NPR COLLEGE OF ENGINEERING &TECHNOLOGY

BE EEE-III/ SEMESTER VI

EE1354 – MODERN CONTROL SYSTEMS

Prepared By:

A.R.SALINIDEVI Lect/EEE

Page 2: Modern Control System (BE)

2

EE1354 – MODERN CONTROL SYSTEMS

(Common to EEE, EIE and ICE)

L T P C

3 1 0 4

UNIT I STATE SPACE ANALYSIS OF CONTINUOUS TIME SYSTEMS 9

State variable representation – Conversion of state variable form to transfer function and vice

versa – Eigenvalues and Eigenvectors – Solution of state equation – Controllability and

observability –Pole placement design – Design of state observer

UNIT II z-TRANSFORM AND SAMPLED DATA SYSTEMS 9

Sampled data theory – Sampling process – Sampling theorem – Signal reconstruction –

Sample and hold circuits – z-Transform – Theorems on z-Transforms – Inverse z-Transforms

– Discrete systems and solution of difference equation using z transform – Pulse transfer

function – Response of sampled data system to step and ramp Inputs – Stability studies –

Jury’s test and bilinear transformation

UNIT III STATE SPACE ANALYSIS OF DISCRETE TIME SYSTEMS 9

State variables – Canonical forms – Digitalization – Solution of state equations –

Controllability and Observability – Effect of sampling time on controllability – Pole

placement by state feedback – Linear observer design – First order and second order

problems

UNIT IV NONLINEAR SYSTEMS 9

Types of nonlinearity – Typical examples – Phase-plane analysis – Singular points – Limit

cycles – Construction of phase trajectories – Describing function method – Basic concepts –

Dead Zone – Saturation – Relay – Backlash – Liapunov stability analysis – Stability in the

sense of Liapunov – Definiteness of scalar functions – Quadratic forms – Second method of

Liapunov – Liapunov stability analysis of linear time invariant systems and non-linear system

UNIT V MIMO SYSTEMS 9

Models of MIMO system – Matrix representation – Transfer function representation – Poles

and Zeros – Decoupling – Introduction to multivariable Nyquist plot and singular values

analysis – Model predictive control

L: 45 T: 15 Total: 60

TEXT BOOKS

1. Gopal, M., “Digital Control and State Variable Methods”, 3rd Edition, Tata McGraw Hill,

2008.

2. Gopal, M., “Modern Control Engineering”, New Age International, 2005.

REFERENCES

1. Richard C. Dorf and Robert H. Bishop, “Modern Control Systems”, 8th Edition, Pearson

Education, 2004.

2. Gopal, M., “Control Systems: Principles and Design”, 2nd Edition, Tata McGraw Hill,

2003.

3. Katsuhiko Ogata, “Discrete-Time Control Systems”, Pearson Education, 2002.

Page 3: Modern Control System (BE)

3

MODERN CONTROL SYSTEM

Unit I

STATE SPACE ANALYSIS OF CONTINUOUS TIME SYSTEMS

State Variable Representation

The state variables may be totally independent of each other, leading

to diagonal or normal form or they could be derived as the derivatives of the output. If

them is no direct relationship between various states. We could use a suitable

transformation to obtain the representation in diagonal form.

Phase Variable Representation

It is often convenient to consider the output of the system as one of the state

variable and remaining state variable as derivatives of this state variable. The state

variables thus obtained from one of the system variables and its (n-1) derivatives, are

known as n-dimensional phase variables.

In a third-order mechanical system, the output may be displacement

vxxx 2

.

1,1 and axx 32

.

in the case of motion of translation or angular displacement

wxxx 2

.

1,11 and .

3

.

2 wxx if the motion is rotational,

Where v ,,, awv respectively, are velocity, angular velocity acceleration, angular

acceleration.

Consider a SISO system described by nth-order differential equation

Where

u is, in general, a function of time.

The nth order transfer function of this system is

State variable representation – Conversion of state variable form to transfer function and

vice versa – Eigenvalues and Eigenvectors – Solution of state equation – Controllability

and observability – Pole placement design – Design of state observer

Page 4: Modern Control System (BE)

4

With the states (each being function of time) be defined as

Equation becomes

Using above Eqs state equations in phase satiable loan can he obtained as

Where

Physical Variable Representation

In this representation the state variables are real physical variables, which can

be measured and used for manipulation or for control purposes. The approach generally

adopted is to break the block diagram of the transfer function into subsystems in such a

way that the physical variables can he identified. The governing equations for the

subsystems can he used to identify the physical variables. To illustrate the approach

consider the block diagram of Fig.

One may represent the transfer function of this system as

Taking H(s) = 1, the block diagram of can be redrawn as in Fig. physical variables can

be speculated as x1=y, output, .

2 wx the angular velocity aix3 the armature

current in a position-control system.

Page 5: Modern Control System (BE)

5

Where

The state space representation can be obtained by

And

State space models from transfer functions

A simple example of system has an input and output as shown in Figure 1. This class

of system has general form of model given in Eq.(1).

1 1

1 0 1 01 1( ) ( )

n n m

n mn n m

d y d y d ua a y t b b u t

dt dt dt

Models of this form have the property of the following:

1 1 2 2 1 1 2 2( ) ( ) ( ) y( ) ( ) ( ) u t u t u t t y t y t (2)

where, (y1, u1) and (y2,u2) each satisfies Eq,(1).

Model of the form of Eq.(1) is known as linear time invariant (abbr. LTI) system. Assume

the system is at rest prior to the time t0=0, and, the input u(t) (0 t < ) produces the output

y(t) (0 t < ), the model of Eq.(1) can be represented by a transfer function in term of

Laplace transform variables, i.e.:

S y(t) u(t)

Page 6: Modern Control System (BE)

6

1

1 0

1

1 0

( ) ( )m m

m m

n n

n n

b s b s by s u s

a s a s a

(3)

Then applying the same input shifted by any amount of time produces the same output

shifted by the same amount q of time. The representation of this fact is given by the following

transfer function:

1

1 0

1

1 0

( ) ( )m m

sm m

n n

n n

b s b s by s e u s

a s a s a

(4)

Models of Eq.(1) having all 0 ( 0)ib i , a state space description arose out of a reduction

to a system of first order differential equations. This technique is quite general. First, Eq.(1)

is written as:

( ) ( 1)

( 1)

0 1 1

, ( ), , . , , ;

with initial conditions: y(0)=y , (0) (0), , (0) (0)

n n

n

n

y f t u t y y y y

y y y y

(5)

Consider the vector nx R with( 1)

1 2 3, , , , n

nx y x y x y x y , Eq.(5) becomes:

2

3

( 1), ( ), , . , ,

n

n

x

xd

Xdt

x

f t u t y y y y

(6)

In case of linear system, Eq.(6) becomes:

0 1 n-1

0 1 0 0 0

0 0 1 0 0 0

0 ( ); y(t)= 1 0 0 0

0 0 1

-a -a -a 1

dX X u t X

dt

(7)

It can be shown that the general form of Eq.(1) can be written as

0 1 m

0 1 n-1

0 1 0 0 0

0 0 1 0 0 0

0 ( ); y(t)= b b b 0 0

0 0 1

-a -a -a 1

dX X u t X

dt

(8)

and, will be represented in an abbreviation form:

Page 7: Modern Control System (BE)

7

; ; D=X AX Bu y CX Du 0 (9)

Eq.(9) is known as the controller canonical form of the system.

Transfer function from state space models

We have just showed that a transfer function model can be expressed as a state space

system of controller canonical form. In the reverse direction, it also easy to see that each

linear state space system of Eq.(9) cab be expressed as a LTI transfer function. The procedure

is to take laplace transformation of the both sides of Eq,(9) to give:

( ) ( ) ( ) ; ( ) ( ) ( )sX s AX s Bu s y s CX s Du s (10)

So that

1 ( )

( ) ( ) ( ) ( )( )

n sy s C sI A B D u s G s u s

d s (11)

An algorithm to compute the transfer function from state space matrices is given by the

Leverrier-Fadeeva-Frame formula of the following:

1

1 2

0 1 2 1

1

1 1

0 1 0

1 0 1 2 1

( )

( )

( )

( )

,

( )

1/ 2 ( )

n n

n n

n n

n n

N ssI A

d s

N s s N s N sN N

d s s d s d s d

where

N I d trace AN

N AN d I d trace AN

1 2 1 1 2

-1 1

1 ( )

1

1 0 A

n n n n n

n n n n

N AN d I d trace ANn

N d I d trace ARn

(12)

Therefore, according to the algorithm mentioned, the transfer function becomes:

( ) ( )n s CN s B CD (13)

or, ( )

( )( )

CN s B CDG s

d s (14)

EigenValues

Consider an equation AX = Y which indicates the transformation of 1n vector

matrix X into 'n x 1' vector matrix Y by 'n x n' matrix operator A.

Page 8: Modern Control System (BE)

8

If there exists such a vector X such that A transforms it to a vector XX then X is

called the solution of the equation,

The set of homogeneous equations (1) have a nontrivial solution only under

the condition,

The determinant | X I - A | is called characteristic polynomial while the equation (2)

is called the characteristic equation.

After expanding, we get the characteristic equation as,

The 'n' roots of the equation (3) i.e. the values of X satisfying the above equation

(3) are called eigen values of the matrix A.

The equation (2) is similar to| sI- A | =0, which is the characteristic equation of the

system. Hence values of X satisfying characteristic equation arc the closed loop

poles of the system. Thus eigen values are the closed loop poles of the system.

Eigen Vectors

Any nonzero vector iX such that iii XAX is said to be eigen vector associated

with eigenvalue i .Thus let i satisfies the equation

Then solution of this equation is called eigen vector of A associated with eigen

value i and is denoted as Mi.

If the rank of the matrix [ i I - A] is r, then there are (n - r) independent Eigen

vectors. Similarly another important point is that if the eigenvalues of matrix A

are all distinct, then the rank r of matrix A is (n - 1) where n is order of the

system.

Page 9: Modern Control System (BE)

9

Mathematically, the Eigen vector can be calculated by taking cofactors of

matrix ( i I - A) along any row.

Where C ki is cofactor of matrix ( i I - A) of kth

row.

Key Point: If the cofactor along a particular row gives null solution i.e. all elements of

corresponding eigen vectors are zero then cofactors along any other row must he

obtained. Otherwise inverse of modal matrix M cannot exist.

Example 1

Obtain the Eigen values, Eigen vectors for the matrix

Solution

Eigen values are roots of

Eigen values are

To find Eigen vector,

Let

Page 10: Modern Control System (BE)

10

Where C = cofactor

For 2 = -2

For 3 = -3

Example 2

For a system with state model matrices

Obtain the system with state model matrices

Page 11: Modern Control System (BE)

11

Solution

The T.F. is given by,

Page 12: Modern Control System (BE)

12

Solution of State Equations

Consider the state equation n of linear time invariant system as,

)()()(.

tBUtAXtX

The matrices A and B are constant matrices. This state equation can be of two types,

1. Homogeneous and

2. Nonhomogeneous

Homogeneous Equation

If A is a constant matrix and input control forces are zero then the equation

takes the form,

Such an equation is called homogeneous equation. The obvious equation is if input is

zero, In such systems, the driving force is provided by the initial conditions of the

system to produce the output. For example, consider a series RC circuit in which

capacitor is initially charged to V volts. The current is the output. Now there is no

input control force i.e. external voltage applied to the system. But the initial voltage on

the capacitor drives the current through the system and capacitor starts

discharging through the resistance R. Such a system which works on the initial

conditions without any input applied to it is called homogeneous system.

Nonhomogeneous Equation

If A is a constant matrix and matrix U(t) is non-zero vector i.e. the input

control forces are applied to the system then the equation takes normal form as,

Such an equation is called nonhomogeneous equation. Most of the practical

systems require inputs to dive them. Such systems arc nonhomogeneous linear

systems.

The solution of the state equation is obtained by considering basic method of

Page 13: Modern Control System (BE)

13

finding the solution of homogeneous equation.

Controllability and Observability

More specially, for system of Eq.(1), there exists a similar transformation that will

diagonalize the system. In other words, There is a transformation matrix Q such that

0 ; ; X(0)=XX AX Bu y CX Du (1)

-1 or X=QX QX X

(2)

y = CX X Bu X Du

(3)

Where

1

2

0 0

0 0

0 n

(4)

Notice that by doing the diagonalizing transformation, the resulting transfer function between

u(s) and y(s) will not be altered.

Looking at Eq.(3), if 0kb

, then kx (t) is uncontrollable by the input u(t), since, kx (t) is

characterized by the mode kte by the equation:

( ) (0 )k t

k kx t e x

The lake of controllability of the state kx (t) is reflect by a zero kth

row of B

, i.e.kb

. Which

would cause a complete zero rows in the following matrix (known as the controllability

matrix), i.e.:

C(A,b)

2 1

1 1 1 1 1 1 1

2 1

2 2 2 2 2 2 2

2 3 n-1

2 1

k k k

A A A A

n

n

n

k k k k

b b b b

b b b b

B B B B Bb b b b

2 1

n n n

n

n n n nb b b b

(5)

A C(A,b) matrix with all non-zero row has a rank of N.

In fact ,1 or B Q B B QB

. Thus, a non-singular C(A,b) matrix implies a non-singular

matrix of C(A,b)of the following:

Page 14: Modern Control System (BE)

14

C(A,b) 2 -1 nB AB A B A B (6)

It is important to note that this result holds in the case of non-distinct eigenvalues as well.

Remark 1]

If matrix A has distinct eigenvalues and is represented as a controller canonical form, it

is easy to show the following identity holds, i.e.:

2 1 2 1

1 1 1 1 1 1 11 1n nA f or each i.

Therefore a transpose of so-called Vandermonde matrix V of n column eigenvectors of A will

diagonalize A, i.e.,

2 1

1 1 11 2 2 12 2 2 2 2 2

1 2

2 n-1

n1 1 n-1

1 2 n

1 1 11

1

1

T

n

n n

Tn

n nn n

W

(6)

and

1 1

T T or, A= AT T T TW A W W W W W A

[Remark 2]

There is an alternative way to explain why C(A,b) should have rank n for state controllable,

let us start from the solution of the state space system:

0

( )( ) (0 ) ( )

ft

At A t

t

X t e X e Bu d (7)

The state controllability requires that for each X(tf) nearby X(t0), there is a finite sequence of

u(t; t [to,tf]).

Page 15: Modern Control System (BE)

15

0

0

0

0

0

0

0

0

( 1)

0

0

( 1) 1

0

0

( ) ( )

( ) ( )

( )

= ( ) ( )

f

f

f

f

t

At A

f

t

t

AtA

f

t

t knA

k t k

t k i ni

i

k it k

X t e X e Bu d

or

e Bu d e X t X

e Bu t k d

A B u t k

0

0

0

( 1)i=n-1

0

i=0 0

1

i=n-122 n-1

i=0

= ( ) ( )

= AB A B A B

n

t k ki

i

kt k

i

i

n

d

A B u t k d

w

wA BW B

w

Thus, in order W has non-trival solution, we need that C(A,b) matrix has exact rank n

There are several alternative ways of establishing the state space controllability:

The (n) rows of Ate B are linearly independent over the real field for all t.

The controllability grammian

0

( , )

fT

t

At T A

ram o f

t

G t t e BB e d is non-singular for all 0ft t .

[Theorem 1] Replace B with b, (i.e. Dim{B}=n 1), a pair [A,b] is non-controllable if

and only if there exists a row vector 0q such that

, 0qA q qb (8)

To prove the “if” part:

If there is such row vector, we have:

Page 16: Modern Control System (BE)

16

2 2 2 1

-1 1

0

0 0

0 , , , , 0 and 0

0

n

n n

qA q and qb

qAb qbq I A

qA b qAb qb q b Ab A b A bqb

qA b qb

Since 0q , we conclude that: 2 1, , , , nb Ab A b A b is singular, and thus the

system is not controllable.

To prove the “only if’ part:

If the pair is noncontrollable, then matrix A can be transformed into non-

controllable form like:

, 0 0

C CCC

C

A A rbA b

A n r (9)

Where, r rank C(A,b) (Notice that Eq.(33) is a well-known theorem in linear

system.)

Thus, one can find a row vector has the form [0 ]q z , where z can be selected as

the eigenvector of CA , (i.e.: CzA z ), for then:

0 z 0qA A z q (10)

Therefore, we have shown that only if [A, b] is non-controllable, there is a

non-zero row vector satisfying Eq.(8).

In fact, according to Eq.(27),

1

1

i

ktAt t t T T

i i

i

e Ve V Ve W v w e

and, 0( ) AtX t e X , we have:

( )( )

0 0

1 10 0

( ) ( ) ( )i ii

t tk nt tAt A t T T

i i i i

i i

X t e X e bu d v w e X v w b e u d

Page 17: Modern Control System (BE)

17

Thus, if b is orthogonal to iw , then the state associated with i will not be controllable,

and hence, the system is not completely controllable. The another form to test for the

controllability of the [A,b] pair is known as the Popov-Belevitch-Hautus (abbrv. PBH) test is

to check if rank sI A b n for all s (not only at eigenvalues of A). This test is based on

the fact that if sI A b has rank n, there cannot be a nonzero row vector q satisfying

Eq.(32). Thus by Theorem 1, pair [A, b] must be controllable.

Referring to the systems described by Eqs.(26) and (27), the state ( )ix t

corresponding to

the mode ite is unobservable at the output 1y , if 1 0iC

for any i=1,2,…,n. The lack of

observability of the state ( )ix t

is reflected by a complete zero (ith) column of so called

observability matrix of the system O ( , )A C

, i.e.:

O1( , )A C

11 12 11

1 11 2 12 11

1 1 11

1 2 12 11

n

n n

n n nn

n n

C C CC

C C CC A

C C CC A

(11)

An observable state ( )ix t

corresponds to a nonzero column of O ( , )A C

. In the case of distinct

eigenvalues, each nonzero column increases the rank by one. Therefore, the rank of

O ( , )A C

corresponding to the total number of modes that are observable at the output y(t) is

termed the observability rank of the system. As in the case of controllability, it is not

necessary to transform a given state-space system to modal canonical form in order to

determine its rank. In general, the observability matrix of the system is defined as:

O ( , )A C =

1n

C

CA

CA

= O

1( , ) ( , )A C Q A C V

With Q=V-1

nonsingular. There, the rank of O ( , )A C equals the rank of O ( , )A C

. It is

important to note that this result holds in the case of non-distinct eigenvalues. Thus, a state-

space system is said to be completely (state) observable if its observability matrix has a full

rank n. Otherwise the system is said to be unobservable

Page 18: Modern Control System (BE)

18

In particular, it is well known that a state-space system is observable if and only if the

following conditions are satisfied:

The (n) column of AtCe are linearly independent over R for all t.

The observability grammian of the following is nonsingular for all 0ft t :

0

,

T

t

A T A

ranm o

t

G e C Ce d

The (n+p) n matrix I A

Cb has rank n at all eigenvalues i of A.

Pole Placement Design

The conventional method of design of single input single output control system

consists of design of a suitable controller or compensator in such a way that the dominant

closed loop poles will have a desired damping ratio % and undamped natural frequency con.

The order of the system in this case is increased by 1 or 2 if there are no pole zero

cancellation taking place. It is assumed in this method that the effects on the responses of non-

dominant closed loop poles lo be negligible. Instead of specifying only the dominant closed

loop poles in the conventional method of design, the pole placement technique describes all the

closed loop poles which require measurements of all state variables or inclusion of a state

observer in the system. The system closed loop poles can be placed at arbitrarily chosen

locations with the condition that the system is completely stale controllable. This condition

can be proved and the proof is given below. Consider a control system described by following

slate equation

Here x is a state vector, u is a control signal which is scalar, A is n x n state matrix. B is n x 1

constant matrix.

Fig open loop control system

Page 19: Modern Control System (BE)

19

The system defined by above equation represents open loop system. The

state x is not fed back to the control signal u. Let us select the control signal to

be u = - Kx state. This indicates that the control signal is obtained from instantaneous state.

This is called state feedback. The k is a matrix of order l x n called state feedback gain matrix.

Let us consider the control signal to be unconstrained. Substituting value of u in equation 1

The system defined by above equation is shown in the Fig. 5.2. It is a closed loop

control system as the system state x is fed back to the control system as the system stale x

is fed back to control signal u. Thus this a system with state feedback

The solution of equation 2 is say

x(t) = e,x(0) is the initial slate …(3)

The stability and the transient response characteristics are determined by the eigen

values of matrix A - BK. Depending on the selection of state feedback gain matrix K, the

matrix A - BK can be made asymptotically stable and it is possible to make x(t) approaching

to zero as time t approaches to infinity provided x(0) * 0. The eigen values of matrix A - BK

arc called regulator poles. These regulator poles when placed in left half of s plane then x(t)

approaches zero as time t approaches infinity. The problem of placing the closed loop poles

at the desired location is called a pole placement problem.

Design of State Observer

In case of state observer, the state variables are estimated based on the

measurements of the output and control variables. The concept of observability

plays important part here in case of state observer.

Consider a system defined by following state equations

Page 20: Modern Control System (BE)

20

Let us consider x as the observed state vectors. The observer is basically a

subsystem which reconstructs the state vector of the system. The mathematical

model of the observer is same as that of the plant except the inclusion of additional

term consisting of estimation error to compensate for inaccuracies in matrices A and

B and the lack of the initial error.

The estimation error or the observation error is the difference between the

measured output and the estimated output. The initial error is the difference

between the initial state and the initial estimated state. Thus the mathematical

model of the observer can be defined as,

Here x is the estimated state and C x is the estimated output. The observer has

inputs of output y and control input u. Matrix K^ is called the observer gain

matrix. It is nothing but weighing matrix for the correction term which contains

the difference between the measured output y and the estimated output cx

This additional term continuously corrects the model output and the performance

of the observer is improved.

Full order state observer

The system equations arc already defined as

The mathematical model of the state observer is taken as.

To determine the observer error equation, subtracting equation of x from x wc get

Page 21: Modern Control System (BE)

21

The block diagram of the system and full order state observer is shown in the Fig.

The dynamic behavior of the error vector is obtained from the Eigen values of matrix

A-K^C If matrix A-K^C is a stable matrix then the error vector will converge to

zero for any initial error vector e(0). Hence x(t) will converge to x(t) irrespective of

values of x(0) and x(0).

If the Eigen values of matrix A-KeC are selected in such a manner that the dynamic

behavior of the error vector is asymptotically stable and is sufficiently fast then

any of the error vector will tend to zero with sufficient speed.

1/ the system is completely observable then it can be shown that it is possible to select

matrix K,. such that A-K^C has arbitrarily desired Eigen values, i.c. observer gain

matrix Ke can be obtained to get the desired matrix A-KCC.

Page 22: Modern Control System (BE)

22

UNIT I

STATE SPACE ANALYSIS OF CONTINUOUS TIME SYSTEMS

PART A

1. What are the advantages of state space analysis?

2. What are the drawbacks in transfer function model analysis?

3. What is state and state variable?

4. What is a state vector?

5. Write the state model of nth

order system?

6. What is state space

7. What are phase variables?

8. Write the solution of homogeneous state equation?

9. Write the solution of nonhomogeneous state equation?

10. What is resolvant matrix?

PART B

1. Explain Kaman’s test for determining state controllability?

2. Explain Gilbert’s test for determining state controllability?

3. Find the output of the system having state model,

and

The input U(t) is unit step and X(0) 0

10

4. Show the following system is completely state controllable and observable.

And

5. Obtain the homogenous solution of the equation X(t) =A X(t)

6. Derive the transfer function of observer based controller?

Page 23: Modern Control System (BE)

23

UNIT II

Z-TRANSFORM AND SAMPLED DATA SYSTEMS

Sampled Data System

When the signal or information at any or some points in a system is in the form of

discrete pulses. Then the system is called discrete data system. In control engineering the

discrete data system is popularly known as sampled data systems.

Sampling process

Sampling is the conversion of a continuous time signal into a discrete time signal

obtained by taking sample of the continuous time signal at discrete time instants.

Thus if f (t) is the input to the sampler

The output is f(kT)

Where T is called the sampling interval

The reciprocal of T

Sampled data theory – Sampling process – Sampling theorem – Signal reconstruction –

Sample and hold circuits – z-Transform – Theorems on z- Transforms – Inverse z-

Transforms – Discrete systems and solution of difference equation using z transform –

Pulse transfer function – Response of sampled data system to step and ramp Inputs –

Stability studies – Jury’s test and bilinear transformation

Page 24: Modern Control System (BE)

24

Let 1/T =Fs is called the sampling rate. This type of sampling is called periodic

Sampling, since samples are obtained uniformly at intervals of T seconds.

Multiple order sampling – A particular sampling pattern is repeated periodically

Multiple rate sampling - In this method two simultaneous sampling operations with

different time periods are carried out on the signal to produce the sampled output.

Random sampling – In this case the sampling instants are random

Sampling Theorem

A band limited continuous time signal with highest frequency fm hertz can be uniquely

recovered from its samples provided that the sampling rate Fs is greater than or equal to 2fm

samples per seconds

Signal Reconstruction

The signal given to the digital controller is a sampled data signal and in turn the

controller gives the controller output in digital form. But the system to be controlled needs an

Page 25: Modern Control System (BE)

25

analog control signal as input. Therefore the digital output of controllers must be converters

into analog form

This can be achieved by means of various types of hold circuits. The simplest hold

circuits are the zero order hold (ZOH). In ZOH, the reconstructed analog signal acquires the

same values as the last received sample for the entire sampling period

The high frequency noises present in the reconstructed signal are automatically

filtered out by the control system component which behaves like low pass filters. In a first

order hold the last two signals for the current sampling period. Similarly higher order hold

circuit can be devised. First or higher order hold circuits offer no particular advantage over

the zero order hold

Z- Transform

Definition of Z Transform

Let f (k) = Discrete time signal

F (z) = Z {f (k)} =z transform of f (k)

The z transforms of a discrete time signal or sequence is defined as the power series

k

k

zkfZF )()( -------------- 1

Where z is a complex variable

Equation (1) is considered to be two sided and the transform is called two sided z transform.

Since the time index k is defined for both positive and negative values.

The one sided z transform of f(k) is defined as

k

k

zkfZF0

)()( --------------- 2

Page 26: Modern Control System (BE)

26

Problem

1. Determine the z transform and their ROC of the discrete sequences f(k) ={3,2,5,7}

Given f (k) = {3, 2, 5, 7}

Where f (0) =3

f (1) =2

f (2) = 5

f (3) = 7

f (k) = 0 for k < 0 and k >3

By definition

k

k

zkfzFkfZ )()()}({

The given sequence is a finite duration sequence. Hence the limits of summation can be

changed as k = 0 to k = 3

k

k

zkfzF3

0

)()(

0)0()( zfzF + 1)1( zf + 2)2( zf + 3)3( zf

= 321 7523 zzz

Here )(zF is bounded, expect when z =0

The ROC is entire z-plane expect z = 0

2. Determine the z transform of discrete sequences f (k) =u (k)

Given f (k) =u (k)

u (k) is a discrete unit step sequence

u (k) = 1 for k 0

= 0 for k < 0

By definition

k

k

zkfzFkfZ )()()}({ k

k

zku0

)(

k

k

z0

k

k

z )( 1

0

Page 27: Modern Control System (BE)

27

F (z) is an infinite geometric series and it converges if 1z

F (z) 11

1

z

z

11

1

1z

z

3. Find the one sided z transform of the discrete sequences generated by mathematically

sampling the continuous time function f (t) kTe at cos

Given

f (t) kTe at cos

By definition

F(z) = k

k

akT zkTekfZ0

cos)}({

k

k

TkjTkjTka z

eee

0 2

0 0

11

2

1

2

1

k k

kTjTakTjTa zeezee

WKT c

ck

k

1

1

0

11 1

1

2

1

1

1

2

1)(

zeezeezF

TwjTaTwjaT

aT

Tj

aT

Tj

ez

e

ez

e1

1

2

1

1

1

2

1

TjaT

aT

TjaT

aT

eez

ez

eez

ez

2

1

TjaTTjaT

TjaTaTTjaTaT

ezeeze

ezezeezeze

2

1

TjTjTjaTTjaTaT

TjaTTjaTaT

eeezeezeze

ezeezeze2)(2

Page 28: Modern Control System (BE)

28

1)(

)(2

2 22 TjTjaTaT

TjTjaTaT

eezeez

eezeze

1cos2

)cos(

2 22 Tzeez

TzezezeaTaT

aTaTaT

2

cosjj ee

Inverse z transform

Partial fraction expansion (PFE)

Power series expansion

Partial fraction expansion

Let f (k) =discrete sequence

F (z) =Z {f (k)} = z transform of f (k)

F (z) =n

nnn

m

mmm

azazaz

bzbzbzb

..........

..........2

2

1

1

2

0

1

00 where nm

The function F (z) can be expressed as a series of sum terms by PFE

n

i i

i

pz

AAzF

1

0)( -------------- 3

Where 0A is a constant

nAAA ,........, 21 are residues

nppp ,........, 21 are poles

Power series expansion

Let f (k) =discrete sequences

F (z) = Z {f (k)} = z transform of f (k)

By definition

k

k

zkfZF )()(

On Expanding

...)..........)2()1()0()1()2()3((.......)( 210123 zfzfzfzfzfzfZF -------4

Problem

1. Determine the inverse z transform of the following function

(i) F (z) =21 5.05.11

1

zz

Page 29: Modern Control System (BE)

29

Given

F (z) = 21 5.05.11

1

zz

2

5.05.11

1

zz

5.05.12

2

zz

z

)5.0()1(

2

zz

z

)5.0()1(

)(

zz

z

z

zF

By partial fraction expansion

)5.0()1(

)( 21

z

A

z

A

z

zF

1A )1()(

zz

zF

Put z =1

1A )1()5.0()1(

zzz

z

)5.0(z

z

)5.01(

1

2

Put z =0.5

2A )5.0()(

zz

zF

2A )5.0()5.0()1(

zzz

z

)1(z

z

Page 30: Modern Control System (BE)

30

)15.0(

5.0

-1

5.0

1

1

2)(

zzz

zF

5.01

2)(

z

z

z

zzF

WKT

az

zaZ k }{ and

1)}({

z

zkuZ

On taking inverse z transform

0,)5.0()(2)( kkukf k

(ii) F (z) =5.02

2

zz

z

Given

F (z) =5.02

2

zz

z

)5.05.0()5.05.0(

2

jzjz

z

)5.05.0()5.05.0(

)(

jzjz

z

z

zF

By partial fraction expansion

)5.05.0()5.05.0(

)( *

jz

A

jz

A

z

zF

A )5.05.0()(

jzz

zF

Put z = 0.5+j0.5

A )5.05.0()5.05.0()5.05.0(

jzjzjz

z

)5.05.0( jz

z

Page 31: Modern Control System (BE)

31

)5.05.05.05.0(

5.05.0

jj

j

5.05.0 j

*A )5.05.0()5.05.0()5.05.0(

jzjzjz

z

Put z =0.5-j0.5

*A)5.05.0( jz

z

)5.05.05.05.0(

5.05.0

jj

j

5.05.0 j

)5.05.0(

)5.05.0(

)5.05.0(

)5.05.0()(

jz

j

jz

j

z

zF

)5.05.0(

)5.05.0(

)5.05.0(

)5.05.0(

jz

zj

jz

zj

WKT az

zaZ k }{

On taking inverse z transform

kk jjjjkf )5.05.0()5.05.0()5.05.0)(5.05.0()(

kk j

jjj

jj )5.05.0()5.0

5.0()5.05.0()5.0

5.0(

kk jjjjjj )5.05.0()5.05.0()5.05.0)(5.05.0(

11 )5.05.0()5.05.0( kk jjjj

2. Determine the inverse z transform of z domain function

F (z) =23

1232

2

zz

zz

Given

F (z) =23

1232

2

zz

zz

3

232 zz 123 2 zz

693 2 zz

511z

Page 32: Modern Control System (BE)

32

F (z) = 23

5113

2 zz

z

)2()1(

5113

zz

z

By PFE

F (z) = )2()1(

3 21

z

A

z

A

1A )1()2()1(

511z

zz

z

)2(

511

z

z6

21

511

2A )2()2()1(

511z

zz

z

)1(

511

z

z

1712

5)2(11

)2(

17

)1(

63)(

zzzF

2

117

)1(

163

z

z

zz

z

z

217

)1(63 11

z

zz

z

zz

On taking inverse z transform

0;)1(217)1(6)(3)( )1( kforkukukkf k

2. Determine the inverse z transform of the following

21

2

1

2

31

1)(

zz

zF

Where (i) ROC 0.1z

(ii) ROC 5.0z

Given

21

2

1

2

31

1)(

zz

zF

(i)

0.1z

Page 33: Modern Control System (BE)

33

..........8

15

4

7

2

31 321 zzz

21

2

1

2

31 zz 1

21

2

1

2

31 zz

321

21

4

3

4

9

2

3

2

1

2

3

zzz

zz

422

22

8

7

4

3

4

7

4

3

4

7

zzz

zz

43

8

7

8

15zz

)(zF ..........8

15

4

7

2

31 321 zzz ------------ -(i)

k

k

zkfZF )()(

For a causal signal

k

k

zkfzF0

)()(

.................)2()1()0()( 321 zfzfzfzF

-------------- (ii)

Comparing equation (i) &(ii)

1)0(f ,2

3)1(f ,

4

7)2(f ,

8

15)3(f

0......}..........,8

15,

4

7,

2

3,1{)( kforkf

Page 34: Modern Control System (BE)

34

(i)

5.0z

..........301162 5432 zzzz

12

3

2

1 12 zz 1

2231 zz

32

2

693

23

zzz

zz

432

2

14217

367

zzz

zz

543

43

304515

1415

zzz

zz

)(zF ..........301162 5432 zzzz -------------- (i)

k

k

zkfZF )()(

For an anti-causal signal

10

)()( zkfZFk

)0()1()2()3()4()5(............)( 12345 fzfzfzfzfzfzF ------------- (ii)

Comparing the equation i & ii

30)5(f , 14)4(f , 6)3(f , 2)2(f , 0)1(f , 0)0(f

}0,0,2,6,14,30..{.........)(kf

Difference equation

Discrete time systems are described by difference equation of the form

Page 35: Modern Control System (BE)

35

If the system is causal, a linear difference equation provides an explicit relationship between

the input and output. This can be seen by rewriting.

Thus the nth value of the output can be computed from the nth input value and the N and M

past values of the output and input, respectively.

Role of z transform in linear difference equations

Equation (1) gives us the form of the linear difference equation that describes the

system. Taking z transform on either side and assuming zero initial conditions, we have

Where H(z) is a z transform of unit sample response h(n).

Stability analysis

Jury’s stability test

Bilinear transformation

Jury’s stability test

Jury’s stability test is used to determine whether the roots of the characteristic

polynomial lie within a unit circle or not. It consists of two parts.One simple test for

necessary condition for stability and another test for sufficient condition for stability.

Let us consider a general characteristic polynomial F (z)

0,................)( 01

1

1 n

n

n

n

n awhereazazazazF

Necessary condition for stability

0)1()1(;0)1( FF n

If this necessary condition is not met, then the system is unstable. We need not check the

sufficient condition.

Page 36: Modern Control System (BE)

36

Sufficient condition for stability

20

20

10

0

..................

rr

cc

bb

aa

n

n

n

If the characteristic polynomial satisfies (n-1) conditions, then the system is stable

Jury’s test

Bilinear transformation

The bilinear transformation maps the interior of unit circle in the z plane into the left half of

the r-plane.

1

1

z

zr Or r

rz

1

1

Fig.Mapping of unit circle in z-plane into left half of r-plane

Consider the characteristic equation

)....(..........0;............ 0

2

2

1

1 iaaazazaza nz

n

n

n

n

n

n

Sub r

rz

1

1 in Equation (i)

Page 37: Modern Control System (BE)

37

)..(..........0)1

1(............)

1

1()

1

1()

1

1( 0

2

2

1

1 iiar

ra

r

ra

r

ra

r

ra n

n

n

n

n

n

Equation (ii) can be simplified

0............ 01

2

2

1

1 brbrbrbrb n

n

n

n

n

n

Problem

1. Check for stability of the sampled data control system srepresented by

characteristic equation.

0225)( 2 zzi

Given

0225)( 2 zzzF

5

225

2)1(2)1(5)1(

225)(

2

2

01

2

2

F

zzazazazF

9

)225(1

2)1(2)1(5)1()1()1( 22Fn

Here n=2

Since 0)1()1(;0)1( FF n, the necessary condition for stability is satisfied.

Check for sufficient condition

It consisting of (2n-3) rows

n=2 (2n-3) = (2*2-3)

= 1

So, it consists of only one row

Row z0

z1

z2

1 a0 a1 a2

5,2,2 210 aaa

10 aa

The necessary condition to be satisfied

Page 38: Modern Control System (BE)

38

The necessary & sufficient conditions for stability are satisfied. Hence the system is stable

(ii) 005.025.02.0)( 23 zzzzF

)(zF 01

2

2

3

3 azazaza

005.025.02.0 23 zzz

Method 1

Check for necessary condition

005.025.02.0)( 23 zzzzF

6.005.0)1(25.0)1(2.01)1( 23F

9.0]05.0)1(25.0)1(2.0)1([)1()1()1( 233Fn

Here n=3

Since )1(F >0 & )1()1( Fn >0

The necessary condition for stability is satisfied.

Check for sufficient condition

It consisting of (2n-3) row

n =3, (2n-3) = (2*6-3) =3

So, the table consists of three rows

Row z0

z1

z2

z3

1 a0 a1 a2 a3

2 a3 a2 a1 a0

3 b0 b1 b2

1

2.0

25.0

05.0

3

2

1

0

a

a

a

a

Page 39: Modern Control System (BE)

39

24.0

)25.0(*)2.0(*05.02.01

25.005.0

1875.0

)2.0*25.0(05.025.01

2.005.0

9975.0

105.005.01

105.0

23

10

3

13

20

1

2

03

30

0

aa

aab

aa

aab

aa

aab

Row z0

z1

z2

z3

1 0.05 -0.25 -0.2 1

2 1 -0.2 -0.25 1

3 -0.9975 0.1875 0.24

The necessary condition to be satisfied

25.09975.0,105.0

, 2030 bbaa

The necessary and sufficient conditions for stability are satisfied. Hence the system is stable.

Method 2

005.025.02.0)( 23 zzzzF

Put r

rz

1

1

005.0)1

1(25.0)

1

1(2.0)

1

1()( 23

r

r

r

r

r

rrF

On multiplying throughout by 3)1( r we get

Page 40: Modern Control System (BE)

40

06.09.26.39.0

0)2.01.04.03.0()8.08.22.32.1(

0)2.01.03.02.01.03.0()8.022.18.022.1(

0)2.01.03.0)(1()8.022.1)(1(

0)1.005.005.025.025.0)(1()2.02.021)(1(

0)21)(1(05.0)1)(1(25.0)1)(1(2.0)21)(1(

0)1(05.0)1)(1(25.0)1()1(2.0)1(

23

2323

232232

22

2222

2222

3223

rrr

rrrrr

rrrrrrrrrr

rrrrrr

rrrrrrrr

rrrrrrrrrr

rrrrrr

The coefficient of the new characteristic equation is positive. Hence the necessary condition

for stability is satisfied.

The sufficient condition for stability can be determined by constructing routh array as

1

4.........6.0:

3.........75.2:

2.........6.06.3:

1.........9.29.0:

0

1

2

3

column

rowr

rowr

rowr

rowr

75.2

6.3

)6.0*9.0()9.2*6.3(1r

6.0

75.2

)6.3*0()6.0*75.2(0r

There is no sign change in the elements of first column of routh array. Hence the sufficient

condition for stability is satisfied.

The necessary condition and sufficient condition for stability are satisfied. Hence the system

is stable.

Pulse transfer function

It is the ratio of s transform of discrete output signal of the system to the z-transform of

discrete input signal to the system. That is

)(

)()(

zR

zCzH (i)

Proof

Consider the z-transform of the convolution sum

k

k m

zmrmkhkCZ0 0

)()()]([ ---------------- (ii)

On interchanging the order of summation, we get

Page 41: Modern Control System (BE)

41

k

km

zmkhmrzC00

)(.)()( ------------------ (iii)

Let mkl Then lkwhenml &0

0lwhen

ml

mkm

m zlhzmrzC )(.)()(0

--------------------- (iv)

l

mkm

m zlhzmrzC )(.)()(0

------------------------ (v)

)().()( zHzRzC

The pulse transfer function

)(

)()(

zR

zCzH --------------------------- (vi)

The block diagram for pulse transfer function

UNIT II

Z-TRANSFORM AND SAMPLED DATA SYSTEMS

PART A

1. What is sampled data control system?

2. Explain the terms sampling and sampler.

3. What is meant by quantization?

4. State (shanon’s) sampling theorem

5. What is zero order hold?

6. What is region of convergence?

7. Define Z-transform of unit step signal?

8. Write any two properties of discrete convolution.

9. What is pulse transfer function?

10. What are the methods available for the stability analysis of sampled data control

systems?

11. What is bilinear transformation?

Page 42: Modern Control System (BE)

42

PART B

1. (i)solve the following difference equation

2 y(k) – 2 y(k-1) + y (k-2) = r(k)

y (k) = 0 for k<0 and

r(k) = {1; k= 0,1,2

{0;k<0 (8)

(ii)check if all the roots of the following characteristics equation lie within the circle.

Z4–1.368Z3+0.4Z2+0.08Z+0.002=0 (8)

2. (i)Explain the concept of sampling process. (6)

(ii)Draw the frequency response of Zero-order Hold (4)

(iii)Explain any two theorems on Z-transform (6)

3. The block diagram of a sampled data system is shown to Fig.(a) Obtain discrete-time state

model for the system. (b) Obtain the equation for inter sample response of the system.

4. The block diagram oils sampled-data system is shown in Fig.

(a) Obtain discrete-time state model for the system

(b) Find the response of the system for a unit step input.

(c) What is the effect on system response (i) when T =0.5 sec (ii) T=1.5 sec

Page 43: Modern Control System (BE)

43

UNIT III

STATE SPACE ANALYSIS OF DISCRETE TIME SYSTEMS

State variables

Concepts of State and State Variables

State

The state of a dynamic system is the smallest set of variables (called state variables) such

that the knowledge of these variables at t=t0, together with the knowledge of the inputs for

0tt , completely determine the behaviour of the system for any time 0tt .

The concept of state is not limited to physical systems. It is applicable to biological systems.

economic systems, social systems, and others.

State variables

The state variables of a dynamic system are the smallest set of variables that determine the

state of the dynamic system. i.e. the state variables are the minimal set of variables such that the

knowledge of these variables at any initial time t = to, together with the knowledge of the

inputs for 0tt is sufficient to completely determine the behaviour of the system for any

time 0tt . If atleast n variables nxxx ,......2,1 are needed to completely describe the

behaviour of a dynamic system than those n variables are a set of state variables.

The state variables need not be physically measurable or observable quantities. Variables that

do not represent physical quantities and those that are neither measurable nor observable can

also be chosen as state variables. Such freedom in choosing state variables is an added

advantage of the state-space methods.

Canonical forms

They are four main canonical forms to be studied:

1. Controller canonical form

2. Observer canonical form

3. Controllability canonical form

4. Observability canonical form

State variables – Canonical forms – Digitalization – Solution of state equations –

Controllability and Observability – Effect of sampling time on controllability – Pole

placement by state feedback – Linear observer design – First order and second order

problems

Page 44: Modern Control System (BE)

44

Controller canonical form

Consider the transfer function of the following for illustration:

2

1 2 3

3 2

1 2 3

( )

( )

b s b s by s

u s s a s a s a

The transfer function is firstly decomposed into two subsystems:

2

1 2 33 2

1 2 3

( ) ( ) ( ) 1

( ) ( ) ( )

y s y s z sb s b s b

u s z s u s s a s a s a

In other words,

3 2

1 2 3

( ) 1;

( )

z s

u s s a s a s a

2

1 2 3( )and

z(s) 1

b s b s by s

It is easy to have the state-space equation of

3 2

0 1 0 0

0 0 1 0 ;

1

Z Z u

a a a

3 1 2 2 1 3 3 2 1 + b z + b z = b b b Zy b z

Thus for a general transfer function of

1

1 0

1

1 0

( ) ( )m m

m m

n n

n n

b s b s by s u s

a s a s a

The state-space representation can be given as

0 1

0 1 0 0

0 0 1 0

- - n

n n n

A

a aa

a a a

;

0

0

1

b

C= 0 1

0 0 0

0 0mb bbC

a a a

For convenience, we shall let 0 1 and 1a m n .

Page 45: Modern Control System (BE)

45

In other words, for system of the following:

1 1

1 2

1

1

( ) ( )n n

n

n n

n

b s b s by s u s

s a s a

We have

1 2 1

0 1 0 0

0 0 1 0

- -n n

A

a a a

;

0

0

1

b

1 1 n nC b b b

Observer canonical form

Now, we set n=3 for illustration. Bu assuming all initial values are zero, can be written as

3 2 2

1 2 3 1 2 3s y a s y a sy a y b s y b sy b y

1

1 2 1 1 1 1 2 1

2 3 2 2 2 1 3 2

3 3 3 3 1 3

y x

x x a y b u a x x b u

x x a y b u a x x b u

x a y b u a x b u

In other words,

1 1

2 2

3

1 0 b

0 1 ; b b ; 0 0 1

0 0 b

a

A a C

a

In general,

1

2

1 0 0 0

0 1 0; b= ; C= 1 0 0

1 0

0 0 0 1n

a

aA

a

Controllability canonical form

Again, use n=3 as illustration, the controllability form is given as:

Page 46: Modern Control System (BE)

46

1

3 2 1

2 3 2 1 1

1

0 0 1 1

1 0 ; b= 0 ; C= b b b 1 0

0 1 0 1 0 0

a a a

A a a

a

In general,

1

2

1

0 0

1 0

0 1 0 -

0 0 1 -

n

n

n

a

a

A a

a

; b=

1

1 2 1

2 3 1

1

1

1

1 0

1 0 0 0 0

1 0 0 0 0

n n

n n

n n

a a a

a a a

b b b

a

1 0 0C

The Observability canonical form

2 1

0 1 0 0 0

0 0 1 0 0

0 0 0 0 1

- n n

A

a a a

;

b

1

1

1

2 1 1

1 2 1

1 0 0 0 0 0

1 0 0 0 0

1 0

1

n n

n

n n

ba

bb

a a ab

a a a

C= 1 0 0 0

Controllability and Observability

The dynamics of a linear time (shift)) invariant discrete-time system may be expressed in

terms state (plant) equation and output (observation or measurement) equation as follows

Where x(k) an n dimensional slate rector at time t =kT. an r-dimensional control (input)

vector y(k). an m-dimensional output vector ,respectively, are represented as

Page 47: Modern Control System (BE)

47

The parameters (elements) of A, an nn (plant parameter) matrix. B an rn control

(input) matrix, and C an rm output parameter, D an rm parametric matrix are constants

for the LTI system. Similar to above equation state variable representation of SISO (single

output and single output) discrete-rime system (with direct coupling of output with input) can

be written as

Where the input u, output y and d. are scalars, and b and c are n-dimensional vectors.

The concepts of controllability and observability for discrete time system are similar to the

continuous-time system.

A discrete time system is said to be controllable if there exists a finite integer n and input

mu(k); ]1,0[ nk that will transfer any state )0(0 bxx to the state nkatx n n.

Controllability

Consider the state Equation can be obtained as

Equation can be written as

State x° can be transferred to some arbitrary state x" in at most n steps to be if p(U) = rank

of nBABAABB n ].........[ 12.

Thus, a system is controllable if the rank composite (n nr) matrix ].........[ 12 BABAABB n

is n.

Observability

Consider the output Equation can be obtained as

Page 48: Modern Control System (BE)

48

Thus, we can write

If rank of

!hen initial state x(0) can be determined from the most n measurements of the output and

input.

We can, therefore. State that "A discrete time system is observable if the rank of the

composite nnm matrix.

Effect of sampling time on controllability

We have a continuous-time plant which is to be controlled. The control action may be

either continuous or discrete and must make the plant behave in a desired manner. If discrete

control action is thought of, then the problem of selection of sampling interval arises. The

selection of best sampling interval for a digital control system is a compromise among many

factors. The basic motivation to lower the sampling rate 1/T is the cost. A decrease in

sampling rate means more time is available for control calculations, hence slower computers

are possible for a given control function or more control capacity is available for a given

computer. That economically, the best choice is the slowest possible sampling rate that meets

all the performance specifications. On the other hand, if the sampling rate is too low, the

sampler discards part of the information present in a continuous.tirne signal. The

minimum sampling rate or frequency has a definite relationship with the highest

significant signal frequency (i.e., signal bandwidth). This relationship is given by the

Sampling Theorem according to which the information contained in a signal is fully

preserved in its sampled version so long as the sampling frequency is at least twice the

highest significant frequency contained in the signal. This sets an absolute lower bound to

the sample rate selection.

Page 49: Modern Control System (BE)

49

We are usually satisfied with the trial and error method of selection of sampling interval.

We compare the response of the continuous-time plant with models discretized for

various sampling rates. Then the model with the slowest sampling rate which gives a

response within tolerable limits is selected for future work. However, the method is not

rigorous in approach. Also a wide variety of inputs must be given to each prospective

model to ensure that it is a tree representative of the plants.

Pole placement by state feedback

Consider a linear dynamic system in the state space form

In some cases one is able to achieve the goal by using the full state feedback, which

represents a linear combination of the state variables, that is

So that the closed loop system given by

has the desired specifications.

If the pair (A,b) is controllable, the original system can be transformed into phase variable

canonical form,i.e it exists a nonsingular transformation of the characteristic polynomial of A

that is

Such that

Where ai are coefficients of the characteristic polynomial of A, that is

For single input single output systems the state feedback is given by

Page 50: Modern Control System (BE)

50

After

Linear observer design

In a linear time invariant observer for reconstruction of the crystal radius from the weighing

signal is derived. As a starting point, a linear approximation of the system behaviour can be

used. For this purpose the nonlinear equations required for observer design need to be

linearized around some operating or ( steady state) values, i.e. the equations are expanded in a

Taylor series which is truncated at the second order

Can be approximated by

Around some fixed values 00

, ee va . With new coordinates )tan(00

cccc vrr

In the same way one can continue with the remaining equations needed for describing the

process dynamics. For example, The linear model he derived is

Where x is the state vector, Furthermore. One has the 3 3 system matrix A. the 3 2 control

matrix B and the 1 3 output matrix C. One has to keep in mind that the values of the state

spare vector .r, rho input sector it and the output y describe the deviation of the corresponding

quantities from their operating willies.

Page 51: Modern Control System (BE)

51

UNIT III

STATE SPACE ANALYSIS OF DISCRETE TIME SYSTEMS

PART A

1. What is state and state variable?

2. What is a state vector?

3. What is state space?

4. What is input and output space?

5. What are the advantages of state space modeling using physical variable?

6. What are phase variables?

7. What is the advantage and the disadvantage in canonical form of state model?

8. Write the solution of discrete time state equation?

9. Write the expression to determine the solution of discrete time state equation using z-

transform

10. Write the state model of the discrete time system?

PART

1. A linear second order single input continuous time system is described by the

following set of differential equations.

)()()(2)(

)(4)(2)(

21

.

2

21

.

1

tutXtXtX

tXtXtX

Comment on the controllability and stability of the system.

2. The state space representation of a second order system is

utxxx

utxx

)(2

)(

21

.

2

1

.

1

State whether the system is controllable.

3. A system is described by

XY

UXX

01

1

0

11

11.

Check the controllability and observability of the system

4. A control system has a transfer function given by G(s) = 2)2)(1(

3

ss

s

Page 52: Modern Control System (BE)

52

Unit IV

NONLINEAR SYSTEMS

Introduction to Nonlinear Systems

It has been mentioned earlier that a control system is said lo be linear if

it obeys law of superposition. Most of the control systems are nonlinear in

nature and are treated to be linear, under certain approximation, from case of

analysis point of view. Let us discuss now the properties of nonlinear systems.

In practice nonlinearities may exist in the systems inherently or may be

purposely introduced in the systems, to improve the performance. Hence

knowledge of properties of nonlinear systems and various nonlinearities

is important.

Properties of Nonlinear Systems

The various characteristics of nonlinear systems are,

The most important characteristics of a nonlinear system is that it does not

obey the law of superposition. Hence its behavior with respect to standard test

inputs cannot be used as base to analyses its behavior with respect to other

inputs. Its response is different for different amplitudes of input signals. Hence

while doing the analysis of nonlinear system, along with the mathematical model

of the system, it is necessary to have information about amplitudes of the

probable inputs, initial conditions etc. This makes the analysis of the nonlinear

system difficult.

Linear system gives sinusoidal output for a sinusoidal input, may be

introducing a phase shift. But nonlinear system produces higher harmonics and

sometimes the sub harmonics. Hence for sinusoidal input, the output of a

nonlinear system is generally non sinusoidal. The output consists of frequencies

which are multiples of the input frequency i.e. harmonics. The sub harmonics

Types of nonlinearity – Typical examples – Phase-plane analysis – Singular points – Limit

cycles – Construction of phase trajectories – Describing function method – Basic concepts –

Dead Zone – Saturation – Relay – Backlash – Liapunov stability analysis – Stability in the sense

of Liapunov – Definiteness of scalar functions – Quadratic forms – Second method of Liapunov

– Liapunov stability analysis of linear time invariant systems and non-linear system

Page 53: Modern Control System (BE)

53

means the presence of frequencies which are lower than the input

frequency. The input and output relations are not linear.

In linear system,the sinusoidal oscillations depend on the input amplitude and

the initial conditions. But in a nonlinear system, the periodic oscillations may

exist which are not dependent on the applied input and other system

parameter variations. In nonlinear system, such periodic oscillations are

nonsinusoidal having fixed amplitude and frequency. Such oscillations arc

called limit cycles in case of nonlinear system.

Another important phenomenon which exists only in case of nonlinear system

is jump resonance. This can be explained by considering a frequency response.

The Fig. (a) Shows the frequency response of a linear system which shows

that output varies continuously as the frequency changes. Similarly though

frequency us increased or decreased, the output travels along the same curve

again and again. But in case of a nonlinear system, if frequency is increased,

the output shows discontinuity i.c. it jumps at a certain frequency. And if

frequency is decreased, it jumps back but at different frequency. This is shown

in the fig.

There is no definite criterion for judging the stability of the nonlinear

system. The analysis and design techniques of linear systems cannot be

applied to the nonlinear system.

Types of nonlinearities

The nonlinearities can be classified as incidental and intentional.

The incidental nonlinearities are those which are inherently present in the system.

Common examples of incidental nonlinearities are saturation, dead zone,

Page 54: Modern Control System (BE)

54

coulomb friction, stiction, backlash, etc.

The intentional nonlinearities are those which are deliberately inserted in the

system to modify system characteristics. The most common examples of this type

of nonlinearity is a relay.

In many cases the system presents a nonlinear phenomenon which is fully

characterised by it static characteristics, i.e., its dynamics can be neglected

Saturation

In this type of nonlinearity the output is proportional to input for a limited

range of input signals. When the input exceeds this range, the output tends to become

nearly constant as shown in the fig.

Saturation

Deadzone

The deadzone is the region in which the output is zero for a given input. Many

physical devices do not respond to small signals, i.e., if the input amplitude is less than

some small value, there will be no output. The region in which the output is zero is called

deadzone. When the input is increased beyond this deadzone value, the output will be

linear.

Dead zone

Page 55: Modern Control System (BE)

55

Friction

Friction exists in any system when there is relative motion between contacting surfaces.

The different types of friction are viscous friction, coulomb friction and stiction.

Stiction

The viscous friction is linear in nature and the frictional force is directly proportional to

relative velocity of the sliding surface.

Relay

Page 56: Modern Control System (BE)

56

Phase plane analysis

Objectives:

- Use eigenvalues and eigenvectors of the Jacobian matrix to characterize the phase

plane behavior.

- Predict the phase-plane behavior close to an equilibrium point, based on the

- Linearized model at that equilibrium point.

- Predict qualitatively the phase-plane behavior of the nonlinear system, when there

are multiple equilibrium points.

Phase-plane analysis

Phase plane analysis is a graphical method for studying second-order systems. This

chapter’s objective is to gain familiarity of the nonlinear systems through the simple

graphical method.

Concepts of Phase Plane Analysis

Phase portraits

The phase plane method is concerned with the graphical study of second-order autonomous

systems described by

Where

x1, x2 : states of the system

f1, f2: nonlinear functions of the states

Geometrically, the state space of this system is a plane having x1, x2 as

coordinates. This plane is called phase plane. The solution of (2.1) with time varies from zero

to infinity can be represented as a curve in the phase plane. Such a curve is called a phase

plane trajectory. A family of phase plane trajectories is called a phase portrait of a system.

Example1

Phase portrait of a mass-spring system as shown in the fig.

Solution

The governing equation of the mass-spring system in Fig (a) is the familiar linear second-

order differential equation

Page 57: Modern Control System (BE)

57

The governing equation of the mass-spring system in Fig (a) is the familiar linear second-

order differential equation

Assume that the mass is initially at rest, at length x0. Then the solution of this equation is

Eliminating time t from the above equations, we obtain the equation of the trajectories

This represents a circle in the phase plane. Its plot is given in fig (b)

The nature of the system response corresponding to various initial conditions is directly

displayed on the phase plane. In the above example, we can easily see that the system

trajectories neither converge to the origin nor diverge to infinity. They simply circle around

the origin, indicating the marginal nature of the system’s stability. A major class of second-

order systems can be described by the differential equations of the form

Page 58: Modern Control System (BE)

58

In state space form, this dynamics can be represented with x1 = x and x2 = x& as follows

Singular points

A singular point is an equilibrium point in the phase plane. Since equilibrium point is defined

as a point where the system states can stay forever,

Example 2

A nonlinear second-order system

The system has two singular points, one at (0,0) and the other at (−3,0) . The motion

patterns of the system trajectories in the vicinity of the two singular points have different

natures. The trajectories move towards the point x = 0 while moving away from the point x =

−3.

Constructing Phase Portraits

There are a number of methods for constructing phase plane trajectories for linear or

nonlinear system, such that so-called analytical method, the method of isoclines, the delta

method, Lienard’s method, and Pell’s method.

Analytical method

Page 59: Modern Control System (BE)

59

There are two techniques for generating phase plane portraits analytically. Both

technique lead to a functional relation between the two phase variables x1 and x2 in the form

g(x1, x2 ) = 0 (2.6) where the constant c represents the effects of initial conditions (and,

possibly, of external input signals). Plotting this relation in the phase plane for different initial

conditions yields a phase portrait.

The first technique involves solving (2.1) for x1 and x2 as a function of time t , i.e., x1(t) =

g1(t) and x2 (t) = g2 (t) , and then, eliminating time t from these equations. The second

technique, on the other hand, involves directly eliminating the time variable, by noting that

and then solving this equation for a functional relation between x1 and x2 . Let us use this

technique to solve the mass spring equation again.

The first case corresponds to a node.

Stable or unstable node (Fig.a -b)

A node can be stable or unstable:

λ1,λ2 < 0 : singularity point is called stable node.

λ1,λ2 > 0 : singularity point is called unstable node.

There is no oscillation in the trajectories.

Saddle point (Fig.c)

The second case (λ1 < 0 < λ2) corresponds to a saddle point. Because of the unstable pole λ2

almost all of the system trajectories diverge to infinity.

Page 60: Modern Control System (BE)

60

Stable or unstable locus (Fig.d-e)

The third case corresponds to a focus.

Re(λ1,λ2 ) < 0 : stable focus

Re(λ1,λ2 ) > 0 : unstable focus

Center point (Fig.f)

The last case corresponds to a certain point. All trajectories are ellipses and the singularity

point is the centre of these ellipses.

⊗ Note that the stability characteristics of linear systems are uniquely determined by the

nature of their singularity points. This, however, is not true for nonlinear systems.

Page 61: Modern Control System (BE)

61

Limit cycle

In the phase plane, a limit cycle is defined as an isolated closed curve. The trajectory

has to be both closed, indicating the periodic nature of the motion, and isolated, indicating the

limiting nature of the cycle (with nearby trajectories converging or diverging from it).

Depending on the motion patterns of the trajectories in the vicinity of the limit cycle, we can

distinguish three kinds of limit cycles.

Limit cycle can be a drawback in control systems:

Instability of the equilibrium point

Wear and failure in mechanical systems

Loss of accuracy in regulation

• Stable Limit Cycles: all trajectories in the vicinity of the limit cycle converge to it as t →∞

(Fig.a).

• Unstable Limit Cycles: all trajectories in the vicinity of the limit cycle diverge to it as

t →∞ (Fig.b)

• Semi-Stable Limit Cycles: some of the trajectories in the vicinity of the limit cycle

converge to it as t →∞ (Fig.c)

Difference between center and limit cycle

Center trajectories can be found in the linear or linearized systems with the largest real part of

the eigenvalues of zero value (in marginal point.)

- à depend on the initial conditions

Limit cycle can occur in nonlinear systems:

- à isolated closed orbit(related to Hopf bifurcation)

Page 62: Modern Control System (BE)

62

Center Limit Cycle

Describing function method

. . •

Of all the analytical methods developed over the years for nonlinear systems. the describing

function method is generally agreed upon as being the most practically useful. It is an

approximate method, but experience with real systems and computer simulation results, shows

adequate accuracy in many cases. The method predicts whether limit cycle oscillations will exist

or not, and gives numerical estimates of oscillation frequency and amplitude when limit cycles

are predicted. Basically, the method an approximate extension of frequency-response methods

(including Nyquist stability criterion) to nonlinear systems.

To discuss the basic concept underlying the describing function analysis. Let us consider the

block diagram of a nonlinear system shown in Fig. 9.5. Where the blocks GO) and G2(s) represent

the linear elements. While the block N represent, the nonlinear element.

The describing function method provides a "linear approximation" to the nonlinear element

based on the assumption that the input to the nonlinear element so sinusoid of known,

constant amplitude. The fundamental harmonic of the element's output is compared with the

input sinusoid, to determine the steady-state amplitude and phase relation. This relation is the

describing function for the nonlinear element. The method can, thus, be viewed as "harmonic

linearization" of a nonlinear element.

The describing function method is based on the Fourier series. A review of the Fourier series

will be in order here.

Page 63: Modern Control System (BE)

63

Fourier series

We begin with the definition of a periodic signal. A signal y(t) is said to be periodic with the

period if y(t+T) =y(t) for every value of t. The smallest positive value of T for which y(t + )

= y(t) is called fundamental period ofy(t). We denote the fundamental period as T0.Obviously,

2 T0 is also a period of y(t), and so is any integer multiple of T0.A periodic signal y(t) may be

represented by the series

The term for n = 1 is called fundamental or first- harmonic, and always has the same

frequency as the repetition rate of the original periodic waveform; whereas n = 2, 3....,

give second, third. and so forth harmonic frequencies as integer multiples of the

fundamental frequency.

Certain simplifications are possible when y(t) has a symmetry clone type or another.

The describing Function approach to the analysis of steady-state oscillations in nonlinear

systems is an approximate tool to estimate the limit cycle parameters.

It is based on the following assumptions

Page 64: Modern Control System (BE)

64

There is only one single nonlinear component

The nonlinear component is not dynamical and time invariant

The linear component has low-pass filter properties

The nonlinear characteristic is symmetric with respect to the origin

There is only one single nonlinear component

The system can be represented by a lumped parameters system with two main blocks:

•The linear part

•The nonlinear part

The nonlinear component is not dynamical and time invariant

The system is autonomous.

All the system dynamics is concentrated in the linear part

So that classical analysis tools such as Nyquist and Bode plots can be applied.

The linear component has low-pass filter properties. This is the main assumption that allows

for neglecting the higher frequency harmonics that can appear when a nonlinear system is

driven by a harmonic signal

The more the low-pass filter assumption is verified the more the estimation error affecting the

limit cycle parameters is small.

Page 65: Modern Control System (BE)

65

The nonlinear characteristic is symmetric with respect to the origin. This guarantees that the

static term in the Fourier expansion of the output of the nonlinearity, subjected to an

harmonic signal, can be neglected

Such an assumption is usually taken for the sake of simplicity, and it can be relaxed.

Ideal relay

The negative reciprocal of the DF is the negative real axis in backward direction. A limit

cycle can exist if the relative degree of G(jω) is greater than Two

The oscillation frequency is the critical frequency ωc of the linear system and the

Oscillation magnitude is proportional to the relay gain M.

Liapunov’s Stability Analysis

The state equation for a general time invariant system has the form x = f (x,

u). If the input u is constant then the equation will have form x = F(x).

For this system, the points, at which derivatives of all state variables are

zero, are the singular points.

These singular points are nothing but equilibrium points where the system

stays if it is undisturbed when the system is placed at these points.

Page 66: Modern Control System (BE)

66

The stability of such a system is defined in two different ways. If the

input to the system is zero with arbitrary initial conditions, the resulting

trajectory in phase-plane, discussed in earlier chapter, tends towards the

equilibrium state.

If tile input to the system is provided then the stability is defined as for

bounded input, the system output is also bounded.

For linear systems with non-zero eigen values, there is only one

equilibrium state and the behaviour of such systems about this

equilibrium state totally determines the qualitative behaviour in the

entire state space.

In case of nonlinear systems, the behaviour for small deviations about the

equilibrium point is different from that for large deviations.

Hence local stability for such systems does not indicate the overall

stability in the state space. Also the non-linear systems having multiple

equilibrium states, the trajectories move from one equilibrium point and

tend to other with time.

Thus stability in case of non-linear system is always referred to

equilibrium state instead of global term stability which is the total stability

of the system.

In case of linear control systems, many of the stability criteria such as

Routh's stability test. Nyquist stability criterions etc. are available. But

these cannot be applied (or non-linear systems.

The second method of Liapunov which is also called direct method of

Liapunov is the most common method for obtaining the stability of non-

linear systems.

This method is equally applicable to time varying systems, stability

analysis of linear, time in variant systems and for solving quadratic

optimal control problem.

Stability in the Sense of Liapunov

Consider a system defined by the state equation ),(.

txfx .Let us assume

that this system has a unique solution starting at the given initial condition. Let us

Page 67: Modern Control System (BE)

67

consider this solution as ):( 0,0 txtF where 0xx at 0tt and t is the observed time.

0000 ),:( xtxtF

If we consider a state ex for system with equation ),(.

txfx in such a way that

0),( txf e for all t then this ex is called equilibrium state. For linear, time

invariant systems having A non-singular, there is only one equilibrium state while

there are one or more equilibrium states if A is singular.

In case of non-linear systems as we have seen previously there are more than

one equilibrium states. The Isolated equilibrium states that is isolated from each

other can be shifted to origin i.e. f(0, t) = 0 by properly shifting the coordinates.

These equilibrium states can be obtained from the solution of equation f(x.. t) = 0.

Now we will consider the stability analysis of equilibrium states at the origin. We

will consider a spherical region of radius R about an equilibrium state ex ,. Such that

Any equilibrium state ex of the system ),(.

txfx is said to be stable in the

sense of Liapunov if corresponding to each S( ) there is S ( )such that trajectories

staring in S( ) do not leave S ( ) as time t increases indefinitely. The real

number depends on and in general also depends on t0. If does not depend on

t0, the equilibrium state is said to be uniformly stable.

The region S( ) must be selected first and for each S( ) , there must be a

region S( ) in such a way that the trajectories staring within S( ) do not leave S( )

as time t progresses.

There are many types of stability definitions such as asymptotic stability,

asymptotic stability in large. We will also see the definition of instability along

with definitions of these types of stability.

Page 68: Modern Control System (BE)

68

Definiteness of scalar function

Positive Definiteness

A scalar function F(x) is said to be positive definite in a particular

region which includes the origin of state space if F(x) > 0 for all non-zero states

x in that region and F(0) = 0.

Negative Definiteness

A scalar function F(x) is said to be negative definite if - F(x) is positive

definite.

Positive Semidefiniteness

A scalar function F(x) is said to be positive semi definite if it is positive at all states in

the particular region except at the origin and at certain other states where it is zero.

Negative Semidefinite

A scalar function F(x) is said to be negative semidefinite if - F(x) is positive

semidefinite.

Indefiniteness

A scalar function F(x) is said to be indefinite in the particular region if it

assumes both positive and negative values irrespective how small the region is

Quadratic Form

A class of scalar functions which plays important role in Ihe stability analysis based on

Liapunov's second method is the quadratic form

Page 69: Modern Control System (BE)

69

P is real symmetric matrix and x is a real vector.

Liapunov's Second Method

A system which is vibrating is stable if its total energy is continuously

decreasing. This indicates that the lime derivative of the total energy must

be negative.

The energy is decreased till an equilibrium state is reached. The total

energy is a positive definite function

This fact obtained from classical mechanics theory is generalized in Liapunov's

second method. If the system has an asymptotically stable equilibrium stale then Ihe

stored energy decays with increase in time till it attains minimum value at the

equilibrium state.

But there is no simple way for defining an energy function. For purely mathematical

system. This difficulty was overcome as Liapunov introduced Liapunov function

method which is fictitious energy function.

Liapunov functions depend on x1, x2, .. xn and t. It is given as F(x1, x2, ... xn, t) or as

F(x, t). In Liapunov's second method, the sign behaviour of F(x, t) and its time

derivative F(x, t) = dF(x, t)/dt gives as information about stability, asymptotic

stability or instability of an equilibrium state without requiring to solve the equations

directly to get the solution

Liapunov's Stability Theorem

Consider a scalar function V(x), where x is n vector and is positive

definite, then the states x that satisfy V(x) = C, where C is a positive constant, lie

on a closed hyper surface in n dimensional slate space at least in the

neighborhood of origin. This is shown in the Fig.

If V(x) is a positive definite function obtained for a given system such that

its time derivative taken along the trajectory is always negative then V(x) becomes

smaller and smaller in terms of C and finally reduced to zero as x reduces to

zero. This indicates asymptotic stability of the origin. Liapunov's main stability

theorem is based on this and gives a sufficient condition for asymptotic stability.

Page 70: Modern Control System (BE)

70

Liapunov's stability theorem is as given below. Consider a system

described by equation x » f(x, t) where f(o, t) = 0 for all L If there exists a

scalar function V(x,t) having continuous first partial derivatives and

satisfying the conditions such as V(x, t) is positive definite and V(x, t) is

negative definite then the equilibrium state at the origin is uniformly

asymptotically stable.

Consider the system described by x = f(x, t) where f (0, t) = 0 for all If

there exists a scalar function V(x, t) having continuous first partial derivatives

and V(x, t) is positive definite, V (x, t) is negative semidefinite V (0 (t: xg, tg),

t) docs not vanish identically in t a t for any t0 and any Xg * 0 where 0 (t: Xg,

tg) denotes or indicates the solution starting from Xg at tg then the

equilibrium state at origin of the system is uniformly asymptotically stable in

the large.

The equilibrium state at origin is unstable when there exists a scalar

function U(x,t) having continuous, first partial derivatives and satisfying the

conditions U (x, t) is positive definite in some region about the origin and U (x, t)

is positive definite in the same region.

Stability of Linear and Nonlinear Systems

If the equilibrium state in case of linear, time invariant system is

asymptotically stable locally then it is asymptotically stable in the large. But

in case of a nonlinear system, the equilibrium state has to be

asymptotically stable in the large for the state to be locally asymptotically

stable. Hence the asymptotic stability of the equilibrium state of linear, time

Page 71: Modern Control System (BE)

71

invariant systems and those of nonlinear systems is different.If it is required to

ent the asymptotic stability of any equilibrium state for a nonlinear system

then the stability analysis of linearized models of non-linear systems is

totally insufficient. The nonlinear systems are to be tested without making

them linearized.

The Direct Method of Liapunov and the Linear System

For linear systems, Liapunov's direct method proves to be a simple

method for stability analysts. Use of Liapunov's method for linear systems

is helpful in extending the thinking towards nonlinear systems.

Consider linear system described by state equaion

The linear system described by above equation is asymptotically stable in the

large at the origin if and only if for any symmetric, posiive definite matrix

Q, there exists a symmetic posiive definite matix P which is the unique

soluion A P + PA = - Q.

The proof of above theorem can be given. For this wc will assume the

symmetic positive deinite matrix P exists which Ls the unique solution of the

equaion V(x) = xT Px.

Consider the scalar (unction, V(x) = xT Px

Let norm of x define as

The system is therefore asymptotically stable in the large at the origin. The result is also

necessary. To prove this, assume that the system is asymptotically stable and P is

negative definite

Page 72: Modern Control System (BE)

72

.

This is the contradiction as V(x) = xT

Px satisfies instability theorem. Hence the

conditions for the positive definiteness of P are necessary and sufficient for asymptotic

stability of the system.

The Liapunov's direct method applied to linear time invariant systems is same as the

Hurwitz stability criterion.

Example

Show that the following quadratic form is positive definite

Solution

The above given V(s) can be written as

Applying Sylvester's criterion we have,

As all the successive principal minors of the matrix p are positive V(x) is positive

definite.

Example

Investigate the stability of the following non-linear system using direct method of Liaupnov.

Given that

Let the Liapunov function be,

Page 73: Modern Control System (BE)

73

It can be seen that .

V < 0 for all non-zero values of xi and x2. Hence the function is negative

definite. Therefore the origin of the system is asymptotically stable in large.

UNIT IV

NONLINEAR SYSTEMS

PART A

1. What are linear and nonlinear systems? Give examples.

2. How nonlinearities are introduced in the systems?

3. How the nonlinearities are classified? Give examples.

4. What is the difference between phase plane and describing function methods of analysis?

5. Write any two properties of nonlinear systems?

6. What is jump resonance?

7. What are limit cycles?

8. What is saturation?

9. What is describing function?

10. Write the describing function of dead zone and saturation nonlinearity.

PART B

11. Write the describing function for the following

(i) Backlash nonlinearity

(ii) Relay with dead zone

12. Construct phase trajectory for the system described by the equation21

21

1

2 34

xx

xx

dx

dx.

Comment on the stability of the system.

13. Draw the phase trajectory of the system described by the equation

02...

xxx .comment on the stability of the system.

Page 74: Modern Control System (BE)

74

UNIT V

MIMO SYSTEMS

MIMO System Model

We consider a MINIO system with a transmit array of MT antennas and a receive array

of MR antennas. The block diagram of such a system is shown in Figure. The transmitted

matrix is a MT x 1 column matrix s where s i is the ith component, transmitted from antenna i.

We consider the channel to be a Gaussian channel such that the elements of s are considered to

be independent identically distributed (i.i.d.) Gaussian variables. If the channel is unknown at

the transmitter, we assume that the signals transmitted from each antenna have equal powers of

Es/MT. The covariance matrix for this transmitted signal is given by

Where Es is the power across the transmitter irrespective of the number of antennas and MT , is

an MT *

MT identity matrix. The transmitted signal bandwidth is so narrow that its frequency

response can be considered flat (i.e., the channel

Models of MIMO system – Matrix representation – Transfer function representation –

Poles and Zeros – Decoupling – Introduction to multivariable Nyquist plot and singular

values analysis – Model predictive control

Page 75: Modern Control System (BE)

75

memory less). The channel matrix H is a Kt x NIT complex matrix. The component 17,,i of

the matrix is the fading coefficient from the jth transmit antenna to the ith receive antenna.

We assume that the received power for each of the receive antennas is equal to the total

transmitted power F. This implies we ignore signal attenuation, antenna gains, and so on.

Thus we obtain the normalization constraint for the elements of H, for a deterministic

channel as

If the channel elements are not deterministic but random, the normalization will apply to the

expected value. We assume that the channel matrix is known at the receiver but unknown at

the transmitter. The channel matrix can he estimated at the receiver by transmitting a training

sequence. If we require the transmitter to know this channel, then we need to communicate

this information to the transmitter via a feedback channel. The elements of H can be

deterministic or random. The noise at the receiver is another column matrix of size MR X 1,

denoted by n. The components of n are zero mean circularly symmetrical complex Gaussian

(ZMCSCG) variables. The covariance matrix of the receiver noise is

If there is no correlation between components of n, the covariance matrix is obtained as

Page 76: Modern Control System (BE)

76

Each of the MR receive branches has identical noise power of No. The receiver operates on

the maximum likelihood detection principle over MR receive antennas. The received signals

constitute a MR X 1 column matrix denoted bye, where each complex component refers to a

receive antenna. Since we assumed that the total received power per antenna is equal to the

total transmitted power, the SNR can be written as

Matrix representation

Figure shows a linear dynamic MIMO filter. Its array of K-inputs, after z-transforming, can

be represented by the column vector [F(z)]. Its array of outputs, having the same number of

elements as the input array, is represented by the column vector [G(z)]. The transfer function

of the MIMO filter is represented by a square K x K matrix of transfer functions

Page 77: Modern Control System (BE)

77

The output vector can be expressed as

Each output is a linear combination of filtered versions of all the inputs. The transfer function

from input j to output i is Hij(z).

A schematic diagram of [H(z)] is shown in Fig.(a). The signal path from input line j to output

line i is illustrated in Fig.(b). A block diagram of the MIMO filter is shown in Fig.(c). The

input vector is [F(z)]. The output vector [G(z)] is equal to [H(z)][F(z)]. The overall transfer

function of the system is [H(z)].

Transfer function representation

A multivariable process admits nu inputs and ny outputs. In general, the number of inputs

should be larger than or equal to the number of outputs so that the process is controllable.

Thus, we will assume nu > ny. The system is supposed to have been identified in continuous

time by transfer functions. In general, this identification is performed by sequentially

imposing signals such as steps on each input ui (i = 1,..., nu ) and recording the corresponding

vector of the responses yij (j = 1, ... ,ny). From each input-output couple (ui,yij), a transfer

function is deduced by a least-squares procedure.

In open loop, the ny outputs yi, are linked to the nu, inputs uj, and to the nd disturbances dk by

the following set of ny linear equations

Page 78: Modern Control System (BE)

78

This will be written in open loop under condensed matrix form as

Where y is the output vector, u is the input vector and d is the disturbance vector (the

modelled disturbances), Gu is the rectangular matrix ny x nu the elements of which are the

input-output transfer functions, and Gd is the rectangular matrix ny x nd, the elements of

which are the disturbance-output transfer function.

Poles and Zeros

As for single-input single output (SISO) systems, poles and zeros determine the stability.

Controllability and observability of a multivariable system. For SISO system, zero, are the

zeros of the numerator polynomial of the scalar transfer function, whereas poles are the zeros

of the denominator polynomial. For multi-input multiple output systems, the transfer function

is not scalar and it is no longer sufficient to determine the zeros and poles of individual

entries of the transfer function matrix. In fact element zeros do not play a major role in

characterizing multivariable systems and their properties beyond their effect on the shape of

the response of the system.

Types of multivariable zeros

1. Input-decoupling zeros, which correspond to uncontrollable modes

2 Output-Decoupling zeros, which correspond to unobservable modes

3. Input-output decoupling zeros

Decoupling

Page 79: Modern Control System (BE)

79

The goal of decoupling control is to eliminate complicated loop interactions so that a change

in one process variable will not cause corresponding changes in other process variables. To

do this a non-interacting or decoupling control scheme is used. In this scheme, a

compensation network called a decoupler is used right before the process. This decoupler is

the inverse of the gain array and allows for all measurements to be passed through it in order

to give full decoupling of all of the loops. This is shown pictorially below.

Model predictive control

Model Predictive Control (MPC) originated in the late seventies and has developed

considerably since then. The term Model Predictive Control does not designate a specific

control strategy but rather an ample range of control methods which make explicit use of a

model of the process to obtain the control signal by minimizing an objective function. These

design methods lead to controllers which have practically the same structure and present ad-

equate degrees of freedom. The ideas, appearing in greater or lesser degree in the predictive

control family; are basically:

• Explicit use of a model to predict the process output at future time instants (horizon);

• Calculation of a control sequence minimizing an objective function; and

• receding strategy, so that at each instant the horizon is displaced towards the future, which

involves the application of the first control signal of the sequence calculated at each step.

The various MPC algorithms (also called receding horizon Predictive Control or RHPC) only

differ amongst themselves in the model used to rep-resent the process and the noises and cost

function to be minimized. This type of control is of an open nature, within which many works

have been developed and are widely received by the academic world and industry,. There are

Page 80: Modern Control System (BE)

80

many applications of predictive control successfully in use at the current time, not only in the

process industry but also applications to the control of other processes ranging from robots.

Applications in the cement industry drying towers, and robot arms are described in (54),

whilst developments for distillation columns, PVC plants, steam generators, or servos. The

good performance of these applications shows the capacity of the MPC to achieve highly

efficient control systems able to operate during long periods of time with hardly any

intervention.

In order to implement this strategy, the basic structure shown in Figure is used. A model is

used to predict the future plant outputs, based on past and current values and on the proposed

optimal future control actions. These actions are calculated by the optimizer taking into

account the cost function (where the future tracking error is considered) as well as the

constraints. The process model plays, in consequence, a decisive role in the controller. The

chosen model must be able to capture the process dynamics to precisely predict the future

outputs and be simple to implement and understand. As MPC is not a unique technique but

rather a set of different methodologies, there are many types of models used in various

formulations. One of the most popular in industry is the Truncated Impulse Response Model,

which is very simple to obtain as it only needs the measurement of the output when the

process is excited with an impulse input. It is widely accepted in industrial practice because it

Page 81: Modern Control System (BE)

81

is very intuitive and can also be used for multivariable processes, although its main

drawbacks are the large number of parameters needed and that only open-loop stable

processes can be described this way. Closely related to this kind of model is the Step

Response Model, obtained when the input is a step.

UNIT V

MIMO SYSTEMS

PART A

1What is state and state variable?

2.What is a state vector?

3.What is state space?

4.What is input and output space?

5.What are the advantages of state space modeling using physical variable?

6.What are phase variables?

7.What is the advantage and the disadvantage in canonical form of state model?

8.Write the solution of discrete time state equation?

9.Write the expression to determine the solution of discrete time state equation using z-

transform

10.Write the state model of the discrete time system?

PART B

1. A linear second order single input continuous time system is described by the

following set of differential equations.

)()()(2)(

)(4)(2)(

21

.

2

21

.

1

tutXtXtX

tXtXtX

Comment on the controllability and stability of the system.

2. The state space representation of a second order system is

utxxx

utxx

)(2

)(

21

.

2

1

.

1

State whether the system is controllable.

3.. A system is described by

Page 82: Modern Control System (BE)

82

XY

UXX

01

1

0

11

11.

Check the controllability and observability of the system

4. A control system has a transfer function given by G(s) = 2)2)(1(

3

ss

s

Page 83: Modern Control System (BE)

83

Page 84: Modern Control System (BE)

84