■ Merlin Gerin ■ Square D ■ Telemecanique selection of fuses for the protection of transformers A client requires to justify the choice of the despatched fuses… This file must help you to answer. KEEP IN MIND Generally, it is sufficient to use the selection tables. For case not covered by the standard selection tables, you must know characteristics of: ■ the transformer, ■ the breaking system, ■ the fuses. We will make an example with SM6 fuses. date 10/95 - B•3•3 - revised 04/2004 THE BEST?? IT’S ME!!!
14
Embed
Mv Partner b33 Selection of Fuses for Protection of Transformers
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
■ Merlin Gerin ■ Square D ■ Telemecanique
selection of fuses for the protection oftransformers
A client requires tojustify the choice ofthe despatched fuses…
This file must help youto answer.
KEEP IN MIND
Generally, it is sufficient to use theselection tables.
For case not covered by thestandard selection tables, youmust know characteristics of:
■ the transformer,
■ the breaking system,
■ the fuses.
We will make an example with SM6fuses.
date
10/95
- B•3•3 -
revised
04/2004
THE BEST??
IT’S ME!!!
1 - RULES GOVERNINGFUSE SELECTION
Medium voltage fuses used in MV/LV substations are coordinated with theoutput rating of the transformer.
Their time/current characteristics are designed to protect medium voltagedistribution systems from transformer faults and low voltage faults upstreamof LV protection devices.
The fuses may be simply connected in series with the switch-disconnectoror equipped with strikers in a fuse-switch combination to automaticallyopen the switch when a fuse blows, thereby preventing continued operationon one or two remaining phases.
In a “transformer protection” cubicle, the fuse-switch combination can bereplaced by a circuit breaker.
The fuse rating is determined for an ambient temperature not exceeding 40 °Cmaximum or a mean daily value of 35 °C.If these values are exceeded, over-rated fuses must be used to avoidunnecessary fuse-blowing due to these temperatures.
For cases not covered by the standard selection tables, the applicable fuseselection rules and criteria must be respected according to the type of loadand the environment (fuse-switch combination).
Generall y, to select the right fuse , it is sufficient to use theSM6 fuse selection tab les (see pa ge 11).
Selection of fuses f or the pr otection of transf ormer s
page 2
date
10/95
- B•3•3 -
revised
04/2004
2 - SOME DEFINITIONS SYSTEM CHARACTERISTICS
Rated voltage U rThe highest phase-to-phase voltage (in kV) of the system on which the fuseis installed
Short-circuit current I kThe maximum current in the event of a three-phase short-circuit on the system
TRANSFORMER CHARACTERISTICS:
■ output power “P” expressed in kVA,■ short-circuit voltage “Uk%”,■ service voltage “Us” in kV,■ operation with or without overload.
We write:
Rms value of the rated current “I rt”
Short-circuit voltage “U k (%)”The supply voltage for which the short-circuit current is equal to Int,expressed as a percentage of the rated voltage.
Short-circuit current “I k” The current corresponding to a solid short-circuit across the terminals of thesecondary winding of the transformer.
Transformer inrush current “I e” Ie = the peak transient current when the transformer is energised.
“X” = I eIrt
Time constant “t 0” The time constant for the damping of the transient conditions that occurwhen the transformer is energised.
Ik=
Irt x 100
Uk %
Irt =P
Us • 3
Selection of fuses f or the pr otection of transf ormer s
page 3
date
10/95
- B•3•3 -
revised
04/2004
2 - SOME DEFINITIONS(cont’d)
FUSE CHARACTERISTICS:
■ rated current “I rf”The current that the fuse can withstand continuously without abnormal heating.
■ minim um interrupting current I 3The minimum current that can blow and interrupt the fuse.I3 is the lower limit of the current zone within which the fuse is capable ofinterrupting. The value of I3 is generally between 3 and 6 Inf (4.5 Irf accordingto standard UTE 64-210).
☞ Remark: a medium voltage fuse can blow without interrupting theflow of current. This is always the case for current values less than I3.
The arc is sustained, destroying the fuse and its environment.Fuses therefore must never be exposed to currents in the zone
between Inf and I3.
■ time/current c haracteristics of the selected rang e of fusesGiven in the supplier documentation (see example on page 12 for the MerlinGerin Fusarc CF range).
■ shor t-cir cuit breaking capacity I 1This is the maximum prospective current that the fuse can interrupt. It is themaximum fuse test value. This current is very high, generally between 20 kA and 63 kA.
■ resistance of a cold fuse R coldSupplied by the fuse manufacturer.
Selection of fuses f or the pr otection of transf ormer s
page 4
date
10/95
- B•3•3 -
revised
04/2004
3 - CRITERIA APPLICABLETO THE SELECTION OFFUSES FOR THEPROTECTION OFTRANSFORMERS
RULES GOVERNING FUSE SELECTION MUST RESPECT:
Urf ≥ Ur
It must be respect the operating voltage tolerances specified by the fusemanufacturer (an excessively high rated fuse voltage could result in highovervoltages on the system when the fuse blows).
I1 ≥ Ik
Ik ≥ I3
To account for the increase in the resistance of the fuse when heated andfor the installation of fuses in SM6 cubicles (higher air temperature), theresistance of the cold fuse must be multiplied by a coefficient that dependson the cubicle characteristics (volume, etc.).
P = 1.9 Rcold x Irt2Rcold = the resistance of a cold fuse.1.9 = coefficient obtained from tests.
Maximum power for fuses in SM6 cubicles:■■ 100 W if ambient temperature < 40 °C■■ 80 W if ambient temperature 40 °C < θ < 55 °C
■ brief transf ormer o verloads To account for these brief overloads, the following coefficient is applied tothe rated current of the transformer.
I rf ≥ Irt
■ contin uous transf ormer o verloadsIf the transformer is required to operate with a continuous overload, i.e. fora period of several hours or more, the fuse rating must be greater than orequal to 1.3 I overload.
We choose:Irf ≥ 1.3 Ioverload
Operating conditions m ust be considered.
The resistance of a cold fuse m ust be m ultiplied b y acoefficient that depends on the cubic le characteristics.
The fault current on the transf ormer secondar y to beinterrupted m ust be greater than or equal to I 3.
The shor t-cir cuit breaking capacity I 1 (in kAmp) m ust begreater than or equal to the shor t-cir cuit current of thesystem I ksystem .
The rated v olta ge of the fuse U rf (in kV) must be greaterthan or equal to the rated v olta ge of the system.
Selection of fuses f or the pr otection of transf ormer s
page 5
date
10/95
- B•3•3 -
revised
04/2004
3 - CRITERIA APPLICABLETO THE SELECTION OFFUSES FOR THEPROTECTION OFTRANSFORMERS (cont’d)
■ transient inrush currentsThe transients produced when a transformer is energised vary according tothe moment the voltage is applied (with respect to zero voltage) and theremanent flux density of the magnetic circuit.The asymmetry and the magnitude of the current are maximum whenenergisation occurs at zero voltage and the remanent flux density on thesame phase is maximum.Before selecting a fuse, it is therefore necessary to determine the rms valueof the inrush current and its duration.
In practice , it is possib le to use a simple rule that takes theserequirements into account to a void premature a geing of fuses.
This rule consists in checking, on the fuse time/current curve, that the maximumcurrent that blows the fuse at time T, corresponding to the time constant ofthe transformer, is always greater than the transformer inrush current.Imin. fuse blow > X x Irt
- X and T are coming from the transformer supplier’s characteristics table.- If the transient characteristics of the transformer are unknown, an empiricalrule may be used. This consists in checking that the fuse-blowing current at0.15 s is greater than X x Ir where:X = 12 for transformers with low kVA ratings.X = 10 for transformer with rating greater than1,000 kVAExample fr om France T ransf o documentation:T transformer time constantX = Ie/Irtand Uk% of the transformer as a function of its output P (kVA rating).
Ie/Ir
inrush current of a 1,000 kV A transf ormer
X =
IeIrt
Selection of fuses f or the pr otection of transf ormer s
The operation of the switch and the fuses is linked.The fuses are equipped with strikers that open the switch when a fuse blowsto prevent continued operation on the remaining one or two phases.
The switch is capable of interrupting a fault current. It can be actuated byopening releases in the event of internal transformer fault (DGPT relays,Buccholz relays, etc.) or by indirect relays supplied by the currenttransformers or toroids for overload protection (QMC cubicle). The fuseratings must satisfy the requirements of standards IEC 60 282-1 and IEC 62271-105
Type of fuses: Fusarc CF or Solefuse with strikers or other brands.
“Medium” type stricker: minimum energy for fuse-blown tripping = 0.5 Joules.
Standard IEC 62 271-105 defines the conditions that ensure coordinated performance of the fuses and the switches used in combination units.
■ the transition current of the combination unit depends both on thetime/current c haracteristics of the fuses and on the opening time ofthe switc h.
Switch opening is initiated by the fuses near the transition point of a 3-phasefault. The fastest fuse blows, thereby interrupting one of the phases, and itsstriker commands the opening of the switch.The two remaining phases are then faced with a lower current (87%) whichwill be interrupted either by the switch or by the remaining two fuses. Thetransition point is where the switch opens at the same time as the remainingtwo fuses blow. At this point, the switch takes over from the fuses, therebydefining the minimum breaking capacity required for the switch.
The selection of fuses f or fuse-s witc h combination unitsdepends on the transition current I 40 and the short-circuitcurrent seen fr om the primar y.
Selection of fuses f or the pr otection of transf ormer s
page 7
date
10/95
- B•3•3 -
revised
04/2004
From a practical standpoint, the transition current is determined by the plottinga time equal to 0.9 times the switch opening time by the fuses on the minimumtime/current characteristic curve of the fuse (i.e. using a current tolerance of - 6.5 %).
The current corresponding to this point is the v alue of the 3-phasetransition current (I 40)This current must not be greater than the rated transition current, which isthe current specified by the manufacturer of the combination unit and checkedby series TD Itransfer tests.
I40 < Itransfer
The rated transition current (I transfer) corresponds to the breaking capacityof the s witc h (see page 9).
VARIOUS CURRENTS ARE DISPATCHED BETWEEN EACH ITEMS OF THE SYSTEM:
☞ Remark: all the currents are expressed as rms values except for thecurrent Ie, which is expressed as a peak value.
I40
I (A)
t (s) minimum time/currentcharacteristic (- 6.5%)
transition point
switch opens at thesame time as theremaining two fusesblow
3-phase fault detected by the first fuse
0.9 x the opening timeof the switch by the fuses(this opening time is 0.04 s for the SM6, 0.06 for the RM6)
fuse striker commands opening of the switch
Itransfer
Selection of fuses f or the pr otection of transf ormer s
page 8
date
10/95
- B•3•3 -
revised
04/2004
4 - FUSE CHARACTERISTICSIN ACCORDANCE WITHTHE TYPE OF CUBICLE(cont’d)
MV/LVtransformer
loadLVfuseMV
fuse
fuse switch combination SM6 PM or QM cubicle
Itransfer
I1 Irf I3 I r Ie Ik IrIk
Z
Irt
Ie
Isc
Irf
swit
ch
fuse
tran
sfo
rmer
Imini fuse blow
I40
ItransferBC
BC I1
I3min. interrupting current
4 - FUSE CHARACTERISTICSIN ACCORDANCE WITHTHE TYPE OF CUBICLE(cont’d)
BREAKING CAPACITY OF THE SM6 SWITCH AS A FUNCTION OF THE SERVICEVOLTAGE (under transition current conditions).
Itransfer= breaking capacity
TRANSITION CURRENT OF THE FUSE-SWITCH COMBINATION I40
The transition current of the fuse-s witc h combination m ust be lo wer thanthe fault current obser ved on the primar y during a solid shor t-cir cuitacross the secondar y terminals of a transf ormer .
A solid short-circuit across the secondary terminals of a transformer leads tohigh values of the TRV (Transient Recovery Voltage) which the switch maynot be able to handle.Consequently the selected fuse must be able to clear such a fault by itself,without making use of the switch.
In pratice, this condition makes it necessary to check that the transitioncurrent of the switch-fuse combination, calculated as indicated in paragraph8.102-3 of IEC 62 271-105, is less than the current observed on the primary.I40 < Ik
Selection of fuses f or the pr otection of transf ormer s
page 9
date
10/95
- B•3•3 -
revised
04/2004
2,600
2,400
2,200
2,000
1,800
1,600
1,4000 5 10 15 20 25
Us (kV)
Breaking capacity = BC (A)
Itransferfor 15 kV
5 - APPLICATIONEXAMPLES
LET US CHECK THAT THE FUSE 31.5 AMPS IS SITTING 20 KV/630 KVAMPSTRANSFORMER PROTECTION
■ determination of the transf ormer c haracteristicsIrt = 18 Amps Ie = 198 Amps Ik= 450 Amps
■ determination of the fuse c haracteristicsIrf > 1.4 Int (see p. 5) so Irf > 18 x 1.4 = 25.2 Amps; the selected fuse is 31.5 AmpsOn page 6, we find that for a 630 kVA transformer, T = 0.3 sOn the curve (see page 12), for 0.3 s and a 31.5 Amps fuse, we find I z 160 Amps < Ie, this fuse is not acceptable. So, we try with Irf = 40 Amps ; I z 210 Amps > Ie, the 40 Amps fuse is OK.We find I40 on the curve page 12 for a time value of the SM6 0.036 s (0.9 timethe opening time of the fuse ; 0.04 for SM6 ; 0.06 for RM6).I40 = 360 Amps I3 = 135 Amps I1 = 40 kA
Selection of fuses f or the pr otection of transf ormer s
page 10
date
10/95
- B•3•3 -
revised
04/2004
5 - APPLICATIONEXAMPLES (cont’d)
These values meet the previous requirement.
Selection of fuses f or the pr otection of transf ormer s
page 11
date
10/95
- B•3•3 -
revised
04/2004
We find page 8 of the technical leaflet AC0479 about fuse for Irf = 40 Amps I3 = 135and L = 442 mm Selection table for the SM6
Rating in A. no overload - 5 °C < θ < 40 °CPlease consult us for overloads and operation over 40 °C.
See pages 8 and 11
}
6303 • 20
I Irt • 1004
Ie = X • IrtX = 11 (see page 6) See fuse
documentation(see page 3)
transformer Int Ie Isc
fuse Irf I3 Iminifufu I40 I1switch Itransfer
315 kVA Fusarc CF 9 A 25 A 41 A 108 A 130 A 210 A 230 A 40 kA
630 kVA Fusarc CF 18 A 31.5 A 101 A 198 A 160 A N O T C O R R E C T
630 kVA Fusarc CF 18 A 40 A 135 A 198 A 210 A 360 A 450 A 40 kA
type of operating transf ormer output rating (kVA) ratedfuse volta ge volta ge
Selection of fuses f or the pr otection of transf ormer s
page 12
Time/current characteristics of a fuse from the Fusarc CF range (Merlin Gerin)
These curves are an average. The current accuracy is ± 10%
5 - APPLICATIONEXAMPLES (cont’d)
6,3
A
10 A
16 A
20 A
25 A
31,5
A
40 A
50 A
63 A
80 A
100
A
I (A)
T (s)
10864
2
-2
10864
2
-1
10864
2
0
10864
2
1
10864
2
2
10864
2
3
10864
2
4
10 2 4 6 81 10 2 4 6 82 10 2 4 6 83 104
0,036
0,3
210160
I40 = 360
date
10/95
- B•3•3 -
revised
04/2004
6 - IDENTIFICATIONPLATE
7 - SAFETY PRECAUTIONS
FUSE RATING PLATE ON THE FRONT OF THE CUBICLE (QM)
In accordance with standard IEC 62 271-105, the front plate of the cubicleindicates that the use of the fuses at a permanent service current must be in accordance with the reference list
fixed indications}} serial indication
☞ Remark: if a customer does not use the fuses specified by thereference list, he must ensure with the technical department that the fuses installedare compatible with the requirements of IEC 62 271-105, the performance of theSM6 switch and the cubicle environment (heat dissipation).
SAFETY PRECAUTIONS FOR ON-SITE FUSE REPLACEMENT
When a fault occurs downstream of the switch, one or two fuses generally“blow”, the other(s) remaining intact.
The characteristics of the remaining fuse or fuses are modified by the faultsince they have been exposed to a current that may have been high enoughto damage the fuse elements without actually blowing the fuse (the activepart of a fuse is made up of a number of parallel elements).
IF YOU HAVE ANY TROUBLE… Please contact the MV Technical Department.
It is theref ore necessar y, in the e vent of a do wnstreamfault c leared b y the pr otection cubic le, to c hang e all threefuses and dispose of them immediatel y to a void allpossibility of subsequent use .
fusessee reference list
IEC 62271-105 :2002
04 03 006 u
Selection of fuses f or the pr otection of transf ormer s
page 13
date
10/95
- B•3•3 -
revised
04/2004
8 - BIBLIOGRAPHY STANDARDS
■ UTE C64-210 (May 1994)Appareillage à haute tension pour courant alternatif.Fusibles à haute tension pour postes de transformation public de typeintérieur.
■ UTE C13-100 (April 2001)Postes de livraison établis à l’intérieur d’un bâtiment et alimentés par unréseau de distribution publique de deuxième catégorie.