Features Wide Range of Temperatures Heavy Duty Self-Contained Replaceable Element Non-Adjustable Rugged Construction Tamper-Proof Operate in Any Position Available for Refrigeration Service 1010 1” NPT 1110 3/4” NPT 1210 1/2” NPT 1010J8 1/2” SAE O-Ring 1010J12 3/4” SAE O-Ring 1010J16 1” SAE O-Ring Fluid Power Energy (FPE) Thermostatic Valves utilize the principle of expanding wax, which in the semi-liquid state undergoes large expansion rates within a relatively narrow temperature range. The self-contained ele- ment activates a stainless steel sleeve, which directs flow. All FPE Thermostatic Valves are factory set at predetermined temperatures: no fur- ther adjustments are necessary. A wide range of temperatures are avail- able for water and oil temperature control applications. When used in a diverting application, on start-up the total fluid flow is rout- ed back to the main system. As fluid temperature rises to the control range, some fluid is diverted to the cooling system. As fluid temperature contin- ues to increase, more flow is diverted. When the thermostat is in a fully stroked condition, all fluid flow is directed to the cooling system. FPE Thermostatic Valves may also be used in a mixing application. In a mixing application, hot fluid enters the “B” port and colder fluid enters the “C” port. The flows mix and the thermostat adjusts to reach the desired temperature, exiting the “A” port. Standard FPE thermostatic valve housings are made from aluminum and grey iron castings, however, ductile iron, bronze, steel and stainless steel housings are available. Optional 1010 features: High over temperature element, plated element. Other options available upon request. FLUID POWER ENERGY , I NC. W229 N591 Foster Court • Waukesha, WI 53186 262 • 548 • 6220 Fax 262 • 548 • 6239 www.fpevalves.com Three-Way Thermostatic Valve MADE IN U. S. A. ISO 9001-2000 Model 1010
24
Embed
Model 101 0 - Fluid · PDF fileFluid Power Energy (FPE) Thermostatic Valves utilize the principle of expanding wax, which in the semi-liquid state undergoes large expansion
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
* (Replace * with body material type; A=Cast Iron, AL=Aluminum, B=Bronze, D=Ductile Iron, S=Steel, SS=Stainless Steel)
To OrderSpecify Model Number, nominal
temperature desired, and housing material. For Model coding information,
visit our website or consult yourfactory representative.
FPE1010-050803
All models
Viton® is a registered trademark of Dupont Dow Elastomers
PART # DESCRIPTION*1010 VALVE BODY (*See table for material)*1020 VALVE COVER (*See table for material)1080 GASKET (Older than 1979)1572** O-RING (Standard material is Buna-N)1071 LIP SEAL1060-Temp THERMOSTAT (Temp to follow dash)1600 HEX BOLT1601 LOCK WASHER1590 NAMEPLATE
FPE Model 1000* Replacement Kit (Includes the following:)1572** O-RING (Standard material is Buna-N)1071 LIP SEAL1060-Temp THERMOSTAT (Temp to follow dash)(For Viton® (V) or Neoprene (E) O-Ring material, replace ** with V or E)
PART # DESCRIPTION*1011 VALVE BODY (*See table for material)*1040 VALVE COVER (*See table for material)1572** O-RING (Standard material is Buna-N)1571 LIP SEAL1560-Temp THERMOSTAT (Temp to follow dash)1600 HEX BOLT1601 LOCK WASHER1590 NAMEPLATE
FPE Model 1500** Replacement Kit (Includes the following:)1572** O-RING (Standard material is Buna-N)1571 LIP SEAL1560-Temp THERMOSTAT (Temp to follow dash)(For Viton® (V) or Neoprene (E) O-Ring material, replace ** with V or E)
PRESSURE RATINGSMATERIAL PSI
A, AL, B 150D 250
S, SS 500
For port sizes not shown consult factory
* (Replace * with body material type; A=Cast Iron, AL=Aluminum, B=Bronze, D=Ductile Iron, S=Steel, SS=Stainless Steel)
1/2” 3/4”
To OrderSpecify Model Number, nominal
temperature desired, and housing material. For Model coding information,
visit our website or consult your factory representative.
FPE1011-050803
1”
All models
1 1/4”
1 1/2”
Viton® is a registered trademark of Dupont Dow Elastomers
Fluid Power Energy (FPE) Thermostatic Valves utilize the principle ofexpanding wax, which in the semi-liquid state undergoes large expansionrates within a relatively narrow temperature range. The self-contained ele-ment activates a stainless steel sleeve, which directs flow. All FPEThermostatic Valves are factory set at predetermined temperatures: no fur-ther adjustments are necessary. A wide range of temperatures are avail-able for water and oil temperature control applications.
When used in a diverting application, on start-up the total fluid flow is rout-ed back to the main system in the three-way valve or blocked by a sleevein the two-way version. As fluid temperature rises to the control range,some fluid is diverted to the cooling system in the three-way valve or todrain in the two-way version. As fluid temperature continues to increase,more flow is diverted. When the thermostat is in a fully stroked condition,all fluid flow is directed to the cooling system in the three-way valve or todrain in the two-way version. FPE Thermostatic Valves may also be usedin a mixing application.
In a mixing application, hot fluid enters the “B” port and colder fluid entersthe “C” port. The flows mix and the thermostat adjusts to reach the desiredtemperature, exiting the “A” port.
FPE Thermostatic Valve Housings are made from cast aluminum or castbronze, with other materials available.
Optional 0750 features: Plated elements and Viton® or Neoprene seals.Other options available upon request.
FLUID POWER ENERGY, INC.W229 N591 Foster Court • Waukesha, WI 53186
PART # DESCRIPTION*0750-1 VALVE BODY (*See table for material)0750-3 CAP0750-4 SPRING0750**-6 O-RING (Standard material is Buna-N)0750-7 SNAP RING0750-9 SLEEVE (Specify weep hole or low flow)0760-Temp THERMOSTAT (Temp to follow dash)0750-10 PLUG (2-way valve only)
FPE Model 0700* Replacement Kit (Includes the following:)0750-4 SPRING0750**-6 O-RING (Standard material is Buna-N)0760-Temp THERMOSTAT (Temp to follow dash)(For Viton® (V) or Neoprene (E) O-Ring material, replace ** with V or E)
PRESSURE RATINGSMATERIAL PSI
AL, B 150
Three-Way Valve Two-Way Valve
For port sizes not shown consult factory
* (Replace * with body material type; AL=Aluminum, B=Bronze)
1/2 3/4
To OrderSpecify Model Number, nominal
temperature desired, and housing material. For Model coding information,
visit our website or consult your factory representative.
FPE-0750-050803
Viton® is a registered trademark of Dupont Dow Elastomers
Fluid Power Energy (FPE) Thermostatic Valves utilize the principle of expand-ing wax, which in the semi-liquid state undergoes large expansion rates with-in a relatively narrow temperature range. The self-contained element activatesa brass or nickel-plated sleeve, which directs flow. All FPE ThermostaticValves are factory set at predetermined temperatures: no further adjustmentsare necessary. A wide range of temperatures are available for water and oiltemperature control applications.
When used in a diverting application, on start-up the total fluid flow is routedback to the main system. As fluid temperature rises to the control range, somefluid is diverted to the cooling system. As fluid temperature continues toincrease, more flow is diverted. When the thermostat is in a fully stroked con-dition, all fluid flow is directed to the cooling system. FPE Thermostatic Valvesmay also be used in a mixing application.
In a mixing application, hot fluid enters the “B” port and colder fluid enters the“C” port. The flows mix and the thermostat adjusts to reach the desired tem-perature, exiting the “A” port.
Standard FPE Thermostatic Valve Housings are made from aluminum andgrey iron castings, however, ductile iron, steel and stainless steel housings areavailable.
Available connections: NPT, SAE O-Ring, 125# FF Flange, 150# RF Flange,300# RF Flange, Navy and Metric Flanges.
Optional Features: Manual Override, High Over Temp elements, Plated ele-ments. Other options available upon request.
FLUID POWER ENERGY, INC.W229 N591 Foster Court • Waukesha, WI 53186
PART # DESCRIPTION*1530 VALVE BODY (*See table for material)*1540 VALVE COVER (*See table for material)1572** O-RING (Standard material is Buna-N)1571 LIP SEAL1560-Temp THERMOSTAT (Temp to follow dash)1600 HEX BOLT1601 LOCK WASHER1590 NAMEPLATE
FPE Model 1500** Replacement Kit (Includes the following:)1572** O-RING (Standard material is Buna-N)1571 LIP SEAL1560-Temp THERMOSTAT (Temp to follow dash)(For Viton® (V) or Neoprene (E) O-Ring material, replace ** with V or E)
PRESSURE RATINGSMATERIAL PSI
A, B 150D 250
S, SS 500SF, SSF 275
SFX, SSFX 720
* (Replace * with body material type; A=Cast Iron, B=Bronze, D=Ductile Iron, S=Steel, SS=Stainless Steel)
To OrderSpecify Model Number, nominal
temperature desired, and housing material. For Model coding information,
visit our website or consult your factory representative.
Fluid Power Energy (FPE) Thermostatic Valves utilize the principle ofexpanding wax, which in the semi-liquid state undergoes large expansionrates within a relatively narrow temperature range. The self-contained ele-ment activates a stainless steel sleeve, which directs flow. All FPEThermostatic Valves are factory set at predetermined temperatures: no fur-ther adjustments are necessary. A wide range of temperatures are avail-able for water and oil temperature control applications.
When used in a diverting application, on start-up the total fluid flow is rout-ed back to the main system. As fluid temperature rises to the controlrange, some fluid is diverted to the cooling system. As fluid temperaturecontinues to increase, more flow is diverted. When the thermostat is in afully stroked condition, all fluid flow is directed to the cooling system. FPEThermostatic Valves may also be used in a mixing application.
In a mixing application, hot fluid enters the “B” port and colder fluid entersthe “C” port. The flows mix and the thermostat adjusts to reach the desiredtemperature, exiting the “A” port.
Standard FPE thermostatic valve housings are made from aluminum andgrey iron castings, however, ductile iron, bronze, steel and stainless steelhousings are available.
* (Replace * with body material type; A=Cast Iron, B=Bronze, D=Ductile, S=Steel, SS=Stainless Steel)
To OrderSpecify Model Number, nominal
temperature desired, and housing material. For Model coding information,
visit our website or consult yourfactory representative.
FPE-2010-050803
*F2010, *F2010X
Flow vs. Pressure Drop
FLOW IN U.S. GPMSAE 10 @ 100° F
1 1/2”
2”
PART # DESCRIPTION*2010 VALVE BODY (*See table for material)*2020 VALVE COVER (*See table for material)1570** O-RING (Standard material is Buna-N)2071 LIP SEAL2050-Temp THERMOSTAT (Temp to follow dash)1600 HEX BOLT1601 LOCK WASHER
FPE Model 2000** Replacement Kit (Includes the following:)1570** BUNA O-RING (Standard material is Buna-N)2071 LIP SEAL2050-Temp THERMOSTAT (Temp to follow dash)(For Viton® (V) or Neoprene (E) O-Ring material, replace ** with V or E)
Viton® is a registered trademark of Dupont Dow ElastomersRecommended Pressure Drop is 2 to 7 PSI
Fluid Power Energy (FPE) Thermostatic Valves utilize the principle ofexpanding wax, which in the semi-liquid state undergoes large expansionrates within a relatively narrow temperature range. The self-contained ele-ment activates a stainless steel sleeve, which directs flow. All FPEThermostatic Valves are factory set at predetermined temperatures: no fur-ther adjustments are necessary. A wide range of temperatures are avail-able for water and oil temperature control applications.
When used in a diverting application, on start-up the total fluid flow is rout-ed back to the main system. As fluid temperature rises to the controlrange, some fluid is diverted to the cooling system. As fluid temperaturecontinues to increase, more flow is diverted. When the thermostat is in afully stroked condition, all fluid flow is directed to the cooling system. FPEThermostatic Valves may also be used in a mixing application.
In a mixing application, hot fluid enters the “B” port and colder fluid entersthe “C” port. The flows mix and the thermostat adjusts to reach the desiredtemperature, exiting the “A” port.
Standard FPE thermostatic valve housings are made from aluminum andgrey iron castings, however, ductile iron, bronze, steel and stainless steelhousings are available.
Optional features: High over temperature element, plated element, manu-al override.
FLUID POWER ENERGY, INC.W229 N591 Foster Court • Waukesha, WI 53186
PART # DESCRIPTION*2012 VALVE BODY (*See table for material)*2013 VALVE BODY W/MOUNTING HOLES*2020 VALVE COVER (*See table for material)2071 LIP SEAL2050-Temp THERMOSTAT (Temp to follow dash)1604 HEX BOLT1605 LOCK WASHER1570** O-RING (Standard material is Buna-N)1590 NAMEPLATE
FPE Model 2000** Replacement Kit (Includes the following:)1570** O-RING (Standard material is Buna-N)2071 LIP SEAL2050-Temp THERMOSTAT (Temp to follow dash)(For Viton® (V) or Neoprene (E) O-Ring material, replace ** with V or E)
*2012, *2012J
* (Replace * with body material type; A=Cast Iron, B=Bronze, D=Ductile, S=Steel, SS=Stainless Steel)
To OrderSpecify Model Number, nominal
temperature desired, and housing material. For Model coding information,
visit our website or consult your factory representative.
FPE-2012-050803
*2012M *F2012 *F2012M *2013, *2013J
Viton® is a registered trademark of Dupont Dow Elastomers
Fluid Power Energy (FPE) Thermostatic Valves utilize the prin-ciple of expanding wax, which in the semi-liquid state under-goes large expansion rates within a relatively narrow temper-ature range. The self-contained nickel-plated element assem-bly activates a sleeve, which directs flow. All FPEThermostatic Valves are factory set at predetermined temper-atures: no further adjustments are necessary. A wide range oftemperatures are available for water and oil temperature con-trol applications.
When used in a diverting application, on start-up the total fluidflow is routed back to the main system. As fluid temperaturerises to the control range, some fluid is diverted to the coolingsystem. As fluid temperature continues to increase, more flowis diverted. When the thermostat is in a fully stroked condition,all fluid flow is directed to the cooling system. FPEThermostatic Valves may also be used in a mixing application.
In a mixing application, hot fluid enters the “B” port and colderfluid enters the “C” port. The flows mix and the thermostatadjusts to reach the desired temperature, exiting the “A” port.
FPE 2014/2015 Thermostatic Valve Housings are made from(WCB) steel.
Optional features available upon request.
FLUID POWER ENERGY, INC.W229 N591 Foster Court • Waukesha, WI 53186
2510 2 1/2” Flange2510M 2 1/2” Flange with Manual Override
Fluid Power Energy (FPE) Thermostatic Valves utilize the principle ofexpanding wax, which in the semi-liquid state undergoes large expansionrates within a relatively narrow temperature range. The self-contained ele-ment activates a stainless steel sleeve, which directs flow. All FPEThermostatic Valves are factory set at predetermined temperatures: no fur-ther adjustments are necessary. A wide range of temperatures are avail-able for water and oil temperature control applications.
When used in a diverting application, on start-up the total fluid flow is rout-ed back to the main system. As fluid temperature rises to the controlrange, some fluid is diverted to the cooling system. As fluid temperaturecontinues to increase, more flow is diverted. When the thermostat is in afully stroked condition, all fluid flow is directed to the cooling system. FPEThermostatic Valves may also be used in a mixing application.
In a mixing application, hot fluid enters the “B” port and colder fluid entersthe “C” port. The flows mix and the thermostat adjusts to reach the desiredtemperature, exiting the “A” port.
Standard FPE thermostatic valve housings are made from aluminum andgrey iron castings, however, ductile iron, bronze, steel and stainless steelhousings are available.
Available Connections: 125# FF Flange, 150# RF Flange, 300# RFFlange, Navy and Metric Flanges.
Optional features: Manual Override, High Over Temp element, Plated ele-ment. Other options available upon request.
Flow vs. Pressure Drop
PRESSURE RATINGSMATERIAL PSI
A, B, D 125S, SS 275
SX, SSX 720
FLUID POWER ENERGY, INC.W229 N591 Foster Court • Waukesha, WI 53186
PART # DESCRIPTION*2510 VALVE BODY (*See table for material)*2520 VALVE COVER (*See table for material)2071 LIP SEAL3080-C GASKET2050-Temp THERMOSTAT (Temp to follow dash)1604 HEX BOLT1605 LOCK WASHER1590 NAMEPLATE
FPE Model 2500 Replacement Kit (Includes the following:)3080-C GASKET(2) 2071 LIP SEAL(2) 2050-Temp THERMOSTAT (Temp to folllow dash)
*2510, *2510X
* (Replace * with body material type; A=Cast Iron, B=Bronze, D=Ductile, S=Steel, SS=Stainless Steel)
To OrderSpecify Model Number, nominal
temperature desired, and housing material. For Model coding information,
visit our website or consult your factory representative.
FPE-2510-050803
*2510M, *2510XM
Recommended Pressure Drop is 2 to 7 PSI
Features
Wide Range of Temperatures
Heavy Duty
Self-Contained
Replaceable Element
Non-Adjustable
Rugged Construction
Tamper-Proof
Operate in Any Position
Compact
Available for Refrigeration Service
3010 3” Flange3010M 3” Flange with Manual Override
Fluid Power Energy (FPE) Thermostatic Valves utilize the principle ofexpanding wax, which in the semi-liquid state undergoes large expansionrates within a relatively narrow temperature range. The self-contained ele-ment activates a stainless steel sleeve, which directs flow. All FPEThermostatic Valves are factory set at predetermined temperatures: no fur-ther adjustments are necessary. A wide range of temperatures are avail-able for water and oil temperature control applications.
When used in a diverting application, on start-up the total fluid flow is rout-ed back to the main system. As fluid temperature rises to the controlrange, some fluid is diverted to the cooling system. As fluid temperaturecontinues to increase, more flow is diverted. When the thermostat is in afully stroked condition, all fluid flow is directed to the cooling system. FPEThermostatic Valves may also be used in a mixing application.
In a mixing application, hot fluid enters the “B” port and colder fluid entersthe “C” port. The flows mix and the thermostat adjusts to reach the desiredtemperature, exiting the “A” port.
Standard FPE thermostatic valve housings are made from aluminum andgrey iron castings, however, ductile iron, bronze, steel and stainless steelhousings are available.
Available Connections: 125# FF Flange, 150# RF Flange, 300# RFFlange, Navy and Metric Flanges.
Optional features: Manual Override, High Over Temp element, Plated ele-ment. Other options available upon request.
FLUID POWER ENERGY, INC.W229 N591 Foster Court • Waukesha, WI 53186
PART # DESCRIPTION*3010 VALVE BODY (*See table for material)*3020 VALVE COVER (*See table for material)2071 LIP SEAL3080-C GASKET2050-Temp THERMOSTAT (Temp to follow dash)1604 HEX BOLT1605 LOCK WASHER1590 NAMEPLATE
FPE Model 3000 Replacement Kit (Includes the following:)3080-C GASKET(2) 2071 LIP SEAL(2) 2050-Temp THERMOSTAT (Temp to follow dash)
*3010, *3010X
* (Replace * with body material type; A=Cast Iron, B=Bronze, D=Ductile, S=Steel, SS=Stainless Steel)
To OrderSpecify Model Number, nominal
temperature desired, and housingmaterial. For Model coding information,
visit our website or consult your factory representative.
FPE-3010-050803
*3010M, *3010XM
Recommended Pressure Drop is 2 to 7 PSI
Features
Wide Range of Temperatures
Heavy Duty
Self-Contained
Replaceable Element
Non-Adjustable
Rugged Construction
Tamper-Proof
Operate in Any Position
Available for Refrigeration Service
4010 4” Flange4010M 4” Flange with Manual Override
Fluid Power Energy (FPE) Thermostatic Valves utilize the principle ofexpanding wax, which in the semi-liquid state undergoes large expansionrates within a relatively narrow temperature range. The self-contained ele-ment activates a stainless steel sleeve, which directs flow. All FPEThermostatic Valves are factory set at predetermined temperatures: no fur-ther adjustments are necessary. A wide range of temperatures are avail-able for water and oil temperature control applications.
When used in a diverting application, on start-up the total fluid flow is rout-ed back to the main system. As fluid temperature rises to the controlrange, some fluid is diverted to the cooling system. As fluid temperaturecontinues to increase, more flow is diverted. When the thermostat is in afully stroked condition, all fluid flow is directed to the cooling system. FPEThermostatic Valves may also be used in a mixing application.
In a mixing application, hot fluid enters the “B” port and colder fluid entersthe “C” port. The flows mix and the thermostat adjusts to reach the desiredtemperature, exiting the “A” port.
Standard FPE thermostatic valve housings are made from aluminum andgrey iron castings, however, ductile iron, bronze, steel and stainless steelhousings are available.
Available Connections: 125# FF Flange, 150# RF Flange, 300# RFFlange, and Navy Flanges.
Optional features: Manual Override, High Over Temp element, Plated ele-ment. Other options available upon request.
FLUID POWER ENERGY, INC.W229 N591 Foster Court • Waukesha, WI 53186
PART # DESCRIPTION*4010 VALVE BODY (*See table for material)*4020 VALVE COVER (*See table for material)2071 LIP SEAL4080-C GASKET2050-Temp THERMOSTAT (Temp to follow dash)1604 HEX BOLT1605 LOCK WASHER1590 NAMEPLATE
FPE Model 4000 Replacement Kit (Includes the following:)4080-C GASKET(4) 2071 LIP SEAL(4) 2050-Temp THERMOSTAT (Temp to follow dash)
*4010, *4010X
* (Replace * with body material type; A=Cast Iron, B=Bronze, D=Ductile, S=Steel, SS=Stainless Steel)
To OrderSpecify Model Number, nominal
temperature desired, and housing material. For Model coding information,
visit our website or consult your factory representative.
FPE-4010-050803
*4010M, *4010XM
Recommended Pressure Drop is 2 to 7 PSI
Features
Wide Range of Temperatures
Heavy Duty
Self-Contained
Replaceable Element
Non-Adjustable
Rugged Construction
Tamper-Proof
Operate in Any Position
Compact
Available for Refrigeration Service
5010 5” Flange5010M 5” Flange with Manual Override
Fluid Power Energy (FPE) Thermostatic Valves utilize the principle ofexpanding wax, which in the semi-liquid state undergoes large expansionrates within a relatively narrow temperature range. The self-contained ele-ment activates a stainless steel sleeve, which directs flow. All FPEThermostatic Valves are factory set at predetermined temperatures: no fur-ther adjustments are necessary. A wide range of temperatures are avail-able for water and oil temperature control applications.
When used in a diverting application, on start-up the total fluid flow is rout-ed back to the main system. As fluid temperature rises to the controlrange, some fluid is diverted to the cooling system. As fluid temperaturecontinues to increase, more flow is diverted. When the thermostat is in afully stroked condition, all fluid flow is directed to the cooling system. FPEThermostatic Valves may also be used in a mixing application.
In a mixing application, hot fluid enters the “B” port and colder fluid entersthe “C” port. The flows mix and the thermostat adjusts to reach the desiredtemperature, exiting the “A” port.
Standard FPE thermostatic valve housings are made from grey iron cast-ings, however, ductile iron, bronze, steel and stainless steel housings areavailable.
Available Connections: 125# FF Flange, 150# RF Flange, 300# RFFlange, and Navy Flanges.
Optional features: Manual Override, High Over Temp element, Plated ele-ment. Other options available upon request.
FLUID POWER ENERGY, INC.W229 N591 Foster Court • Waukesha, WI 53186