6.1 RISK ASSESSMENT
6.1.1 INTRODUCTION
Hazard analysis involves the identification and quantification of the various hazards (unsafe
conditions). On the other hand, risk assessment deals with recognition and computation of
risks, the equipment in the plant and personnel are prone to, due to accidents resulting
from the hazards present in the plant. Risk assessment follows an extensive hazard analysis.
It involves the identification and assessment of risks the neighboring populations are
exposed to as a result of hazards present. This requires a thorough knowledge of failure
probability, credible accident scenario, vulnerability of population etc. Much of this
information is difficult to get or generate. Consequently, the risk assessment is often
confined to maximum credible accident studies. It provides basis for what should be type
and capacity of its on-site and off-site emergency plan also what types of safety measures
shall be required.
6.1.2 APPROACH TO THE STUDY
Risk involves the occurrence or potential occurrence of some accidents consisting of an
event or sequence of events. The risk assessment study covers the following:
• Identification of potential hazard area;
• Identification of representative failure cases;
• Visualization of the resulting scenarios in terms of fire and explosion;
• Assess the overall damage potential of the identified hazardous events and the
impact zones form the accidental scenarios;
Page 2
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENTAL IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 165
• Furnish the recommendations on the minimization of the worst accident possibilities
• Preparation of Disaster Management Plan;
• Emergency Plan, which includes Occupational and Health Safety Plan;
6.1.3 METHODOLOGY
Quantitative risk assessment (QRA) is a means of making a systematic assessment of the
risks from hazardous activities, and forming a rational evaluation of their significance, in
order to provide input to a decision-making process. The term ‘quantitative risk assessment’
is widely used, but strictly this refers to the purely numerical assessment of risks without
any evaluation of their significance. The study has been conducted based on the premises of
a traditional Quantitative Risk Assessment. The key components of a QRA are explained
below, and illustrated in Figure-6.1 and Figure-6.2.
FIGURE – 6.1
QRA METHODOLOGY
Page 3
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENTAL IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 166
FIGURE–6.2
FLOW CHART FOR QUANTITATIVE RISK ASSESSMENT
Start Identify Risk Areas
Select a Risk Area
Identify Failure Cases
Select a Failure Cases
Identify Consequence Outcomes
Select Consequence Outcomes
Determine Frequency
Estimate Consequence
Record Frequency and Consequence in a summary Table
Have all Consequence outcomes been studied?
Have all failure cases been studied?
Have all risk areas been studied?
Draw Risk Contours Finish
Yes
Next Next
Page 4
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENTAL IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 167
FIGURE–6.3
EMERGENCY ORGANIZATIONAL CHART
Site controller
(GM - Operations)
Amit Upadhayay
Incident Controller
(Production Head & Engg. Head, etc.) Mihir Abhyankar & Ishvar Panchal
EHS Department - Ajay Pancholi - Akash Patel
Fire Fighting Squad (As per
Annex. E-I)
First aid Squad (As per
Annex. E-II)
P & A Dept.
Engineering Security Dept.
Shift In charge
Page 5
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENTAL IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 168
6.1.4 HAZARD IDENTIFICATION
Identification of hazards in the proposed project activity is of primary significance of the
analysis, and quantification. Hazard states the characteristics of system/plant/process that
presents potential for an accident. All the components of a system/plant/process need to be
thoroughly examined to assess their potential for initiating or propagating an unplanned
event/sequence of events, which can be termed as an accident.
6.1.4.1 IDENTIFICATION OF HAZARDOUS AREAS
The procedure for QRA starts with identification of major risk areas in the installation.
Operation carried out in specialty and agrochemical Industries usually come under certain
board, general categories. At M/s. DIC Fine Chemicals Pvt. Ltd., major risk areas are as
follows:
• Bulk storage area for Raw Materials at ambient temperature and atmospheric
pressure.
• Process Plant involving pumping, transportation, reactors, distillation, heating, cooling,
etc.
• Bulk loading and unloading from storage tanks to road takers and vice versa.
6.1.4.2 IDENTIFICATION OF FAILURE CASES FOR HAZARDOUS AREAS
• Release due to catastrophic failure of storage tanks or process vessels.
• Rupture of connected pipe with storage tank or process vessels.
• Continuous release at significant rates for long durations transfer pipelines caused by
sudden, major break of the pipeline.
• Continuous release at low rate through small holes or cracks in piping and vessels, flange
leaks, and leakage from pump glands and similar seals.
It is to be noted that for Quantitative Risk Assessment, worst case scenarios has been
considered, though their frequency of occurrence is much lower than the cases of small
leaks.
Page 6
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENTAL IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 169
6.1.4.3 MAJOR HAZARDOUS AREAS
The hazardous chemical storage area is shown in Figure-6.4. The major Hazardous chemicals
to be stored, transported, handled and utilized within the plot area are summarized in the
Table-6.1. Other hazards and control measures are summarized in Table-6.2. Facilities /
System for process safety, transportation, fire fighting system and emergency capabilities to
be adopted are stated below.
FIGURE-6.4
HAZARDOUS CHEMICAL STORAGE AREA
Antiskin Storage
Maleic Anhydride Storage
Para Formaldehyde Storage
Page 7
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENTAL IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 170
TABLE-6.1
STORAGE AND HANDLING DETAILS OF HAZARDOUS CHEMICALS
Sr.
No. Consumption ( Year wise )
Control
Measure
Provided
Chemicals
(Raw Materials) State
Existin
g
After
Expansi
on
Total
Means
of
Storag
e
Capacity
of
Vessel/P
ack/
Barrel
( Kg)
No.
of
Vess
els
Storage
capacity
(Tonne)
Ink Manufacturing
1 Varnish Liquid 65-
70%
No
change
65-
70% Tanks 60000 9 540
Fire detection
with sprinklers
2
Pigment
(Black/Yellow/Red/Blue/Ex
tender)
Solid 20-
32%
No
change
20-
32% Bags
20/25/400
/
500/800
-- -- Fire detection
with sprinklers
3 Alkyd Resin Liquid 2-20% No
change 2-20% Tanks 60000 3 170
Fire detection
with sprinklers
4 Wax & Additives Paste 2-10% No
change 2-10% Drums 200 -- --
Fire detection
with sprinklers
5 Vegetable oil ester Liquid 2-5% No
change 2-5% Tanks 60000 7 420 Tank farm
6 Tonner Paste 1-10% No
change 1-10% Drum 200 -- -- Tank farm
7 Antiox Liquid 0.5-2% No
change 0.5-2% Tot 1100 -- -- Tank farm
8 Wetting agent Liquid 0.2-1% No
change 0.2-1% Tot 1000 -- -- Tank farm
9 Dryer Liquid 1-4.5% No
change 1-4.5% Drum 200 -- -- Tank farm
Varnish Manufacturing
1 Gum Rosin Solid 22-
35%
No
change
30-
35% Drums 200 -- --
Fire detection
with sprinklers
2 Vegetable oil (Soya/
Linseed/ Wood) Liquid
32-
38%
No
change
42-
58% Tank 60000 -- -- Tank farm
3 Vegetable oil ester Liquid 10-
22%
No
change
10-
22% Tank 60000 -- -- Tank farm
4 Mineral Oil Liquid 16% No
change 16% Tank 60000 -- -- Tank farm
5 Catalyst
(CaO/ZNO2/MgO Solid
0.01-
0.05%
No
change
0.01-
0.05% Bags 20 -- --
Fire detection
with sprinklers
6 PTBP Solid 5-10% No
change 5-10% Bag 25 -- --
Fire detection
with sprinklers
7 Maleic acid anhydride Solid 0.3-2% No
change 0.3-2% Bag 25 -- --
Fire detection
with sprinklers
8 Formaldehyde Solid 2-5% No
change 2-5% Bag 25 -- --
Fire detection
with sprinklers
9 Pentaerytheritol Solid 2-5% No
change 2-5% Bag 25 -- --
Fire detection
with sprinklers
10 Antiox Solid 0.07-
0.21%
No
change
0.07-
0.21 Bag 15 -- --
Fire detection
with sprinklers
11 Resin Solid 2-35% No
change 2-3% Bag 25 -- --
Fire detection
with sprinklers
Page 8
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENTAL IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 171
Additive Manufacturing (wax)
1 Vegetable oil (Soya/
Linseed) Liquid NA 60-70%
60-
70% Tank -- -- -- Tank Farm
2 Wax Solid NA 28-40% 28-
40% Bags -- -- --
Fire detection
with sprinklers
3 Antiox Liquid NA 0-1% 0-1% Drums -- -- -- Fire detection
with sprinklers
Page 9
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENTAL IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 172
TABLE 6.2
OTHER HAZARDS AND CONTROL
SR.
NO.
NAME OF THE POSSIBLE
HAZARD OR
EMERGENCY
ITS SOURCES
&
REASONS
ITS EFFECTS ON
PERSONS, PROPERTY
& ENVIRONMENT
PLACE OF ITS
EFFECT
CONTROL MEASURES PROVIDED
1 BOILER
(1) Burning
(2) Physical injury
(3) Explosion
Over pressure in the boiler if
safety valve not working.
Water level indicator not
working. Low water level
indicator fail. High temp.
System fails.
Minor/Major Injury
Loss of human life
Loss of property (Loss
of Main/ Machine
Material)
Boiler House and
surrounding places
Lower & Upper Level Indication System provision. Safety valves
for pressure control fixed temp. & pressure indicator provided.
Blow down & blowing system provided for cleaning tube and
shell. Soft water used. Inter locking provided on pumps, FD fan, ID
fan. Periodical checking & inspection maintenance done. Yearly
inspection done by Boiler Inspector
2 ELECTRICITY
(1) Burning
(2) Fire
(3) Shock
Loose Contacts, Weak
earthling Short Circuit
Improper Insulation
Burning, Shock,
Death
Surrounding the
accident area
Proper Earthing, Periodical Checking of joints, proper insulations
of Equipments, etc. Flame proof fitting in solvent storage area,
bounding and jumpers to all solvent barrier lines provided.
3 HOUSE KEEPING
(1) Physical
(2) Burning
(3) Fire
(4) Chemical Exposure
Bad House keeping Physical / Chemical
Thermal Burn Injury
(Major / Minor)
In all surrounding
areas i.e. Storage,
Plants
Proper Handling, regular cleaning, Proper placement of material
(RIGHT THING AT THE RIGHT PLACE)
4 PIPE LINE LEAKAGES
Spillages etc.
(1) Corrosion
(2) Toxic gas release
Leaking of pipe line due to
corrosion, Loose contact etc.
Physical / Chemical
Thermal Burn Injury
(Major / Minor)
Plant area Proper maintenance, Proper Selection of Material for pipe lines,
Immediate attention, Earthing provided, flame proof fitting, NO
SMOKING Boards displayed.
5 Structural Failure Inside the factory (Corrosion) Injury/Death to
persons, damage to
property
Within the factory Automatic operation Periodic Testing of safety valves Regular
Inspection and Maintenance
6 Toxic Release from
outside
Outside the factory Injury/Death Within & outside
the unit
Alarm, Evacuation rescue & shelter/ Welfare
7 Natural Calamity Nature Injury / Death to
persons, damage to
property
Within & outside
the unit
Alarm, Evacuation rescue & shelter/ Welfare
Page 10
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENTAL IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 173
TABLE 6.3
HAZARDOUS PROPERTIES OF THE CHEMICALS, COMPATIBILITIES, SPECIAL HAZARD
Liquid Material Flammability Characteristics (Lab Scale – In very small quantities i.e. 2.5 Lit and stored in Flame Proof Storage Cabinets)
S. No. Chemical Appearance Flash Point (°C) Boiling Point (°C) Specific Gravity Vapor Density LEL (%) UEL (%) AIT(°C)
1.
Acetone
Appearance: Liquid.
Color: Colorless.
Clear
Closed Cup: -20°C
Open Cup: -9°C
(Cleveland)
56.2°C
0.79 (Water = 1)
2 (Air = 1)
2.6%
12.8%
465°C
2.
Diesel Oil/HSD
Physical State:
Liquid. Appearance:
Yellowish Brown
32 °C
215 - 376. °C
0.86 - 0.90 At 20
°C
Not Available
0.6%
6%
225 °C
3.
Ethyl Ether
Appearance:
Liquid. (Volatile,
Mobile Liquid )
Color: Clear
Colorless.
-45°C
34.6°C
0.7134 (Water = 1)
2.56 (Air = 1)
1.9%
36%
180°C
4.
Ethanol
Appearance: Liquid.)
Color: Clear
Colorless.
16.6°C
78°C
0.790 At 20°C
1.59
3.3%
19%
363 °C
5.
Hydrazine
Appearance: Liquid.
Color: Not
Available.
Closed Cup:
37.78°C
113.5°C
1 (Water = 1)
1.1 (Air = 1)
2.9%
98%
-
Page 11
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENTAL IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 174
S. No. Chemical Appearance Flash Point (°C) Boiling Point (°C) Specific Gravity Vapor Density LEL (%) UEL (%) AIT(°C)
6.
Potassium Hydroxide
Solutions In Ethanol
Appearance: Liquid.)
Color: Clear Colorless
Or Orange.
18°C
78°C
0.8 – 0.9
-
4%
19%
370°C
7.
Methyl Alcohol
Appearance: Liquid.
Color:
Colorless.
Closed Cup: 12°C
(53.6°F). Open
Cup: 16°C (60.8°F).
64.5°C
0.7915 (Water = 1)
1.11 (Air = 1)
6%
36.5%
464°C
8.
Gasoline/Petrol
Physical State: Liquid
Appearance: Orange,
Red
-38 To -42 °C
(Closed Cup)
30 To 215 °C
0.75-0.85 At
20 °C
3-4
1.4%
7.6%
456°C
9.
N-Heptane
Appearance:
Liquid.
Color: Clear
Colorless.
Closed Cup: -4°C
(24.8°F). (Tag)
Open Cup: -
1.1111°C (30°F).
98.4
0.6838
3.5
1.05%
6.7%
203.89°C -223
°C
10.
Phenolphthalein
Appearance: Liquid.
Color: Colorless.
Closed Cup:
12.78°C (55°F).
Open Cup: 12.78°C
78.5°C
0.8
1.59
3.3%
19%
363°C
11. Thinner Appearance: Liquid.
Color: Colorless. -4.°F - 48.°F 133.°F - 232.°F 0.829 Heavier Than Air 1.4% 12.8%
-
12.
Toluene Appearance: Liquid.
Color: Colorless.
7°C
232.°F
0.9
3.1
1.2%
7.1%
422°C
13.
Xylene
Appearance: Liquid.
Color: Colorless.
21 – 27 °C
135 - 155 °C
0.870 Kg/Dm3 At
15°C
3.7
1%
7.1 %
432 - 530 °C
Page 12
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENTAL IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 175
S. No. Chemical Appearance Flash Point (°C) Boiling Point (°C) Specific Gravity Vapor Density LEL (%) UEL (%) AIT(°C)
14.
Natural gas
Appearance:
Gas.
Color: Colorless.
Not Available
–161.5ºC
Not applicable
0.53 - 0.7
4%
16.0%
593 ºC
Powder Material Flammability Characteristics
S. No.
Chemical (Pigments)
Minimum Ignition
Energy (mJ)
LEL (%)
AIT (oC)
Pmax (bar)
Kst (bar m/sec)
1.
RED 3164-009
30<MIE<100
60<MIE<70
430
8.3+/- 10%
178+/- 10%
2.
Yellow 1128-D621
1<MIE<3
40<MIE<50
460
8.6+/- 10%
269+/- 10%
3.
SP-004 and SP-005 Cyan
1000
125
350
6.7
77
4.
Black
10000
-
-
-
-
Page 13
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENTAL IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 176
List of Some Hazardous Chemicals & Actions
S.
No
Name of Raw
Material
Hazard
Class
Flash
Point
°C
Melting
Point
°C
Reactivity
Data
Compatibility
Data First Aid
MSDS
AVAILABLE
Precautions
during Handling
1 Butyladed Hydro
toluene (BHT) 118.3 70
Stable,
instable in
excess heat
May react with
oxidizing agent
Skin Contact:
Immediately remove the
contaminated clothing
and flush with plenty of
water. Seek medical
attention
Eye Contact: Immediately
flush with plenty of water
and get medical
attention.
Inhalation: Remove to
fresh air. If not breathing
give artificial respiration.
Seek medical attention
yes
Wear Safety
goggles,
Protective
clothing, Dust
mask, Gloves,
Safety Shoes
2 Calcium Oxide 8 N.A 2572 Stable, Reacts
with water
Reactive with
organic materials,
acids, moisture
Skin Contact:
Immediately remove the
contaminated clothing
and flush with plenty of
water. Seek medical
attention
Eye Contact: Immediately
flush with plenty of water
and get medical
attention.
Inhalation: Remove to
fresh air. If not breathing
give artificial respiration.
Seek medical attention
yes
Wear Safety
goggles,
Protective
clothing, Dust
mask, Gloves,
Safety Shoes
Page 14
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENTAL IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 177
S.
No
Name of Raw
Material
Hazard
Class
Flash
Point
°C
Melting
Point
°C
Reactivity
Data
Compatibility
Data First Aid
MSDS
AVAILABLE
Precautions
during Handling
3 Gum Rosin 187 70 - 78 Stable Reactive with
oxidizing agent
Skin Contact:
Immediately remove the
contaminated clothing
and flush with plenty of
water. Seek medical
attention
Eye Contact: Immediately
flush with plenty of water
and get medical
attention.
Inhalation: Remove to
fresh air. If not breathing
give artificial respiration.
Seek medical attention
yes
Wear Safety
goggles,
Protective
clothing, Dust
mask, Gloves,
Safety Shoes
4 Magnesium Oxide 2800
Stable,
Hygroscopic,
Air sensitive
Reactive with
oxidizing agent,
acids
Skin Contact:
Immediately remove the
contaminated clothing
and flush with plenty of
water. Seek medical
attention
Eye Contact: Immediately
flush with plenty of water
and get medical
attention.
Inhalation: Remove to
fresh air. If not breathing
give artificial respiration.
Seek medical attention
yes
Wear Safety
goggles,
Protective
clothing, Dust
mask, Gloves,
Safety Shoes
Page 15
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENTAL IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 178
S.
No
Name of Raw
Material
Hazard
Class
Flash
Point
°C
Melting
Point
°C
Reactivity
Data
Compatibility
Data First Aid
MSDS
AVAILABLE
Precautions
during Handling
5 Maleic Acid
Anhydrous 103.33 52.8
Stable, May
decompose
on exposure
to moist air
or water
Reactive with
oxidizing agent,
acids, metals,
reducing agent
Skin Contact:
Immediately remove the
contaminated clothing
and flush with plenty of
water. Seek medical
attention
Eye Contact: Immediately
flush with plenty of water
and get medical
attention.
Inhalation: Remove to
fresh air. If not breathing
give artificial respiration.
Seek medical attention
yes
Wear Safety
goggles,
Protective
clothing, Dust
mask, Gloves,
Safety Shoes
6 Para Formaldehyde
92 % & 96 % 4.1 70 120 - 170 Stable
Reactive with
oxidizing agent,
acids, metals,
reducing agent
Skin Contact:
Immediately remove the
contaminated clothing
and flush with plenty of
water. Seek medical
attention
Eye Contact: Immediately
flush with plenty of water
and get medical
attention.
Inhalation: Remove to
fresh air. If not breathing
give artificial respiration.
Seek medical attention
yes
Wear Safety
goggles,
Protective
clothing, Dust
mask, Gloves,
Safety Shoes
Page 16
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENTAL IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 179
S.
No
Name of Raw
Material
Hazard
Class
Flash
Point
°C
Melting
Point
°C
Reactivity
Data
Compatibility
Data First Aid
MSDS
AVAILABLE
Precautions
during Handling
7 Para Tertiary Butyl
Phenol (PTBP) 9 118 99
Avoid
ignitious
source
May react with
strong oxidizing
agent
Skin Contact:
Immediately remove the
contaminated clothing
and flush with plenty of
water. Seek medical
attention
Eye Contact: Immediately
flush with plenty of water
and get medical
attention.
Inhalation: Remove to
fresh air. If not breathing
give artificial respiration.
Seek medical attention
yes
Wear Safety
goggles,
Protective
clothing, Dust
mask, Gloves,
Safety Shoes
8 Pentaerythritol 96
%
N.A 260 Stable Not Available
Skin Contact:
Immediately remove the
contaminated clothing
and flush with plenty of
water. Seek medical
attention
Eye Contact: Immediately
flush with plenty of water
and get medical
attention.
Inhalation: Remove to
fresh air. If not breathing
give artificial respiration.
Seek medical attention
yes
Wear Safety
goggles,
Protective
clothing, Dust
mask, Gloves,
Safety Shoes
Page 17
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENTAL IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 180
S.
No
Name of Raw
Material
Hazard
Class
Flash
Point
°C
Melting
Point
°C
Reactivity
Data
Compatibility
Data First Aid
MSDS
AVAILABLE
Precautions
during Handling
9
Pigment:
Black
Blue
Red
Yellow
80 -120 70 - 90
Skin Contact:
Immediately remove the
contaminated clothing
and flush with plenty of
water. Seek medical
attention
Eye Contact: Immediately
flush with plenty of water
and get medical
attention.
Inhalation: Remove to
fresh air. If not breathing
give artificial respiration.
Seek medical attention
yes
Wear Safety
goggles,
Protective
clothing, Dust
mask, Gloves,
Safety Shoes
Page 18
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENTAL IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 181
Scenario based Emergency Actions
Based on the reactions involved during the production process and the raw material involved the possible hazards are identified. The action for the emergency situation is
given.
Emergency Situations can cause Occupational Health hazards and Handling Procedure (ESHP)
S. No Name of process
/equipment Type of emergency
Possible Cause for
emergency
Effect of emergency on
process Action after emergency Responsibility
Stoppage of all utility and
agitation of the reactor
Utility dept for giving service
in less time
1.Electric Stoppage Electric main supply cut off Pressure can increase over
specified limit
Keep the pressure lower
than specified limit of 0.35
Mpa if pressure is increasing
above the limit, depressurize
through packed column by
opening manual valve
carefully
Leader/Operator who are
available on place.
1. Motor problem cool the reaction mass by
operating cooling system
2.Seal problem
If not controlled the foam,
slowly depressurize through
manually valve to reduce
pressure 2. Stop of agitation
3.Breakdown in assembly
Foaming in reactor
Try to keep pressure 0.35
Mpa
Operator
3.Stopage of cooling system
Electric main supply cut off
/Breakdown ,leakage in
system
Over pressure
/uncontrolled pressure
,Electrical cut off.
Try to keep the pressure
below 0.35 Mpa and get
electricity on regular with in
less time
Operator
1 Pressurized
reaction process
4. Leakage from agitator
axial seal Miss alignment
Fuming /smell of
formaldehyde as pungent
smell and eye irritation
Put on Air /Gas Mask Operator
Page 19
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 182
PRECAUTIONS DURING STORAGE AND TRANSPORTATION OF HAZARDOUS CHEMICALS
LIQUIDS
• Always use the road tankers having authorization for transporting the said liquids.
• Vendor will be asked to provide MSDS to Tanker Driver.
• Tankers will have clearly marked identification of material being contained with mentioning
Safety Card.
• Driver to have concerned Safety Officer’s contact details to contact him in case of
emergency.
• Provide muffler on exhaust while entering tanker within premises.
• Ensure Earthing Boss connection before starting any transferring.
• SOP to cover routine checking of Tank farm area to be carried out for checking any spillage /
leakage.
• Tanks will be inspected physically daily for having any visual abnormality.
• Readings of Temperature & Pressure will be noted, recorded & reported immediately for
abnormality.
• Safety instruments like rupture disc, safety valves will be checked at defined duration for
intakeness.
• Scheduled testing of tanks to be done for thickness testing.
• Tanks to be painted on regular interval defined as per laws to protect them from
atmospheric corrosion.
• Barrels to be checked for proper fixing of bungs before sending it outside the premises.
• Barrels to be monitored physically daily for developing any pressure or vacuum within it on
long storage.
• Concerned persons will be trained properly to use spill kit in case of observing any spillage
inside warehouse.
SOLIDS
• Vendor will be asked to provide MSDS to Truck Driver.
Page 20
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 183
• Driver to have concerned Safety Officer’s contact details to contact him in case of
emergency.
• Provide muffler on exhaust while entering truck within premises.
• SOP to cover routine checking of Bags & Containers for checking any damage.
• Containers to be tested for safe racking & transportation.
• Proper PPE to be used while handling the material & concerned persons to be trained for
usage of the same.
• Concerned persons will be trained properly to use spill kit in case of observing any spillage
inside warehouse.
The major hazards in the M/s. DIC Fine Chemicals Pvt. Ltd. are described below.
• Toxic/Corrosive hazards due to leakage of hazardous chemicals from storage tank or
carboys.
• Electrical hazards due to the electrical major equipment/ machinery, operations, welding,
motors, and heavy lift devices, cabling, human intervention (short circuit possibility),
maintenance work (due to machinery breakdown etc.), plant lighting related electrical
hazards.
• Possibility of human injury due to working with mechanical machines, manual handling etc.
• Possibility of injury during chemicals handled, during operations and due to intoxication.
• Major dropped objects hazard due to large number of physical handling steps / operations
involved with overhead lifting/ hoisting equipment.
• Fires in any part of the plant working areas – there is a possibility of rapid escalation if it is
not brought under control quickly.
• Possibilities of fire hazards at transformers, switchgear and other electrical equipment etc.
Page 21
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 184
6.1.4.4 TRANSPORTATION, UNLOADING AND HANDLING PROCEDURE FOR HAZARDOUS
CHEMICALS
Transportation, Unloading and Handling Procedure
SR.
NO.
ACTIVITY TYPE OF POSSIBLE
HAZARD
MITIGATION MEASURES
Leakage& Spillage
• Check the source of leakage point.
• Do not touch damaged containers or spilled material
unless wearing appropriate protective clothing.
• Stop leak if you can do it without risk.
Fire,& explosion • Use water spray to reduce vapors; do not put water
directly on leak, spill area or inside container.
• Keep combustibles (wood, paper, oil, etc.) away from
spilled material.
1 Transportation of Solvents by
road tanker
Toxic release • Isolate the area
• Isolate the container
• Training will be provided to driver and cleaner
regarding the safe driving, hazard of Flammable
chemicals, emergency handling.
• TREM card will kept with TL.
• Fire extinguishers will be kept with TL.
• Flame arrestor will be provided to TL exhaust.
• Instructions will be given not to stop road tanker in
populated area.
• Clear Hazard Identification symbol and emergency
telephone number will be displayed as per HAZCHEM
CODE.
• Appropriate PPEs will be kept with TL.
2 Road tanker unloading at
project site.
Leakage& Spillage
• Check the source of leakage point.
• Do not touch damaged containers or spilled material
unless wearing appropriate protective clothing.
• Stop leak if you can do it without risk.
Fire,& explosion • Use water spray to reduce vapors; do not put water
directly on leak, spill area or inside container.
• Keep combustibles (wood, paper, oil, etc.) away from
spilled material.
Toxic release • Isolate the area
• Isolate the container
• Check the source of leakage point.
• Isolate the area
• Isolate the container
• Spray the water on leakage
• Priority will be given to Tanker to immediately enter the
storage premises at site and will not be kept waiting
near the gate or the main road.
• Security person will check License, TREM CARD, Fire
extinguisher condition; required PPEs as per SOP laid
down.
• Store officer will take sample as per sampling SOP from
sampling point.
Page 22
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 185
• After approval of QC department unloading procedure
will be allowed be started.
Following precautions will be adopted during unloading
• Wheel stopper will be provided to TL at unloading
platform.
• Static earthing will be provided to road tanker.
• Tanker unloading procedure will be followed according
to check list and implemented.
• Flexible SS hose connection will be done at TL outlet
line.
• The quantity remaining in the hose pipeline will be
drained to a small underground storage tank, which will
be subsequently transferred by nitrogen pressure to the
main storage tank thus ensuring complete closed
conditions for transfer from road tanker.
• All TL valves will be closed in TL.
• Finally earthing connection and wheel stopper will be
removed.
• Only day time unloading will be permitted.
Leakage& Spillage • Check the source of leakage point.
• Do not touch damaged containers or spilled material
unless wearing appropriate protective clothing.
• Stop leak if you can do it without risk.
Fire, Explosion • Use water spray to reduce vapors; do not put water
directly on leak, spill area or inside container.
• Keep combustibles (wood, paper, oil, etc.) away from
spilled material.
3 Storage tank safety
Toxic release. • Isolate the area
• Isolate the container
• Check the source of leakage point.
• Isolate the area
• Isolate the container
• Spray the water on leakage
• storage tank will be provided as per IS code.
• Dyke wall will be provided to storage tank.
• Level transmitter will be provided with low level high
level auto cut-off provision.
• Flame arrester and breather valve will be provided to
vent line.
• Fire hydrant monitor with foam attachment facility will
be provided.
• FLP type pump will be provided.
• Nitrogen blanketing will be provided to storage tank.
• Double static earthing will be provided to storage tank.
• Double Jumper clip will be provided to all Solvent
handling pipeline flanges.
4 Solvent transfer from storage
tank to Day tank
Leakage& Spillage due to
Line rupture, Flange
Gasket failure, Fire,
Explosion, Toxic release.
• Double mechanical seal type FLP type pump will be
provided.
• Double on / off switch will provided at tank farm and
process area near day tank. Pump auto cut off with day
Page 23
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 186
tank high level will be provided.
• Flame arrestor will be provided on day tank vent.
• Over flow will be provided for additional safety and it
will be connected to main storage tank.
• NRV will be provided on pump discharge line.
• Double Jumper clip will be provided to all solvent
handling pipeline.
• Double static earthing will be provided to day tank.
5 Solvent transfer from Day
tank to reactor.
Leakage, Spillage due to
Line rupture, Flange
Gasket failure, Fire,
Explosion, Toxic release.
• Gravity transfer.
• Total quantity of day tank material will be charged in to
reactor at a time.
• Static earthing will be provided to storage tank.
• Double Jumpers will be provided to pipeline flanges.
6.1.5 CONSEQUENCE ANALYSIS
In a plant handling hazardous chemicals, the main hazard arises due to storage, handling & use
of these chemicals. If these chemicals are released into the atmosphere, they may cause
damage due to resulting fires or vapour clouds. Blast Overpressures depend upon the reactivity
class of material between two explosive limits.
Operating Parameters
Potential vapour release for the same material depends significantly on the operating
conditions. Especially for any liquefied gas, the operating conditions are very critical to assess
the damage potential. If we take up an example of ammonia, if it is stored at ambient
temperature, say 30oC, and then the vapour release potential of the inventory is much higher as
compared to the case if it is stored at 0oC.
Inventory
Inventory Analysis is commonly used in understanding the relative hazards and short listing of
release scenarios. Inventory plays an important role in regard to the potential hazard. Larger
the inventory of a vessel or a system, larger the quantity of potential release. The potential
vapour release (source strength) depends upon the quantity of liquid release, the properties of
the materials and the operating conditions (pressure, temperature). If all these influencing
parameters are combined into a matrix and vapour source strength estimated for each release
case, a ranking should become a credible exercise.
Page 24
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 187
Loss of Containment
Plant inventory can get discharged to Environment due to Loss of Containment. Certain
features of materials to be handled at the plant need to the clearly understood to firstly list out
all significant release cases and then to short list release scenarios for a detailed examination.
Liquid release can be either instantaneous or continuous. Failure of a vessel leading to an
instantaneous outflow assumes the sudden appearance of such a major crack that practically all
of the contents above the crack shall be released in a very short time. The more likely event is
the case of liquid release from a hole in a pipe connected to the vessel. The flow rate is
depending on the size of the hole as well as on the pressure, which was present, in front of the
hole, prior to the accident. Such pressure is basically dependent on the pressure in the vessel.
The vaporisation of released liquid depends on the vapour pressure and weather conditions.
Such consideration and others have been kept in mind both during the initial listing as well as
during the short listing procedure. In the study, Maximum Credible Loss accident methodology
is to be used, therefore, the largest potential hazard inventories have been considered for
consequence estimation.
6.1.5.1 DAMAGE CRITERIA
Hazard Identification and Consequence Analysis
Background
Key issues in Risk Assessment (RA) of the Ink Plant Manufacturing Unit (M/s DIC Fine Chemicals
Pvt. Ltd.,) i.e. Category 5 (f) of the Schedule to the EIA Notification dated Sept. 14, 2006
(amended till date), for proposed regularize / Amendment of existing EC by addition of Wax &
Additives. The risk assessment process is intended to identify existing and probable hazards in
the work environment and all operations, to quantify the hazards and to assess the risk levels of
those hazards in order to prioritize those that need an immediate attention.
In the unlikely event that an abnormal consequence has occurred, the disaster management
kicks in. This includes prescribing the procedures pertaining to a number of issues such as
Page 25
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 188
communication, encounter, rescue, rehabilitation and further steps to prevent recurrence of
such consequence in future. These issues are addressed in the disaster management plan.
Both, the RA and DMP are living documents and need to be updated whenever there are
changes in operations, equipment or procedures.
Key Definitions
The terminologies used in this Risk Assessment (RA) study are defined below.
Consequence: Magnitude or size of the damage or loss. In terms of health and safety, it is the
degree of harm that could be caused to the people exposed to hazard, the potential severity of
injuries or ill health, and/or the number of people who could be potentially affected.
Consequence of hazard need not only be in terms of human safety criteria, but could also be in
terms of a financial loss due to production and incurred costs due to repairs/replacement,
environmental impacts as well as public outrage.
Disaster: A catastrophic consequence of a major emergency/accident that leads to not only
extensive damage to life and property, but also disrupts all normal human activity for a
significant period of time and requires a major national and/or international effort for rescue
and rehabilitation of those affected.
Emergency: A situation of process deviation that, if uncontrolled, may lead to a major
accident/disaster with potential short term and/or long term risk damage consequence to life
and property in and/or around the workplace.
Emergency Response Planning Guidelines 1 (ERPG 1): The maximum airborne concentration
below which it is believed that nearly all individuals could be exposed for up to 1 hour (without
a respirator) without experiencing other than mild transient adverse health effects or without
perceiving a clearly defined objectionable odour.
Emergency Response Planning Guidelines 2 (ERPG 2): The maximum airborne concentration
below which it is believed that nearly all individuals could be exposed for up to 1 hour without
experiencing or developing irreversible or other serious health effects or symptoms that could
impair their abilities to take protective action.
Page 26
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 189
Emergency Response Planning Guidelines 3 (ERPG 3): The maximum airborne concentration
below which it is believed nearly all individuals could be exposed for up to 1 hour without
experiencing or developing life-threatening health effects.
Hazard: Source of potential harm, injury or loss to man and machines.
Immediately Dangerous to life and health (IDLH): It represents the maximum concentration of
a chemical from which, in the event of respiratory failure, one could escape within 30 minutes
without a respirator and without experiencing any escape/impairing (e.g. severe irritation) or
irreversible health effects.
Lethal Concentration Low (LCLo): It is the lowest concentration of a material in air, other that
LC50, which has been reported to cause death in human or animals.
Risk: Combination of the likelihood of a specific unwanted event and the potential
consequences, if it occurs.
Risk Assessment: A process that involves estimation and measurement of risk to determine
priorities and to enable identification of appropriate level of risk treatment (used also to
describe the overall process of risk management).
Risk Control: Implementation of strategies to prevent, control and minimize hazards.
Risk Management: Overall description of the steps taken to manage risk, by identifying hazards
and implementing controls in the workplace.
Risk Rating: The category, level, or risk assigned following risk assessment (e.g. High, Medium,
or Low).
Threshold Limit Value (TLV): it is the permitted level of exposure for a given period on a
weighted average basis (usually 8 hrs for 5 days in a week).
Short Time Exposure Limit (STEL): it is the permitted short-term exposure limit usually for a 15
minutes exposure.
Toxic Concentration Low (TCLo): It is the lowest concentration of a material in air, to which
humans or animals have been exposed for any given period of time that has produced an toxic
effects in humans or produced carcinogenic, neoplastigenic or tetratogenic effect in humans or
animals.
Page 27
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 190
Methodology for Risk Assessment
Toxic, flammable and explosive substances released from sources of storage as a result of
failures or catastrophes, can cause losses in the surrounding area in the form of:
• Toxic gas dispersion, resulting in toxic levels in ambient air,
• Fires, fireballs, and flash back fires, resulting in a heat wave (radiation), or
• Explosions (Vapour Cloud Explosions) resulting in blast waves (overpressure).
The scope of work includes site inspection, hazard identification, selection of potential loss
scenarios, and simulation of release source model on DNV’s PHAST Professional 6.54,
consequence analysis and plotting of Damage contour on site map in order to take strategic
decision to mitigate/minimize the level of risk to the facility and to the community. The steps
undertaken to carry out Risk Assessment for the proposed increased capacity are described in
subsequent sections.
MCLS Development Techniques
As a first step towards risk assessment is to identify the possible release scenarios based on
available information about scenario development for Maximum Credible Loss Scenarios
(MCLS).
Basis for Selecting the Material to be studied for Consequence Assessment Following points are
considered while selecting the release scenarios:
• Flammability and the flash point of the material
• Phase of the material i.e. liquid or gas
• Threshold quantity of the chemical as prescribed in MSHIC Rule
• Operating Temperature and Pressure of the material
• Total inventory of the material
MCLS’ Selected from Vessel Source
MCLS’ selected are based on the types of failures discussed in publication World Bank Technical
Paper 55, and TNO purple Book.
Page 28
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 191
Failure Rates
A leak or rupture of the tank / pipe, releasing some or all of its contents, can be caused by
brittle failure of the tank walls, welds or connected pipe work due to use of inadequate
materials, combined with loading such as wind, earthquake or impact. The failure rates are the
deciding factor for selecting the MCLS’. The failure rates for selected MCLS’ are given in below
table:
Failure Frequencies for Storage Tanks
Categories
Catastrophic Rupture
Frequency
(per tank per year)
Leak Frequency (per year)
Atmospheric Storage
Tank 3.0 × 10-6 2.8× 10-3
1.2 × 10-5 (for Hole Size 3 to 10 mm) Pressure Vessels 4.7 × 10-7
7.1 × 10-6 (for Hole Size 10 to 50 mm)
Reference: International Association of Oil & Gas Producers (OGP); Report No. 434-3, March
2010
Failure Frequencies for Pipe work
Failure Rates (per meter per year) for Pipe work diameter (mm) Leak Size
0 - 49 50 - 149 150 - 299 300 - 499 500 - 1000
3 mm dia 1 ×10-5 2 ×10-6
4 mm dia 1 ×10-6 8 ×10-7 7 ×10-7
25 mm dia 5 ×10-6 1 ×10-6 7 ×10-7 5 ×10-7 4 ×10-7
1/3 Pipe work
dia 4 ×10-7 2 ×10-7 1 ×10-7
Guillotine /
Full Bore
Rupture
1 ×10-6 5 ×10-7 2 ×10-7 7 ×10-8 4 ×10-8
Reference: Health & Safety Executive, UK
Hazardous Event Classification
Hazards that can lead to accidents in operations due to MCLS’ are discussed in this section.
Important hazardous events are classified as follows:
Event Classification
Type of Event Explanation
BLEVE
Boiling Liquid Evaporating Vapor Explosion; may happen due to
catastrophic failure of refrigerated or pressurized gases or liquids stored
above their boiling points, followed by early ignition of the same, typically
leading to a fire ball
Page 29
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 192
Type of Event Explanation
Deflagration Is the same as detonation but with reaction occurring at less than sonic
velocity and initiation of the reaction at lower energy levels
Detonation
A propagating chemical reaction of a substance in which the reaction front
advances in the un-reacted substance at or greater than sonic velocity in
the unreacted material
Explosion A release of large amount of energy that form a blast wave
Fire Fire
Fireball
The burning of a flammable gas cloud on being immediately ignited at the
edge before forming a flammable/explosive mixture.
Flash Fire A flammable gas release gets ignited at the farthest edge resulting in flash-
back fire
Jet Fire
A jet fire occurs when flammable gas releases from the pipeline (or hole)
and the released gas ignites immediately. Damage distance depends on
the operating pressure and the diameter of the hole or opening flow rate.
Pool Fire
Pool fire is a turbulent diffusion fire burning above a horizontal pool of
vaporizing hydrocarbon fuel where the fuel has zero or low initial
momentum
Spill Release
‘Loss of containment’. Release of fluid or gas to the surroundings from
unit’s own equipment / tanks causing (potential) pollution and / or risk of
explosion and / or fire
Structural Damage Breakage or fatigue failures (mostly failures caused by weather but not
necessarily) of structural support and direct structural failures
Vapor Cloud
Explosion
Explosion resulting from vapor clouds formed from flashing liquids or non-
flashing liquids and gases
Consequences of Hazardous Event due to Release of Material into Environment
Consequences of Fire/Heat Wave
The effect of thermal radiation on people is mainly a function of intensity of radiation and
exposure time. The effect is expressed in term of the probability of death and different degree
of burn. The consequence effects studied to assess the impact of the events on the receptors
are:
Page 30
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 193
Damage due to Radiation Intensity
Radiation
(kW/m2)
Damage to Equipment Damage to People
1.2 Solar heat at noon
1.6 - Minimum level of pain threshold
2.0 PVC insulated cable
damage
4.0 - Causes pain if duration is longer than 20 sec.
But blistering is unlikely.
6.4 - Pain threshold reached after 8 sec. Second
degree burns after 20 sec.
12.5
Minimum energy to ignite
wood with a flame; melts
plastic tubing.
1% lethality in one minute. First degree burns
in 10 sec.
16.0 - Severe burns after 5 sec.
25.0
Minimum energy to ignite
wood at identifying long
exposure without a flame.
100% lethality in 1 min. Significant injury in 10
sec.
37.5 Severe damage to plant
100% lethality in 1 min.
50% lethality in 20 sec.
1% lethality in 10 sec.
Consequences of Overpressure
The effects of the shock wave vary depending on the characteristics of the material, the
quantity involved and the degree of confinement of the vapor cloud. The peak pressures in an
explosion therefore vary between a slight over-pressure and a few hundred kilopascals (kPa).
Direct injury to people occurs at pressures of 5-10 (5E-5 to E-4) kPa (with loss of life generally
occurring at a greater over-pressure), whereas dwellings are demolished and windows and
doors broken at pressures of as low as 3-10 kPa. The pressure of the shock wave decreases
rapidly with the increase in distance from the source of the explosion.
Overpressure Damage
Overpressure
(bar) Damage
0.001
0.002
0.003
Annoying noise (137 dB if of low frequency 10-15 Hz)
Loud noise (143 dB, sonic boom glass failure
Occasional breaking of large glass windows already under strain
0.007 Breakage of small windows under strain
Page 31
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 194
Overpressure
(bar) Damage
0.010
0.020
Typical pressure for glass breakage
projectile limit; some damage to house ceilings; 10% window glass
broken
0.027 Limited minor structural damage
0.034
0.034 to 0.068
Large and small windows usually shattered; occasional damage to
window frames
0.048
0.068
0.068 to 0.136
Minor damage to house structures
Partial demolition of houses, made uninhabitable
Corrugated asbestos shattered; corrugated steel or aluminum
panels, fastenings fail, followed by buckling, wood panels (standard
housing) fastenings fail, panels blown in
0.088
0.136
0.136 to 0.204
Steel frame of clad building slightly distorted
Partial collapse of walls and roofs of houses
Concrete of cinder brick walls, not reinforced, shattered
0.157 Lower limit of serious structural damage
0.170
0.204
0.204 to 0.272
50% destruction of brickwork of houses
Heavy machines (3,000 lb) in industrial building suffered little damage;
steel frame building distorted and pulled away from foundations.
Frameless, self -framing steel panel building demolished; rupture of oil
storage tanks
0.272
0.340
Cladding of light industrial buildings ruptured
Wooden utility poles snapped; tall hydraulic press (40,000 lb) in building
slightly damaged
0.340 to 0.476
0.476
Nearly complete destruction of houses
Loaded train wagons overturned
0.476 to 0.544
0.612
0.680
20.414
Brick panels, 8-12 inches thick, not reinforced; heavy machine tools
(7,000 lb) moved and badly
Loaded trains boxcars completely demolished
Probable total destruction of buildings; heavy machines tools (7,000 lb)
moved and badly damaged, very heavy machines tools (12,000 lb)
survived.
Limit of crater lip
Source: CCPS Consequence analysis of chemical release
Consequences of Toxic Release
The effect of exposure to toxic substance depends upon the duration of exposure and the
concentration of the toxic substance. Short-term exposures to high concentration give Acute
Page 32
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 195
Effects while long term exposures to low concentrations result in Chronic Effects. Only acute
effects are considered under hazard analysis. These effects are:
• Irritation (respiratory system skin, eyes)
• Narcosis (nervous system)
• Asphyxiation (oxygen deficiency)
• System damage (blood organs)
Wind Direction at Site
Predominant wind direction of the study area is shown as follows:
Predominant Wind Direction
1st
Predominant 2nd
Predominant 3rd
Predominant
Time Direction
Percent No.
of days in a
year
Direction
Percent No.
of days in a
year
Direction
Percent No.
of days in a
year
Day Time SW 40 NE 19 SE 11
Night
Time SW 45 NE 19 NW 13
6.1.5.2 MAXIMUM CREDIBLE LOSS ACCIDENT SCENARIOS
A Maximum Credible Accident (MCA) can be characterised as the worst credible accident. In
other words: an accident in an activity, resulting in the maximum consequence distance that is
still believed to be possible. A MCA-analysis does not include a quantification of the probability
of occurrence of the accident. Another aspect, in which the pessimistic approach of MCA
studies appears, is the atmospheric condition that is used for dispersion calculations. As per the
reference of the study, weather conditions having an average wind speed of 1.40 m/s have
been chosen.
The Maximum Credible Loss (MCL) scenarios have been developed for the Facility. The MCL
cases considered, attempt to include the worst “Credible” incidents- what constitutes a credible
incident is always subjective. Nevertheless, guidelines have evolved over the years and based
on basic engineering judgement, the cases have been found to be credible and modelling for
Page 33
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 196
assessing vulnerability zones is prepared accordingly. Only catastrophic cases have been
considered and not partial or small failures (as is the case in Quantitative Risk Assessment
where contributions from low frequency - high outcome effect as well as high frequency - low
outcome events are distinguished). The objective of the study is emergency planning, hence
only holistic & conservative assumptions are used for obvious reasons. Hence though the
outcomes may look pessimistic, the planning for emergency concept should be borne in mind
whilst interpreting the results.
6.1.5.2.1 CONSEQUENCE ANALYSIS CALCULATIONS
The Consequence Analysis has been done for selected scenarios. This has been done for
weather conditions having wind speed 1.40 m/s. In Consequence Analysis, geographical
location of the source of potential release plays an important role. Consideration of a large
number of scenarios in the same geographical location serves little purpose if the dominant
scenario has been identified and duly considered.
6.1.5.2.2 SOFTWARE USED FOR CALCULATIONS
PHAST MICRO: Phast is the most comprehensive software available for performing Process
Hazard Analysis (PHA), Quantitative Risk Assessment (QRA) and Financial Risk Analysis (FRA).
Our extensively validated software for consequence and risk assessment is used by
governments and industry helping them to comply with local safety regulation and their own
corporate best practice. Phast contains all the discharge, dispersion, effects and risk models you
will need to accurately assess all your major hazards and associated risks. Phast Consequence
provides you with comprehensive hazard analysis facilities to examine the progress of a
potential incident from the initial release to its far-field effects.
TOXIC AND FLAMMABLE IMPACT
It calculates the initial discharge, as the material expands from its storage conditions to
atmospheric, through dispersion, as the material mixes with air and dilutes, and the
Page 34
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 197
subsequent toxic or flammable effects. Phast includes a wide range of models for discharge
and dispersion as well as flammable, explosive and toxic effects.
DISCHARGE
• Phast requires basic information about storage or process conditions and material
properties in order to perform discharge calculations
• The software comes with an integrated material property database containing more
than 1,600 pre-defined pure component chemicals
• Various discharge scenario options have been implemented to represent common
process failures, and model their behaviour. These include:
� Leaks and line ruptures from long & short pipelines
� Catastrophic ruptures
� Relief valve and disc ruptures
� Tank roof collapse
� Vent from vapour spaces
� In building release effects
DISPERSION
The dispersion models within Phast are able to model the following phenomena
• Dispersion of gas, liquid and two-phase releases
• Liquid droplet thermo dynamics calculations and liquid droplet rainout
• Pool spreading and vaporization
• Building wake dispersion effects for vapour releases
FLAMMABLE EFFECTS
For releases of flammable material Phast calculates
• Radiation profiles and contours from a range of fire scenarios including pool fires, flash
fires, jet fires and fire balls, including cross-wind effects on a jet fire
Page 35
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 198
• Vapour Cloud Explosion modeling using industry standards models including the TNO
Multi-energy, Baker Strehlow Tang and TNT Equivalence models
• Overpressure contours from Boiling Liquid Expanding Vapour Explosions
TOXIC EFFECTS
• Graphs of toxic concentration profile
• Indoor and outdoor toxic dose prediction
• Reporting of distance to specific dose and concentration
• Calculated exposure time and use as “averaging time” for passive dispersion effects
PHAST RISK
Phast Risk allows you to combine the flammable and toxic consequences from each scenario in
your QRA model with their likelihood to quantify the risk of fatalities. Phast Risk allows you to
take account of local population distribution, sources of ignition, land usage and local
prevailing weather conditions. It is designed to perform all the analysis, data handling and
results presentation elements of a QRA within a structured framework.
Phast Risk allows you to quickly identify major risk contributors so that time and efforts can be
directed to mitigating these highest risk activities. Based on effects calculations and population
vulnerabilities, Phast Risk can integrate over all scenarios and weather conditions to estimate
the total risk. The established individual and societal risk indicators are predicted by Phast Risk
across your facility and surrounding area using the classical QRA methodology. Risk ranking
reports can be produced at points of strategic importance to show the relative influence of the
various failure scenarios and their contribution to both the individual and societal risk metrics.
A key benefit of Phast Risk is the ability to identify major risk contributors and differentiate
these from incidents with worst case consequences which might otherwise dominate the
safety reviews. Whilst medium scale incidents have lesser consequences, they may have a
higher frequency, which, when combined with their hazardous effects, generate a higher level
Page 36
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 199
of risk. Time and effort directed to mitigating high consequence but often low frequency
events may not be well spent. Phast Risk helps you direct this effort more effectively.
Phast Risk also provides facilities to help you manage large quantities of input data, including
scenarios, parameters, wind roses, ignition and population, and combine these in many ways.
This is critical when looking at sensitivity analyses and assessing the merits of a range of risk
reduction measures.
Benefits
• Facilitates cost reduction in terms of losses and insurance
• Allows optimization of plant and process design
• Assist in compliance with safety regulators
• Enables quicker response to hazardous incidents
• Improve engineer’s understanding of potential hazards
• Regular software upgrades incorporate industry experience and expertise, and
advances in consequence modeling technology
6.1.5.2.3 SCENARIOS
TABLE – 6.4
POSSIBLE ACCIDENT SCENARIOS
Scenario MCL Scenario Pressure & Temp. Quantity
1 10 mm Leak of Antiskin NTP 4 KL
2 Catastrophic Rupture of Antiskin NTP 4 KL
3 Catastrophic Rupture of Para Formaldehyde NTP 10 Tonne
4 Catastrophic Rupture of Maleic Anhydride NTP 20 Tonne
Page 37
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 200
ANTISKIN STORAGE AREA
All anti skin barrel been stored in close air conditioner container with specified temperature
range given is 30 °C, in case of high temperature or malfunctioning of the system hooter is
provided for indication purpose.
Page 38
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 201
Scenario#1: 10 mm Leak of Antiskin
This scenario considers 10 mm Leak of Antiskin:
Results indicate:
10 mm Leak
Input Data
Stored quantity - 4 KL
Results indicate
Pool Fire Scenario
Radiation Level
(KW/m2)
Distance in meter
Effect if IHR at Height of simulation
Early Pool Fire
1.5 F 1.5 D 5 D
4 12.92 12.82 14.85
This level is sufficient to cause personnel if unable to reach
cover within 20s; however blistering of the skin (second degree
burn) is likely; 0: lethality
12.5 8.64 8.54 11.10
This level will cause extreme pain within 20 seconds and
movement to a safer place is instinctive. This level indicates
around 6% fatality for 20 seconds exposure.
37.5 4.49 4.40 6.54 This level of radiation is assumed to give 100% fatality as
outlined above.
Late Pool Fire
1.5 F 1.5 D 5 D
4 39.12 39.01 45.39
This level is sufficient to cause personnel if unable to reach
cover within 20s; however blistering of the skin (second degree
burn) is likely; 0: lethality
12.5 18.63 18.53 26.08
This level will cause extreme pain within 20 seconds and
movement to a safer place is instinctive. This level indicates
around 6% fatality for 20 seconds exposure.
37.5 9.79 9.69 11.00 This level of radiation is assumed to give 100% fatality as
outlined above.
Jet Fire
1.5 F 1.5 D 5 D
4 - - 0.85
This level is sufficient to cause personnel if unable to reach
cover within 20s; however blistering of the skin (second degree
burn) is likely; 0: lethality
Maximum Pool Radius – 6.753 m
Pool Diameter – 1.63 m
Late Pool Fire Diameter – 13.51 m
Page 39
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 202
Antiskin (10 mm Leak)
Page 40
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 203
Page 41
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 204
Page 42
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 205
Page 43
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 206
Early Pool Fire Ellipse
Late Pool Fire Ellipse
Green – 4 KW/m2
Yellow – 12.5 KW/m2
Red – 37.5 KW/m2
Page 44
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 207
Scenario#2: Catastrophic Rupture of Antiskin
This scenario considers Catastrophic Rupture of Antiskin:
Results indicate:
Catastrophic Rupture
Input Data
Stored quantity - 4 KL
Results indicate
Pool Fire Scenario
Radiation
Level
(KW/m2)
Distance in meter Effect if IHR at Height of simulation
Late Pool Fire
1.5 F 1.5 D 5 D
4 50.16 50.16 64.22
This level is sufficient to cause personnel if unable to reach
cover within 20s; however blistering of the skin (second degree
burn) is likely; 0: lethality
12.5 18.23 18.23 21.28
This level will cause extreme pain within 20 seconds and
movement to a safer place is instinctive. This level indicates
around 6% fatality for 20 seconds exposure.
Maximum Pool Radius – 15.91 m
Pool Diameter – 31.83 m
Page 45
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 208
Catastrophic Rupture
Page 46
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 209
Page 47
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 210
Late Pool Fire Ellipse
Green – 4 KW/m2
Yellow – 12.5 KW/m2
Page 48
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 211
Scenario#3: Catastrophic Rupture of Para Formaldehyde
This scenario considers Catastrophic Rupture of Para Formaldehyde:
Results indicate:
Catastrophic Rupture
Input Data
Stored quantity - 10 Tonne
Results indicate
Pool Fire Scenario
Radiation
Level
(KW/m2)
Distance in meter Effect if IHR at Height of simulation
Fireball
1.5 F 1.5 D 5 D
4 158.98 158.98 158.98
This level is sufficient to cause personnel if unable to reach
cover within 20s; however blistering of the skin (second
degree burn) is likely; 0: lethality
Fireball Radius – 64.98 m
Page 49
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 212
Formaldehyde (Catastrophic)
Page 50
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 213
Page 51
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 214
Page 52
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 215
Radiation Effects: Fireball Ellipse (4 KW/m2)
Page 53
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 216
Scenario#4: Catastrophic Rupture of Maleic Anhydride
This scenario considers Catastrophic Rupture of Maleic Anhydride:
Results indicate:
Catastrophic Rupture
Input Data
Stored quantity - 20 Tonne
Results indicate
Maximum Pool Radius – 30.77 m
Cloud Segment Duration – 507 s
Pool Vaporization Rate – 0.0148 kg/s
Page 54
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 217
Page 55
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 218
Page 56
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 219
6.1.6 RISK ASSESSMENT SUMMARY
• From the Risk Assessment studies conducted, it would be observed that by and large,
the risks are confined within the factory boundary walls.
• Based on these studies company has been proposed to plan its facility sitting as well as
location of operator cabin, open area, etc.
• Company has to increase awareness programme in the surrounding vicinity and educate
people for safe evacuation at the time of toxic release.
• Induction safety course to be prepared and trained all new employees before starting
duties in plant.
6.1.6.1 PROCESS SAFETY
• Safety measures are adopted & will be adopted from the design stage.
• Safety Valve and pressure gauge are provided on reactor and its jacket (if jacket is
provided).
• Utility like Chilling, cooling, vacuum, steaming and its alternative is provided to control
reaction parameters in a safe manner.
• Free Fall of any flammable material in the vessel is being avoided.
• Static Earthing provision is made at design stage to all solvent handling equipments,
reactors, vessels & powder handling equipments.
• Any reaction upsets will be confined to the reaction vessel itself.
• All emergency valves and switches and emergency handling facilities are easily
assessable.
• Further all the vessels are examined & will be examined periodically by a recognized
competent person under the Gujarat Factory Rules.
• All the vessels and equipments are earthed appropriately and protected against Static
Electricity. Also for draining in drums proper Earthing facilities is provided.
• Materials are transferred by pumping through pipeline or by vacuum from drums.
• Jumpers are provided on all vegetable / solvent handling pipeline flanges.
• Caution note, safety posters, stickers, periodic training & Updation in safety and
emergency preparedness plan is displayed and conducted.
• Flame proof light fittings are and will be installed in the plant.
• All the Plant Personnel are provided with Personal Protection
• Equipments to protect against any adverse health effect during operations, leakage,
spillages or splash. PPE like Helmets, Safety Shoes, Safety
• All employees are given and updated in Safety aspects through periodic training in
safety.
• Material Safety Data Sheets of Raw Materials & Products is readily available that the
shop floor.
6.1.6.2 FOR HAZARDOUS STORAGE TANK FARM
• Tank farm is constructed as per the requirement For HSD & Liq. N2 Storage – Explosive
department) and separation distance will be maintained.
Page 57
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 220
• Tanks are located and marked in designated area of RM storage.
• Static Earthing provision is made for road tanker as well as storage tank.
• Tanks of proper MOC have been selected.
• Flame arrestor with breather valve is provided on vent line.
• Road tanker unloading procedure is prepared and implemented.
• Fire load calculation is done and as per fire load Hydrant System will be provided as per
NFPA std. and Fire extinguishers are provided as per fire load calculation.
• Flame proof type equipments and lighting is provided.
• Trained and experience operator is employed for tank farm area.
• NFPA label (hazard identification) capacity and content is displayed on storage tank.
• Flexible SS hose is used for road tanker unloading purpose and other temperature
connection.
• All tanks are & shall be uniformly tagged.
• Level indicator is provided in tanks.
• Dyke is provided.
• Industrial type electric fittings are provided.
• Adequate fire fighting equipments is provided.
• Anti corrosive paint is done.
• Safety instruction board is displayed.
6.1.6.2 FOR DRUM/CARBOY STORAGE AREA
Some chemicals are received at plant in drums/Carboys by road truck and stored in a
drum/Carboy storage area.
• FLP type light fittings are provided.
• Proper ventilation is provided in RM & FG dome area.
• Proper label and identification board /stickers are provided in the storage area.
• Drum handling trolley /stackers/fork lift is used for drum handling.
• Materials are stored as per its compatibility study and separate area will be made for
flammable, corrosive and toxic chemical drums storage.
• Smoking and other spark, flame generating item is banned from the Gate.
6.1.6.3 TRANSPORTATION
• Road tanker unloading procedure is in place and is implemented for safe unloading of
road tanker.
• Static Earthing provision is made for tanker unloading.
• Earthed Flexible Steel hose is used for solvent unloading from the road tanker.
• Fixed pipelines with pumps are provided for solvent transfer up to Day tanks/reactors.
• Mechanical seal type pumps are installed.
• NRV provision is made on all pump discharge line.
Page 58
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 221
6.1.7 OTHER RISK REDUCTION OPPORTUNITIES
The following opportunities shall be considered as a potential means of reducing identified risks
during the detailed design phase:
• Buildings and plants structures shall be designed for cyclone floods and seismic events to
prevent structural collapse and integrity of weather (water) proofing for storage of goods;
• Provision for adequate water capacity to supply fire protection systems and critical process
water;
• Isolate people from load carrying/mechanical handling systems, vehicle traffic and storage
and stacks locations;
6.1.8 RECOMMENDATIONS FOR ALARP
The following actions are particularly recommended to be implemented in order to ensure
ALARP (As Low As reasonably practical) performance in the operation: Maintain and ensure
effectiveness of all the safety measures, among others through the following actions:
Raw Material Storage Area
• The raw material storage area should be declared as a prohibited area and should be
provided having at least two exits, “No Smoking” and “Prohibited Area” display boards,
as applicable should be provided at site.
• Regular inspection of tanks/drums/carboys containing raw material to be done to take
care.
• Periodic site inspection should be carried out to ensure that there is no leakage from
any of the drums in the ware house.
• Fire hydrant system needs to be provided in storage area as per TAC standards.
• Smoke detector and fire alarm systems need to be provided.
• Provision of fire doors in ware house area.
Fire access for Tank Farm area and Ware Houses
• Fire access roads should be provided to storage area. The storage tanks/area should
have suitable fire protection and fire fighting facility.
The following features are also important for the project by taking the layout into
consideration:
• Hinged doors swing outward in an explosion.
• Window panes (if installed) are shatterproof or plastic in frame.
• Floors, walls and ceilings are designed and installed to limit the generation and
accumulation of static electricity.
• All doors must be fire resistant. Floors, walls and ceilings are designed for at least 2 h of
fire resistance.
• Walls or partitions are continuous from floor to ceiling, and securely anchored.
Page 59
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 222
• Integrity of the wall should be ensured i.e. blast wall not to be broken or drilled as that
can leads to weak spots.
• The building is constructed of non-combustible materials, on a substantial frame.
• Restrained deflagration vent panels are present.
• There is adequate ventilation, and any heating in rooms is limited to steam, hot water,
or other indirect means.
Electrical Safety for Whole Facility
• Electrical Safety: All cables and electric fittings shall be constructed, installed, protected,
operated and maintained in such a manner so as to prevent risk of open sparking.
6.2 DISASTER MANAGEMENT PLAN
Accident
Accidents will an unplanned event which has a probability of causing personal injury or
property damage or both. It may result in physical harm (injury of disease) to personnel and
also damage to property, loss to the company, a new miss or combination of these effects.
Major Accident
It will be a sudden, unexpected, unplanned event, resulting from uncontrolled developments
during an industrial activity, which causes, or has the potential to cause;
• Serious adverse effect immediately or delayed (death, injuries, poisoning or hospitalization)
to number of people inside the installation and/or to persons outside the establishments or,
• Significant damage to crops, plant or animals, or significant contamination of land, water or
air or,
• An emergency intervention outside the establishment (ex. Evacuation of local population,
stopping of local traffic) or,
• Significant changes in the process operating conditions, such as stoppage or suspension or
normal work in the concerned plan for a significant period of time, or
• Any combination of above effects.
Emergency
It could be defined as any situation which presents a threat of safety of persons or/and
property. It may require outside help also. Emergency due to operating conditions
(uncontrolled reaction, small fire, small gas, leak, spill, failure of power, water, air, steam,
cooling media, scrubbing media, etc.) and which can be locally handled by plant personnel
alone (without outside help) will considered as emergency.
Major Emergency
Major Emergency could be defined as any situation which may affect several departments
within and/ or may cause serious injuries, loss of life, extensive damage to property of serious
disruption outside the work. It will require the use of outside resources to handle it effectively.
Page 60
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 223
Usually the result of a malfunction of the normal operating procedure, it may also be
participated by the intervention of an outside agency, such as severs electrical storm, flooding,
crashed aircraft or deliberate acts of arson or sabotage.
Disaster
It will a catastrophic situation in which the day to day patterns of life are, in many instances,
suddenly disrupted and people are plugged into helplessness, suffering and as a result need
protection, clothing, shelter, medical & social care and other necessities of life such as:
• Disaster resulting from natural phenomena like earthquakes, volcanic eruptions, storm,
surges, cyclones, tropical storms, floods, landsides, forest fires and massive infect
infestation. Also in this group, violent drought which will cause a creeping disaster leading
to famine disease and death must be included.
• Second group includes disastrous events occasioned by man or by man’s impact upon the
environment, such as armed conflict, industrial accidents, factory fires, explosions and
escape of toxic gases or chemical substances, rivers, pollution, mining or other structural
collapse, air, sea, rail and road transport accident, aircraft crashes, collisions of carrying
inflammable liquids, oil spills at sea and dam failures.
Risk
It will the likelihood of an undesired event (i.e. accident, injury or death) occurring within a
specified period or under specified circumstances. It may be either a frequency or a probability
depending on the circumstances.
Hazard
Hazard is a physical situation which may cause human injury, damage to property or the
environmental or combination of these criteria.
Objectives of the On Site Emergency Plan
• To define & assess emergencies, including risk & environment impact assessment.
• To control & contain incidents.
• To safeguard employees, visitors & other people in the vicinity.
• To minimize damage to property &/or the environment.
• To inform employees, the general public and the authorities about the hazards/ risk
assessed safeguard provided residual risk if any and the role to be played by them in the
vent of emergency.
• To be ready for the mutual aid if need rises to help the neighboring unit. Normal jurisdiction
of an OEP will the own premises only, but looking to the time factor in the arriving the
external help of off-side plan agency, the jurisdiction must be extended outside to the
extent possible in case of emergency occurring outside.
• To inform authorities and mutual aid centers to come for help.
• To affect rescue and treatment of causalities to count injured.
• To identify and list any dead.
Page 61
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 224
• To inform and help relatives.
• To secure the safe rehabilitation of affected area and to restore normalcy.
• To provide authoritative information to the news media.
• To preserve records, equipments, etc., and to organize investigation into the cause of the
emergency and preventive measure to stop its recurrence.
• To ensure safely of the works before personnel re-enter and resume work.
• To work out a plan with all provisions to handle emergencies and to provide for emergency
preparedness and the periodical rehearsal of the plan.
In order to meet the above objectives, detailed procedure for handling On Site Emergency has
been prepared, which will intended to cover all foreseeable eventualities even those leading to
the evacuation of the site.
SECTION 41B of Factory Act 1948 requires a factory to draw up an Onsite Emergency Plan with
mentioned of all control measures for the industry. It will mandatory for an industry to educate
employees accordingly about the plan.
Rule 13 of Manufacture, Storage and Import of Hazardous Chemical Rules, 1989 says to prepare
an Onsite Emergency Plan.
The enclosed On-site Emergency Plan is made for the Varnish and Ink Manufacturing process
plant of DIC Fine Chemicals Pvt ltd at Dahej. The plant has a manufacturing facility to produce
Printing Ink as final product.
The plant is designed and equipped to handle hazardous chemical and to carry out various
processes and operations on these chemicals. The plant is provided with Fire Hydrant system,
Fire extinguishers and Scrubber system. In addition to this adequate types and number of
Personal Protective Equipment, First Aid Boxes, Eye washers, Ventilation system has been
provided.
Considering the types of operations carried out in the plant and the nature, extent of hazards
existing, the management of M/s. DIC Fine Chemicals Pvt Ltd thought it necessary to have some
system of tackling an emergency. The formulation of this document is an outcome of the above
thought process.
Internal Safety Survey
DICFC will follow a system of Safety survey to prevent emergency situation from being created.
DICFC also intends to employ a system of accepting suggestions from its workforce &
supervisors for continual improvement in its follow up of safety system.
Page 62
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 225
In spite of various preventive and precautionary measures taken in the plant, the possibility of
a mishap cannot be totally ruled out. Hence, the need to prepare a Contingency Plan for
dealing with incidences which may still occur and are likely to affect LIFE and / or PROPERTY,
both within the plant and in the immediate neighborhood.
Such an emergency could be the result of malfunction of the Plant & Equipment or non-
observance of operating instructions. It could, at times, be the consequence of acts outside
the control of plant management like severe storm, earthquake, flooding, or deliberate acts of
arson or sabotage.
A Major Emergency in the plant is one that may cause serious injury or loss of life and damage
to the property.
6.3 ON-SITE EMERGENCY PLAN
This On Site Emergency Plan (OEP) explains the code of conduct of all personnel in the plant &
actions to be carried out in case of an Emergency. This is an indicative guideline for
employees, contractors, transporters, etc. associated directly or indirectly with the emergent
situation. It also covers prompt rescue operations, evacuations, rehabilitation, co-ordination
and communication.
Emergency:
An Emergency is a situation, which may lead to or cause large-scale damage or destruction of
life, property or environment within or outside the Factory. Such non-routine situation may be
out of control of routine staff.
• A hazardous situation (or a threat of hazardous situation) which required actions to control,
correct and return a site to a safe condition and also requires timely actions to protect
people, property and the environment from the harm.
Nature of emergency:
Emergencies are defined according to the type on the basis of the material and activities
involved. The type of emergency will determine the potential impact of the incident on
people, property and the environment.
The emergency specified in the OEP refers to occurrence of one or more of the following
events:
• Fire/Explosion.
• Major accident such as structural or building collapse, overturning of road tanker
containing flammable substances, Electrical emergencies
• Natural calamities like storm, flood, earthquake, etc.,
• Sabotage act of terrorism, civil commotion, air raid etc.
• Medical emergencies heart attack, Brain stroke, cardiac arrest, and fisher
Page 63
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 226
Identification of Hazardous Areas:
Nature of Emergencies:
The emergency has been identified and can be specified in one or more of the followings with
source and effect:
Emergency Source Effect
Fire / Explosion
Electrical Panels, cable trenches,
DG sets, Compressors, welding ,DG Set,
Boiler, Thermic Fluid (Thermopac Area),
Ware house storage, Electrical Substation,
Varnish 12 m (due to Pressure increase),
Emergency venting system
Smoky Fire, flash fire,
Small fires, Total equipment
loss, Major Fire.
Human injury or Death.
Air & soil pollution, Runaway
reaction
Leakages Nitrogen Leakages, Para formaldehyde gas
leakage
Inhalation hazards, fatality as
carcinogen material
Leakages Natural Gas (Emergency shut off valve at
near Diesel tank farm area) Fire
Overturning of the
tanker containing
flammable
Substances / acid.
Diesel Tanks & Other vegetable oil based
Tankers
Major Fire, Burns / Explosion
Injury or Death
Soil , Water & Air Pollution
Spillage of
flammable
substance/ acid
Drums, Diesel tank,
battery acid
Fire, Burns, Death
Soil pollution, Water Pollution,
Air Pollution
Leakage of Ozone
Depleting
substances / CNG
gas
Refrigeration / Cooling System /
Ozone Depletion,
Air Pollution
Confined Space All confined space area in plant layout (as
per list of confined space entry in plant) Oxygen deficiency
Failure of ETP pump ETP Plant Water pollution and
soil pollution
Overflow of ETP
during
heavy rains
ETP Plant Toxic Water Release, water
pollution and Soil pollution.
Food Poisoning Canteen Severe health affect, death
Road Accident Bus Major Accident ,Fatality
Page 64
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 227
6.3.1 EMERGENCY CONTROL CENTRE (ECC):
DICFC Have Designated following as the ECC
• During normal working hours – Director - Operations’ office.
• During hours other than normal working hrs - Ink Incharge act as a Site Incharge
All communications to and from will originate at this CONTROL CENTRE. The Emergency
Control Center will have the following:
• A copy of ON-SITE EMERGENCY PLAN.
• List of important telephone numbers such as Police, Fire
• Brigade, Hospitals, and other outside Emergency Services, etc.
• List of key Personnel with addresses and telephone numbers.
• List of Fire and Rescue Squad Members.
• Plant layout indicating storage of hazardous materials
• List Fire Extinguisher.
• Fire Fighting System (Layout of Fire Hydrants)
• List of Personal Protective Equipment
• First Aid box.
• List of Hazardous Chemicals with MSDS
• Emergency organization Chart
6.3.2 ASSEMBLY POINTS
In case of an EMERGENCY the employees should assemble near the defined Assembly Points,
as indicated below:
• All employees from work place: Area near Canteen and Behind FG Store.
• Others - Area near Security Gate.
Wind socks is installed above Fire Water storage tank and & HT Yard (Opp. Security Gate office)
to indicted the wind direction.
The employees should run perpendicular to the wind direction and not against / along the wind
direction.
Codification of Sirens
S.
No. Sirens Indicates Authority
1.
30 SECOND for
three times
CONTINUOUS
ON SITE
EMERGENCY (ALERT) SITE CONTROLLER
2. 1 MINUTE
CONTINOUS
EMERGENCY
CONTROLLED
(ALL CLEAR)
SITE CONTROLLER
Page 65
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 228
NOTE: 1) EMERGENCY SIREN TO BE SOUNDED ONLY IF REQUIRED
2) ALL EMPLOYEES IN AREAS OTHER THAN AFFECTED TO CONTINUE WORK UNLESS
DISASTER SIREN IS BLOWN.
3) MEMBER OF EMERGENCY RESPONSE TEAM WILL NOT LEAVE THE EMERGENCY SPOT
UNLESS `ALL CLEAR’ SIREN BLOWN.
6.3.3 TRAINING AND EDUCATION
Experience with on site – emergency planning has proved the need of training and rehearsal.
Major emergency procedure should be laid down clearly and convincingly to everyone on site
particularly Key Personnel and Essential workers. It is obvious that in house or outdoor training
is essential. The duties and responsibilities of each person and the emergency procedure to be
followed by him should be very clear.
• Seminar/refresher guidance On Site Emergency Plan.
• Emergency instruction Booklet.
Seminar: Seminar is conducted in house/. Site controller will explain the plan to all associated
concerned employees. Expert from outside explain the plan to all associated concerned
employees. Expert from also may be invited to impart training.
Emergency Instruction Booklet:
Emergency instruction Booklet contains all detailed emergency duties. The booklet contains –
• Emergency duties,
• Reporting relationship.
Thus everyone is conspicuous about his role in the Emergency Plan.
Mock Rehearsal:
DICFC intends to conduct Mock Rehearsals at regular intervals & observations will be analyzed
& acted upon for preparedness to combat emergency. (Once in Six Month)
Updating the Plan:
DICFC intends to review the OEM at regular intervals & during learning lessons, mock rehearsals
& update it after duly analyzing the shortcomings.
Nitrogen Tank:
DO & DON’TS OF VACUUM INSULATED VESSELS
• Please operate the valves as per P & I diagram & Working Instructions.
• Please ensure that Overflow valve is opened during the fill and full quantity delivered
will be when liquid starts flowing out from the overflow valve & not as per the readings
of D.P. Gauge.
• Please observe pressure rise for at least One hour after the fill has been given. In the
event of any excess pressure build up than that of working pressure, release the gas
from vent valve.
Page 66
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 229
• Liquid level gauge is only indicator of approximate quantity available in the vessel and
not accurate.
• Do not change the setting of Pressure raising Regulator. Need base call on BOC
personnel in the event of your requirement of lowering/increasing the working
pressure.
• Do not operate instrumentation valves of Pressure gauge & D.P.Gauge.
• Do not tamper with spring loaded Safety valves and Rupture Discs.
• In the event of pressure build up in the vessel, close the pressure raising valve and
release excess pressure through vent valve.
• In the event of lower pressure than that of working pressure please check pressure
raising valves. If close, please open.
• In the event of failure one rupture disc, reduce the pressure to working pressure than
slowly change over 3 way valve on other side, so that 2nd
Rupture discs remains in
operation.
� Please call on us Tel:080-28396272 and after office hours
� Mobile No:- 9663310093, 9036432246, 09831509713
In the event of any assistance required towards smooth operation of the system
Emergency Organization
Note: Responsibility will be automatically delegated in absence of concern person/s in following
manner.
SITE CONTROLLER: GM - Operations in routine days (other than routine work Ink Incharge shall
act as a Site controller
INCIDENT CONTROLLER: Production Manager in routine days (Other than routine hours both
INK & VARNISH Incharge has to work on a mutual understanding for the responsibilities of a
incident controller
DUTY OFFICER: ON Saturday/SUNDAYS/HOLIDAYS
ADVISORY COMMITTEE: The Advisory committee will comprise of GM - Operations /Head
Production /Head QA/ Head EHS/ Head Maint. & Plant Engineer & Human Resource
Manager/Safety Committee
COMMUNICATION COMMITTEE: Human Resource Manager & Plant Engineers
6.3.4 KEY PERSONNEL & THEIR RESPONSIBILITIES
Key Personnel’s Responsibility during normal working hours:
Page 67
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 230
6.3.4.1 Site Controller:
He will retain overall responsibility for the factory and its personnel. As soon as he is informed
of the emergency his office shall convert into Emergency e control room. His duties shall be:
• Assess the magnitude of the situation and decide if staff needs to be evacuated from
their assembly points.
• Exercise direct operational control over areas other than those affected.
• Maintain a continuous review of possible development and assess in consultation with
Incident Controller and other Key personnel as to whether shutting down of the plant or
any section of the plant and evacuation of persons is required.
• Liaison with Senior Officials of Police, Fire Brigade, Directorate of Industrial Safety,
provide advice on possible effects on areas outside the factory premises.
• Control rehabilitation of affected areas on discontinuation of emergency.
• Issues authorized statements to news media, and ensure that evidence is preserved for
inquiries to be conducted by statutory authorities.
6.3.4.2 Incident Controller:
On hearing of an emergency siren he will rush to the scene of the occurrence and take overall
charge and report to Site Controller. On arrival he will assess the scale of emergency and
decide if major emergency exists or is likely and inform the Communication Officer accordingly.
• Direct all operations within the affected areas with the priorities for safety of personnel
minimize damage to the plant, property and minimize loss of materials.
• Pending arrival of Site Controller, assume the duties of his post and, in particular.
• Direct the shutting down and evacuation of plant and areas likely to be adversely
affected by the emergency.
• Ensure that all Key personnel and outside help are called in.
• Provide advice and information to the Fire squad & Security Officer and the local fire
service as and when they arrive.
• Ensure that all non-essential workers/staff of the areas affected are evacuated to the
appropriate assembly points, and the areas are searched for casualties.
• In the event of failure of electric supply and internal telephones, set up communication
point and establish contact with Emergency Control Centre.
• Report on all significant developments to Director/Site Controller
• Have regard to the need for preservation of evidence so as to facilitate any inquiry into
the causes and circumstances, which caused or escalated the emergency.
6.3.4.3 Human Resources Manager
He will also work as liaison Officer and will be stationed at the Main Entrance (Security Office
near Main Gate) during the emergency. He will under the direction of the site Controller
handle police, press and other inquiries, receive reports from roll-call leaders from assembly
points and pass on the absentee information to the Incident Controller. His responsibilities shall
include:
Page 68
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 231
• To ensure that casualties receive adequate attention, to arrange additional help if
required and information relatives.
• To control traffic movements into the factory and ensuring that alternative transport is
available when need arises.
• When emergency is prolonged, arrange for the relief of personnel and organize
refreshments / catering facility.
• From information received, advise the Site Controller of the situation, recommending (if
necessary) evacuation of staff from assembly points.
• Recruit suitable staff to act as runners between the Incident Controller and himself if the
telephone and other system of communication fails due to whatsoever reasons.
• Maintain prior agreed inventory in the control centre.
• In case of prolonged emergency involving risk to outside areas by wind-blown materials,
contact local Meteorological Office to receive early notification of changes in weather
conditions.
6.3.4.4 Security Officer:
• On hearing alarm advice fire squad and security staff in the factory of the incident zone
and cancel the alarm. He will also announce through telephone or messengers to the
HR Manager, Incident Controller and Site Controller that incident has occurred in such
and such zone. He will open the gates nearest to the incident and stand by to direct the
emergency service.
• If told of a large escape of gas he shall inform the Incident Controller by telephone and
stand-by the telephone to receive further messages.
• On hearing the emergency alarm, he will immediately contact Site Controller and on his
advice call the local fire brigade. In case fire is discovered but no alarm is sounding he
shall receive information about location from the person discovering the fire and
thereafter immediately consult the Site Incident Controller and make announcement on
telephone telling the staff location of the incident and to evacuate to their assembly
points. He will continue to operate the switchboard advising the calls connected with
the incident to the Communications Officer.
6.3.4.5 Departmental Heads:
• The Departmental head wherein the incident has taken place will report to Incident
Controller and provide assistance as required. They will decide which members of their
staff they require at the scene.
6.3.4.6 First-aid Teams:
• The HR Manager shall keep in security the roll call lists for the fire and first-aid teams on
duty. Each Departmental Head for his shift-team appoints roll call leaders and first
aiders. Roll call leaders shall check their roles as members of the services report for
emergency duty. Names of any unaccounted for absentees will be informed to the
Security Officer.
Page 69
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 232
• Members of first-aid Teams will report to the Incident Controller on hearing of the alarm
in day time. The Emergency vehicle driver, if safe to do so, shall collect the emergency
vehicle and park nearest to the scene of the incident. First aider shall inform the
incident controller that the Emergency Vehicle is leaving the site, giving the name of
the patient and destination i.e. hospital or doctor’s room and request the Incident
Controller to inform the destination (hospital, etc.) advising them about the casualties
reaching there.
6.3.4.7 Factory Fire Squad Personnel:
• The duty Fire fighting Squad under the command of the Security Officer shall be
responsible for fire fighting and rescue. On hearing the alarm, they shall proceed to the
place of incident. The men at security gate shall find out the location of the emergency
and proceed to the site of the occurrence.
• At the incident scene, a team members detailed for this purpose will check squad
members against roll-call sheet. At the site, all the squad members will respond to the
advice and information given by the Incident Controller On arrival of the local fire
brigade, they will also assist in fire-fighting work with the advice of the Incident
Controller.
Emergency Action Plan
Anyone noticing emergency situation like fire, explosion, gas etc. must
DO’s
• Attract the nearby person/employee by shouting “FIRE – FIRE – FIRE“
• Seek help from the persons working nearby.
• Try to control the incident at its initial stage with available means/sources quickly.
• Inform Shift In-charge / Duty Officer (In Night Shift) about the Incident.
DON’Ts
• Do not be panicky.
• Do not run – Walk fast.
6.3.4.8 Incident Controller Must
DO’s
A. If Fire / Other Incidents Are Controllable
• Approach the emergency site immediately taking note of wind direction.
• Assess the situation.
• Inform Security Officer, Tell – NAME, TYPE OF INCIDENT, ACTION TAKEN, HELP NEEDED
and Order Security Officer/Guard to inform all KEY persons.
• Take lead in controlling emergency until such time concerned Section Manager takes
over the charge.
DON’TS
• Do not panic.
Page 70
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 233
• Do not lose temperament.
B. If Fire/Other Incidents Are Not Controllable
In Addition to Above (A):
• Order to blow emergency `ALERT’ Siren (30 second continuous).
• Organize Fire fighting / rescue team members to control the Incident.
• Take stock of situation if required shut down the plant / process in affected area.
• Call Fire Brigade if situation demands.
• Evacuate affected area.
• Organize head count of the plant.
• Act as INCIDENT CONTROLLER till such time senior person takes charges as indicated in
Emergency organization
NOTE: 1) Messenger will wait until such time Security Officer arrives.
2) Also inform Telephone Operator.
6.3.4.9 Security Officer / Guard
DO’s
• Do not allow any vehicle to come inside the factory.
• Do not entertain any outside call except for emergency purpose.
• Do not allow visitors to move around.
• Inform all key persons about location and type of emergency.
• Follow this sequence – Inform concerned HOD/Section Head, Main Site Controller, Main
Incident Controller & EHS Dept and other KEY persons.
• Inform Main Site Controller about Government visitors, if any.
• Keep the main Gate open to move the vehicle in out on Emergency
DON’Ts
• Do not entertain any outside call except for emergency purpose.
• Do not allow visitor to move around, from reception.
6.3.4.10 Security Guard
DO’s
• Immediately report at Security Gate in shortest possible time.
• Follow instructions of Officer In-charge.
• Assist in controlling emergency.
• Assist in controlling contractors, vehicle movement and mob.
• Assist in cordoning off the area.
• Take note of wind direction while approaching emergency site.
• Render all possible help for controlling overall situation.
DON’Ts
• Do not leave the site unless asked to do so.
Page 71
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 234
6.3.4.11 Emergency Vehicle Driver
DO’s
• Immediately start vehicle and reach rescue squad assembly point (near Canteen and RM
Store).
• Rescue squad members to emergency site.
• Take vehicle near to emergency site as directed.
• Take note of wind direction.
• Reverse the emergency vehicle for quick transports of injured, if any.
• Keep vehicle engine running.
• Always be on Driver’s seat of the vehicle.
• Take the injured to the hospital as directed.
DON’Ts
• Do not take the vehicle very near to the site.
• Do not leave the vehicle. Do not leave the site unless asked to do so.
6.3.4.12 Incident Controller
DO’s
• Approach emergency site as early as possible taking note of wind direction.
• Take stock of situation.
• Interact with all concerned departments as the situation demands.
• Keep Main Site Controller informed about the latest emergency situation on continuous
basis
6.3.4.13 Site Controller
DO’s
• Will approach emergency site immediately / assess the situation.
• Consult Incident Controller.
• Consult advising Committee Members.
• Instruct Main Incident Controller.
• Communicate to higher ups and Govt. authorities, if required.
• Decide upon need for evacuation and blow `Disaster Siren’.
• After getting satisfied with the situation, give instruction to blow ALL CLEAR Siren.
DON’Ts
• Do not instruct to blow ALL CLEAR siren unless the situation is fully under control.
• Don’t evacuate the entire plant unless the situation demands.
6.3.4.14 Fire Fighting Squad on Hearing Siren
DO’s
• Inform fellow employees/Officers.
• Report to Fire Squad at Incident point.
• Find out emergency location.
Page 72
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 235
• Approach emergency site immediately.
• Take quick action as per the instructions from Incident controller.
• Bring emergency under control as early as possible.
DON’Ts
• Do not leave process/equipment in UNSAFE CONDITION.
• Do not leave emergency site unless ALL CLEAR siren blown.
• Do not use improper fire extinguisher.
• Do not be panic
6.3.4.15 Rescue Squad
DO’s
• Report to assembly point near Canteen or RM Store as per instructed.
• Get in touch with security about location and type of emergency.
• Approach emergency site quickly with Breathing Apparatus set, First Aid Box and
Ambulance.
• Get in touch with incident controller.
• Follow instructions of Incident controller.
• Render first aid to the injured, hospitalize, if required.
• Accompany him to hospital and assist Doctor / Nurse.
• Search for missing person in that area, if required.
• Help in head count
6.3.4.16 All General Employees except Those Who Are In Emergency Organization on Hearing
Siren
DO’s
• Be alert and be available if required.
• Wait for further instructions.
• Bring down the process/plant/equipment in SAFE CONDITION in case of DISASTER siren
as per instructions from Incident Controller.
• Approach respective safe assembling points route as taking note of wind direction.
• Help in taking roll call.
• After hearing ALL CLEAR, go back to the departments.
• Start the work again after setting instruction from Incident controller.
DON’Ts
• Do not be panicky. Do not run.
• Do not approach emergency site unless asked for.
• Do not engage telephone except for emergency purpose. Keep lines free
6.3.4.17 Technical Team: Engineering Department on Hearing Siren
DO’s
• Be available in Engineering Department at respective location for any help.
Page 73
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 236
• Approach emergency site with required with tools and equipments and should work on
instructions of Incident controlled.
• Help Incident Controller to provide technical assistance.
• Isolate lines, process equipments, if required by Incident Controller.
• Provide emergency equipments like Fire Extinguisher, Hoses, etc., if asked by Incident
Controller.
• Provide stop gap arrangements as per the requirement of Incident Controller.
• Carry out electrical isolation of area as per instructions from Incident Controller.
6.3.4.18 Advisory Committee (Environment, Safety and Health Department And All
Department Heads
DO’s
• Approach emergency site as early as possible.
• Render advice to Main Incident Controller and Main Site Controller to control
emergency.
6.3.4.19 Communication Committee – (P&A)
DO’s
• Consult Main Site Controller
• Give necessary instructions to security / Telephone Operator.
• Give instruction to Security to control traffic / crowd.
• Look after injured, communicate with the family members, if situation demands.
• Arrange transportation, if required.
DON’Ts
Do not communicate to any one or brief press without permission of Main Site Controller.
6.3.4.20 General Instructions
DO’S
• Stop work at height. / Stop all hot works.
• Stop all vessel entry.
• Take note of wind direction.
• On hearing Disaster Siren evacuates as per evacuation route without running and
panicky and assembles at respective safe Assembly Points.
DON’Ts
• Do not use telephone except for emergency purpose.
• Do not start work at height, vessel entry, hot work unless permit conditions are verified.
• Do not allow unauthorized person to approach emergency site
Page 74
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 237
TELEPHONE NUMBERS OF POLICE, FIRE BRIGADE, HOSPITALS, AND OTHER OUTSIDE
EMERGENCY SERVICES
DAHEJ / BHARUCH TEL. NOS.
POLICE DEPT-
VAGARA POLICE STATION 02641-225233
DAHEJ POLICE STATION 02641-256233
DSP BHARUCH 02642-269303
COLLECTOR OFFICE 02642-240600
CIVIL HOSPITAL BHARUCH 02642-243515
BLOOD BANK BHARUCH 02642-243603
GRAMPANCHAYAT OFFICE VAGRA :-
SARPANCH VAGARA 02641-256312
TAHASILDAR VAGRA 02641-225221
GRAMPANCHAYAT OFFICE DAHEJ :-
SARPANCH DAHEJ
Fire and Emergency Services of Dahej SEZ Ltd.,
Mr. Jaydeep Bhatt
DSL Fire Station
7874787973
02646-291191, 8347420101
Disaster Management Centre, Dahej (DMC)
Mr. Hitesh Shah
DMC Office
9824475576
02646-256670, 9924937101
DSL Infra – Mr. Niraj Shah 9825740882
MUNICIPAL CORPORATION BHARUCH 02642-241753
Assist. Commissioner MCP bharuch 02642-249389
GPCB OFFICE BHARUCH 02642-246333
FIRE CONTROL ROOM ( MUNICIPAL CORPORATION BHARUCH)
FIRE CONTROL STATION AVAILABLE NEARBY GIDC GACL: 02641-256315/16/17
IPCL: 02641-256401/410
BARODA HEART & MULTI SPECIALITIES HOSPITAL 02642 – 260551, 260552
Page 75
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 238
TELEPHONE NUMBERS AND ADDRESSES OF KEY PERSONNEL LIST OF KEY PERSONS
(EMERGENCY RESPONSE TEAM AT SITE)
NAME RESIDENCE TEL. NO.
Prashant Limaye 09099967101
Vikas ji Agarwal 09099967102
Amit Upadhyay 09099967105
Ishvar Panchal 09099967106
Mihir Abhyankar 09879665537
Ajay Pancholi 09099967117
Mayank Amit 09825337959
Pradosh Mohanty 08000511999
Jatin Patel 09099967113
Avantika Rathod 09429984738
Aarti Vahalia 09099911262
Akash Patel 07573884111
MUTUAL AID SCHEME MEMBERS & MUTUAL AID RESPONSE GROUP
COMPANY OFFICE PHONE
G.A.C.L. 02641-256315/16/17
Birla Copper 02641-256004/5/6
Welspun 02641-256011
IPCL 02641-256401/410
GCPTCL 02641-2566604/05
PIDILITE 022228357558
Dahej Disaster Management Society
For External fire tenders (Hitesh Shah) 09824475576
Page 76
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 239
LIST OF FIRE FIGHTING SQUAD MEMBERS
LIST OF FIRST AIDERS MEMBERS
Name Dept.
Mukesh Solanki INK
Nimesh Patel INK
Sanjay Bhatt INK
Rakesh Biswal INK
Ghanshyam Sindha INK
Mihir Vanza INK
Gaurang Patel INK
Jignesh Vadher INK
Raghuvendra Kumar INK
Nitin Patel INK
Dhruvesh Patel QC
Sandeep Mistry QC
Name Dept. Contact No.
Rakesh Patel Prod. – Varnish 9913613170
Roshan Patel Prod. – Varnish 9426564318
Nitin Patel Prod. – Varnish 9428588477
Pradeep Patel Prod. – Varnish 9427157959
Nimesh Patel Prod. – Ink 9925222907
Jignesh Vadher Prod. – Ink 9898323178
Mukesh Solanki Prod. – Ink 9909956356
Salman Sheikh Prod. – Varnish 9724132706
Gaurang Patel Prod. – Ink 8511190149
Sanjay Bhatt Prod. – Ink 9099956965
Pradosh Mohanty Engg 8000511999
Mayank Amit Engg 9825537959
Ghanshyam Chauhan Logistics 9924199923
Ranvir Rana RM 9924940088
Lotan Patil Qc 7567896983
Manish Patel Logistics 9898029824
Mihir Abhyankar Production 9879665537
Subhash Parekh Engg. 9909148767
Page 77
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 240
Jigar Raj QC
Sagar Parmar ETP
Punit Thakor ENGG
Pradosh Mohanthy ENGG
Parshuram Mahakund ENGG
Subhash Parekh ENGG
Rakesh Patel VARNISH
Salman Sheikh VARNISH
Roshan Patel VARNISH
Ajitendra Ojha VARNISH
Bhavik Kayasth VARNISH
Tushar Parmar HR
Ajay Pancholi EHS
Bhavik Jadav IT
Gaurav Madlani Finance
Ranvir Rana Store
6.4 EMERGENCY CONTROL SYSTEM FIRE HYDRANT SYSTEM
An underground Fire Hydrant System has been installed in the plant with rings around all blocks
to achieve maximum coverage. Fire water reservoir of 650m3
effective capacity for Hydrant as
well as sprinkler system with feed from the GIDC water supply has been provided in the plant.
Following are the details of the system.
• Fire Water Reservoir- 650m3
• Type of Hazard- “High Hazard Occupancies, Category A” as per Fire
• Protection Manual of TAC & “Extra Hazard Occupancies, Gr 2 as per NFPA.
• Design Code-NFPA and TAC”s Fire Protection Manual.
• Total no. of External Fire Hydrant including landing Values, Water monitor - 22 Nos (15
nos of Single hydrants, 7 nos of Double headed hydrants & one no. of foam monitor)
• Automatic Operation-Jockey pump of 50 GPM@88M head capacity with pressure
switches.
• Standby arrangement-Diesel Generator with AMF control panel.
Page 78
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 241
• Nos of Hose Boxes-External-25 nos
• Nos of Hose Boxes- Internal -02 nos
• Total Nos of Hoses- 68 nos
• Nos of Nozzles-20 mm bore-18 nos.
• Hydrant flexible rill - 6 nos.
• Electric Driven main pump - 1500 GPM@88M head capacity with pressure switches.
• One Jockey pump provided of capacity 50 GPM@88M head
List of Fire Extinguishers: Area Wise
Page 79
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 242
List of SCBA Nos. & Trained Manpower
List of PPEs
S. NO. MATERIAL
1. Tough Helmet (Safety)
2. Safety Goggle (anti fog & Scratch resistant)
3. Safety Steel toe Shoes (At present Allen Cooper using)
4. Heat Resistant Hand Gloves ( At present Leather Gloves)
5. PVC Hand gloves
6. Nitrile Hand gloves EFN-15
7. Cotton Knitted Hand gloves 8”
8. Surgical Hand Gloves 7.5”
9. Rubber Hand gloves (Shock proof electric Sub-station/HT)
10. Cut resistant Hand Gloves (Both single side & double side Nitrile coating)
11. Eye washer & Safety shower fountain
12. Steel toe Gum boot
13. Double harness full body Safety Belt (steel scaffold hook)
14. Dust Mask (3M 9004IN P1 at present)
15. Organic Vapour mask
16. SCBA Sets
17. Flame proof Torch
18. Electrical Safety Shoes, Gumboot
19. Aluminized Suit (Fire Entry)
20. Splash Goggle
21. Welding fumes protection mask
22. Ear Plug
23. Ear Muff
24. Chest guard heat resistant
25. Sleeve Heat Resistant
26. Fire water Hose
27. Fire Hose Reel
28. Positive Pressure Suit
29. Convex Mirror
30. Shoe cover
31. Mobile foam unit
32. Disposable Cap
33. Wind shock
34. Oil observer
35. Eye washer bottle
36. Fire Blanket
37. Traffic Cone
38. Barricading tape
39. Spark Arrestor
40. Welding shield
Page 80
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 243
S. No SCBA Set Ident. No. Location
1 SCBA Set – I V1 Varnish 0 Mt
2 SCBA Set – II V2 Varnish 12 Mt
3 SCBA Set - III T1 Thermopack
S. No Name Dept. Contact Details
1 Rakesh Patel Prod. - Varnish 9913613170
2 Roshan Patel Prod. - Varnish 9426564318
3 Nitin Patel Prod. - Varnish 9428588477
4 Pradeep Patel Prod. - Varnish 9427157959
First Aid Medical Facilities
The company has provided “First –AID” boxes at security office. Following are the contents of
First aid.
• Tincture iodine.
• Eye wash solution.
• Soframycin (ointment)
• Sterilized cotton wool.
• Band-aid.
• Antiseptic Solution (Dettol)
• Bandage.
• Paracetamol tablets.
• Iodex
• Pair of scissor
• BP Instrument (Digital & Manual)
• Glucometer
The company has got its own transport facilities to take the injured to the hospital. The nearest
hospitals are in Dahej for Primary treatment & Bharuch for specialized treatment.
Page 81
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 244
List of Emergency Equipments
Smoke Detector List: Area Wise
Smoke Detector List Area Wise
S. No ID No. Area Description Device Type Remark
1 L1/01 Admin Passage Smoke Detector ok
2 L1/02 Admin Purchase manager cabin Smoke Detector ok
3 L1/03 Admin Purchase manager cabin Above Smoke Detector ok
4 L1/04 Admin meeting room Smoke Detector ok
5 L1/05 Admin HR Cabin Smoke Detector ok
6 L1/06 Admin nr. Meeting room Above Smoke Detector ok
7 L1/07 Admin nr. Hr cabin Smoke Detector ok
8 L1/08 Admin GM cabin Smoke Detector ok
9 L1/09 Admin Conference room Smoke Detector ok
10 L1/10 Admin Conference room Smoke Detector ok
11 L1/11 Admin GM cabin Above Smoke Detector ok
12 L1/12 Admin reception Smoke Detector ok
13 L1/13 Admin Lobby D-1 Above Smoke Detector ok
14 L1/14 Admin Lobby D-2 Smoke Detector ok
15 L1/15 Change Room D1 Smoke Detector ok
16 L1/16 Change Room D2 Above Smoke Detector ok
17 L1/17 Admin Ladies change room D1 Smoke Detector ok
18 L1/18 Admin Ladies change room D2 Above Smoke Detector ok
19 L1/19 Plant entry passage - D1 Smoke Detector ok
20 L1/20 Plant entry passage - D2 Smoke Detector ok
21 L1/21 Laboratory D1 Above Smoke Detector ok
22 L1/22 Laboratory D2 Smoke Detector ok
23 L1/23 Prod. Control Room INK D1 Smoke Detector ok
24 L1/24 Prod. Control Room INK D2 Above Smoke Detector ok
25 L1/25 Spare - Printing room Smoke Detector ok
26 L1/26 Lab storage room D1 Above Smoke Detector ok
27 L1/27 Lab storage room D2 Smoke Detector ok
28 L1/28 QC HOD office D1 Above Smoke Detector ok
29 L1/29 QC HOD office D1 Smoke Detector ok
30 L1/30 Engineering HOD office D1 Smoke Detector ok
31 L1/31 Engineering HOD office D2 Above Smoke Detector ok
32 L1/32 Engg. Office D1 Smoke Detector ok
33 L1/33 Engg. Office D2 Smoke Detector ok
Page 82
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 245
Smoke Detector List Area Wise
S. No ID No. Area Description Device Type Remark
34 L1/34 Training Room D1 Smoke Detector ok
35 L1/35 Training Room D2 Above Smoke Detector ok
36 L1/36 Plant Manager office D1 Smoke Detector ok
37 L1/37 Plant Manager office D2 Above Smoke Detector ok
38 L1/38 Engg. Office D3 Above Smoke Detector ok
39 L1/39 Server room D1 Smoke Detector ok
40 L1/40 Server room D2 Above Smoke Detector ok
41 L2/5 Engg. Work Shop D1 Above Smoke Detector ok
42 L2/6 Engg. Work Shop D2 Smoke Detector ok
43 L2/7 Conference Room Smoke Detector ok
44 L2/9 Vanish Control Room D1 Smoke Detector ok
45 L2/10 Vanish Control Room D2 Smoke Detector ok
46 L3/151 Security Visitor Room Smoke Detector ok
47 L3/152 Security Driver Room Smoke Detector ok
48 L3/153 Security Electrical Panel Room Smoke Detector ok
49 L3/154 Security Drinking Water Smoke Detector ok
50 L3/155 Security Reception Smoke Detector ok
51 L3/169 Security OHC Room Smoke Detector ok
52 L3/156 HT Room G.F. D1 Smoke Detector ok
53 L3/157 HT Room F.F. D2 Smoke Detector ok
54 L3/160 Canteen Staff Dining D3 Smoke Detector ok
55 L3/161 Canteen Store Room Smoke Detector ok
56 L3/162 Canteen Staff Dining D4 Smoke Detector ok
Page 83
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 246
Heat Detector List: Area Wise
Heat Detector List Area Wise
S. No ID No. Area Description Device Type
1 L2/1 Elec. Panel D1 HD
2 L2/2 Elec. Panel D2 HD
3 L2/3 Elec. Panel D3 HD
4 L2/4 Elec. Panel D4 HD
5 L2/8 Boiler Room HD
6 L3/158 Canteen Staff Dining D1 HD
7 L3/159 Canteen Staff Dining D2 HD
8 L3/163 Canteen Staff Dining D5 HD
9 L3/164 Canteen Kitchen D1 HD
10 L3/165 Canteen Rest Rom HD
11 L3/166 Canteen Executive Dining D1 HD
12 L3/167 Canteen Executive Dining D2 HD
13 L3/168 Canteen Staff Dining D6 HD
14 L4/151 Substation D1 HD
15 L4/152 Substation D2 HD
16 L4/153 Substation D3 HD
17 L4/154 Sub Station Battery Room D4 HD
18 L4/155 Substation D5 HD
19 L4/156 Substation D6 HD
Beam Detector List: Area Wise
Beam Detector List Area Wise
S. No ID No. Area Description Device Type
1 L1/131 Ink Plant Beam detector-1 BD-1
2 L1/130 Ink Plant Beam detector-2 BD-2
3 L1/121 Ink Plant Beam detector-3 BD-3
4 L1/122 Ink Plant Beam detector-4 BD-4
5 L1/123 Ink Plant Beam detector-5 BD-5
6 L1/124 Ink Plant Beam detector-6 BD-6
7 L2/143 Pigment Area Beam Detector-1 BD-7
8 L2/141 Pigment Area Beam Detector-2 BD-8
9 L2/142 Pigment Area Beam Detector-3 BD-9
Page 84
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 247
Manual Call Point List: Area Wise
Heat Detector List Area Wise
S. No ID No. Area Description Device Type
1 L1/102 Dispatch door-1 MCP
2 L1/103 Admin Passage MCP
3 L1/106 Admin Nr. GM Cabin MCP
4 L1/110 Nr. Plant Entry Door-1 MCP
5 L1/112 Lab entry from production MCP
6 L1/115 Nr. Engineer HOD Office MCP
7 L1/120 Engg. Office Dorr-2 MCP
8 L1/127 Ink PlanT E.Exit Door-2 MCP
9 L1/129 Ink PlanT E.Exit Door-1 MCP
10 L1/133 Dispatch E.Exit Door-2 MCP
11 L1/135 Dispatch door-1 MCP
12 L2/102 Ware House Shutter-2 MCP
13 L2/103 Varnish Tank Farm Area MCP
14 L2/106 Varnish Tank Entrance MCP
15 L2/107 Elec. Panel Room MCP
16 L2/111 Compression Room MCP
17 L2/113 Varnish Plant E. Exit Door-2 MCP
18 L2/114 Dilutor Plant MCP
19 L2/117 Reactor Plant E.Exit Door-1 MCP
20 L2/120 Reactor Plant Door-2 MCP
21 L2/122 Reactor plant Nr. Lift MCP
22 L2/125 Varnish control room e. exit MCP
23 L2/128 Nr. Varnish Control room Exit MCP
24 L2/130 Rosin Crusher path way MCP
25 L2/132 Rosin Crusher Plant MCP
26 L2/134 Ware house entrance MCP
27 L2/136 Ware house e. exit door-3 MCP
28 L2/140 Ware house e. exit door-2 MCP
29 L3/178 Security reception MCP
30 L3/176 HT Room GF MCP
31 L3/173 Canteen Entrance Door-2 MCP
32 L3/175 Canteen Entrance Door-1 MCP
33 L3/172 Substation E.Exit Door1 MCP
Page 85
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 248
34 L3/174 Substation Door-2 MCP
35 L3/176 Substation Nr. Shutter MCP
36 L3/178 Utility Entrance MCP
List of Fire Hydrant Nos. & Hose Boxes
List of Fire Hydrant Nos & Hose boxes
S. No Location Fire Hydrant No. Fire Hydrant Box No.
1 Near QC LAB DH-02 HB-05
2 Near Engg Store DH--01 HB-07
3 Near Varnish Main Entrance SH-01 HB-10
4 New E waste room SH-11 HB-18
5 Near Foam Tank DH-04 HB-12
6 Electrical substation main road DH-04 HB-13
7 Entrance of Hazardous waste SH-02 HB-16
8 ETP Garden SH-10 HB-15
9 Near Transformer Area SH-16 HB-14
10 cooling tower Back side SH-08 HB-11
11 Chilling plant Back side SH-07 HB-08
12 Boiler back side DH-03 HB-06
13 Diesel Tank Farm Back Side DH-01 HB-03
14 Near Tank Farm area DH-02 HB-04
15 Near MCC Panel Room SH-04 HB-09
16 Haz. Waste Back Side SH-03 HB-17
17 Near Gum Rosin Dom SH-12 HB-19
18 Near FK Engg SH-03 HB-20
19 FG main Road Back Side SH-09 HB-21
20 Pigment Road back side SH-14 HB-22
21 RM Stores Backside SH-01 HB-24
22 Near Admin Building SH-05 HB-01
23 Near Canteen SH-15 HB-02
24 Ink Plant main road back side SH-15 HB-23
25 Varnish Crushing Area SH-13 HB-25
Page 86
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 249
FIRE HYDRANT DRAWINGS
Page 87
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 250
Page 88
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 251
Page 89
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 252
Page 90
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 253
Page 91
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 254
Page 92
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 255
Page 93
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 256
Page 94
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 257
Detailed fire control plan for flammable substances and processes showing hydrant
pipeline network, provision of DG Sets, fire pumps, jockey pump, toxic gas detectors etc.
Page 95
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 258
6.5 OFF – SITE EMERGENCY PLAN
6.5.1 NEED OF THE OFF – SITE EMERGENCY PLAN
An off-site emergency plan is prepared to deal with those incidents which have the potential
to harm persons or the environment outside the boundary of the factory premises. A major
accident, major emergency and disaster may affect areas outside the plant. An explosion
can scatter debris over wide areas and its effects of blasts can cover considerable distances.
Wind can spread burning fumes of toxic gases. Thus the events like these described above
can affect outside areas and combating them needs an Off-site Emergency plan.
Envisaging such a rare incident, an off-site emergency plan should be drawn up for the
following purpose.
1. To provide basic information about the risk and environmental impact assessment
related to the unit to local / district authorities, police, fire-brigade, surrounding
units, and the general public. To appraise them of consequences and the protection
/ prevention measures and control actions and to seek their help to communicate
with public in case of a major emergency. The information from all industries shall
enable district authorities to educate public about what could go wrong, and to train
them of measures to be taken as an individual.
2. To enable district authorities to prepare the off-site emergency plan (contingency)
for the district or particular area and to organize rehearsals and initiate actions
learnt from these incidents.
Our Emergency Plan shall be made after considering the all possible effects of incidents on
the neighboring population and the remedial measures will be devised in consultation with
the local authorities and emergency services.
6.6 OCCUPATIONAL HEALTH AND SAFETY
Details of possibilities of occupational health hazards from the proposed manufacturing
activities and proposed measures to prevent them
DICFC is having Health & Hygiene SOP to develop a health and hygiene control program for
the persons on board to ensure that all potential health hazards in work environment are
recognized, evaluated and controlled.
Page 96
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 259
Health & Hygiene is to provide and implement a documented procedure for conducting and
reporting site industrial hygiene risk assessment in order to identify and evaluate potential
community health risks resulting from exposure to physical, chemical, biological,
psychological (i.e. mental stresses) and physiological (i.e. physical stress or ergonomic risk
factors) hazards, as required by the HSE department for identifying and reporting hazards
and mitigating HSE risks, and the HSE Conservation policy for taking foremost account of
employees’ health.
This procedure covers the methodology used for site Industrial Health Hygiene assessment
activities in plant and facilities. The procedure may include desk top review, walk-through
survey and/or exposure assessment, or any combination of these methods. The assessment
activities shall include identifying hazardous tasks or activities, sources of hazardous agents
and potentially exposed workers, followed by evaluating the controls used to prevent or
minimize the exposure, assessing the level(s) of health effects with the associated exposure,
rating the hazards so that the higher risks are addressed first, and recommending additional
controls for preventing or minimizing exposure, as appropriate.
Procedure:
The Health and Hygiene coordinator (EHS Person / Medical Officer), identify and evaluate
occupational health and industrial hygiene hazards that exists in DIC Fine Chemicals Pvt.
Ltd., operations through a structured approach via systematic inspections. The structured
approach can include:
• Review of work activities for all occupations.
• Review of task analysis and technical surveys.
• Review of hazards identified in planned inspections and reported hazards.
• Applicable regulations, legislation, codes and standards.
• Interviews with employees and managers.
These identification surveys are conducted once every year and/ or after major modification
of installation facilities which may result in occupational health and hygiene hazards.
Page 97
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 260
The surveys particularly address the identification and evaluation of the following
occupational health and hygiene hazards:
• Noise Hazards.
• Vibration Hazards.
• Stress related Hazards.
Health Hazard Control
The MR will constitute a team of officers and staff supported by medical officer, which will
• Prioritize the hazards based on their risk potential.
• Identify specific work groups affected by each hazard.
• Determine the controls required to manage these identified hazards. The cost of
each identified control versus benefits of its implementation may be evaluated.
• Develop an action plan identifying
• Work to be done
• Person responsible to complete the work
• target dates of completion
• Develop a follow up system to ensure the action plan is accomplished.
Health Care
The health and hygiene of the personnel at DICFC, Dahej is monitored through periodic
health checks of the persons. All employees undergo a periodic medical examination once in
year. This medical examination focuses on individual medical surveillance of all types of
health hazards covering both occupational and non-occupational issues.
First Aid
First aid boxes are provided at different strategic locations in Site and are regularly checked
for the consumptions by Fire & Safety department in co-ordination with Medical Officer.
Page 98
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 261
Occupational Health of Workers
Noise
Noise will be regularly monitored both at plant boundary for checking compliance against
environmental noise parameters issued by the CPCB. It will also be monitored near noise
generating equipment to ensure that all noise generating equipment do not emit noise in
excess of 85 db (A) 1.0 m from source. All workmen will be provided with required set of
PPEs like ear plug, ear muff etc. where noise levels in excess of 80 db (A) are regularly
generated. Preventive maintenance of noise generating equipment shall be regularly carried
out to ensure that noise levels are minimized to the extent possible. To the extent feasible,
equipment will be purchased considering noise generation as one of the parameters.
Heat
The project does not envisage conditions that could lead to excessive heating.
Consequently, special requirements for protection against heat stress are not anticipated.
However, the following shall be carried out:
• Ventilation shall be provided to take care of heat evacuation. An air-exchange ratio
(ACH: Air changes per hour) of at least 6 will be maintained at all times.
• Drinking water availability shall be ensured at several locations within the plant to
ensure workers have easy access to the same.
• In case of occasional handling of heated equipment or materials, suitable PPEs such as
heat resistant gloves will be used.
Dust, other Chemicals and metals being suspended in the environment
The possibility of suspended particles going into the body of the workmen, either in the
form of inhalation, ingestion or through skin absorption are least and negligible because the
entire operation at the plant will be performed under closed loop condition, right from
charging till discharging, hence it’s a rare possibility that the workmen will come in direct
contact with raw material or final goods, At the same time the level of SPM and RPM will
definitely be of least and nominal value. But even though the same will be under closed
monitoring and periodical surveillance as per GPCB norms and applicable legislations and
any minor deviation from the same will be dealt with immediately and will be corrected.
Page 99
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 262
Further to this all of the workmen will be provided with complete set of appropriate PPEs,
like nose musk / nose respirator, gloves, hard hat or cap, protective uniform and clothing,
eye protections etc.
Steps taken to avoid Musculoskeletal Disorder (MSD), backache, pain in major and minor
joints, fatigue etc.
In past ergonomic studies were carried out at most MSD prone activities / places like ink
filling and raw material charging but associated risk level have been found to be very low.
But in-spite of this as mentioned, the entire new set up will be having the facility of
automation and least involvement of manual handling hence chances of MSD are going to
be almost nil. Further to this some activities like raw material carriage, storage, issuance,
charging etc, all those might lead MSD will also be done through improvised manner by use
of latest / automated lifting and handling equipments, hence the possibility of MSD in these
cases also doesn’t exists.
Occupational Hazards specific pre-placement and periodical monitoring
As per policy and norms all of the workmen are put to medical examination and testing
periodically and at set interval and based on the medical report actions are taken, if at all
anything is necessary and required. Even based on the medical examination report /
feedback, workmen are counseled and put in different area / job rotation kind of activities
For large industries, where multifarious activities are involved during construction, erection,
testing, commissioning, operation and maintenance; the men, materials and machines are
the basic inputs. Along with the boons, industrialization generally brings several problems
like occupational health and safety. The industrial planner, therefore, has to properly plan
and take steps to minimize the impacts of industrialization and to ensure appropriate
occupational health and safety including fire plans. All these activities again may be
classified under construction and erection, and operation and maintenance.
Page 100
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 263
6.6.1 OCCUPATIONAL HEALTH
Occupational health needs attention both during construction & erection and operation &
maintenance phases. However, the problem varies both in magnitude and variety in the
above phases.
6.6.1.1 CONSTRUCTION AND ERECTION
The occupational health problems envisaged at this stage can mainly be due to
constructional accident and noise. To overcome these hazards, in addition to arrangements
to reduce it within TLV's, necessary protective equipments shall be supplied to workers.
6.6.1.2 OPERATION AND MAINTENANCE
The problem of occupational health, in the operation and maintenance phase is primarily
due to noise which could affect consultation. The necessary personal protective equipments
will be given to all the workers. The working personnel shall be given the following
appropriate personnel protective equipments.
• Industrial Safety Helmet;
• Face shield
• Zero power plain goggles with cut type filters on both ends;
• Zero power goggles with cut type filters on both sides and blue color glasses;
• Welders equipment for eye and face protection;
• Cylindrical type earplug;
• Ear muffs;
• Canister Gas mask;
• Self contained breathing apparatus;
• Leather apron;
• Aluminized fiber glass fix proximity suit with hood and gloves;
• Boiler suit;
• Safety belt/line man's safety belt;
• Leather hand gloves;
• Asbestos hand gloves;
Page 101
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 264
• Acid/Alkali proof rubberized hand gloves;
• Canvas cum leather hand gloves with leather palm;
• Lead hand glove;
• Electrically tested electrical resistance hand gloves; and
• Industrial safety shoes with steel toe.
6.6.1.3 HOSPITAL FACILITIES
It is proposed that client will make formal agreements with nearby hospital having facilities
to attend fire and toxic effect cases for attending the affected persons in the emergency
arising out of accidents, if any.
6.6.1.4 FACTORY MEDICAL OFFICER
A qualified doctor is appointed as FMO on visiting basis. Apart from him, Paramedical Staff is
employed.
6.6.1.5 PROPOSED FACILITY TO BE MADE AVAILABLE AT OHC
One Room is proposed to be provided to be operated as OHC. The centre will be equipped
with following medical equipments:—
1. Examination Table
2 Dressing Tables For performing Dressing
3. Glucometer For measurement of Blood Sugar
4 Vision chart To evaluate vision acuity
5. Nebuliser For relieving coughs & Breathing Difficulty
6. Infra red light for relieving muscular pain
7. Suction machine For cleaning airway
8. Autoclave machine For sterilizing cotton &dressing material
9. Weighing Machine For measuring body weight
10. Medical Oxygen Cylinder kit
11. Sphygmomanometer To measure blood pressure
12. Refrigerator To preserve medicines
13. Thermometer
Page 102
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 265
6.6.1.6 AMBULANCE VAN
An ambulance van is proposed to be made available 24 hours at Fire Station.
6.6.1.6 FIRST AID BOX
First Aid Boxes are proposed to be made available at the different location in the plant,
Training to be given to employees for First Aid.
6.6.1.7 PERIODIC MEDICAL EXAMINATION
It is proposed that client will ensure that…
(1) Workers employed shall be medically examined by a qualified medical practitioner/
Factory Medical Officer, in the following manner:
(a) Once in a period of 6 months, to ascertain physical fitness of the person to do the
particular job;
(b) Once in a period of 6 months, to ascertain the health status of all the workers in respect
of occupational health hazards to which they are exposed and in cases where in the opinion
of the Factory Medical Officer it is necessary to do so at a shorter interval in respect of any
workers;
© In periodic and pre-medical examinations, various parameters will be checked. Viz., LIVER
FUNCRION TESTS, Chest X-rays, Audiometry, Spirometry, Vision testing (Far & Near vision,
color vision and any other ocular defect) ECG and other parameters as will be found
necessary as per the opinion of Factory Medical officer.
(2) No person shall be employed for the first time without a certificate of granted by the
Factory Medical Officer.
6.6.1.8 EMP FOR THE OCCUPATIONAL SAFETY & HEALTH HAZARDS SO THAT SUCH
EXPOSURE CAN BE KEPT WITHIN PERMISSIBLE EXPOSURE LEVEL (PEL)/THRESHOLD
LEVEL VALUE (TLV) SO AS TO PROTECT HEALTH OF WORKERS
1. It is proposed to formulate and implement an EMP for Occupational Safety and Health
with following aims…
• To keep air-borne concentration of toxic and hazardous chemicals below PEL and TLV.
• Protect general health of workers likely to be exposed to such chemicals
Page 103
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 266
• Providing training, guidelines, resources and facilities to concerned department for
occupational health hazards.
• Permanent changes to workplace procedures or work location to be done if it is found
necessary on the basis of findings from workplace Monitoring Plan.
2. It is proposed that this EMP be formulated on the guidelines issued by Bureau of Indian
Standards on OH&S Management Systems: IS 18001:2000 Occupational Health and
Safety Management Systems
3. Proposed EMP will be incorporated in Standard Operating Procedure also.
4. The proposed EMP will also include measure to keep air-born concentration of toxic
and hazardous chemicals below its PEL and TLV, like…
a. Leak Surveys
b. Separate storage for toxic chemicals
c. Exhaust Ventilation
d. Proper illumination
e. On-line detectors toxic chemicals like Chlorine and Bromine
f. Close processes to avoid spills and exposures
g. Atomization of process operations to hazards of manual handling of chemicals
h. Supply of proper PPEs like Air mask, Berating canisters, SCBA sets, On-line breathing
apparatus at the places where there is possibility of presence of toxic chemicals
i. Decontamination procedure for empty drums and carboys.
j. Regular maintenance program for pumps, equipment, instruments handling toxic and
corrosive chemicals
k. Display of warning boards
l. Training to persons handling toxic and corrosive chemicals
5. Workplace Monitoring Plan
• It is proposed that a Workplace Monitoring Plan to be prepared & implemented in
consultation with FMO and industrial hygienists.
• Each workplace must be evaluated to identify potential hazards from toxic substances
or harmful physical agents. Air-borne concentration of toxic chemicals will be measured
and record will be kept.
• The current state-of-the-art exposure measurement model is as follows: For purposes of
measuring worker exposure across a single shift it is sufficient t o place a reasonably
accurate exposure measuring device on the worker , within t he worker ’s breathing
Page 104
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 267
zone, and have it operate for nearly the full shift. Client has been proposed to study the
exposure data when the plant is operative.
6. Health Evaluation of Workers
1. It is proposed that management will device a plan to check and evaluate the exposure
specific health status evaluation of workers
2. Workers will be checked for physical fitness with special reference to the possible health
hazards likely to be present where he/she is being expected to work before being
employed for that purpose. Basic examinations like Liver Function tests, chest x ray,
Audiometry, Spirometry Vision testing (Far & Near vision, color vision and any other
ocular defect) ECG, etc. will be carried out. However, the parameters and frequency of
such examination will be decided in consultation with Factory Medical Officer and
Industrial Hygienists.
3. While in work, all the workers will be periodically examined for the health with specific
reference to the hazards which they are likely to be exposed to during work. Health
evaluation will be carried out considering the bodily functions likely to be affected
during work. The parameters and frequency of such examination will be decided in
consultation with Factory Medical Officer and Industrial Hygienists. Plan of monthly and
yearly report of the health status of workers with special reference to Occupational
Health and Safety.
6.6.1.9 MEDICAL SURVEILLANCE PROGRAM
Pre-employment Medical Check Up
1. Chest X-ray
2. Cardiogram
3. Audiometry
4. Hematological Examination:- CBC, SGOT, SGPT, Cholesterol, Blood Sugar etc
5. Urine Examination
6. Vision test
7. Colour blindness test
8. Lung function test- Spirometry
Periodical Medical Check up
1. Lung Function test
2. Cardiogram
3. Audiometry
4. Hematological Examination
5. Urine examination
6. Vision test
7. Colour blindness test
8. Biomarker in Blood & Urine
Page 105
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 268
6.6.2 SAFETY PLAN
Safety of both men and materials during construction and operation phases is of concern.
Safety plan shall be prepared and implemented in the proposed project activity. The
preparedness of an industry for the occurrence of possible disasters is known as emergency
plan. The disaster in the plant is possible due to collapse of structures and fire/explosion etc.
• The proposed project would formulate safety policy keeping in view the safety
requirement during construction, operation, maintenance phases, with the following
regulations:
• To allocate sufficient resources to maintain safe and healthy conditions of work;
• To take steps to ensure that all known safety factors are taken into account in the design,
construction, operation and maintenance of plants, machinery and equipment;
• To ensure that adequate safety instructions are given to all employees;
• To provide wherever necessary protective equipment, safety appliances and clothing and
to ensure their proper use;
• To inform employees about materials, equipment or processes used in their work which
are known to be potentially hazardous to health or safety;
• To keep all operations and methods of work under regular review for making necessary
changes from the point of view of safety in the light of experience and up to date
knowledge;
• To provide appropriate facilities for first aid and prompt treatment of injuries and illness
at work;
• To provide appropriate instruction, training, retraining and supervision to employees in
health and safety, first aid and to ensure that adequate publicity is given to these
matters;
• To ensure proper implementation of fire prevention methods and an appropriate fire
fighting service together with training facilities for personnel involved in this service;
• To organize collection, analysis and presentation of data on accident, sickness and
incident involving people injury or injury to health with a view to taking corrective,
remedial and preventive action;
• To promote through the established machinery, joint consultation in health and safety
matters to ensure effective participation by all employees;
• To publish/notify regulations, instructions and notices in the common language of
employees;
• To prepare separate safety rules for each type of occupation/processes involved in a
plant; and
Page 106
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 269
• To ensure regular safety inspection by a competent person at suitable intervals of all
buildings, equipments, work places and operations.
6.6.3 SAFETY ORGANIZATION
Construction and Erection Phase
A qualified and experienced safety officer shall be appointed. The responsibilities of the
safety officer include identification of the hazardous conditions and unsafe acts of workers
and advice on corrective actions, conduct safety audit, organize training programs and
provide professional expert advice on various issues related to occupational safety and
health. He is also responsible to ensure compliance of Safety Rules/ Statutory Provisions.
Operation and Maintenance Phase
When the construction is completed the posting of safety officers shall be in accordance
with the requirement of Factories Act and their duties and responsibilities shall be as
defined there of.
6.6.4 SAFETY CIRCLE
In order to fully develop the capabilities of the employees in identification of hazardous
processes and improving safety and health, safety circles would be constituted in each area
of work. The circle would consist of about five to six employees from that area. The circle
normally shall meet for about an hour every week.
6.6.5 SAFETY TRAINING
Safety training shall be provided by the Safety Officers with the assistance of faculty
members called from Professional Safety Institutions and Universities. In addition to regular
employees, limited contractor labors shall also be provided safety training. To create safety
awareness safety films shall be shown to workers and leaflets shall be distributed.
Some precautions and remedial measures proposed to be adopted to prevent fires are:
• Compartmentalization of cable galleries, use of proper sealing techniques of cable
passages and crevices in all directions would help in localizing and identifying the area of
occurrence of fire as well as ensure effective automatic and manual fire fighting
operations;
Page 107
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 270
• Spread of fire in horizontal direction would be checked by providing fire stops for cable
shafts;
• Reliable and dependable type of fire detection system with proper zoning and interlocks
for alarms are effective protection methods for conveyor galleries;
• Housekeeping of high standard helps in eliminating the causes of fire and regular fire
watching system strengthens fire prevention and fire fighting; and
• Proper fire watching by all concerned would be ensured.
6.6.6 HEALTH AND SAFETY MONITORING PLAN
The health of all employees shall be periodically monitored for early detection of any
ailment due to exposure to heat and noise.
6.7 TRAINING, REHERASAL & RECORDS
6.7.1 NEED OF TRAINNING & REHEARASAL
Training is important in order to –
• Teach worker’s how to handle chemicals safely, how to act as a runner/messenger, how
to use PPE, how to start and shut down the plant, how to carry out emergency repairs
etc.
• Teach one to be a safe and alert worker.
Rehearsal is essential for -
• Explaining and making key personnel and essential workers aware of their role in case of
an emergency.
• Testing the emergency procedure, emergency arrangements and ability of all involved
with it to grasp the procedure and implement the same.
• Testing the effectiveness of communication system including the alternative
arrangement in case of failure.
• Testing the speed of mobilization of resources, search, rescue and treatment of
casualties, emergency isolation and shut down.
• Detecting the shortcomings in the emergency plan and incorporating remedial measures.
Page 108
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 271
• Allowing professional emergency services to test their parts of the plan and testing co-
ordination.
• Building confidence in workers which is helpful in facing real situations.
Training shall be given to regular employees and contract personnel also. Effective and
latest teaching aids will be used to train workers and supervisory staff. Such training courses
shall be conducted once in a year and co-ordination with offsite personnel shall be sought
during such training. Records will be maintained for training.
6.7.2 SOME CHECK POINTS
Following points can be checked at the time of training/assessing the adequacy of the
Emergency Plan.
� Does the plan cover the range of incidents that can realistically be anticipated?
� Have the consequences of the various incidents considered been adequately assessed?
� Are there sufficient resources in terms of personnel and equipment on the site to carry
out the Emergency Plan for the various incidents in conjunction with the public
emergency services?
� Have the time scales been assesses correctly?
� Is there a logical sequence of actions for each person given a role in the plan? Whether
key personnel, especially the nominated incident controllers, consulted in the
preparation of the plan?
� Is there 24 hours cover, to take account of absences due to sickness and holidays,
minimum shift manning, operator only periods, silent hours, shutdown periods, only
security personnel being present, or for unmanned sites etc.?
� Is there satisfactory co-operation with the local emergency services and district
emergency planning officers?
� At sites where an off-site plan to protect people and the environment outside the site in
the event of an incident is appropriate what is the procedure for initiating the off-site
plan and is this satisfactory?
Page 109
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 272
6.7.3 RECORDS AND UPDATING THE PLAN
All records of On-Site and Off-Site Emergency Plan and modifications by experience and
suggestion, the rehearsals and conclusions of such plans and the enquiries shall be well
maintained and preserved. The necessary data bank shall be also maintained for the utility
of industries and others. New information and the deficiencies identified during the
rehearsal is reviewed and incorporated in the document for continual up dating of the plan
and such information shall be communicated to the concerned authorities.
6.8 HAZOP STUDY
6.8.1 OBJECTIVE
For identifying cause and the consequences of perceived mal operations of equipment and
associated operator interfaces in the context of the complete system. It accommodates the
status of recognized design standards and codes of practice but rightly questions the
relevance of these in specific circumstances where hazards may remain undetected.
6.8.2 PURPOSE OF HAZOP
It emphasizes upon the operating integrity of a system, thereby leading methodically to
most potential and detectable deviations which could conceivably arise in the course of
normal operating routine
- including "start-up” and "shut-down" procedures
- as well as steady-state operations.
It is important to remember at all times that HAZOP is an identifying technique and not
intended as a means of solving problems nor is the method intended to be used solely as an
undisciplined means of searching for hazardous scenarios.
6.8.3 FEATURES OF HAZOP STUDY
Subsystems of interest line and valve, etc
Equipment, Vessels
Modes of operation Normal operation
Start -up mode
Shutdown mode
Maintenance /construction / inspection mode
Trigger events Human failure
Equipment /instrument/component failure
Supply failure
Emergency environment event
Page 110
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 273
Other causes of abnormal operation, including
instrument disturbance
Effects within plant Changes in chemical conditions
Changes in inventory
Change in chemical physical conditions
Hazardous conditions Release of material
Changes in material hazard characteristics
Operating limit reached
Energy source exposed etc.
Corrective actions Change of process design
Change of operating limits
Change of system reliability
Improvement of material containment
Change control system
Add/remove materials
How would hazardous During normal operation
Conditions detected? Upon human failure
Upon component failure
In other circumstances
Contingency actions Improve isolation
Improve protection
6.8.4 HAZOP STUDY PROCEDURE
• Procedure in HAZOP study consists of examining the process and instrumentation (P&I)
line diagram, process line by process line.
• A list of guide words is used to generate deviations from normal operation
corresponding to all conceivable possibilities.
• Guide words covering every parameter relevant to the system under review i.e. flow
rate and quality, pressure, temperature, viscosity, components etc.
• Flowchart for application of HAZOP is shown in figure.
Page 111
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 274
HAZOP STUDY FLOW CHART
Page 112
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 275
GUIDE WORDS
NONE No forward flow when there should be
MORE More of any parameter than there should be, e.g. more
flow, more pressure, more temperature, etc.
LESS As above, but "less of" in each instance
PART System composition difference from what it should be
MORE THAN More "components" present than there should be for
example, extra phase, impurities
OTHER What needs to happen other than normal operation, e.g.
start up, shutdown, maintenance?
NONE e.g., NO FLOW caused by blockage; pump failure; valve
closed or jammed: leak: valve open; suction vessel empty;
delivery side over - pressurized: vapor lock; control failure
REVERSE e.g., REVERSE FLOW caused by pump failure: NRV failure or
wrongly inserted; wrong routing; delivery over pressured;
back- siphoning; pump reversed
MORE OF e.g., MORE FLOW caused by reduced delivery head ; surging
; suction pressurized ; controller failure ; valve stuck open
leak ; incorrect instrument reading.
MORE OF MORE TEMPERATURE, pressure caused by external fires;
blockage ; shot spots; loss of control ; foaming; gas release;
reaction; explosion; valve closed; loss of level in heater; sun.
LESS OF e.g., LESS FLOW caused by pump failure; leak; scale in
delivery; partial blockage ; sediments ; poor suction head;
process turndown.
LESS e.g., low temperature, pressure caused by Heat loss;
vaporization; ambient conditions; rain; imbalance of input
and output; sealing; blocked vent.
PART OF Change in composition high or low concentration of mixture;
additional reactions in reactor or other location; feed
change.
MORE THAN Impurities or extra phase Ingress of contaminants such as
air, water, lube oils; corrosion products; presence of other
process materials due to internal leakage ; failure of
isolation ; start-up features.
OTHER Activities other than normal operation start-up and
shutdown of plant ; testing and inspection ; sampling ;
maintenance; activating catalyst; removing blockage or scale
; corrosion; process emergency ; safety procedures activated
; failure of power, fuel, steam , air, water or inert gas;
emissions and lack of compatibility with other emission and
effluents.
Page 113
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 276
6.8.5 PROCESS HAZARD AND ITS CONTROL
Parameter Guide
Word
Name of
hazardous
process
and
operation
Possible causes Possible
consequences
Measures
safeguard
Action Require
Distillation
More Good Heating 1. No process hazards.
It is part of the
requirement.
2. It will accelerate
the distillation
process.
Temp.
Less Poor Heating No distillation will
take place. Process
delayed.
More Not Possible -- Pressure
Less Not Possible --
More Not Possible --
1. Temperature
gauge &
pressure
gauge
provided.
2. Sight glass
provided.
3. Safety valve
provided .
4. Cooling &
chilling
arrangement
with
alternative
provided.
1. Non return Valve to be provided.
2. Arrow indicator to be provided on
pipeline.
3. Stand by pump to be provided.
4. Pump, storage tank & pipe line
identification to be done.
5. Color code to be provided.
6. Periodic checking of the condenser
to be followed.
Flow
Power
Failure
Distillation
No GEB Supply Distillation will not
achieve.
D.G.Set
provided.
Raw material to the storage tank ( Day Tank ) - Transferring
No 1. No material
in the
storage tank.
2. Pump
tripped.
3. Pump
discharge
valve closed.
4. Heavy
leakage in
pipe line or
chocking the
pipeline.
No material to service
tank.
Pressure gauge
provided on the
pump discharge
valve.
pipeline
arrangement
with alternative
provided.
1. Non-returnable Valve to be
provided.
2. Arrow indicator to be provided on
pipeline.
3. Stand by pump to be provided.
4. Pump, storage tank & pipe line
identification to be done.
5. Color code to be provided.
6. Work permit procedure to be
followed for handling of
hazardous chemicals.
7. PPE compliance to be followed
during handling of acid.
More 1. Valve
opened
more than
set value
2. Human
Error.
More material to the
service tank.
Reverse Not possible
Flow
Pressure
Less
Transferrin
g of Raw
material to
the Storage
Tank
SOP to be prepared.
Page 114
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 277
Transferring of Raw material from storage tank to Process vessel
More 1. Seasonal effect
2. Poor insulation
of pipeline.
3. Falling of hot
water on
uninsulated
line.
4. Incoming
material from
storage tank
itself has high
temperature.
1. More pressure in the
pipeline may give rise
to leakage.
2. From poor flange
joints, valve. Fire &
health hazards.
Insulation on
pipeline &
batch tank
provided.
1. Considering this
sufficient quantity of
water shall be ensured.
2. All flange joints shall be
checked regularly.
Temp.
Less 1. Seasonal effect
2. Leakage of
chilled water
from tank.
No workplace Hazards. Safety valve
provided on
batch tank.
More 1. N2 pressures
more.
2. Valve failure
3. FIC mal
function.
4. Human error.
1. Pressure rise in batch
tank.
2. Leakage in flange joint.
3. Safety valve of batch
tank may popup.
4. Tank filling operation
completed in less
time.
Pressure gauge shall be
provided on batch tank.
Pressure
Less 1. Low pressure of
N2 itself.
No safety hazards but it will
take more time for filling
operation.
More Same as
Pressure
Same as Pressure Same as Pressure
Less 1. Choking in the
excess flow
valve. (Holes are
choked.)
2. Low pressure of
N2 itself.
3. Valve choked.
No safety hazards but it will
take more time for filling
operation.
Flow
Reverse
Transferri
ng of Raw
material
from the
Storage
Tank to
Process
Vessel
No chances 1. NRV
provided.
2. Auto shut
off valve
provided.
Page 115
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 278
Transferring of Raw material from storage tank to Process vessel
More 5. Seasonal
effect
6. Poor
insulation of
pipeline.
7. Falling of hot
water on
uninsulated
line.
8. Incoming
material
from storage
tank itself
has high
temperature
.
3. More pressure in
the pipeline may
give rise to
leakage.
4. From poor flange
joints, valve. Fire
& health
hazards.
Insulation on
pipeline & batch
tank provided.
3. Considering this sufficient
quantity of water shall be
ensured.
4. All flange joints shall be checked
regularly.
Temp.
Less 3. Seasonal
effect
4. Leakage of
chilled water
from tank.
No workplace
Hazards.
Safety valve
provided on
batch tank.
More 5. N2 pressures
more.
6. Valve failure
7. FIC mal
function.
8. Human
error.
5. Pressure rise in
batch tank.
6. Leakage in flange
joint.
7. Safety valve of
batch tank may
popup.
8. Tank filling
operation
completed in less
time.
Pressure gauge shall be provided on
batch tank.
Pressure
Less 2. Low
pressure of
N2 itself.
No safety hazards but
it will take more time
for filling operation.
More Same as
Pressure
Same as Pressure Same as Pressure
Less 4. Choking in
the excess
flow valve.
(Holes are
choked.)
5. Low
pressure of
N2 itself.
6. Valve
choked.
No safety hazards but
it will take more time
for filling operation.
Flow
Reverse
Transferri
ng of Raw
material
from the
Storage
Tank to
Process
Vessel
No chances 3. NRV
provided.
4. Auto shut off
valve
provided.
Page 116
M/s. DIC FINE CHEMICALS PVT. LTD. ENVIRONMENT IMPACT ASSESSMENT REPORT
Prepared By: Aqua-Air Environmental Engineers Pvt. Ltd., Surat 279
6.8.6 PLANNING FOR HAZOP
• Safety procedures documents
• Relief/venting philosophy
• Chemical involved
• Piping specifications
• Carry out the study
• Record the results
• Follow-up of actions noted
1. Final report contains resolution of all recommended actions.
2. Must appoint someone as leader to check progress of action.
3. Team may meet again if answers to questions do not simply lead to an action.
Team may meet again if significant design changes in interim report.