February 2019 Technical Data Submittal Document Model GPW Full Service Reduced Voltage Wye-delta Closed Electric Fire Pump Controller Contents: Data Sheets Dimensional Data Wiring Schematics Field Connections Project: Customer: Engineer: Pump Manufacturer: The drawings included in this package are for controllers covered under our standard offering. Actual AS BUILT drawings may differ from what is shown in this package. Note:
13
Embed
Model GPW - Tornatech...Modbus with RTU frame format and RS485 connection D27 Motor heater connection (external single phase power source and heater on/off contact) D27A Motor heater
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
The drawings included in this package are for controllers covered under our standard offering. Actual AS BUILT drawings may differ from what is shown in this package.
Note:
2
Technical DataModel GPW Electric Fire Pump Controller
This is a Marketing document. Please consult factory if additional information is required. Manufacturer reserves the right to modify this information without noticeFebruary 2019
Standard,Listings,
Approvals andCertifications
Built to NFPA 20 (latest edition)
Underwriters Laboratory (UL) • UL218 - Fire Pump Controllers• CSA C22.2 No. 14 Industrial Control Equipment
FM Global Class 1321/1323New York City Accepted for use in the City of New York by the Department of BuildingsSeismic Certification See page 7 for detailsOptional CE Mark Various EN, IEC & CEE directives and standards
Enclosure
Protection Rating□ Standard: NEMA 2 (IP31)Optional□ NEMA 12□ NEMA 3□ NEMA 3R□ NEMA 4
From normalincoming power throughDisconnecting Means(IS/CB)* M
T2
T1
T31M
T4
T6
T52M
1S
2S
RES
RES
RES
1M
CR4
2M
CR5
1S
2M(LB)
1S
3L1
3L2
3L3
2S
2S(LB)
CR3A
CR3A
2M(LB)
3L1
3L2
3
Technical DataModel GPW Electric Fire Pump Controller
This is a Marketing document. Please consult factory if additional information is required. Manufacturer reserves the right to modify this information without noticeFebruary 2019
Ambient Temperature
Rating
Standard: □ 4°C to 40°C / 39°F to 104°F
Surge Suppression Surge arrestor rated to suppress surges above line voltage
Disconnecting Means
• Isolating switch and circuit breaker assembly:- Door interlocked in the ON position - Isolating switch rated not less than 115% of motor full load current- Circuit breaker continuous rating not less than 115% of motor full load current- Overcurrent sensing non-thermal type, magnetic only- Instantaneous trip setting of not more than 20 times the motor full load current
• Common flange mounted operating handle Service Entrance
Rating Suitable as service entrance equipment
Emergency Start Handle
• Flange mounted • Integrated limit switch• Pull and latch activation • Across the line start (direct on line)
Locked Rotor Protector
• Operate shunt trip to open circuit breaker • Trip between 8 and 20 seconds• Factory set at 600% of motor full load current
Electrical Readings
• Voltage phase to phase (normal power)• Amperage of each phase when motor is running
Pressure Readings
• Continuous system pressure display• Cut-in and Cut-out pressure settings
Pressure and Event recorder
• Pressure readings with date stamp• Event recording with date stamp• Under regular maintained operation, events are stored in memory for the life of the controller.• Data viewable on operator interface display screen• Downloadable by USB port to external memory device
Pressure Sensing
• Pressure transducer and run test solenoid valve assembly for fresh water application• Pressure sensing line connection 1/2” Female NPT• Drain connection 3/8”• Rated for 0-500PSI working pressure (standard display at 0-300PSI)• Externally mounted with protective cover
Optional: □ 4°C to 55°C / 39°F to 131°FControllers built in Dubai, UAE (Tornatech FZE) are supplied standard with 55°C rating.
4
Technical DataModel GPW Electric Fire Pump Controller
This is a Marketing document. Please consult factory if additional information is required. Manufacturer reserves the right to modify this information without noticeFebruary 2019
Audible Alarm 4” alarm bell - 85 dB at 10ft. (3m)
Visual Indications
• Power available• Motor run• Periodic test• Manual start
Visual & Audible Alarms
Visual• Control voltage not healthy• Invalid cut-in• Lock rotor current• Loss of power• Low ambient temperature• Low water level• Motor trouble• Normal power phase reversal
Visual and audible• Fail to start
Remote Alarm Contacts
DPDT-8A-250V.AC• Power available• Phase reversal• Motor run• Common pump room alarm (field re-assignable)**
• Overvoltage • Undervoltage • Phase unbalance• Low pump room temperature • High Pump room temperature
• Common motor trouble (field re-assignable)**• Overcurrent • Fail to start• Undercurrent • Ground fault
• Free (field programmable)**
**Tornatech reserves the right to use any of these three alarm points for special specific application requirements.
• Pump on demand/Automatic start• Pump room temperature (ºF or ºC)• Lockout
• Pump on demand• Pump room alarm• Service required• Undercurrent• Undervoltage• Check weekly test solenoid• Weekly test cut-in reached
• Overcurrent• Overvoltage• Phase loss L1• Phase loss L2• Phase loss L3• Phase unbalanced• Pressure transducer fault detected
5
Technical DataModel GPW Electric Fire Pump Controller
This is a Marketing document. Please consult factory if additional information is required. Manufacturer reserves the right to modify this information without noticeFebruary 2019
ViZiTouch V2 Operator Interface
• Embedded microcomputer with software PLC logic• 7.0” color touch screen (HMI technology)• Upgradable software• Multi-language
Automatic Start• Start on pressure drop• Remote start signal from automatic device• Deluge valve start
Manual Start• Start pushbutton• Run test pushbutton• Remote start from manual device
Stopping • Manual with Stop pushbutton• Automatic after expiration of minimum run timer ***
Timers Field Adjustable & Visual Countdown
• Minimum run timer ***(off delay)• Sequential start timer (on delay)• Periodic test timer
ActuationVisual Indication
• Pressure• Non-pressure
Mode • Automatic• Non-automatic
***Can only be used if approved by the AHJ
6
Technical DataModel GPW Electric Fire Pump Controller
This is a Marketing document. Please consult factory if additional information is required. Manufacturer reserves the right to modify this information without noticeFebruary 2019
Seismic Certification
Seismic Certification Company
TRU Compliance, LLCA Tobalski Watkins Affiliate TWEI Project No.: 15014
Mounting details Rigid base and wall mounting
Seismic Information
Building Code
Test Criteria
Seismic Parameters SDS z/h IP AFLX-H ARIG-H AFLX-V ARIG-V
IBC 2015, CBC 2016
ICC-ES
AC156
ASCE 7-10 Chapter 13
2.0 1.0 1.5 3.20 2.40 1.33 0.53
3.2 0.0 1.5 3.20 1.28 2.13 0.85
0.1
1.0
10.0
0.1 1.0 10.0
Spe
ctra
l Res
pons
e A
ccel
erat
ion
(g)
Frequency, f (Hz)
RRS for Nonstructural Components Testing
Horiz. Level 1 Vert. Level 1
Notes:• Components are tested in accordance with ICC-ES AC156, IBC 2015 & CBC 2016. • OSHPD Special Seismic Certification Preapproval (OSP)
7
Technical DataModel GPW Electric Fire Pump Controller
This is a Marketing document. Please consult factory if additional information is required. Manufacturer reserves the right to modify this information without noticeFebruary 2019
A4 Flow switch provision
A8 Foam pump application w/o pressure transducer and run test solenoid valve.
A9 Low zone pump control function
A10 Middle zone pump control function
A11 High zone pump control function
A13 Non-pressure actuated controller w/o pressure transducer and run test solenoid valve
A16 Lockout/interlock circuit from equipment installed inside the pump room
B11
Built in alarm panel (120V.AC supervisory power) providing indication for:• Audible alarm & silence pushbutton for motor run, phase reversal, loss of phase.• Pilot lights for loss of phase & supervisory power available
B11B Built in alarm panel same as B11 but 220-240VAC supervisory power
B19A High motor temperature c/w thermoster relay and alarm contacts (DPDT)
B19B High motor temperature c/w PT100 relay and alarm contacts (DPDT)
D26 Modbus with RTU frame format and RS485 connection
D27 Motor heater connection (external single phase power source and heater on/off contact)
D27A Motor heater connection (internal single phase power source and heater on/off contact)
8
Technical DataModel GPW Electric Fire Pump Controller
This is a Marketing document. Please consult factory if additional information is required. Manufacturer reserves the right to modify this information without noticeFebruary 2019
Note: Options chosen from this page are not electrically represented on the wiring schematics in this submittal package.
Technical DataModel GPW Electric Fire Pump Controller
This is a Marketing document. Please consult factory if additional information is required. Manufacturer reserves the right to modify this information without noticeFebruary 2019
PMS 295 PMS 361 Noir
ViZiTouch V2 Operator Interface
Home
®
4
1
5 6 78
32
1 - Color touch screen2 - Onscreen menu • HOME page • ALARM page • CONFIGURATION page • HISTORY page • SERVICE page • MANUAL page • LANGUAGES page
3 - Screen protector 4 - Power LED (3 colors)5 - START button6 - STOP button7 - RUN TEST button8 - USB port
Dimensions Built to the latest edition of the NFPA 20 standard
DD/MM/YYDESCRIPTIONREV.NYC
Dpt of BuildingApproved
Drawing number
Electric Fire Pump Controller Model:GPR/GPW
DI371 /EGPX-CDL
NormalPower and
Motor LeadsEntrance
Voltage Min HP Max HP
208 200
220 - 240 250
380 - 400 - 415 350 450
440 - 480
600 NotApplicable
Projection
Voltage / Power Table
Drawing for information only.Manufacturer reserves the right to modify this drawing without notice.Contact manufacturer for "As Built" drawing.
Notes:
- Protect equipment against drilling chips.- Door swing equal to door width.
- Use watertight conduit and connector only.- Bottom conduit entrance through removable gland plate recommended.
- Standard paint : textured red RAL 3002.- All dimensions are in inches [millimeters].
- Standard NEMA: NEMA 2
- Center of ViZiTouch screen: 61-5/8" [1564] from Bottom.
Sensing Line Connection - 1/2 " F.NPT
Drain - 3/8 " M.TUBE
- Seismic mounting to be rigid wall and base only.
0. First issue 16/11/161. Box Size Revision and Valve Change 21/11/17
500
2. New Logo 10/05/18
DD/MM/YYDESCRIPTIONREV.NYC
Dpt of BuildingApproved
Drawing number
Electric Fire Pump Controller Model:GPW
WS600 /EGPW-
Reduced Voltage / Wye-Delta (Closed Transition)
CDL0 First issue 10/11/16
3L1
3L3
3L2
1L1
1L2
1L3
4 2
** Contact closes when emergency start is in "ON" position
J42
J37
J39
J41
J55
Black
Red
White
3L1
3L2X1
X2
H2
H1
J76
L1
J25
IN1
TB2
TB3
TB4
TB5
TB6
* Remove jumper to use this feature
C
NC
NO
Drawing for information only.Manufacturer reserves the right to modify this drawing without notice.Contact manufacturer for "As Built" drawing.
To CT1-CT2-CT3
To 3L1-3L2-3L3
C
NC
NOJ40TB1
IN2
IN3
IN4
IN5
IN6
IN7
IN8
J14 AI4
-
+
J15 AI3
-
+
J16 AI2
-
+
J17 AI1
-
+
J54LS1
DOWN
J46AB
J43SV
J45ST
J44 24V in
24V out
J47 24VAC
C
NO
NC
C
NO
NC
J4
J3
J2 L1
J53
- +Black
Red
42
UPJ20
J8
12
C
NC
NOC
NC
NO1
2
C
NC
NOC
NC
NO1
2
C
NC
NOC
NC
NO1
2
C
NC
NOC
NC
NO1
2
C
NC
NOC
NC
NO1
2
J36CR4
J38CR5
L2
L3
GF
L2
L3
Blac
k
Whi
te
Blac
k
Whi
te
Whi
te
Blac
k
6465
6667
6869
To J76To J2-J3-J4
3L3
3L13L2
Blue
Brown
Motor Run
Phase Reversal
Pump Room Alarm
Motor Trouble
Remote Manual Start
Lockout
Remote Automatic Start
Deluge Valve
Water Reservoir Low
(Field Programmable)
3L2
3L1
18 20
23 21
17
24
29
28
LS2-1
Wiring schematic Built to the latest edition of the NFPA 20 standard
3
1
J1*
LS1-2LS1-1
J2*
SV1-2SV1-1
CR4-2CR4-1
6869
6667
6465
3L3
3L2
3L1
CR5-2CR5-1
Legend
1M-2M Contactors1S-2S Contactors
AB Alarm BellCB Circuit BreakerCR Control Relay
CT Current TransformerEB Electric I/O BoardIS Isolating Switch
J Jumper
LS Limit SwitchPT Pressure Transducer
RES Primary Resistor
SA Surge Arrester
ST Shunt Trip
SV Solenoid ValveVMB ViZiTouch Main BoardXTR Transformer
Power Available
1 Removed (fail safe) text from Power Available relay 20/02/172 Update Logo 23/04/18
Terminal Diagram and Sizing for Isolating Switch
DD/MM/YYDESCRIPTIONREV.NYC
Dpt of BuildingApproved
Drawing number
Electric Fire Pump Controller Model:GPX
TD602 1/2 /EGPX-
Incoming Power3 Phases
Bonding
L2L1IS1
Ground
L3
Power TerminalsNotes:1 - For proper wire sizing, refer to NFPA70 and NEC (USA) or CEC (Canada) or local code.2 - Controller suitable for service entrance in USA.3 - For more accurate motor connections refer to motor manufacturer or motor nameplate.4 - Controller is phase sensitive. Incoming lines must be connected in ABC sequence.
5 7.5 10 15 20 25
220 to 240
380 to 416
600
440 to 480
208 1x (10 to 1/0)
30 40 50 60
75 100 125 150 200 250 300 350 400 450 500
1x (8 to 1/0)
1x (6 to 1/0)
1x (4 to 1/0)
1x (3 to 1/0)
1x (4 to 1/0)
1x (3 to 1/0)
1x (3 to 1/0)
1x (3 to 1/0)
1x (1 to 250)
1x (1/0 to 250)
1x (250 to 500)
1x (300 to 500)
1x (1 to 250)
1x (2/0 to 250)
1x (3/0 to 250)
1x (350 to 500)
1x (500)
1x (3/0 to 250)
1x (2/0 to 250)
1x (250)
2x (3/0 to 500)
2x (4/0 to 500)
1x (3/0 to 250)
1x (4/0 to 250)
1x (300 to 500)
2x (4/0 to 500)
2x (250 to 500)
1x (250 to 500)
1x (350 to 500)
2x (3/0 to 250)
1x (350 to 500)
2x (3/0 to 250)
2x (4/0 to 500)
2x (3/0 to 250)
2x (4/0 to 500)
2x (300 to 500)
--------
--------
--------
2x (4/0 to 500)
2x (300 to 500)
--------
--------
2x (250 to 500)
--------
--------
2x (300 to 500)
--------
--------
--------
--------
--------
220 to 240
380 to 416
600
440 to 480
208
5 " (127 mm) 8 " (203 mm)
12 " (305 mm)
5 " (127 mm) 8 " (203 mm) 12 " (305 mm)
1x (10 to 1/0)
1x (10 to 1/0)
1x (10 to 1/0)
1x (10 to 1/0)
1x (10 to 1/0)
1x (10 to 1/0)
1x (10 to 1/0)
1x (10 to 1/0)
1x (10 to 1/0)
1x (10 to 1/0)
1x (10 to 1/0)
1x (8 to 1/0)
1x (8 to 1/0)
1x (10 to 1/0)
1x (10 to 1/0)
1x (8 to 1/0)
1x (6 to 1/0)
1x (6 to 1/0)
1x (10 to 1/0)
1x (8 to 1/0)
1x (8 to 1/0)
1x (4 to 1/0)
1x (4 to 1/0)
1x (8 to 1/0)
1x (8 to 1/0)
1x (6 to 1/0)
1x (4 to 1/0)
1x (3 to 1/0)
1x (8 to 1/0)
1x (6 to 1/0)
1x (6 to 1/0)
1x (3 to 1/0)
1x (2 to 1/0)
1x (4 to 1/0)
1x (6 to 1/0)
1x (6 to 1/0)
1x (1 to 250)
1x (1/0 to 250)
1x (2/0 to 250)
1x (3/0 to 250)
1x (3/0 to 250)
1x (4/0 to 250)
2x (350 to 500)
2x (350 to 500)
2x (350 to 500)
Voltage
BendingSpace
HP
HP
2x (400 to 500)
2x (400 to 600)
2x (500 to 600)
2x (500 to 600) 2x (600)
2x (400 to 600) 2x (500 to 600)
2x (400 to 600)
16 " (406 mm)
BendingSpace
BendingSpace
Voltage
BendingSpace
0 First issue 16/03/17 CDL
Built to the latest edition of the NFPA 20 standard
Drawing for information only.Manufacturer reserves the right to modify this drawing without notice.Contact manufacturer for "As Built" drawing.
5 7.5 10 15 20 25
220 to 240
380 to 416
600
440 to 480
208 1x (10 to 1/0)
30 40 50 60
75 100 125 150 200 250 300 350 400 450 500
1x (6 to 1/0)
1x (4 to 1/0)
1x (2 to 1/0)
1x (1 to 1/0)
1x (2 to 1/0)
1x (1 to 1/0)
1x (1/0)
1x (1 to 1/0)
1x (1/0 to 250)
1x (3/0 to 250)
1x (350 to 500)
1x (400 to 500)
1x (2/0 to 250)
1x (3/0 to 250)
1x (250)
1x (500)
1x (250)
1x (3/0 to 250)
1x (350) **
2x (250 to 500)
2x (300 to 500)
1x (4/0 to 250)
1x (400 to 500)
2x (300 to 500)
2x (350 to 500)
1x (350 to 500)
1x (500)
2x (4/0 to 250)
1x (500)
2x (250)
2x (300 to 500)
2x (4/0 to 250)
2x (300 to 500)
2x (400 to 500)
--------
--------
--------
2x (300 to 500)
2x (400 to 500)
--------
--------
2x (350 to 500)
--------
--------
2x (400 to 500)
--------
--------
--------
--------
--------
220 to 240
380 to 416
600
440 to 480
208
5 " (127 mm) 8 " (203 mm)
12 " (305 mm)
5 " (127 mm) 8 " (203 mm) 12 " (305 mm)
1x (10 to 1/0)
1x (10 to 1/0)
1x (10 to 1/0)
1x (10 to 1/0)
1x (8 to 1/0)
1x (10 to 1/0)
1x (10 to 1/0)
1x (10 to 1/0)
1x (10 to 1/0)
1x (10 to 1/0)
1x (10 to 1/0)
1x (6 to 1/0)
1x (6 to 1/0)
1x (8 to 1/0)
1x (10 to 1/0)
1x (6 to 1/0)
1x (4 to 1/0)
1x (4 to 1/0)
1x (8 to 1/0)
1x (6 to 1/0)
1x (6 to 1/0)
1x (3 to 1/0)
1x (3 to 1/0)
1x (6 to 1/0)
1x (6 to 1/0)
1x (4 to 1/0)
1x (2 to 1/0)
1x (1 to 1/0)
1x (6 to 1/0)
1x (6 to 1/0)
1x (4 to 1/0)
1x (1 to 1/0)
1x (1/0)
1x (2 to 1/0)
1x (4 to 1/0)
1x (4 to 1/0)
1x (2/0 to 250)
1x (3/0 to 250)
1x (4/0 to 250)
1x (4/0 to 250)
1x (250)
1x (300) ** or
2x (500)
2x (500)
2x (500)
Voltage
BendingSpace
HP
HP
2x (500)
2x (600)
2x (600) 90°C *
2x (600) 90°C * 2x (600) 90°C *
2x (600) 2x (600) 90°C *
2x (500 to 600)
16 " (406 mm)
BendingSpace
BendingSpace
Voltage
BendingSpace
10 " (254 mm)
1x (250) 90°C *
2x(4/0 to 250) **1x(500) 90°C or
1x (300) ** or1x (250) 90°C *
N/A **
1 General Revision (added AL coverage) 10/07/17
For standard enclosure, use 90°C aluminium wire. Consult Factory for Use of Conductors Rated Lower than 90°C.Consult Factory
***
ALUMINUM CONDUCTORS for Isolating Switch (IS1).Field Wiring According to Bending Space (AWG or MCM). Terminals L1 - L2 - L3
COPPER CONDUCTORS for Isolating Switch (IS1).Field Wiring According to Bending Space (AWG or MCM). Terminals L1 - L2 - L3
2 Revised logo 18/06/18
Terminal Diagram and Sizing For GPP,GPY & GPW
DD/MM/YYDESCRIPTIONREV.NYC
Dpt of BuildingApproved
Drawing number
Electric Fire Pump Controller Model:GPX
TD602 2/2 /EGPX-
5 7.5 10 15 20 25
220 to 240
380 to 416
600
440 to 480
208 1x (12 to 10)
30 40 50 60
75 100 125 150 200 250 300 350 400 450 500
1x (12 to 10)
1x (12 to 10)
1x (12 to 10)
1x (12 to 10)
1x (12 to 10)
1x (12 to 10)
1x (12 to 10)
1x (10)
1x (10)
1x (12 to 10)
1x (12 to 10)
1x (12 to 10)
1x (10)
1x (10)
1x (12 to 10)
1x (12 to 10)
1x (10)
1x (8 to 2)
1x (8 to 2)
1x (10)
1x (10)
1x (10)
1x (8 to 2)
1x (6 to 2)
1x (10)
1x (10)
1x (8 to 2)
1x (6 to 2)
1x (4 to 2)
1x (10)
1x (8 to 2)
1x (8 to 2)
1x (4 to 1/0)
1x (4 to 1/0)
1x (8 to 2)
1x (8 to 2)
1x (6 to 2)
1x (2 to 2/0)
1x (2 to 2/0)
1x (8 to 2)
1x (6 to 2)
1x (4 to 2)
1x (1 to 2/0)
1x (1/0 to 3/0)
1x (6 to 2)
1x (4 to 2)
1x (3 to 1/0)
1x (1/0 to 2/0)
1x (2/0)
1x (4 to 2)
1x (3 to 2/0)
1x (2 to 2/0)
1x (2/0) 90°C *
1x (3/0)
1x (3 to 2/0)
1x (2 to 2/0)
1x (1/0 to 2/0)
1x (2/0) 90°C *
1x (2 to 2/0)
1x (1/0 to 2/0)
1x (300)
1x (300) 90°C *
1x (1/0 to 3/0)
1x (2/0 to 3/0)
1x (3/0) 90°C *
2x (3/0 to 300)
1x (3/0)
2x (4/0 to 300)
2x (4/0 to 300)
--------
--------
--------
2x (3/0 to 300)
--------
--------
2x (4/0 to 300)
--------
--------
2x (3/0 to 300)
--------
--------
2x (4/0 to 300)
--------
--------
--------
220 to 240
380 to 416
600
440 to 480
208
1x (300)
1x (300)
1x (300)
HP
HP
2x (250 to 300)
2x (250 to 350)
2x (300 to 350)
2x (300 to 350) 2x (300 to 350)
2x (250 to 350) 2x (300 to 350)
Voltage
Voltage
0 CDL
Notes:1 - For proper wire sizing, refer to NFPA70 and NEC (USA) or CEC (Canada) or local code.2 - Controller suitable for service entrance in USA.3 - For more accurate motor connections refer to motor manufacturer or motor nameplate.4 - Controller is phase sensitive. Incoming lines must be connected in ABC sequence.
Built to the latest edition of the NFPA 20 standard
Drawing for information only.Manufacturer reserves the right to modify this drawing without notice.Contact manufacturer for "As Built" drawing.
First issue 16/03/171 General Revision (added AL coverage) 10/07/17
5 7.5 10 15 20 25
220 to 240
380 to 416
600
440 to 480
208 1x (14 to 10)
30 40 50 60
75 100 125 150 200 250 300 350 400 450 500
1x (14 to 10)
1x (14 to 10)
1x (14 to 10)
1x (14 to 10)
1x (14 to 10)
1x (14 to 10)
1x (14 to 10)
1x (12 to 10)
1x (12 to 10)
1x (14 to 10)
1x (14 to 10)
1x (14 to 10)
1x (10)
1x (10)
1x (14 to 10)
1x (12 to 10)
1x (12 to 10)
1x (8 to 2)
1x (8 to 2)
1x (12 to 10)
1x (12 to 10)
1x (10)
1x (8 to 2)
1x (8 to 2)
1x (12 to 10)
1x (10)
1x (10)
1x (6 to 2)
1x (6 to 2)
1x (10)
1x (10 to 2)
1x (8 to 2)
1x (6 to 1/0)
1x (6 to 1/0)
1x (10 to 2)
1x (8 to 2)
1x (6 to 2)
1x (4 to 2/0)
1x (4 to 2/0)
1x (8 to 2)
1x (6 to 2)
1x (6 to 2)
1x (3 to 2/0)
1x (2 to 3/0)
1x (8 to 2)
1x (6 to 2)
1x (4 to 1/0)
1x (2 to 2/0)
1x (1 to 2/0)
1x (6 to 2)
1x (4 to 2/0)
1x (4 to 2/0)
1x (1/0 to 2/0)
1x (2/0 to 3/0)
1x (4 to 2/0)
1x (3 to 2/0)
1x (2 to 2/0)
1x (3/0)
1x (3/0 to 300)
1x (2 to 2/0)
1x (3 to 2/0)
1x (1/0 to 2/0)
1x (4/0 to 300)
1x (250 to 300)
1x (2 to 3/0)
1x (1/0 to 3/0)
1x (2/0 to 3/0)
1x (300)
2x (1/0 to 300)
1x (1/0 to 3/0)
1x (2/0 to 3/0)
2x (2/0 to 300)
1x (2/0 to 3/0)
1x (300)
1x (300)
2x (2/0 to 300)
--------
--------
--------
1x (250 to 300)
2x (1/0 to 300)
--------
--------
1x (300)
2x (2/0 to 300)
--------
--------
2x (1/0 to 300)
--------
--------
2x (2/0 to 300)
--------
--------
--------
220 to 240
380 to 416
600
440 to 480
208
1x (4/0 to 300)
1x (4/0 to 300)
1x (4/0 to 300)
HP
HP
2x (3/0 to 300)
2x (3/0 to 350)
2x (4/0 to 350)
2x (4/0 to 350) 2x (4/0 to 350)
2x (3/0 to 350) 2x (4/0 to 350)
Voltage
Voltage
COPPER CONDUCTORS for Motor Connection (1M-2M).Field Wiring According to Bending Space (AWG or MCM). Terminals T1-T2-T3-T4-T5-T6-T7-T8-T9
ALUMINUM CONDUCTORS for Contactor (1M-2M).Field Wiring According to Bending Space (AWG or MCM). Terminals T1-T2-T3-T4-T5-T6-T7-T8-T9
*
1x (300) 90°C *
1x (3/0) 90°C *
1x (300) 90°C *
1x (3/0) 90°C *
1x (300) 90°C *
1x (300) 90°C *
For standard enclosure, use 90°C aluminium wire. Consult Factory for Use of Conductors Rated Lower than 90°C.