

    S F ADR DIM CRC

    Lets assume the following response:

  • 7/28/2019 Na20 Mb0 Manual Pr 0250

    14/51

    PRON NA20-MB0

    3.1.8 ENUM

    The ENUM field, whenever is defined, contains the meaning of all possible values assumed by the variable.

    3.2 Common properties

    Some common properties are now described for a better understanding.

    3.2.1 Input state

    StateIts the physical state of the Input: 0 or 1 (OFF or ON)

    3.2.2 Output state

    State

    Its the logical state of the output: 0 or 1 (OFF or ON); could not correspond with its physical state Fail

    Its the Coil Failure Status: 0 or 1 (OFF=OK o ON=Fault).

  • 7/28/2019 Na20 Mb0 Manual Pr 0250

    15/51

    PRON NA20-MB0

    4 Examples

    For all the examples, the following symbols are assumed:

    S = Slave Modbus address (1-247)F = Modbus Function code (1,2,3,4,5,6,15,16)B = number of byte in the DATA fieldADR = Modbus DATA address

    DIM = number of Modbus DATA addressCRC = Cyclical Redundancy CheckDATAx = register x of DATA fieldVALx = value x of the variable

    4.1 Example 1. How to read a variable

    Lets read from the Slave address 1 the value of the Relay phase nominal current - In .

    From the Address Data Table (Appendix A) we find out the following information;

    VAR REF IDX DIM TYPE UM Kv ENUM

    Relay phase nominal current - In 3x 50 1 UWORD A 1

    The REF field value specify an Input Register (3x), so the function 0x04 is used for reading. From the IDX theModbus address is derived: Modbus address = IDX -1 = 50 - 1 = 49. DIM specify the number of register to be read.

    01 04 00 3E 00 02 - -

    TX S F ADR DIM CRC

    01 04 04 00 05 - -RX

    S F B DATA CRC

    The TYPE field value is equal to UWORD. Applying the rules described in the chapter 2.1, the following value isobtained

    VAL = 0x0005= 5.

    Il UM field specify the Unit of measure that is Ampere, while Kv = 1 means that the value doesnt need to bescaled. The Relay phase nominal current In is equal to 5A.

  • 7/28/2019 Na20 Mb0 Manual Pr 0250

    16/51

    PRON NA20-MB0

    4.2 Example 2. How to read a BIT data typeLets read from the Slave address 1 the variable I> Trip.

    From the Address Data Table (Appendix A) we find out the following information;

    VAR REF IDX DIM TYPE UM Kv ENUM

    I> Trip 1x 7 1 BIT 0=OFF, 1=ON

    The REF field value specify a Discrete Input (1x), so the function 0x02 is used for reading. From the IDX the

    Modbus address is derived: Modbus address = IDX -1 = 7 - 1 = 6. DIM specify the number of register to be read.

    01 02 00 06 00 01 - -TX

    S F ADR DIM CRC

    01 02 01 00 01 - -RX

    S F B VAL CRC

    The TYPE field value is equal to BIT. Applying the rules described in the chapter 2.1, the following value is

    obtainedVAL = 1.

    The ENUM field specifies the meaning of the value. In this case, the value 1 corresponds to the ON state and itmeans that a Trip has occurred on the first threshold of the 51 function.

    4.3 Example 3. How to execute a command

    Lets execute the command Reset events on the Slave address 1.From the Address Data Table (Appendix A) we find out the following information;

    VAR REF IDX DIM TYPE UM Kv ENUM

    Reset LEDs 0x 2 1 CMD 0=OFF, 1=ON

    The TYPE field value specifies a Command (CMD). As described in chapter 2.1, to execute the command, it isnecessary to set its value to 1.The REF field value specify a Coil(0x), so the function 0x05 is used for writing. From the IDX the Modbus address

    is derived: Modbus address = IDX -1 = 2 - 1 = 1The Response message is known as an Acknowledge because its an echo of the request, and it means that theCoil has been set:

    01 05 00 01 FF 00 - -TX

    S F ADR DATA CRC

  • 7/28/2019 Na20 Mb0 Manual Pr 0250

    17/51

    PRON NA20-MB0

    5 Glossary

    BH Most significative Byte of a Word data (Higher byte)BL Least significative Byte of a Word data (Lower byte)LSB Least Significative Bytelsb least significative bitMSB Most Significative Byte

    msb Most significative bitNTP Network Time ProtocolRTU Remote Terminal UnitTPR Thytronic Protective RelayWH Most significative Word of a Long data (Higher word)WL Least significative Word of a Long data (Lower word)

  • 7/28/2019 Na20 Mb0 Manual Pr 0250

    18/51

    PRON NA20-MB0

    Version 2.50

    PRON NA20-MB0 Remote Setting Manual Page: 18 of 51

    6 Appendix A. Address Data Table

    VAR REF IDX DIM TYPE Range Um Kv ENUM

    Commands

    Set RTC 0x 1 1 CMD 0=OFF, 1=ON

    Reset CB Open counter 0x 2 1 CMD 0=OFF, 1=ON

    Reset LEDs 0x 3 1 CMD 0=OFF, 1=ON

    Reset CB time action 0x 4 1 CMD 0=OFF, 1=ON

    Reset Breaking currents SumI2t 0x 5 1 CMD 0=OFF, 1=ON

    Reset Breaking currents SumI 0x 6 1 CMD 0=OFF, 1=ON

    Reset partial counters 0x 7 1 CMD 0=OFF, 1=ON

    Thermal image presetting 0x 8 1 CMD 0=OFF, 1=ON

    Fault reading 0x 9 1 CMD 0=OFF, 1=ON

    Reset faults 0x 10 1 CMD 0=OFF, 1=ON

    Reset faults identifier 0x 11 1 CMD 0=OFF, 1=ON

    Events reading 0x 12 1 CMD 0=OFF, 1=ON

    Reset events 0x 13 1 CMD 0=OFF, 1=ON

    Reset event identifier 0x 14 1 CMD 0=OFF, 1=ON

    Open CB 0x 15 1 CMD 0=OFF, 1=ON

    Close CB 0x 16 1 CMD 0=OFF, 1=ON

    Test-off 0x 17 1 CMD 0=OFF, 1=ON

    Test-on 0x 18 1 CMD 0=OFF, 1=ON

    Reset on demand measures 0x 19 1 CMD 0=OFF, 1=ON

    Day 4x 1 1 UWORD 1,31,1 1

    Month 4x 2 1 UWORD 1,12,1 1Year 4x 3 1 UWORD 2000,2099,1 1

    Hour 4x 4 1 UWORD 0,23,1 1

    Minute 4x 5 1 UWORD 0,59,1 1

    Second 4x 6 1 UWORD 0,59,1 1

    Testing rele 4x 7 1 WORD 0="K1",1="K2",2="K3",3="K4",4="K5",5="K6",6="K7",7="K8",8="K9",9="K10"

  • 7/28/2019 Na20 Mb0 Manual Pr 0250

    19/51

    PRON NA20-MB0

    Version 2.50

    PRON NA20-MB0 Remote Setting Manual Page: 19 of 51

    VAR REF IDX DIM TYPE Range Um Kv ENUM

    InfoCode 3x 1 6 STR

    Serial number - 3x 7 2 LONG 1

    Application sw release 3x 9 6 STR

    Base sw release 3x 15 6 STR

    DSP fw identifier 3x 21 1 UWORD 1

    DSP fw release 3x 22 6 STR

    Communication

    Address 3x 28 1 UBYTE 1IP host address 3x 29 8 STR

    IP net mask 3x 37 8 STR

    Autonegotiation 1x 1 1 BIT 0=OFF, 1=ON

    Enable 1x 2 1 BIT 0=OFF, 1=ON

    Rated nominal values

    Relay reference name 3x 45 8 STR

    Relay phase nominal current - In 3x 53 2 ULONG A 1

    Relay residual nominal current - IEn 3x 55 2 ULONG A 1

    Phase CT primary nominal current - Inp 3x 57 2 ULONG A 1

    Residual CT primary nominal current - IEnp 3x 59 2 ULONG A 1

    Relay nominal frequency - fn 3x 61 2 ULONG Hz 1

    Measurements reading mode 3x 63 1 WORD 0="RELATIVE",1="PRIMARY"

    Profile selection

    Profile 3x 64 1 WORD 0="A",1="B"

    Clock

    Day 3x 65 1 UWORD 1

    Month 3x 66 1 UWORD 1

    Year 3x 67 1 UWORD 1

    Hour 3x 68 1 UWORD 1

    Minute 3x 69 1 UWORD 1

    Second 3x 70 1 UWORD 1

  • 7/28/2019 Na20 Mb0 Manual Pr 0250

    20/51

    PRON NA20-MB0

    Version 2.50

    PRON NA20-MB0 Remote Setting Manual Page: 20 of 51

    VAR REF IDX DIM TYPE Range Um Kv ENUM

    READINGSDiagnostic

    MINOR Fail alarm 1x 3 1 BIT 0=NO, 1=YES

    Protection and controls 1x 4 1 BIT 0=OUT OF SERVICE, 1=ONSERVICE

    System diagnostic 3x 71 1 WORD 0="OK",1="FATAL",2="MAJOR",3="MINOR"

    Device diagnostic 1x 5 1 BIT 0=OK, 1=NOT OK

    Program diagnostic 3x 72 1 WORD 0="OK",1="NOTOK",2="Disappeared"

    Data-base boot 3x 73 1 WORD 0="OK",1="NOTOK",2="Disappeared"

    Data-base run-time 3x 74 1 WORD 0="OK",1="NOTOK",2="Disappeared"

    DSP boot 3x 75 1 WORD 0="OK",1="NOTOK",2="Disappeared"

    DSP run-time 3x 76 1 WORD 0="OK",1="NOTOK",2="Disappeared"

    Memory boot 3x 77 1 WORD 0="OK",1="NOTOK",2="Disappeared"

    Memory run-time 3x 78 1 WORD 0="OK",1="NOT

    OK",2="Disappeared"Serial flash startup 3x 79 1 WORD 0="OK",1="NOT

    OK",2="Disappeared"Serial flash run-time 3x 80 1 WORD 0="OK",1="NOT

    OK",2="Disappeared"Data Bus heavy 3x 81 1 WORD 0="OK",1="NOT

    OK",2="Disappeared"

    Data Bus minor 3x 82 1 WORD 0="OK",1="NOTOK",2="Disappeared"

    Protection I/O assigned verify startup 3x 83 1 WORD 0="OK",1="NOTOK",2="Disappeared"

    Protection I/O assigned verify run-time major 3x 84 1 WORD 0="OK",1="NOTOK",2="Disappeared"

    Protection I/O assigned verify run-time minor 3x 85 1 WORD 0="OK",1="NOTOK",2="Disappeared"

    PLC I/O assigned verify startup 3x 86 1 WORD 0="OK",1="NOTOK",2="Disappeared"

    PLC I/O assigned verify run-time major 3x 87 1 WORD 0="OK",1="NOTOK",2="Disappeared"

    PLC I/O assigned verify run-time minor 3x 88 1 WORD 0="OK",1="NOTOK",2="Disappeared"

  • 7/28/2019 Na20 Mb0 Manual Pr 0250

    21/51

    PRON NA20-MB0

    Version 2.50

    PRON NA20-MB0 Remote Setting Manual Page: 21 of 51

    VAR REF IDX DIM TYPE Range Um Kv ENUM

    DiagnosticMMI module - Boot 3x 89 1 WORD 0="NOT OK: Undefined

    module",1="OK",2="NOT OK:missing module",3="NOT OK:incompatiblemodule",4="OK",5="NOTOK",6="OFF",7="OFF: Removemodule"

    MMI module - Run-time 3x 90 1 WORD 0="NOT OK: Undefinedmodule",1="OK",2="NOT OK:missing module",3="NOT OK:

    incompatiblemodule",4="OK",5="NOTOK",6="OFF",7="OFF: Removemodule"

    MRI module - Boot 3x 91 1 WORD 0="NOT OK: Undefinedmodule",1="OK",2="NOT OK:missing module",3="NOT OK:incompatiblemodule",4="OK",5="NOTOK",6="OFF",7="OFF: Removemodule"

    MRI module - Run-time 3x 92 1 WORD 0="NOT OK: Undefinedmodule",1="OK",2="NOT OK:missing module",3="NOT OK:incompatiblemodule",4="OK",5="NOTOK",6="OFF",7="OFF: Removemodule"

  • 7/28/2019 Na20 Mb0 Manual Pr 0250

    22/51

    PRON NA20-MB0

    Version 2.50

    PRON NA20-MB0 Remote Setting Manual Page: 22 of 51

    VAR REF IDX DIM TYPE Range Um Kv ENUM

    DiagnosticMID16-1 module - Boot 3x 93 1 WORD 0="NOT OK: Undefined

    module",1="OK",2="NOT OK:missing module",3="NOT OK:incompatiblemodule",4="OK",5="NOTOK",6="OFF",7="OFF: Removemodule"

    MID16-1 module - Run-time 3x 94 1 WORD 0="NOT OK: Undefinedmodule",1="OK",2="NOT OK:missing module",3="NOT OK:

    incompatiblemodule",4="OK",5="NOTOK",6="OFF",7="OFF: Removemodule"

    MID16-2 module - Boot 3x 95 1 WORD 0="NOT OK: Undefinedmodule",1="OK",2="NOT OK:missing module",3="NOT OK:incompatiblemodule",4="OK",5="NOTOK",6="OFF",7="OFF: Removemodule"

    MID16-2 module - Run-time 3x 96 1 WORD 0="NOT OK: Undefinedmodule",1="OK",2="NOT OK:missing module",3="NOT OK:incompatiblemodule",4="OK",5="NOTOK",6="OFF",7="OFF: Removemodule"

    PT100 module - Boot 3x 97 1 WORD 0="NOT OK: Undefinedmodule",1="OK",2="NOT OK:missing module",3="NOT OK:incompatiblemodule",4="OK",5="NOT

    OK",6="OFF",7="OFF: Removemodule"

  • 7/28/2019 Na20 Mb0 Manual Pr 0250

    23/51

    PRON NA20-MB0

    Version 2.50

    PRON NA20-MB0 Remote Setting Manual Page: 23 of 51

    VAR REF IDX DIM TYPE Range Um Kv ENUM

    DiagnosticPT100 module - Run-time 3x 98 1 WORD 0="NOT OK: Undefined

    module",1="OK",2="NOT OK:missing module",3="NOT OK:incompatiblemodule",4="OK",5="NOTOK",6="OFF",7="OFF: Removemodule"

    MCI module (4...20mA) - Boot 3x 99 1 WORD 0="NOT OK: Undefinedmodule",1="OK",2="NOT OK:missing module",3="NOT OK:

    incompatiblemodule",4="OK",5="NOTOK",6="OFF",7="OFF: Removemodule"

    MCI module (4...20mA) - Run-time 3x 100 1 WORD 0="NOT OK: Undefinedmodule",1="OK",2="NOT OK:missing module",3="NOT OK:incompatiblemodule",4="OK",5="NOTOK",6="OFF",7="OFF: Removemodule"

  • 7/28/2019 Na20 Mb0 Manual Pr 0250

    24/51

    PRON NA20-MB0

    Version 2.50

    PRON NA20-MB0 Remote Setting Manual Page: 24 of 51

    VAR REF IDX DIM TYPE Range Um Kv ENUM

    PROTECTIONSThermal protection with RTD thermometric probes - 26

    Alarm ThAL1 1x 6 1 BIT 0=OFF, 1=ON

    Trip Th>1 1x 7 1 BIT 0=OFF, 1=ON

    Alarm ThAL2 1x 8 1 BIT 0=OFF, 1=ON

    Trip Th>2 1x 9 1 BIT 0=OFF, 1=ON

    Alarm ThAL3 1x 10 1 BIT 0=OFF, 1=ON

    Trip Th>3 1x 11 1 BIT 0=OFF, 1=ON

    Alarm ThAL4 1x 12 1 BIT 0=OFF, 1=ONTrip Th>4 1x 13 1 BIT 0=OFF, 1=ON

    Alarm ThAL5 1x 14 1 BIT 0=OFF, 1=ON

    Trip Th>5 1x 15 1 BIT 0=OFF, 1=ON

    Alarm ThAL6 1x 16 1 BIT 0=OFF, 1=ON

    Trip Th>6 1x 17 1 BIT 0=OFF, 1=ON

    Alarm ThAL7 1x 18 1 BIT 0=OFF, 1=ON

    Trip Th>7 1x 19 1 BIT 0=OFF, 1=ON

    Alarm ThAL8 1x 20 1 BIT 0=OFF, 1=ONTrip Th>8 1x 21 1 BIT 0=OFF, 1=ON

    Diag PT100 1x 22 1 BIT 0=OFF, 1=ON

    Undercurrent - 37

    Start I< 1x 23 1 BIT 0=OFF, 1=ON

    Trip I< 1x 24 1 BIT 0=OFF, 1=ON

    BLK1 I< 1x 25 1 BIT 0=OFF, 1=ON

  • 7/28/2019 Na20 Mb0 Manual Pr 0250

    25/51

    PRON NA20-MB0

    Version 2.50

    PRON NA20-MB0 Remote Setting Manual Page: 25 of 51

    VAR REF IDX DIM TYPE Range Um Kv ENUM

    Negative sequence overcurrent - 46Start I2> 1x 26 1 BIT 0=OFF, 1=ON

    Trip I2> 1x 27 1 BIT 0=OFF, 1=ON

    BLK1 I2> 1x 28 1 BIT 0=OFF, 1=ON

    BLK2IN I2> 1x 29 1 BIT 0=OFF, 1=ON

    CLP I2> 1x 30 1 BIT 0=OFF, 1=ON

    Start I2>> 1x 31 1 BIT 0=OFF, 1=ON

    Trip I2>> 1x 32 1 BIT 0=OFF, 1=ON

    BLK1 I2>> 1x 33 1 BIT 0=OFF, 1=ONBLK2IN I2>> 1x 34 1 BIT 0=OFF, 1=ON

    CLP I2>> 1x 35 1 BIT 0=OFF, 1=ON

    Negative sequence current / positive sequence current ratio -I2/I1

    Start I21> 1x 36 1 BIT 0=OFF, 1=ON

    Trip I21> 1x 37 1 BIT 0=OFF, 1=ON

    BLK1 I21> 1x 38 1 BIT 0=OFF, 1=ON

    Thermal image - 49Alarm DthAL1 1x 39 1 BIT 0=OFF, 1=ON

    BLK1 DthAL1 1x 40 1 BIT 0=OFF, 1=ON

    BLK2IN DthAL1 1x 41 1 BIT 0=OFF, 1=ON

    Alarm DthAL2 1x 42 1 BIT 0=OFF, 1=ON

    BLK1 DthAL2 1x 43 1 BIT 0=OFF, 1=ON

    BLK2IN DthAL2 1x 44 1 BIT 0=OFF, 1=ON

    Trip Dth> 1x 45 1 BIT 0=OFF, 1=ON

    BLK1 Dth> 1x 46 1 BIT 0=OFF, 1=ON

    BLK2IN Dth> 1x 47 1 BIT 0=OFF, 1=ON

    CLP Dth 1x 48 1 BIT 0=OFF, 1=ON

  • 7/28/2019 Na20 Mb0 Manual Pr 0250

    26/51

    PRON NA20-MB0

    Version 2.50

    PRON NA20-MB0 Remote Setting Manual Page: 26 of 51

    VAR REF IDX DIM TYPE Range Um Kv ENUM

    Phase overcurrent - 50/51Start I> 1x 49 1 BIT 0=OFF, 1=ON

    Trip I> 1x 50 1 BIT 0=OFF, 1=ON

    BLK1 I> 1x 51 1 BIT 0=OFF, 1=ON

    BLK2IN I> 1x 52 1 BIT 0=OFF, 1=ON

    CLP I> 1x 53 1 BIT 0=OFF, 1=ON

    Start I>> 1x 54 1 BIT 0=OFF, 1=ON

    Trip I>> 1x 55 1 BIT 0=OFF, 1=ON

    BLK1 I>> 1x 56 1 BIT 0=OFF, 1=ONBLK2IN I>> 1x 57 1 BIT 0=OFF, 1=ON

    CLP I>> 1x 58 1 BIT 0=OFF, 1=ON

    Start I>>> 1x 59 1 BIT 0=OFF, 1=ON

    Trip I>>> 1x 60 1 BIT 0=OFF, 1=ON

    BLK1 I>>> 1x 61 1 BIT 0=OFF, 1=ON

    BLK2IN I>>> 1x 62 1 BIT 0=OFF, 1=ON

    CLP I>>> 1x 63 1 BIT 0=OFF, 1=ON

    Residual overcurrent - 50N/51NStart IE> 1x 64 1 BIT 0=OFF, 1=ON

    Trip IE> 1x 65 1 BIT 0=OFF, 1=ON

    BLK1 IE> 1x 66 1 BIT 0=OFF, 1=ON

    BLK2IN IE> 1x 67 1 BIT 0=OFF, 1=ON

    CLP IE> 1x 68 1 BIT 0=OFF, 1=ON

    Start IE>> 1x 69 1 BIT 0=OFF, 1=ON

    Trip IE>> 1x 70 1 BIT 0=OFF, 1=ON

    BLK1 IE>> 1x 71 1 BIT 0=OFF, 1=ON

    BLK2IN IE>> 1x 72 1 BIT 0=OFF, 1=ON

    CLP IE>> 1x 73 1 BIT 0=OFF, 1=ON

    Start IE>>> 1x 74 1 BIT 0=OFF, 1=ON

    Trip IE>>> 1x 75 1 BIT 0=OFF, 1=ON

    BLK1 IE>>> 1x 76 1 BIT 0=OFF, 1=ON

    BLK2IN IE>>> 1x 77 1 BIT 0=OFF, 1=ON

    CLP IE>>> 1x 78 1 BIT 0=OFF, 1=ON

  • 7/28/2019 Na20 Mb0 Manual Pr 0250

    27/51

    PRON NA20-MB0

    Version 2.50

    PRON NA20-MB0 Remote Setting Manual Page: 27 of 51

    VAR REF IDX DIM TYPE Range Um Kv ENUM

    Second Harmonic Restraint

    Start I2ndh> 1x 79 1 BIT 0=OFF, 1=ON

    Trip circuit supervision - 74TCS

    Start 74TCS 1x 80 1 BIT 0=OFF, 1=ON

    Trip 74TCS 1x 81 1 BIT 0=OFF, 1=ON

    BLK1 74TCS 1x 82 1 BIT 0=OFF, 1=ON

    Breaker Failure - BF

    Trip Int/Ext 1x 83 1 BIT 0=OFF, 1=ON

    Start IBF> 1x 84 1 BIT 0=OFF, 1=ONStart IEBF> 1x 85 1 BIT 0=OFF, 1=ON

    Start BF 1x 86 1 BIT 0=OFF, 1=ON

    Trip BF 1x 87 1 BIT 0=OFF, 1=ON

    BLK1 BF 1x 88 1 BIT 0=OFF, 1=ON

    CT supervision - 74CT

    Start I* 1x 89 1 BIT 0=OFF, 1=ON

    Trip S< 1x 90 1 BIT 0=OFF, 1=ON

    BLK1 S< 1x 91 1 BIT 0=OFF, 1=ON

    PRON NA20 MB0

  • 7/28/2019 Na20 Mb0 Manual Pr 0250

    28/51

    PRON NA20-MB0

    Version 2.50

    PRON NA20-MB0 Remote Setting Manual Page: 28 of 51

    VAR REF IDX DIM TYPE Range Um Kv ENUM

    PLC

    State 1 3x 101 1 WORD 0="0",1="1"

    State 2 3x 102 1 WORD 0="0",1="1"

    State 3 3x 103 1 WORD 0="0",1="1"

    State 4 3x 104 1 WORD 0="0",1="1"

    State 5 3x 105 1 WORD 0="0",1="1"

    State 6 3x 106 1 WORD 0="0",1="1"

    State 7 3x 107 1 WORD 0="0",1="1"

    State 8 3x 108 1 WORD 0="0",1="1"State 9 3x 109 1 WORD 0="0",1="1"

    State 10 3x 110 1 WORD 0="0",1="1"

    State 11 3x 111 1 WORD 0="0",1="1"

    State 12 3x 112 1 WORD 0="0",1="1"

    State 13 3x 113 1 WORD 0="0",1="1"

    State 14 3x 114 1 WORD 0="0",1="1"

    State 15 3x 115 1 WORD 0="0",1="1"

    State 16 3x 116 1 WORD 0="0",1="1"State 17 3x 117 1 WORD 0="0",1="1"

    State 18 3x 118 1 WORD 0="0",1="1"

    State 19 3x 119 1 WORD 0="0",1="1"

    State 20 3x 120 1 WORD 0="0",1="1"

    State 21 3x 121 1 WORD 0="0",1="1"

    State 22 3x 122 1 WORD 0="0",1="1"

    State 23 3x 123 1 WORD 0="0",1="1"

    State 24 3x 124 1 WORD 0="0",1="1"

    State 25 3x 125 1 WORD 0="0",1="1"

    State 26 3x 126 1 WORD 0="0",1="1"

    State 27 3x 127 1 WORD 0="0",1="1"

    State 28 3x 128 1 WORD 0="0",1="1"

    State 29 3x 129 1 WORD 0="0",1="1"

    State 30 3x 130 1 WORD 0="0",1="1"

    State 31 3x 131 1 WORD 0="0",1="1"

    State 32 3x 132 1 WORD 0="0",1="1"

    PRON NA20 MB0

  • 7/28/2019 Na20 Mb0 Manual Pr 0250

    29/51

    PRON NA20-MB0

    Version 2.50

    PRON NA20-MB0 Remote Setting Manual Page: 29 of 51

    VAR REF IDX DIM TYPE Range Um Kv ENUM

    Circuit Breaker supervision

    CB-State 3x 133 1 WORD 0="Open",1="Closed",2="?"

    52a 1x 92 1 BIT 0=OFF, 1=ON

    52b 1x 93 1 BIT 0=OFF, 1=ON

    CB fail 1x 94 1 BIT 0=OFF, 1=ON

    Break time assigned relays state 1x 95 1 BIT 0=OFF, 1=ON

    State N.Open 1x 96 1 BIT 0=OFF, 1=ON

    State SumI 1x 97 1 BIT 0=OFF, 1=ON

    SumIL1 3x 134 2 ULONG In 16000

    SumIL2 3x 136 2 ULONG In 16000SumIL3 3x 138 2 ULONG In 16000

    State SumI^2t 1x 98 1 BIT 0=OFF, 1=ON

    SumIL1^2t 3x 140 2 ULONG In^2s 250000

    SumIL2^2t 3x 142 2 ULONG In^2s 250000

    SumIL3^2t 3x 144 2 ULONG In^2s 250000

    State tbreak 1x 99 1 BIT 0=OFF, 1=ON

    PARTIAL COUNTERS

    Thermal protection with RTD thermometric probes - 26ParThAL1cnt - Value 3x 146 1 WORD

    ParTh>1cnt - Value 3x 147 1 WORD

    ParThAL2cnt - Value 3x 148 1 WORD

    ParTh>2cnt - Value 3x 149 1 WORD

    ParThAL3cnt - Value 3x 150 1 WORD

    ParTh>3cnt - Value 3x 151 1 WORD

    ParThAL4cnt - Value 3x 152 1 WORD

    ParTh>4cnt - Value 3x 153 1 WORDParThAL5cnt - Value 3x 154 1 WORD

    ParTh>5cnt - Value 3x 155 1 WORD

    ParThAL6cnt - Value 3x 156 1 WORD

    ParTh>6cnt - Value 3x 157 1 WORD

    ParThAL7cnt - Value 3x 158 1 WORD

    ParTh>7cnt - Value 3x 159 1 WORD

    ParThAL8cnt - Value 3x 160 1 WORD

    ParTh>8cnt - Value 3x 161 1 WORD

    PRON NA20 MB0

  • 7/28/2019 Na20 Mb0 Manual Pr 0250

    30/51

    PRON NA20-MB0

    Version 2.50

    PRON NA20-MB0 Remote Setting Manual Page: 30 of 51

    VAR REF IDX DIM TYPE Range Um Kv ENUM

    Undercurrent - 37

    ParStIcnt - Value 3x 167 1 WORD

    ParBk2I2>cnt - Value 3x 168 1 WORD

    ParStI2>>cnt - Value 3x 169 1 WORDParTrI2>>cnt - Value 3x 170 1 WORD

    ParBk1I2>>cnt - Value 3x 171 1 WORD

    ParBk2I2>>cnt - Value 3x 172 1 WORD

    Negative sequence current / positive sequence current ratio -I2/I1

    ParStI21>cnt - Value 3x 173 1 WORD

    ParTrI21>cnt - Value 3x 174 1 WORD

    ParBk1I21>cnt - Value 3x 175 1 WORDThermal image - 49

    ParAlDthAL1cnt - Value 3x 176 1 WORD

    ParBk1DthAL1cnt - Value 3x 177 1 WORD

    ParBk2DthAL1cnt - Value 3x 178 1 WORD

    ParAlDthAL2cnt - Value 3x 179 1 WORD

    ParBk1DthAL2cnt - Value 3x 180 1 WORD

    ParBk2DthAL2cnt - Value 3x 181 1 WORD

    ParTrDth>cnt - Value 3x 182 1 WORDParBk1Dth>cnt - Value 3x 183 1 WORD

    ParBk2Dth>cnt - Value 3x 184 1 WORD

    PRON NA20 MB0

  • 7/28/2019 Na20 Mb0 Manual Pr 0250

    31/51

    PRON NA20-MB0

    Version 2.50

    PRON NA20-MB0 Remote Setting Manual Page: 31 of 51

    VAR REF IDX DIM TYPE Range Um Kv ENUM

    Phase overcurrent - 50/51

    ParStI>cnt - Value 3x 185 1 WORD

    ParTrI>cnt - Value 3x 186 1 WORD

    ParBk1I>cnt - Value 3x 187 1 WORD

    ParBk2I>cnt - Value 3x 188 1 WORD

    ParStI>>cnt - Value 3x 189 1 WORD

    ParTrI>>cnt - Value 3x 190 1 WORD

    ParBk1I>>cnt - Value 3x 191 1 WORD

    ParBk2I>>cnt - Value 3x 192 1 WORDParStI>>>cnt - Value 3x 193 1 WORD

    ParTrI>>>cnt - Value 3x 194 1 WORD

    ParBk1I>>>cnt - Value 3x 195 1 WORD

    ParBk2I>>>cnt - Value 3x 196 1 WORD

    Residual overcurrent - 50N/51N

    ParStIE>cnt - Value 3x 197 1 WORD

    ParTrIE>cnt - Value 3x 198 1 WORD

    ParBk1IE>cnt - Value 3x 199 1 WORDParBk2IE>cnt - Value 3x 200 1 WORD

    ParStIE>>cnt - Value 3x 201 1 WORD

    ParTrIE>>cnt - Value 3x 202 1 WORD

    ParBk1IE>>cnt - Value 3x 203 1 WORD

    ParBk2IE>>cnt - Value 3x 204 1 WORD

    ParStIE>>>cnt - Value 3x 205 1 WORD

    ParTrIE>>>cnt - Value 3x 206 1 WORD

    ParBk1IE>>>cnt - Value 3x 207 1 WORDParBk2IE>>>cnt - Value 3x 208 1 WORD

    Second Harmonic Restraint

    ParStI2ndh>cnt - Value 3x 209 1 WORD

    PRON NA20 MB0

  • 7/28/2019 Na20 Mb0 Manual Pr 0250

    32/51

    PRON NA20-MB0

    Version 2.50

    PRON NA20-MB0 Remote Setting Manual Page: 32 of 51

    VAR REF IDX DIM TYPE Range Um Kv ENUM

    Trip circuit supervision - 74TCS

    ParTr74TCScnt - Value 3x 210 1 WORD

    ParBk1-74TCScnt - Value 3x 211 1 WORD

    Circuit Breaker supervision

    N.OpenCBcnt 3x 212 1 UWORD 1

    CT supervision - 74CT

    ParTr74CTcnt - Value 3x 213 1 WORD

    ParBk1-74CTcnt - Value 3x 214 1 WORD

    Accessory countersParStBFcnt - Value 3x 215 1 WORD

    ParTrBFcnt - Value 3x 216 1 WORD

    ParBk1BFcnt - Value 3x 217 1 WORD

    PRON NA20-MB0

  • 7/28/2019 Na20 Mb0 Manual Pr 0250

    33/51

    PRON NA20-MB0

    Version 2.50

    PRON NA20-MB0 Remote Setting Manual Page: 33 of 51

    VAR REF IDX DIM TYPE Range Um Kv ENUM

    Delayed inputs

    IN1 1x 100 1 BIT 0=OFF, 1=ON

    IN2 1x 101 1 BIT 0=OFF, 1=ON

    IN3 1x 102 1 BIT 0=OFF, 1=ON

    IN4 1x 103 1 BIT 0=OFF, 1=ON

    IN5 1x 104 1 BIT 0=OFF, 1=ON

    IN6 1x 105 1 BIT 0=OFF, 1=ON

    IN7 1x 106 1 BIT 0=OFF, 1=ON

    IN8 1x 107 1 BIT 0=OFF, 1=ON

    IN9 1x 108 1 BIT 0=OFF, 1=ON

    IN10 1x 109 1 BIT 0=OFF, 1=ON

    IN11 1x 110 1 BIT 0=OFF, 1=ON

    IN12 1x 111 1 BIT 0=OFF, 1=ON

    IN13 1x 112 1 BIT 0=OFF, 1=ON

    IN14 1x 113 1 BIT 0=OFF, 1=ON

    IN15 1x 114 1 BIT 0=OFF, 1=ON

    IN16 1x 115 1 BIT 0=OFF, 1=ONIN17 1x 116 1 BIT 0=OFF, 1=ON

    IN18 1x 117 1 BIT 0=OFF, 1=ON

    IN19 1x 118 1 BIT 0=OFF, 1=ON

    IN20 1x 119 1 BIT 0=OFF, 1=ON

    IN21 1x 120 1 BIT 0=OFF, 1=ON

    IN22 1x 121 1 BIT 0=OFF, 1=ON

    IN23 1x 122 1 BIT 0=OFF, 1=ON

    IN24 1x 123 1 BIT 0=OFF, 1=ONIN25 1x 124 1 BIT 0=OFF, 1=ON

    IN26 1x 125 1 BIT 0=OFF, 1=ON

    IN27 1x 126 1 BIT 0=OFF, 1=ON

    IN28 1x 127 1 BIT 0=OFF, 1=ON

    IN29 1x 128 1 BIT 0=OFF, 1=ON

    IN30 1x 129 1 BIT 0=OFF, 1=ON

    IN31 1x 130 1 BIT 0=OFF, 1=ON

    IN32 1x 131 1 BIT 0=OFF, 1=ON

    PRON NA20-MB0

  • 7/28/2019 Na20 Mb0 Manual Pr 0250

    34/51

    PRON NA20-MB0

    Version 2.50

    PRON NA20-MB0 Remote Setting Manual Page: 34 of 51

    VAR REF IDX DIM TYPE Range Um Kv ENUM

    Delayed inputs

    IN33 1x 132 1 BIT 0=OFF, 1=ON

    IN34 1x 133 1 BIT 0=OFF, 1=ON

    IN35 1x 134 1 BIT 0=OFF, 1=ON

    IN36 1x 135 1 BIT 0=OFF, 1=ON

    IN37 1x 136 1 BIT 0=OFF, 1=ON

    IN38 1x 137 1 BIT 0=OFF, 1=ON

    IN39 1x 138 1 BIT 0=OFF, 1=ON

    IN40 1x 139 1 BIT 0=OFF, 1=ON

    IN41 1x 140 1 BIT 0=OFF, 1=ON

    IN42 1x 141 1 BIT 0=OFF, 1=ON

    IN43 1x 142 1 BIT 0=OFF, 1=ON

    IN44 1x 143 1 BIT 0=OFF, 1=ON

    IN45 1x 144 1 BIT 0=OFF, 1=ON

    PRON NA20-MB0

  • 7/28/2019 Na20 Mb0 Manual Pr 0250

    35/51

    PRON NA20 MB0

    Version 2.50

    PRON NA20-MB0 Remote Setting Manual Page: 35 of 51

    VAR REF IDX DIM TYPE Range Um Kv ENUM

    Internal states

    Reset LEDs 1x 145 1 BIT 0=OFF, 1=ON

    Profile selection 1x 146 1 BIT 0=OFF, 1=ON

    Fault trigger 1x 147 1 BIT 0=OFF, 1=ON

    IE/IPh Block2 1x 148 1 BIT 0=OFF, 1=ON

    IPh Block2 1x 149 1 BIT 0=OFF, 1=ON

    IE Block2 1x 150 1 BIT 0=OFF, 1=ON

    Block1 1x 151 1 BIT 0=OFF, 1=ON

    Tcs1 1x 152 1 BIT 0=OFF, 1=ON

    Tcs2 1x 153 1 BIT 0=OFF, 1=ON

    Trip External protections 1x 154 1 BIT 0=OFF, 1=ON

    Reset partial counters 1x 155 1 BIT 0=OFF, 1=ON

    Reset CB monitoring data 1x 156 1 BIT 0=OFF, 1=ON

    52a 1x 157 1 BIT 0=OFF, 1=ON

    52b 1x 158 1 BIT 0=OFF, 1=ON

    Open CB 1x 159 1 BIT 0=OFF, 1=ON

    Close CB 1x 160 1 BIT 0=OFF, 1=ONThermal image presetting 1x 161 1 BIT 0=OFF, 1=ON

    Remote trip 1x 162 1 BIT 0=OFF, 1=ON

    Reset on demand measures 1x 163 1 BIT 0=OFF, 1=ON

    Block2

    BLK2IN-Iph 1x 164 1 BIT 0=OFF, 1=ON

    BLK2IN-IE 1x 165 1 BIT 0=OFF, 1=ON

    tB timeout 1x 166 1 BIT 0=OFF, 1=ON

    ST-Iph-BLK2 1x 167 1 BIT 0=OFF, 1=ONST-IE-BLK2 1x 168 1 BIT 0=OFF, 1=ON

    BLK2OUT-Iph 1x 169 1 BIT 0=OFF, 1=ON

    BLK2OUT-IE 1x 170 1 BIT 0=OFF, 1=ON

    BLK2OUT-Iph/IE 1x 171 1 BIT 0=OFF, 1=ON

    PRON NA20-MB0

  • 7/28/2019 Na20 Mb0 Manual Pr 0250

    36/51

    PRON NA20 MB0

    Version 2.50

    PRON NA20-MB0 Remote Setting Manual Page: 36 of 51

    VAR REF IDX DIM TYPE Range Um Kv ENUM

    Relays

    K1 - State 1x 172 1 BIT 0=OFF, 1=ON

    K1 - Diagnostic 1x 173 1 BIT 0=OFF, 1=ON

    K2 - State 1x 174 1 BIT 0=OFF, 1=ON

    K2 - Diagnostic 1x 175 1 BIT 0=OFF, 1=ON

    K3 - State 1x 176 1 BIT 0=OFF, 1=ON

    K3 - Diagnostic 1x 177 1 BIT 0=OFF, 1=ON

    K4 - State 1x 178 1 BIT 0=OFF, 1=ON

    K4 - Diagnostic 1x 179 1 BIT 0=OFF, 1=ON

    K5 - State 1x 180 1 BIT 0=OFF, 1=ON

    K5 - Diagnostic 1x 181 1 BIT 0=OFF, 1=ON

    K6 - State 1x 182 1 BIT 0=OFF, 1=ON

    K6 - Diagnostic 1x 183 1 BIT 0=OFF, 1=ON

    K7 - State 1x 184 1 BIT 0=OFF, 1=ON

    K7 - Diagnostic 1x 185 1 BIT 0=OFF, 1=ON

    K8 - State 1x 186 1 BIT 0=OFF, 1=ON

    K8 - Diagnostic 1x 187 1 BIT 0=OFF, 1=ONK9 - State 1x 188 1 BIT 0=OFF, 1=ON

    K9 - Diagnostic 1x 189 1 BIT 0=OFF, 1=ON

    K10 - State 1x 190 1 BIT 0=OFF, 1=ON

    K10 - Diagnostic 1x 191 1 BIT 0=OFF, 1=ON

    MEASURES

    Physical

    f - Value 3x 218 2 LONG Hz 1000

    IL1 - Value 3x 220 2 LONG In 16000IL2 - Value 3x 222 2 LONG In 16000

    IL3 - Value 3x 224 2 LONG In 16000

    IE - Value 3x 226 2 LONG IEn 80000

    Calculated

    DTheta - Value 3x 228 2 LONG DThetaB 1000

    ILmax - Value 3x 230 2 LONG In 16000

    ILmin - Value 3x 232 2 LONG In 16000

    IL - Value 3x 234 2 LONG In 16000

    PRON NA20-MB0

  • 7/28/2019 Na20 Mb0 Manual Pr 0250

    37/51

    PRON NA20 MB0

    Version 2.50

    PRON NA20-MB0 Remote Setting Manual Page: 37 of 51

    VAR REF IDX DIM TYPE Range Um Kv ENUM

    Sequence

    I1 - Value 3x 236 2 LONG In 16000

    I2 - Value 3x 238 2 LONG In 16000

    I2/I1 - Value 3x 240 2 LONG 8000

    2nd harmonic

    IL1-2nd - Value 3x 242 2 LONG In 16000

    IL2-2nd - Value 3x 244 2 LONG In 16000

    IL3-2nd - Value 3x 246 2 LONG In 16000

    I-2nd/IL - Value 3x 248 2 LONG % 20

    3rd harmonic

    IL1-3rd - Value 3x 250 2 LONG In 16000

    IL2-3rd - Value 3x 252 2 LONG In 16000

    IL3-3rd - Value 3x 254 2 LONG In 16000

    IE-3rd - Value 3x 256 2 LONG IEn 80000

    4th harmonic

    IL1-4th - Value 3x 258 2 LONG In 16000

    IL2-4th - Value 3x 260 2 LONG In 16000

    IL3-4th - Value 3x 262 2 LONG In 16000

    5th harmonic

    IL1-5th - Value 3x 264 2 LONG In 16000

    IL2-5th - Value 3x 266 2 LONG In 16000

    IL3-5th - Value 3x 268 2 LONG In 16000

    PRON NA20-MB0

  • 7/28/2019 Na20 Mb0 Manual Pr 0250

    38/51

    Version 2.50

    PRON NA20-MB0 Remote Setting Manual Page: 38 of 51

    VAR REF IDX DIM TYPE Range Um Kv ENUM

    Phase demands

    IL1FIX - Value 3x 270 2 LONG In 16000

    IL2FIX - Value 3x 272 2 LONG In 16000

    IL3FIX - Value 3x 274 2 LONG In 16000

    IL1ROL - Value 3x 276 2 LONG In 16000

    IL2ROL - Value 3x 278 2 LONG In 16000

    IL3ROL - Value 3x 280 2 LONG In 16000

    IL1MAX - Value 3x 282 2 LONG In 16000

    IL2MAX - Value 3x 284 2 LONG In 16000

    IL3MAX - Value 3x 286 2 LONG In 16000

    IL1MIN - Value 3x 288 2 LONG In 16000

    IL2MIN - Value 3x 290 2 LONG In 16000

    IL3MIN - Value 3x 292 2 LONG In 16000

  • 7/28/2019 Na20 Mb0 Manual Pr 0250

    39/51

    PRON NA20-MB0

  • 7/28/2019 Na20 Mb0 Manual Pr 0250

    40/51

    Version 2.50

    PRON NA20-MB0 Remote Setting Manual Page: 40 of 51

    VAR REF IDX DIM TYPE Range Um Kv ENUM

    Fault 0

    Fault n. 0 - Fault counter 3x 318 2 LONG 1

    Fault n. 0 - Date 3x 320 6 STR

    Fault n. 0 - Time 3x 326 6 STR

    Fault n. 0 - Fault cause 3x 332 1 WORD 0="No faults",1="I< Start",2="I Start",4="I2>Trip",5="I2>> Start",6="I2>>Trip",7="I21> Start",8="I21>Trip",9="I> Start",10="I>Trip",11="I>> Start",12="I>>

    Trip",13="I>>> Start",14="I>>>Trip",15="IE> Start",16="IE>Trip",17="IE>> Start",18="IE>>Trip",19="IE>>> Start",20="IE>>>Trip",21="DThetaAL1Alarm",22="DThetaAL2Alarm",23="DTheta>Trip",24="PT1 Alarm",25="PT1Trip",26="PT2 Alarm",27="PT2Trip",28="PT3 Alarm",29="PT3Trip",30="PT4 Alarm",31="PT4Trip",32="PT5 Alarm",33="PT5

    Trip",34="PT6 Alarm",35="PT6Trip",36="PT7 Alarm",37="PT7Trip",38="PT8 Alarm",39="PT8Trip",40="74TCS Trip",41="74CTTrip",42="BF Start",43="BFTrip",44="Logic input"

    PRON NA20-MB0

  • 7/28/2019 Na20 Mb0 Manual Pr 0250

    41/51

    Version 2.50

    PRON NA20-MB0 Remote Setting Manual Page: 41 of 51

    VAR REF IDX DIM TYPE Range Um Kv ENUM

    Fault 0

    Fault n. 0 - IL1r 3x 333 2 ULONG In 16000

    Fault n. 0 - IL2r 3x 335 2 ULONG In 16000

    Fault n. 0 - IL3r 3x 337 2 ULONG In 16000

    Fault n. 0 - IEr 3x 339 2 ULONG IEn 80000

    Fault n. 0 - DTheta-r 3x 341 2 ULONG DThetaB 1000

    Fault n. 0 - I2r 3x 343 2 ULONG In 16000

    Fault n. 0 - (I2/I1)r 3x 345 2 ULONG 8000

    Fault n. 0 - T1r 3x 347 2 LONG ^C 10

    Fault n. 0 - T2r 3x 349 2 LONG ^C 10

    Fault n. 0 - T3r 3x 351 2 LONG ^C 10

    Fault n. 0 - T4r 3x 353 2 LONG ^C 10

    Fault n. 0 - T5r 3x 355 2 LONG ^C 10

    Fault n. 0 - T6r 3x 357 2 LONG ^C 10

    Fault n. 0 - T7r 3x 359 2 LONG ^C 10

    Fault n. 0 - T8r 3x 361 2 LONG ^C 10

    Fault n. 0 - Inputs IN1-IN5 3x 363 1 UWORD 1

    Fault n. 0 - Inputs IN6-IN13 3x 364 1 UWORD 1

    Fault n. 0 - Inputs IN14-IN29 3x 365 1 UWORD 1

    Fault n. 0 - Inputs IN30-IN45 3x 366 1 UWORD 1

    Fault n. 0 - Outputs K1-K6 3x 367 1 UWORD 1

    Fault n. 0 - Outputs K7-K10 3x 368 1 UWORD 1

    Fault n. 0 - Fault cause info 3x 369 8 STR

    PRON NA20-MB0

  • 7/28/2019 Na20 Mb0 Manual Pr 0250

    42/51

    Version 2.50

    PRON NA20-MB0 Remote Setting Manual Page: 42 of 51

    VAR REF IDX DIM TYPE Range Um Kv ENUM

    Fault 1

    Fault n. 1 - Fault counter 3x 377 2 LONG 1

    Fault n. 1 - Date 3x 379 6 STR

    Fault n. 1 - Time 3x 385 6 STR

    Fault n. 1 - Fault cause 3x 391 1 WORD 0="No faults",1="I< Start",2="I Start",4="I2>Trip",5="I2>> Start",6="I2>>Trip",7="I21> Start",8="I21>Trip",9="I> Start",10="I>Trip",11="I>> Start",12="I>>Trip",13="I>>> Start",14="I>>>Trip",15="IE> Start",16="IE>Trip",17="IE>> Start",18="IE>>Trip",19="IE>>> Start",20="IE>>>Trip",21="DThetaAL1Alarm",22="DThetaAL2Alarm",23="DTheta>Trip",24="PT1 Alarm",25="PT1Trip",26="PT2 Alarm",27="PT2Trip",28="PT3 Alarm",29="PT3Trip",30="PT4 Alarm",31="PT4Trip",32="PT5 Alarm",33="PT5

    Trip",34="PT6 Alarm",35="PT6Trip",36="PT7 Alarm",37="PT7Trip",38="PT8 Alarm",39="PT8Trip",40="74TCS Trip",41="74CTTrip",42="BF Start",43="BFTrip",44="Logic input"

    PRON NA20-MB0

  • 7/28/2019 Na20 Mb0 Manual Pr 0250

    43/51

    Version 2.50

    PRON NA20-MB0 Remote Setting Manual Page: 43 of 51

    VAR REF IDX DIM TYPE Range Um Kv ENUM

    Fault 1

    Fault n. 1 - IL1r 3x 392 2 ULONG In 16000

    Fault n. 1 - IL2r 3x 394 2 ULONG In 16000

    Fault n. 1 - IL3r 3x 396 2 ULONG In 16000

    Fault n. 1 - IEr 3x 398 2 ULONG IEn 80000

    Fault n. 1 - DTheta-r 3x 400 2 ULONG DThetaB 1000

    Fault n. 1 - I2r 3x 402 2 ULONG In 16000

    Fault n. 1 - (I2/I1)r 3x 404 2 ULONG 8000

    Fault n. 1 - T1r 3x 406 2 LONG ^C 10

    Fault n. 1 - T2r 3x 408 2 LONG ^C 10

    Fault n. 1 - T3r 3x 410 2 LONG ^C 10

    Fault n. 1 - T4r 3x 412 2 LONG ^C 10

    Fault n. 1 - T5r 3x 414 2 LONG ^C 10

    Fault n. 1 - T6r 3x 416 2 LONG ^C 10

    Fault n. 1 - T7r 3x 418 2 LONG ^C 10

    Fault n. 1 - T8r 3x 420 2 LONG ^C 10

    Fault n. 1 - Inputs IN1-IN5 3x 422 1 UWORD 1

    Fault n. 1 - Inputs IN6-IN13 3x 423 1 UWORD 1

    Fault n. 1 - Inputs IN14-IN29 3x 424 1 UWORD 1

    Fault n. 1 - Inputs IN30-IN45 3x 425 1 UWORD 1

    Fault n. 1 - Outputs K1-K6 3x 426 1 UWORD 1

    Fault n. 1 - Outputs K7-K10 3x 427 1 UWORD 1

    Fault n. 1 - Fault cause info 3x 428 8 STR

    PRON NA20-MB0

  • 7/28/2019 Na20 Mb0 Manual Pr 0250

    44/51

    Version 2.50

    PRON NA20-MB0 Remote Setting Manual Page: 44 of 51

    VAR REF IDX DIM TYPE Range Um Kv ENUM

    Fault 2

    Fault n. 2 - Fault counter 3x 436 2 LONG 1

    Fault n. 2 - Date 3x 438 6 STR

    Fault n. 2 - Time 3x 444 6 STR

    Fault n. 2 - Fault cause 3x 450 1 WORD 0="No faults",1="I< Start",2="I Start",4="I2>Trip",5="I2>> Start",6="I2>>Trip",7="I21> Start",8="I21>Trip",9="I> Start",10="I>Trip",11="I>> Start",12="I>>Trip",13="I>>> Start",14="I>>>Trip",15="IE> Start",16="IE>Trip",17="IE>> Start",18="IE>>Trip",19="IE>>> Start",20="IE>>>Trip",21="DThetaAL1Alarm",22="DThetaAL2Alarm",23="DTheta>Trip",24="PT1 Alarm",25="PT1Trip",26="PT2 Alarm",27="PT2Trip",28="PT3 Alarm",29="PT3Trip",30="PT4 Alarm",31="PT4Trip",32="PT5 Alarm",33="PT5

    Trip",34="PT6 Alarm",35="PT6Trip",36="PT7 Alarm",37="PT7Trip",38="PT8 Alarm",39="PT8Trip",40="74TCS Trip",41="74CTTrip",42="BF Start",43="BFTrip",44="Logic input"

    PRON NA20-MB0

  • 7/28/2019 Na20 Mb0 Manual Pr 0250

    45/51

    Version 2.50

    PRON NA20-MB0 Remote Setting Manual Page: 45 of 51

    VAR REF IDX DIM TYPE Range Um Kv ENUM

    Fault 2

    Fault n. 2 - IL1r 3x 451 2 ULONG In 16000

    Fault n. 2 - IL2r 3x 453 2 ULONG In 16000

    Fault n. 2 - IL3r 3x 455 2 ULONG In 16000

    Fault n. 2 - IEr 3x 457 2 ULONG IEn 80000

    Fault n. 2 - DTheta-r 3x 459 2 ULONG DThetaB 1000

    Fault n. 2 - I2r 3x 461 2 ULONG In 16000

    Fault n. 2 - (I2/I1)r 3x 463 2 ULONG 8000

    Fault n. 2 - T1r 3x 465 2 LONG ^C 10

    Fault n. 2 - T2r 3x 467 2 LONG ^C 10

    Fault n. 2 - T3r 3x 469 2 LONG ^C 10

    Fault n. 2 - T4r 3x 471 2 LONG ^C 10

    Fault n. 2 - T5r 3x 473 2 LONG ^C 10

    Fault n. 2 - T6r 3x 475 2 LONG ^C 10

    Fault n. 2 - T7r 3x 477 2 LONG ^C 10

    Fault n. 2 - T8r 3x 479 2 LONG ^C 10

    Fault n. 2 - Inputs IN1-IN5 3x 481 1 UWORD 1

    Fault n. 2 - Inputs IN6-IN13 3x 482 1 UWORD 1

    Fault n. 2 - Inputs IN14-IN29 3x 483 1 UWORD 1

    Fault n. 2 - Inputs IN30-IN45 3x 484 1 UWORD 1

    Fault n. 2 - Outputs K1-K6 3x 485 1 UWORD 1

    Fault n. 2 - Outputs K7-K10 3x 486 1 UWORD 1

    Fault n. 2 - Fault cause info 3x 487 8 STR

    PRON NA20-MB0

  • 7/28/2019 Na20 Mb0 Manual Pr 0250

    46/51

    Version 2.50

    PRON NA20-MB0 Remote Setting Manual Page: 46 of 51

    VAR REF IDX DIM TYPE Range Um Kv ENUM

    Fault 3

    Fault n. 3 - Fault counter 3x 495 2 LONG 1

    Fault n. 3 - Date 3x 497 6 STR

    Fault n. 3 - Time 3x 503 6 STR

    Fault n. 3 - Fault cause 3x 509 1 WORD 0="No faults",1="I< Start",2="I Start",4="I2>Trip",5="I2>> Start",6="I2>>Trip",7="I21> Start",8="I21>Trip",9="I> Start",10="I>Trip",11="I>> Start",12="I>>Trip",13="I>>> Start",14="I>>>Trip",15="IE> Start",16="IE>Trip",17="IE>> Start",18="IE>>Trip",19="IE>>> Start",20="IE>>>Trip",21="DThetaAL1Alarm",22="DThetaAL2Alarm",23="DTheta>Trip",24="PT1 Alarm",25="PT1Trip",26="PT2 Alarm",27="PT2Trip",28="PT3 Alarm",29="PT3Trip",30="PT4 Alarm",31="PT4Trip",32="PT5 Alarm",33="PT5

    Trip",34="PT6 Alarm",35="PT6Trip",36="PT7 Alarm",37="PT7Trip",38="PT8 Alarm",39="PT8Trip",40="74TCS Trip",41="74CTTrip",42="BF Start",43="BFTrip",44="Logic input"

    PRON NA20-MB0

  • 7/28/2019 Na20 Mb0 Manual Pr 0250

    47/51

    Version 2.50

    PRON NA20-MB0 Remote Setting Manual Page: 47 of 51

    VAR REF IDX DIM TYPE Range Um Kv ENUM

    Fault 3

    Fault n. 3 - IL1r 3x 510 2 ULONG In 16000

    Fault n. 3 - IL2r 3x 512 2 ULONG In 16000

    Fault n. 3 - IL3r 3x 514 2 ULONG In 16000

    Fault n. 3 - IEr 3x 516 2 ULONG IEn 80000

    Fault n. 3 - DTheta-r 3x 518 2 ULONG DThetaB 1000

    Fault n. 3 - I2r 3x 520 2 ULONG In 16000

    Fault n. 3 - (I2/I1)r 3x 522 2 ULONG 8000

    Fault n. 3 - T1r 3x 524 2 LONG ^C 10

    Fault n. 3 - T2r 3x 526 2 LONG ^C 10

    Fault n. 3 - T3r 3x 528 2 LONG ^C 10

    Fault n. 3 - T4r 3x 530 2 LONG ^C 10

    Fault n. 3 - T5r 3x 532 2 LONG ^C 10

    Fault n. 3 - T6r 3x 534 2 LONG ^C 10

    Fault n. 3 - T7r 3x 536 2 LONG ^C 10

    Fault n. 3 - T8r 3x 538 2 LONG ^C 10

    Fault n. 3 - Inputs IN1-IN5 3x 540 1 UWORD 1

    Fault n. 3 - Inputs IN6-IN13 3x 541 1 UWORD 1

    Fault n. 3 - Inputs IN14-IN29 3x 542 1 UWORD 1

    Fault n. 3 - Inputs IN30-IN45 3x 543 1 UWORD 1

    Fault n. 3 - Outputs K1-K6 3x 544 1 UWORD 1

    Fault n. 3 - Outputs K7-K10 3x 545 1 UWORD 1

    Fault n. 3 - Fault cause info 3x 546 8 STR

    PRON NA20-MB0

  • 7/28/2019 Na20 Mb0 Manual Pr 0250

    48/51

    Version 2.50

    PRON NA20-MB0 Remote Setting Manual Page: 48 of 51

    VAR REF IDX DIM TYPE Range Um Kv ENUM

    Events

    Event n. 0 - Event counter 3x 554 2 LONG 1

    Event n. 0 - Date 3x 556 6 STR

    Event n. 0 - Hour 3x 562 6 STR

    Event n. 0 - Cause 3x 568 1 WORD SEE MANUAL END PAGE

    Event n. 1 - Event counter 3x 569 2 LONG 1

    Event n. 1 - Date 3x 571 6 STR

    Event n. 1 - Hour 3x 577 6 STR

    Event n. 1 - Cause 3x 583 1 WORD SEE MANUAL END PAGE

    Event n. 2 - Event counter 3x 584 2 LONG 1Event n. 2 - Date 3x 586 6 STR

    Event n. 2 - Hour 3x 592 6 STR

    Event n. 2 - Cause 3x 598 1 WORD SEE MANUAL END PAGE

    Event n. 3 - Event counter 3x 599 2 LONG 1

    Event n. 3 - Date 3x 601 6 STR

    Event n. 3 - Hour 3x 607 6 STR

    Event n. 3 - Cause 3x 613 1 WORD SEE MANUAL END PAGE

    Event n. 4 - Event counter 3x 614 2 LONG 1

    Event n. 4 - Date 3x 616 6 STR

    Event n. 4 - Hour 3x 622 6 STR

    Event n. 4 - Cause 3x 628 1 WORD SEE MANUAL END PAGE

    Event n. 5 - Event counter 3x 629 2 LONG 1

    Event n. 5 - Date 3x 631 6 STR

    Event n. 5 - Hour 3x 637 6 STR

    Event n. 5 - Cause 3x 643 1 WORD SEE MANUAL END PAGEEvent n. 6 - Event counter 3x 644 2 LONG 1

    Event n. 6 - Date 3x 646 6 STREvent n. 6 - Hour 3x 652 6 STR

    Event n. 6 - Cause 3x 658 1 WORD SEE MANUAL END PAGE

    Event n. 7 - Event counter 3x 659 2 LONG 1

    Event n. 7 - Date 3x 661 6 STR

    Event n. 7 - Hour 3x 667 6 STR

    Event n. 7 - Cause 3x 673 1 WORD SEE MANUAL END PAGE

    PRON NA20-MB0

  • 7/28/2019 Na20 Mb0 Manual Pr 0250

    49/51

    Version 2.50

    PRON NA20-MB0 Remote Setting Manual Page: 49 of 51

    VAR REF IDX DIM TYPE Range Um Kv ENUM

    Events

    Event n. 8 - Event counter 3x 674 2 LONG 1

    Event n. 8 - Date 3x 676 6 STR

    Event n. 8 - Hour 3x 682 6 STR

    Event n. 8 - Cause 3x 688 1 WORD SEE MANUAL END PAGE

    Event n. 9 - Event counter 3x 689 2 LONG 1

    Event n. 9 - Date 3x 691 6 STR

    Event n. 9 - Hour 3x 697 6 STR

    Event n. 9 - Cause 3x 703 1 WORD SEE MANUAL END PAGE

    Event n. 10 - Event counter 3x 704 2 LONG 1Event n. 10 - Date 3x 706 6 STR

    Event n. 10 - Hour 3x 712 6 STR

    Event n. 10 - Cause 3x 718 1 WORD SEE MANUAL END PAGE

    Event n. 11 - Event counter 3x 719 2 LONG 1

    Event n. 11 - Date 3x 721 6 STR

    Event n. 11 - Hour 3x 727 6 STR

    Event n. 11 - Cause 3x 733 1 WORD SEE MANUAL END PAGE

    Event n. 12 - Event counter 3x 734 2 LONG 1

    Event n. 12 - Date 3x 736 6 STR

    Event n. 12 - Hour 3x 742 6 STR

    Event n. 12 - Cause 3x 748 1 WORD SEE MANUAL END PAGE

    Event n. 13 - Event counter 3x 749 2 LONG 1

    Event n. 13 - Date 3x 751 6 STR

    Event n. 13 - Hour 3x 757 6 STR

    Event n. 13 - Cause 3x 763 1 WORD SEE MANUAL END PAGEEvent n. 14 - Event counter 3x 764 2 LONG 1

    Event n. 14 - Date 3x 766 6 STREvent n. 14 - Hour 3x 772 6 STR

    Event n. 14 - Cause 3x 778 1 WORD SEE MANUAL END PAGE

    Event n. 15 - Event counter 3x 779 2 LONG 1

    Event n. 15 - Date 3x 781 6 STR

    Event n. 15 - Hour 3x 787 6 STR

    Event n. 15 - Cause 3x 793 1 WORD SEE MANUAL END PAGE

    PRON NA20-MB0

  • 7/28/2019 Na20 Mb0 Manual Pr 0250

    50/51

    Version 2.50

    PRON NA20-MB0 Remote Setting Manual Page: 50 of 51

    VAR REF IDX DIM TYPE Range Um Kv ENUM

    Events

    Event n. 16 - Event counter 3x 794 2 LONG 1

    Event n. 16 - Date 3x 796 6 STR

    Event n. 16 - Hour 3x 802 6 STR

    Event n. 16 - Cause 3x 808 1 WORD SEE MANUAL END PAGE

    Event n. 17 - Event counter 3x 809 2 LONG 1

    Event n. 17 - Date 3x 811 6 STR

    Event n. 17 - Hour 3x 817 6 STR

    Event n. 17 - Cause 3x 823 1 WORD SEE MANUAL END PAGEEvent n. 18 - Event counter 3x 824 2 LONG 1

    Event n. 18 - Date 3x 826 6 STR

    Event n. 18 - Hour 3x 832 6 STR

    Event n. 18 - Cause 3x 838 1 WORD SEE MANUAL END PAGE

    Event n. 19 - Event counter 3x 839 2 LONG 1

    Event n. 19 - Date 3x 841 6 STR

    Event n. 19 - Hour 3x 847 6 STR

    Event n. 19 - Cause 3x 853 1 WORD SEE MANUAL END PAGE

    VAR REF IDX DIM TYPE Range Um Kv ENUM

    Test

    TEST state 1x 192 1 BIT 0=OFF, 1=ON

  • 7/28/2019 Na20 Mb0 Manual Pr 0250

    51/51