T Cam Switches, P Motor Disconnect Switches Overview Cam Switches, Motor Disconnect Switches Moeller Electric Corporation T Cam Switches, P Motor Disconnect Switches Page Overview of functions 07/002 Technical overview 07/004 System overview 07/006 Key to type references, modular system 07/010 Single-phase switches Motor disconnect switches 07/012 On-Off switches 07/014 Emergency-Stop switches 07/016 Change-over switches 07/018 Three-phase switches Motor disconnect switches 07/020 On-Off switches 07/024 Change-over switches 07/028 Reversing switches 07/030 Star-delta switches 07/030 Multi-speed switches 07/032 Control switches Stepping switches 07/034 On-Off switches 07/038 Change-over switches 07/038 Hand-Off-Auto switches 07/040 Spring-return switches 07/042 Multi-purpose switches 07/044 Instrumentation selector switches 07/046 Switches with locking arrangements Panic switches 07/048 On-Off switches 07/048 Hand/Auto switches 07/050 Accessories Front plates 07/052 Key operators 07/056 Other accessories 07/058 Tripping Characteristics 07/071 Technical Data 07/072 Dimensions 07/076 Ordering non-standard switches 07/087 07/001 1-866-595-9616 1-630-595-9515 Go to: http://www.klocknermoeller.com
90
Embed
Moeller Electric Corporation 07/001 T Cam Switches, P ... · c m System overview Reversing switches Control switches Multi-purpose switches Key operators T Cam Switches, P Motor Disconnect
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
T Cam Switches, P Motor Disconnect SwitchesOverview
Cam
Sw
itch
es,
Mot
orD
isco
nnec
tSw
itch
es
Moeller Electric Corporation
T Cam Switches, P Motor Disconnect Switches
PageOverview of functions 07/002Technical overview 07/004
Base mounting with cover (.../IVS) 1Front IP 30Additional front protection when panel door is openIdeal for switches mounted internally in larger panelsCan be either panel mounted with screws or clipped on DIN rail to EN 50 022Switch can accommodate up to 11 contact chambers (T0 switch only)
a page 07/017
Base mounting (.../Z) 2Can be either panel mounted with screws or clipped on DIN rail to EN 50 022 (T0 or T3)Can be equipped with knobs or padlockable handlesCoupling drive mounts in door or coverField-wiring terminals accessible from front.
a page 07/017
Base mounting motor disconnect switches (.../V/SVB)
2
Padlockable handle, black or red-yellow (Emergency-Stop)OFF position lockable with up 3 padlocksMeets IEC/EN 60 204 (main disconnectors, Emergency-Stop switches) and IEC/EN 60 947-3 (switch-disconnectors), up to 8 circuits for T0-..., up to 12 circuits for T3-...UL listed / CSA certified motor disconnect switches per NECCover interlocked when switch is in the ON position
a page 07/013
Cover mounting (.../E) 3For mounting in covers, doors or walls of control panelsField-wiring terminals accessible from back for easy accessFinger and back of hand safe design
a page 07/016
Cover mounting motor disconnect switches (.../EA/SVB)
3
Padlockable handle, black or red-yellow (Emergency-Stop)OFF position lockable with up 3 padlocksMeets IEC/EN 60 204 (main disconnectors, Emergency-Stop switches) and IEC/EN 60 947-3 (switch-disconnectors), up to 8 circuits for T0-..., up to 12 circuits for T3-...UL listed / CSA certified motor disconnect switches per NEC
a page 07/012
Center mounting (.../EZ) 3Mounting in standard opening used by 22.5mm pilot devices (refer to Section 05, RMQ-Titan)Permits a “one person” assembly to save mounting timeIdeal for cam switches programmed for control circuit functions and mounted together with standard pilot devices in large control panel doors.
a page 07/017
Surface mounting enclosures (.../I...) 4Corrosion-resistant, insulating material enclosures, IP 65 Can be equipped with standard knobs or padlockable handles for main disconnect switch applicationsSurface mounting main disconnect switch-es in accordance with IEC/EN 60 204 and IEC/EN 60 947-3, T0-... up to 8 circuits, T3-... up to 10 circuitsLockable in the OFF position with up to 3 padlocksSuitable as surface mounted Emergency-Stop switches per IEC/EN 60 204, with red handle, yellow collar
a page 07/017
Main disconnect switch handles suitable for Emergency-OFF applications
5
Designed to meet the requirements of main disconnect switches per IEC/EN 60 204-1, VDE 0113-1Red padlockable handle with yellow collarLockable in OFF position with up to 3 pad-locks
a page 07/060
Main disconnect switch handle 6Designed to meet the requirements of main disconnect switches per IEC/EN 60 204, VDE 0113Black padlockable handle and collarLockable in the OFF position with up to 3 padlocks
a page 07/060
Standard knob handles suitable for Emergency-Stop applications
7
Designed to meet the requirements ofIEC/EN 60 204-1, VDE 0113-1Red handle with yellow nameplate
a page 07/060
Standard knob handles 8Designed to meet the requirements ofIEC/EN 60 204, VDE 0113Black handle with silver-colored name-plate
a page 07/060
Coupling drive 9Includes push-to-fit shaftLinking mechanism used in the conversion of a basic switch (T0(3)-.../...) into a base mounted version (T0(T3)-.../ZCan be stocked as spare part for T0(T3)-.../Z switchChanges a cover mounted switch (T5B-.../E) into a base mounted version (T5B-.../Z)Can be stocked as a spare part for the T5B-.../Z switch
a page 07/064
07/007
Type T0, T3 and T5B manually operated rotary cam switches can be used for a wide range of power switching and control circuit functions. The rotary cam / individual contact chamber design allows the switch to be easily configured to meet both simple and complex switching requirements. A variety of handles, enclosures and accessories further enable Type T switches to fulfill a number of more specific requirements. They offer many approval features:• UL listing, CSA certification as manual motor controllers and motor disconnect switches per the intent of the NEC and OSHA lock out/tag out
requirements.• Compliance with IEC/EN 60 204 as Main Disconnect and Emergency-Stop switches and conformity with 60 947-3 as Switch-disconnectors for
CE applications.• Finger and back-of-hand-safe design for enhanced protection in the workplace against shock hazards.
1-866-595-96161-630-595-9515 Go to: http://www.klocknermoeller.com
Type P1 and P3 switches are 2-position (On-Off), 90° rotary operated 3 phase manual motor controllers and disconnect switches rated up to 100A. A variety of handles, enclosures and accessories further enable Type P switches to fulfill a number of more specific requirements. They are ideally suited as Main Disconnect switches where load shedding functions are necessary for the application.The side mounted auxiliary contact module operates as late-make and early-break in relation to the main contacts to execute the load shedding task.They offer many additional approval features:• UL listing, CSA certificationas manual motor controllers and motor disconnect switches per the intent of the NEC and OSHA lock-out/tag-out requirements.• Compliance with IEC/EN 60 204 as Main Disconnect and Emergency-Stop switches and conformity to IEC/EN 60 947-3 as Switch-Disconnectors for CE applica-
tions.• Finger and back-of-hand-safe design for enhanced protection in the workplace against shock hazards.
07/008
1-866-595-96161-630-595-9515 Go to: http://www.klocknermoeller.com
Base mounting with cover (.../IVS) 1Front IP 30Additional front protection when panel door is openIdeal for switches mounted internally in larger panelsCan be either panel mounted with screws or clipped on DIN rail to EN 50 022P3-.../IVS can be padlocked in the OFF position
a page 07/017
Base mounting (.../Z) 2Front IP 65Can be either panel mounted with screws or clipped on DINrail to EN 50 022Can be equipped with knobs or padlock-able handlesCoupling drive mounts in door or coverField-wiring terminals accessible from front
a page 07/017
Base mounting main disconnect switches (.../V/SVB)
2
Padlockable handle, black or red-yellow (Emergency-Stop), rated NEMA 3R, 12, IP 65Off position lockable with up to 3 padlocksMeets IEC/EN 60 204 (main disconnectors, Emergency-Stop switches) and IEC/EN 60 947-3 (switch-disconnectors)UL listed / CSA certified motor disconnect switches per NECCover interlocked when switch is in the ON position
a page 07/013
Cover mounting (.../E) 3NEMA 3R, 12, IP 65For mounting in covers, doors or walls of control panelsField-wiring terminals accessible from back for easy accessFinger and back of hand safe design
a page 07/016
Cover mounting main disconnect switches (.../EA/SVB)
3
Padlockable handle, black or red-yellow (Emergency-Stop), rated NEMA 3R, 12,IP 65Off position lockable with up to 3 padlocksMeets IEC/EN 60 204 (main disconnectors, Emergency-Stop switches) and IEC/EN 60 947-3 ((switch-disconnectors)UL listed / CSA certified motor disconnect switches per NEC
a page 07/012
Center mounting (.../EZ) 3NEMA 3R, 12, IP 65 (P1 only)Mounting in standard opening used by 22.5mm pilot devices (refer to Section 05, RMQ-Titan)Permits a “one person” assembly to save mounting time
a page 07/017
Add-on modules 4Switching neutral pole (early-make) for 4-pole applications (predominantly in cer-tain IEC countries). The 4th pole switches in advance of the main power contacts.Auxiliary contact module HI11 (1 N.O. and 1 N.C.). The N.O. contact is designed to operate as a load-shedding contact: switches after the main contacts when turning ON and opens before when turn-ing OFF (late make/early break)Both modules feature finger-safe construc-tion
a page 07/062
Surface mounting enclosures (.../I...) 5Corrosion-resistant, insulating enclosures IP 65 Can be equipped with standard knobs or padlockable handles for main disconnect switch applicationsSurface mounting main disconnect switch-es in accordance with IEC/EN 60 204 and IEC/EN 60 947-3Lockable in the Off position with up to 3 padlocksSuitable as surface mounted Emergency-Stop switches per IEC/EN 60 204-1 with red handle, yellow collarNumber of possible add-on modules for enclosed switches: 1 for P1 switch; 2 for P3 switch
a page 07/017
Main disconnect switch handles suitable for Emergency-Stop applications
6
Designed to meet requirements ofIEC/EN 60 204-1, VDE 0113 part 1Red padlockable handle with yellow collarLockable in the Off position with up to 3 padlocks
a page 07/060
Main disconnect switch handles 7Designed to meet requirements of IEC/EN 60-204.Black padlockable handle and collarLockable in the Off position with up to 3 padlocks
a page 07/060
Standard knob handles suitable for Emergency-Stop applications
8
Designed to meet the requirements of IEC/EN 60 204-1, VDE 0113 part 1Red handle with yellow nameplate
a page 07/060
Standard knob handles 9Designed to meet the requirements of IEC/EN 60 204Black handle with silver-colored name-plate
a page 07/060
Coupling drive 10Includes push-to-fit shaftLinking mechanism used in the conversion of a basic switch into a base mounted ver-sion .../ZCan be stocked as a spare part for P1(P3)-.../Z switch
a page 07/064
07/009
Note: For information regarding the P3 switch listed as a molded case switch, please consult Moeller Electric.
1-866-595-96161-630-595-9515 Go to: http://www.klocknermoeller.com
T Cam Switches, P Motor Disconnect SwitchesKey to Type References, Modular System
Cam
Sw
itch
es,
Mot
or D
isco
nnec
t Sw
itch
esMoeller Electric Corporation
Using the modular system to convert the mounting form
Using the modular system to convert the mounting form of T5B
Rotary cam switches can be used in a wide range of applications and are just as suitable for switching motors as they are for control circuits. Applications include ON-OFF switches, motor disconnects, manu-al transfer switches, stepping switches, instrumenta-tion, etc. They function essentially as inexpensive “hard-wired” programmable controllers and are ex-tremely reliable.
Switches are made up of the following parts:• handle assembly• the basic switch body containing contact chambers
and handle position index• peripheral accessories
Each contact chamber in types T0, T3 and T5B switches features two contacts.
Our catalog “Rotary Switches T” (K 115) contains over 800 commonly used standard switching se-quences. The switches shown on the following pages of this section of our catalog are the more commonly used switches. K 115 is available upon request.
Type T rotary cam switches are free of any PCBs, fluoro-carbons, asbestos and silicon. Their contacts are cadmi-um-free.
Rated thermal current Front plate type(if different from standard)a page 07/054
Mounting forma page 07/005
Type suffix(if required)
Accessoriesa page 07/056
Circuit diagrams
on pages 07/012 – 053 and 07/074 – 082
Example:
(see also ordering sample page 07/087)Switch position 1:contact 1 – 2 opencontact 3 – 4 closed
Switching from 1 to 2:contact 1 – 2 closes with early-makecontact 3 – 4 opens with late break
Switching from 2 to 3:contact 1 – 2 opens briefly
Switching from 3 to 4:contact 1 – 2 remains closedautomatic return from 4 to 3
Type P1 and P3 switches are 2-position (ON-OFF), 90° rotary operated 3-phase manual motor control-lers and disconnect switches, rated from 20A up to 100A. They are all HP rated and ideally suited as mo-tor disconnect switches.
A side mounted auxiliary contact module operates as a late-make and early-break in relation to the main contacts to execute a load shedding task which is of-ten required in industrial applications.
Type P and (Type T cam) switches feature a finger and back of hand safe design for enhanced safety in the workplace.Type P manual controllers and disconnects are free of any PCBs, fluorocarbons, asbestos and silicon. Their contacts are cadmium-free.
Terminal designation
Customer connection
Link
1
2
3
4
0
1
2
3
4
1-2 3-4
07/011
Contact
1-866-595-96161-630-595-9515 Go to: http://www.klocknermoeller.com
Motor disconnect switches with load shedding auxiliary contact3 1 1 1 ½ 3 3 20 P1-25/... EA/SVB/HI11
091080I2/SVB/HI11-NA255888
V/SVB/HI11095826
EA/SVB-SW/HI11070194
I2/SVB-SW/HI11-NA255889
V/SVB-SW/HI11098199
2 3 5 30 P1-32/... EA/SVB/HI11072567
I2/SVB/HI11-NA255894
V/SVB/HI11015145
EA/SVB-SW/HI11012772
I2/SVB-SW/HI11-NA255895
V/SVB-SW/HI11017518
3 7 ½ 10 60 P3-63/... EA/SVB/HI11019891
I4/SVB/HI11-NA255901
V/SVB/HI11024637
EA/SVB-SW/HI11022264
I4/SVB-SW/HI11-NA255900
V/SVB-SW/HI11027010
5 10 15 100 P3-100/... EA/SVB/HI11029383
I5/SVB/HI11-NA255906
V/SVB/HI11034129
EA/SVB-SW/HI11031756
I5/SVB-SW/HI11-NA255907
V/SVB-SW/HI11036502
Notes: 1) Surface mounting enclosures are IEC type, totally insulated, corrosion-resistant rated IP 65, NEMA rated 3R, 12.2) All handles supplied in the above combinations are padlockable in the OFF position. Switches with red handles and yellow collars
(...SVB) are suitable as Emergency-Stop main disconnect switches per Machinery Directive Standard EN 60 204-1. In applications where the switch is not intended to fulfill the Emergency-Stop function, use black handle and collar (...SVB-SW).
3) All switches are UL listed and CSA certified as manual controllers, additionally evaluated as motor disconnects per the intent of NEC. All switches are in compliance with IEC/EN 60 947-3 (switch-disconnectors) and are CE marked. For IEC ratings consult Moeller Elec-tric.
4) All front plates shown may be exchanged at the time of the order at no extra charge. The prerequisite is that switching angles, the number of positions and the location of position 0 must be identical; a pages 07/052 and 053 for ordering details. English front plates supplied with the switches as shown in the catalog, can be exchanged for their French equivalent by adding the FS... number shown with suffix -F to the switch type (Example: T0-1-8200/EA/SVB-NA+FS908-F).
FS 908
ON
OFF
07/012 07/013
1-866-595-96161-630-595-9515 Go to: http://www.klocknermoeller.com
Motor disconnect switches with load shedding auxiliary contact3 1 1 1 ½ 3 3 20 P1-25/... EA/SVB/HI11
091080I2/SVB/HI11-NA255888
V/SVB/HI11095826
EA/SVB-SW/HI11070194
I2/SVB-SW/HI11-NA255889
V/SVB-SW/HI11098199
2 3 5 30 P1-32/... EA/SVB/HI11072567
I2/SVB/HI11-NA255894
V/SVB/HI11015145
EA/SVB-SW/HI11012772
I2/SVB-SW/HI11-NA255895
V/SVB-SW/HI11017518
3 7 ½ 10 60 P3-63/... EA/SVB/HI11019891
I4/SVB/HI11-NA255901
V/SVB/HI11024637
EA/SVB-SW/HI11022264
I4/SVB-SW/HI11-NA255900
V/SVB-SW/HI11027010
5 10 15 100 P3-100/... EA/SVB/HI11029383
I5/SVB/HI11-NA255906
V/SVB/HI11034129
EA/SVB-SW/HI11031756
I5/SVB-SW/HI11-NA255907
V/SVB-SW/HI11036502
Notes: 1) Surface mounting enclosures are IEC type, totally insulated, corrosion-resistant rated IP 65, NEMA rated 3R, 12.2) All handles supplied in the above combinations are padlockable in the OFF position. Switches with red handles and yellow collars
(...SVB) are suitable as Emergency-Stop main disconnect switches per Machinery Directive Standard EN 60 204-1. In applications where the switch is not intended to fulfill the Emergency-Stop function, use black handle and collar (...SVB-SW).
3) All switches are UL listed and CSA certified as manual controllers, additionally evaluated as motor disconnects per the intent of NEC. All switches are in compliance with IEC/EN 60 947-3 (switch-disconnectors) and are CE marked. For IEC ratings consult Moeller Elec-tric.
4) All front plates shown may be exchanged at the time of the order at no extra charge. The prerequisite is that switching angles, the number of positions and the location of position 0 must be identical; a pages 07/052 and 053 for ordering details. English front plates supplied with the switches as shown in the catalog, can be exchanged for their French equivalent by adding the FS... number shown with suffix -F to the switch type (Example: T0-1-8200/EA/SVB-NA+FS908-F).
FS 908
ON
OFF
07/012 07/013
1-866-595-96161-630-595-9515 Go to: http://www.klocknermoeller.com
Cam Switches, Manual Motor Controllers, DisconnectsFor Single phase Applications
Cam
Sw
itch
es,
Mot
or D
isco
nnec
t Sw
itch
es
Cam
Sw
itch
es,
Mot
or D
isco
nnec
tSw
itch
es
Cam Switches, Manual Motor Controllers, DisconnectsFor Single phase Applications
UL / CSA / IEC / CEUL / CSA / IEC / CE
Moeller Electric Corporation Moeller Electric Corporation
Circuit function diagram Front Plate No. 3)
Maincontacts (Number of power poles)
Auxiliary contacts
Max. HP rating50-60 Hz, single-phaseUL/CSA
Current ratingUL/CSA
Cover mountingFront IP 65
Center mountingFront IP 6522.5 mm opening
Surface mounting 1)Enclosure
Base mountingwith coverFront IP 30
Base mountingwith cover mounted handle and coupling driveFront IP 65
Basic type
for ...., insert mountng form
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price list
N.O. N.O. N.C.115 VHP
200 VHP
230 VHP A
On-Off switches, with black handle and silver-colored front plate1 0 0 ¾ 2 2 14 T0-1-8200/... E-NA
104447EZ-NA104449
I2-NA109874
IVS-NA109892
Z-NA104455
1 ½ 3 3 25 T3-1-8200/... E-NA104748
EZ-NA104750
I2-NA109875
– Z-NA104756
3 7 ½ 10 65 T5B-1-8200/... E-NA104871
– I4-NA109876
– Z-NA104878
2 0 0 ¾ 2 2 14 T0-1-102/... E-NA104367
EZ-NA104369
I2-NA109877
IVS-NA109893
Z-NA104378
1 ½ 3 3 25 T3-1-102/... E-NA104725
EZ-NA104727
I2-NA109878
– Z-NA104733
3 7 ½ 10 65 T5B-1-102/... E-NA104851
– I4-NA109879
– Z-NA104858
3 0 0 ¾ 2 2 14 T0-2-1/... E-NA104475
EZ-NA104477
I2-NA109880
IVS-NA109894
Z-NA104483
1 ½ 3 3 20 P1-25/... E038724
EZ041250
I2-NA255884
IVS052962
Z057708
2 3 5 30 P1-32/... E079065
EZ048369
I2-NA255890
IVS093303
Z098049
3 7 ½ 10 60 P3-63/... E026861
– I4-NA255896
IVS041099
Z050591
5 10 15 100 P3-100/... E067201
– I5-NA255902
IVS081439
Z090931
On-OFF switches, with auxiliary contacts3 1 0 ¾ 2 2 14 T0-2-15679/... E
029387EZ031760
I2109885
IVS036506
Z041252
3 1 1 1 ½ 3 3 20 P1-25/... E/HI11045998
EZ/HI11048371
I2/HI11-NA109886
IVS/HI11053117
Z/HI11057863
2 3 5 30 P1-32/... E/HI11062609
EZ/HI11064982
I2/HI11-NA109887
IVS/HI11069728
Z/HI11074474
3 7 ½ 10 60 P3-63/... E/HI11079220
– I4/HI11-NA109888
IVS/HI11081593
Z/HI11086339
5 10 15 100 P3-100/... E/HI11069574
– I5/HI11-NA109889
IVS/HI11091085
Z/HI11093304
Fractional HP motor reversing switch, auxiliary winding6 0 0 ¾ 2 2 14 T0-3-15098/... E-NA
109869EZ-NA109872
I2-NA109890
IVS-NA109896
Z-NA109897
1 ½ 3 3 25 T3-3-15098/... E-NA104764
EZ-NA104765
I2-NA109891
– Z-NA104767
Notes 1) Surface mounting enclosures are IEC type, totally insulated, corrosion-resistant to IP 65, NEMA rated 3R, 12.2) Above switches are identical to the selection on pages 07/012 and 013, except that the associated handle is not padlockable.
Exception: P3-.../IVS can be padlocked in the Off position.All above handles are black with light grey front plate.
3) All front plates shown may be exchanged at the time of the order at no extra charge. The prerequisite is that switching angles, the number of positions and the location of position 0 must be identical; a pages 07/052 and 053 for ordering details. English front plates supplied with the switches as shown in the catalog, can be exchanged for their French equivalent by adding the FS... number shown with suffix -F to the switch type (Example: T0-1-8200/E-NA+FS908-F).
FS 908
ON
OFF
2
1 3
4
5
6
7
8
2
1 3
4
5
6
13
14 22
21
07/014 07/015
1-866-595-96161-630-595-9515 Go to: http://www.klocknermoeller.com
Cam Switches, Manual Motor Controllers, DisconnectsFor Single phase Applications
Cam
Sw
itch
es,
Mot
or D
isco
nnec
t Sw
itch
es
Cam
Sw
itch
es,
Mot
or D
isco
nnec
tSw
itch
es
Cam Switches, Manual Motor Controllers, DisconnectsFor Single phase Applications
UL / CSA / IEC / CEUL / CSA / IEC / CE
Moeller Electric Corporation Moeller Electric Corporation
Circuit function diagram Front Plate No. 3)
Maincontacts (Number of power poles)
Auxiliary contacts
Max. HP rating50-60 Hz, single-phaseUL/CSA
Current ratingUL/CSA
Cover mountingFront IP 65
Center mountingFront IP 6522.5 mm opening
Surface mounting 1)Enclosure
Base mountingwith coverFront IP 30
Base mountingwith cover mounted handle and coupling driveFront IP 65
Basic type
for ...., insert mountng form
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price list
N.O. N.O. N.C.115 VHP
200 VHP
230 VHP A
On-Off switches, with black handle and silver-colored front plate1 0 0 ¾ 2 2 14 T0-1-8200/... E-NA
104447EZ-NA104449
I2-NA109874
IVS-NA109892
Z-NA104455
1 ½ 3 3 25 T3-1-8200/... E-NA104748
EZ-NA104750
I2-NA109875
– Z-NA104756
3 7 ½ 10 65 T5B-1-8200/... E-NA104871
– I4-NA109876
– Z-NA104878
2 0 0 ¾ 2 2 14 T0-1-102/... E-NA104367
EZ-NA104369
I2-NA109877
IVS-NA109893
Z-NA104378
1 ½ 3 3 25 T3-1-102/... E-NA104725
EZ-NA104727
I2-NA109878
– Z-NA104733
3 7 ½ 10 65 T5B-1-102/... E-NA104851
– I4-NA109879
– Z-NA104858
3 0 0 ¾ 2 2 14 T0-2-1/... E-NA104475
EZ-NA104477
I2-NA109880
IVS-NA109894
Z-NA104483
1 ½ 3 3 20 P1-25/... E038724
EZ041250
I2-NA255884
IVS052962
Z057708
2 3 5 30 P1-32/... E079065
EZ048369
I2-NA255890
IVS093303
Z098049
3 7 ½ 10 60 P3-63/... E026861
– I4-NA255896
IVS041099
Z050591
5 10 15 100 P3-100/... E067201
– I5-NA255902
IVS081439
Z090931
On-OFF switches, with auxiliary contacts3 1 0 ¾ 2 2 14 T0-2-15679/... E
029387EZ031760
I2109885
IVS036506
Z041252
3 1 1 1 ½ 3 3 20 P1-25/... E/HI11045998
EZ/HI11048371
I2/HI11-NA109886
IVS/HI11053117
Z/HI11057863
2 3 5 30 P1-32/... E/HI11062609
EZ/HI11064982
I2/HI11-NA109887
IVS/HI11069728
Z/HI11074474
3 7 ½ 10 60 P3-63/... E/HI11079220
– I4/HI11-NA109888
IVS/HI11081593
Z/HI11086339
5 10 15 100 P3-100/... E/HI11069574
– I5/HI11-NA109889
IVS/HI11091085
Z/HI11093304
Fractional HP motor reversing switch, auxiliary winding6 0 0 ¾ 2 2 14 T0-3-15098/... E-NA
109869EZ-NA109872
I2-NA109890
IVS-NA109896
Z-NA109897
1 ½ 3 3 25 T3-3-15098/... E-NA104764
EZ-NA104765
I2-NA109891
– Z-NA104767
Notes 1) Surface mounting enclosures are IEC type, totally insulated, corrosion-resistant to IP 65, NEMA rated 3R, 12.2) Above switches are identical to the selection on pages 07/012 and 013, except that the associated handle is not padlockable.
Exception: P3-.../IVS can be padlocked in the Off position.All above handles are black with light grey front plate.
3) All front plates shown may be exchanged at the time of the order at no extra charge. The prerequisite is that switching angles, the number of positions and the location of position 0 must be identical; a pages 07/052 and 053 for ordering details. English front plates supplied with the switches as shown in the catalog, can be exchanged for their French equivalent by adding the FS... number shown with suffix -F to the switch type (Example: T0-1-8200/E-NA+FS908-F).
FS 908
ON
OFF
2
1 3
4
5
6
7
8
2
1 3
4
5
6
13
14 22
21
07/014 07/015
1-866-595-96161-630-595-9515 Go to: http://www.klocknermoeller.com
Cam Switches, Manual Motor Controllers, DisconnectsFor Single phase Applications
Cam
Sw
itch
es,
Mot
or D
isco
nnec
t Sw
itch
es
Cam
Sw
itch
es,
Mot
or D
isco
nnec
tSw
itch
es
Cam Switches, Manual Motor Controllers, DisconnectsFor Single phase Applications
UL / CSA / IEC / CEUL / CSA / IEC / CE
Moeller Electric Corporation Moeller Electric Corporation
Circuit function diagram Front plate No. 3)
Main contacts(Number of power poles)
Auxiliary contacts
Max. HP rating50-60 Hz, single-phaseUL/CSA
Current ratingUL/CSA
Cover mountingFront IP 65
Surface mounting 2)
EnclosureBase mountingwith coverFront IP 30
Basic type for ...., insert mounting form
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price list
N.O. N.O. N.C.115 VHP
200 VHP
230 VHP A
Emergency-Stop switches, with red handle and yellow front plate1 0 0 ¾ 2 2 14 T0-1-8200/... E-RT-NA
109898I2-RT-NA109905
IVS-RT-NA109916
1 ½ 3 3 25 T3-1-8200/... E-RT-NA109899
I2-RT-NA109906
–
3 7 ½ 10 65 T5B-1-8200/... E-RT-NA109900
I4-RT-NA109907
–
2 0 0 ¾ 2 2 14 T0-1-102/... E-RT-NA109901
I2-RT-NA109908
IVS-RT-NA109917
1 ½ 3 3 25 T3-1-102/... E-RT-NA109902
I2-RT-NA109909
–
3 7 ½ 10 65 T5B-1-102/... E-RT-NA109903
I4-RT-NA109910
–
3 0 0 ¾ 2 2 14 T0-2-1/... E-RT-NA109904
I2-RT-NA109911
IVS-RT-NA109918
1 ½ 3 3 20 P1-25/... E-RT002388
I2-RT-NA255887
IVS-RT013140
2 3 5 30 P1-32/... E-RT003197
I2-RT-NA255893
IVS-RT022632
3 7 ½ 10 60 P3-63/... E-RT005743
I4-RT-NA255899
IVS-RT045845
5 10 15 100 P3-100/... E-RT007189
I5-RT-NA255905
IVS-RT086185
Notes 1) Surface mounting enclosures are IEC type, totally insulated, corrosion-resistant rated IP 65, NEMA rated 3R,12.2) Above switches are identical to the selection on pages 07/012 and 013, except that the associated handle assembly is red with yellow
background, making them suitable for Emergency-Stop applications. Handles are not padlockable.For padlockable handles used in Emergency-Stop applications, a 07/048.
3) All front plates shown may be exchanged at the time of the order at no extra charge. The prerequisite is that switching angles, the number of positions and the location of position 0 must be identical; a pages 07/052 and 053 for ordering details. English front plates supplied with the switches as shown in the catalog, can be exchanged for their French equivalent by adding the FS... number shown with suffix -F to the switch type (Example: T0-1-8200/E-RT-NA+FS908-F).
FS 908 GE
1
0
07/016 07/017
1-866-595-96161-630-595-9515 Go to: http://www.klocknermoeller.com
Cam Switches, Manual Motor Controllers, DisconnectsFor Single phase Applications
Cam
Sw
itch
es,
Mot
or D
isco
nnec
t Sw
itch
es
Cam
Sw
itch
es,
Mot
or D
isco
nnec
tSw
itch
es
Cam Switches, Manual Motor Controllers, DisconnectsFor Single phase Applications
UL / CSA / IEC / CEUL / CSA / IEC / CE
Moeller Electric Corporation Moeller Electric Corporation
Circuit function diagram Front plate No. 3)
Main contacts(Number of power poles)
Auxiliary contacts
Max. HP rating50-60 Hz, single-phaseUL/CSA
Current ratingUL/CSA
Cover mountingFront IP 65
Surface mounting 2)
EnclosureBase mountingwith coverFront IP 30
Basic type for ...., insert mounting form
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price list
N.O. N.O. N.C.115 VHP
200 VHP
230 VHP A
Emergency-Stop switches, with red handle and yellow front plate1 0 0 ¾ 2 2 14 T0-1-8200/... E-RT-NA
109898I2-RT-NA109905
IVS-RT-NA109916
1 ½ 3 3 25 T3-1-8200/... E-RT-NA109899
I2-RT-NA109906
–
3 7 ½ 10 65 T5B-1-8200/... E-RT-NA109900
I4-RT-NA109907
–
2 0 0 ¾ 2 2 14 T0-1-102/... E-RT-NA109901
I2-RT-NA109908
IVS-RT-NA109917
1 ½ 3 3 25 T3-1-102/... E-RT-NA109902
I2-RT-NA109909
–
3 7 ½ 10 65 T5B-1-102/... E-RT-NA109903
I4-RT-NA109910
–
3 0 0 ¾ 2 2 14 T0-2-1/... E-RT-NA109904
I2-RT-NA109911
IVS-RT-NA109918
1 ½ 3 3 20 P1-25/... E-RT002388
I2-RT-NA255887
IVS-RT013140
2 3 5 30 P1-32/... E-RT003197
I2-RT-NA255893
IVS-RT022632
3 7 ½ 10 60 P3-63/... E-RT005743
I4-RT-NA255899
IVS-RT045845
5 10 15 100 P3-100/... E-RT007189
I5-RT-NA255905
IVS-RT086185
Notes 1) Surface mounting enclosures are IEC type, totally insulated, corrosion-resistant rated IP 65, NEMA rated 3R,12.2) Above switches are identical to the selection on pages 07/012 and 013, except that the associated handle assembly is red with yellow
background, making them suitable for Emergency-Stop applications. Handles are not padlockable.For padlockable handles used in Emergency-Stop applications, a 07/048.
3) All front plates shown may be exchanged at the time of the order at no extra charge. The prerequisite is that switching angles, the number of positions and the location of position 0 must be identical; a pages 07/052 and 053 for ordering details. English front plates supplied with the switches as shown in the catalog, can be exchanged for their French equivalent by adding the FS... number shown with suffix -F to the switch type (Example: T0-1-8200/E-RT-NA+FS908-F).
FS 908 GE
1
0
07/016 07/017
1-866-595-96161-630-595-9515 Go to: http://www.klocknermoeller.com
Moeller Electric Corporation Moeller Electric Corporation
Circuit function diagram Front Plate No. 3)
Main contacts(Number of power poles)
Max. HP rating50-60 Hz, single-phaseUL/CSA
Current ratingUL/CSA
Cover mountingFront IP 65
Center mountingFront IP 65
Surface mounting 1)
EnclosureBase mountingwith coverFront IP 30
Base mountingwith cover mounted handleand coupling driveFront IP 65
Basic typefor ..., insert mounting form
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price list
N.O.115 VHP
200 VHP
230 VHP A
Change-over switches with OFF position1 ¾ 2 2 14 T0-1-8210/... E
012742EZ048337
I2-NA109921
IVS074440
Z019862
1 ½ 3 3 25 T3-1-8210/... E054718
EZ003072
I2-NA109922
– Z057091
3 7 ½ 10 65 T5B-1-8210/... E094261
– I4-NA109923
– Z094258
2 ¾ 2 2 14 T0-2-8211/... E022234
EZ053083
I2-NA109924
IVS076813
Z029354
1 ½ 3 3 25 T3-2-8211/... E061837
EZ003075
I2-NA109925
– Z064210
3 7 ½ 10 65 T5B-2-8211/... E093094
– I4-NA109926
– Z093082
Change-over switches with OFF positionwith spring-return from both directions to “0”
1 ¾ 2 2 14 T0-1-8214/... E-NA104459
EZ-NA104460
I2-NA109927
IVS-NA109936
Z-NA104462
1 ½ 3 3 25 T3-1-8214/... E-NA109919
EZ-NA109920
I2-NA109928
– Z-NA109937
2 ¾ 2 2 14 T0-2-8215/... E022236
EZ081561
I2-NA109929
IVS048340
Z053093
1 ½ 3 3 25 T3-2-8215/... E016751
EZ001074
I2-NA109930
– Z019124
Change-over switches without OFF position1 ¾ 2 2 14 T0-1-8220/... E
031728EZ095799
I2-NA109931
IVS055459
Z086312
1 ½ 3 3 25 T3-1-8220/... E038108
EZ001018
I2-NA109932
– Z040481
2 ¾ 2 2 14 T0-2-8221/... E038847
EZ010372
I2-NA109933
IVS057832
Z074450
1 ½ 3 3 25 T3-2-8221/... E045227
EZ001025
I2-NA109934
– Z047600
3 7 ½ 10 65 T5B-2-8221/... E093047
– I4-NA109935
– Z093044
Notes: 1) Surface mounting enclosures are IEC type, totally insulated, corrosion-resistant rated IP 65, NEMA rated 3R, 12.2) All handles suppled with above switches are black with light gray front plate.3) All front plates shown may be exchanged at the time of the order at no extra charge. The prerequisite is that switching angles, the
number of positions and the location of position 0 must be identical; a pages 07/052 and 053 for ordering details. English front plates supplied with the switches as shown in the catalog, can be exchanged for their French equivalent by adding the FS... number shown with suffix -F to the switch type (Example: T0-1-8214/E-NA+FS147474-F).
201
2
1 3
4
FS 684
01 2
201
2
1 3
4
5
6
7
8
FS 684
01 2
12
2
1 3
4
12
2
1 3
4
5
6
7
8
07/018 07/019
1-866-595-96161-630-595-9515 Go to: http://www.klocknermoeller.com
Moeller Electric Corporation Moeller Electric Corporation
Circuit function diagram Front Plate No. 3)
Main contacts(Number of power poles)
Max. HP rating50-60 Hz, single-phaseUL/CSA
Current ratingUL/CSA
Cover mountingFront IP 65
Center mountingFront IP 65
Surface mounting 1)
EnclosureBase mountingwith coverFront IP 30
Base mountingwith cover mounted handleand coupling driveFront IP 65
Basic typefor ..., insert mounting form
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price list
N.O.115 VHP
200 VHP
230 VHP A
Change-over switches with OFF position1 ¾ 2 2 14 T0-1-8210/... E
012742EZ048337
I2-NA109921
IVS074440
Z019862
1 ½ 3 3 25 T3-1-8210/... E054718
EZ003072
I2-NA109922
– Z057091
3 7 ½ 10 65 T5B-1-8210/... E094261
– I4-NA109923
– Z094258
2 ¾ 2 2 14 T0-2-8211/... E022234
EZ053083
I2-NA109924
IVS076813
Z029354
1 ½ 3 3 25 T3-2-8211/... E061837
EZ003075
I2-NA109925
– Z064210
3 7 ½ 10 65 T5B-2-8211/... E093094
– I4-NA109926
– Z093082
Change-over switches with OFF positionwith spring-return from both directions to “0”
1 ¾ 2 2 14 T0-1-8214/... E-NA104459
EZ-NA104460
I2-NA109927
IVS-NA109936
Z-NA104462
1 ½ 3 3 25 T3-1-8214/... E-NA109919
EZ-NA109920
I2-NA109928
– Z-NA109937
2 ¾ 2 2 14 T0-2-8215/... E022236
EZ081561
I2-NA109929
IVS048340
Z053093
1 ½ 3 3 25 T3-2-8215/... E016751
EZ001074
I2-NA109930
– Z019124
Change-over switches without OFF position1 ¾ 2 2 14 T0-1-8220/... E
031728EZ095799
I2-NA109931
IVS055459
Z086312
1 ½ 3 3 25 T3-1-8220/... E038108
EZ001018
I2-NA109932
– Z040481
2 ¾ 2 2 14 T0-2-8221/... E038847
EZ010372
I2-NA109933
IVS057832
Z074450
1 ½ 3 3 25 T3-2-8221/... E045227
EZ001025
I2-NA109934
– Z047600
3 7 ½ 10 65 T5B-2-8221/... E093047
– I4-NA109935
– Z093044
Notes: 1) Surface mounting enclosures are IEC type, totally insulated, corrosion-resistant rated IP 65, NEMA rated 3R, 12.2) All handles suppled with above switches are black with light gray front plate.3) All front plates shown may be exchanged at the time of the order at no extra charge. The prerequisite is that switching angles, the
number of positions and the location of position 0 must be identical; a pages 07/052 and 053 for ordering details. English front plates supplied with the switches as shown in the catalog, can be exchanged for their French equivalent by adding the FS... number shown with suffix -F to the switch type (Example: T0-1-8214/E-NA+FS147474-F).
201
2
1 3
4
FS 684
01 2
201
2
1 3
4
5
6
7
8
FS 684
01 2
12
2
1 3
4
12
2
1 3
4
5
6
7
8
07/018 07/019
1-866-595-96161-630-595-9515 Go to: http://www.klocknermoeller.com
Notes 1) Surface mounting enclosures are IEC type, totally insulated, corrosion-resistant rated IP 65, NEMA rated 3R, 12.2) All handles supplied in the above combinations are padlockable in the OFF position. Switches with red handles and yellow collars
(...SVB) are suitable as Emergency-Stop main disconnect switches per Machinery Directive Standard EN 60 204-1. In applications where the switch is not intended to fulfill the Emergency-Stop function, use black handle and collar (...SVB-SW)
3) All switches are in compliance with IEC/EN 947-3 (switch-disconnectors) and are CE marked. For IEC ratings consult Moeller Electric.4) All front plates shown may be exchanged at the time of the order at no extra charge. The prerequisite is that switching angles, the
number of positions and the location of position 0 must be identical; a pages 07/052 and 053 for ordering details. English front plates supplied with the switches as shown in the catalog, can be exchanged for their French equivalent by adding the FS... number shown with suffix -F to the switch type (Example: T0-2-1/EA/SVB-NA+FS908-F).
5) All switches are UL listed and CSA certified as manual controllers. Additionally evaluated as motor disconnect switches per the intent of the NEC. (T5B-... listed as manual controller only.)
FS 908
ON
OFF
2
1 3
4
5
6
7
8
9
10 12
11
2
1 3
4
5
6
7
8
9
10 12
11 13
14 16
15
07/020 07/021
1-866-595-96161-630-595-9515 Go to: http://www.klocknermoeller.com
Notes 1) Surface mounting enclosures are IEC type, totally insulated, corrosion-resistant rated IP 65, NEMA rated 3R, 12.2) All handles supplied in the above combinations are padlockable in the OFF position. Switches with red handles and yellow collars
(...SVB) are suitable as Emergency-Stop main disconnect switches per Machinery Directive Standard EN 60 204-1. In applications where the switch is not intended to fulfill the Emergency-Stop function, use black handle and collar (...SVB-SW)
3) All switches are in compliance with IEC/EN 947-3 (switch-disconnectors) and are CE marked. For IEC ratings consult Moeller Electric.4) All front plates shown may be exchanged at the time of the order at no extra charge. The prerequisite is that switching angles, the
number of positions and the location of position 0 must be identical; a pages 07/052 and 053 for ordering details. English front plates supplied with the switches as shown in the catalog, can be exchanged for their French equivalent by adding the FS... number shown with suffix -F to the switch type (Example: T0-2-1/EA/SVB-NA+FS908-F).
5) All switches are UL listed and CSA certified as manual controllers. Additionally evaluated as motor disconnect switches per the intent of the NEC. (T5B-... listed as manual controller only.)
FS 908
ON
OFF
2
1 3
4
5
6
7
8
9
10 12
11
2
1 3
4
5
6
7
8
9
10 12
11 13
14 16
15
07/020 07/021
1-866-595-96161-630-595-9515 Go to: http://www.klocknermoeller.com
Cam Switches, Manual Motor Controllers, DisconnectsFor Three phase Applications
Cam
Sw
itch
es,
Mot
or D
isco
nnec
t Sw
itch
es
Cam
Sw
itch
es,
Mot
or D
isco
nnec
t Sw
itch
es
Cam Switches, Manual Motor Controllers, DisconnectsFor Three phase Applications
UL / CSA / IEC / CE UL / CSA / IEC / CE
Moeller Electric Corporation Moeller Electric Corporation
For use as Emergency-Stop device without Emergency-Stop functionCircuit function diagram Front
PlateNo. 5)
Main contacts(Number of power poles)
Auxiliary contacts
Max. HP rating50-60 Hz, three-phaseUL/CSA
Current ratingUL/CSA
Cover mountingPadlockable,red handle with yellow collarsuitable as Emergency-Stop
Surface mountingPadlockablered handle with yellow collarsuitable as Emergency-Stop
Base mountingPadlockable,red handle with yellow collarsuitable as Emergency-Stop
Cover mountingPadlockable,black handle and collar
Surface mountingPadlockable,black handle and collar
Base mountingPadlockable,black handle and collar,coupling drive
Basic type
for ..., insert mounting form
Mounting formArticle No.
Price
see price list
Mounting formArticle No.
Price
see price list
Mounting formArticle No.
Price
see price list
Mounting formArticle No.
Price
see price list
Mounting formArticle No.
Price
see price list
Mounting formArticle No.
Price
see price list
N.O. N.O. N.C.200 VHP
230 VHP
460 VHP
575 VHP A
Main disconnect switches with auxiliary contacts3 1 0 3 3 10 10 14 T0-2-15679/... EA/SVB
081588I2/SVB-NA109956
V/SVB086334
EA/SVB-SW083961
I2/SVB-SW-NA109962
V/SVB-SW088707
3 1 1 5 5 10 15 20 P1-25/... EA/SVB/HI11091080
I2/SVB/HI11-NA255888
V/SVB/HI11095826
EA/SVB-SW/HI11070194
I2/SVB-SW/HI11-NA255889
V/SVB-SW/HI11098199
7 ½ 10 20 25 30 P1-32/... EA/SVB/HI11072567
I2/SVB/HI11-NA255894
V/SVB/HI11015145
EA/SVB-SW/HI11012772
I2/SVB-SW/HI11-NA255895
V/SVB-SW/HI11017518
15 15 40 50 60 P3-63/... EA/SVB/HI11019891
I4/SVB/HI11-NA255901
V/SVB/HI11024637
EA/SVB-SW/HI11022264
I4/SVB-SW/HI11-NA255900
V/SVB-SW/HI11027010
20 25 60 75 100 P3-100/... EA/SVB/HI11029383
I5/SVB/HI11-NA255906
V/SVB/HI11034129
EA/SVB-SW/HI11031756
I5/SVB-SW/HI11-NA255907
V/SVB-SW/HI11036502
3 2 1 3 3 10 10 14 T0-3-15683/... EA/SVB015571
I2/SVB-NA109957
V/SVB015634
EA/SVB-SW015600
I2/SVB-SW-NA109963
V/SVB-SW015664
5 7 ½ 15 15 25 T3-3-15683/... EA/SVB040478
I2/SVB-NA255912
V/SVB045224
EA/SVB-SW042851
I2/SVB-SW-NA109964
V/SVB-SW047597
6 1 1 3 3 10 10 14 T0-4-15682/... EA/SVB019892
I2/SVB-NA109959
V/SVB024638
EA/SVB-SW022265
I2/SVB-SW-NA109965
V/SVB-SW027011
5 7 ½ 15 15 25 T3-4-15682/... EA/SVB054716
I2/SVB-NA109960
V/SVB059462
EA/SVB-SW057089
I2/SVB-SW-NA109966
V/SVB-SW061835
15 15 40 50 65 T5B-4-15682/... EA/SVB207425
I4/SVB-NA109961
V/SVB207427
EA/SVB-SW207426
I4/SVB-SW-NA109967
V/SVB-SW207428
Notes: 1) Surface mounted enclosures are IEC type, totally insulated, corrosion-resistant rated IP 65, NEMA rated 3R, 12.2) All handles supplied with the above combinations are padlockable in the OFF position. Switches with red handles and yellow collars
(...SVB) are suitable as Emergency-Stop main disconnect switches per Machinery Directive standard EN 60 204-1. In applications where the switch is not intended to fulfill the Emergency-Stop function, use black handle and collar (...SVB-SW).
3) All switches are UL listed and CSA certified as manual controllers, additionally evaluated as motor disconnect switches per the intent of NEC. (T5B-... listed as manual motor controller only).All switches are in compliance with IEC/EN 60 947-3 (switch-disconnectors) and are CE marked. For IEC ratings, consult Moeller Electric.
4) N.O. auxiliary contacts can be used for load shedding purposes (late-make, early-break characteristic).5) All front plates shown may be exchanged at the time of the order at no extra charge. The prerequisite is that switching angles, the
number of positions and the location of position 0 must be identical; a pages 07/052 and 053 for ordering details. English front plates supplied with the switches as shown in the catalog, can be exchanged for their French equivalent by adding the FS... number shown with suffix -F to the switch type (Example: T0--2-15679/EA/SVB+FS908-F).
FS 908
ON
OFF
2
1 3
4
5
6
7
8
2
1 3
4
5
6
13
14 22
21
L2 L3L1
2
1 3
4
5
6
7
8
9
10 12
11
2
1 3
4
5
6
7
8
9
10 12
11 13
14 16
15
07/022 07/023
1-866-595-96161-630-595-9515 Go to: http://www.klocknermoeller.com
Cam Switches, Manual Motor Controllers, DisconnectsFor Three phase Applications
Cam
Sw
itch
es,
Mot
or D
isco
nnec
t Sw
itch
es
Cam
Sw
itch
es,
Mot
or D
isco
nnec
t Sw
itch
es
Cam Switches, Manual Motor Controllers, DisconnectsFor Three phase Applications
UL / CSA / IEC / CE UL / CSA / IEC / CE
Moeller Electric Corporation Moeller Electric Corporation
For use as Emergency-Stop device without Emergency-Stop functionCircuit function diagram Front
PlateNo. 5)
Main contacts(Number of power poles)
Auxiliary contacts
Max. HP rating50-60 Hz, three-phaseUL/CSA
Current ratingUL/CSA
Cover mountingPadlockable,red handle with yellow collarsuitable as Emergency-Stop
Surface mountingPadlockablered handle with yellow collarsuitable as Emergency-Stop
Base mountingPadlockable,red handle with yellow collarsuitable as Emergency-Stop
Cover mountingPadlockable,black handle and collar
Surface mountingPadlockable,black handle and collar
Base mountingPadlockable,black handle and collar,coupling drive
Basic type
for ..., insert mounting form
Mounting formArticle No.
Price
see price list
Mounting formArticle No.
Price
see price list
Mounting formArticle No.
Price
see price list
Mounting formArticle No.
Price
see price list
Mounting formArticle No.
Price
see price list
Mounting formArticle No.
Price
see price list
N.O. N.O. N.C.200 VHP
230 VHP
460 VHP
575 VHP A
Main disconnect switches with auxiliary contacts3 1 0 3 3 10 10 14 T0-2-15679/... EA/SVB
081588I2/SVB-NA109956
V/SVB086334
EA/SVB-SW083961
I2/SVB-SW-NA109962
V/SVB-SW088707
3 1 1 5 5 10 15 20 P1-25/... EA/SVB/HI11091080
I2/SVB/HI11-NA255888
V/SVB/HI11095826
EA/SVB-SW/HI11070194
I2/SVB-SW/HI11-NA255889
V/SVB-SW/HI11098199
7 ½ 10 20 25 30 P1-32/... EA/SVB/HI11072567
I2/SVB/HI11-NA255894
V/SVB/HI11015145
EA/SVB-SW/HI11012772
I2/SVB-SW/HI11-NA255895
V/SVB-SW/HI11017518
15 15 40 50 60 P3-63/... EA/SVB/HI11019891
I4/SVB/HI11-NA255901
V/SVB/HI11024637
EA/SVB-SW/HI11022264
I4/SVB-SW/HI11-NA255900
V/SVB-SW/HI11027010
20 25 60 75 100 P3-100/... EA/SVB/HI11029383
I5/SVB/HI11-NA255906
V/SVB/HI11034129
EA/SVB-SW/HI11031756
I5/SVB-SW/HI11-NA255907
V/SVB-SW/HI11036502
3 2 1 3 3 10 10 14 T0-3-15683/... EA/SVB015571
I2/SVB-NA109957
V/SVB015634
EA/SVB-SW015600
I2/SVB-SW-NA109963
V/SVB-SW015664
5 7 ½ 15 15 25 T3-3-15683/... EA/SVB040478
I2/SVB-NA255912
V/SVB045224
EA/SVB-SW042851
I2/SVB-SW-NA109964
V/SVB-SW047597
6 1 1 3 3 10 10 14 T0-4-15682/... EA/SVB019892
I2/SVB-NA109959
V/SVB024638
EA/SVB-SW022265
I2/SVB-SW-NA109965
V/SVB-SW027011
5 7 ½ 15 15 25 T3-4-15682/... EA/SVB054716
I2/SVB-NA109960
V/SVB059462
EA/SVB-SW057089
I2/SVB-SW-NA109966
V/SVB-SW061835
15 15 40 50 65 T5B-4-15682/... EA/SVB207425
I4/SVB-NA109961
V/SVB207427
EA/SVB-SW207426
I4/SVB-SW-NA109967
V/SVB-SW207428
Notes: 1) Surface mounted enclosures are IEC type, totally insulated, corrosion-resistant rated IP 65, NEMA rated 3R, 12.2) All handles supplied with the above combinations are padlockable in the OFF position. Switches with red handles and yellow collars
(...SVB) are suitable as Emergency-Stop main disconnect switches per Machinery Directive standard EN 60 204-1. In applications where the switch is not intended to fulfill the Emergency-Stop function, use black handle and collar (...SVB-SW).
3) All switches are UL listed and CSA certified as manual controllers, additionally evaluated as motor disconnect switches per the intent of NEC. (T5B-... listed as manual motor controller only).All switches are in compliance with IEC/EN 60 947-3 (switch-disconnectors) and are CE marked. For IEC ratings, consult Moeller Electric.
4) N.O. auxiliary contacts can be used for load shedding purposes (late-make, early-break characteristic).5) All front plates shown may be exchanged at the time of the order at no extra charge. The prerequisite is that switching angles, the
number of positions and the location of position 0 must be identical; a pages 07/052 and 053 for ordering details. English front plates supplied with the switches as shown in the catalog, can be exchanged for their French equivalent by adding the FS... number shown with suffix -F to the switch type (Example: T0--2-15679/EA/SVB+FS908-F).
FS 908
ON
OFF
2
1 3
4
5
6
7
8
2
1 3
4
5
6
13
14 22
21
L2 L3L1
2
1 3
4
5
6
7
8
9
10 12
11
2
1 3
4
5
6
7
8
9
10 12
11 13
14 16
15
07/022 07/023
1-866-595-96161-630-595-9515 Go to: http://www.klocknermoeller.com
Cam Switches, Manual Motor Controllers, DisconnectsFor Three phase Applications
Cam
Sw
itch
es,
Mot
or D
isco
nnec
t Sw
itch
es
Cam
Sw
itch
es,
Mot
or D
isco
nnec
t Sw
itch
es
Cam Switches, Manual Motor Controllers, DisconnectsFor Three phase Applications
UL / CSA / IEC / CE UL / CSA / IEC / CE
Moeller Electric Corporation Moeller Electric Corporation
Circuit function diagram Front PlateNo. 3)
Main contacts(Num-ber of power poles)
Auxiliary contacts
Max. HP rating50-60 Hz, three-phaseUL/CSA
Current ratingUL/CSA
Cover mounting Center mounting22.5 mm opening
Surface mountingEnclosure 1)
Base mountingwith cover
Base mountingwith cover mounted handle and coupling drive
Basic type
for ..., insert mounting form
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price listN.O. N.O. N.C.
200 VHP
230 VHP
460 VHP
575 VHP A
On-Off switches3 0 0 3 3 10 10 14 T0-2-1/... E-NA
104475EZ-NA104477
I2-NA109880
IVS-NA109894
Z-NA104483
5 5 10 15 20 P1-25/... E038724
EZ041250
I2-NA255884
IVS052962
Z057708
7 ½ 10 20 25 30 P1-32/... E079065
EZ048369
I2-NA255890
IVS093303
Z098049
15 15 40 50 60 P3-63/... E026861
– I4-NA255896
IVS041099
Z050591
20 25 60 75 100 P3-100/... E067201
– I5-NA255902
IVS081439
Z090931
6 0 0 3 3 10 10 14 T0-3-8342/... E043624
EZ045997
I2-NA109969
IVS050743
Z055489
5 7 ½ 15 15 25 T3-3-8342/... E045225
EZ047598
I2-NA109970
– Z052344
15 15 40 50 65 T5B-3-8342/... E092310
– I4-NA109971
– Z092297
8 0 0 3 3 10 10 14 T0-4-8344/... E014000
EZ014002
I2-NA109972
IVS014006
Z014009
5 7 ½ 15 15 25 T3-4-8344/... E020593
EZ020595
I2-NA109973
– Z020600
15 15 40 50 65 T5B-4-8344/... E092064
– I4-NA109974
– Z092053
Notes: 1) Surface mounting enclosures are IEC type, totally insulated, corrosion-resistant, rated IP 65, NEMA rated 3R, 12.2) Above switches are identical to the selection on pages 07/020 and 021, except that the associated handle is not padlockable.
Exception: P3-.../IVS can be padlocked in the OFF position.All above handles are black with light-gray front plate.
3) All front plates shown may be exchanged at the time of the order at no extra charge. The prerequisite is that switching angles, the number of positions and the location of position 0 must be identical; a pages 07/052 and 053 for ordering details. English front plates supplied with the switches as shown in the catalog, can be exchanged for their French equivalent by adding the FS... number shown with suffix -F to the switch type (Example: T0-2-1/E-NA+FS908-F).
FS 908
ON
OFF
2
1 3
4
5
6
7
8
9
10 12
11
2
1 3
4
5
6
7
8
9
10 12
11 13
14 16
15
07/024 07/026
1-866-595-96161-630-595-9515 Go to: http://www.klocknermoeller.com
Cam Switches, Manual Motor Controllers, DisconnectsFor Three phase Applications
Cam
Sw
itch
es,
Mot
or D
isco
nnec
t Sw
itch
es
Cam
Sw
itch
es,
Mot
or D
isco
nnec
t Sw
itch
es
Cam Switches, Manual Motor Controllers, DisconnectsFor Three phase Applications
UL / CSA / IEC / CE UL / CSA / IEC / CE
Moeller Electric Corporation Moeller Electric Corporation
Circuit function diagram Front PlateNo. 3)
Main contacts(Num-ber of power poles)
Auxiliary contacts
Max. HP rating50-60 Hz, three-phaseUL/CSA
Current ratingUL/CSA
Cover mounting Center mounting22.5 mm opening
Surface mountingEnclosure 1)
Base mountingwith cover
Base mountingwith cover mounted handle and coupling drive
Basic type
for ..., insert mounting form
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price listN.O. N.O. N.C.
200 VHP
230 VHP
460 VHP
575 VHP A
On-Off switches3 0 0 3 3 10 10 14 T0-2-1/... E-NA
104475EZ-NA104477
I2-NA109880
IVS-NA109894
Z-NA104483
5 5 10 15 20 P1-25/... E038724
EZ041250
I2-NA255884
IVS052962
Z057708
7 ½ 10 20 25 30 P1-32/... E079065
EZ048369
I2-NA255890
IVS093303
Z098049
15 15 40 50 60 P3-63/... E026861
– I4-NA255896
IVS041099
Z050591
20 25 60 75 100 P3-100/... E067201
– I5-NA255902
IVS081439
Z090931
6 0 0 3 3 10 10 14 T0-3-8342/... E043624
EZ045997
I2-NA109969
IVS050743
Z055489
5 7 ½ 15 15 25 T3-3-8342/... E045225
EZ047598
I2-NA109970
– Z052344
15 15 40 50 65 T5B-3-8342/... E092310
– I4-NA109971
– Z092297
8 0 0 3 3 10 10 14 T0-4-8344/... E014000
EZ014002
I2-NA109972
IVS014006
Z014009
5 7 ½ 15 15 25 T3-4-8344/... E020593
EZ020595
I2-NA109973
– Z020600
15 15 40 50 65 T5B-4-8344/... E092064
– I4-NA109974
– Z092053
Notes: 1) Surface mounting enclosures are IEC type, totally insulated, corrosion-resistant, rated IP 65, NEMA rated 3R, 12.2) Above switches are identical to the selection on pages 07/020 and 021, except that the associated handle is not padlockable.
Exception: P3-.../IVS can be padlocked in the OFF position.All above handles are black with light-gray front plate.
3) All front plates shown may be exchanged at the time of the order at no extra charge. The prerequisite is that switching angles, the number of positions and the location of position 0 must be identical; a pages 07/052 and 053 for ordering details. English front plates supplied with the switches as shown in the catalog, can be exchanged for their French equivalent by adding the FS... number shown with suffix -F to the switch type (Example: T0-2-1/E-NA+FS908-F).
FS 908
ON
OFF
2
1 3
4
5
6
7
8
9
10 12
11
2
1 3
4
5
6
7
8
9
10 12
11 13
14 16
15
07/024 07/025
1-866-595-96161-630-595-9515 Go to: http://www.klocknermoeller.com
Cam Switches, Manual Motor Controllers, DisconnectsFor Three phase Applications
Cam
Sw
itch
es,
Mot
or D
isco
nnec
t Sw
itch
es
Cam
Sw
itch
es,
Mot
or D
isco
nnec
t Sw
itch
es
Cam Switches, Manual Motor Controllers, DisconnectsFor Three phase Applications
UL / CSA / IEC / CE UL / CSA / IEC / CE
Moeller Electric Corporation Moeller Electric Corporation
Circuit function diagram Front plate No. 3)
Main contacts (Number of power poles)
Auxiliary contacts
Max. HP rating50-60 Hz, three-phaseUL/CSA
Current ratingUL/CSA
Cover mounting Center mounting22.5 mm opening
Surface mountingEnclosure 1)
Base mountingwith cover
Base mountingwith cover mounted handleand coupling drive
Basic type
for ..., insert mounting form
Mounting formArticle No.
Price
see price list
Mounting formArticle No.
Price
see price list
Mounting formArticle No.
Price
see price list
Mounting formArticle No.
Price
see price list
Mounting formArticle No.
Price
see price list
N.O. N.O. N.C.200 VHP
230 VHP
460 VHP
575 VHP A
ON-OFF switches with auxiliary contacts3 1 0 3 3 10 10 14 T0-2-15679/... E
029387EZ031760
I2-NA109885
IVS036506
Z041252
3 1 1 5 5 10 15 20 P1-25/... E/HI11045998
EZ/HI11048371
I2/HI11-NA109886
IVS/HI11053117
Z/HI11057863
7 ½ 10 20 25 30 P1-32/... E/HI11062609
EZ/HI11064982
I2/HI11-NA109887
IVS/HI11069728
Z/HI11074474
15 15 40 50 60 P3-63/... E/HI11079220
– I4/HI11-NA109888
IVS/HI11081593
Z/HI11086339
20 25 60 75 100 P3-100/... E/HI11069574
– I5/HI11-NA109889
IVS/HI11091085
Z/HI11093304
3 2 1 3 3 10 10 14 T0-3-15683/... E016619
EZ016658
I2-NA109979
IVS016722
Z016843
5 7 ½ 15 15 25 T3-3-15683/... E014377
EZ040480
I2-NA109980
– Z019123
6 1 1 3 3 10 10 14 T0-4-15682/... E010405
EZ012778
I2-NA109981
IVS017524
Z022270
5 7 ½ 15 15 25 T3-4-15682/... E023869
EZ026242
I2-NA109982
– Z030988
15 15 40 50 65 T5B-4-15682/... E207424
– I4-NA109983
– Z207429
ON-OFF switches, used as Emergency-Stop switches3 0 0 3 3 10 10 14 T0-2-1/... E-RT-NA
109904– I2-RT-NA
109911IVS-RT-NA109918
–
5 5 10 15 20 P1-25/... E-RT002388
– I2-RT-NA255887
IVS-RT013140
–
7 ½ 10 20 25 30 P1-32/... E-RT003197
– I2-RT-NA255893
IVS-RT022632
–
15 15 40 50 60 P3-63/... E-RT005743
– I4-RT-NA255899
IVS-RT045845
–
20 25 60 75 100 P3-100/... E-RT007189
– I5-RT-NA255905
IVS-RT086185
–
Notes: 1) Surface mounted enclosures are IEC type, totally insulated, corrosion-resistant rated IP 65, NEMA rated 3R, 12.2) On-Off switches with auxiliary contacts have black handle with light gray nameplate,
On-Off switches used as Emergency-Stop have a red handle with yellow back frame.Above handles are not lockable. Exception: P3-.../IVS(-RT) can be padlocked in the OFF position.
3) All front plates shown may be exchanged at the time of the order at no extra charge. The prerequisite is that switching angles, the number of positions and the location of position 0 must be identical; a pages 07/052 and 053 for ordering details. English front plates supplied with the switches as shown in the catalog, can be exchanged for their French equivalent by adding the FS... number shown with suffix -F to the switch type (Example: T0-2-15679-E+FS908-F).
FS 908
ON
OFF
2
1 3
4
5
6
7
8
2
1 3
4
5
6
13
14 22
21
L2 L3L1
2
1 3
4
5
6
7
8
9
10 12
11
2
1 3
4
5
6
7
8
9
10 12
11 13
14 16
15
FS 908 GE
1
0
07/026 07/027
1-866-595-96161-630-595-9515 Go to: http://www.klocknermoeller.com
Cam Switches, Manual Motor Controllers, DisconnectsFor Three phase Applications
Cam
Sw
itch
es,
Mot
or D
isco
nnec
t Sw
itch
es
Cam
Sw
itch
es,
Mot
or D
isco
nnec
t Sw
itch
es
Cam Switches, Manual Motor Controllers, DisconnectsFor Three phase Applications
UL / CSA / IEC / CE UL / CSA / IEC / CE
Moeller Electric Corporation Moeller Electric Corporation
Circuit function diagram Front plate No. 3)
Main contacts (Number of power poles)
Auxiliary contacts
Max. HP rating50-60 Hz, three-phaseUL/CSA
Current ratingUL/CSA
Cover mounting Center mounting22.5 mm opening
Surface mountingEnclosure 1)
Base mountingwith cover
Base mountingwith cover mounted handleand coupling drive
Basic type
for ..., insert mounting form
Mounting formArticle No.
Price
see price list
Mounting formArticle No.
Price
see price list
Mounting formArticle No.
Price
see price list
Mounting formArticle No.
Price
see price list
Mounting formArticle No.
Price
see price list
N.O. N.O. N.C.200 VHP
230 VHP
460 VHP
575 VHP A
ON-OFF switches with auxiliary contacts3 1 0 3 3 10 10 14 T0-2-15679/... E
029387EZ031760
I2-NA109885
IVS036506
Z041252
3 1 1 5 5 10 15 20 P1-25/... E/HI11045998
EZ/HI11048371
I2/HI11-NA109886
IVS/HI11053117
Z/HI11057863
7 ½ 10 20 25 30 P1-32/... E/HI11062609
EZ/HI11064982
I2/HI11-NA109887
IVS/HI11069728
Z/HI11074474
15 15 40 50 60 P3-63/... E/HI11079220
– I4/HI11-NA109888
IVS/HI11081593
Z/HI11086339
20 25 60 75 100 P3-100/... E/HI11069574
– I5/HI11-NA109889
IVS/HI11091085
Z/HI11093304
3 2 1 3 3 10 10 14 T0-3-15683/... E016619
EZ016658
I2-NA109979
IVS016722
Z016843
5 7 ½ 15 15 25 T3-3-15683/... E014377
EZ040480
I2-NA109980
– Z019123
6 1 1 3 3 10 10 14 T0-4-15682/... E010405
EZ012778
I2-NA109981
IVS017524
Z022270
5 7 ½ 15 15 25 T3-4-15682/... E023869
EZ026242
I2-NA109982
– Z030988
15 15 40 50 65 T5B-4-15682/... E207424
– I4-NA109983
– Z207429
ON-OFF switches, used as Emergency-Stop switches3 0 0 3 3 10 10 14 T0-2-1/... E-RT-NA
109904– I2-RT-NA
109911IVS-RT-NA109918
–
5 5 10 15 20 P1-25/... E-RT002388
– I2-RT-NA255887
IVS-RT013140
–
7 ½ 10 20 25 30 P1-32/... E-RT003197
– I2-RT-NA255893
IVS-RT022632
–
15 15 40 50 60 P3-63/... E-RT005743
– I4-RT-NA255899
IVS-RT045845
–
20 25 60 75 100 P3-100/... E-RT007189
– I5-RT-NA255905
IVS-RT086185
–
Notes: 1) Surface mounted enclosures are IEC type, totally insulated, corrosion-resistant rated IP 65, NEMA rated 3R, 12.2) On-Off switches with auxiliary contacts have black handle with light gray nameplate,
On-Off switches used as Emergency-Stop have a red handle with yellow back frame.Above handles are not lockable. Exception: P3-.../IVS(-RT) can be padlocked in the OFF position.
3) All front plates shown may be exchanged at the time of the order at no extra charge. The prerequisite is that switching angles, the number of positions and the location of position 0 must be identical; a pages 07/052 and 053 for ordering details. English front plates supplied with the switches as shown in the catalog, can be exchanged for their French equivalent by adding the FS... number shown with suffix -F to the switch type (Example: T0-2-15679-E+FS908-F).
FS 908
ON
OFF
2
1 3
4
5
6
7
8
2
1 3
4
5
6
13
14 22
21
L2 L3L1
2
1 3
4
5
6
7
8
9
10 12
11
2
1 3
4
5
6
7
8
9
10 12
11 13
14 16
15
FS 908 GE
1
0
07/026 07/027
1-866-595-96161-630-595-9515 Go to: http://www.klocknermoeller.com
Moeller Electric Corporation Moeller Electric Corporation
Circuit function diagram Front plateNo. 3)
Main contacts(Number of power poles)
Max. HP rating50-60 Hz, three-phaseUL/CSA
CurrentratingUL/CSA
Cover mounting Center mounting22.5 mm opening
Surface mounting Enclosure 1)
Base mountingwith cover
Base mountingwith cover mounted handleand coupling drive
Basic type
for ..., insert mounting form
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price listN.O.
200 VHP
230 VHP
460 VHP
575 VHP A
Change-over switches with OFF positionPositions are maintained
3 3 3 10 10 14 T0-3-8212/... E029353
EZ057829
I2-NA109984
IVS079186
Z036473
5 7 ½ 15 15 25 T3-3-8212/... E068956
EZ003080
I2-NA109985
– Z071329
15 15 40 50 65 T5B-3-8212/... E092386
– I4-NA109986
– Z092383
Change-over switches with OFF positionPositions are spring-returned to OFF
3 3 3 10 10 14 T0-3-8216/... E024609
EZ086307
I2-NA109987
IVS050713
Z055466
5 7 ½ 15 15 25 T3-3-8216/... E023870
EZ001077
I2-NA109988
– Z026243
Change-over switches without OFF positionPositions are maintained
3 3 3 10 10 14 T0-3-8222/... E048339
EZ015118
I2-NA109989
IVS060205
Z088686
5 7 ½ 15 15 25 T3-3-8222/... E052346
EZ001069
I2-NA109990
– Z057092
15 15 40 50 65 T5B-3-8222/... E092378
– I4-NA109991
– Z092375
6 3 3 10 10 14 T0-6-8370/... E062577
EZ029356
– IVS067324
Z010380
5 7 ½ 15 15 25 T3-6-8370/... E073703
EZ004506
– – Z078449
Notes: 1) Surface mounting enclosures are IEC type, totally insulated, corrosion-resistant rated IP 65, NEMA rated 3R, 12.2) Above switches have black handle with light gray nameplates.3) All front plates shown may be exchanged at the time of the order at no extra charge. The prerequisite is that switching angles, the
number of positions and the location of position 0 must be identical; a pages 07/052 and 053 for ordering details.
201
2
1 3
4
5
6
7
8
9
10
11
12
FS 684
01 2
102
2
1 3
4
5
6
7
8
9
10
11
12
FS 4011
01 2
12
2
1 3
4
5
6
7
8
9
10
11
12 1 2
FS 943
12
2
1 3
4
5
6
7
8
9
10
11
12
13 15
1614
17 19
2018
21
22 24
23
07/028 07/029
1-866-595-96161-630-595-9515 Go to: http://www.klocknermoeller.com
Moeller Electric Corporation Moeller Electric Corporation
Circuit function diagram Front plateNo. 3)
Main contacts(Number of power poles)
Max. HP rating50-60 Hz, three-phaseUL/CSA
CurrentratingUL/CSA
Cover mounting Center mounting22.5 mm opening
Surface mounting Enclosure 1)
Base mountingwith cover
Base mountingwith cover mounted handleand coupling drive
Basic type
for ..., insert mounting form
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price listN.O.
200 VHP
230 VHP
460 VHP
575 VHP A
Change-over switches with OFF positionPositions are maintained
3 3 3 10 10 14 T0-3-8212/... E029353
EZ057829
I2-NA109984
IVS079186
Z036473
5 7 ½ 15 15 25 T3-3-8212/... E068956
EZ003080
I2-NA109985
– Z071329
15 15 40 50 65 T5B-3-8212/... E092386
– I4-NA109986
– Z092383
Change-over switches with OFF positionPositions are spring-returned to OFF
3 3 3 10 10 14 T0-3-8216/... E024609
EZ086307
I2-NA109987
IVS050713
Z055466
5 7 ½ 15 15 25 T3-3-8216/... E023870
EZ001077
I2-NA109988
– Z026243
Change-over switches without OFF positionPositions are maintained
3 3 3 10 10 14 T0-3-8222/... E048339
EZ015118
I2-NA109989
IVS060205
Z088686
5 7 ½ 15 15 25 T3-3-8222/... E052346
EZ001069
I2-NA109990
– Z057092
15 15 40 50 65 T5B-3-8222/... E092378
– I4-NA109991
– Z092375
6 3 3 10 10 14 T0-6-8370/... E062577
EZ029356
– IVS067324
Z010380
5 7 ½ 15 15 25 T3-6-8370/... E073703
EZ004506
– – Z078449
Notes: 1) Surface mounting enclosures are IEC type, totally insulated, corrosion-resistant rated IP 65, NEMA rated 3R, 12.2) Above switches have black handle with light gray nameplates.3) All front plates shown may be exchanged at the time of the order at no extra charge. The prerequisite is that switching angles, the
number of positions and the location of position 0 must be identical; a pages 07/052 and 053 for ordering details.
201
2
1 3
4
5
6
7
8
9
10
11
12
FS 684
01 2
102
2
1 3
4
5
6
7
8
9
10
11
12
FS 4011
01 2
12
2
1 3
4
5
6
7
8
9
10
11
12 1 2
FS 943
12
2
1 3
4
5
6
7
8
9
10
11
12
13 15
1614
17 19
2018
21
22 24
23
07/028 07/029
1-866-595-96161-630-595-9515 Go to: http://www.klocknermoeller.com
Notes: 1) Surface mounting enclosures are IEC type, totally insulated, corrosion resistant rated IP 65, NEMA rated 3R, 12.2) Above switches have black handle with light gray nameplate.3) All front plates shown may be exchanged at the time of the order at no extra charge. The prerequisite is that switching angles, the
number of positions and the location of position 0 must be identical; a pages 07/052 and 053 for ordering details. English front plates supplied with the switches as shown in the catalog, can be exchanged for their French equivalent by adding the FS... number shown with suffix -F to the switch type (Example: T0-3-8401/E-NA+FS1665-F).
07/030 07/031
1-866-595-96161-630-595-9515 Go to: http://www.klocknermoeller.com
Notes: 1) Surface mounting enclosures are IEC type, totally insulated, corrosion resistant rated IP 65, NEMA rated 3R, 12.2) Above switches have black handle with light gray nameplate.3) All front plates shown may be exchanged at the time of the order at no extra charge. The prerequisite is that switching angles, the
number of positions and the location of position 0 must be identical; a pages 07/052 and 053 for ordering details. English front plates supplied with the switches as shown in the catalog, can be exchanged for their French equivalent by adding the FS... number shown with suffix -F to the switch type (Example: T0-3-8401/E-NA+FS1665-F).
07/030 07/031
1-866-595-96161-630-595-9515 Go to: http://www.klocknermoeller.com
Moeller Electric Corporation Moeller Electric Corporation
Circuit function diagram Front Plate No. 3)
Main contacts (Number of power poles)
Max. HP rating50-60 Hz, three-phaseUL/CSA
Current ratingUL/CSA
Cover mounting Center mounting22.5 mm opening
Surface mountingEnclosure 1)
Base mountingwith cover
Base mountingwith cover mounted handleand coupling drive
Basic type
for ..., insert mounting form
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price listN.O.
200 VHP
230 VHP
460 VHP
575 VHP A
Multi-speed switchesTwo-speed, non-reversing for two separate windings
3 3 3 10 10 14 T0-3-8451/... E-NA104650
EZ-NA104651
I2-NA110018
IVS-NA110027
Z-NA104653
5 7 ½ 15 15 25 T3-3-8451/... E-NA104783
EZ-NA104784
I2-NA110019
– Z-NA104786
15 15 40 50 65 T5B-3-8451/... E-NA110014
– I4-NA110020
– Z-NA110031
Two-speed, non-reversing for one tapped winding3 3 3 10 10 14 T0-4-8440/... E-NA
104673EZ-NA104674
I2-NA110021
IVS-NA110028
Z-NA104676
5 7 ½ 15 15 25 T3-4-8440/... E-NA104794
EZ-NA104795
I2-NA110022
– Z-NA104797
15 15 40 50 65 T5B-4-8440/... E-NA110015
– I4-NA110023
– Z-NA110032
3 3 3 10 10 14 T0-4-8441/... E-NA104677
EZ-NA104678
I2-NA110024
IVS-NA110029
Z-NA104680
5 7 ½ 15 15 25 T3-4-8441/... E-NA104798
EZ-NA104799
I2-NA110025
– Z-NA104801
15 15 40 50 65 T5B-4-8441/... E-NA110016
– I4-NA110026
– Z-NA110033
Reversing multi-speed switchesTwo-speed , for one tapped winding
3 3 3 10 10 14 T0-6-15866/... E-NA104710
EZ-NA104711
– IVS-NA110030
Z-NA104712
5 7 ½ 15 15 25 T3-6-15866/... E-NA104812
EZ-NA104813
– – Z-NA104814
3 15 15 40 50 65 T5B-7-15866/... E-NA110017
– – – Z-NA110034
Notes: 1) Surface mounting enclosures are IEC type, totally insulated, corrosion-resistant rated IP 65, NEMA 3R, 12.2) Above switches have black handle with light gray nameplate.3) All front plates shown may be exchanged at the time of the order at no extra charge. The prerequisite is that switching angles, the number
of positions and the location of position 0 must be identical; a pages 07/052 and 053 for ordering details. English front plates supplied with the switches as shown in the catalog, can be exchanged for their French equivalent by adding the FS... number shown with suffix -F to the switch type (Example: T0-3-8451/E-NA+FS16052-F).
07/032 07/033
1-866-595-96161-630-595-9515 Go to: http://www.klocknermoeller.com
Moeller Electric Corporation Moeller Electric Corporation
Circuit function diagram Front Plate No. 3)
Main contacts (Number of power poles)
Max. HP rating50-60 Hz, three-phaseUL/CSA
Current ratingUL/CSA
Cover mounting Center mounting22.5 mm opening
Surface mountingEnclosure 1)
Base mountingwith cover
Base mountingwith cover mounted handleand coupling drive
Basic type
for ..., insert mounting form
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price listN.O.
200 VHP
230 VHP
460 VHP
575 VHP A
Multi-speed switchesTwo-speed, non-reversing for two separate windings
3 3 3 10 10 14 T0-3-8451/... E-NA104650
EZ-NA104651
I2-NA110018
IVS-NA110027
Z-NA104653
5 7 ½ 15 15 25 T3-3-8451/... E-NA104783
EZ-NA104784
I2-NA110019
– Z-NA104786
15 15 40 50 65 T5B-3-8451/... E-NA110014
– I4-NA110020
– Z-NA110031
Two-speed, non-reversing for one tapped winding3 3 3 10 10 14 T0-4-8440/... E-NA
104673EZ-NA104674
I2-NA110021
IVS-NA110028
Z-NA104676
5 7 ½ 15 15 25 T3-4-8440/... E-NA104794
EZ-NA104795
I2-NA110022
– Z-NA104797
15 15 40 50 65 T5B-4-8440/... E-NA110015
– I4-NA110023
– Z-NA110032
3 3 3 10 10 14 T0-4-8441/... E-NA104677
EZ-NA104678
I2-NA110024
IVS-NA110029
Z-NA104680
5 7 ½ 15 15 25 T3-4-8441/... E-NA104798
EZ-NA104799
I2-NA110025
– Z-NA104801
15 15 40 50 65 T5B-4-8441/... E-NA110016
– I4-NA110026
– Z-NA110033
Reversing multi-speed switchesTwo-speed , for one tapped winding
3 3 3 10 10 14 T0-6-15866/... E-NA104710
EZ-NA104711
– IVS-NA110030
Z-NA104712
5 7 ½ 15 15 25 T3-6-15866/... E-NA104812
EZ-NA104813
– – Z-NA104814
3 15 15 40 50 65 T5B-7-15866/... E-NA110017
– – – Z-NA110034
Notes: 1) Surface mounting enclosures are IEC type, totally insulated, corrosion-resistant rated IP 65, NEMA 3R, 12.2) Above switches have black handle with light gray nameplate.3) All front plates shown may be exchanged at the time of the order at no extra charge. The prerequisite is that switching angles, the number
of positions and the location of position 0 must be identical; a pages 07/052 and 053 for ordering details. English front plates supplied with the switches as shown in the catalog, can be exchanged for their French equivalent by adding the FS... number shown with suffix -F to the switch type (Example: T0-3-8451/E-NA+FS16052-F).
07/032 07/033
1-866-595-96161-630-595-9515 Go to: http://www.klocknermoeller.com
Cam SwitchesFor Control Circuit Functions: Stepping Switches
Cam
Sw
itch
es,
Mot
orD
isco
nnec
t Sw
itch
es
Cam
Sw
itch
es,
Mot
or D
isco
nnec
t Sw
itch
es
Cam SwitchesFor Control Circuit Functions: Stepping Switches
UL / CSA / IEC / CE UL / CSA / IEC / CE
Moeller Electric CorporationMoeller Electric Corporation
Circuit function diagram Front Plate No. 3)
No. of poles
No. of steps
Cover mounting Center mounting22.5 mm opening
Surface mounting 1)
EnclosureBase mountingwith cover
Base mountingwith cover mounted handleand coupling drive
Basic typefor ..., insert mounting form
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price list
Stepping switchesOne contact closed per step (without overlap), with additional OFF (0) position
1 2 T0-1-8240/... E034105
EZ043597
I2-NA110047
IVS027076
Z060208
1 3 T0-2-8241/... E050716
EZ053089
I2-NA110048
IVS057835
Z062581
1 4 T0-2-8242/... E067327
EZ069700
I2-NA110049
IVS074446
Z076819
1 5 T0-3-8243/... E081565
EZ083938
I2-NA110050
IVS088684
Z091057
1 6 T0-3-8244/... E095803
EZ098176
I2-NA110051
IVS012749
Z015122
3 2 T0-3-8280/... E034106
EZ036479
I2-NA110052
IVS041225
Z043598
3 3 T0-5-8281/... E048344
EZ050717
– IVS055463
Z057836
3 4 T0-6-8282/... E062582
EZ064955
– IVS069701
Z072074
Notes: 1) Surface mounting enclosure are IEC type, toally insulated, corrosion-resistantrated IP 65, NEMA rated 3R, 12.2) All switches have black handle with light gray nameplate. 3) All front plates shown may be exchanged at the time of the order at no extra charge. The prerequisite is that switching angles, the
number of positions and the location of position 0 must be identical; a pages 07/052 and 053 for ordering details.
FS 418
21
0
3210
2
1 3
4
5
6
FS 420
21
03
3210
4
2
1 3
4
5
6
7
8
FS 422
21
034
3210
45
2
1 3
4
5
6
7
8
9
10
FS 424
21
034
5
3210
456
2
1 3
4
5
6
7
8
11
1210
9
FS 426
21
034
65
210
2
1 3
4
5
6
7
8
9
10
11
12
FS 418
21
0
210
3
2
1 3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
FS 420
21
03
210
34
2
1 3
4
5
6
7
8
9
10
11 13 15
12 14 16
17 19
18 20
21
22
23
24
FS 422
21
034
Notes:IEC RatingsSuitable for actuating electronic devices Rated uninterrupted current Iu 20 ARated operational current Ie
AC-15220 – 240 V380 – 415 V
6 A4 A
AC-21A 12 ADC-13 32 V per contact 10 A
Further technical data a page 07/072UL/CSA Ratings:Heavy Pilot Duty A 600, P 600
07/034 07/035
1-866-595-96161-630-595-9515 Go to: http://www.klocknermoeller.com
Cam SwitchesFor Control Circuit Functions: Stepping Switches
Cam
Sw
itch
es,
Mot
orD
isco
nnec
t Sw
itch
es
Cam
Sw
itch
es,
Mot
or D
isco
nnec
t Sw
itch
es
Cam SwitchesFor Control Circuit Functions: Stepping Switches
UL / CSA / IEC / CE UL / CSA / IEC / CE
Moeller Electric CorporationMoeller Electric Corporation
Circuit function diagram Front Plate No. 3)
No. of poles
No. of steps
Cover mounting Center mounting22.5 mm opening
Surface mounting 1)
EnclosureBase mountingwith cover
Base mountingwith cover mounted handleand coupling drive
Basic typefor ..., insert mounting form
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price list
Stepping switchesOne contact closed per step (without overlap), with additional OFF (0) position
1 2 T0-1-8240/... E034105
EZ043597
I2-NA110047
IVS027076
Z060208
1 3 T0-2-8241/... E050716
EZ053089
I2-NA110048
IVS057835
Z062581
1 4 T0-2-8242/... E067327
EZ069700
I2-NA110049
IVS074446
Z076819
1 5 T0-3-8243/... E081565
EZ083938
I2-NA110050
IVS088684
Z091057
1 6 T0-3-8244/... E095803
EZ098176
I2-NA110051
IVS012749
Z015122
3 2 T0-3-8280/... E034106
EZ036479
I2-NA110052
IVS041225
Z043598
3 3 T0-5-8281/... E048344
EZ050717
– IVS055463
Z057836
3 4 T0-6-8282/... E062582
EZ064955
– IVS069701
Z072074
Notes: 1) Surface mounting enclosure are IEC type, toally insulated, corrosion-resistantrated IP 65, NEMA rated 3R, 12.2) All switches have black handle with light gray nameplate. 3) All front plates shown may be exchanged at the time of the order at no extra charge. The prerequisite is that switching angles, the
number of positions and the location of position 0 must be identical; a pages 07/052 and 053 for ordering details.
FS 418
21
0
3210
2
1 3
4
5
6
FS 420
21
03
3210
4
2
1 3
4
5
6
7
8
FS 422
21
034
3210
45
2
1 3
4
5
6
7
8
9
10
FS 424
21
034
5
3210
456
2
1 3
4
5
6
7
8
11
1210
9
FS 426
21
034
65
210
2
1 3
4
5
6
7
8
9
10
11
12
FS 418
21
0
210
3
2
1 3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
FS 420
21
03
210
34
2
1 3
4
5
6
7
8
9
10
11 13 15
12 14 16
17 19
18 20
21
22
23
24
FS 422
21
034
Notes:IEC RatingsSuitable for actuating electronic devices Rated uninterrupted current Iu 20 ARated operational current Ie
AC-15220 – 240 V380 – 415 V
6 A4 A
AC-21A 12 ADC-13 32 V per contact 10 A
Further technical data a page 07/072UL/CSA Ratings:Heavy Pilot Duty A 600, P 600
07/034 07/035
1-866-595-96161-630-595-9515 Go to: http://www.klocknermoeller.com
Cam SwitchesFor Control Circuit Functions: Stepping Switches
Cam
Sw
itch
es,
Mot
orD
isco
nnec
t Sw
itch
es
Cam
Sw
itch
es,
Mot
or D
isco
nnec
t Sw
itch
es
Cam SwitchesFor Control Circuit Functions: Stepping Switches
UL / CSA / IEC / CE UL / CSA / IEC / CE
Moeller Electric CorporationMoeller Electric Corporation
Circuit function diagram Front Plate No. 3)
No. of poles
No. of steps
Cover mounting Center mounting22.5 mm opening
Surface mountingEnclosure
Base mountingwith cover
Base mountingwith cover mounted handleand coupling drive
Basic typefor ..., insert mounting form
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price list
Stepping switchesOne contact closed per step (without overlap),without additional OFF position
1 2 T0-1-8220/... E031728
EZ095799
I2-NA109931
IVS055459
Z086312
1 3 T0-2-8230/... E088685
EZ091058
I2-NA110054
IVS095804
Z098177
1 4 T0-2-8231/... E012750
EZ015123
I2-NA110055
IVS019869
Z022242
1 5 T0-3-8232/... E026988
EZ029361
I2-NA110056
IVS034107
Z036480
1 6 T0-3-8233/... E041226
EZ043599
I2-NA110057
IVS048345
Z050718
3 2 T0-3-8222/... E048339
EZ015118
I2-NA109989
IVS060205
Z088686
3 3 T0-5-8270/... E091059
EZ093432
– IVS098178
Z010378
3 4 T0-6-8271/... E015124
EZ017497
– IVS022243
Z024616
Notes: 1) Surface mounted enclosures are IEC type, totally insulated, corrosion-resistant rated IP 65, NEMA rated 3R, 12.2) All switches have black handle with light gray nameplate.3) All front plates shown may be exchanged at the time of the order at no extra charge. The prerequisite is that switching angles, the
number of positions and the location of position 0 must be identical; a pages 07/052 and 053 for ordering details.
12
2
1 3
4
FS 943
1 2
321
2
1 3
4
5
6
FS 404
32
1
321
4
2
1 3
4
5
6
7
8
FS 606
2
41
3
321
45
2
1 3
4
5
6
7
8
9
10
FS 408
32 4
51
321
456
2
1 3
4
5
6
7
8
9
10
11
12
FS 410
32 4
516
12
2
1 3
4
5
6
7
8
9
10
11
12
FS 943
1 2
321
2
1 3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
FS 404
32
1
21
34
2
1 3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
FS 606
2
41
3
Notes:IEC Ratings:Suitable for actuating electronic devcesRated uninterrupted cur-rent Iu
20 A
Rated operational current Ie
AC-15220 – 240 V380 – 415 V
6 A4 A
AC-21A 12 ADC-13 32 V per con-
tact10 A
Further technical data a page 07/072UL/CSA Ratings:Heavy Pilot duty A 600, P 600
07/036 07/037
1-866-595-96161-630-595-9515 Go to: http://www.klocknermoeller.com
Cam SwitchesFor Control Circuit Functions: Stepping Switches
Cam
Sw
itch
es,
Mot
orD
isco
nnec
t Sw
itch
es
Cam
Sw
itch
es,
Mot
or D
isco
nnec
t Sw
itch
es
Cam SwitchesFor Control Circuit Functions: Stepping Switches
UL / CSA / IEC / CE UL / CSA / IEC / CE
Moeller Electric CorporationMoeller Electric Corporation
Circuit function diagram Front Plate No. 3)
No. of poles
No. of steps
Cover mounting Center mounting22.5 mm opening
Surface mountingEnclosure
Base mountingwith cover
Base mountingwith cover mounted handleand coupling drive
Basic typefor ..., insert mounting form
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price list
Stepping switchesOne contact closed per step (without overlap),without additional OFF position
1 2 T0-1-8220/... E031728
EZ095799
I2-NA109931
IVS055459
Z086312
1 3 T0-2-8230/... E088685
EZ091058
I2-NA110054
IVS095804
Z098177
1 4 T0-2-8231/... E012750
EZ015123
I2-NA110055
IVS019869
Z022242
1 5 T0-3-8232/... E026988
EZ029361
I2-NA110056
IVS034107
Z036480
1 6 T0-3-8233/... E041226
EZ043599
I2-NA110057
IVS048345
Z050718
3 2 T0-3-8222/... E048339
EZ015118
I2-NA109989
IVS060205
Z088686
3 3 T0-5-8270/... E091059
EZ093432
– IVS098178
Z010378
3 4 T0-6-8271/... E015124
EZ017497
– IVS022243
Z024616
Notes: 1) Surface mounted enclosures are IEC type, totally insulated, corrosion-resistant rated IP 65, NEMA rated 3R, 12.2) All switches have black handle with light gray nameplate.3) All front plates shown may be exchanged at the time of the order at no extra charge. The prerequisite is that switching angles, the
number of positions and the location of position 0 must be identical; a pages 07/052 and 053 for ordering details.
12
2
1 3
4
FS 943
1 2
321
2
1 3
4
5
6
FS 404
32
1
321
4
2
1 3
4
5
6
7
8
FS 606
2
41
3
321
45
2
1 3
4
5
6
7
8
9
10
FS 408
32 4
51
321
456
2
1 3
4
5
6
7
8
9
10
11
12
FS 410
32 4
516
12
2
1 3
4
5
6
7
8
9
10
11
12
FS 943
1 2
321
2
1 3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
FS 404
32
1
21
34
2
1 3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
FS 606
2
41
3
Notes:IEC Ratings:Suitable for actuating electronic devcesRated uninterrupted cur-rent Iu
20 A
Rated operational current Ie
AC-15220 – 240 V380 – 415 V
6 A4 A
AC-21A 12 ADC-13 32 V per con-
tact10 A
Further technical data a page 07/072UL/CSA Ratings:Heavy Pilot duty A 600, P 600
07/036 07/037
1-866-595-96161-630-595-9515 Go to: http://www.klocknermoeller.com
Cam SwitchesFor Control Circuit Functions: ON-OFF, Change-over Switches
Cam
Sw
itch
es,
Mot
orD
isco
nnec
t Sw
itch
es
Cam
Sw
itch
es,
Mot
or D
isco
nnec
t Sw
itch
es
Cam SwitchesFor Control Circuit Functions: ON-OFF, Change-over Switches
UL / CSA / IEC / CE UL / CSA / IEC / CE
Moeller Electric CorporationMoeller Electric Corporation
Circuit function diagram Front Plate No. 3)
No. of poles
Cover mounting Center mounting22.5 mm opening
Surface mountingEnclosure
Base mountingwith cover
Base mountingwith cover mounted handleand coupling drive
Basic type
for ..., insert mounting form
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price list
ON-OFF switches1 T0-1-15401/... E-NA
104403EZ-NA104404
I2-NA110058
IVS-NA110065
Z-NA104406
2 T0-1-15402/... E-NA104407
EZ-NA104408
I2-NA110059
IVS-NA110066
Z-NA104410
3 T0-2-15403/... E-NA104491
EZ-NA104492
I2-NA110060
IVS-NA110067
Z-NA104494
4 T0-2-15404/... E-NA104495
EZ-NA104496
I2-NA110061
IVS-NA110068
Z-NA104498
Change-over switches1 T0-1-15421/... E
095806EZ098179
I2-NA110062
IVS012752
Z015125
2 T0-2-15422/... E019871
EZ022244
I2-NA110063
IVS026990
Z029363
3 T0-3-15423/... E034109
EZ036482
I2-NA110064
IVS041228
Z043601
Notes: 1) Surface mounted enclosures are IEC type, totally insulated, corrosion-resistant rated IP 65, NEMA rated 3R, 12.2) All switches have black handle with light gray nameplate. 3) All front plates shown may be exchanged at the time of the order at no extra charge. The prerequisite is that switching angles, the
number of positions and the location of position 0 must be identical; a pages 07/052 and 053 for ordering details. English front plates supplied with the switches as shown in the catalog, can be exchanged for their French equivalent by adding the FS... number shown with suffix -F to the switch type (Example: T0-1-15401/E-NA+FS147472-F).
102
2
1 3
4
FS 429
02 1
102
2
1 3
4
5
6
7
8
FS 429
02 1
102
2
1 3
4
5
6
7
8
9
10
11
12
FS 429
02 1
NotesIEC Ratings:Suitable for actuating electronic devicesRated uninterrupted cur-rent Iu
20 A
Rated operational current Ie
AC-15220 – 240 V380 – 415 V
6 A4 A
AC-21A 12 ADC-13 32 V per con-
tact10 A
Further technical data a page 07/072UL/CSA Ratings:Heavy Pilot Duty A 600, P 600
07/038 07/039
1-866-595-96161-630-595-9515 Go to: http://www.klocknermoeller.com
Cam SwitchesFor Control Circuit Functions: ON-OFF, Change-over Switches
Cam
Sw
itch
es,
Mot
orD
isco
nnec
t Sw
itch
es
Cam
Sw
itch
es,
Mot
or D
isco
nnec
t Sw
itch
es
Cam SwitchesFor Control Circuit Functions: ON-OFF, Change-over Switches
UL / CSA / IEC / CE UL / CSA / IEC / CE
Moeller Electric CorporationMoeller Electric Corporation
Circuit function diagram Front Plate No. 3)
No. of poles
Cover mounting Center mounting22.5 mm opening
Surface mountingEnclosure
Base mountingwith cover
Base mountingwith cover mounted handleand coupling drive
Basic type
for ..., insert mounting form
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price list
ON-OFF switches1 T0-1-15401/... E-NA
104403EZ-NA104404
I2-NA110058
IVS-NA110065
Z-NA104406
2 T0-1-15402/... E-NA104407
EZ-NA104408
I2-NA110059
IVS-NA110066
Z-NA104410
3 T0-2-15403/... E-NA104491
EZ-NA104492
I2-NA110060
IVS-NA110067
Z-NA104494
4 T0-2-15404/... E-NA104495
EZ-NA104496
I2-NA110061
IVS-NA110068
Z-NA104498
Change-over switches1 T0-1-15421/... E
095806EZ098179
I2-NA110062
IVS012752
Z015125
2 T0-2-15422/... E019871
EZ022244
I2-NA110063
IVS026990
Z029363
3 T0-3-15423/... E034109
EZ036482
I2-NA110064
IVS041228
Z043601
Notes: 1) Surface mounted enclosures are IEC type, totally insulated, corrosion-resistant rated IP 65, NEMA rated 3R, 12.2) All switches have black handle with light gray nameplate. 3) All front plates shown may be exchanged at the time of the order at no extra charge. The prerequisite is that switching angles, the
number of positions and the location of position 0 must be identical; a pages 07/052 and 053 for ordering details. English front plates supplied with the switches as shown in the catalog, can be exchanged for their French equivalent by adding the FS... number shown with suffix -F to the switch type (Example: T0-1-15401/E-NA+FS147472-F).
102
2
1 3
4
FS 429
02 1
102
2
1 3
4
5
6
7
8
FS 429
02 1
102
2
1 3
4
5
6
7
8
9
10
11
12
FS 429
02 1
NotesIEC Ratings:Suitable for actuating electronic devicesRated uninterrupted cur-rent Iu
20 A
Rated operational current Ie
AC-15220 – 240 V380 – 415 V
6 A4 A
AC-21A 12 ADC-13 32 V per con-
tact10 A
Further technical data a page 07/072UL/CSA Ratings:Heavy Pilot Duty A 600, P 600
07/038 07/039
1-866-595-96161-630-595-9515 Go to: http://www.klocknermoeller.com
Cam SwitchesFor Control Circuit Functions: Hand/Auto Switches
Cam
Sw
itch
es,
Mot
orD
isco
nnec
t Sw
itch
es
Cam
Sw
itch
es,
Mot
or D
isco
nnec
t Sw
itch
es
Cam SwitchesFor Control Circuit Functions: Hand/Auto Switches
UL / CSA / IEC / CE UL / CSA / IEC / CE
Moeller Electric CorporationMoeller Electric Corporation
Circuit function diagram Front Plate No. 3)
No. of poles
Cover mounting Center mounting22.5 mm opening
Surface mountingEnclosure 1)
Base mountingwith cover
Base mountingwith cover mounted handleand coupling drive
Basic typefor ..., insert mounting form
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price list
Hand/Auto switcheswith OFF position
1 T0-1-15431/... E-NA104415
EZ-NA104416
I2-NA110071
IVS-NA110079
Z-NA104418
2 T0-2-15432/... E-NA104503
EZ-NA104504
I2-NA110072
IVS-NA110080
Z-NA104506
3 T0-3-15433/... E-NA104597
EZ-NA104598
I2-NA110073
IVS-NA110081
Z-NA104600
with spring-return function for HAND1 T0-1-15434/... E-NA
104419EZ-NA104420
I2-NA110074
IVS-NA110082
Z-NA104422
with spring-return function for START1 T0-2-15907/... E
066931EZ069304
I2-NA110075
IVS076423
Z078796
without OFF position1 T0-1-15451/... E
076824EZ079197
I2-NA110076
IVS083943
Z086316
2 T0-2-15452/... E091062
EZ093435
I2-NA110077
IVS098181
Z010381
3 T0-3-15453/... E015127
EZ017500
I2-NA110078
IVS022246
Z024619
Notes: 1) Surface mounted enclosures are IEC type, totally insulated, corrosion-resistant rated IP 65, NEMA rated 3R, 12.2) All switches have black handle with light gray nameplate. 3) All front plates shown may be exchanged at the time of the order at no extra charge. The prerequisite is that switching angles, the
number of positions and the location of position 0 must be identical; a pages 07/052 and 053 for ordering details. English front plates supplied with the switches as shown in the catalog, can be exchanged for their French equivalent by adding the FS... number shown with suffix -F to the switch type (Example: T0-1-15431/E-NA+FS1420-F).
0AUTO
STARTHAND
2
1 3
4
5
6
7
8
FS 1413890
0AUTO HAND
START
HANDAUTO
2
1 3
4
FS 19334
HAND AUTO
HANDAUTO
2
1 3
4
5
6
7
8
HANDAUTO
2
1 3
4
5
6
7
8
9
10
11
12
Notes:IEC RatingsSuitable for actuating electronic devicesRated uninterrupted current Iu 20 ARated operational current Ie
AC-15220 – 240 V380 – 415 V
6 A4 A
AC-21A 12 ADC-13 32 V per contact 10 A
Further technical data a page 07/072UL/CSA Ratings:Heavy Pilot Duty A 600, P 600
07/040 07/041
1-866-595-96161-630-595-9515 Go to: http://www.klocknermoeller.com
Cam SwitchesFor Control Circuit Functions: Hand/Auto Switches
Cam
Sw
itch
es,
Mot
orD
isco
nnec
t Sw
itch
es
Cam
Sw
itch
es,
Mot
or D
isco
nnec
t Sw
itch
es
Cam SwitchesFor Control Circuit Functions: Hand/Auto Switches
UL / CSA / IEC / CE UL / CSA / IEC / CE
Moeller Electric CorporationMoeller Electric Corporation
Circuit function diagram Front Plate No. 3)
No. of poles
Cover mounting Center mounting22.5 mm opening
Surface mountingEnclosure 1)
Base mountingwith cover
Base mountingwith cover mounted handleand coupling drive
Basic typefor ..., insert mounting form
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price list
Hand/Auto switcheswith OFF position
1 T0-1-15431/... E-NA104415
EZ-NA104416
I2-NA110071
IVS-NA110079
Z-NA104418
2 T0-2-15432/... E-NA104503
EZ-NA104504
I2-NA110072
IVS-NA110080
Z-NA104506
3 T0-3-15433/... E-NA104597
EZ-NA104598
I2-NA110073
IVS-NA110081
Z-NA104600
with spring-return function for HAND1 T0-1-15434/... E-NA
104419EZ-NA104420
I2-NA110074
IVS-NA110082
Z-NA104422
with spring-return function for START1 T0-2-15907/... E
066931EZ069304
I2-NA110075
IVS076423
Z078796
without OFF position1 T0-1-15451/... E
076824EZ079197
I2-NA110076
IVS083943
Z086316
2 T0-2-15452/... E091062
EZ093435
I2-NA110077
IVS098181
Z010381
3 T0-3-15453/... E015127
EZ017500
I2-NA110078
IVS022246
Z024619
Notes: 1) Surface mounted enclosures are IEC type, totally insulated, corrosion-resistant rated IP 65, NEMA rated 3R, 12.2) All switches have black handle with light gray nameplate. 3) All front plates shown may be exchanged at the time of the order at no extra charge. The prerequisite is that switching angles, the
number of positions and the location of position 0 must be identical; a pages 07/052 and 053 for ordering details. English front plates supplied with the switches as shown in the catalog, can be exchanged for their French equivalent by adding the FS... number shown with suffix -F to the switch type (Example: T0-1-15431/E-NA+FS1420-F).
0AUTO
STARTHAND
2
1 3
4
5
6
7
8
FS 1413890
0AUTO HAND
START
HANDAUTO
2
1 3
4
FS 19334
HAND AUTO
HANDAUTO
2
1 3
4
5
6
7
8
HANDAUTO
2
1 3
4
5
6
7
8
9
10
11
12
Notes:IEC RatingsSuitable for actuating electronic devicesRated uninterrupted current Iu 20 ARated operational current Ie
AC-15220 – 240 V380 – 415 V
6 A4 A
AC-21A 12 ADC-13 32 V per contact 10 A
Further technical data a page 07/072UL/CSA Ratings:Heavy Pilot Duty A 600, P 600
07/040 07/041
1-866-595-96161-630-595-9515 Go to: http://www.klocknermoeller.com
Cam SwitchesFor Control Circuit Functions: Spring-return Application Switches
Cam
Sw
itch
es,
Mot
orD
isco
nnec
t Sw
itch
es
Cam
Sw
itch
es,
Mot
orD
isco
nnec
tSw
itch
es
Cam SwitchesFor Control Circuit Functions: Spring-return Application Switches
UL / CSA / IEC / CE UL / CSA / IEC / CE
Moeller Electric Corporation Moeller Electric Corporation
Circuit function diagram Front Plate No. 3)
No. of poles Cover mounting Center mounting22.5 mm opening
Surface mountingEnclosure 1)
Base mountingwith cover
Base mountingwith cover mounted handleand coupling drive
Basic typefor ..., insert mounting form
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price list
ON switches (make contacts)Spring-return from position “1”
1 T0-1-15321/... E086317
EZ088690
I2-NA110083
IVS093436
Z095809
2 T0-1-15322/... E010382
EZ012755
I2-NA110084
IVS017501
Z019874
3 T0-2-15323/... E024620
EZ026993
I2-NA110085
IVS031739
Z034112
ON-OFF switchesSpring-return from position “0” and ”1”
To control: 1 contactor
T0-1-15366/... E081572
EZ083945
I2-NA110086
IVS088691
Z091064
ON-OFF switchesSpring-return from the START position
1 T0-1-15511/... E019875
EZ022248
I2-NA110087
IVS026994
Z029367
2 T0-2-15512/... E034113
EZ036486
I2-NA110088
IVS041232
Z043605
3 T0-3-15513/... E048351
EZ050724
I2-NA110089
IVS055470
Z057843
To control: 1 reversing contactor
T0-2-8177/... E-NA104539
EZ-NA104540
I2-NA110090
IVS-NA110091
Z-NA104542
Notes:1) Surface mounting enclosures are IEC type, totally insulated, corrosion-resistant rated IP 65, NEMA rated 3R, 12.2) All switches have black handle with light gray nameplate.3) All front plates shown may be exchanged at the time of the order at no extra charge. The prerequisite is that switching angles, the
number of positions and the location of position 0 must be identical; a pages 07/052 and 053 for ordering details. English front plates supplied with the switches as shown in the catalog, can be exchanged for their French equivalent by adding the FS... number shown with suffix -F to the switch type (Example: T0-2-8177/E-NA+FS140660-F).
1
2
1
FS 4721
1
1
2
1
4
3
FS 4721
1
1
2
1 3
4
5
6
FS 4721
1
1
0
2
1 3
4
FS 456
0 1
10
START
2
1 3
4
FS 147767
1
0 START
10
START
2
1 3
4
5
6
7
8
FS 147767
1
0 START
10
START
2
1 3
4
5
6
7
8
9
10
11
12
FS 147767
1
0 START
Notes:IEC Ratings:Suitable for actuating electronic devicesRated uninterrupted current Iu 20 ARated operational current Ie
AC-15220 – 240 V380 – 415 V
6 A4 A
AC-21A 12 ADC-13 32 V per contact 10 A
Further technical data a page 07/072UL/CSA Ratings:Heay Pilot duty: A 600, P 600
07/042 07/043
1-866-595-96161-630-595-9515 Go to: http://www.klocknermoeller.com
Cam SwitchesFor Control Circuit Functions: Spring-return Application Switches
Cam
Sw
itch
es,
Mot
orD
isco
nnec
t Sw
itch
es
Cam
Sw
itch
es,
Mot
orD
isco
nnec
tSw
itch
es
Cam SwitchesFor Control Circuit Functions: Spring-return Application Switches
UL / CSA / IEC / CE UL / CSA / IEC / CE
Moeller Electric Corporation Moeller Electric Corporation
Circuit function diagram Front Plate No. 3)
No. of poles Cover mounting Center mounting22.5 mm opening
Surface mountingEnclosure 1)
Base mountingwith cover
Base mountingwith cover mounted handleand coupling drive
Basic typefor ..., insert mounting form
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price list
ON switches (make contacts)Spring-return from position “1”
1 T0-1-15321/... E086317
EZ088690
I2-NA110083
IVS093436
Z095809
2 T0-1-15322/... E010382
EZ012755
I2-NA110084
IVS017501
Z019874
3 T0-2-15323/... E024620
EZ026993
I2-NA110085
IVS031739
Z034112
ON-OFF switchesSpring-return from position “0” and ”1”
To control: 1 contactor
T0-1-15366/... E081572
EZ083945
I2-NA110086
IVS088691
Z091064
ON-OFF switchesSpring-return from the START position
1 T0-1-15511/... E019875
EZ022248
I2-NA110087
IVS026994
Z029367
2 T0-2-15512/... E034113
EZ036486
I2-NA110088
IVS041232
Z043605
3 T0-3-15513/... E048351
EZ050724
I2-NA110089
IVS055470
Z057843
To control: 1 reversing contactor
T0-2-8177/... E-NA104539
EZ-NA104540
I2-NA110090
IVS-NA110091
Z-NA104542
Notes:1) Surface mounting enclosures are IEC type, totally insulated, corrosion-resistant rated IP 65, NEMA rated 3R, 12.2) All switches have black handle with light gray nameplate.3) All front plates shown may be exchanged at the time of the order at no extra charge. The prerequisite is that switching angles, the
number of positions and the location of position 0 must be identical; a pages 07/052 and 053 for ordering details. English front plates supplied with the switches as shown in the catalog, can be exchanged for their French equivalent by adding the FS... number shown with suffix -F to the switch type (Example: T0-2-8177/E-NA+FS140660-F).
1
2
1
FS 4721
1
1
2
1
4
3
FS 4721
1
1
2
1 3
4
5
6
FS 4721
1
1
0
2
1 3
4
FS 456
0 1
10
START
2
1 3
4
FS 147767
1
0 START
10
START
2
1 3
4
5
6
7
8
FS 147767
1
0 START
10
START
2
1 3
4
5
6
7
8
9
10
11
12
FS 147767
1
0 START
Notes:IEC Ratings:Suitable for actuating electronic devicesRated uninterrupted current Iu 20 ARated operational current Ie
AC-15220 – 240 V380 – 415 V
6 A4 A
AC-21A 12 ADC-13 32 V per contact 10 A
Further technical data a page 07/072UL/CSA Ratings:Heay Pilot duty: A 600, P 600
07/042 07/043
1-866-595-96161-630-595-9515 Go to: http://www.klocknermoeller.com
Cam Switches and Motor ControllersControl Switches, Coding Switches, Series Switches
Cam
Sw
itch
es,
Mot
orD
isco
nnec
t Sw
itch
es
Cam
Sw
itch
es,
Mot
orD
isco
nnec
tSw
itch
es
Cam Switches and Motor ControllersControl Switches, Coding Switches, Series Switches
UL / CSA / IEC / CE UL / CSA / IEC / CE
Moeller Electric CorporationMoeller Electric Corporation
Circuit function diagram Front Plate No. 3)
No. of poles
Cover mounting Center mounting22.5 mm opening
Surface mountingEnclosure
Base mountingwith cover
Base mountingwith cover mounted handleand coupling drive
Basic type
for ..., insert mounting form
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price list
Multi-purpose control switchesMaintained, 3-position switches1 contact closed in each position; in addition:1 contact closed in positions 0 and 11 contact closed in positions 0 and 21 contact closed in positions 1 and 2
– T0-3-15391/... E029365
EZ031738
I2-NA110092
IVS036484
Z038857
same as above, but with spring-return for positions 1 and 2– T0-3-15394/... E
072079EZ074452
I2-NA110093
IVS079198
Z081571
Coding switcheswith complete rotation in both directions
Dual BCD-CODE
T0-4-15602/... E029368
EZ031741
I2-NA110094
IVS036487
Z038860
Series switcheswith OFF position (heater switches))
1 T0-1-91/... E072082
EZ074455
I2-NA110095
IVS079201
Z081574
Notes:1) Surface mounting enclosures are IEC type, totally insulated, corrosion-resistant rated IP 65, NEMA rated 3R, 12.2) All switches have black handle with light gray nameplate.3) All front plates shown may be exchanged at the time of the order at no extra charge. The prerequisite is that switching angles, the
number of positions and the location of position 0 must be identical; a pages 07/052 and 053 for ordering details.
201
2
1 3
4
5
6
7
8
9
10 12
11
FS 429
02 1
201
2
1 3
4
5
6
7
8
9
10 12
11
FS 458
012
9876543210
2
1 3
4
5
6
7
8
9 11 13 15
10 12 14 16
42
0
3
9
6
8
1 5
7
FS 312
210
2
1
4
3
FS 614
0
21
Notes:IEC Ratings:Suitable for actuating electronic devicesRated uninterrupted current Iu 20 ARated operational current Ie
AC-15220 – 240 V380 – 415 V
6 A4 A
AC-21A 12 ADC-13 32 V per contact 10 A
Further t echnical data a page 07/072UL/CSA RatingsHeavy Pilot Duty A 600, P 600
07/044 07/045
1-866-595-96161-630-595-9515 Go to: http://www.klocknermoeller.com
Cam Switches and Motor ControllersControl Switches, Coding Switches, Series Switches
Cam
Sw
itch
es,
Mot
orD
isco
nnec
t Sw
itch
es
Cam
Sw
itch
es,
Mot
orD
isco
nnec
tSw
itch
es
Cam Switches and Motor ControllersControl Switches, Coding Switches, Series Switches
UL / CSA / IEC / CE UL / CSA / IEC / CE
Moeller Electric CorporationMoeller Electric Corporation
Circuit function diagram Front Plate No. 3)
No. of poles
Cover mounting Center mounting22.5 mm opening
Surface mountingEnclosure
Base mountingwith cover
Base mountingwith cover mounted handleand coupling drive
Basic type
for ..., insert mounting form
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price list
Multi-purpose control switchesMaintained, 3-position switches1 contact closed in each position; in addition:1 contact closed in positions 0 and 11 contact closed in positions 0 and 21 contact closed in positions 1 and 2
– T0-3-15391/... E029365
EZ031738
I2-NA110092
IVS036484
Z038857
same as above, but with spring-return for positions 1 and 2– T0-3-15394/... E
072079EZ074452
I2-NA110093
IVS079198
Z081571
Coding switcheswith complete rotation in both directions
Dual BCD-CODE
T0-4-15602/... E029368
EZ031741
I2-NA110094
IVS036487
Z038860
Series switcheswith OFF position (heater switches))
1 T0-1-91/... E072082
EZ074455
I2-NA110095
IVS079201
Z081574
Notes:1) Surface mounting enclosures are IEC type, totally insulated, corrosion-resistant rated IP 65, NEMA rated 3R, 12.2) All switches have black handle with light gray nameplate.3) All front plates shown may be exchanged at the time of the order at no extra charge. The prerequisite is that switching angles, the
number of positions and the location of position 0 must be identical; a pages 07/052 and 053 for ordering details.
201
2
1 3
4
5
6
7
8
9
10 12
11
FS 429
02 1
201
2
1 3
4
5
6
7
8
9
10 12
11
FS 458
012
9876543210
2
1 3
4
5
6
7
8
9 11 13 15
10 12 14 16
42
0
3
9
6
8
1 5
7
FS 312
210
2
1
4
3
FS 614
0
21
Notes:IEC Ratings:Suitable for actuating electronic devicesRated uninterrupted current Iu 20 ARated operational current Ie
AC-15220 – 240 V380 – 415 V
6 A4 A
AC-21A 12 ADC-13 32 V per contact 10 A
Further t echnical data a page 07/072UL/CSA RatingsHeavy Pilot Duty A 600, P 600
07/044 07/045
1-866-595-96161-630-595-9515 Go to: http://www.klocknermoeller.com
Moeller Electric CorporationMoeller Electric Corporation
Circuit function diagram Front Plate No. 3)
No. of poles Cover mounting Center mounting22.5 mm opening
Surface mountingEnclosure 1)
Base moutingwith cover
Base mountingwith cover mounted handleand coupling drive
Basic type
for ..., insert mounting form
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price list
Instrumentation selector switchesVoltmeter 3 x Phase-Phase
with OFF positionT0-2-15176/... E-NA
104485EZ-NA104486
I2-NA110096
IVS-NA110103
Z-NA104487
3 x Phase-Phase without OFF position
T0-2-15922/... E053099
EZ055472
I2-NA110097
IVS060218
Z062591
3 x Phase to neutralwith OFF position
T0-2-15177/... E-NA104488
EZ-NA104489
I2-NA110098
IVS-NA110104
Z-NA104490
3 x Phase-Phase + 3 x Phase to neutralwith OFF position
T0-3-8007/... E-NA104608
EZ-NA104609
I2-NA110099
IVS-NA110105
Z-NA104610
3 x Phase-Phase + 3 x Phase to neutral without OFF position, with com-plete rotation in both directions
T0-3-15924/... E019878
EZ022251
I2-NA110100
IVS026997
Z029370
Ammeter
with complete rotation in both directionsMeasurement via current transformers
with OFF position T0-3-8048/... E-NA104611
EZ-NA104612
I2-NA110101
IVS-NA110106
Z-NA104613
Voltmeter and ammeter
with complete rotation in both directionsMeasurement via transformers
with OFF position T0-3-8030/... E013401
EZ013402
I2-NA110102
IVS013404
Z013406
Notes:1) Surface mounting enclosures are IEC type, totally insulated, corrosion-resistant rated IP 65, NEMA rated 3R, 12.2) All switches have black handle with light gray nameplate.3) All front plates shown may be exchanged at the time of the order at no extra charge. The prerequisite is that switching angles, the
number of positions and the location of position 0 must be identical; a pages 07/052 and 053 for ordering details. English front plates supplied with the switches as shown in the catalog, can be exchanged for their French equivalent by adding the FS... number shown with suffix -F to the switch type (Example: T0-2-15176/E-NA+FS194321-F).
L3-L1L2-L3L1-L2
2
1 3
4
5
6
7
8
L1-L2L2-L3
L3-L1
FS 164854
0
L3-NL2-NL1-N
L1-L2L2-L3L3-L1
2
1 3
4
5
6
7
8
9 11
10 12
L3-NL2-NL1-NL3-L1L2-L3L1-L2
2
1 3
4
5
6
7
8
9 11
10 12
0
201
2
1 3
4
5
6
7
8
9
10 12
11
Notes:IEC RatingsSuitable for actuating electronic devicesRated uninterrupted current Iu 20 ARated operational current Ie
AC-15220 – 240 V380 – 415 V
6 A4 A
AC-21A 12 ADC-13 32 V per contact 10 A
Further technical data a page 07/072UL/CSA Ratings:Heavy Pilot duty: A 600, P 600
07/046 07/047
1-866-595-96161-630-595-9515 Go to: http://www.klocknermoeller.com
Moeller Electric CorporationMoeller Electric Corporation
Circuit function diagram Front Plate No. 3)
No. of poles Cover mounting Center mounting22.5 mm opening
Surface mountingEnclosure 1)
Base moutingwith cover
Base mountingwith cover mounted handleand coupling drive
Basic type
for ..., insert mounting form
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price list
Mounting formArticle No.
Pricesee price list
Instrumentation selector switchesVoltmeter 3 x Phase-Phase
with OFF positionT0-2-15176/... E-NA
104485EZ-NA104486
I2-NA110096
IVS-NA110103
Z-NA104487
3 x Phase-Phase without OFF position
T0-2-15922/... E053099
EZ055472
I2-NA110097
IVS060218
Z062591
3 x Phase to neutralwith OFF position
T0-2-15177/... E-NA104488
EZ-NA104489
I2-NA110098
IVS-NA110104
Z-NA104490
3 x Phase-Phase + 3 x Phase to neutralwith OFF position
T0-3-8007/... E-NA104608
EZ-NA104609
I2-NA110099
IVS-NA110105
Z-NA104610
3 x Phase-Phase + 3 x Phase to neutral without OFF position, with com-plete rotation in both directions
T0-3-15924/... E019878
EZ022251
I2-NA110100
IVS026997
Z029370
Ammeter
with complete rotation in both directionsMeasurement via current transformers
with OFF position T0-3-8048/... E-NA104611
EZ-NA104612
I2-NA110101
IVS-NA110106
Z-NA104613
Voltmeter and ammeter
with complete rotation in both directionsMeasurement via transformers
with OFF position T0-3-8030/... E013401
EZ013402
I2-NA110102
IVS013404
Z013406
Notes:1) Surface mounting enclosures are IEC type, totally insulated, corrosion-resistant rated IP 65, NEMA rated 3R, 12.2) All switches have black handle with light gray nameplate.3) All front plates shown may be exchanged at the time of the order at no extra charge. The prerequisite is that switching angles, the
number of positions and the location of position 0 must be identical; a pages 07/052 and 053 for ordering details. English front plates supplied with the switches as shown in the catalog, can be exchanged for their French equivalent by adding the FS... number shown with suffix -F to the switch type (Example: T0-2-15176/E-NA+FS194321-F).
L3-L1L2-L3L1-L2
2
1 3
4
5
6
7
8
L1-L2L2-L3
L3-L1
FS 164854
0
L3-NL2-NL1-N
L1-L2L2-L3L3-L1
2
1 3
4
5
6
7
8
9 11
10 12
L3-NL2-NL1-NL3-L1L2-L3L1-L2
2
1 3
4
5
6
7
8
9 11
10 12
0
201
2
1 3
4
5
6
7
8
9
10 12
11
Notes:IEC RatingsSuitable for actuating electronic devicesRated uninterrupted current Iu 20 ARated operational current Ie
AC-15220 – 240 V380 – 415 V
6 A4 A
AC-21A 12 ADC-13 32 V per contact 10 A
Further technical data a page 07/072UL/CSA Ratings:Heavy Pilot duty: A 600, P 600
07/046 07/047
1-866-595-96161-630-595-9515 Go to: http://www.klocknermoeller.com
Moeller Electric CorporationMoeller Electric Corporation
Circuit function diagram Front Plate No. 4)
No. of poles
Max. HP rating50-60 Hz three-phaseUL/CSA
Current ratingUL/CSA
Cover mounting Surface mountingEnclosure 1)
Base mountingwith cover mounted handle and coupling drive
200 VHP
230 VHP
460 VHP
575 VHP
A Type
Article No.
Pricesee price list
Type
Article No.
Pricesee price list
TypeArticle No.
Pricesee price list
Switches with locking arrangements, Type KMS 1 keyPanic switches without Emergency-Stop function 2)
with type SVA cylinder lockThe key can be withdrawn in OFF and ON positions. If the key is withdrawn inthe ON position, the switch can still be turned to OFF, but cannot be switched backto ON again without the key.
3 3 3 10 10 14 T0-2-1/E/SVA(S)050977
T0-2-1/I2/SVA(S)-NA110107
–
5 5 10 15 20 P1-25/E/SVA(S)050966
P1-25/I2/SVA(S)-NA110108
–
7 ½ 10 20 25 30 P1-32/E/SVA(S)044977
P1-32/I2/SVA(S)-NA110109
–
5 7 ½ 15 15 25 T3-2-1/E/SVA(S)050983
T3-2-1/I2/SVA(S)-NA110110
–
ON-OFF switches without Emergency-Stop function 2)
with type SVA cylinder lockKey can be withdrawn only in OFF position (position A in diagram at right)
3 3 3 10 10 14 T0-2-1/E/SVA(A)050976
T0-2-1/I2/SVA(A)-NA110111
T0-2-1/Z/SVA(A)050978
5 5 10 15 20 P1-25/E/SVA(A)050965
P1-25/I2/SVA(A)-NA110112
P1-25/Z/SVA(A)050969
7 ½ 10 20 25 30 P1-32/E/SVA(A)050970
P1-32/I2/SVA(A)-NA110113
P1-32/Z/SVA(A)050973
5 7 ½ 15 15 25 T3-2-1/E/SVA(A)050982
T3-2-1/I2/SVA(A)-NA110114
T3-2-1/Z/SVA(A)050984
Panic switches with Emergency-Stop function 3)
with type SVA cylinder lockThe key can be withdrawn in OFF and ON positions. If the key is withdrawn inthe ON position, the switch can still be turned to OFF, but cannot be switched backto ON again without the key.
3 3 3 10 10 14 T0-2-1/E/SVA(S)-RT044971
T0-2-1/I2/SVA(S)-RT-NA110115
–
5 5 10 15 20 P1-25/E/SVA(S)-RT050967
P1-25/I2/SVA(S)-RT-NA110116
–
7 ½ 10 20 25 30 P1-32/E/SVA(S)-RT050971
P1-32/I2/SVA(S)-RT-NA110117
–
5 7 ½ 15 15 25 T3-2-1/E/SVA(S)-RT044972
T3-2-1/I2/SVA(S)-RT-NA110118
–
Panic switches with Emergency-Stop function 3)
with type SVC padlocking featureLocking slide can be padlocked in OFF and ON positions. If the locking slide ispadlocked in the ON position with a padlock, the switch can still be turned OFF, butcannot be switched back to ON without a removal of the padlock.
3 3 3 10 10 14 T0-2-1/E/SVC(S)-RT044973
T0-2-1/I2/SVC(S)-RT-NA110119
–
5 5 10 15 20 P1-25/E/SVC(S)-RT044974
P1-25/I2/SVC(S)-RT-NA110120
–
7 ½ 10 20 25 30 P1-32/E/SVC(S)-RT044975
P1-32/I2/SVC(S)-RT-NA110121
–
5 7 ½ 15 15 25 T3-2-1/E/SVC(S)-RT044976
T3-2-1/I2/SVC(S)-RT-NA110122
–
ON-OFF switches without Emergency-Stop functionwith S-T0 key operation, light gray nameplateKey can be withdrawn only in OFF position (position A)
Single phase115 VHP
200/230VHP
2 ¾ 2 – 14 T0-1-102/EZ/S014933
5) T0-1-102/I2/S-NA110123
T0-1-102/Z/S014971
1 3 5
2 4 6
FS 908
ON
OFF
1 3 5
2 4 6
FS 908
ON
OFF
1 3 5
2 4 6
FS 908 GE
1
0
1 3 5
2 4 6
FS 908 GE
1
0
1
2
3
4
FS 908
ON
OFF
Notes:
1) Surface mounting enclosures are IEC type, totally in-sulated, corrosion-resitant rated IP 65.NEMA rated 3R, 12.
2) With black handle and light gray nameplate.
3) With red handle and yellow nameplate, per IEC/EN 60 204-1 Machinery Directive.
Code letters corresponding to lockable switch positionsLetter S for panic lock with FS908GE
4) All front plates shown may be exchanged at the timeof the order at no extra charge. The prerequisite is that switching angles, the number of positions and the location of position 0 must be identical; a pages 07/052 and 053 for ordering details. English front plates supplied with the switches as shown in the catalog, can be exchanged for their French equivalent by adding the FS... number shown with suffix -F to the switch type (Example: T0-2-1/E/SVA(S)+FS908-F)
5) Degree of protection IP 53
330 0 30
300
240225
210180
150
135120
90
6045
270
F
HG
J
KL
MN
PQ
R
A
BC
DE
315
07/048 07/049
1-866-595-96161-630-595-9515 Go to: http://www.klocknermoeller.com
Moeller Electric CorporationMoeller Electric Corporation
Circuit function diagram Front Plate No. 4)
No. of poles
Max. HP rating50-60 Hz three-phaseUL/CSA
Current ratingUL/CSA
Cover mounting Surface mountingEnclosure 1)
Base mountingwith cover mounted handle and coupling drive
200 VHP
230 VHP
460 VHP
575 VHP
A Type
Article No.
Pricesee price list
Type
Article No.
Pricesee price list
TypeArticle No.
Pricesee price list
Switches with locking arrangements, Type KMS 1 keyPanic switches without Emergency-Stop function 2)
with type SVA cylinder lockThe key can be withdrawn in OFF and ON positions. If the key is withdrawn inthe ON position, the switch can still be turned to OFF, but cannot be switched backto ON again without the key.
3 3 3 10 10 14 T0-2-1/E/SVA(S)050977
T0-2-1/I2/SVA(S)-NA110107
–
5 5 10 15 20 P1-25/E/SVA(S)050966
P1-25/I2/SVA(S)-NA110108
–
7 ½ 10 20 25 30 P1-32/E/SVA(S)044977
P1-32/I2/SVA(S)-NA110109
–
5 7 ½ 15 15 25 T3-2-1/E/SVA(S)050983
T3-2-1/I2/SVA(S)-NA110110
–
ON-OFF switches without Emergency-Stop function 2)
with type SVA cylinder lockKey can be withdrawn only in OFF position (position A in diagram at right)
3 3 3 10 10 14 T0-2-1/E/SVA(A)050976
T0-2-1/I2/SVA(A)-NA110111
T0-2-1/Z/SVA(A)050978
5 5 10 15 20 P1-25/E/SVA(A)050965
P1-25/I2/SVA(A)-NA110112
P1-25/Z/SVA(A)050969
7 ½ 10 20 25 30 P1-32/E/SVA(A)050970
P1-32/I2/SVA(A)-NA110113
P1-32/Z/SVA(A)050973
5 7 ½ 15 15 25 T3-2-1/E/SVA(A)050982
T3-2-1/I2/SVA(A)-NA110114
T3-2-1/Z/SVA(A)050984
Panic switches with Emergency-Stop function 3)
with type SVA cylinder lockThe key can be withdrawn in OFF and ON positions. If the key is withdrawn inthe ON position, the switch can still be turned to OFF, but cannot be switched backto ON again without the key.
3 3 3 10 10 14 T0-2-1/E/SVA(S)-RT044971
T0-2-1/I2/SVA(S)-RT-NA110115
–
5 5 10 15 20 P1-25/E/SVA(S)-RT050967
P1-25/I2/SVA(S)-RT-NA110116
–
7 ½ 10 20 25 30 P1-32/E/SVA(S)-RT050971
P1-32/I2/SVA(S)-RT-NA110117
–
5 7 ½ 15 15 25 T3-2-1/E/SVA(S)-RT044972
T3-2-1/I2/SVA(S)-RT-NA110118
–
Panic switches with Emergency-Stop function 3)
with type SVC padlocking featureLocking slide can be padlocked in OFF and ON positions. If the locking slide ispadlocked in the ON position with a padlock, the switch can still be turned OFF, butcannot be switched back to ON without a removal of the padlock.
3 3 3 10 10 14 T0-2-1/E/SVC(S)-RT044973
T0-2-1/I2/SVC(S)-RT-NA110119
–
5 5 10 15 20 P1-25/E/SVC(S)-RT044974
P1-25/I2/SVC(S)-RT-NA110120
–
7 ½ 10 20 25 30 P1-32/E/SVC(S)-RT044975
P1-32/I2/SVC(S)-RT-NA110121
–
5 7 ½ 15 15 25 T3-2-1/E/SVC(S)-RT044976
T3-2-1/I2/SVC(S)-RT-NA110122
–
ON-OFF switches without Emergency-Stop functionwith S-T0 key operation, light gray nameplateKey can be withdrawn only in OFF position (position A)
Single phase115 VHP
200/230VHP
2 ¾ 2 – 14 T0-1-102/EZ/S014933
5) T0-1-102/I2/S-NA110123
T0-1-102/Z/S014971
1 3 5
2 4 6
FS 908
ON
OFF
1 3 5
2 4 6
FS 908
ON
OFF
1 3 5
2 4 6
FS 908 GE
1
0
1 3 5
2 4 6
FS 908 GE
1
0
1
2
3
4
FS 908
ON
OFF
Notes:
1) Surface mounting enclosures are IEC type, totally in-sulated, corrosion-resitant rated IP 65.NEMA rated 3R, 12.
2) With black handle and light gray nameplate.
3) With red handle and yellow nameplate, per IEC/EN 60 204-1 Machinery Directive.
Code letters corresponding to lockable switch positionsLetter S for panic lock with FS908GE
4) All front plates shown may be exchanged at the timeof the order at no extra charge. The prerequisite is that switching angles, the number of positions and the location of position 0 must be identical; a pages 07/052 and 053 for ordering details. English front plates supplied with the switches as shown in the catalog, can be exchanged for their French equivalent by adding the FS... number shown with suffix -F to the switch type (Example: T0-2-1/E/SVA(S)+FS908-F)
5) Degree of protection IP 53
330 0 30
300
240225
210180
150
135120
90
6045
270
F
HG
J
KL
MN
PQ
R
A
BC
DE
315
07/048 07/049
1-866-595-96161-630-595-9515 Go to: http://www.klocknermoeller.com
Moeller Electric CorporationMoeller Electric Corporation
Circuit function diagram Front Plate No. 1)
Current rating
UL/CSA
Cover mounting Surface mountingEnclosure 1)
Base mountingwith cover mounted handleand coupling drive
TypeArticle No.
Pricesee price list
TypeArticle No.
Pricesee price list
TypeArticle No.
Pricesee price list
A
Switches with locking arrangements, type KMS 1 keyHAND/AUTO switch with type SVA cylinder lock
The key can be withdrawn in all positions. If the key is withdrawn in HANDposition, then START can be actuated without the key, but not position 0 (onlypermissible with separate OFF switch)
14 T0-2-15907/E/SVA(C,E,G-J)050979
T0-2-15907/I2/SVA(C,E,G-J)-NA110124
–
25 T3-2-15907/E/SVA(C,E,G-J)050985
T3-2-15907/I2/SVA(C,E,G-J)-NA110125
–
HAND/AUTO switch with SVC padlocking feature
Locking slide can be padlocked in all positions.If the locking slide is padlocked in the HAND position, the START can be actuated without removal of the padlock,but not the O position (only permissible with separate OFF switch)
14 T0-2-15907/E/SVC(C,E,G-J)044996
T0-2-15907/I2/SVC(C,E,G-J)-NA110126
T0-2-15907/Z/SVC(C,E,G-J)050980
25 T3-2-15907/E/SVC(C,E,G-J)044997
T3-2-15907/I2/SVC(C,E,G-J)-NA110127
T3-2-15907/Z/SVC(C,E,G-J)050986
Contactor interlocking control circuitsControl section for standard contactor interlocking circuits:The electrical interlocking of a rotary cam switch and con-tactor provides a clean and economical solution to a wide range of control function tasks. For example; remote discon-nection via a stop switch, overload protection via overload relays, protection against automatic restarting after a power failure or overload, OFF position interlocking, etc.
The examples shown at right (each standardized contactor interlocking circuit is issued a “SOND...” identification num-ber) are but a few of the possible application schemes which can be realized by the combination of these components. Note: if the contact sequence of a standard switch is intend-ed to contain a contactor interlocking circuit scheme as well, it can be ordered from the cam switch catalog K 115 (consult Moeller Electric) or as a non-standard switch.
SOND 27 SOND 28 SOND 29 SOND 30
Supply disconnection only by contactor. Restarting possible only after reset with cam switch in the Off position. Used mainly for star-delta switches (only at 60°or 90° switching angles.)
Supply disconnection by combining both contactor and cam switch.Restarting: same as SOND 27.Used mainly for star-delta, transfer and multi-speed switch applications (only at 60° or 90° switching angles).
Power applied by contactor only when cam switch is in the Off position (OFF position interlock).Use primarily for star-delta, transfer and multi-speed switch applications.
Power applied by contactor only when cam switch is switched to the run positions.Each change in switch position causes contactor to drop out.Used for transfer and multi-speed switch applications.
0AUTO
STARTHAND
2
1 3
4
5
6
7
8
FS 1413890
0AUTO HAND
START
0AUTO
STARTHAND
2
1 3
4
5
6
7
8
FS 1413890
0AUTO HAND
START
Notes:
Suitable for actuating electronic devicesRated uninterrupted current Iu 20 ARated operational current Ie
AC-15220 – 240 V380 – 415 V
6 A4 A
AC-21A 12 ADC-13 32 V per contact 10 A
Further technical data a page 07/072
Rotary switches with a SVA locking arrangement can also be used as operating mode selector switches for the purposes of EU Machinery Di-rective 89/392 (minimum switching angle 60°)
Code letters for lockable switch positions
1) All front plates shown may be exchanged at the time of the order at no extra charge. The prerequisite is that switching angles, the num-ber of positions and the location of position 0 must be identical; a pages 07/052 and 053 for ordering details. English front plates supplied with the switches as shown in the catalog, can be exchanged for their French equivalent by adding the FS... number shown with suffix -F to the switch type Example: T0-2-15907/E/SVA(C,E,G-J)+FS1413890-F.
330 0 30
300
240225
210180
150
135120
90
6045
270
F
HG
J
KL
MN
PQ
R
A
BC
DE
315
07/050 07/051
1-866-595-96161-630-595-9515 Go to: http://www.klocknermoeller.com
Moeller Electric CorporationMoeller Electric Corporation
Circuit function diagram Front Plate No. 1)
Current rating
UL/CSA
Cover mounting Surface mountingEnclosure 1)
Base mountingwith cover mounted handleand coupling drive
TypeArticle No.
Pricesee price list
TypeArticle No.
Pricesee price list
TypeArticle No.
Pricesee price list
A
Switches with locking arrangements, type KMS 1 keyHAND/AUTO switch with type SVA cylinder lock
The key can be withdrawn in all positions. If the key is withdrawn in HANDposition, then START can be actuated without the key, but not position 0 (onlypermissible with separate OFF switch)
14 T0-2-15907/E/SVA(C,E,G-J)050979
T0-2-15907/I2/SVA(C,E,G-J)-NA110124
–
25 T3-2-15907/E/SVA(C,E,G-J)050985
T3-2-15907/I2/SVA(C,E,G-J)-NA110125
–
HAND/AUTO switch with SVC padlocking feature
Locking slide can be padlocked in all positions.If the locking slide is padlocked in the HAND position, the START can be actuated without removal of the padlock,but not the O position (only permissible with separate OFF switch)
14 T0-2-15907/E/SVC(C,E,G-J)044996
T0-2-15907/I2/SVC(C,E,G-J)-NA110126
T0-2-15907/Z/SVC(C,E,G-J)050980
25 T3-2-15907/E/SVC(C,E,G-J)044997
T3-2-15907/I2/SVC(C,E,G-J)-NA110127
T3-2-15907/Z/SVC(C,E,G-J)050986
Contactor interlocking control circuitsControl section for standard contactor interlocking circuits:The electrical interlocking of a rotary cam switch and con-tactor provides a clean and economical solution to a wide range of control function tasks. For example; remote discon-nection via a stop switch, overload protection via overload relays, protection against automatic restarting after a power failure or overload, OFF position interlocking, etc.
The examples shown at right (each standardized contactor interlocking circuit is issued a “SOND...” identification num-ber) are but a few of the possible application schemes which can be realized by the combination of these components. Note: if the contact sequence of a standard switch is intend-ed to contain a contactor interlocking circuit scheme as well, it can be ordered from the cam switch catalog K 115 (consult Moeller Electric) or as a non-standard switch.
SOND 27 SOND 28 SOND 29 SOND 30
Supply disconnection only by contactor. Restarting possible only after reset with cam switch in the Off position. Used mainly for star-delta switches (only at 60°or 90° switching angles.)
Supply disconnection by combining both contactor and cam switch.Restarting: same as SOND 27.Used mainly for star-delta, transfer and multi-speed switch applications (only at 60° or 90° switching angles).
Power applied by contactor only when cam switch is in the Off position (OFF position interlock).Use primarily for star-delta, transfer and multi-speed switch applications.
Power applied by contactor only when cam switch is switched to the run positions.Each change in switch position causes contactor to drop out.Used for transfer and multi-speed switch applications.
0AUTO
STARTHAND
2
1 3
4
5
6
7
8
FS 1413890
0AUTO HAND
START
0AUTO
STARTHAND
2
1 3
4
5
6
7
8
FS 1413890
0AUTO HAND
START
Notes:
Suitable for actuating electronic devicesRated uninterrupted current Iu 20 ARated operational current Ie
AC-15220 – 240 V380 – 415 V
6 A4 A
AC-21A 12 ADC-13 32 V per contact 10 A
Further technical data a page 07/072
Rotary switches with a SVA locking arrangement can also be used as operating mode selector switches for the purposes of EU Machinery Di-rective 89/392 (minimum switching angle 60°)
Code letters for lockable switch positions
1) All front plates shown may be exchanged at the time of the order at no extra charge. The prerequisite is that switching angles, the num-ber of positions and the location of position 0 must be identical; a pages 07/052 and 053 for ordering details. English front plates supplied with the switches as shown in the catalog, can be exchanged for their French equivalent by adding the FS... number shown with suffix -F to the switch type Example: T0-2-15907/E/SVA(C,E,G-J)+FS1413890-F.
330 0 30
300
240225
210180
150
135120
90
6045
270
F
HG
J
KL
MN
PQ
R
A
BC
DE
315
07/050 07/051
1-866-595-96161-630-595-9515 Go to: http://www.klocknermoeller.com
Cam Switches T, Motor Disconnect Switches PStandard and Special Front Plates
Cam
Sw
itch
es,
Mot
or D
isco
nnec
t Sw
itch
esMoeller Electric Corporation
Standard front plate Emergency-Stop front plateSwitch type Dimensions yellow
TypeArticle No.
Pricesee price list
TypeArticle No.
Pricesee price list
mmInsert front plate number
Standard front platesT0, T3, P1 45 x 45
(frame size 48 x 48)FS...-T0231893
FS908 GE-T0003198
P3, T5B 84 x 84(frame size 88 x 88)
FS...-P3231895
FS908 GE-P3031475
Standard front platesBlack lettering on light gray backgroundThe standard front plates shown here should be used for non-standard switches wherever possible. The front plates shown throughout the catalog, that are supplied with standard switches can be exchanged for any of the ones shown here at the time of the order, at no extra charge. The prerequisite is that switching angles, the number of positions and the location of position 0 must be identical. To order a different front plate, just add the FS... number shown below to the switch.Example: T0-1-8210/E+FS161570
Switching angle 90°
Switching angle 60°
Switching angle 45°
Switching angle 30 °
1
0
07/052
1-866-595-96161-630-595-9515 Go to: http://www.klocknermoeller.com
Cam Switches T, Motor Disconnect Switches PFront Plates
Moeller Electric Corporation
Blank plates Non-standard front plates Non-standard front platescan be engraved
TypeArticle No.
Pricesee price list
TypeArticle No.
Pricesee price list
Height of letters
≤ 2 characters
mm
> 2 characters
mm
FS980-T0003199
FS-SOND-ERSTBESTELLUNG-T01)
2253554 3
FS980-P3043340
FS-SOND-ERSTBESTELLUNG-P32)
2253568 5
Non-standard front plates 1) = first order; for subsequent orders, use FS...-T02) = first order; for subsequent orders, use FS...-P3
Inscription to order (note max. number of characters per section)The FS number will be sufficient for reordering purposes.Non-standard T0, T3, T5B switches: non-standard front plate included in price.
Switching angle90°/45°Max. number of characters
FS-SOND-T0 (T3, T5B, P1, P3)
60°/30°
FS-SOND-T0 (T3, T5B)
Standard front plates, arranged according to front plate numbers
13646
13
64
6M
1385457
13
85457
07/053
1-866-595-96161-630-595-9515 Go to: http://www.klocknermoeller.com
T Cam Switches, P Motor Disconnect SwitchesAccessories
Cam
Sw
itch
es,
Mot
orD
isco
nnec
t Sw
itch
es
Cam
Swit
ches
,M
otor
Dis
conn
ect
Swit
ches
T Cam Switches, P Motor Disconnect SwitchesAccessories
Moeller Electric Corporation Moeller Electric Corporation
For use with Type suffix Price Type Price Type suffix Price Type PriceArticle No. see price
listArticle No. see price
listArticle No. see price
listArticle No. see price
list
when ordered with basic device
when ordered separately when ordered with basicdevice
when ordered separately
Add-on front plates, clip on
For use with front plates and for padlocking features,Consisting of one label mount, black, and one insert label, grey coloredBlank, can be engraved T.../I2/SVB(-SW) and
P.../I2/SVB(-SW) except .../I2.../IVS
T..., P..., except .../I2, 3 .../IVS
– ZFS60-T0019924
– ZFS60-P3022297
ZFS...-T0 and ZFS...-P3 can be used for any T... and P...as requiredDimensions with frame W x H = 48 x 17 mmDimensions with frame W x H = 88 x 27 mm
With inscription 1)
Main Switch - open only in the OFF position
T.../E, T.../Z, P.../E, P.../Z included as standard withT.../EA/SVB, P.../EA/SVBT.../V/SVB, P.../V/SVB
62 = English +ZFS62-T0205500
ZFS62-T0205534
+ZFS62-P3205517
ZFS62-P3205551
63 = French +ZFS63-T0065741
ZFS63-T0047424
+ZFS63-P3065743
ZFS63-P3047423
68 = Italian +ZFS68-T0065745
ZFS68-T0065751
+ZFS68-P3065748
ZFS68-P3065754
77 = Spanish +ZFS77-T0065746
ZFS77-T0065752
+ZFS77-P3065749
ZFS77-P3047422
Label mounts, blackT.../I2/SVB(-SW) and P.../I2/SVB(-SW) except .../I2, .../IVS
T..., P..., except .../I2, 3.../IVS
– ZFSX-T0024670
– ZFSX-P3027043
ZFSX...-T0 and ZFSX...-P3 can be used for any T... and P... switches, as required.Dimensions with frame W x H = 48x 17 mmDimensions with frame W x H = 88 x 27 mm
Notes: 1) Inscriptions in other languages available upon request, consult Moeller Electric
07/054 07/055
1-866-595-96161-630-595-9515 Go to: http://www.klocknermoeller.com
T Cam Switches, P Motor Disconnect SwitchesAccessories
Cam
Sw
itch
es,
Mot
orD
isco
nnec
t Sw
itch
es
Cam
Swit
ches
,M
otor
Dis
conn
ect
Swit
ches
T Cam Switches, P Motor Disconnect SwitchesAccessories
Moeller Electric Corporation Moeller Electric Corporation
For use with Type suffix Price Type Price Type suffix Price Type PriceArticle No. see price
listArticle No. see price
listArticle No. see price
listArticle No. see price
list
when ordered with basic device
when ordered separately when ordered with basicdevice
when ordered separately
Add-on front plates, clip on
For use with front plates and for padlocking features,Consisting of one label mount, black, and one insert label, grey coloredBlank, can be engraved T.../I2/SVB(-SW) and
P.../I2/SVB(-SW) except .../I2.../IVS
T..., P..., except .../I2, 3 .../IVS
– ZFS60-T0019924
– ZFS60-P3022297
ZFS...-T0 and ZFS...-P3 can be used for any T... and P...as requiredDimensions with frame W x H = 48 x 17 mmDimensions with frame W x H = 88 x 27 mm
With inscription 1)
Main Switch - open only in the OFF position
T.../E, T.../Z, P.../E, P.../Z included as standard withT.../EA/SVB, P.../EA/SVBT.../V/SVB, P.../V/SVB
62 = English +ZFS62-T0205500
ZFS62-T0205534
+ZFS62-P3205517
ZFS62-P3205551
63 = French +ZFS63-T0065741
ZFS63-T0047424
+ZFS63-P3065743
ZFS63-P3047423
68 = Italian +ZFS68-T0065745
ZFS68-T0065751
+ZFS68-P3065748
ZFS68-P3065754
77 = Spanish +ZFS77-T0065746
ZFS77-T0065752
+ZFS77-P3065749
ZFS77-P3047422
Label mounts, blackT.../I2/SVB(-SW) and P.../I2/SVB(-SW) except .../I2, .../IVS
T..., P..., except .../I2, 3.../IVS
– ZFSX-T0024670
– ZFSX-P3027043
ZFSX...-T0 and ZFSX...-P3 can be used for any T... and P... switches, as required.Dimensions with frame W x H = 48x 17 mmDimensions with frame W x H = 88 x 27 mm
Notes: 1) Inscriptions in other languages available upon request, consult Moeller Electric
07/054 07/055
1-866-595-96161-630-595-9515 Go to: http://www.klocknermoeller.com
Removable key positions pre-programmed from factory
+SVA-T3050962
Removable key positions programmed on site
SVA-T3050974
Lock mechanism type KMS 2–10 1)
Lock mechanism type KMS 201–400 1)
(individual locks, not suitable for master key systems)
+SVA-SOND-KMS...-T3231966
SVA-SOND-KMS...-T3231967
Key is removable in customer specified positionsLock mechanism Type KMS 1Switches with FS 908 are suitable as main switches:T0-1-...to T0-4-.../I1, .../E T3-1-...to T3-5-.../I2T3-1-...to T3-6- .../EP1-.../I2, .../E
Removable key positions pre-programmed by factory per or-der specifica-tions
+SVA(...)-T3907737
Removable key positions pre-pro-grammed by factory per or-der specifica-tions
SVA(...)-T3907745
Lock mechanism type KMS 2–10 1)
Lock mechanism type KMS 201–400 1)
(individual locks, not suitable for master key systems)
+SVA(...)-SOND-KMS...-T3231968
SVA(...)-SOND-KMS...-T3231969
(SAE) = custom individual lock mechanism supplied with a security certificate (without master key)
+SVA(...)-SOND-SAE-T3907736
SVA(...)-SOND-SAE-T3907744
(SA...) = customized master key system supplied with a security certificate. 2)
+SVA(...)-SOND-(SA...)-T3231970
SVA(...)-SOND-(SA...)-T3231971
Notes: 1) Availability for KMS 1 locks is immediate. Please allow 4 - 6 weeks for KMS 2-10, 201-400 lock mechanisms and SA(E)-... master key assemblies.
2) SA(E)-... master key systems are customized assemblies to fit individual plant setups. When ordering, fill out your desired master key layout plan using form FO 276, (available from any Moeller Electric office) and submit with your order. The master key system is supplied with a security certificate and a proprietary identification number. Reordering of keys and locks for that system can be made by referencing the ID number and the item’s location in the master key system plan. Example: master key system # Z4711, position 7)
Notes
S-T0 can be used for P1-... motor disconnect switches, T0 cam switches with up to 6 contact chambers, and T3-... switches with up to 5 chambers.
The key replaces the thumb-grip handle and switching without the key is not possible. The switch position indicator is on the locking mechanism. In standard applications, the key is re-movable in each switch position. Switches using FS 908 as a name plate (90°, ON-OFF) are supplied standard with the key removable in the OFF position only. However, the user can se-lect new positions in which the key can be withdrawn by means of locking cam accessory VR-T0.
The switching angle is determined by the switch and cannot be modified in the field.
Lock mechanism: standard KMS 1 (CES lock)Additional lock mechanisms and master key systems are also available upon request.
SVA-T3 will fit on all T0, T3 and P1 switches. Switching is carried out using the thumb-grip handle. Turning the key will lock in the position and the key can be removed. Supplied as stan-dard, all positions can be locked. In case of subsequent installation use the front plate supplied with switch for position locations. Standard lock mechanism: type KMS 1 (CES lock)If required, additional lock mechanisms can be used, and if planned in advance, master key systems as well. If desired, individual positions or an entire portion of a switching range can be pre-programmed for locking (this can be done in the field using the VR-T3 locking cam ac-cessory).The key cannot be withdrawn from positions which are not lockable. In locked ranges, switch-ing without a key is only possible within that range. Lockable positions or ranges are deter-mined as follows:Example 1: SVA(A)-T3 only position A is lockedExample 2: SVA(A,E)-T3positions A and E are lockedExample 3: SVA(A-J)-T3positions A through J are locked (range)Example 4: SVA(S)-T3main disconnect switch, fulfilling also the Emergency-Stopfunction per IEC/EN 602-4-1, with red handle and yellowfront plate. Suitable as “panic switch” with lockablepositions A(OFF) and E(ON); switching remains possiblefrom ON to OFF (E to A) without a key, but not from OFF to ON (A to E).
If the accessories are field installed, use the front plate supplied with the switch for position indication.
Letter S designates panic lock switch with Emergency-Stop FS908GE front plate (yellow)
330 0 30
300
240225
210180
150
135120
90
6045
270
F
HG
J
KL
MN
PQ
R
A
BC
DE
315
07/056 07/057
1-866-595-96161-630-595-9515 Go to: http://www.klocknermoeller.com
Removable key positions pre-programmed from factory
+SVA-T3050962
Removable key positions programmed on site
SVA-T3050974
Lock mechanism type KMS 2–10 1)
Lock mechanism type KMS 201–400 1)
(individual locks, not suitable for master key systems)
+SVA-SOND-KMS...-T3231966
SVA-SOND-KMS...-T3231967
Key is removable in customer specified positionsLock mechanism Type KMS 1Switches with FS 908 are suitable as main switches:T0-1-...to T0-4-.../I1, .../E T3-1-...to T3-5-.../I2T3-1-...to T3-6- .../EP1-.../I2, .../E
Removable key positions pre-programmed by factory per or-der specifica-tions
+SVA(...)-T3907737
Removable key positions pre-pro-grammed by factory per or-der specifica-tions
SVA(...)-T3907745
Lock mechanism type KMS 2–10 1)
Lock mechanism type KMS 201–400 1)
(individual locks, not suitable for master key systems)
+SVA(...)-SOND-KMS...-T3231968
SVA(...)-SOND-KMS...-T3231969
(SAE) = custom individual lock mechanism supplied with a security certificate (without master key)
+SVA(...)-SOND-SAE-T3907736
SVA(...)-SOND-SAE-T3907744
(SA...) = customized master key system supplied with a security certificate. 2)
+SVA(...)-SOND-(SA...)-T3231970
SVA(...)-SOND-(SA...)-T3231971
Notes: 1) Availability for KMS 1 locks is immediate. Please allow 4 - 6 weeks for KMS 2-10, 201-400 lock mechanisms and SA(E)-... master key assemblies.
2) SA(E)-... master key systems are customized assemblies to fit individual plant setups. When ordering, fill out your desired master key layout plan using form FO 276, (available from any Moeller Electric office) and submit with your order. The master key system is supplied with a security certificate and a proprietary identification number. Reordering of keys and locks for that system can be made by referencing the ID number and the item’s location in the master key system plan. Example: master key system # Z4711, position 7)
Notes
S-T0 can be used for P1-... motor disconnect switches, T0 cam switches with up to 6 contact chambers, and T3-... switches with up to 5 chambers.
The key replaces the thumb-grip handle and switching without the key is not possible. The switch position indicator is on the locking mechanism. In standard applications, the key is re-movable in each switch position. Switches using FS 908 as a name plate (90°, ON-OFF) are supplied standard with the key removable in the OFF position only. However, the user can se-lect new positions in which the key can be withdrawn by means of locking cam accessory VR-T0.
The switching angle is determined by the switch and cannot be modified in the field.
Lock mechanism: standard KMS 1 (CES lock)Additional lock mechanisms and master key systems are also available upon request.
SVA-T3 will fit on all T0, T3 and P1 switches. Switching is carried out using the thumb-grip handle. Turning the key will lock in the position and the key can be removed. Supplied as stan-dard, all positions can be locked. In case of subsequent installation use the front plate supplied with switch for position locations. Standard lock mechanism: type KMS 1 (CES lock)If required, additional lock mechanisms can be used, and if planned in advance, master key systems as well. If desired, individual positions or an entire portion of a switching range can be pre-programmed for locking (this can be done in the field using the VR-T3 locking cam ac-cessory).The key cannot be withdrawn from positions which are not lockable. In locked ranges, switch-ing without a key is only possible within that range. Lockable positions or ranges are deter-mined as follows:Example 1: SVA(A)-T3 only position A is lockedExample 2: SVA(A,E)-T3positions A and E are lockedExample 3: SVA(A-J)-T3positions A through J are locked (range)Example 4: SVA(S)-T3main disconnect switch, fulfilling also the Emergency-Stopfunction per IEC/EN 602-4-1, with red handle and yellowfront plate. Suitable as “panic switch” with lockablepositions A(OFF) and E(ON); switching remains possiblefrom ON to OFF (E to A) without a key, but not from OFF to ON (A to E).
If the accessories are field installed, use the front plate supplied with the switch for position indication.
Letter S designates panic lock switch with Emergency-Stop FS908GE front plate (yellow)
330 0 30
300
240225
210180
150
135120
90
6045
270
F
HG
J
KL
MN
PQ
R
A
BC
DE
315
07/056 07/057
1-866-595-96161-630-595-9515 Go to: http://www.klocknermoeller.com
T Cam Switches, P Motor Disconnect SwitchesAccessories
Cam
Sw
itch
es,
Mot
orD
isco
nnec
t Sw
itch
es
Cam
Swit
ches
,M
otor
Dis
conn
ect
Swit
ches
T Cam Switches, P Motor Disconnect SwitchesAccessories
Moeller Electric Corporation Moeller Electric Corporation
For use with Interlocking provisions
Type Suffix Price Interlocking provisions
Type PriceArticle No. Article No.
when ordered with basic device
see price list
when ordered separately see price list
SVC-T3 Padlocking feature, Front IP 65
The locking slide can be padlocked in the pushed-in position withup to 3 padlocks
All switch positions can be locked T0-.../E, .../I2, .../Z T3-.../E, .../I2, .../Z P1-.../E, .../I2, .../Z
interlocked posi-tions pre-pro-grammed from factory
+SVC-T3050963
interlocked posi-tions programmed on site
SVC-T3050975
Specified positions or ranges need to be locked T0-1-... up to T0-4-.../I2, .../ET3-1-... up to T3-5-.../I2 T3-1-... up to T3-6-.../E P1-.../I2, .../E
interlocked posi-tions programmed by factory per order specifications
+SVC(...)-T3907740
interlocked posi-tions programmed by factory per order specifications
SVC(...)-T3907748
DTV-T3 Push-release interlock, Front IP 65
This accessory allows a position to be switched only after the push-release locking slide has been pushed in. Should the push-release locking slide be padlocked in its released state, the device cannot be operated..
T0-.../E, .../I2, .../Z T3-.../E, .../I2, .../Z P1-.../E, .../I2, .../Z padlockable with up to 2 pad-locks
interlocked posi-tions pre-pro-grammed from factory
+DTV-T3050961
–
Specified positions need to be locked.Push-release locking slide can be padlocked in its released state with up to 2 padlocks.
interlocked posi-tions programmed by factory per order specifications
+DTV(...)-T3907733
–
Locking cams (2 cams per set)Select this accessory to change the position in which key can be removed
S-T0 for all switching angles – VR-T0089082
Select this accessory to change the position or ranges in which the switch can be locked.
SVA-T3, SVC-T3, for all switching anglesFor DTV-T3: order 2 x VR-T3
– VR-T3050987
Spare keys
For individual lock mechanisms Type KMS 1 S-T0, SVA-T3 – ES-KMS1-T0231972
For master key systems and registered lock mechanisms; specify as-signed plan number and the lock number position.
S-T0, SVA-T3 – ES-KMS-SA(*)-T0231974
Notes:
SVC-T3 will fit on all T0, T3 and P! switches. Switching is carried out using the thumb-grip handle. Pushing in the locking slide will interlock the position, which can then be padlocked off with up to 3 padlocks. Supplied as standard, all positions can be interlocked. With the SVC(...)-T3 accessory only those positions or ranges specified will be interlockable. In inter-locked ranges, switching without removal of the padlocks is only possible within that range.
In similar fashion to the SVA(...)-T3 accessory shown on the previous pages, the interlock-able positions or ranges for the SVC(...)-T3 and the locked positions and ranges for the DTV(...)-T3 are to be specified as follows:Example 1: SVC(A)-T3 only position A is lockedExample 2: SVC(A,E)-T3positions A and E are lockedExample 3: SVC(A-J)-T3positions A through J are locked (range)Example 4: DTV(G)-T3push-release mechanism needs to be actuated (pushed in) to allow switching of position G.Example 5: SVC(S)-T3main disconnect switch, fulfilling also the Emergency-Stopfunction per IEC/EN 602-4-1, with red handle and yellowfront plate. Suitable as “panic switch” with lockablepositions A(OFF) and E(ON); switching remains possiblefrom ON to OFF (E to A) without a key, but not from OFF to ON (A to E).
If the accessories are field installed, use the front plate supplied with the switch for position indication.
Letter S designates panic lock switch with Emergency-OFF FS908GE front plate (yellow)
Master keys must always be ordered separately. Send or submit the security certificate with repeat orders. For SA(...), the precise designation of the key must be stated.Example: ES-KMS-SA(A6294-½)-T0
330 0 30
300
240225
210180
150
135120
90
6045
270
F
HG
J
KL
MN
PQ
R
A
BC
DE
315
07/058 07/059
1-866-595-96161-630-595-9515 Go to: http://www.klocknermoeller.com
T Cam Switches, P Motor Disconnect SwitchesAccessories
Cam
Sw
itch
es,
Mot
orD
isco
nnec
t Sw
itch
es
Cam
Swit
ches
,M
otor
Dis
conn
ect
Swit
ches
T Cam Switches, P Motor Disconnect SwitchesAccessories
Moeller Electric Corporation Moeller Electric Corporation
For use with Interlocking provisions
Type Suffix Price Interlocking provisions
Type PriceArticle No. Article No.
when ordered with basic device
see price list
when ordered separately see price list
SVC-T3 Padlocking feature, Front IP 65
The locking slide can be padlocked in the pushed-in position withup to 3 padlocks
All switch positions can be locked T0-.../E, .../I2, .../Z T3-.../E, .../I2, .../Z P1-.../E, .../I2, .../Z
interlocked posi-tions pre-pro-grammed from factory
+SVC-T3050963
interlocked posi-tions programmed on site
SVC-T3050975
Specified positions or ranges need to be locked T0-1-... up to T0-4-.../I2, .../ET3-1-... up to T3-5-.../I2 T3-1-... up to T3-6-.../E P1-.../I2, .../E
interlocked posi-tions programmed by factory per order specifications
+SVC(...)-T3907740
interlocked posi-tions programmed by factory per order specifications
SVC(...)-T3907748
DTV-T3 Push-release interlock, Front IP 65
This accessory allows a position to be switched only after the push-release locking slide has been pushed in. Should the push-release locking slide be padlocked in its released state, the device cannot be operated..
T0-.../E, .../I2, .../Z T3-.../E, .../I2, .../Z P1-.../E, .../I2, .../Z padlockable with up to 2 pad-locks
interlocked posi-tions pre-pro-grammed from factory
+DTV-T3050961
–
Specified positions need to be locked.Push-release locking slide can be padlocked in its released state with up to 2 padlocks.
interlocked posi-tions programmed by factory per order specifications
+DTV(...)-T3907733
–
Locking cams (2 cams per set)Select this accessory to change the position in which key can be removed
S-T0 for all switching angles – VR-T0089082
Select this accessory to change the position or ranges in which the switch can be locked.
SVA-T3, SVC-T3, for all switching anglesFor DTV-T3: order 2 x VR-T3
– VR-T3050987
Spare keys
For individual lock mechanisms Type KMS 1 S-T0, SVA-T3 – ES-KMS1-T0231972
For master key systems and registered lock mechanisms; specify as-signed plan number and the lock number position.
S-T0, SVA-T3 – ES-KMS-SA(*)-T0231974
Notes:
SVC-T3 will fit on all T0, T3 and P! switches. Switching is carried out using the thumb-grip handle. Pushing in the locking slide will interlock the position, which can then be padlocked off with up to 3 padlocks. Supplied as standard, all positions can be interlocked. With the SVC(...)-T3 accessory only those positions or ranges specified will be interlockable. In inter-locked ranges, switching without removal of the padlocks is only possible within that range.
In similar fashion to the SVA(...)-T3 accessory shown on the previous pages, the interlock-able positions or ranges for the SVC(...)-T3 and the locked positions and ranges for the DTV(...)-T3 are to be specified as follows:Example 1: SVC(A)-T3 only position A is lockedExample 2: SVC(A,E)-T3positions A and E are lockedExample 3: SVC(A-J)-T3positions A through J are locked (range)Example 4: DTV(G)-T3push-release mechanism needs to be actuated (pushed in) to allow switching of position G.Example 5: SVC(S)-T3main disconnect switch, fulfilling also the Emergency-Stopfunction per IEC/EN 602-4-1, with red handle and yellowfront plate. Suitable as “panic switch” with lockablepositions A(OFF) and E(ON); switching remains possiblefrom ON to OFF (E to A) without a key, but not from OFF to ON (A to E).
If the accessories are field installed, use the front plate supplied with the switch for position indication.
Letter S designates panic lock switch with Emergency-OFF FS908GE front plate (yellow)
Master keys must always be ordered separately. Send or submit the security certificate with repeat orders. For SA(...), the precise designation of the key must be stated.Example: ES-KMS-SA(A6294-½)-T0
330 0 30
300
240225
210180
150
135120
90
6045
270
F
HG
J
KL
MN
PQ
R
A
BC
DE
315
07/058 07/059
1-866-595-96161-630-595-9515 Go to: http://www.klocknermoeller.com
For locking in the OFF position. Exclusive for 90° switching angle switches such as the ones using FS 908(GE) as a front plate.Will accept a maximum of 3 padlocks.
Note: The red and yellow colored handles should be used only if the switch fulfills the function of Emergency-Stop. Otherwise, select the black version for Main Disconnect applications.
Padlocking feature, exclusively for main disconnect switches without Emergency-Stop functionBlack handle, black locking collarAdmissible for T0-... up to 4 contact chambers (8 contacts) and up to 6 chamber (12 contacts) for T3-...
Same as above, except that, on demand, handle can also be locked in the ON position (not permissible for red-yellow Emergency-Stop versions).Will accept a maximum of 3 padlocks.3Padlocks with KMS lock mechanism, type 219/38 (KMS....): please inquireT5B-.../E, .../Z, .../I4
P3-63/E, .../Z, .../I4 P3-100/E, .../Z, .../I5
– SVB-SW-P3062491
Main switch assembly kits, with PE terminals and N terminal
Padlocking feature, exclusively for main disconnect switches, to permit them to be used as Emergency-Stop devices 1)
Admissible for T0-... up to 4 contact chambers (8 contacts) and up to 6 chamber (12 contacts) for T3-...
T0-.../E, .../Z T3-.../E, .../Z
– V/EA/SVB-T0062638
These kits can be used to convert from one mounting form to another:• T.../E cover mounting switches (with front plate FS908 and thumb-grip handle) into T.../EA/SVB... cover mounting
main disconnect switches with padlockable handle
• T.../Z base mounting switches (with front plate FS908 and thumb-grip handle) into T.../V/SVB base mounting main disconnect switches with padlockable handle and cover interlock feature.
Note: the red and yellow colored handles should be used only if the switch fulfills the function of Emergency-Stop. Otherwise, select the black version for main disconnect applications
T5B-.../E, .../Z – V/EA/SVB-T5045065
T0-.../E, .../Z T3-.../E, .../Z
– V/EA/SVB-SW-T0065011
Padlocking feature, exclusively for main disconnect switches without Emergency-Stop functionBlack handle, black locking collarAdmissible for T0-... up to 4 contact chambers (8 contacts) and up to 6 chamber (12 contacts) for T3-...
The red colored handle is used internationally to denote an Emergency-Stop function and should be combined with the yellow colored name plate, type FS 908GE-T0. Order separately.
black T5B-.../E, .../Z, .../I4 P3-63/E, .../Z, .../I4 P3-100/E, .../Z, .../I5
– KNB-P3041282
red T5B-.../E, .../Z, .../I4 P3-63/E, .../Z, .../I4 P3-100/E, .../Z, .../I5
+KNB-RT-P3003215
KNB-RT-P3046028
The red colored handle is used internationally to denote an Emergency-Stop function and should be combined with the yellow colored name plate, type FS 908GE-P3. Order separately.
Maintenance handledesigned for cover interlocked switches mounted in panels T0-.../V, T3-.../V, P1-.../V – KNK-T0
000650Base mounted main disconnect switches have a cover interlock feature which prevents inadvertent opening of a control panel door when the switch is in the ON position. Per EN 60 204-1, part 1 (Machinery Directive standard), KNK-... handles are spe-cially designed to defeat the interlock and permit authorized personnel to switch the disconnect ON and OFF when the panel door is open in order to perform routine panel maintenance or troubleshooting tasks.
T5B-.../V, P3-.../V – KNK-P3000649
Notes: 1) Main disconnect switches which fulfill the function of Emergency-Stop have red handles and yellow collars andare padlockable in the OFF position (IEC/EN 60 204-1).
07/060 07/061
1-866-595-96161-630-595-9515 Go to: http://www.klocknermoeller.com
For locking in the OFF position. Exclusive for 90° switching angle switches such as the ones using FS 908(GE) as a front plate.Will accept a maximum of 3 padlocks.
Note: The red and yellow colored handles should be used only if the switch fulfills the function of Emergency-Stop. Otherwise, select the black version for Main Disconnect applications.
Padlocking feature, exclusively for main disconnect switches without Emergency-Stop functionBlack handle, black locking collarAdmissible for T0-... up to 4 contact chambers (8 contacts) and up to 6 chamber (12 contacts) for T3-...
Same as above, except that, on demand, handle can also be locked in the ON position (not permissible for red-yellow Emergency-Stop versions).Will accept a maximum of 3 padlocks.3Padlocks with KMS lock mechanism, type 219/38 (KMS....): please inquireT5B-.../E, .../Z, .../I4
P3-63/E, .../Z, .../I4 P3-100/E, .../Z, .../I5
– SVB-SW-P3062491
Main switch assembly kits, with PE terminals and N terminal
Padlocking feature, exclusively for main disconnect switches, to permit them to be used as Emergency-Stop devices 1)
Admissible for T0-... up to 4 contact chambers (8 contacts) and up to 6 chamber (12 contacts) for T3-...
T0-.../E, .../Z T3-.../E, .../Z
– V/EA/SVB-T0062638
These kits can be used to convert from one mounting form to another:• T.../E cover mounting switches (with front plate FS908 and thumb-grip handle) into T.../EA/SVB... cover mounting
main disconnect switches with padlockable handle
• T.../Z base mounting switches (with front plate FS908 and thumb-grip handle) into T.../V/SVB base mounting main disconnect switches with padlockable handle and cover interlock feature.
Note: the red and yellow colored handles should be used only if the switch fulfills the function of Emergency-Stop. Otherwise, select the black version for main disconnect applications
T5B-.../E, .../Z – V/EA/SVB-T5045065
T0-.../E, .../Z T3-.../E, .../Z
– V/EA/SVB-SW-T0065011
Padlocking feature, exclusively for main disconnect switches without Emergency-Stop functionBlack handle, black locking collarAdmissible for T0-... up to 4 contact chambers (8 contacts) and up to 6 chamber (12 contacts) for T3-...
The red colored handle is used internationally to denote an Emergency-Stop function and should be combined with the yellow colored name plate, type FS 908GE-T0. Order separately.
black T5B-.../E, .../Z, .../I4 P3-63/E, .../Z, .../I4 P3-100/E, .../Z, .../I5
– KNB-P3041282
red T5B-.../E, .../Z, .../I4 P3-63/E, .../Z, .../I4 P3-100/E, .../Z, .../I5
+KNB-RT-P3003215
KNB-RT-P3046028
The red colored handle is used internationally to denote an Emergency-Stop function and should be combined with the yellow colored name plate, type FS 908GE-P3. Order separately.
Maintenance handledesigned for cover interlocked switches mounted in panels T0-.../V, T3-.../V, P1-.../V – KNK-T0
000650Base mounted main disconnect switches have a cover interlock feature which prevents inadvertent opening of a control panel door when the switch is in the ON position. Per EN 60 204-1, part 1 (Machinery Directive standard), KNK-... handles are spe-cially designed to defeat the interlock and permit authorized personnel to switch the disconnect ON and OFF when the panel door is open in order to perform routine panel maintenance or troubleshooting tasks.
T5B-.../V, P3-.../V – KNK-P3000649
Notes: 1) Main disconnect switches which fulfill the function of Emergency-Stop have red handles and yellow collars andare padlockable in the OFF position (IEC/EN 60 204-1).
07/060 07/061
1-866-595-96161-630-595-9515 Go to: http://www.klocknermoeller.com
1 N.O., 1 N.C. contact (2 modules maximum per 3 pole switch)
Can be mounted to the left and/or right of a 3-pole P... disconnect switch P1-.../E, .../EA..., .../EZ P3-.../E, .../EA
+HI11-P1/P3E064100
HI11-P1/P3E061813
The N.O. auxiliary contact is always switching as a load shedding contact, i.e. it operates as a late make-early break contact with respect to the main power (L1, L2, L3) contactsThis feature is especially designed to insure that, when switching OFF the main disconnect, certain critical circuits will be de-energized prior to opening of the main contacts.
With P1-.../I2:optional HI11-P1/P3Z or N-P1Z can only be mounted to the left
Will enable a cover mounted switch to mount in a 22.5 mm opening (same as a 22.5 mm pilot device)
With front plate T0-.../E, T3-.../E +EZ-T0001750
EZ-T0081622
The switch snaps into place and speeds up mounting in panel walls, plates and doors. Will also accommodate legend plates from the RMQ-Titan line of control circuit devices.
Without front plate(to accommodate custom engraved front plate)
T0-.../E, T3-.../E +EZ/OFS-T0001751
EZ/OFS-T0001869
For both 22,5 mm and 30,5 mm openings T0-.../E, T3-.../E, P1-.../E +EZ-P1026222
EZ-P1091455
Permits one-person mounting of the switch in a 22.5mm or 30.5 mm opening. Mounting is done with screws.Will also accommodate legend plate from the RMQ-Titan line of control circuit devices.
Cover for base mounted T0 switchesSupplied with plug-in shaft to accommodate handle T0-.../XZ +IVS-T0
045472IVS-T0091114
Cover for base mounted, open style panel switch. Supplied with a shaft to accommodate a thumb-grip handle.Will also accommodate front plate supplied with the switch.
07/062 07/063
1-866-595-96161-630-595-9515 Go to: http://www.klocknermoeller.com
1 N.O., 1 N.C. contact (2 modules maximum per 3 pole switch)
Can be mounted to the left and/or right of a 3-pole P... disconnect switch P1-.../E, .../EA..., .../EZ P3-.../E, .../EA
+HI11-P1/P3E064100
HI11-P1/P3E061813
The N.O. auxiliary contact is always switching as a load shedding contact, i.e. it operates as a late make-early break contact with respect to the main power (L1, L2, L3) contactsThis feature is especially designed to insure that, when switching OFF the main disconnect, certain critical circuits will be de-energized prior to opening of the main contacts.
With P1-.../I2:optional HI11-P1/P3Z or N-P1Z can only be mounted to the left
Will enable a cover mounted switch to mount in a 22.5 mm opening (same as a 22.5 mm pilot device)
With front plate T0-.../E, T3-.../E +EZ-T0001750
EZ-T0081622
The switch snaps into place and speeds up mounting in panel walls, plates and doors. Will also accommodate legend plates from the RMQ-Titan line of control circuit devices.
Without front plate(to accommodate custom engraved front plate)
T0-.../E, T3-.../E +EZ/OFS-T0001751
EZ/OFS-T0001869
For both 22,5 mm and 30,5 mm openings T0-.../E, T3-.../E, P1-.../E +EZ-P1026222
EZ-P1091455
Permits one-person mounting of the switch in a 22.5mm or 30.5 mm opening. Mounting is done with screws.Will also accommodate legend plate from the RMQ-Titan line of control circuit devices.
Cover for base mounted T0 switchesSupplied with plug-in shaft to accommodate handle T0-.../XZ +IVS-T0
045472IVS-T0091114
Cover for base mounted, open style panel switch. Supplied with a shaft to accommodate a thumb-grip handle.Will also accommodate front plate supplied with the switch.
07/062 07/063
1-866-595-96161-630-595-9515 Go to: http://www.klocknermoeller.com
T Cam Switches, P Motor Disconnect SwitchesAccessories
Cam
Sw
itch
es,
Mot
orD
isco
nnec
t Sw
itch
es
Cam
Swit
ches
,M
otor
Dis
conn
ect
Swit
ches
T Cam Switches, P Motor Disconnect SwitchesAccessories
Moeller Electric Corporation Moeller Electric Corporation
For use with Type Suffix Price Type PriceArticle No. Article No.when ordered with basic device
see price list
when ordered separately see price list
Coupling drive
Supplied with plug-in shaft to accommodate handle
Linking mechanism used in the conversion of a basic switch T0(3)-.../XZ into a base mounted version .../Z.
– DE-T0093487
Can also be stocked as a spare part for the T0(3)(P1)-.../Z switch
For the conversion of T5B-.../E cover mounted switches into T5B-.../Z base mounted switches.
– DE-P3093972
Can also be stocked as a spare part for the T5B(P3)-.../Z switch.
Interlock sections
Provides cover mounted switches with 2 terminals for PE and N conductor connection. T0-.../E, .../EZ T3-.../E, .../EZ P1-.../E, .../EZ
+UV-T0038519
UV-T0019925
Featuring a set of terminals for connection of ground (PE) and neutral (N) conductors and mounts on the back side of the cover mounted switch to provide easier access to these terminals.
T5B-.../E P3-.../E
+UV-P3030402
UV-P3048289
Provides base mounted switches with a cover or door interlockwith PE and N conductor connection
T0-.../Z T3-.../Z P1-.../Z
+UV-T0038519
UV-T0019925
With base mounted switches, the accessory mounts on the front of the switch and, in addition to providing a set of PE and N terminals, functions as a cover interlock to prevent opening of the panel door when the switch is in the ON position.
T5B-.../Z P3-.../Z
+UV-P3030402
UV-P3048289
Cover interlock extensions 1)
Max. of 4, 25 mm each, can be plugged onto interlock section(an equal number of shaft extensions is required for this purpose)
UV-T0 +ZVV-T0024662
ZVV-T0022298
Refer to page 07/70 for information on matching switch heights when mounting into an enclosure.
UV-P3 +ZVV-P3024379
ZVV-P3024671
Shaft extensionsMax. of 4, 25 mm each, can be plugged onto switch shaft T0-.../Z
T3-.../Z P1-.../Z
+ZAV-T0023736
ZAV-T0027044
Refer to page 07/70 for information on matching switch heights when mounting into an enclosure.
T5B-.../Z P3-.../Z
+ZAV-P3026623
ZAV-P3029417
Notes: 1) Use ZVV-T0 only with T0/T3-.../Z and P1-.../Z Use ZVV-P3 only with T5B-.../Z and P3-.../Z
07/064 07/065
1-866-595-96161-630-595-9515 Go to: http://www.klocknermoeller.com
T Cam Switches, P Motor Disconnect SwitchesAccessories
Cam
Sw
itch
es,
Mot
orD
isco
nnec
t Sw
itch
es
Cam
Swit
ches
,M
otor
Dis
conn
ect
Swit
ches
T Cam Switches, P Motor Disconnect SwitchesAccessories
Moeller Electric Corporation Moeller Electric Corporation
For use with Type Suffix Price Type PriceArticle No. Article No.when ordered with basic device
see price list
when ordered separately see price list
Coupling drive
Supplied with plug-in shaft to accommodate handle
Linking mechanism used in the conversion of a basic switch T0(3)-.../XZ into a base mounted version .../Z.
– DE-T0093487
Can also be stocked as a spare part for the T0(3)(P1)-.../Z switch
For the conversion of T5B-.../E cover mounted switches into T5B-.../Z base mounted switches.
– DE-P3093972
Can also be stocked as a spare part for the T5B(P3)-.../Z switch.
Interlock sections
Provides cover mounted switches with 2 terminals for PE and N conductor connection. T0-.../E, .../EZ T3-.../E, .../EZ P1-.../E, .../EZ
+UV-T0038519
UV-T0019925
Featuring a set of terminals for connection of ground (PE) and neutral (N) conductors and mounts on the back side of the cover mounted switch to provide easier access to these terminals.
T5B-.../E P3-.../E
+UV-P3030402
UV-P3048289
Provides base mounted switches with a cover or door interlockwith PE and N conductor connection
T0-.../Z T3-.../Z P1-.../Z
+UV-T0038519
UV-T0019925
With base mounted switches, the accessory mounts on the front of the switch and, in addition to providing a set of PE and N terminals, functions as a cover interlock to prevent opening of the panel door when the switch is in the ON position.
T5B-.../Z P3-.../Z
+UV-P3030402
UV-P3048289
Cover interlock extensions 1)
Max. of 4, 25 mm each, can be plugged onto interlock section(an equal number of shaft extensions is required for this purpose)
UV-T0 +ZVV-T0024662
ZVV-T0022298
Refer to page 07/70 for information on matching switch heights when mounting into an enclosure.
UV-P3 +ZVV-P3024379
ZVV-P3024671
Shaft extensionsMax. of 4, 25 mm each, can be plugged onto switch shaft T0-.../Z
T3-.../Z P1-.../Z
+ZAV-T0023736
ZAV-T0027044
Refer to page 07/70 for information on matching switch heights when mounting into an enclosure.
T5B-.../Z P3-.../Z
+ZAV-P3026623
ZAV-P3029417
Notes: 1) Use ZVV-T0 only with T0/T3-.../Z and P1-.../Z Use ZVV-P3 only with T5B-.../Z and P3-.../Z
07/064 07/065
1-866-595-96161-630-595-9515 Go to: http://www.klocknermoeller.com
Can be used to shield incoming and/or outgoing conductors.Order 2 covers in the case of both. The cover fits over the entire widthof a 5 pole switch (3 power poles and 2 auxiliary modules). Unusedportions of the cover can be broken off.
07/066 07/067
1-866-595-96161-630-595-9515 Go to: http://www.klocknermoeller.com
Can be used to shield incoming and/or outgoing conductors.Order 2 covers in the case of both. The cover fits over the entire widthof a 5 pole switch (3 power poles and 2 auxiliary modules). Unusedportions of the cover can be broken off.
07/066 07/067
1-866-595-96161-630-595-9515 Go to: http://www.klocknermoeller.com
T Cam SwitchesMounting Cam Switches with Coupling (T.../Z or T.../V/SVB) into Enclosures
Cam
Sw
itch
es,
Mot
or D
isco
nnec
t Sw
itch
esMoeller Electric Corporation
Notes
CI-K... insulated enclosures are enclosures specifically designed for the installation of cam switches, such as T0 and T5B with up to 4 contact chambers = 8 contacts, T3 with up to 5 contact chambers = 10 contacts. They have a high degree of protection. If more than 5 cables or large cross-section cables are to be connected, then we recommend the use of insulated enclosures from the the CI system (a Section 11) .
How to match enclosure and Type T... switch sizes:1) Select the required switch and determine the cables to be connected.2) Select an enclosure according to the minimum mounting depth of the switch.
This depth dimension has to be less than or equal to the internal mountingdepth of the enclosure. In addition, the quantity and size of the cable must betaken into account.
Use the tables below to determine whether, and if so how many, ZAV-... shaft ex-tensions are required and, for .../SVB switches, the identical quantity of ZVV-.... in-terlock extensions.
Example:Switch:T3-6-.../V/SVBMinimum mounting depth:T...-6/Z = 147 mmExtensions:No extension is required for an enclosure having a mounting depth of 150 mm. Two ZAV-T0 shaft extensions and two ZVV-T0 interlock extensions are required for an enclosure having a mounting depth of 200 mm.
T Cam Switches, P Motor Disconnect SwitchesTripping Characteristics
Moeller Electric Corporation 07/071
Component lifespan in relation to breaking current and utilization category 1)
In order to achieve a reasonable lifespan in utilization category AC-4 (severe duty: 100 % inching, reversing or plugging)the stalled motor current should not exceed the rated current of the switch at AC-21A.
Notes 1) AC-3 and AC-21 at 400 V, AC-15 at 230 V
1-866-595-96161-630-595-9515 Go to: http://www.klocknermoeller.com
Switch-disconnectors to IEC/EN 60 947-3Load-break switch to IEC/EN 60 947-3
Mechanical lifespan,max. operating frequency
Operationsops./h
> 106
30005 x 105
30005 x 105
3000Climatic proofing Damp heat, constant, to IEC 60 068-2-3
Damp heat, cyclical, to IEC 60 068-2-30Ambient temperature open min./max. °C −25/+50 −25/+50 −25/+50
enclosed min./max. °C −25/+40 −25/+40 −25/+40Mounting position as requiredDimensions a page 07/076 a page 07/081Weight a page 14/020Mechanical shock resistance (shock duration 20 ms) g > 15 > 152) > 15
Main contact rating per IEC/EN 60 947Rated operational voltage Ue V AC 690 3) 690 3) 690Rated impulse withstand voltage Uimp V 6000 6000 6000Overvoltage category / degree of pollution III/3 III/3 III/3Rated uninterrupted current Iu open and enclosedwith max. cable connected
A 20 32 63
Load-carrying capacity in intermittent operation, Class 12, AB 60/40/25 % DF 1,3/1,6/2 x IeShort circuit rating max. fuse A gL/gG 20 25 80Rated short time withstand current (1-s current) Icw Aeff 320 650 1300Safe isolation between contacts to VDE 0106 part 101and part 101 A1
V AC 440 440 440
Protection against direct contact Finger and back-of-hand proof to VDE 0106 part 100
Universal device ratingsSwitching angles 90°/60°/45°/30°Contact chambers max. 11 11 10Double break contacts max. 22 22 20Current heat loss per contact at Ie W 0.6 1.1 4.5
Main contact rating per UL/CSARated operational voltage V AC 600 600 600Rated uninterrupted current (general use) A 14 25 65
Terminal capacity per IEC/EN 60 947Solid or stranded 1) mm2 1 x (1 – 2.5) 1 x (1 – 6) 1 x (2.5 – 35)
mm2 2 x (1 – 2.5) 2 x ( 1 – 6) 2 x (2.5 – 16)Flexible with ferrule 1)
(ferrule to DIN 46 228)mm2 1 x (0.75 – 1.5) 1 x (0.75 – 4) 1 x (1.5 – 25)mm2 2 x (0.75 – 1.5) 2 x (0.75 – 4) 2 x (1.5 – 10)
Rated making capacity cos v = 0,35 A 130 320 800Rated breaking capacity 230 V AC, cos v = 0,35 A 100 260 520Motor load switches 400 V AC, cos v= 0,35 A 110 260 600
500 V AC, cos v = 0,35 A 80 240 480690 V AC, cos v = 0,35 A 60 170 340
AC-21A Load-break switches Rated operational current Ie440 V
A 20 32 63
AC-3 Motor load switches, for op-erational switching, star-delta values Yd : Y d-switches without automatic spring-return
Switch-disconnector to IEC/EN 60 947-3Mechanical lifespan operations 3 x 105 3 x 105 105 105
Max. switching frequency ops./h 50 50 50 50Climatic proofing Damp heat, constant, to IEC 60 068-2-3
Damp heat, cyclical, to IEC 60 068-2-30Ambient temperature open min./max. °C −25/+50 −25/+50 −25/+50 −25/+50
enclosed min./max. °C −25/+40 −25/+40 −25/+40 −25/+40Mounting position as requiredDimension a page 07/083Weight a page 14/020Mechanical shock resistance (half-sinusoidal shock 20 ms) g 15 15 15 15
Main contact ratings per IEC/EN 60 947Rated operational voltage Ue V AC 690 690 690 690Rated impulse withstand voltage Uimp V 6000 6000 6000 6000Overvoltage category / degree of pollution III/3 III/3 III/3 III/3Rated uninterrupted current Iu with max. cable connected A 25 32 63 100Load-carrying capacity in intermittent operation Class 12, AB 60/40/25 % DF
x Ie 1.3/1.6/2 1.3/1.6/2 1.3/1.6/2 1.3/1.6/2
Short-circuit rating max. fuse A gL/gG 25 50 80 100Rated short-time withstand current (1-s current) Icw Aeff 640 640 1260 2000Isolating characteristics to IEC/EN 60 947 up to V AC ≤ 690 ≤ 690 ≤ 690 ≤ 690Safe isolation to VDE 0106 part 101 and part 101 A1 between the main contacts and the auxiliary contacts
V AC 440 440 440 440
Universal device ratingsProtection against direct contact Finger and back-of-hand proof to VDE 0106 part 100Switching angle 90° 90° 90° 90°Main contacts (current paths) max. max. 3 (+N) max. 3 (+N) max. 3 (+N) max. 3 (+N)Current heat loss per contact at Ie W 1.1 1.8 4.5 7.5
Main contact rating per UL/CSARated operational voltage V AC 600 600 600 600Rated uninterrupted current (general use) A 20 30 60 100
Rated making capacity cos v = 0,35 A 240 320 800 950Rated breaking capacity 230 V AC, cos v = 0,35 A 190 260 640 760Motor load switches 400 V AC, cos v = 0,35 A 150 300 600 740
500 V AC, cos v = 0,35 A 170 290 590 880690 V AC, cos v = 0,35 A 150 250 340 520
AC-21A Load break switches Rated operational current 440 V A 25 32 63 100AC-3 Motor load switches for
operational switching230 V kW 5,5 7,5 15 22400 V kW 7,5 13 30 37500 V kW 7,5 18,5 30 45690 V kW 7,5 15 30 37
AC-23A Motor load switches(main switches, maintenance switches)
230 V kW 7 8,5 18,5 30400 V kW 13 15 37 50500 V kW 11 18,5 37 65690 V kW 11 18,5 30 75
DCDC-1 Load-break switches
L/R = 1 msRated operational current Ie A 25 32 63 100
Voltage per contact pair in series V 60 60 60 60DC-23A Motor load switches
L/R = 15 ms
Figures in parentheses:number of contacts to be switches in series)
24 V A 25 (1) 25 (1) 50 (1) 50 (1)48 V A 25 (2) 25 (2) 50 (2) 50 (2)60 V A 25 (3) 25 (3) 50 (3) 50 (3)120 V A 12 (3) 12 (3) 25 (3) 25 (3)
Short-circuit current ratings per UL/CSAManual motor controller 600 V AC kA 5 5 10 10
with backup fuse A 110 110 150 150with circuit breaker Type NZM(H)6(B) 1)
Circuit breaker current rating A 125Motor disconnect 600 V AC kA 10 10 10 10
with backup fuse Class 50 A/J 50 A/J 100 A 100 A
N-P1... N-P3...
Switched neutralSwitching capacity as P1-32 as P3-100
HI11-P1/P3
Auxiliary contactsIEC ratings
Standards Control circuit isolator to IEC/EN 60 947-5Rated Insulation voltage Ui V AC 500Rated uninterrupted current Iu with max. cable connected A 10Rated operational current Ie AC-15 at 230/380 – 415/500 V A 6/4/3Short-circuit rating without welding, max. fuse A gL/gG 10Terminal capacity solid mm2 0.75 – 2.5
stranded with ferrule mm2 0.5 – 1.5Max. tightening torque Nm 0,6Control circit reliability at 24 V DC, 10 mA
Fault probability HF < 10−5, < 1 fault in 100000 operations
UL/CSA ratingsRated operational voltage V AC 600Rated continuous current (general use) A 10Pilot Duty A A 600, P 600
Notes: 1) Consult section 09 of this catalog for more information on NZM(H)6(B) circuit breakers
07/075
1-866-595-96161-630-595-9515 Go to: http://www.klocknermoeller.com
Switch size Number of contact chambers Contact sequence numberWith manufacturing country identifier. For initial order, enclose completed form (see next page).Contact sequence number is issued by factory.For subsequent orders, type suffix issufficient.
• Base mounting with cover /IVS (for T0)• Base mounting /Z• Cover mounting main switches
/EA/SVB2)
• Surface mounting main switches /I.../SVB
• Base mounting main switches /V/SVB 2)
Accessoriesa pages07/056 – 071State in full with every order!
Max. chambers
Max.contacts
T0 11 22T3 11 22T5B 10 20
07/087
Contact sequenceForm FO 2 (see next page) makes it easy to de-termine the contact sequence. Master copy a page 07/088Switching angles30, 45, 60, 90° Preferred angle: 60°For On/Off switches: 90°For main switches: 90° as FS 908Interruption of contacts between 2 switch posi-tions (On-Off-On) not admissible on T0; or T3 at switching angles of 30°, 45°; or T5B at switching angle of 30°
Spring-returnThe switching movement is limited by a stop. The switch returns under spring pressure to the last indexed position. Where a switch has spring-return from both directions, a maximum of three positions can be transversed.The return angle is < ½ switching angle. A max-imum of 6 contacts can be returned at the same time.
Fleeting contactsDuration of contact depends primarily on the speed of actuation. If a contactor is to be actu-ated by means of fleeting contact, the switching angle of the cam switch must not be less than 60°, or the switching pulse may be too short. Fleeting contacts always act in both directions.
Complete rotationPossible only with a total switching angle of 360°. Unrestricted rotation in either direction. The number of switch positions multiplied by the switching angle must equal 360°.
Number of contact chambersNumber of contacts = round up to nearest whole
2
Each contact chamber = contact unit has 1 or 2 contacts, each oeprated by a cam.On T5B one cam operates both contacts. Consequently: where the total switching angle is less than 180°, the contacts can be operated in-dependently of one another. At switching angles of 180° and above, two contacts per chamber are possible only if their switching sequences are the same, but offset by 180°. (e.g. stepping switch T5B-4-8235).
Standard featuresas for cam switches with standard contact se-quencesa page 07/006, 008
Notes pageTechnical data 07/072Dimensions 07/076
NotesThe sequence of the contacts may be changed if tech-nical reasons so dictate.For non-standard switches it is preferable to arrange the links so that terminals whose numbers differ by 4 are linked with one another, e.g. terminals 1-5-9; 2-6-10; 3-7-11- or 4-8-12-. Such links can be removed (al-so applies for standard switches), whereas links 1-3, 2-4, 5-7, 6-8 cannot be removed because they are sit-uated within the switch.
Links between an even number and an odd number (e.g. 2-3) cannot be provided by the factory and must be supplied by the user.
1) T0-.../I2 up to 4 contact chambers T3-.../I2 up to 5 contact chambers
2) T0 up to 8 contacts = 4 contact chambers, T3 up to 12 contacts = 6 contact chambers
1-866-595-96161-630-595-9515 Go to: http://www.klocknermoeller.com
T Cam SwitchesOrdering of Non-standard Front Plates
Cam
Sw
itch
es,
Mot
or D
isco
nnec
t Sw
itch
esMoeller Electric Corporation
/ D Initial ordering of non-standard front plates
Première commande de plastrons spéciaux
Ordering number:N° de commande :
Position:Poste :
Office:Bureau :
Representative:Employé :
Customer:Client
Customer number:N° client :
Quantity:Quantité :
Price/eachPrix unitaire :
Date:Date :
Non-standard front plates / Plastrons spéciauxMarking/repérage):Front plate with black letteringPlastron à caractères noirsInsert text / insèrer texteNote the maximum number of characters allowed outside the marked area!Indiquer le nombre max. de caractères permis à l’extérieur du marquageType
q FS-SOND-T0 (T3, P1)Height of letters / hauteur des caractères
For P1 and P3 complete only positions 270° and 0° / Pour P1 et P3, indiquer seulement les positions 270° et 0°
Max. no. of characters / Nombre max. des caractèresPositionDegrees / degrés T0/P1 T5/P3 Dimensions0, 180 13 13 Type Size of front plate / Dimensions du plastron30, 210, 330 8 845, 135, 225, 315 6 7 T0, T3, P1 45 x 45 mm (for frame sizes / pour cadres 48 x 48)60, 120, 240, 300 5 7 P3, T5B 84 x 84 mm (for frame sizes / pour cadres 88 x 88) 90, 270 4 7150 8 8
Type for re-orders (to be filled in by Factory)Référence pour commandes ultérieures (à compléter par l´usine) FS.....................................................................................
07/090
1-866-595-96161-630-595-9515 Go to: http://www.klocknermoeller.com