REFRIGERANT GAS CONDITIONING 1 DATA SHEET Manuals, catalogues and data sheets: available on our website OUTDOOR UNITS Mini MVD V6M Super DC Inverter (up to 33.5 kW) DIMENSIONS Mini MVD series with single-phase units from 7.2 kW to 16 kW with only one fan and dual-fan units from 28 to 33.5 kW. NEW FUNCTIONALITIES The new V6M series has all the new functionalities of the CCM-180, CCM-270, IMMP-BAC centralized controls and the GW-MOD and GW-LON gateways. DC INVERTER COMPRESSOR AND FAN MOTORS All of the units from this range come with a DC Inverter compressors and fan motors, this way the frequency system performance is improved and a more sensitive and effective control is achieved. SIMPLIFIED CONNECTION The central control is connected to the outdoor unit and the automatic direction is activated, this way the control can detect all indoor units connected to that outdoor unit. Afterward we can modify the addresses manually with the individual control of each equipment. Model Max. indoor units 80 4 100 6 120 7 140 8 160 9 280 16 335 20 R410A Centralized controller Software control BMS Wattmeter IMMP-S(A) (CL 97 825) GW-MOD(A) (CL 97 828) GW-LON(A) (CL 97 829) OPTIONALS More information on optional components in “MUNDOCLIMA CONTROL SYSTEMS” CCM-180A/WS (CL 97 800) CCM-270B/WS (CL 97 802) IMMP-BAC(A) (CL 97 826) Mod. 280 to 335 Mod. 100 up to 160 Mod. 80 AUTOMATIC ADDRESSING By default, the first time the power supply is activated, the outdoor unit automatically assigns the address to each indoor unit. It is also possible to observe and modify the address of each indoor unit from your controller. DTS343-3 (CL 97 827)
4
Embed
Mini MVD V6M Super DC Inverter (up to 33.5 kW) R410A · 2021. 4. 13. · Mini MVD V6M. Super DC Inverter (up to 33.5 kW) DIMENSIONS. Mini MVD series with single-phase units from 7.2
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
REFRIGERANT GAS CONDITIONING 1
DATA SHEETManuals, catalogues and data sheets: available on our website
OUTDOOR UNITSMini MVD V6MSuper DC Inverter (up to 33.5 kW)
DIMENSIONS
Mini MVD series with single-phase units from 7.2 kW to 16 kW with only one fan and dual-fan units from 28 to 33.5 kW.
NEW FUNCTIONALITIES
The new V6M series has all the new functionalities of the CCM-180, CCM-270, IMMP-BAC centralized controls and the GW-MOD and GW-LON gateways.
DC INVERTER COMPRESSOR AND FAN MOTORS
All of the units from this range come with a DC Inverter compressors and fan motors, this way the frequency system performance is improved and a more sensitive and effective control is achieved.
SIMPLIFIED CONNECTION
The central control is connected to the outdoor unit and the automatic direction is activated, this way the control can detect all indoor units connected to that outdoor unit. Afterward we can modify the addresses manually with the individual control of each equipment.
Model Max. indoor units
80 4100 6120 7140 8160 9280 16335 20
R410A
Centralized controller Software control BMS Wattmeter
IMMP-S(A)(CL 97 825)
GW-MOD(A) (CL 97 828)
GW-LON(A) (CL 97 829)
OPTIONALS More information on optional components in “MUNDOCLIMA CONTROL SYSTEMS”
CCM-180A/WS(CL 97 800)
CCM-270B/WS(CL 97 802)
IMMP-BAC(A)(CL 97 826)
Mod. 280 to 335
Mod. 100 up to 160
Mod. 80
AUTOMATIC ADDRESSING
By default, the first time the power supply is activated,
the outdoor unit automatically assigns the address to each
indoor unit. It is also possible to observe
and modify the address of each indoor unit fromyour controller.
DTS343-3 (CL 97 827)
REFRIGERANT GAS CONDITIONING 2
DATA SHEETManuals, catalogues and data sheets: available on our website
Air deflector
New grille
New fan
EASY PIPE CONNECTIONIt comes with four different pipe and cable connection solutions to cater to different installation needs.
EASY INSTALLATIONThe mini MVD can be transported with a forklift. Its small size makes it easier to install and effectively reduces the time and number of personnel needed.
EASY MAINTENANCEThe forced cooling button causes the outdoor unit to operate in cooling mode in any state, so it is very easy to load refrigerant into the system when needed. The self-diagnosis function detects malfunctions in the main system and displays the type of error and its location. This allows for more efficient servicing and maintenance operations.
SPACE-SAVINGThe mini MVD units are more compact, which means that they will take very little space when installed. They are suitable for small offices, hotels, shops, etc.
DESIGNED TO ACHIEVE A LOW NOISE LEVEL WHILE OPERATINGThe fan’s new design, the air outlet and the baffle allow for a higher air flow and very little noise level during operation.
TOTAL PIPE LENGTHThe Mini MVD V6M system withstands a maximum pipe length of 150m, with a height difference between the outdoor and indoor units of up to 50m.
Model Max. value (m)
PIPE LENGTH
Total pipe length
80 50100 up to 120 65140 up to 160 100280 up to 335 150
Maximum distance (L) (btw. outdoor and furthest indoor unit)
Total length
80 35100 up to 120 45
65100
Equivalent length
80 40100 up to 120 50
70110
Equivalent pipe length between the furthest indoor unit and the first distributor.80 up to 160 20
280 up to 335 40Equivalent pipe length between the indoor unit and the nearest distributor. 80 up to 335 15
HEIGHT DIFFERENCE
Height difference between indoor and outdoor units.
80 10100 up to 120 20140 up to 160 30280 up to 335 50
80 10100 up to 120 20140 up to 160 20280 up to 335 40
Height difference between indoor units80 up to 160 8
280 up to 335 15
MINI MVD V6M
Frontal view Lateral right view
150m: Maximum pipe length between the outdoor unit and the farthest indoor unit.
50m: Maximum height difference between the indoor and outdoor unit.
15m: Maximum height difference between indoor units.
Note: In models 280 and 335, see other models in the table below.
140 up to 160280 up to 335
140 up to 160280 up to 335
Higher outdoor unit
Lower outdoor unit
REFRIGERANT GAS CONDITIONING 3
DATA SHEETManuals, catalogues and data sheets: available on our website
Heating ºC -15 - 27 -15 - 27 -15 - 27 -15 - 27 -15 - 27Note:(1) Nominal cooling conditions: indoor 27ºC DB, 19ºC WB and outdoor 35ºC DB, for a pipe length of 5 m and a height difference of 0 m.(2) Nominal heating conditions: indoor 20ºC DB, 15ºC WB and outdoor 7ºC DB, for a pipe length of 5 m and a height difference of 0 m.(3) Noise level measured in an anechoic chamber at 1m distance front and 1.2m high (1 m for models from 20 to 26kW). During operation these values may be slightly higher due to
environmental conditions.(4) Pipe length when outdoor unit is installed higher than the indoor units.(5) The specified diameters are for the service valves, this does not mean that the pipe must have this diameter.(6) Power wiring recommended for L < 20 m, for longer distances it should be recalculated.* Data measured under EUROVENT EN 14825 conditions, at 100% simultaneity with indoor cassette units. For more information, please refer to the document "INFORMATION REQUIREMENTS".
*Data and specs can be changed without previous notice.
REFRIGERANT GAS CONDITIONING 4
DATA SHEETManuals, catalogues and data sheets: available on our website
Type DC Inverter - rotating DC Inverter - rotating
Number 1 1
Model LNB65FAGMC LNB65FAGMC
Fan
Type DC DC
Number 2 2
Flow rate m³/h 11,000 11,300
Sound pressure (3) dB(A) 59 61
Sound power (LwA) (3) dB(A) 76 77
Dimensions (W x H x D) mm 1120 x 1558 x 528 1120 x 1558 x 528
Weight kg 157 157
RefrigerantType / PCA R410A / 2088 R410A / 2088
Number kg / TCO2eq 8.0 / 16.7 8.0 / 16.7
Refrigerant pipe length (4)
Max. vertical m 50 50
Total m 150 150
Connection pipes(5)Liquid mm (inches) 9.52 (3/8) 12.7 (1/2)
Gas mm (inches) 22.2 (7/8) 25.4 (1")
Electrical connections (6)
Power wiring / ICP mm² / A 4 x 6 + T / 32 4 x 6 + T / 32
Communication wiring mm² 3 x 0,75 (shielded) 3 x 0,75 (shielded)
Operation temp. range
Cooling ºC -5 - 48 -5 - 48
Heating ºC -20 - 24 -20 - 24
Note:(1) Nominal cooling conditions: indoor 27ºC DB, 19ºC WB and outdoor 35ºC DB, for a pipe length of 7.5 m and a height difference of 0 m.(2) Nominal heating conditions: indoor 20ºC DB, 15ºC WB and outdoor 7ºC DB, for a pipe length of 7.5 m and a height difference of 0 m.(3) Pressure noise level measured in a semi-anechoic chamber at 1 m frontal distance and 1.3 m height.(4) Pipe length when outdoor unit is installed higher than the indoor units.(5) The specified diameters are for the service valves, this does not mean that the pipe must have this diameter.(6) Power wiring recommended for L < 20 m, for longer distances it should be recalculated.
* Data measured under Eurovent conditions EN14825, at 100% simultaneity.* Data and specs can be changed without previous notice.