This report is solely for the use of Sidel Group personnel. No part of it may be circulated, quoted, or reproduced for distribution outside Sidel Group organization without its prior approval. This material was used by Sidel Group during an oral presentation; it is not a complete record of the discussion. Engineering & Conveying MOVIGEAR Technical Rules & Recommendation January 2010
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
This report is solely for the use of Sidel Group personnel. No part of it may be circulated, quoted, or reproduced for distribution outside Sidel Group organization without its prior approval. This material was used by Sidel Group during an oral presentation; it is not a complete record of the discussion.
Engineering & Conveying
MOVIGEARTechnical Rules & Recommendation
January 2010
May 2007 x Sidel Group Presentation x 2/X
Engineering & Conveying
E&C Network Architecture with Movigear
May 2007 x Sidel Group Presentation x 3/X
Engineering & Conveying
SNI-Movigear Network Architecture
SEWMovifit-SNI
SEW Movigear-SNI
SEW Gateway
PLC
Standard Ethernet UDP protocolcommunication Managed by SEW Gateway
Profibus DP or DeviceNetStandard PLC Field Bus communication
Ethernet Powerlan Powerline Communication Managed by SEW
Ethernet SWITCHStandard Ethernet Device
Electrical Panel (IP20 area)
Field (IP65 area)
Installation rules = standard for Ethernet
Installation rules = Specific SEW-SNI
SWITCH is recommended for maintenance and configuration via MOVITOOLS Motion Studio software
May 2007 x Sidel Group Presentation x 4/X
Engineering & Conveying
SEW Gateway – Field Bus / Ethernet UDP
IN = Field Bus:
• Profibus
• DeviceNetOUT = Ethernet UDP for Movifit SNI
• Communication managed by SEW GatewayMaximum 2 Movifit-SNI connected to 1 GatewayGateway protection = IP20 (panel device)
Profibus DP
Standard Ethernet UDP protocolcommunication Managed by SEW Gateway
Maximum 2 Movifit-SNI per Gateway
SEW Gateway Ref: UFF41B\OMG42B\UOH21B
May 2007 x Sidel Group Presentation x 5/X
Engineering & Conveying
SNI-Movigear wiring topology
Only ONE SNI Line bellow one Movifit-SNI SEW recommended to do a "classic" line topology
Only 1 "classic" line topology NO 2nd Line possible
Movifit-SNI
Movigear-SNI
May 2007 x Sidel Group Presentation x 6/X
Engineering & Conveying
SNI-Movigear topology & rules
Maximum 10 MOVIGEAR connected to one Movifit-SNIMaximum length SNI Line = 100m
100m is the Max cable length between Movifit-SNI and last Movigear connected to this Movifit-SNI.
Maximum load per SNI = 20A SNI-Movigear power cable = Double screened cable
Maximum 100m
1 2 3 10 Maximum 10 MOVIGEAR
Maximum 20 Amps (total load SNI line)(MGF2 = 1,53A and MGF4 = 2,77A at Max load)
Movifit-SNI
Movigear-SNI
4G4mm² Double Screened cable
May 2007 x Sidel Group Presentation x 7/X
Engineering & Conveying
SNI-Movigear cable specification
SEW recommended to use a double screened cable for SNI-lineCable recommended by SEW or at least the technical data the cable must fulfil
Cable installed by SIDEL at Drinktec Fair (variant)
HELUKABEL Ref: 22086
HELUKABEL Ref: 22236
May 2007 x Sidel Group Presentation x 8/X
Engineering & Conveying
MOVIFIT® SNI Housing construction
Solid aluminium die cast housing
Separate electronics for quick replacement and quick maintenance:
• EBOX: Encapsulated electronics unit
• ABOX: Passive connection section
Closing mechanism – with only one screw
• EBOX is plugged onto the ABOX
• ABOX is a large plug !!
Electronics can be replaced quickly
12 DI (Digital Input)
4 DI/DO (Digital Input or Output)
LED display for unit status and I/O, window shield can be labelled
* MGF4 = Not in standard catalogue (special version for Aqmax available by SEW)
All Movigear to be ordered with EXTENDED SPEED CONTROL RANGE (1 to 2000rpm)
Conveyor Sprocket Type
This report is solely for the use of Sidel Group personnel. No part of it may be circulated, quoted, or reproduced for distribution outside Sidel Group organization without its prior approval. This material was used by Sidel Group during an oral presentation; it is not a complete record of the discussion.