Top Banner
BUILD YOUR REPUTATION ON OURS Modular Hi-Rise Series FAN COIL TECHNICAL CATALOG
32

Modular Hi-Rise Series - IEC Environmental International€¦ · installations where two units share riser ... Room B Room A MPY MPY Room B ... International Environmental Corporation

Apr 19, 2018

Download

Documents

lenhan
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: Modular Hi-Rise Series - IEC Environmental International€¦ · installations where two units share riser ... Room B Room A MPY MPY Room B ... International Environmental Corporation

BUILD YOUR REPUTATION ON OURS

Modular Hi-Rise SeriesFAN COIL TECHNICAL CATALOG

Page 2: Modular Hi-Rise Series - IEC Environmental International€¦ · installations where two units share riser ... Room B Room A MPY MPY Room B ... International Environmental Corporation

International Environmental Corporation • Modular Hi-Rise Series Fan Coil Technical Catalogwww.iec-okc.com2

Modular Hi-Rise Series

International Environmental Corporation (IEC) works continually

to improve its products. As a result, the design and specifications

of each product may be changed without notice and may not be

as described herein. Please contact IEC for information regarding

current design and product specifications. Statements and

other information contained herein are not express warranties

and do not form the basis of any bargain between the parties

but are merely IEC’s opinion or commendation of its products.

Manufacturer’s standard limited warranty applies.

Page 3: Modular Hi-Rise Series - IEC Environmental International€¦ · installations where two units share riser ... Room B Room A MPY MPY Room B ... International Environmental Corporation

International Environmental Corporation • Modular Hi-Rise Series Fan Coil Technical Catalogwww.iec-okc.com

Modular Hi-Rise Series

3

TABLE OF CONTENTS

3 Table of Contents

4 Portfolio

5 Features and Benefits

7 Product Application

11 Unit Model Key

12 Ratings and Listings

13 Fan Performance Curves

16 Electric Heating

17 Motor Data

18 Submittal Data

25 Standard Features and Options

Page 4: Modular Hi-Rise Series - IEC Environmental International€¦ · installations where two units share riser ... Room B Room A MPY MPY Room B ... International Environmental Corporation

International Environmental Corporation • Modular Hi-Rise Series Fan Coil Technical Catalogwww.iec-okc.com4

Modular Hi-Rise SeriesPORTFOLIO

MXY – Modular Hi-Rise Cabinet – 300 CFM to 1200 CFMThe Exposed Modular (MXY) fan coil unit is

designed for applications where concealed

installation is not possible or practical. The

slim, attractively-styled cabinet of the MXY

blends with all types of decor. MXY units

feature a double-deflection supply grille, an

integral return air panel and a unit-mounted

thermostat control. Standard MXY units are

provided with a powder-coat paint finish.

MMY/MSY – Modular Hi-Rise Concealed Primary/Secondary – 300 CFM to 1200 CFMThe Primary/Secondary Modular (MMY/MSY) fan coil

unit is ideal for applications where design restricts the

installation of IEC’s Ditto or Siamese Ditto systems. With

this configuration, field brazing is required to complete the

piping between two separate Modular Hi-Rise fan coil units.

Standard MMY/MSY units are provided with a galvanized

finish on the cabinet and a powder-coat paint finish on the

return air panel.

MRY – ReStoraMOD® Hi-Rise – 300 CFM to 1200 CFMThe ReStoraMOD® fan coil unit allows for

replacement of aging hi-rise fan coils

without waiting for a complete whole

room renovation budget. This mod offers

the latest in energy savings and IAQ

features including optional ECM, closed cell

insulation, and more. Replaces most existing

modular hi-rise units including competitor’s

units. Minimal disturbance of wall and room

finishes eliminates downtime with the

fastest Modular Hi-Rise installation in the

industry.

MPY – Modular Hi-Rise Concealed – 300 CFM to 1200 CFMThe Concealed Modular (MPY) fan coil unit,

International Environmental Corporation’s

(IEC) premier Modular unit, is designed

for concealed applications in corners or

along room walls. Once installed, only

the thermostat control, supply grille and

decorative return air panel of the MPY

are visible in the room. The return air

panel provides easy access to all internal

components. Standard MPY units are provided

with a galvanized finish on the cabinet and a powder-coat

paint finish on the return air panel.

MAY/MBY – Modular Hi-Rise Concealed Ditto – 300 CFM to 1200 CFMThe Ditto Concealed Modular (MAY/

MBY) fan coil system is designed for

installations where two units share riser

piping in the separation wall between

two rooms but are equipped with

individual valves, supply and return

grilles, and controls. The Ditto Concealed

Modular unit is shipped factory

assembled for additional installed cost

savings. Standard Ditto units are provided with a galvanized

finish on the cabinet and a powder-coat paint finish on the

return air panel.

Page 5: Modular Hi-Rise Series - IEC Environmental International€¦ · installations where two units share riser ... Room B Room A MPY MPY Room B ... International Environmental Corporation

International Environmental Corporation • Modular Hi-Rise Series Fan Coil Technical Catalogwww.iec-okc.com

Modular Hi-Rise Series

5

FEATURES AND BENEFITS

Versatility In Design and InstallationModular Hi-Rise fan coil systems offer versatile unit arrangements made possible as a factory-assembled and integrated package. They are designed to be of low visual impact in the room, often positioned in a corner, along the perimeter wall or as part of a partition separating two areas. They can also stand alone in an exposed configuration.

Design Features

Field or factory-installed insulated water and condensate risers

Swaged riser connection

Double-deflection supply air grille

Galvanized steel cabinet

Unit installed behind drywall

Thermostat with quick-connect

Powder-coat return air access panel

Removable motor and blower assembly with quick-connect plug

Draw-through, 4-pipe coil*

Filter

Factory-installed control valves with quick-connect actuators

Insulated drain pan with p-trap

Control box with cover

Removable acoustical service access panel (not shown)

* Available applications are 2-pipe, 4-pipe (shown), 2-pipe auxiliary electric heat, and 2-pipe total electric heat.

The Ditto is designed for those applications where the Hi-Rise fan coils are part of a partition separating two areas. The Ditto consists of two units complete with separate valves and controls, which are shipped factory-assembled with common risers.

Page 6: Modular Hi-Rise Series - IEC Environmental International€¦ · installations where two units share riser ... Room B Room A MPY MPY Room B ... International Environmental Corporation

International Environmental Corporation • Modular Hi-Rise Series Fan Coil Technical Catalogwww.iec-okc.com6

Modular Hi-Rise SeriesFEATURES AND BENEFITS, Cont’d.

Application Fit• Exposed and concealed cabinets with 45 possible

airflow configurations provide solutions for multiple applications.

• A variety of aesthetically pleasing return and supply grilles will blend with most décors.

• Thermostats are available as unit, surface, wall or ADA mounted for ease of human interface.

• Units are specifically designed for quiet operation.

Design Flexibility• Easy to use computer rating program to speed up

project design.• Wide variety of coil configurations to match the

heating and cooling loads of the space. Coils with different pressure drops to meet the needs of custom applications are also available.

• Standard motor/blower assemblies to meet the needs of applications where duct work is required.

• Customizable cabinetry is available for special applications. Ideal for new construction and renovation projects.

• Optional Ditto fan coil designed to serve two separate rooms using UL listed one-hour fire-rated riser chase.

• Multiple riser locations for total flexibility.• Wide variety of valve packages factory installed to

meet desired control specifications.• Manual or motorized outside air dampers are available

to meet ventilation requirements and reduce field labor.

• Several MERV rated filter media available to address IAQ requirements.

• Extensive offering of control options available.• Wide variety of insulation material available to address

IAQ concerns.• Heavy galvanized or stainless steel drain pan with pre-

formed rubber p-trap.

Ease of Installation• Units assembled at the factory in coordination with

the jobsite construction schedule.• Riser length is matched to the job specifications and

pre-fabricated with the specified material. Risers are factory installed or shipped separately.

• Risers swaged to reduce field brazing labor and to ensure the integrity of the connections.

• Drywall can be applied directly to the surface of the concealed unit with factory provided duct collars and drywall stops to ensure a high quality finished appearance.

• Control box at eye level for ease of field wiring and easy access.

Ease of Service• Filters are easily accessible by removing return air

panel.• Motor and blower are removable with quick-connect

plug.• Control box is easily accessible and at eye level.

Quality and Safety• Every unit tested and inspected at the factory for

trouble free start-up.• ETL listed• AHRI certified

Page 7: Modular Hi-Rise Series - IEC Environmental International€¦ · installations where two units share riser ... Room B Room A MPY MPY Room B ... International Environmental Corporation

International Environmental Corporation • Modular Hi-Rise Series Fan Coil Technical Catalogwww.iec-okc.com

Modular Hi-Rise Series

7

PRODUCT APPLICATION

Versatile Unit Arrangement OptionsOne of the unique traits of the Modular Hi-Rise fan coil

system is the versatile unit arrangements possible with this

factory-assembled, integrated package. When selecting the

best unit design configuration for your specific single- or

multi-story building, you are afforded the luxury of choosing

from numerous unit arrangement options which achieve

maximum efficiency while conserving floor space and

reducing installation costs.

Modular Hi-Rise fan coils are designed to be unobtrusive in

the room and, thus, are often positioned in a corner, along a

perimeter wall, as part of a partition separating two areas, or

as a stand-alone unit in the exposed configuration. Modular

Hi-Rise fan coils can be specified with up to three side-

discharge openings as well as a top discharge for ducted

applications.

Below are a few of the many arrangement possibilities of the

Modular Hi-Rise fan coil system.

Exterior Wall

LEGEND

Field Sheetrock

IEC Sheetrock

Separation or Utility Chase

Modular Riser Unit

Field-installed Piping

Partition (or Separation) Wall

Supply Air

Return Air

Room ARoom B

MPY

MPY

Room ARoom B

MPY

Room ARoom B

MSY MMY

Room A Room B

MPY

Room ARoom B

MAY MBY

Room A Room B

MAY MBY

Room A Room B

Closet Closet

MAY

MBY

Room A Room B

MRY

Room ARoom B

Room A Room B

MRYMRY

Page 8: Modular Hi-Rise Series - IEC Environmental International€¦ · installations where two units share riser ... Room B Room A MPY MPY Room B ... International Environmental Corporation

International Environmental Corporation • Modular Hi-Rise Series Fan Coil Technical Catalogwww.iec-okc.com8

Modular Hi-Rise SeriesPRODUCT APPLICATION, Cont’d.

Double-side Supply

A2 B2 D2

K2H2G2

T2Q2P2

Top with Two-side SupplyB3 C3 D3

H3 J3 K3

Q3 S3 T3

RearRiser Location

MODCABINET

Right

Front

Left

Single-side Supply

A1

S1Q1P1

J1H1G1

C1B1

Top with One-side Supply

C2 E2 F2

N2

W2V2S2

M2J2

Top Supply OnlyD1

K1 T1

Three-side Supply

A3 G3 P3

Top with Three-side SupplyA4

G4 P4

Legend:Return

Supply

HR = Hot Water ReturnHS = Hot Water SupplyD = DrainCR = Cold Water ReturnCS = Cold Water Supply

D CRHS CSHR

R = ReturnD = DrainS = Supply

R D S

NOTES: 1. The risers (or riser chase) always determines the rear of the unit. The return air/access panel may then be on the left, right or front of the cabinet (as determined by project requirements).

2. MXY models are available with front return air only.

Page 9: Modular Hi-Rise Series - IEC Environmental International€¦ · installations where two units share riser ... Room B Room A MPY MPY Room B ... International Environmental Corporation

International Environmental Corporation • Modular Hi-Rise Series Fan Coil Technical Catalogwww.iec-okc.com

Modular Hi-Rise Series

9

PRODUCT APPLICATION, Cont’d.

.000 .005 .030.025.020.015.010 .035

THERMAL EXPANSION OF COPPER RISERS

EXPANSION (INCHES PER FOOT)

300

275

250

225

200

175

125

100

75

50

25

0

150

MA

XIM

UM

WAT

ER T

EMPE

RATU

RE D

IFFE

REN

CES

(ºF)

movement by the internal piping structure is not intended

to replace necessary expansion compensation devices

that the consulting engineer may deem advisable for the

external riser system. External riser expansion/contraction

compensation and anchoring are the responsibility of the

consulting engineer and the installing contractor.

Riser Material, Sizing and InsulationBecause Modular Hi-Rise units are furnished with

field or factory installed risers, the riser type, size

and length, and insulation for each unit must

be determined based on the position of the

unit in the building. The chilled and hot water

risers and condensate drain are available in a

variety of diameters from 3/4" through 2-1/2".

See Mechanical Specifications section. All factory

furnished risers and riser extensions, including

condensate drains, are insulated for the full riser

length to eliminate the need for field furnished

insulation. Other materials to accommodate

such critical specifications as riser expansion and

between-the-floor fire proofing must be field

furnished and installed by others. Consult the

factory for special Applications.

Riser sizing is normally based on the water flow

requirements of each unit and the units above and

below the unit in the riser column depending on

the type of system being used. A common design

criteria is to select the risers to limit water velocity

at four to seven feet per second. Using this method,

risers may be reduced in size as the water flow

reduces from floor to floor. Uniform riser sizing may

be used on shorter buildings where the additional

riser expense would likely be offset by a greater

savings in unit handling expense on the job.

Riser ExpansionIEC’s Modular Hi-Rise units are built to

accommodate modest expansion of the external risers.

Standard unit construction, including internal expansion

loops, allows for a maximum of ±3/4-inch of external riser

expansion/contraction. This only allows for expansion

between the unit and the riser. This allowance for the

Page 10: Modular Hi-Rise Series - IEC Environmental International€¦ · installations where two units share riser ... Room B Room A MPY MPY Room B ... International Environmental Corporation

International Environmental Corporation • Modular Hi-Rise Series Fan Coil Technical Catalogwww.iec-okc.com10

Modular Hi-Rise SeriesPRODUCT APPLICATION, Cont’d.

PRES

SURE

DRO

P –

FT. W

ATER

/ 10

0 FT

. OF

RISE

R

WATER FLOW RATE– GPM

100 90 80 70

60

50

40

30

20

10 9.0 8.0 7.0 6.0

5.0

4.0

3.0

2.0

1.0 .9 .8 .7 .6

.5

.4

.3

.2

.1

100 90 80 70

60

50

40

30

20

10 9.0 8.0 7.0 6.0

5.0

4.0

3.0

2.0

1.0 .9 .8 .7 .6

.5

.4

.3

.2

.1

1.0 2.0 3.0 4.0 5.0 6.0 8.0 10 20 30 40 50 60 80 100 200 300

1.0 2.0 3.0 4.0 5.0 6.0 8.0 10 20 30 40 50 60 80 100 200 300

1½ In

ch N

omin

al

6 FPS

5 FPS

4 FPS

3 FPS

2 FPS

8 FPS7 FPS

¾ In

ch N

omin

al

1 In

ch N

omin

al

1¼ In

ch N

omin

al

2½ In

ch N

omin

al

2 In

ch N

omin

al

3 In

ch N

omin

al

4 In

ch N

omin

al

Page 11: Modular Hi-Rise Series - IEC Environmental International€¦ · installations where two units share riser ... Room B Room A MPY MPY Room B ... International Environmental Corporation

International Environmental Corporation • Modular Hi-Rise Series Fan Coil Technical Catalogwww.iec-okc.com

Modular Hi-Rise Series

11

UNIT MODEL KEY

ThermostatFunction Control

***********

Note that kWs depend on voltage and unit size.For additional codes check the price sheet.Consult factory for pricing.

03 • 300 CFM04 • 400 CFM06 • 600 CFM08 • 800 CFM10 • 1000 CFM12 • 1200 CFM

Two-pipe Cooling and Heatingor Four-pipe Cooling

A • 3 RowB • 4 RowR • 3 Row, AAVS • 4 Row, AAV

Four-pipeHeating

Y • None6 • 1 Row Water

Heating7 • 2 Row Water

Heating

Voltage

C • 115-1-60D • 208-1-60E • 230-1-60F • 277-1-60

SINGLE SUPPLY**

ARR Code Return SupplyA1 Front FrontB1 Front RightC1 Front LeftD1 Front Top

DOUBLE SUPPLY**

ARR Code Return SupplyA2 Front Front/RightB2 Front Front/LeftC2 Front Front/TopD2 Front Right/LeftE2 Front Right/TopF2 Front Left/Top

Voltage

B • 24 V

C • 120 V

D • 208 VE • 240 VF • 277 V

System/Thermostat

Manual Fan Operation

A1 • Standard Unit Mount (Switch Only)

G • 2-Pipe Heat OnlyH • 2-Pipe Cool OnlyJ • 2-Pipe Heat and Cool, MCOK • 2-Pipe Heat and Cool, ACOL • 2-Pipe Heat and Cool w/ Aux. Elec. Heat, MCOM • 2-Pipe Heat and Cool w/ Aux. Elec. Heat, ACON • 2-Pipe Cool w/ Total Elec. Heat, MCOP • 2-Pipe Cool w/ Total Elec. Heat, ACOQ • 4-Pipe Heat and Cool, MCOR • 4-Pipe Heat and Cool, ACO

Type

2 • Permanent Split Capacitor

kW*

B • 1.00C • 1.50D • 2.00F • 3.00G • 4.00

Coil

A • 3 RowB • 4 Row

Voltage

C • 115-1-60D • 208-1-60E • 230-1-60F • 277-1-60

H • 5.00J • 6.00L • 8.00N • 10.00Y • No Electric Heat

Y •S •

CoilConnection

None Same End

CoilConstruction

Y • StdS • SS Wrapper

C • Unit Mounted Series 1564 • Wall Series 4039A • Wall Series 155 VerticalB • Wall Series 155 HorizontalP • 24 V Digital Programmable Wall SeriesN • 24 V Digital Non-Programmable Wall Series

Coil Construction

Y • StdS • SS Wrapper

MPY • Modular ConcealedMAY • Modular Concealed (Ditto-A)MBY • Modular Concealed (Ditto-B)MMY • Modular Concealed (Primary)MRY • Modular ReStoraMOD® Concealed MSY • Modular Concealed (Secondary)MXY • Modular Cabinet

Code ItemsUnit Code

MOTOR

05C 2

SIZE

030 4

CONTROLS

07C 4P

COILSw/ELECTRIC HEAT

04aC YA C

VINTAGEUNIT

02Y

01M P

COILS

04Y YA Y

ARRANGEMENT

06A 1

Page 12: Modular Hi-Rise Series - IEC Environmental International€¦ · installations where two units share riser ... Room B Room A MPY MPY Room B ... International Environmental Corporation

International Environmental Corporation • Modular Hi-Rise Series Fan Coil Technical Catalogwww.iec-okc.com12

Modular Hi-Rise SeriesRATINGS AND LISTINGS

C-ETL-US ListingIEC’s Modular Hi-Rise Series units are

listed by ETL. The C-ETL-US listing

signifies that IEC’s fan coil units have

been examined by ETL and are in

compliance with both the U.S. and

Canadian applicable standards.

Hydronic Heating – Base Capacity

Rows EWTUnit Coil Size

GPM

0.5 1.0 2.0 3.0 4.0 6.0 8.0

1-Row 160˚F

03 11.3 14.0 15.8 16.5 – – –

04 11.5 14.4 16.3 17.1 – – –

06 – 19.8 23.3 24.7 25.4 – –

08 – 20.1 23.9 25.4 26.2 – –

10 – 25.2 31.1 33.6 34.9 – –

12 – 25.4 31.6 34.1 35.5 – –

2-Row 160˚F

03 15.9 21.0 24.2 – – – –

04 16.2 21.8 25.6 27.0 – – –

06 – 27.2 35.5 37.4 39.0 – –

08 – 28.0 36.1 39.5 41.1 – –

10 – 33.2 45.5 50.8 53.8 56.9 –

12 – 33.7 46.6 52.5 55.8 59.3 61.2

3-Row 140˚F

03 14.3 20.0 23.5 24.8 – – –

04 14.6 20.8 25.0 26.5 – – –

06 – 25.1 32.9 36.0 37.7 – –

08 – 25.7 34.6 38.3 40.3 – –

10 – – 41.7 47.8 51.1 54.6 –

12 – – 42.9 49.7 53.5 57.7 –

4-Row 140˚F

03 – 21.0 25.1 – – – –

04 – 22.0 27.1 28.9 – – –

06 – 27.6 36.9 40.4 42.1 – –

08 – 28.4 39.3 43.7 46.0 – –

10 – – – 53.1 57.1 61.2 63.3

12 – – – 55.7 60.5 65.5 68.1

NOTES: 1. All base hot water capacities are given in thousands of BTUH (MBH).

2. Ratings are based on nominal CFM at 70°F EAT and 160°F EWT.

3. For information regarding performance at specific conditions, please use the IEC rating program or consult your IEC representative for assistance.

AHRI CertificationIEC’s Modular Hi-Rise Series units

are certified in compliance with

Air-Conditioning, Heating, and

Refrigeration Institute (AHRI) industry standard AHRI-440 for

room fan coil units. Approved standard ratings are tabulated

below.

Standard Ratings

Unit Type

Unit Coil Size

Nominal CFM

Cooling Capacity Water Power Input Watts

PSCTotal MBH

Sensible MBH

Flow Rate

(GPM)

WPD (ft.

wg.)

MAY MBY MMY MPYMRYMSYMXY

03-A 300 11.5 7.0 2.7 4.4 85

04-A 400 13.6 9.0 2.8 5.0 115

06-A 600 21.9 14.0 4.1 4.1 135

08-A 800 27.5 17.8 4.4 4.7 250

10-A 1000 37.7 24.5 6.3 11.9 325

12-A 1200 43.1 28.4 6.7 13.4 440

03-B 300 12.2 7.3 3.2 8.6 85

04-B 400 15.6 9.6 3.5 10.0 115

06-B 600 26.0 15.3 5.1 8.3 135

08-B 800 31.4 19.5 5.6 9.9 250

10-B 1000 42.2 25.6 7.5 9.4 325

12-B 1200 46.5 30.5 8.0 10.8 440

NOTES: 1. Ratings are based on 80°F DB and 67°F WB EAT, 45°F EWT, 10°F water temperature rise, high fan speed, motor voltage 115-1-60, and airflow under dry coil conditions.

2. Ratings shown for Ditto, Siamese Ditto and Primary/Secondary configurations are for each unit in the two-unit system.

3. For all application ratings, use IEC’s computer selection program, the quick-selection ratings provided in this catalog, or contact your local IEC representative.

4. For additional information, please consult AHRI’s website at www.ahrinet.org.

3061627HEATING AND COOLING EQUIPMENT

Page 13: Modular Hi-Rise Series - IEC Environmental International€¦ · installations where two units share riser ... Room B Room A MPY MPY Room B ... International Environmental Corporation

International Environmental Corporation • Modular Hi-Rise Series Fan Coil Technical Catalogwww.iec-okc.com

Modular Hi-Rise Series

13

FAN PERFORMANCE CURVES

0

0.05

0.1

0.15

0.2

0.25

0.3

0.35

0.4

0.45

0.5

0 50 100 150 200 250 300 350 400 450 500

ESP

(in.W

.C.)

SCFM

Unit Size 03 - MPY, MRY, MMY, MSY, MAY, MBY

PSC Motor Fan Curve: 3-Row 4-Row ECM Operating Range:

Low

Med

High

NOTE: Supply air grille and return air panel static pressure losses are included in all fan performance curves for all sizes.

0

0.05

0.1

0.15

0.2

0.25

0.3

0.35

0.4

0.45

0.5

0 100 200 300 400 500 600

ESP

(in.W

.C.)

SCFM

Unit Size 04 - MPY, MRY, MMY, MSY, MAY, MBY

PSC Motor Fan Curve: 3-Row 4-Row ECM Operating Range:

Low

Med

High

Page 14: Modular Hi-Rise Series - IEC Environmental International€¦ · installations where two units share riser ... Room B Room A MPY MPY Room B ... International Environmental Corporation

International Environmental Corporation • Modular Hi-Rise Series Fan Coil Technical Catalogwww.iec-okc.com14

Modular Hi-Rise SeriesFAN PERFORMANCE CURVES, Cont’d.

0

0.05

0.1

0.15

0.2

0.25

0.3

0.35

0.4

0.45

0.5

0 100 200 300 400 500 600 700

ESP

(in.W

.C.)

SCFM

Unit Size 06 - MPY, MRY, MMY, MSY, MAY, MBY

PSC Motor Fan Curve: 3-Row 4-Row ECM Operating Range:

Low Med High

0

0.05

0.1

0.15

0.2

0.25

0.3

0.35

0.4

0.45

0.5

0 100 200 300 400 500 600 700 800 900 1000

ESP

(in.W

.C.)

SCFM

Unit Size 08 - MPY, MRY, MMY, MSY, MAY, MBY

PSC Motor Fan Curve: 3-Row 4-Row ECM Operating Range:

Low Med High

Page 15: Modular Hi-Rise Series - IEC Environmental International€¦ · installations where two units share riser ... Room B Room A MPY MPY Room B ... International Environmental Corporation

International Environmental Corporation • Modular Hi-Rise Series Fan Coil Technical Catalogwww.iec-okc.com

Modular Hi-Rise Series

15

0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1

0 100 200 300 400 500 600 700 800 900 1000 1100 1200

ESP

(in.W

.C.)

SCFM

Unit Size 10 - MPY, MRY, MMY, MSY, MAY, MBY

PSC Motor Fan Curve: 3-Row 4-Row ECM Operating Range:

Low Med High

0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1

0 100 200 300 400 500 600 700 800 900 1000 1100 1200 1300

ESP

(in.W

.C.)

SCFM

Unit Size 12 - MPY, MRY, MMY, MSY, MAY, MBY

PSC Motor Fan Curve: 3-Row 4-Row ECM Operating Range:

Low Med High

FAN PERFORMANCE CURVES, Cont’d.

Page 16: Modular Hi-Rise Series - IEC Environmental International€¦ · installations where two units share riser ... Room B Room A MPY MPY Room B ... International Environmental Corporation

International Environmental Corporation • Modular Hi-Rise Series Fan Coil Technical Catalogwww.iec-okc.com16

Modular Hi-Rise SeriesELECTRIC HEATING

Electric heaters are available on IEC Modular Hi-Rise Series

fan coil units for the following applications.

Total Electric HeatTotal electric heat eliminates the requirement for a boiler.

Heating and/or cooling may be available on an individual

basis throughout the year. Two-pipe chilled water is used

for cooling, and the electric heater is used for heating.

Individual room controls can be supplied for either manual

or automatic changeover.

Auxiliary Electric HeatAuxiliary electric heat is ideal for tempering room air

between seasons and during the cooling season when

chilled water is being circulated. Individual room controls

are supplied to provide electric heat only when chilled water

is being circulated. During regular heating season, heating is

provided by hot water being circulated in the system.

ConstructionHeater coils of high-grade resistance wire are supported by

ceramic insulators on plated steel brackets. These heating

elements are located at the discharge area of the motor/

blower. High limit thermal cutouts protect the unit in the

event of airflow loss. There are many special applications

and control sequences for electric heat. For special

applications please consult the factory.

Electric Heater SelectionVoltage kW

Unit Size

03 04 06 08 10 12

120V

1.0 • • • • • •1.5 • • • • • •2.0 • • • • • •3.0 • • • • • •

208V

1.0 • • • • • •1.5 • • • • • •2.0 • • • • • •3.0 • • • • • •4.0 – • • • • •5.0 – – • • • •6.0 – – • • • •8.0 – – – • • •

240V277V

1.0 • • • • • •1.5 • • • • • •2.0 • • • • • •3.0 • • • • • •4.0 – • • • • •5.0 – – • • • •6.0 – – • • • •8.0 – – – • • •

10.0 – – – – • •

Page 17: Modular Hi-Rise Series - IEC Environmental International€¦ · installations where two units share riser ... Room B Room A MPY MPY Room B ... International Environmental Corporation

International Environmental Corporation • Modular Hi-Rise Series Fan Coil Technical Catalogwww.iec-okc.com

Modular Hi-Rise Series

17

MOTOR DATA

Thermal Overload ProtectionAll PSC motors furnished by IEC contain internal thermal overload protection. The overload automatically resets when the

temperature returns to a safe limit.

Underwriters Laboratories Inc. approves the motor and thermal overload combination at locked rotor conditions only.

PSC Motor Performance Data – MPY, MRY, MAY/MBY, MMY/MSY, MXYVoltage Fan Speed

Unit Size 03 04 06 08 10 12Nominal HP 1/30 1/20 1/15 1/5 1/5 1/4

115 60 Hz

1-Phase

HighAmps 0.81 1.25 1.30 2.33 3.30 5.10

Watts 85 115 135 210 325 420

MediumAmps 0.60 0.70 1.00 1.40 2.46 2.80

Watts 60 70 100 145 255 285

LowAmps 0.40 0.50 0.65 1.00 2.00 2.20

Watts 40 50 65 90 190 210

20860 Hz

1-Phase

HighAmps 0.31 0.60 0.70 0.96 1.40 2.20

Watts 122 114 125 185 300 355

MediumAmps 0.35 0.32 0.46 0.77 1.10 1.20

Watts 66 63 95 137 214 235

LowAmps 0.24 0.21 0.35 0.68 0.86 0.80

Watts 42 40 70 122 162 150

23060 Hz

1-Phase

HighAmps 0.31 0.60 0.70 0.96 1.40 2.20

Watts 140 130 140 193 320 405

MediumAmps 0.36 0.33 0.46 0.77 1.10 1.20

Watts 76 72 105 152 245 270

LowAmps 0.25 0.22 0.38 0.69 0.91 0.85

Watts 50 47 85 140 186 180

27760 Hz

1-Phase

HighAmps 0.38 0.40 0.60 0.71 1.20 1.60

Watts 80 115 135 200 325 420

MediumAmps 0.20 0.30 0.40 0.60 1.00 1.17

Watts 60 75 100 160 270 300

LowAmps 0.10 0.20 0.35 0.50 0.75 0.90

Watts 40 50 77 115 180 200

NOTE: Total unit motor Amps and Watts are shown.

Page 18: Modular Hi-Rise Series - IEC Environmental International€¦ · installations where two units share riser ... Room B Room A MPY MPY Room B ... International Environmental Corporation

International Environmental Corporation • Modular Hi-Rise Series Fan Coil Technical Catalogwww.iec-okc.com18

Modular Hi-Rise SeriesSUBMITTAL DATA

MPY – Modular Hi-Rise Concealed with Electric Heat

MPY4-PIPE

OPTION

MOTOR, 3SPEED,PSC,W/QUICKCONNECT

COIL 1/2"(13)O.D. COPPER TUBE

RISER,DRAIN,

( COPPER )

RISER,SUPPLY & RETURN

( COPPER)

CONTROL BOX

SUPPLY AIROPENING(S)

DUCT COLLAR, 1/2"(13)EXTENSION (TYPICAL)

CONTROL OPENING(SURFACE MOUNT STAT)

AIR VENT,MANUAL

RETURN AIROPENING

3"(76) EXPANDEDSECTION OF RISER

FILTER,THROWAWAY,

1"(25), (F&I)

FLEXIBLE DRAINTUBE/P-TRAP

BLOWER

DRAIN PAN

STRIP HEATER(OPTIONAL)

ACCESS PANEL(CONTROL BOX)

HEATER LIMITSWITCH,(F&I) (OPTIONAL)

RISERCHASE,

OPTIONAL

KNOCKOUT(FOR OPTIONAL

REMOTE MOUNTING)

MOLEX CONNECTORFOR FIELD INSTALLED STAT

ELECTRICAL KNOCKOUTS

1/2"(13) ISOLATIONBALL VALVES (F&I)ACOUSTICAL

SERVICE ACCESS

PANEL

SUPPLY & RETURNTOP DUCTCOLLAR, 1" (25)

CL

3(76)

88(2235)

TAILPIECE

5(127)

54(1372)

I

A

B

G

FRI

SER

LEN

GTH

D

1-1/4(32)

H C H

E

63(1600)

R D S

(NOTE 7)

HS D CRHR CS

3-5/8(92)

1(25)

3(76)

3(76)3

(76)3

(76)3-5/8(92)

E

Unit Model

Dimension – Inches (Millimeters)Unit

Weight*Single Supply Double Supply Top SupplyE F G H I

A B A B C DMPY 03 14 (356) 8 (203) 14 (356) 6 (152) 14 (356) 10 (254) 17 (432) 22-3/8 (568) 1-1/2 (38) 1-1/2 (38) 14 (356) 180 (82)MPY 04 14 (356) 12 (305) 14 (356) 6 (152) 14 (356) 10 (254) 17 (432) 22-3/8 (568) 1-1/2 (38) 1-1/2 (38) 14 (356) 225 (102)MPY 06 18 (457) 10 (254) 18 (457) 6 (152) 16 (406) 12 (305) 20 (508) 25-3/8 (645) 1 (25) 2 (51) 18 (457) 240 (109)MPY 08 18 (457) 12 (305) 18 (457) 6 (152) 16 (406) 12 (305) 20 (508) 25-3/8 (645) 1 (25) 2 (51) 18 (457) 260 (118)MPY 10 — — 22 (559) 8 (203) 18 (457) 16 (406) 24 (610) 29-3/8 (746) 1 (25) 3 (76) 22 (559) 280 (127)MPY 12 — — 22 (559) 8 (203) 18 (457) 16 (406) 24 (610) 29-3/8 (746) 1 (25) 3 (76) 22 (559) 305 (138)

NOTES: * Unit weights are approximate (shown in pounds and kg) and are based on dry coils, minimum rows and exclude packaging, valves or other components.

1. Units are fabricated of galvanized steel with a 16 gauge galvanized fan deck. 2. All risers are insulated with 1/2" (13) closed cell insulation. 3. Thermostats shipped loose for field connection. 4. Risers are factory piped to coil with valves as specified. 5. Blower, motor, valves, coil and filter are accessible through the return air opening. 6. Unit and control box are insulated with 1/2" (13) coated glass-fiber insulation. 7. Riser length = {floor to floor +2" (51)}. Maximum riser length is 115" (2921). Consult project submittal for riser specifications. 8. Maximum riser size is 2-1/2" (64) diameter. If larger sizes are required, please consult the factory. 9. Expansion loops in hot water heating circuits as required. 10. A 9"x2-1/4" (229x57) slot is provided in the inside back panel for coil connection penetration to permit expansion and contraction of

risers. Care must be taken to position the risers so that coil connection is at center of slot. 11. This drawing is pictorial. (See unit arrangements for actual supply and return air orientation.) 12. Dimensions are in inches, dimensions in ( ) are in millimeters.

Drawing is provided for reference only. Dimensions may vary with options ordered. Consult IEC website for submittal drawings.

Page 19: Modular Hi-Rise Series - IEC Environmental International€¦ · installations where two units share riser ... Room B Room A MPY MPY Room B ... International Environmental Corporation

International Environmental Corporation • Modular Hi-Rise Series Fan Coil Technical Catalogwww.iec-okc.com

Modular Hi-Rise Series

19

SUBMITTAL DATA, Cont’d.

MRY – ReStoraMOD® 86 Inch Concealed Hi-Rise with Optional Electric Heat

COIL 1/2"(13)O.D. COPPER

TUBE

CONTROL BOX

SUPPLY AIR OPENING(S)

CONTROL OPENING (SURFACE MOUNT STAT)

RETURN AIR

OPENINGFILTER,

THROWAWAY, 1"(25), (F&I)

FLEXIBLE DRAIN

TUBE/P-TRAP

BLOWER

DRAIN PAN

STRIP HEATER (OPTIONAL)

ACCESS PANEL (CONTROL BOX)

HEATERLIMIT SWITCH, (F&I) (OPTIONAL)

KNOCKOUT (FOR

OPTIONAL REMOTE

MOUNTING)/SIDE

MOLEX CONNECTOR FOR FIELD

INSTALLED STAT

ACOUSTICAL SERVICE ACCESS PANEL

OPTIONALFLOAT SW

RA PNL ASSY MRY(03-04-06-08-10-12)

86(2184)

HE

B

D

1-1/4(32)

E

63(1600)

1 (25)

G C G

60(1524)

JI

A

Unit Model

Dimension – Inches (Millimeters)Unit

Weight*Single Supply Top SupplyE G H I J

A B SIZE C DMRY 03 14 (356) 8 (203) 14x8 14 (356) 10 (254) 16 (406) 1 (25) 14 (356) 1 (25) 21 (534) 180 (82)MRY 04 14 (356) 12 (305) 14x12 14 (356) 10 (254) 16 (406) 1 (25) 14 (356) 1 (25) 21 (534) 225 (102)MRY 06 18 (457) 10 (254) 18x10 16 (406) 12 (305) 19 (432) 1-1/2 (38) 18 (457) 1 (25) 24 (610) 240 (109)MRY 08 18 (457) 12 (305) 18x12 16 (406) 12 (305) 19 (432) 1-1/2 (38) 18 (457) 1 (25) 24 (610) 260 (118)MRY 10 22 (559) 16 (406) 22x16 18 (457) 16 (406) 23 (584) 2-1/2 (64) 22 (559) 1 (25) 28 (711) 280 (127)MRY 12 22 (559) 16 (406) 22x16 18 (457) 16 (406) 23 (584) 2-1/2 (64) 22 (559) 1 (25) 28 (711) 305 (138)

NOTES: * Unit weights are approximate (shown in pounds and kg) and are based on dry coils, minimum rows and exclude packaging, valves or other components.

1. Units are fabricated of galvanized steel with a 16 gauge galvanized fan deck. 2. Thermostats shipped loose for field connection. 3. Blower, motor, valves, coil and filter are accessible through the return air opening. 4. Unit and control box are insulated with 1/2” (13) coated glass-fiber insulation. 5. Hoses ship with unit but are not shown. 6. Threaded fittings must be field tightened and tested. 7. Unit designed for 39” riser stub out height. Contact factory for alternate heights. 8. Return air panel not shown. 9. Dimensions are in inches, dimensions in ( ) are in millimeters.

Drawing is provided for reference only. Dimensions may vary with options ordered. Consult IEC website for submittal drawings.

Page 20: Modular Hi-Rise Series - IEC Environmental International€¦ · installations where two units share riser ... Room B Room A MPY MPY Room B ... International Environmental Corporation

International Environmental Corporation • Modular Hi-Rise Series Fan Coil Technical Catalogwww.iec-okc.com20

Modular Hi-Rise SeriesSUBMITTAL DATA, Cont’d.

MRY – ReStoraMOD® 66 Inch Concealed Hi-Rise with Optional Electric Heat

MOTOR, W/QUICK CONNECT

COIL 1/2"(13) O.D. COPPER

TUBE

CONTROL BOX

SUPPLY AIR OPENING

CONTROL OPENING (SURFACE MOUNT STAT)

RETURN AIR OPENING

FILTER, THROWAWAY,

1"(25), (F&I)

FLEXIBLE DRAIN TUBE/P-TRAP

BLOWER

DRAIN PAN

STRIPHEATER (OPTIONAL)ACCESS PANEL

(CONTROL BOX)

HEATER LIMIT SWITCH, (F&I) (OPTIONAL)

KNOCKOUT (FOR

OPTIONAL REMOTE

MOUNTING)/SIDE

MOLEX CONNECTOR FOR FIELD

INSTALLED STAT

ACOUSTICAL SERVICE ACCESS PANEL

OPTIONAL FLOAT SW

RA PNL ASSY MRY (03-04-06-08-10-12)

66(1676)

FC

B

1-1/4(32)

C

63(1600)

E A E

60(1524)

HG

Unit ModelDimension – Inches (Millimeters)

Unit Weight*Top SupplyC E F G H

A B SIZEMRY 03 14 (356) 10 (254) 14x10 16 (406) 17 (432) 14 (356) 1 (25) 21 (534) 360 (163)MRY 04 14 (356) 10 (254) 14x10 16 (406) 17 (432) 14 (356) 1 (25) 21 (534) 450 (204)MRY 06 16 (406) 12 (305) 16x12 19 (483) 20 (508) 18 (457) 1 (25) 24 (610) 480 (217)MRY 08 16 (406) 12 (305) 16x12 19 (483) 20 (508) 18 (457) 1 (25) 24 (610) 520 (236)MRY 10 18 (457) 16 (406) 18x16 23 (584) 24 (610) 22 (559) 1 (25) 28 (711) 560 (254)MRY 12 18 (457) 16 (406) 18x16 23 (584) 24 (610) 22 (559) 1 (25) 28 (711) 610 (276)

NOTES: * Unit weights are approximate (shown in pounds and kg) and are based on dry coils, minimum rows and exclude packaging, valves or other components.

1. Units are fabricated of galvanized steel with a 16 gauge galvanized fan deck. 2. Thermostats shipped loose for field connection. 3. Blower, motor, valves, coil and filter are accessible through the return air opening. 4. Unit and control box are insulated with 1/2” (13) coated glass-fiber insulation. 5. Hoses ship with unit but are not shown. 6. Threaded fittings must be field tightened and tested. 7. Unit designed for 39” riser stub out height. Contact factory for alternate heights. 8. Return air panel not shown. 9. Dimensions are in inches, dimensions in ( ) are in millimeters.

Drawing is provided for reference only. Dimensions may vary with options ordered. Consult IEC website for submittal drawings.

Page 21: Modular Hi-Rise Series - IEC Environmental International€¦ · installations where two units share riser ... Room B Room A MPY MPY Room B ... International Environmental Corporation

International Environmental Corporation • Modular Hi-Rise Series Fan Coil Technical Catalogwww.iec-okc.com

Modular Hi-Rise Series

21

SUBMITTAL DATA, Cont’d.

MAY/MBY – Ditto (Chase Concealed) with Electric Heat

RISER, DRAIN,

( COPPER )

MOTOR, 3 SPEED, PSC, W/ QUICK CONNECT

RISER, SUPPLY &

RETURN ( COPPER)

DUCT COLLAR, 1/2"(13)

EXTENSION (TYPICAL)

CONTROL OPENING

(SURFACE MOUNTED STAT)

FLEXIBLE DRAIN TUBE/P-TRAP

FILTER, THROWAWAY,

1"(25), (F&I)

ACCESS PANEL(CONTROL BOX) KNOCKOUT

(FOR OPTIONAL REMOTE

MOUNTING)/SIDE

MOLEX CONNECTOR

FOR FIELD INSTALLED STAT

GYPSUM BOARD, 5/8"(16) TYPE "X"

HEATER LIMIT SWITCH, (F&I) (OPTIONAL)

STRIP HEATER, (F&I) (OPTIONAL)

63(1600)

54(1372)

IE

RISE

R LE

NG

TH

ELECTRICAL KNOCKOUTS

ETHERMAFIBER INSULATION

DRAIN PAN

BLOWER

CONTROL BOX

SUPPLY AIR OPENING(S)

3"(76) EXPANDEDSECTION OF RISER

AIR VENT, MANUAL

RETURN AIR OPENING

COIL 1/2"(13) O.D. COPPER TUBE

3(76) 3

(76)

LC

SDR

3(76)

88(2235)

TAILPIECE

J

OPTION4-PIPE

3-5/8 (92)

MAY MBYMAY

HRHS

CRCS

D

(NOTE 7)

1/2"(13) ISOLATIONBALL VALVES (F&I)ACOUSTICAL

SERVICE ACCESS PANEL

3 (76)3 (76)

G A1(25)

B

H

H

C

D 1-1/4(32)

SUPPLY & RETURNTOP DUCT COLLAR, 1"(25)

5(127)

3-5/8 (92)

Unit ModelDimension – Inches (Millimeters)

Unit Weight*Single Supply Double Supply Top Supply

E G H I JA B A B C D

MAY/MBY 03 14 (356) 8 (203) 14 (356) 6 (152) 14 (356) 10 (254) 17 (432) 1-1/2 (38) 1-1/2 (38) 14 (356) 39-5/8 (1007) 360 (163)MAY/MBY 04 14 (356) 12 (305) 14 (356) 6 (152) 14 (356) 10 (254) 17 (432) 1-1/2 (38) 1-1/2 (38) 14 (356) 39-5/8 (1007) 450 (204)MAY/MBY 06 18 (457) 10 (254) 18 (457) 6 (152) 16 (406) 12 (305) 20 (508) 1 (25) 2 (51) 18 (457) 45-5/8 (1159) 480 (217)MAY/MBY 08 18 (457) 12 (305) 18 (457) 6 (152) 16 (406) 12 (305) 20 (508) 1 (25) 2 (51) 18 (457) 45-5/8 (1159) 520 (236)MAY/MBY 10 — — 22 (559) 8 (203) 18 (457) 16 (406) 24 (610) 1 (25) 3 (76) 22 (559) 53-5/8 (1362) 560 (254)MAY/MBY 12 — — 22 (559) 8 (203) 18 (457) 16 (406) 24 (610) 1 (25) 3 (76) 22 (559) 53-5/8 (1362) 610 (276)

NOTES: * Unit weights are approximate (shown in pounds and kg) and are based on dry coils, minimum rows and exclude packaging, valves or other components.

1. Units are fabricated of galvanized steel with a 16 gauge galvanized fan deck. 2. All risers are insulated with 1/2" (13) closed cell insulation. 3. Thermostats shipped loose for field connection. 4. Risers are factory piped to coil with valves as specified. 5. Blower, motor, valves, coil and filter are accessible through the return air opening. 6. Unit and control box are insulated with 1/2" (13) coated glass-fiber insulation. 7. Riser length = {floor to floor +2" (51)}. Maximum riser length is 115" (2921). Consult project submittal for riser specifications. 8. Maximum riser size is 2-1/2" (64) diameter. If larger sizes are required, please consult the factory. 9. Expansion loops in hot water heating circuits as required. 10. A 9"x2-1/4" (229x57) slot is provided in the inside back panel for coil connection penetration to permit expansion and contraction of

risers. Care must be taken to position the risers so that coil connection is at center of slot. 11. This drawing is pictorial. (See unit arrangements for actual supply and return air orientation.) 12. Dimensions are in inches, dimensions in ( ) are in millimeters.

Drawing is provided for reference only. Dimensions may vary with options ordered. Consult IEC website for submittal drawings.

Page 22: Modular Hi-Rise Series - IEC Environmental International€¦ · installations where two units share riser ... Room B Room A MPY MPY Room B ... International Environmental Corporation

International Environmental Corporation • Modular Hi-Rise Series Fan Coil Technical Catalogwww.iec-okc.com22

Modular Hi-Rise SeriesSUBMITTAL DATA, Cont’d.

MMY – Modular Hi-Rise Concealed Primary with Electric Heat

3(76)

54(1372)

IE

A

B

G

RISE

R LE

NG

TH

D

1-1/4(32)

H C H

E

63(1600)

R D S

CL

88(2235)

TAILPIECE

(NOTE 7)

39

3(76)

HR

OPTION4-PIPEMMY

3(76)

HS D CSCR

3-5/8(92)

3-5/8(92)

(991)

AIR VENT, MANUAL

BLOWER

DRAIN PAN

CL

5(127)

5(127)

1(25)

3(76)

3(76)

CONTROL BOX

MOTOR, 3 SPEED, PSC, W/ QUICK CONNECT

COIL 1/2"(13) O.D.COPPER TUBE

RISER, DRAIN, ( COPPER )

RISER, SUPPLY & RETURN ( COPPER)

SUPPLY AIR OPENING(S)

DUCT COLLAR,1/2"(13) EXTENSION

(TYPICAL)

CONTROL OPENING

(SURFACE MOUNT STAT)

RETURN AIR OPENING

3"(76) EXPANDEDSECTION OF RISER

FILTER, THROWAWAY,

1"(25), (F&I)

FLEXIBLE DRAIN

TUBE/P-TRAP

STRIP HEATER (OPTIONAL)

ACCESS PANEL (CONTROL BOX)

HEATER LIMIT SWITCH, (F&I) (OPTIONAL)

KNOCKOUT(FOR OPTIONAL

REMOTEMOUNTING)/SIDE

MOLEX CONNECTOR

FOR FIELD INSTALLED STAT

ELECTRICALKNOCKOUTS

1/2"(13) ISOLATION BALL VALVES (F&I)

ACOUSTICAL SERVICE ACCESS

PANEL

SUPPLY & RETURNTOP DUCT COLLAR, 1" (25)

Unit Model

Dimension – Inches (Millimeters)Unit

Weight*Single Supply Double Supply Top SupplyA B A B C D E G H I

MMY 03 14 (356) 8 (203) 14 (356) 6 (152) 14 (356) 10 (254) 17 (432) 1-1/2 (38) 1-1/2 (38) 14 (356) 180 (82)MMY 04 14 (356) 12 (305) 14 (356) 6 (152) 14 (356) 10 (254) 17 (432) 1-1/2 (38) 1-1/2 (38) 14 (356) 225 (102)MMY 06 18 (457) 10 (254) 18 (457) 6 (152) 16 (406) 12 (305) 20 (508) 1 (25) 2 (51) 18 (457) 240 (109)MMY 08 18 (457) 12 (305) 18 (457) 6 (152) 16 (406) 12 (305) 20 (508) 1 (25) 2 (51) 18 (457) 260 (118)MMY 10 — — 22 (559) 8 (203) 18 (457) 16 (406) 24 (610) 1 (25) 3 (76) 22 (559) 280 (127)MMY 12 — — 22 (559) 8 (203) 18 (457) 16 (406) 24 (610) 1 (25) 3 (76) 22 (559) 305 (138)

NOTES: * Unit weights are approximate (shown in pounds and kg) and are based on dry coils, minimum rows and exclude packaging, valves or other components.

1. Units are fabricated of galvanized steel with a 16 gauge galvanized fan deck. 2. All risers are insulated with 1/2" (13) closed cell insulation. 3. Thermostats shipped loose for field connection. 4. Risers are factory piped to coil with valves as specified. 5. Blower, motor, valves, coil and filter are accessible through the return air opening. 6. Unit and control box are insulated with 1/2" (13) coated glass-fiber insulation. 7. Riser length = {floor to floor +2" (51)}. Maximum riser length is 115" (2921). Consult project submittal for riser specifications. 8. Maximum riser size is 2-1/2" (64) diameter. If larger sizes are required, please consult the factory. 9. Expansion loops in hot water heating circuits as required. 10. A 9"x2-1/4" (229x57) slot is provided in the inside back panel for coil connection penetration to permit expansion and contraction of

risers. Care must be taken to position the risers so that coil connection is at center of slot. 11. This drawing is pictorial. (See unit arrangements for actual supply and return air orientation.) 12. Dimensions are in inches, dimensions in ( ) are in millimeters.

Drawing is provided for reference only. Dimensions may vary with options ordered. Consult IEC website for submittal drawings.

Page 23: Modular Hi-Rise Series - IEC Environmental International€¦ · installations where two units share riser ... Room B Room A MPY MPY Room B ... International Environmental Corporation

International Environmental Corporation • Modular Hi-Rise Series Fan Coil Technical Catalogwww.iec-okc.com

Modular Hi-Rise Series

23

SUBMITTAL DATA, Cont’d.

MSY – Modular Hi-Rise Concealed Secondary with Electric Heat

63(1600)

G

B

54(1372)

5(127)E

I

HCH

3(76)

3(76)

L

DS

C

1-1/4(32)

D

R

SHIPPING BRACE

ELECTRICAL KNOCKOUTS

MOLEX CONNECTOR FOR FIELD

INSTALLED STATKNOCKOUT

(FOR OPTIONAL REMOTE

MOUNTING)/SIDE

HEATER LIMIT SWITCH, (F&I) (OPTIONAL)

ACCESS PANEL(CONTROL BOX)

STRIP HEATER (OPTIONAL)

FLEXIBLE DRAIN TUBE/P-TRAP

FILTER, THROWAWAY, 1"(25), (F&I)

RETURN AIR OPENING

AIR VENT, MANUAL

CONTROL OPENING (SURFACE MOUNT STAT)

DUCT COLLAR, 1/2"(13) EXTENSION

SUPPLY AIR OPENING(S)

CONTROL BOX

COIL 1/2"(13) O.D. COPPER TUBE

MOTOR,3 SPEED, PSC, W/QUICK CONNECT

E

39

DRAIN PAN

BLOWER

A

3(76)

CS

OPTION4-PIPEMSY

3(76)

CR D HRHS

3-5/8(92)

3-5/8(92)

1/2"(13) ISOLATION BALL VALVES (F&I)

88

ACOUSTICAL SERVICE ACCESS

PANEL

SUPPLY AND RETURN TOP DUCT COLLAR, 1"(25)

(2235)

(991)

5(127)

LC

1(25)

Unit Model

Dimension – Inches (Millimeters)Unit

Weight*Single Supply Double Supply Top SupplyA B A B C D E G H I

MSY 03 14 (356) 8 (203) 14 (356) 6 (152) 14 (356) 10 (254) 17 (432) 1-1/2 (38) 1-1/2 (38) 14 (356) 162 (73)MSY 04 14 (356) 12 (305) 14 (356) 6 (152) 14 (356) 10 (254) 17 (432) 1-1/2 (38) 1-1/2 (38) 14 (356) 203 (92)MSY 06 18 (457) 10 (254) 18 (457) 6 (152) 16 (406) 12 (305) 20 (508) 1 (25) 2 (51) 18 (457) 216 (98)MSY 08 18 (457) 12 (305) 18 (457) 6 (152) 16 (406) 12 (305) 20 (508) 1 (25) 2 (51) 18 (457) 234 (106)MSY 10 — — 22 (559) 8 (203) 18 (457) 16 (406) 24 (610) 1 (25) 3 (76) 22 (559) 252 (114)MSY 12 — — 22 (559) 8 (203) 18 (457) 16 (406) 24 (610) 1 (25) 3 (76) 22 (559) 275 (125)

NOTES: * Unit weights are approximate (shown in pounds and kg) and are based on dry coils, minimum rows and exclude packaging, valves or other components.

1. Units are fabricated of galvanized steel with a 16 gauge galvanized fan deck. 2. Thermostats shipped loose for field connection. 3. Coil with valves as specified. 4. Blower, motor, valves, coil and filter are accessible through the return air opening. 5. Unit and control box are insulated with 1/2" (13) coated glass-fiber insulation. 6. Expansion loops in hot water heating circuits as required. 7. A 9"x2-1/4" (229x57) slot is provided in the inside back panel for coil connection penetration to permit expansion and contraction of

risers. Care must be taken to position the risers so that coil connection is at center of slot. 8. This drawing is pictorial. (See unit arrangements for actual supply and return air orientation.) 9. Dimensions are in inches, dimensions in ( ) are in millimeters.

Drawing is provided for reference only. Dimensions may vary with options ordered. Consult IEC website for submittal drawings.

Page 24: Modular Hi-Rise Series - IEC Environmental International€¦ · installations where two units share riser ... Room B Room A MPY MPY Room B ... International Environmental Corporation

International Environmental Corporation • Modular Hi-Rise Series Fan Coil Technical Catalogwww.iec-okc.com24

Modular Hi-Rise SeriesSUBMITTAL DATA, Cont’d.

MXY – Modular Hi-Rise Cabinet with Electric Heat

DWG. IS PICTORALSEE UNIT ARRGMTS.

FOR ACTUAL

MXY4-PIPE

OPTION

HR HS D CSCR R D S

RISER, SUPPLY& RETURN,

(TYPE "M" COPPER)

D.D. STEELCORE GRILLE

ASSY

3"(76) EXPANSIONSECTION OF RISER

HINGEDCONTROL

ACCESS DOOR

FILTER,T.A, 1"(25),

(F&I)

FLEXIBLE DRAINTUBE/P-TRAP

RETURNAIR PANEL

STRIP HEATER(OPTIONAL)

ELECTRICALACCESS PANEL

HEATER LIMITSWITCH, (F&I)(OPTIONAL)

ELECTRICALKNOCKOUTS

BLOWER

DRAIN PAN

AIR VENT,MANUAL

T'STAT

MOTOR,3 SPEED,PSC SERIES 'L'

RISER, DRAIN,(TYPE "M" COPPER)

COIL 1/2"(13)O.D. TUBE

CONTROL BOXCABINETCAMLOCKS

1/2"(13) ISOLATIONBALL VALVES (F&I)

CL

D

C

CG

F

E A

B

CL

88(2235)

3(76)

TAILPIECE

(NOTE 7)

RISE

R LE

NG

TH

3(76)

3-5/8(92)

5(127)

3(76)

3(76)

3(76)

3-5/8(92)

Unit ModelDimension – Inches (Millimeters)

Unit Weight*Single Supply Double Supply

C D E F GA B A B

MXY 03 14 (356) 8 (203) 14 (356) 6 (152) 17 (432) 22-3/8 (568) 2-1/2 (64) 22-1/8(568) 14-3/4 (375) 202 (92)MXY 04 14 (356) 12 (305) 14 (356) 8 (203) 17 (432) 22-3/8 (568) 2-1/2 (64) 22-1/8(568) 14-3/4 (375) 247 (112)MXY 06 14 (356) 12 (305) 14 (356) 8 (203) 20 (508) 25-3/8 (645) 2-1/2 (64) 26-5/8(676) 17-3/4 (451) 262 (119)MXY 08 14 (356) 16 (406) 14 (356) 10 (254) 20 (508) 25-3/8 (645) 2-1/2 (64) 26-5/8(676) 17-3/4 (451) 286 (130)MXY 10 18 (457) 16 (406) 14 (356) 12 (305) 24 (610) 29-3/8 (747) 2-1/2 (64) 31-1/8(791) 17-3/4 (451) 311 (141)MXY 12 18 (457) 16 (406) 14 (356) 12 (305) 24 (610) 29-3/8 (747) 2-1/2 (64) 31-1/8(791) 17-3/4 (451) 336 (152)

NOTES: * Unit weights are approximate (shown in pounds and kg) and are based on dry coils, minimum rows and exclude packaging, valves or other components.

1. Units are fabricated of galvanized steel with a 16 gauge galvanized fan deck. 2. All risers are insulated with 1/2” (13) closed cell insulation. 3. Thermostats shipped loose for field connection. 4. Risers are factory piped to coil with valves as specified. 5. Blower, motor, valves, coil and filter are accessible through the return air opening. 6. Unit and control box are insulated with 1/2" (13) coated glass-fiber insulation. 7. Riser length = {floor to floor +2" (51)}. Maximum riser length is 115" (2921). Consult project submittal for riser specifications. 8. Maximum riser size is 2-1/2" (64) diameter. If larger sizes are required, please consult the factory. 9. Expansion loops in hot water heating circuits as required. 10. A 9"x2-1/4" (229x57) slot is provided in the inside back panel for coil connection penetration to permit expansion and contraction of

risers. Care must be taken to position the risers so that coil connection is at center of slot. 11. This drawing is pictorial. (See unit arrangements for actual supply and return air orientation.) 12. Dimensions are in inches, dimensions in ( ) are in millimeters.

Drawing is provided for reference only. Dimensions may vary with options ordered. Consult IEC website for submittal drawings.

Page 25: Modular Hi-Rise Series - IEC Environmental International€¦ · installations where two units share riser ... Room B Room A MPY MPY Room B ... International Environmental Corporation

International Environmental Corporation • Modular Hi-Rise Series Fan Coil Technical Catalogwww.iec-okc.com

Modular Hi-Rise Series

25

STANDARD FEATURES AND OPTIONS

Features and Options StandardFactory

Installed Option

Field Installed Option

Factory Special Quote

Air Flow ArrangementSee Unit Configuration XCoils3-Rows 2-Pipe (MPY, MRY, MXY, MMY/MSY, MAY/MBY) X4-Rows 2-Pipe (MPY, MRY, MXY, MMY/MSY, MAY/MBY) X3/1, 3/2, or 4/1-Rows CW/HW (MPY, MRY, MXY, MMY/MSY, MAY/MBY) XManual Air Vent XAutomatic Air Vent XDrain PanGalvanized Internally Coated with a 2 part closed cell foam XStainless Steel Externally Coated with a 2 part closed cell foam XFin MaterialAluminum w/Galvanized End Sheets XCopper w/Stainless End Sheets & Bottom Coil Baffle X XNickrome Wire Strip Electric Heater XFilters1" Throwaway non-woven synthetic X1" Permanent (washable media or aluminum mesh) X X1" MERV 8 Pleated XInsulation1/2" Standard Fiberglass X1/2" Premium IAQ Fiberglass, sealed edges X X1/2" Foil Face, taped edges X1/4" Closed Cell X1 Hour Fire Rated Riser Chase (MAY/MBY) XMotor TypeStandard 3-Speed PSC Motors w/Quick connect Plug XHi Static 3-Speed PSC Motors w/Quick-connect Plug X XMotor Voltage120/1/60 3-Speed X208/230/277/1/60 3-Speed XSupply GrillesIntegral Double Deflection Aluminum Supply Grille (MXY) XDouble Deflection, Aluminum Supply Grille XDouble Deflection, Aluminum Supply Grille w/Opposed Blade Dampers XCustom Supply Grille X XReturn Air PanelLouvered Front Panel (MXY) X (M)Standard Height with or without Frame (All except MXY) X (F) X (F, H)Extended Height with or without Frame (All except MXY) X (G, J)Extended Height with or without Control Door (All except MXY) X (K, L)Custom Return Air Panel X XCabinet ModificationsStandard Height is 88", 79" Optional X (88") X (79") XMRY - Standard height is 86", 66" Optional X (86") X (66")Custom Options X XCustom Colors X X

Page 26: Modular Hi-Rise Series - IEC Environmental International€¦ · installations where two units share riser ... Room B Room A MPY MPY Room B ... International Environmental Corporation

International Environmental Corporation • Modular Hi-Rise Series Fan Coil Technical Catalogwww.iec-okc.com26

Modular Hi-Rise SeriesSTANDARD FEATURES AND OPTIONS, Cont’d.

Features and Options StandardFactory

Installed Option

Field Installed Option

Factory Special Quote

RisersRiser Factory Installed XRisers Shipped Loose X XFlex Hoses X X XRiser Length (to 115") X X (>115")Riser Diameter (3/4" to 2-1/2") X X (>2-1/2")Closed Cell Riser Insulation1/2" X X3/4" XFiberglass Riser Insulation1/2" X X1" X XRiser/Drain MaterialType M Copper X X XType L Copper X XRiser Extension (M or L) XControlsService Switch with Lockout Tabs XSingle Point Power Connection XIncoming Power Fusing X24 V Controls XCondensate Overflow Switch XThermostats X X Surface Mounted w/Tile Ring X Unit Mounted X Wall/Remote Mounted XSpecial Control (DDC) X XOutside Air DampersManual Controlled Damper XMotorized Controlled Damper X X

Page 27: Modular Hi-Rise Series - IEC Environmental International€¦ · installations where two units share riser ... Room B Room A MPY MPY Room B ... International Environmental Corporation

International Environmental Corporation • Modular Hi-Rise Series Fan Coil Technical Catalogwww.iec-okc.com

Modular Hi-Rise Series

27

STANDARD FEATURES AND OPTIONS, Cont’d.

As detailed in the table below, we offer a control for most of our customer’s needs. Additional controls and devices are available to meet even the most demanding operating logic.

3-speed Fan ControlAll of our basic control schemes utilize a 3-speed switch to modulate the cooling output, to maximize the percentage of latent heat removal, and to further minimize the sound level when maximum cooling or heating performance is not required.

Low Voltage Control (24 V)An optional low voltage control is available with all of our control schemes.

Condensate Overflow SwitchThis optional switch shuts down the unit when the water level in the drain pan reaches an unsafe level. Building code changes in much of our country may require this type of device.

Service SwitchesWe offer optional service switches for use by maintenance and service personnel.

FusingWe offer optional incoming power fusing as well as blower motor and control sub-fusing for units that use electric heat.

ThermostatsThermostats System Function Mode Control Type*

C 4 A B P N

BasicControl Needs

2-Pipe Heat Only ACO X X X X X X2-Pipe Cool Only ACO X X X X X X

2-Pipe Heat/Cool ACO X X X X X XMCO N/A X X X X X

2-Pipe Heat/Cool with Auxiliary Electric Heat

ACO X X X X X XMCO N/A X X X X X

2-Pipe Heat/Cool with Total Electric Heat ACO X X X X X XMCO N/A X X X X X

4-Pipe Heat/Cool ACO X X X X X XMCO N/A X X X X X

ThermostatFeatures

All listed controls include

fan switching.

24 Volts X X X X X XProgrammable N/A N/A N/A N/A X N/A

Non-Programmable X X X X N/A XSurface Mounted N/A X X X X X

Remote Wall Mounted N/A X X X X X3-Speed Fan X X X X X X

Continuous Fan X X X X X XCycling Fan X N/A N/A N/A X X

Remote Temperature Sensor N/A N/A Opt Opt X XAdjustable Operating Range (Range Stop Kit) Kit Kit Kit Kit X X

Touch Pad/Digital Display N/A N/A N/A N/A X XLocal Temperature Set-Back N/A N/A N/A N/A X X

Water Temperature Purge Cycle N/A N/A N/A N/A X XPipe Sensor N/A N/A N/A N/A X X

* Control Type Legend:C Unit Mounted Series 1564 Wall Series 4039A Wall Series 155 VerticalB Wall Series 155 HorizontalP 24 V Digital Programmable Wall SeriesN 24 V Digital Non-Programmable Wall Series

Page 28: Modular Hi-Rise Series - IEC Environmental International€¦ · installations where two units share riser ... Room B Room A MPY MPY Room B ... International Environmental Corporation

International Environmental Corporation • Modular Hi-Rise Series Fan Coil Technical Catalogwww.iec-okc.com28

Modular Hi-Rise SeriesSTANDARD FEATURES AND OPTIONS, Cont’d.

Return Air Panels

H

W

F

W

H

W

G

W

LK

W

J

W

NOTE: See table on next page for height and width information.

Page 29: Modular Hi-Rise Series - IEC Environmental International€¦ · installations where two units share riser ... Room B Room A MPY MPY Room B ... International Environmental Corporation

International Environmental Corporation • Modular Hi-Rise Series Fan Coil Technical Catalogwww.iec-okc.com

Modular Hi-Rise Series

29

STANDARD FEATURES AND OPTIONS, Cont’d.

Panel Type

Unit Size and Dimensions1

03/04 06/08 10/12H W H W H W

F 55.5 (1410)

15.5 (394)

55.5 (1410)

19.5 (495)

55.5 (1410)

23.5 (597)

G 61.1 (1552)

15.5 (394)

61.1 (1552)

19.5 (495)

61.1 (1552)

23.5 (597)

H 54.7 (1389)

15.1 (384)

54.7 (1389)

19.1 (485)

54.7 (1389)

23.1 (587)

J 60.4 (1534)

15.1 (384)

60.4 (1534)

19.1 (485)

60.4 (1534)

23.1 (587)

K 61.1 (1552)

15.5 (394)

61.1 (1552)

19.5 (495)

61.1 (1552)

23.5 (597)

L 60.4 (1534)

15.1 (384)

60.4 (1534)

19.1 (485)

60.4 (1534)

23.1 (587)

U 88.5 (2248)

21.0 (534)

88.5 (2248)

24.0 (610)

88.5 (2248)

28.0 (711)

V 68.5 (1740)

21.0 (534)

68.5 (1740)

24.0 (610)

68.5 (1740)

28.0 (711)

NOTE: Dimensions shown in inches and millimeters {inches(mm)}.

General Specifications:• Heavy gauge galvanized steel with arctic white powder-

coat finish• Rear of panel is insulated with 1/2" dual density fiberglass• Integral stamped steel return air grille• 1/4 turn tamper-proof fasteners for panel removal• Removal of panel provides service access to all internal

components• Framed panel series requires separate field installation of

frame

Return Air/Access Panel ApplicationControl Mounting Options Panel

1. Surface mounted controls: This requires a a tile ring mounted above the return air panel and quick-connect plug wiring on the thermostat. After the drywall/sheetrock has been applied to the cabinet, the thermostat plug will be attached to a matching plug in the unit and the thermostat will be fastened to the tile ring. (Not available for MXY models)

F, H, R, S, V

2. Unit mounted: Thermostat is mounted behind the control door or the return air panel. G, J, K, L, U

3. Remote wall mounted: Thermostat is mounted on a wall remote from the cabinet and wiring from the unit to thermostat is done in the field.

F, H, K, L, R, S, V

4. Other Considerations: All above (#1, 2, & 3) are for drywall attached directly to the cabinet. (Not available for MXY models).

F, H, J, L, R, S, V

W

H

W

VU

Page 30: Modular Hi-Rise Series - IEC Environmental International€¦ · installations where two units share riser ... Room B Room A MPY MPY Room B ... International Environmental Corporation

International Environmental Corporation • Modular Hi-Rise Series Fan Coil Technical Catalogwww.iec-okc.com30

Modular Hi-Rise SeriesSTANDARD FEATURES AND OPTIONS, Cont’d.

Supply Air Grilles

NOTE: Classic style supply air grille shown.

Unit Size

Nominal CFM

Recommended Grille Sizes

Single Supply* Double Supply Top Supply

03 300 14 (356) x 8 (203)

14 (356) x 6 (152)

14 (356) x 10 (254)

04 400 14 (356) x 12 (305)

14 (356) x 6 (152)

14 (356) x 10 (254)

06 600 18 (457) x 10 (254)

18 (457) x 6 (152)

16 (406) x 12 (305)

08 800 18 (457) x 12 (305)

18 (457) x 6 (152)

16 (406) x 12 (305)

10 1000 22 (559) x 16 (406)

22 (559) x 8 (203)

18 (457) x 16 (406)

12 1200 22 (559) x 16 (406)

22 (559) x 8 (203)

18 (457) x 16 (406)

NOTE: Single-side supply units are available with indicated supply openings on 88" tall cabinets only. Consult the factory for cabinets less than 88".

Specifications:Frame and blades are 6063 extruded aluminum alloy with 200-

R1 satin anodized finish. The frame has a typical wall thickness

of .050" and is separated from the blades with injection-molded

nylon bushings. This method of assembly minimizes corrosion

and vibration. The frame mounting holes are dimpled, allowing

for a counter-sunk fastener head appearance.

All blades are airfoil in design, individually adjustable and

spaced 3/4" on center. At the outer edge of the frame is a

Classic Aluminum Return Air/Access Grille

Unit Size and Dimensions¹03/04 06/08 10/12

W 15.2 (386) 19.2 (488) 23.2 (589)H 55.3 (1405) 55.3 (1405) 55.3 (1405)

NOTE: Dimensions shown in inches and millimeters {inches(mm)}.

General Specifications:• Fully louvered core grille is mounted in a full frame.

• Core grille is removable without tools and provides access to all internal components.

• Frame is clear anodized extruded aluminum.

• Grille louvers are also clear anodized extruded aluminum.

• Designed for use with surface mounted or remote wall mounted controls.

• Use with dry wall directly applied to cabinet or with space between dry wall and cabinet.

Type R: Anodized Aluminum

Type S: Arctic White

W

H

Continued on next page.

Page 31: Modular Hi-Rise Series - IEC Environmental International€¦ · installations where two units share riser ... Room B Room A MPY MPY Room B ... International Environmental Corporation

International Environmental Corporation • Modular Hi-Rise Series Fan Coil Technical Catalogwww.iec-okc.com

Modular Hi-Rise Series

31

STANDARD FEATURES AND OPTIONS, Cont’d.

specially engineered channel which retains an extruded

flexible vinyl bulb gasket that produces a positive air seal

at the mounting surface, minimizing smudging.

An optional opposed blade damper is screwdriver-

operated through the face of the unit and has the same

extruded aluminum construction and injection-molded

nylon bushings.

The unit achieves an effective area of 80% with the blades

set at a 0° pattern, thus eliminating high velocity and

pressure drop at the grille face. Wider deflection with

reduced throw may be achieved at the 22° and 45° blade

settings with slightly increased sound levels.

Suitable for sidewall application. Available in clear

anodized, white or a variety of custom colors. Contact the

factory for available optional colors and color chart.

FiltersUnit Size

Nominal 1" Filter Size

MPY, MAY/MBY, MMY/MSY, MXY MRY

03 12-1/2 (316) x 24-1/4 (616) 12-1/2 (316) x 24-1/4 (616)

04 12-1/2 (316) x 24-1/4 (616) 12-1/2 (316) x 24-1/4 (616)

06 16-1/4 (413) x 26-3/4 (679) 15-1/4 (387) x 26-3/4 (679)

08 16-1/4 (413) x 26-3/4 (679) 15-1/4 (387) x 26-3/4 (679)

10 20-1/2 (521) x 29-1/4 (743) 19-1/2 (495) x 29-1/4 (743)

12 20-1/2 (521) x 29-1/4 (743) 19-1/2 (495) x 29-1/4 (743)

NOTE: Sizes shown are nominal ordering sizes.

Page 32: Modular Hi-Rise Series - IEC Environmental International€¦ · installations where two units share riser ... Room B Room A MPY MPY Room B ... International Environmental Corporation

P.O. Box 2598Oklahoma City, OK 73101-2598

p: 405.605.5000f: 405.605.5001

www.iec-okc.com

IEC Catalog Part #: I100-90002105 CA-050 Revision 12

©2002-2016 International Environmental Corporation ReStoraMOD® patent pending