O O p 43 18 o 94 p p 90 p p 94 90 p 94 p 41 o 90 51 o 94 p p 43 o 41 Menomonie Falls Appleton Washington Waukesha Waukesha Co. Racine Co. Kenosha Co. Platteville Janesville Monroe Beloit Walworth Co. Center Richland Richland Co. Grant Co. Prairie du Chien Crawford Co. Vernon Co. LaCrosse Co. Monroe Co. La Crosse Pierce Co. Pepin Co. Buffalo Co. Trempealeau Co. Tomah Eau Claire Portage Rock Co. Dodgeville Lafayette Co. Iowa Co. Green Co. Dane Co. Madison Whitewater Jefferson Co. Watertown Co. du Lac Fond Beaver Dam Point Stevens Rapids Wisconsin Marshfield Wausau Oshkosh Shawano Waupaca Co. Shawano Co. Outagamie Co. New London Kenosha Ozaukee Co. Milwaukee Co. Racine Co. Racine Milwaukee Port Washington Sheboygan Bend West Manitowoc Kewaunee Co. Door Co. Bay Green Marinette Co. Oconto Co. Price Co. Ashland Barron Co. Washburn Co. St. Croix Co. Polk Co. Dunn Co. Burnett Co. Rice Lake Chippewa Co. Chippewa Rusk Co. Taylor Co. Sawyer Co. Superior Douglas Co. Bayfield Co. Ashland Co. Langlade Co. Rhinelander Tomahawk Lincoln Co. Oneida Co. Park Falls Menominee Co. Forest Co. Florence Co. Iron Co. Vilas Co. Marinette Milwaukee, Wisconsin Milwaukee, County 17400 West Capitol Drive Brookfield, WI 53045 Phone: 414.778.1700 Fax: 414.778.2360 E-Mail: [email protected]REV DATE DESCRIPTION OF ISSUE SHEET NAME DRAWN APPROVED DATE R&D PROJECT NO. SHEET NUMBER PROJECT TITLE MILWAUKEE INTERMODAL STATION REHABILITATION PROJECT 2019 TITLE SHEET 02/22/2019 218089.00 T000 RD RD MILWAUKEE INTERMODAL STATION REHABILITATION PROJECT 2019 MILWAUKEE INTERMODAL STATION 433 W ST. PAUL AVENUE MILWAUKEE, WI 53203 WISCONSIN DEPARTMENT OF TRANSPORTATION 4822 MADISON YARDS WAY, 6TH FLOOR SOUTH MADISON, WI 53705 PROJECT CONTACTS: ELECTRICAL: 17400 WEST CAPITOL DRIVE BROOKFIELD, WI 53045 PHONE: 414.778.1700 FAX: 414.778.2360 E-Mail: [email protected]MECHANICAL: 17400 WEST CAPITOL DRIVE BROOKFIELD, WI 53045 PHONE: 414.778.1700 FAX: 414.778.2360 E-Mail: [email protected]STRUCTURAL: 555 SOUTH RIVER STREET JANESVILLE, WI 53548 PHONE: 608.756.2326 FAX: 608.756.0464 ARCHITECTURAL: 207 EAST MICHIGAN STREET - SUITE 400 P.O. BOX 510663 MILWAUKEE, WI 53203 PHONE: 414.220.9640 NTS 1 PROJECT LOCATOR MAP NTS 2 PROJECT SITE MAP NORTH NORTH SHEET INDEX No. TITLE T000 TITLE SHEET A001 GENERAL INFORMATION PARTITION TYPES A010 LIFE SAFETY PLANS A102 DEMOLITION PLAN - LEVEL 02 A202 NEW WORK PLAN - LEVEL 02 A700 INTERIOR ELEVATIONS A900 ROOM FINISH/DOOR SCHEDULE S200 EQUIPMENT FRAMING PLAN P000 PLUMBING SYMBOLS, ABBREVIATIONS & SHEET INDEX P200 PLUMBING BASEMENT OVERALL PLANS P201 PLUMBING FIRST FLOOR OVERALL PLANS P202 PLUMBING SECOND FLOOR OVERALL PLANS P204 PLUMBING ROOF PLAN OVERALL PLANS M000 MECHANICAL SYMBOLS, ABBREVIATIONS, SHEET INDEX M100 PENTHOUSE MECH. DEMOLITION PLANS M200 PENTHOUSE MECH. NEW CONSTRUCTION PLANS M210 BASEMENT AND SECOND MECH. FLOOR PLANS M500 MECHANICAL DETAILS M501 MECHANICAL DETAILS M600 MECHANICAL SCHEDULES E000 SYMBOLS, ABBREVIATIONS & SHEET INDEX E200 PENTHOUSE - ELECTRICAL E210 BASEMENT AND SECOND FLOOR PLAN - ELECTRICAL E400 ONE LINE DIAGRAM E600 ELECTRICAL SCHEDULES PLUMBING: 17400 WEST CAPITOL DRIVE BROOKFIELD, WI 53045 PHONE: 414.778.1700 FAX: 414.778.2360 E-Mail: [email protected]1 02/22/19 BIDDING DOCUMENTS
26
Embed
MILWAUKEE INTERMODAL STATION · mkbd marker board mo masonry opening mp manufactured metal panel mpc metal pan ceiling mr moisture resistant mtd mounted nts not to scale oc on center
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
O
Op43
18o
94p
p90 pp94
90p94p
41o
90
51o
94p
p43
o41Menomonie Falls
Appleton
Washington
Waukesha
Waukesha Co.
Racine Co.
Kenosha Co.
Platteville
Janesville
Monroe Beloit Walworth Co.
CenterRichland
Richland Co.
Grant Co.
Prairie duChien
Crawford Co.
Vernon Co.
LaCrosse Co. Monroe Co.
La Crosse
Pierce Co.
Pepin Co.
Buffalo Co.
Trempealeau Co.
Tomah
Eau Claire
Portage
Rock Co.
Dodgeville
Lafayette Co.
Iowa Co.
Green Co.
Dane Co.
Madison
Whitewater
Jefferson Co.
WatertownCo.
du LacFond
Beaver Dam
PointStevens
RapidsWisconsin
Marshfield
Wausau
Oshkosh
Shawano
Waupaca Co.
Shawano Co.
Outagamie Co.
New London
Kenosha
Ozaukee Co.
Milwaukee Co.
Racine Co.
Racine
Milwaukee
Port Washington
Sheboygan
BendWest
Manitowoc
Kewaunee Co.
Door Co.
BayGreen
Marinette Co.
Oconto Co.
Price Co.
Ashland
Barron Co.
Washburn Co.
St. Croix Co.
Polk Co.
Dunn Co.
Burnett Co.
Rice Lake
Chippewa Co.
Chippewa
Rusk Co.
Taylor Co.
Sawyer Co.
Superior
Douglas Co. Bayfield Co. Ashland Co.
Langlade Co.
Rhinelander
Tomahawk
Lincoln Co.
Oneida Co.
Park Falls
Menominee Co.
Forest Co. Florence Co.
Iron Co.
Vilas Co.
Marinette
Milwaukee, WisconsinMilwaukee, County
17400 West Capitol DriveBrookfield, WI 53045Phone: 414.778.1700Fax: 414.778.2360E-Mail: [email protected]
REV DATE DESCRIPTION OF ISSUE
SHEET NAME
DRAWN APPROVED
DATE
R&D PROJECT NO.
SHEET NUMBER
PROJECT TITLE
MILWAUKEE INTERMODAL
STATION REHABILITATION
PROJECT 2019
TITLE SHEET
02/22/2019
218089.00
T000
RD RD
MILWAUKEE INTERMODAL STATION REHABILITATION PROJECT 2019MILWAUKEE INTERMODAL STATION433 W ST. PAUL AVENUEMILWAUKEE, WI 53203
WISCONSIN DEPARTMENT OF TRANSPORTATION4822 MADISON YARDS WAY, 6TH FLOOR SOUTHMADISON, WI 53705
FD FLOOR DRAINFDN FOUNDATIONFE FIRE EXTINGUISHERFEP FINISHED END PANELFF FINISHED FLOORFL MAT FLOOR MAT AND FRAMEFLR FLOORFR FRAMEFRP FIBERGLASS REINFORCED POLYESTERFSTOP FIRESTOPPINGFTG FOOTINGFWS FOUNDATION WALL SYSTEM
PC PRECAST CONCRETEPLAM PLASTIC LAMINATEPPT PRESSURE TREATED WOODPREFIN PREFINISHEDPRT PARTITIONPS PROJECTION SCREENP+S CLOSET POLE AND SHELFPT PAINTPTD PAPER TOWEL DESPENSER
INSTALL 20 GA CLIP ANGLES TO SUBSTRATE, SEE NOTES BELOW FOR SPACING CLIP ANGLE AT TOP OF STUD IN ADDITION TO SPACINGS NOTED BELOW.
THERMAL INSULWIDTH
(SUBSCRIPT T) & R VALUE
3 5/8" 4 1/4"3 1/2"R=11
METAL STUD FURRINGF FIRE RATING: 0 HR
PROVIDE BRACES TO BACK-UP AT VERT. MIDPOINT OF STUD WHERE UNBRACED HEIGHT EXCEEDS 12'-0"
SCALE: 1 1/2" = 1'-0"
NOTE:REFER TO PARTITION TYPE SUBSCRIPT KEY FOR MORE INFORMATION AND REQUIREMENTS.
PARTITIONTYPE
STUDWIDTH
PARTITIONWIDTH
ACOUSTICALINSULATION
WIDTH (SUBSCRIPT A) NOTES
3 1/2"
AT FULL HEIGHT REQUIREMENTS, ATTACH 3" DEEP METAL DEFLECTION TRACK TO STRUCTURAL CEILING. HOLD METAL STUDS AND GWB 5/8" BELOW STRUCTURAL CEILING. PROVIDE PERIMETER SEALANT AT STRUCTURAL CEILING TERMINATIONS AND AT ALL OTHER PENETRATIONS. HOLD GWB ANCHORAGES 3 1/2" BELOW STRUCTURAL CEILING TO FACILITATE SLIP-JOINT ACTION.
SCHEDULED CEILING
ONE LAYER 5/8" GWB APPLIED VERTICALLY, JOINTS STAGGERED, TYP.
METAL STUDS: PROVIDE 25 GAUGE @ 16"O.C., UNLESS NOTED OTHERWISE, OR OTHER GAUGE AND SPACING REQUIRED TO COMPLY WITH DEFLECTION CRITERIA. PROVIDE MINIMUM 20 GAUGE AT ABUSE RESISTANT GWB OR AS RECOMMENDED BY MANUFACTURER.
TAPERED EDGE OF GWB SHALL NOT BE INSTALLED ALONG BOTTOM EDGE. BOTTOM EDGE MUST BE FINISHED FLUSH TO RECEIVE SCHEDULED BASE.
SCHEDULED BASE
HOLD GWB 3/8" FROM STRUCTURAL FLOOR. PROVIDE PERIMETER SEALANT AT STRUCTURAL FLOOR TERMINATIONS AND AT ALL PENETRATIONS.
F3-
SILL
PLAN
HEAD
BRACE TO STRUCTURE AS REQUIRED TO COMPLY WITH DEFLECTION CRITERIA
NA NA
STC @ 0,1HR
W/OINS
W/INS
F6- 6" 6 5/8"
6 1/4"R=19
PROVIDE BRACES TO BACK-UP AT VERT. MIDPOINT OF STUD WHERE UNBRACED HEIGHT EXCEEDS 12'-0"
6 1/4" NA NA
SCALE: 1 1/2" = 1'-0"
NOTE:REFER TO PARTITION TYPE SUBSCRIPT KEY FOR MORE INFORMATION AND REQUIREMENTS.
PARTITIONTYPE
STUDWIDTH
PARTITIONWIDTH
0,1HR; 2HR
ACOUSTICALINSULATION
WIDTH (SUBSCRIPT A)
STC @ 0,1HR
W/OINS
W/INS
STC @ 2HR
W/OINS
W/INS NOTES
3 5/8"4 7/8"/6 1/8" 3 1/2" 40 50 45 56
METAL STUD PARTITIONA FIRE RATING: 0,1,2 HR - UL #U419
1 1/2" BATT INS. REQ. @ 1HR RATED PARTITION
AT FIRE RATED PARTITIONS INSTALL UL RATED FIRESTOPPING JOINT SYSTEM.
AT FULL HEIGHT REQUIREMENTS, ATTACH 3" DEEP METAL DEFLECTION TRACK TO STRUCTURAL CEILING. HOLD METAL STUDS AND GWB 5/8" BELOW STRUCTURAL CEILING. PROVIDE PERIMETER SEALANT AT STRUCTURAL CEILING TERMINATIONS AND AT ALL OTHER PENETRATIONS. HOLD GWB ANCHORAGES 3 1/2" BELOW STRUCTURAL CEILING TO FACILITATE SLIP-JOINT ACTION. AT FIRE RATED PARTITIONS PROVIDE UL TESTED DEFLECTION TRACK ASSEMBLY.
SCHEDULED CEILING
ONE LAYER 5/8" GWB EACH SIDE AT 0HR AND 1HR RATED PARTITIONS. TWO LAYERS 5/8" GWB EACH SIDE AT 2HR RATED PARTITIONS. GWB APPLIED VERTICALLY, JOINTS STAGGERED, TYP.
METAL STUDS: PROVIDE 25 GAUGE @ 16"O.C., UNLESS NOTED OTHERWISE, OR OTHER GAUGE AND SPACING REQUIRED TO COMPLY WITH DEFLECTION CRITERIA. PROVIDE MINIMUM 20 GAUGE AT ABUSE RESISTANT GWB OR AS RECOMMENDED BY MANUFACTURER.
TAPERED EDGE OF GWB SHALL NOT BE INSTALLED ALONG BOTTOM EDGE. BOTTOM EDGE MUST BE FINISHED FLUSH TO RECEIVE SCHEDULED BASE.
SCHEDULED BASE
HOLD GWB 3/8" FROM STRUCTURAL FLOOR. PROVIDE PERIMETER SEALANT AT STRUCTURAL FLOOR TERMINATIONS AND AT ALL PENETRATIONS.
BATT INSULATION REQUIRED AT SOME RATED WALLS. SEE CHART BELOW.
A3-
SILL
PLAN
HEADBRACE TO STRUCTURE AS REQUIRED TO COMPLY WITH DEFLECTION CRITERIA
SUBSCRIPT (-)EXTEND TOTAL PARTITION TO STRUCTURE
SUBSCRIPT (A):ACOUSTICAL INSULATION
PARTITION TYPE SUBSCRIPT KEYNOTE: TYPE A PARTITION IS SHOWN HERE AS A GENERAL REPRESENTATION. THESE SUBSCRIPTS MODIFY BASIC PARTITION TYPE CONSTRUCTION REQUIREMENTS AND APPLY TO ALL PARTITION TYPES.
A
-
A
A
SUBSCRIPT (0):STUDS & GYP 6" ABOVE CEILING
SUBSCRIPT (T):THERMAL INSULATION
6"
A
0
A
T
ACT
SCALE: 1 1/2" = 1'-0"
PARTITIONTYPE
BLOCKWIDTH
7 5/8"
FIRE RESISTANCEHOLLOW
CORESOLIDCORE
1HR2HR3HR
4HR
STC @ DENSITY 135pcfHOLLOW
UNITSGROUTFILLED
SANDFILLED
49 57 55
NOTES
UL #U901 - 4 HRUL #U904 - 3 HRUL #U905 - 2 HR
MASONRY PARTITIONM FIRE RATING: 0,1,2,3,4 HR - UL #U---
M8-
CONCRETE MASONRY UNITS
SCHEDULE BASE
EXISTING MASONRY PARTITION
NOTE:REFER TO PARTITION TYPE SUBSCRIPT KEY FOR MORE INFORMATION AND REQUIREMENTS.
SILL
PLAN
HEAD
GROUT SOLID WHERE REQUIRED BY RATED ASSEMBLY, SPECIFIED, OR NOTED ON DRAWINGS.
17400 West Capitol DriveBrookfield, WI 53045Phone: 414.778.1700Fax: 414.778.2360E-Mail: [email protected]
REV DATE DESCRIPTION OF ISSUE
SHEET NAME
DRAWN APPROVED
DATE
R&D PROJECT NO.
SHEET NUMBER
PROJECT TITLE
MILWAUKEE INTERMODAL
STATION REHABILITATION
PROJECT 2019
GENERALINFORMATION/
PARTITIONTYPES
02/22/2019
218089.00
A001
Author Approver
GENERAL INFORMATION NOTES TO CONTRACTOR
1. THESE DRAWINGS ARE DIAGRAMMATIC AND SHOW THE INTENT OF THE PROJECT, BUT DO NOT NECESSARILYINDICATE ALL MATERIALS OR METHODS OF CONSTRUCTION. ALL CONTRACTORS ARE RESPONSIBLE TO REVIEWTHE DOCUMENTS THOROUGHLY, AND FOR PROVIDING ALL MATERIALS AND MEANS OF CONSTRUCTIONNECESSARY FOR THE COMPLETION OF THE WORK IN ACCORDANCE WITH THE INTENT OF THE DRAWINGS.
2. ALL WORK OF ALL TRADES, SHALL BE COMPLETED IN ACCORDANCE WITH ALL LOCAL GOVERNING CODES ANDORDINANCES.
3. EACH CONTRACTOR SHALL COORDINATE THEIR WORK WITH THE OWNER, THE OWNER'S OTHER CONTRACTORS,AND ALL OTHERS AT THE SITE.
4. EACH CONTRACTOR IS TO OBTAIN AND PAY FOR PERMITS, LICENSES, FEES, ETC. AS REQUIRED FOR THECOMPLETION OF THEIR PORTION OF WORK.
5. EACH CONTRACTOR SHALL VERIFY ALL CONDITIONS AND DIMENSIONS AT THE SITE TO SATISFY THEIR EXECUTIONOF THE WORK. ANY DISCREPANCIES SHALL BE REPORTED TO THE ARCHITECT PRIOR TO PROCEEDING. NEITHERTHE OWNER NOR THE ARCHITECT ASSUMES RESPONSIBILITY FOR CONDITIONS OR DIMENSIONS SHOWN ASEXISTING.
6. IF ANY CONTRACTOR OBSERVES THAT ANY OF THE CONTRACT DOCUMENTS ARE AT VARIANCE WITH APPLICABLELAWS, STATUTES, BUILDING CODES, OR ORDINANCES, THEY SHALL PROMPTLY NOTIFY THE ARCHITECT.
7. ALL HOLES FOR PLUMBING, ELECTRICAL, HVAC, FIRE PROTECTION CONDUIT, PIPING, OR DUCTWORK ARE TO BEREPAIRED BY THE ASSOCIATED TRADE.
8. ALL TRADES SHALL TAKE CARE TO MAKE HOLES ONLY AS LARGE AS NECESSARY. DO NOT PUNCH OR POUNDHOLES IN WALL, FLOOR, OR ROOF DECK.
9. ANY HOLES OR PENETRATIONS THROUGH FIRE RATED CONSTRUCTION SHALL BE APPROPRIATELY FIRE STOPPED,DAMPENED, OR SEALED AS REQUIRED BY CODE.
10. EACH CONTRACTOR SHALL INCLUDE THE NECESSARY DEMOLITION, REMOVAL, AND CUTTING/PATCHING OF ALLMATERIAL AS REQUIRED TO PERFORM THEIR WORK.
11. REMOVAL OF ALL HAZARDOUS CONTAINING MATERIALS IS THE SOLE RESPONSIBILITY OF THE OWNER. SHOULDANY MATERIALS BE ENCOUNTERED DURING ANY OF THE CONSTRUCTION PHASES CONTAINING, OR SUSPECTEDTO BE HAZARDOUS: CONTRACTOR SHALL STOP WORK IMMEDIATELY AND NOTIFY OWNER AND ARCHITECT.
12. DO NOT SCALE DRAWINGS.13. EACH CONTRACTOR SHALL PATCH, LEVEL, AND PREPARE ALL WALLS AND FLOORS AS SCHEDULED TO RECEIVE
NEW FINISHES.
GENERAL INTERIOR PARTITION NOTES TO CONTRACTOR
1. REFER TO PARTITION DETAILS FOR CONSTRUCTION REQUIREMENTS OF PARTITION TYPES. REFER ALSO TOPARTITION TYPE SUBSCRIPT KEY FOR MODIFICATIONS TO BASIC PARTITION TYPE. IF NO PARTITION TYPE TAG ISINDICATED ON THE PLANS FOR A SPECIFIC SECTION OF METAL STUD WALL, PROVIDE PARTITION TYPE 'A3,SUBSCRIPT -,A'. IF NO PARTITION TYPE TAG IS INDICATED ON THE PLANS FOR A SPECIFIC SECTION OF MASONRYWALL, PROVIDE PARTITION TYPE 'M8', NOTE: SOME PARTITION TYPES DESCRIBED MAY NOT BE USED ON THISPROJECT.
2. REFER TO 'PARTITION TYPE SUBSCRIPT KEY' FOR SYMBOLS AND SUBSCRIPTS USED TO IDENTIFY ADDITIONALREQUIREMENTS OR MODIFICATIONS TO BASIC PARTITION TYPE.
3. PARTITION DETAILS DESCRIBE GENERAL REQUIREMENTS FOR PARTITIONS. REFER TO THE MANUFACTURERS'SPECIFICATIONS AND REQUIREMENTS OF APPLICABLE TESTING AGENCIES FOR SPECIFICS OF PARTITIONCONSTRUCTION.
4. ALL PENETRATIONS IN ACOUSTICALLY RATED, FIRE RATED, AND SMOKE RATED PARTITIONS AND CONNECTIONS OFTHE PARTITIONS TO OTHER PORTIONS OF THE WORK SHALL BE IN ACCORDANCE WITH MANUFACTURER'SRECOMMENDED DETAILS AND IN COMPLIANCE WITH APPLICABLE TESTING AGENCY REQUIREMENTS.
5. ALL PENETRATIONS IN ACOUSTICALLY RATED PARTITIONS ARE TO BE ACOUSTICALLY SEALED TO MAINTAIN STCASSEMBLY RATINGS.
6. FIREWALLS, FIRE PARTITIONS, FIRE BARRIERS OR ANY WALL REQUIRED TO HAVE PROTECTED OPENINGS ORPENETRATIONS SHALL BE IDENTIFIED PER SPECIFICATIONS AND CODE.
7. WHERE FIREWALLS, FIRE PARTITIONS, FIRE BARRIERS OR ANY WALL REQUIRED TO HAVE FIRE RATING IS CALLEDOUT IN THE DRAWINGS, EXTEND THE RATING UP TO THE NEXT FIRE RATED PARTITION IN A MANNER THATENSURES A CONTINUOUS FIRE SEPARATION AND MAINTAINS THE INTEGRITY OF THE FIRE RATED PARTITION.PROVIDE FIRE RESISTIVE JOINT SYSTEMS PER SPECIFICATIONS.
8. AT PLENUM RATED CEILINGS, ALL PENETRATIONS ARE TO BE SEALED TO MAINTAIN PLENUM CEILINGS AIRTIGHTNESS / 5PSF.
9. INSTALL BLOCKING OR BACKER MATERIAL FOR ATTACHMENT/MOUNTING OF ALL WALL HUNG ITEMS OR EQUIPMENTDESCRIBED IN THE DOCUMENTS, WHETHER CONTRACTOR FURNISHED OR OWNER FURNISHED.
10. COORDINATE WITH OWNER THE LOCATION OF BLOCKING FOR OWNER SUPPLIED ITEMS.11. WHERE PARTITIONS AND/OR FURRING MEET, MAINTAIN SURFACES FLUSH AND PLUMB.12. PROVIDE 5/8" GWB UNLESS NOTED OTHERWISE.13. PROVIDE MOISTURE RESISTANT GYPSUM BOARD AT ALL TOILET ROOMS AND WET AREAS UNLESS NOTED
OTHERWISE.14. INSTALLATION OF ALL TYPES OF GYPSUM BOARD SHALL CONFORM TO REQUIREMENTS FOR FIRE RATINGS AND
ACOUSTICAL RATINGS.15. ALL GYPSUM WALL BOARD IS TO BE INSTALLED WITH THE LONG DIMENSION RUNNING HORIZONTALLY UNLESS THE
REQUIREMENT FOR THE FIRE RATING AND ACOUSTICAL RATINGS DIFFER.16. U.O.N. PROVIDE 4" AT DOOR JAMBS (FROM EDGE OF FRAME TO FINISHED FACE OF WALL)17. TYPICAL FLOOR PLAN DIMENSIONS ARE TO THE FACE OF THE OUTERMOST LAYER OF GYPSUM BOARD UNLESS
NOTED AS TO CENTERLINE OF PARITION.18. WHERE A CLEAR DIMENSION OR OPENING IS REQUIRED OR NOTED, MEASURE DIMENSION TO FACE OF PARTITION
FINISH.19. WHERE THERMAL INSULATION IS NOTED BY SUBSCRIPT, INSTALL VAPOR RETARDER. SEAL AT ALL TERMINATIONS,
PENETRATIONS, AND SEAMS. INSTALL FELT ISOLATION STRIPS BETWEEN CLIP ANGLE AND SUBSTRATE.
ARCHITECTURALA001 GENERAL INFORMATION/ PARTITION TYPESA010 LIFE SAFETY PLANSA102 DEMOLITION PLAN - LEVEL 02A202 NEW WORK PLAN - LEVEL 02A700 INTERIOR ELEVATIONSA900 ROOM FINISH/DOOR SCHEDULE
SHEET INDEX:
larjt
Text Box
1 02/22/19 BIDDING DOCUMENTS
1 1
2 2
UP
11
11
11
1 1
11
1 11
11
11
11
22
222
2
1 1
11
1 1
2 2
22
2 2
11
11
11
11
11
11
22
112
2
LIFE SAFETY PLAN SUMMARY
WISCONSIN ENROLLED COMMERCIAL BUILDING CODE - IBC 2015
2015 INTERNATIONAL EXISTING BUILDING CODEWISCONSIN CODE AMENDMENTS COMM 66 - SPS 366
INTERNATIONAL CODE COUNCIL - ACCESSIBLE AND USEABLE BUILDING AND FACILITIES STANDARDS - ANSI 117.1
UNIFORM FEDERAL ACCESSIBILITY STANDARDS (UFAS) OR AMERICAN WITH DISABILITY ACT - ACCESSIBILITY GUIDELINES FOR BUILDINGS AND FACILITIES (ADDAG).
LIFE SAFETY CODE - NFPA-101
SAFETY & HEALTH - OSHA CFR PART 1926.62
ARCHITECT/ENGINEER CONTRACTOR DESIGN REQUIREMENTS - 48CFR PART 36
2015 INTERNATIONAL BUILDING CODE WISCONSIN AMENDMENTS COMM 62 - SPS 362
2015 INTERNATIONAL ENERGY CONSERVATION CODEWISCONSIN CODE AMENDMENTS COMM 63 - SPS 363
2015 INTERNATIONAL MECHANICAL CODE WISCONSIN CODE AMENDMENTS COMM 64 - SPS 364
205 INTERNATIONAL FUEL GAS CODE WISCONSIN CODE AMENDMENTS COMM 65 - SPS 365
2011 NATIONAL ELECTRICAL CODE NECWISCONSIN CODE AMENDMENTS SPS 316
APPLICABLE CODESARCHITECTURAL:
PLUMBING:
ENERGY:
MECHANICAL:
FUEL:
ELECTRICAL:
LIFE SAFETY PLAN KEY
EXIT WIDTH PROVIDED
FIRE EXTINGUISHER - MAXIMUM TRAVEL DISTANCE - 75 FEET - SEE SPECIFICATIONS FOR FIRE EXTINGUISHER TYPE.
EXIT SIGN
ACCESSIBLE ROUTE
EXIT TRAVEL DISTANCE
ONE HOUR RATED FIRE PARTITION OR WALL
TWO HOUR RATED FIRE PARTITION OR WALL
XX"
FEC
IEBC SUMMARY:NO CHANGE OF OCCUPANCY. EXISTING SPACE USED AS BUSINESS OCCUPANCY. NEW SPACE USED AS BUSINESS OCCUPANCY.
IEBC 101.5: COMPLIANCE METHOD: WORK AREA COMPLIANCE METHOD (CHAPTERS 4 - 12).
IEBC 403: PROJECT FOLLOWS A LEVEL 2 ALTERATION AS THE SPACE IS BEING RECONFIGURED BUT THE WORK DOES NOT EXCEED 50% OF THE AGGREGATE AREA OF THE BUILDING.
IEBC 704 MINIMUM NUMBER OF EXITS ARE BEING MET WITH THE RENOVATION PER OCCUPANT LOAD OF THE FLOOR.
(IBC 2015) TABLE 506.2 ALLOWABLE AREAOCCUPANCY TYPE B, SPRINKLERED, CONSTRUCTION TYPE I-B = 23,000 SF
(IBC 2015) TABLE 601, CONSTRUCTION TYPE:EXISTING BUILDING CONSTRUCTION - TYPE I-BFIRE RESISTANCE RATINGS FOR:
PRIMARY STRUCTURAL FRAME = 2 HOURSEXTERIOR BEARING WALLS = 2 HOURSNON BEARING INTERIOR WALLS = 0 HOURSFLOOR CONSTRUCTION AND SECONDARY MEMBERS = 2 HOURSROOF CONSTRUCTION AND SECONDARY MEMBERS = 1 HOUR
(IBC 2015) TABLE 803.9, INTERIOR WALL AND CEILING FINISH REQUIREMENTS BY OCCUPANCY: (SPRINKLERED)- CORRIDORS ARE TO BE MIN. CLASS C FOR OCCUPANCY GROUP B.- ROOMS AND ENCLOSED SPACES ARE TO BE A MIN. CLASS C FOR OCCUPANCY GROUPS B
(IBC 2015) TABLE 1004.1.2, MAXIMUM FLOOR AREA ALLOWANCES PER OCCUPANT:OCCUPANCY TYPE B = 100 SF/PERSON
ACTUAL FLOOR AREA PER OCCUPANT:LEVEL 02 - ENTIRE FLOOR 18,228 SF / 100 = 183LEVEL 02 - AREA OF WORK
(IBC 2015) 1005.3 MIN. REQUIRED EGRESS:STAIR WIDTH = 0.3 INCHES PER OCCUPANT (MINIMUM 44 INCHES)OTHER EGRESS COMPONENTS = 0.2 INCHES PER OCCUPANT
(IBC 2015) TABLE 1006.2.1:A TYPE B OCCUPANCY EQUIPPED WITH AN AUTOMATIC SPRINKLER SYSTEM INSTALLED IN ACCORDANCE WITH SECTION 903.3.1.1 OR 903.3.1.2 SHALL HAVE A MAXIMUM COMMON PATH OF TRAVEL DISTANCE OF 100 FEET.
(IBC 2015) TABLE 1017.2 EXIT ACCESS TRAVEL DISTANCE:IN OCCUPANCY TYPE B EQUIPPED WITH AN AUTOMATIC SPRINKLER SYSTEM INSTALLED IN ACCORDANCE WITH SECTION 903.3.1.1 OR 903.3.1.2, SHALL HAVE A MAXIMUM EXIT ACCESS TRAVEL DISTANCE OF 300 FEET.
(IBC 2015) TABLE 1020.1 CORRIDOR RESISTANCE FIRE RATING:IN OCCUPANCY TYPE B EQUIPPED WITH AN SPRINKLER SYSTEM INSTALLED IN ACCORDANCE WITH SECTION 903.3.1.1 OR 903.3.1.2 AND SERVING GREATER AREA THAN 30 PEOPLE, CORRIDOR WALLS TO HAVE A MINIMUM FIRE RESITING OF 0 HOURS
(IBC 2015) 1020.4 DEAD ENDS:WHERE MORE THAN ONE EXIT OR EXIT ACCESS DOORWAY IS REQUIRED, AND WHERE EQUIPPED WITH AN AUTOMATIC SPRINKLER SYSTEM INSTALLED IN ACCORDANCE WITH SECTION 903.3.11 OR 903.3.1.2 EXITS SHALL BE ARRANGED SUCH THAT THERE ARE NO DEAD ENDS IN CORRIDORS MORE THAN 50 FEET IN LENGTH.
IBC 2015) TABLE 2902.1, MINIMUM SANITARY FIXTURES:INTERNATIONAL PLUMBING CODE 410.1 DRINKING FOUNTAIN APPROVAL - WHERE DRINKING FOUNTAINS ARE REQUIRED, WATER COOLERS OR BOTTLED WATER DISPENSER SHALL BE PERMITTED BY SUBSTITUTION.
OCCUPANCY TYPE B 1 WATER CLOSETS/URINAL PER 25 OCCUPANTS FOR THE FIRST 50 AND 1 ADDITIONAL PER 50 FOR REMAINDER1 LAVATORY PER 40 OCCUPANTS FOR FIRST 80 AND 1 ADDTIONAL PER 80 FOR REMAINDER1 DRINKING FOUNTAIN PER 100 OCCUPANTS1 SERVICE SINK
ACTUAL SANITARY FIXTURES PROVIDED - OCCUPANCY TYPE BLEVEL 02 - 183 OCCUPANTS (92 MALE / 92 FEMALE)WATER CLOSETS - 5 MALE AND 5 FEMALE LAVATORIES - 3 MALE AND 3 FEMALEDRINKING FOUNTAIN - 1 REQUIREDSERVICE SINK - 1 REQUIRED
A B C D E F G H I J K
.01
1
1a
2
3
0.9
112 SF
MEN204
175 SF
WOMEN205
1603 SF
SPACE B229
1711 SF
SPACE 1-C230
72 SF
SPACE 3-C232
75 SF
SPACE 2-C231
9786 SF
SPACE A228
104 SF
CORRIDOR203218 SF
CORRIDOR223
131 SF
WOMEN222
177 SF
MEN221
216 SF
STAIR 1S-1
57 SF
ELEVATOR 1E-1
82 SF
UTILITY223A
148 SF
STAIR 2S-2
57 SF
ELEVATOR 2E-2
STAIR 3S-3
OPEN TO 1ST FLOOR LOBBYAREA NOT IN SCOPE
AREA NOT IS SCOPEAREA NOT IS SCOPE
FE
FEFE
75' - 0"
75' -
0"
75' - 0"
COMMON PATH OF TRAVEL = 59'-2"
36"
36"
36"
36"
WEST ST. PAUL AVENUE
EXISTING EXITS TO GRADE "NO CHANGE"
EXISTING RATED WALLS "NO CHANGE"
EXISTING RATED WALLS "NO CHANGE"
EXISTING EXITS TO GRADE "NO CHANGE"
EXISTING EXITS TO GRADE "NO CHANGE"
EXISTING RATED WALLS "NO CHANGE"
NORTH
17400 West Capitol DriveBrookfield, WI 53045Phone: 414.778.1700Fax: 414.778.2360E-Mail: [email protected]
REV DATE DESCRIPTION OF ISSUE
SHEET NAME
DRAWN APPROVED
DATE
R&D PROJECT NO.
SHEET NUMBER
2ND LEVEL KEY PLAN
AREA OF WORKALT BID
PROJECT TITLE
MILWAUKEE INTERMODAL
STATION REHABILITATION
PROJECT 2019
LIFE SAFETYPLANS
02/22/2019
218089.00
A010
Author Approver
Scale:
0' 2" 4" 6"1"
1" = 10'-0"1 NEW WORK PLAN - LEVEL 02 - LIFE SAFETY PLAN - ALTERNATE BIDBASE BID - NO WORK LEVEL 2
A010
larjt
Text Box
1 02/22/19 BIDDING DOCUMENTS
UP
A B C D E F G H I J K
.01
1
1a
2
3
0.9
AREA NOT IS SCOPE AREA NOT IS SCOPE
OPEN TO 1ST FLOOR LOBBYAREA NOT IN SCOPE
FUTURE TENNANT SPACE A
FUTURE TENNANT SPACE C
FUTURE TENNANT SPACE B
1
2
1
1
3
3
3
1
4
5
8"
EDGE OF NEW OPENING
6
12' -
4"
2
2
DEMOLITION PLAN LEGEND
EXISTING, TO BE REMOVED
EXISTING, TO REMAIN
AREA NOT IN SCOPE OF WORK
NORTH
17400 West Capitol DriveBrookfield, WI 53045Phone: 414.778.1700Fax: 414.778.2360E-Mail: [email protected]
REV DATE DESCRIPTION OF ISSUE
SHEET NAME
DRAWN APPROVED
DATE
R&D PROJECT NO.
SHEET NUMBER
2ND LEVEL KEY PLAN
AREA OF WORKALT BID
PROJECT TITLE
MILWAUKEE INTERMODAL
STATION REHABILITATION
PROJECT 2019
DEMOLITIONPLAN - LEVEL 02
02/22/2019
218089.00
A102
Author Approver
Scale:
0' 1' 2' 3'6"
1/8" = 1'-0"1 DEMOLITION PLAN - LEVEL 02
GENERAL DEMOLITION NOTES TO CONTRACTOR
1. DRAWINGS WERE PREPARED BASED ON AVAILABLE EXISTING BUILDING DOCUMENTATION. PRIOR TO CONSTRUCTION,CONTRACTOR SHALL FIELD VERIFY EXISTING CONDITIONS, AND DIMENSIONS TO SATISFY EXECUTION OF WORK. ANYDISCREPANCIES SHALL BE REPORTED TO THE ARCHITECT IMMEDIATELY.
2. EXISTING WALLS, DOORS, FRAMES, ETC. THAT ARE SCHEDULED TO BE REMOVED ARE SHOWN BY HEAVY DASHED LINETYPES. SEE DEMOLITION KEY NOTES FOR SPECIFIC INSTRUCTIONS.
3. EXISTING WALLS, DOORS, FRAMES, ETC. THAT ARE SCHEDULED TO REMAIN ARE SHOWN HALF-TONE AND ARE TO BEPROTECTED FROM DAMAGE DURING DEMOLITION AND CONSTRUCTION. ANY SUCH EXISTING CONDITIONS WHICH AREDAMAGED OR BECOME UNSTABLE DUE TO OTHER DEMOLITION SHALL BE REPLACED AT NO COST TO THE OWNER,WITH NEW CONSTRUCTION TO MATCH.
4. REMOVAL OF ALL HAZARDOUS MATERIALS IS THE SOLE RESPONSIBILITY OF THE OWNER. THE EXISTING BUILDING ISASSUMED TO NOT CONTAIN SUCH MATERIALS. SHOULD ANY MATERIAL BE FOUND, OR IS SUSPECTED TO CONTAINHAZARDOUS MATERIAL, THE CONTRACTOR SHOULD STOP WORK IMMEDIATELY AND NOTIFY OWNER AND ARCHITECT.
5. SEE MEPFP DRAWINGS AND SPECIFICATIONS FOR ELECTRICAL, PLUMBING, FIRE PROTECTION AND HVAC REMOVAL.THESE SYSTEMS ARE SHOWN FOR COORDINATION PURPOSES ONLY.
6. COORDINATE ALL ITEMS TO BE SALVAGED AND TURN OVER TO OWNER.
SEE PROJECT GENERAL CONDITIONS, GENERAL INFORMATION ON SHEET A001 AND SELECTIVE DEMOLITION, CUTTING AND PATCHINGSPECIFICATIONS THAT ARE USED IN ASSOCIATION WITH THESE NOTES.
DEMOLITION PLAN KEY NOTES APPLY TO ALL NEW WORK DRAWINGS AND MAY NOT BE USED ON EVERY SHEET.
DEMOLITION PLAN KEY NOTES
1 REMOVE EXISTING MASONRY WING WALL2 REMOVE EXISTING DOOR AND FRAME3 REMOVE EXISTING FLOOR FINISHES THROUGHOUT AREA OF WORK4 REMOVE EXISTING FLOOR AND WALL FINISHES THROUGHOUT AREA OF WORK - PREP TO RECIEVE NEW5 CUT AND PATCH NEW OPENING IN KIND WITH EXISTING MASONRY WALL FOR NEW DOOR AND FRAME - REFER TO NEW FLOOR
PLAN AND DOOR SCHEDULE6 REMOVE SECTION OF EXISTING MASONRY PARTITION (TO DECK) AS INDICATED, PATCH AND PREP CONCRETE FLOOR AS
NEEDED AT AREA OF REMOVAL TO RECIVE NEW FINISHES
ALTERNATE BID BASE BID - NO WORK LEVEL 2
A102
larjt
Text Box
1 02/22/19 BIDDING DOCUMENTS
UP
A B C D E F G H I J K
.01
1
1a
2
3
0.9
1603 SF
SPACE B229
1711 SF
SPACE 1-C230
72 SF
SPACE 3-C232
75 SF
SPACE 2-C231
9786 SF
SPACE A228
104 SF
CORRIDOR203
218 SF
CORRIDOR223
131 SF
WOMEN222
177 SF
MEN221
216 SF
STAIR 1S-1
57 SF
ELEVATOR 1E-1
82 SF
UTILITY223A
148 SF
STAIR 2S-2
57 SF
ELEVATOR 2E-2
STAIR 3S-3
OPEN TO 1ST FLOOR LOBBYAREA NOT IN SCOPE
A2022
AREA NOT IS SCOPE
AREA NOT IS SCOPE112 SF
MEN204
175 SF
WOMEN205
1
1
1
NEW WORK PLAN LEGEND
EXISTING, TO REMAIN
MASONRY PARTITION, SEE PARTITION TYPES FOR DETAILS
GYPSUM WALL BOARD CEILINGSEE ROOM FINISH SCHEDULE AND SPECIFICATIONS FOR MORE INFORMATION
2X2 ACOUSTICAL CEILING TILESEE ROOM FINISH SCHEDULE AND SPECIFICATIONS FOR MORE INFORMATION
EXPOSED CEILINGSEE ROOM FINISH SCHEDULE
NOT ALL SYMBOLS MAY BE USED.
NORTH
17400 West Capitol DriveBrookfield, WI 53045Phone: 414.778.1700Fax: 414.778.2360E-Mail: [email protected]
REV DATE DESCRIPTION OF ISSUE
SHEET NAME
DRAWN APPROVED
DATE
R&D PROJECT NO.
SHEET NUMBER
2ND LEVEL KEY PLAN
AREA OF WORKALT BID
PROJECT TITLE
MILWAUKEE INTERMODAL
STATION REHABILITATION
PROJECT 2019
NEW WORKPLAN - LEVEL 02
02/22/2019
218089.00
A202
Author Approver
Scale:
0' 4' 8' 12'2'
1/8" = 1'-0"1 NEW WORK PLAN - LEVEL 02
GENERAL FLOOR PLAN NOTES TO CONTRACTOR
1. THIS DRAWING IS FURTHER SUPPORTED BY INFORMATION CONTAINED IN THE SPECIFICATION MANUAL.2. THE CIVIL, STRUCTURAL, MECHANICAL, ELECTRICAL, PLUMBING, FIRE PROTECTION, AUDIO-VISUAL, AND SECURITY
DRAWINGS ARE SUPPLEMENTARY TO THE ARCHITECTURAL DRAWINGS. IT SHALL BE THE RESPONSIBILITY OF THECONTRACTOR TO COORDINATE THE INFORMATION CONTAINED IN ALL THE DRAWINGS BEFORE THE INSTALLATION OF ALLWORK.
3. DO NOT SCALE DRAWINGS. CONTRACTOR TO VERIFY ALL CONDITIONS AND DIMENSIONS AT THE JOB SITE PRIOR TOCOMMENCING CONSTRUCTION.
4. FLOOR ELEVATIONS ARE TO THE TOP OF THE SUB-FLOOR MATERIAL UNLESS OTHERWISE NOTED.5. CONTRACTORS SHALL JOINTLY PROVIDE AND INSTALL ALL STIFFENERS, BRACING, BACKING PLATES, WALL BLOCKING AND
SUPPORTING BRACKETS REQUIRED FOR THE INSTALLATION OF CASEWORK, TOILET ACCESSORIES, PARTITIONS.MILLWORK, AND ALL WORK MOUNTED OR SUSPENDED BY ALL TRADES.
6 REFER TO INTERIOR ELEVATIONS (SHEET A700) FOR ALL WALL MOUNTED EQUIPMENT MOUNTING HEIGHTS ANDEQUIPMENT TAGS
7 REFER TO PLUMBING DRAWINGS AND SPECS FOR P-FIXTURE TYPES
SEE PROJECT GENERAL CONDITIONS, GENERAL INFORMATION ON SHEET A001 AND SELECTIVE DEMOLITION, CUTTING AND PATCHINGSPECIFICATIONS THAT ARE USED IN ASSOCIATION WITH THESE NOTES.
NEW WORK PLAN KEY NOTES APPLY TO ALL NEW WORK DRAWINGS AND MAY NOT BE USED ON EVERY SHEET.
NEW WORK PLAN KEY NOTES
1 PATCH AREAS OF REMOVED FINISHES WITH SIMILAR CONSTRUCTION2 TYP. FURNISH AND INSTALL (F&I) NEW PARTITIONS AS INDICATED - REFER TO PARTITION TYPES3 F&I NEW DOOR, FRAME AND HARDWARE - REFER TO DOOR SCHEDULE4 F&I NEW FLOOR FINISHES, WALL FINISHES AND WALL BASE - REFER TO ROOM FINISH SCHEDULE
Scale:
0' 2' 4' 6'1'
1/4" = 1'-0"2 ENLARGED PLAN - EAST RESTROOMSScale:
0' 2' 4' 6'1'
1/4" = 1'-0"3 ENLARGED PLAN - EAST RESTROOMS
GENERAL REFLECTED CEILING PLAN NOTES TO CONTRACTOR
1. THIS PLAN SHALL BE USED TO ESTABLISH THE LOCATIONS OF THE MAJOR CEILING PENETRATIONS INCLUDING: LIGHTING,HVAC, ACCESS PANEL, SPRINKLERS, SPEAKERS, ETC. SEE MEPFP DRAWINGS FOR MORE SPECIFIC INFORMATIONREGARDING EACH DISCIPLINE. IF CONFLICTS ARE DISCOVERED REGARDING LOCATION OF CEILING PENETRATIONS,CONTACT ARCHITECT FOR FURTHER INFORMATION.
2. ALL DEVICES SHOWN IN CEILING TILE SHALL BE LOCATED IN THE CENTER OF THAT TILE UNLESS OTHERWISE NOTED.3. ALL DIMENSIONS TO CEILING FIXTURES ARE TO CENTER OF FIXTURE UNLESS NOTED OTHERWISE.
SEE PROJECT GENERAL CONDITIONS, GENERAL INFORMATION ON SHEET A001 AND SELECTIVE DEMOLITION, CUTTING AND PATCHINGSPECIFICATIONS THAT ARE USED IN ASSOCIATION WITH THESE NOTES.
REFLECTED CEILING PLAN KEY NOTES APPLY TO ALL NEW WORK DRAWINGS AND MAY NOT BE USED ON EVERY SHEET.
REFLECTED CEILING PLAN KEY NOTES
1 F&I NEW CEILING TILE AND GRID - REFER TO ROOM FINISH SCHEDULE2 REFER TO ELECTRICAL DRAWINGS FOR LIGHTING FIXTURE TYPES AND LOCATIONS
A010
A202
ALTERNATE BID BASE BID - NO WORK LEVEL 2
larjt
Text Box
1 02/22/19 BIDDING DOCUMENTS
SEE
CEI
LIN
G P
LAN
GB-2
SEE PLAN SEE PLAN
MAX
1' -
5"6"
HEATER (BY OTHERS)
34" M
AX
40" M
AX
*TO BOTTOM OFREFLECTIVE SURFACE
HEATER (BY OTHERS)
SEE
CEI
LIN
G P
LAN
PTD-2
MR-1
SD-1
UG-1
6"
1' - 1 7/8"
3' - 7 1/8"
SEE PLAN
6"
SEE
CEI
LIN
G P
LAN
GB-1
GB-3
TPD-1
6"
HEATER (BY OTHERS)
34" M
AX
40" M
AX
*TO BOTTOM OF MR-1REFLECTIVE SURFACE
SEE
CEI
LIN
G P
LAN
PTD-2
MR-1
SD-1
UG-1
4' - 2 1/2"
7 1/8"
SEE PLAN
6"
SEE
CEI
LIN
G P
LAN
SND-1
TPD-1
1' - 11 1/4"
6"
SEE
CEI
LIN
G P
LAN
GB-2
SEE PLAN
SEE PLAN
6"
SEE
CEI
LIN
G P
LAN
GB-1
GB-3
TPD-1
SND-1
1' - 11 1/4"
TO O
UTL
ET
WH
EN O
PEN
ED
T.O
. SEA
T
TO R
IM
(17'-19") AMBULATORYACCESSIBLE WATER CLOSET
STANDARDWATER CLOSET
ACCESSIBLE WHEELCHAIRWATER CLOSET
WATER CLOSET -SIDE ELEVATION
STANDARD URINAL
ADA URINAL
SANITARY NAPKIN
DISPOSAL
DIAPER CHANGING STATION
PAPER TOWEL DISPENSER /
WASTE RECEPTACLE
LAVATORY, SOAP DISPENSER, AND MIRROR
FIRE EXTINGUISHER
CABINET
ROOMSIGNAGE
FLUSH VALVE
GENERAL NOTES:
FLUSH VALVE
1. LIGHT SWITCHES, ELECTRICAL OUTLETS, AND OTHER ENVIRONMENTAL CONTROLS SHALL BE MOUNTED NO HIGHER THAN 4'-0" U.N.O. & NO LOWER THAN1'-3" ABOVE FINISHED FLOOR. IF THE CONTROL IS MOUNTED ABOVE A COUNTER OR OTHER OBSTRUCTION, WHICH IS BETWEEN 20"-25" IN DEPTH, THENTHE MAXIMUM MOUNTING HEIGHT SHALL BE LOWERED TO 3'-8" AFF. LIGHT SWITCHES AND THERMOSTATS IN THE SAME LOCATION ARE TO ALIGNHORIZONTALLY. IF SWITCHES ARE UNABLE TO BE ALIGNED, THE CONTRACTOR IS TO NOTIFY THE ARCHITECT BEFORE PROCEEDING WITH WORK. SEEGENERAL ADA REACH RANGES DIAGRAM FOR MORE INFORMATION.
2. PROVIDE SOLID WOOD BLOCKING OR METAL STRAPPING IN WALLS FOR INSTALLATION OF ACCESSORIES.
3. NOT ALL ACCESSORIES SHOWN ON THIS DRAWING ARE PROVIDED IN THE PROJECT.
SOURCE: ANSI A117.1 - 2003
MAX
IMU
M
4' -
0"
MIN
IMU
M
4' -
6"
9"
ROOM SIGN
LATCH SIDE OF DOOR
TOW
EL S
LOT
3' -
4" T
OOPE
NIN
G1'
- 7"
TO
TABL
E TO
P
2' -
10" T
O
TO P
UM
P
3' -
4"
11"
40" M
AX.
TO R
IM O
F SI
NK
2' -
10" M
AX.
4"
2' -
6" M
IN.
3' -
8"M
AX.
1' -
5"
3' - 0"
2' -
0"
1' -
0"3'
- 6"
PAR
TITI
ON
MIN
.
1' -
3" 33" T
O 3
6"
39" T
O 4
1"18
" MIN
.
39" TO 41"
12" MAX. 42" MIN.
9" MAX.7" MIN.
1 1/
2" M
IN.
33" T
O 3
6"
16" TO 18"
3' - 0" 6"
19" M
AX.
17" M
IN.
1' -
0"4'
- 10
" PAR
TITI
ON
1' - 6"
T.O
. BO
WL
1' -
3"
SND-1
PTD-2
DCS-1
SD-1
TPD-1
GB-3
GB-1
GB-2
MR-1
UG-1 UG-1
SD-1
17400 West Capitol DriveBrookfield, WI 53045Phone: 414.778.1700Fax: 414.778.2360E-Mail: [email protected]
REV DATE DESCRIPTION OF ISSUE
SHEET NAME
DRAWN APPROVED
DATE
R&D PROJECT NO.
SHEET NUMBER
PROJECT TITLE
MILWAUKEE INTERMODAL
STATION REHABILITATION
PROJECT 2019
INTERIORELEVATIONS
02/22/2019
218089.00
A700
Author Approver
Scale:
0' 2' 4' 6'1'
3/8" = 1'-0"1 MEN'S RESTROOM - SOUTHScale:
0' 2' 4' 6'1'
3/8" = 1'-0"2 MEN'S RESTROOM - WESTScale:
0' 2' 4' 6'1'
3/8" = 1'-0"3 MEN'S RESTROOM - NORTHScale:
0' 2' 4' 6'1'
3/8" = 1'-0"4 MEN'S RESTROOM - EAST
Scale:
0' 2' 4' 6'1'
3/8" = 1'-0"5 WOMEN'S RESTROOM - SOUTHScale:
0' 2' 4' 6'1'
3/8" = 1'-0"6 WOMEN'S RESTROOM - WESTScale:
0' 2' 4' 6'1'
3/8" = 1'-0"7 WOMEN'S RESTROOM - NORTHScale:
0' 2' 4' 6'1'
3/8" = 1'-0"8 WOMEN'S RESTROOM - EAST
Scale:
0' 1.3' 2.7' 4'0.7'
3/8" = 1'-0"9 MOUNTING HEIGHT STANDARDS - FOR REFERENCE ONLY
IAW INTERIOR ARCHITECTURAL WOODWORKIWP IMPACT WALL PROTECTIONLMC LINEAR METAL CEILINGLWC LINEAR WOOD CEILINGMPC METAL PAN CEILINGPLAM PLASTIC LAMINATEPLAS PLASTERPT PAINTRT RUBBER FLOOR TILE
INTEGRAL COVE BASEEXP EXPOSEDEXTG EXISTINGFAB FABRICFL MAT FLOOR MATG GROUTGROM GROMMETGWB GYPSUM WALL BOARD
DOOR SCHEDULE ABBREVIATIONS
ALUM ALUMINUMGL GLASS
HM HOLLOW METAL SSV STAIN, SEAL AND VARNISH
PREFIN PRE-FINISHEDPT PAINT
SST STAINLESS STEELWD WOOD DOOR
SPOT GROUT @JAMB ANCHORS
JAMB ANCHOR(3) PER DOOR
H.M. DOOR FRAME(SEE DOOR SCHED.)
GWB PARTITION(SEE PLAN FOR PARTITION TYPE)
A GWB PARTITIONS
H.M. DOOR FRAME(SEE DOOR SCHED.)
JAMB ANCHOR(3 PER DOOR)
GWB LAYER (SEE PLAN FOR PARTITION TYPE)
SPOT GROUT @JAMB ANCHORS
CMU PARTITION (SEE PLAN FOR PARTITION TYPE)
SEALANT & BACKER ROD(BOTH SIDES)
B GWB/CMU PARTITIONS
6" 1"
NOTE:DETAIL SIMILAR AT CONDITIONS WITH FURRING ON BOTH SIDES.
NOTE:PROVIDE WRAP AROUND FRAMES AT ALL GWB PARTITIONS
CERAMIC TILE SEE ROOM FINISH SCHEDULE FOR LOCATIONS.
PROVIDE METAL EDGE STRIP WHERE CERAMIC TILE ABUTS DOOR FRAMES, TYP.
H.M. DOOR FRAME(SEE DOOR SCHED.)
GWB LAYER (SEE PLAN FOR PARTITION TYPE)
CMU BOND BEAM
SEALANT & BACKER ROD(BOTH SIDES)
B GWB/CMU PARTITIONS
6"
NOTE:DETAIL SIMILAR AT CONDITIONS WITH FURRING ON BOTH SIDES.
SPOT GROUT @JAMB ANCHORS
JAMB ANCHOR(3) PER DOOR
H.M. DOOR FRAME(SEE DOOR SCHED.)
GWB PARTITION(SEE PLAN FOR PARTITION TYPE)
A GWB PARTITIONS
NOTE:PROVIDE WRAP AROUND FRAMES AT ALL GWB PARTITIONS
CERAMIC TILE SEE ROOM FINISH SCHEDULE FOR LOCATIONS.
PROVIDE METAL EDGE STRIP WHERE CERAMIC TILE ABUTS DOOR FRAMES, TYP.
LINTEL SCHEDULE FOR MASONRY DOOR ROUGH OPENINGS UP TO6'-4" (MAX.); 8" BOND BEAM W/ (2) #5's (MIN.) SEE STRUCTURAL. BOND BEAM IS 16"GREATER THAN SCHEDULED MASONRY R.O. (TYP.). GROUT EA. 8" JAMBCELL SOLID W/ (2) #5's AS REQ'D FOR LINTEL BEARING
HOLLOW METALDOOR FRAME
A
GWB PARTITION
2"
2" VARY 2"
3/8"
1/2"
TYPE
VARIESSEE PARTITION 1/2"
SINGLE LEAF DOOR FLUSH
F
SEESCHED.
SEE
SCH
ED.
1
SEE
SCH
ED.
2"
2"SEE
SCHED. 2"
A
17400 West Capitol DriveBrookfield, WI 53045Phone: 414.778.1700Fax: 414.778.2360E-Mail: [email protected]
REV DATE DESCRIPTION OF ISSUE
SHEET NAME
DRAWN APPROVED
DATE
R&D PROJECT NO.
SHEET NUMBER
PROJECT TITLE
MILWAUKEE INTERMODAL
STATION REHABILITATION
PROJECT 2019
ROOMFINISH/DOORSCHEDULE
02/22/2019
218089.00
A900
Author Approver
ROOM FINISH SCHEDULE
ROOM # ROOM NAME FLOOR BASEWALL
CEILING NOTESNORTH SOUTH WEST EASTENLARGED PLAN - EAST RESTROOMS203 CORRIDOR - - - - - ACT-1 1204 MEN CT-1 CTB-1 PT-1 PT-1/CT-2 PT-1 PT-1 ACT-2 1205 WOMEN CT-1 CTB-1 PT-1/CT-2 PT-1 PT-1 PT-1 ACT-2 1228 SPACE A - - - - - - - 1229 SPACE B - - - - - - - 1230 SPACE 1-C - - - - - - - 1231 SPACE 2-C - - - - - - - 1232 SPACE 3-C - - - - - - - 1
ROOM FINISH SCHEDULE NOTES
1. PATCH EXISTING FINISHES AFFECTED BY DEMOLITION
FINISHES SCHEDULE
MARK MANUFACTURER PRODUCT STYLE SIZE COMMENTSACT-1 ACOUSTICAL CEILING TILE 2' X 2'ACT-2 ACOUSTICAL GYPSUM CEILING TILE 2' X 2'CT-1 CROSSVILLE CERAMIC FLOOR TILE 12" X 12"CT-2 CROSSVILLE CERAMIC WALL TILE 12" X 24"
CTB-1 CROSSVILLE CERAMIC TILE BASE 6" X 12"PT-1 WALL PAINT
DOOR AND FRAME SCHEDULE
DOORNO. ROOM NAME
DOORS DOORS FRAMES DETAILSFIRE
RATINGHARDWARE
GROUP NOTESLEAF
QUANTITY WIDTH WIDTH HEIGHT TYPE MATERIAL FINISH GLASS TYPE MATERIAL FINISH HEAD JAMB204A MEN (1) 3' - 0" 3' - 0" 7' - 0" F WD SSV NA 1 HM PT-1 2B 1B 0 90 1,2204B CHASE (1) 2' - 0" 2' - 0" 7' - 0" F WD SSV NA 1 HM PT-1 2A 1A 0 14 1205 WOMEN (1) 3' - 0" 3' - 0" 7' - 0" F WD SSV NA 1 HM PT-1 2A 1A 0 90 1,2
DOOR AND FRAME SCHEDULE NOTES
1. REFER TO SPECIFICATIONS FOR HARDWARE GROUP INFORMATION (SEE SPECIFICATION SECTION 08 71 00 - DOOR HARDWARE)2 WOOD (WD) DOOR SPECIES AND FINISH TO MATCH EXISTING 2ND FLOOR EAST RESTROOMS
KOHLER ADA COMPLIANT WALL HUNG, 20"x18" VITREOUS CHINA
LAVATORY WITH 4" FAUCET CENTERS.
DECK MOUNTED FAUCET WITH GOOSENECK SPOUT,
WRISTBLADE HANDLES, CERAMIC DISC CARTRIDGES AND AERATOR OUTLET.
WITH LAMINAR FLOW OUTLET
895-317CPR
-E29
CHICAGO
FAUCET
FAUCET
COMMERCIAL GRADE, ADJUSTABLE, FLOOR MOUNTED WITH
SHORT FEET, FOR CONCEALED ARM MOUNTING.CARRIER
BARDON
K-4991-ET
KOHLER
COMMERCIAL GRADE, FLOOR MOUNTED WITH SHORT FEET
ADA COMPIANT, VITREOUS CHINA, WALL HUNG, 3/4" TOP
SPUD, 1.0 GPF WASHDOWN FLUSHING ACTION.
SLOAN
CARRIER
FLUSH VALVE
URINAL
U-1
SLOAN EXPOSED FLUSH VALVE, 1.0 GPF.
EXPOSED FLUSH VALVE, 1.6 GPF.
KINGSTON
K-4325
KOHLER
COMMERCIAL GRADE, ADJUSTABLE, FLOOR MOUNTED WITH
SHORT FEET
ELONGATED, WHITE, OPEN FRONT LESS COVER, WITH
STAINLESS STEEL SELF-SUSTAINING CHECK HINGE.
VITREOUS CHINA, WALL HUNG, ELONGATED BOWL, TOP SPUD,
1.6 GPF.
1955 SSCBEMIS
SLOAN
CARRIER
FLUSH VALVE
SEAT
WATER CLOSET
WC-2
SLOAN
NON-FREEZE TYPE WITH APPROVED VACUUM BREAKER-
BACKFLOW PREVENTER WITH WALL FLANGE, LOOSE KEY OPERATED.
65WOODFORDHOSEBIBB
HB-1
WATER HEATER SCHEDULE
MECH RM
LOCATION
CEMLINE H8SEH830 -
MANUFACTURER MODEL NO.RECOVERY
GPH ELEC
CONTROL VALVE
- 30 40 140 1523.01 2 NO
°F OUT
HOT WATERRISE(°F) GPM
TEMP.
°F IN PSILBS/HR
STEAM
AIR
YES 120 1
ELECTRICAL
VOLT PHASETAG. NO.
WH-1
CLEANOUT SCHEDULE
COVER
MATERIAL
FCO.
WCO.
FCO.
CO.
TAG
C.I.
-
BODY
-
N.B.
C.P.
FACE PLATE
-
-
-
-
-
ANCHORPLATE
-
CONCRETEPAD
-
J.R. SMITH FIG. NO. 4020-Y
BRASS RECESSED PLUG W/ SLOTTED RECESS
TYPICAL MODEL NO.
J.R. SMITH FIG. NO. 4710
J.R. SMITH FIG. NO. 4108
CARPET MARKER
MISC.
-
BRASS - -
-BRASS N.B.
IRON
-
DRAIN SCHEDULE
CLAMP
FLASHINGLOCATION
FD-1
TAG NO.
FLOOR
TYPE
N.B.
MATERIAL
C.I.
BODY TOP
5" N.B.
STRAINER
J.R. SMITH 2010-A-NB
MISC.
YES
MODEL NO.
NOTE:
PROVIDE FLASHING FOR ALL DRAINS INSTALLED ABOVE GRADE.
AREASFINISHED -
17400 West Capitol DriveBrookfield, WI 53045Phone: 414.778.1700Fax: 414.778.2360E-Mail: [email protected]
REV DATE DESCRIPTION OF ISSUE
PROJECT TITLE
SHEET NAME
DRAWN APPROVED
DATE
R&D PROJECT NO.
SHEET NUMBER
MILWAUKEEINTERMODAL
STATION
PLUMBINGSYMBOLS,
ABBREVIATIONS& SHEET INDEX
02/22/19
218089.00
P000
R&D R&D
PLUMBING SHEET INDEX
No. Sheet Name
P000 PLUMBING SYMBOLS, ABBREVIATIONS & SHEET INDEX
P200 PLUMBING BASEMENT OVERALL PLANS
P201 PLUMBING FIRST FLOOR OVERALL PLANS
P202 PLUMBING SECOND FLOOR OVERALL PLANS
P204 PLUMBING ROOF PLAN OVERALL PLANS
P000
1 TYPICAL PIPE SUPPORT DETAILSP000
2 Pd-TYPICAL IN-LINE CIRCULATION PUMP
1 02/22/19 BIDDING DOCUMENTS
B C D E F G H I J K
1
1a
2
3
4
RAMP UP TO TRAINS
CRAWL SPACE
VESTIBULE
ELECTRICAL EQUIPMENT
MECHANICAL EQUIPMENT
B C D E F G H I J K
1
1a
2
3
4
RAMP UP TO TRAINS
CRAWL SPACE
VESTIBULE
ELECTRICAL EQUIPMENT
MECHANICAL EQUIPMENT
B C D E F G H I J K
WATER
HEATER
x
CIRC.
PUMP
x
SEE HVAC DEMO
PLANS FOR
CONTINUATION
(2) WATERMETERSSTACKED VERTICALLY
6" WS
GG
GAS METER
FCO.
CO.
6"
6"
6" COND. UP
CO.
5"
CO.
4"
3"
CO.
3" W. UP
GAS VALVE
FD
GAS VALVE
3" WS
3" CW
3/4" GAS VENTGAS VENT
TO FIRE SPRINKLER SYSTEM
3/4" CW
3/4" CW UP TO HB
CO.
4" W. UP
3" W. UP
SUMP PUMP DISCHARGE
3"
4" W. UP
2"
2" HW UP
2"
3/4" HWR UP
3" CW UP
3/4"
x
B C D E F G H I J K
6" WS
GG
GAS METER
FCO.
CO.
6"
6"
6" COND. UP
CO.
5"
CO.
4"
3"
CO.
3" W. UP
GAS VALVE
FD
GAS VALVE
3" WS
3" CW
3/4" GAS VENTGAS VENT
TO FIRE SPRINKLER SYSTEM
3/4" CW
3/4" CW UP TO HB
CO.
4" W. UP
3" W. UP
SUMP PUMP DISCHARGE
3"
WH-1
CP-1
4" W. UP
2"
3/4"
2" HW UP
2"
3/4" HWR UP
2" CW
TO WH
3" CW UP
MODIFY PIPING FOR
NEW EQUIPMENT
(2) WATERMETERSSTACKED VERTICALLY
NORTH
17400 West Capitol DriveBrookfield, WI 53045Phone: 414.778.1700Fax: 414.778.2360E-Mail: [email protected]
REV DATE DESCRIPTION OF ISSUE
PROJECT TITLE
SHEET NAME
DRAWN APPROVED
DATE
R&D PROJECT NO.
SHEET NUMBER
KEY PLAN
MILWAUKEE
INTERMODAL
STATION
PLUMBING
BASEMENT
OVERALL
PLANS
02/22/19
218089.00
P200
R&D R&D
1/8" = 1'-0"P200
1 BASEMENT DEMO
1/8" = 1'-0"P200
2 BASEMENT NEW
NORTH
NORTH
1 02/22/19 BIDDING DOCUMENTS
F.E.
F.E.C.
F.E.
F.E.
F.E.C.
F.E.C.
F.E.C.F.E.C.
WE ENERGIES MSB
MAIN
DIST
DIST MAIN
DP
EXISTING EQUIPMENT
T/DP
LCP1 LP1 PP1
DP/MB 40PSB
ATS/40PSB
ATS/4LS
DP/EM
4LS2LS
T/2LS
FACP
T/20PSB
20PSB
B C D E F G H I J K
2'-8" AFF
FUTURERETAILKIOSK
136A
BAGGAGE
GREYHOUND
104
TICKETING
AMTRAK
140
CORRIDOR116A
PHONES
116B
SECURITY
116C
CLOSET
JANITOR'S
107
CASH
111
CLOSET
132
ROOM
ELECTRICAL
131
ROOM
ELECTRICAL
122
CORRIDOR
121
RESTROOM
WOMEN'S
120
RESTROOM
MEN'S
119
ALCOVE
118
TOILET ROOM
FAMILY UNISEX
117
CORRIDOR
S-3
STAIR 3
E-2
ELEVATOR 2
S-2
STAIR 2
114
QUEUING
AMTRAK
112
BAGGAGE
AMTRAK
110
TOILET109
STORAGE
108
OFFICE
AGENT'S
106
ACCOUNTING
105
PASSAGE
113
CLAIM
BAGGAGE
101
LOBBY
ELEVATOR
100
CORRIDOR
115
TENANT SPACE
136
BAGGAGE
GREYHOUND
123
TICKETING
GREYHOUND
127
SERVICE
CUSTOMER
129
CLERK
REPORT
128
ROOM
COPY
124
CASH
125
MANAGER
TERMINAL
133
CLOSET
JANITOR
126
CORRIDOR
130
C.O.D.
F.E.
F.E.C.
F.E.
F.E.
F.E.C.
F.E.C.
F.E.C.F.E.C.
WE ENERGIES MSB
MAIN
DIST
DIST MAIN
DP
EXISTING EQUIPMENT
T/DP
LCP1 LP1 PP1
DP/MB 40PSB
ATS/40PSB
ATS/4LS
DP/EM
4LS2LS
T/2LS
FACP
T/20PSB
20PSB
B C D E F G H I J K
2'-8" AFF
FUTURERETAILKIOSK
136A
BAGGAGE
GREYHOUND
104
TICKETING
AMTRAK
140
CORRIDOR116A
PHONES
116B
SECURITY
116C
CLOSET
JANITOR'S
107
CASH
111
CLOSET
132
ROOM
ELECTRICAL
131
ROOM
ELECTRICAL
122
CORRIDOR
121
RESTROOM
WOMEN'S
120
RESTROOM
MEN'S
119
ALCOVE
118
TOILET ROOM
FAMILY UNISEX
117
CORRIDOR
S-3
STAIR 3
E-2
ELEVATOR 2
S-2
STAIR 2
114
QUEUING
AMTRAK
112
BAGGAGE
AMTRAK
110
TOILET109
STORAGE
108
OFFICE
AGENT'S
106
ACCOUNTING
105
PASSAGE
113
CLAIM
BAGGAGE
101
LOBBY
ELEVATOR
100
CORRIDOR
115
TENANT SPACE
136
BAGGAGE
GREYHOUND
123
TICKETING
GREYHOUND
127
SERVICE
CUSTOMER
129
CLERK
REPORT
128
ROOM
COPY
124
CASH
125
MANAGER
TERMINAL
133
CLOSET
JANITOR
126
CORRIDOR
130
C.O.D.
1
1a
2
3
4
.09
B C D E F G H I J K
4" VS UP
4" WS UP
3" CW, 1-1/4" HW & 3/4" HWR UP
6" COND. UP & DN.
4" W. DN.
3" CW, 2" HW & 1" HWR DN.
3" CW, 2" HW & 1" HWR
4"
2" W.
CO.
1
1a
2
3
4
.09
B C D E F G H I J K
6" COND. UP & DN.
4" W. DN.
3" CW, 2" HW & 1" HWR DN.
3" CW, 2" HW & 1" HWR
4"
4" VS UP
4" WS UP
3" CW, 1-1/4" HW & 3/4" HWR UP
2" W.
2" W. UP
3" W. UP
3" W. UP
2" W. UP
3"
3"
CO.
NORTH
17400 West Capitol DriveBrookfield, WI 53045Phone: 414.778.1700Fax: 414.778.2360E-Mail: [email protected]
REV DATE DESCRIPTION OF ISSUE
PROJECT TITLE
SHEET NAME
DRAWN APPROVED
DATE
R&D PROJECT NO.
SHEET NUMBER
KEY PLAN
MILWAUKEE
INTERMODAL
STATION
PLUMBING
FIRST FLOOR
OVERALL
PLANS
02/22/19
218089.00
P201
R&D R&D
1/8" = 1'-0"P201
1 FIRST FLOOR DEMO
NORTH
1/8" = 1'-0"P201
2 FIRST FLOOR NEW
NORTH
1 02/22/19 BIDDING DOCUMENTS
1
1a
2
3
4
.09
B C D E F G H I J K
2-1/2" CW UP, 1" HW UP& 3/4" HWR UP & DN.
4" WS & VS UP & DN.
2" CW CAPPED CONNECTIONREMOVE ABANDON
WATER, WASTE & VENT
PIPING IN WALL
REMOVE ABANDON
WATER, WASTE & VENT
PIPING IN WALL
CO.
x
x
1
1a
2
3
4
.09
B C D E F G H I J K
L-1
L-1
U-1FD-1
FD-1
WC-1
WC-1
WC-2
2-1/2" CW UP, 1" HW UP& 3/4" HWR UP & DN.
4" WS & VS UP & DN.
NEW HW & HWR VALVES
2" CW CAPPED CONNECTION
NEW WASTE &
VENT CONNECTION
2" CW DN.
1/2" CW DN.
2" W. DN. & 1-1/2" V.
1/2" HW DN.
1/2" CW DN.
2" W. DN. & 1-1/2" V.
1/2" HW DN.
CO.
NORTH
17400 West Capitol DriveBrookfield, WI 53045Phone: 414.778.1700Fax: 414.778.2360E-Mail: [email protected]
REV DATE DESCRIPTION OF ISSUE
PROJECT TITLE
SHEET NAME
DRAWN APPROVED
DATE
R&D PROJECT NO.
SHEET NUMBER
KEY PLAN
MILWAUKEE
INTERMODAL
STATION
PLUMBING
SECOND FLOOR
OVERALL
PLANS
02/22/19
218089.00
P202
R&D R&D
1/8" = 1'-0"P202
1 SECOND FLOOR DEMO
NORTH
1/8" = 1'-0"P202
2 SECOND FLOOR NEW
NORTH
1 02/22/19 BIDDING DOCUMENTS
1
1a
2
3
4
.09
B C D E F G H I J K
1"TO HB
1-1/2"
1-1/2"TO HVAC EQPM. x
1-1/2" CW DN.
1
1a
2
3
4
.09
B C D E F G H I J K
1-1/2"
1-1/2"
1"TO HB1-1/2" CW DN.
1-1/2" CW
HB-1
3/4" CW DN.
NORTH
17400 West Capitol DriveBrookfield, WI 53045Phone: 414.778.1700Fax: 414.778.2360E-Mail: [email protected]
REV DATE DESCRIPTION OF ISSUE
PROJECT TITLE
SHEET NAME
DRAWN APPROVED
DATE
R&D PROJECT NO.
SHEET NUMBER
KEY PLAN
MILWAUKEE
INTERMODAL
STATION
PLUMBING
ROOF PLAN
OVERALL
PLANS
02/22/19
218089.00
P204
R&D R&D
1/8" = 1'-0"P204
1 ROOF PLAN DEMO
NORTH
1/8" = 1'-0"P204
2 ROOF PLAN NEW
NORTH
1 02/22/19 BIDDING DOCUMENTS
ABBREVIATIONS:(ALL ABBREVIATIONS SHOWN MAY NOT APPEAR ON DRAWINGS)
COMPRESSED AIR
ACCESS DOOR
ABOVE FINISHED FLOORAIR FLOW MEASURING STATION
ACOUSTICALLY LINED DUCT
AUTO MAKE-UP VALVE
ACCESS PANELBACKDRAFT DAMPER
BLIND FLANGE
BOILER FEED
BETWEEN JOISTSBALANCING VALVE
CHEMICAL FEED
CHECK VALVE
CHILLED/HOT WATER RETURNCHILLED/HOT WATER SUPPLY
CONDENSER WATER RETURN
CONDENSER WATER SUPPLY
COMBINATION VALVECHILLED WATER RETURN
CHILLED WATER SUPPLY
CLEAR WATER WASTE
DRAINDIFFERENTIAL PRESSURE TRANSMITTER
DUCT SMOKE DETECTOR
DOOR TRANSFER GRILLE
DRAIN VALVEDOMESTIC WATER
EXHAUST AIR
ELECTRICAL CONTRACTOR
EXHAUST GRILLEFLEXIBLE CONNECTION
FLOW CONTROL VALVE
FIRE DAMPER
FLOW METERFIRE/SMOKE DAMPER
NATURAL GAS
GENERAL CONTRACTOR
GLOBE VALVEGLYCOL WATER RETURN
GLYCOL WATER SUPPLY
HVAC CONTRACTOR
HIGH PRESSURE CONDENSATEHIGH PRESSURE STEAM
HOT WATER RETURN
HOT WATER SUPPLY
LP GASLOW PRESSURE CONDENSATE
LOW PRESSURE STEAM
MANUAL AIR VENT
MECHANICAL CONTRACTORMOTOR OPERATED DAMPER
MINIMUM
MAKE-UP WATER
NOT IN CONTRACTOUTSIDE AIR
OIL RETURN
OIL SUPPLY
PUMPPLUMBING CONTRACTOR
PUMPED CONDENSATE RETURN
POWER ROOF VENTILATOR
RETURN AIRRETURN AIR OPENING
REHEAT COIL
RADIANT CEILING PANEL
RETURN GRILLEREFRIGERANT LIQUID
REFRIGERANT SUCTION
SMOKE DAMPER
SUPPLY AIRSLOT DIFFUSER
SUPPLY GRILLE
SOLAR HEATING WATER RETURN
SOLAR HEATING WATER SUPPLYSHUT OFF VALVE
STARTER
TRANSFER AIR
TRANSFER AIR OPENINGTEMPERATURE CONTROL CONTRACTOR
TEMPERATURE CONTROL PANEL
TEMPERATURE CONTROL VALVE
TRANSFER GRILLETHRU JOISTS
TIGHT TO STRUCTURE
TYPICAL
UNDER CUT DOORVENT
VOLUME DAMPER
VARIABLE FREQUENCY DRIVE
WATER FLOW MEASURING STATIONWELL FIELD RETURN
WELL FIELD SUPPLY
WATER RELIEF VALVE
WELDED WIRE MESH
A
AD
AFFAFMS
ALD
AMV
APBDD
BF
BF
BJBV
CF
CHV
CHWRCHWS
CR
CS
CVCWR
CWS
CWW
DDPT
DSD
DTG
DVDW
EA
E.C.
EGFC
FCV
F
FMFS
G
G.C.
GLVGR
GS
H.C.
HPCHPS
HWR
HWS
LPLPC
LPS
MAV
M.C.MOD
MIN.
MUW
NICOA
OR
OS
PP.C.
PCR
PRV
RARAO
RC
RCP
RGRL
RS
S
SASD
SG
SOLR
SOLSSOV
STR
TA
TAOT.C.C.
TCP
TCV
TGTJ
TTS
TYP.
UCDV
VD
VFD
WFMSWFR
WFS
WRV
WWM
SYMBOLS:(ALL SYMBOLS SHOWN MAY NOT APPEAR ON DRAWINGS)
UCD
DG
MOD
D
DUCT (R)ISE / (D)ROP
RADIUS ELBOW1.5 W 1 W
MITERED ELBOW WITHOUT
TURNING VANES
MITERED ELBOW WITH
TURNING VANES
RECTANGULAR BRANCH
TAKEOFF
ROUND BRANCH
TAKEOFF
BULLHEAD TEE FOR
RETURN OR EXHAUST
BULLHEAD TEE FOR
SUPPLY
RADIUS TEE
ECCENTRIC TRANSITION
CONCENTRIC TRANSITION
DUCT CAP
SUPPLY AIR DUCT
RETURN AIR DUCT
EXHAUST AIR DUCT
FLEXIBLE DUCTWORK
HIDDEN DUCTWORK
DUCT SIZE
(FIRST FIGURE IS SIDE SHOWN)
SUPPLY GIRLLE
(4-WAY THROW)
(E)XHAUST / (R)ETURN
(T)RANSFER GIRLLE
TYPE OF GRILLE:(S)UPPLY(R)ETURN(E)XHAUST(T)RANSFER
SCHEDULE
DESIGNATION
CFM
DOOR UNDERCUT
DOOR GRILLE
SUPPLY GIRLLE
(2 OR 3-WAY THROW)
MOTOR OPERATED DAMPER
FIRE DAMPER
SMOKE DAMPER
FIRE / SMOKE DAMPER
BALANCING DAMPER
BALL VALVE
BALANCING VALVE
BUTTERFLY VALVE
SHUT-OFF VALVE
STRAINER
THERMOMETER
UNION
PIPE/DUCT PITCH
PRESSURE GAUGE
FLOW METER
TEST CONNECTION
PIPE GUIDE
ANCHOR
FLEXIBLE CONNECTION
PIPING CAP
BLIND FLANGE/CLEANOUT
MANUAL AIR VENT
GAUGE COCK
DIFFERENTIAL PRESSURE SENSOR
FLOW SENSORFS
P
FM
CHILLED WATER RETURN
CHILLED WATER SUPPLY
HOT WATER RETURN
HOT WATER SUPPLY
DOMESTIC WATER
DRAIN
VENT
HUMIDISTAT
CUMULATED THERMOSTAT
THERMOSTAT
H
TC
T
HS HUMIDITY SENSOR
TEMPERATURE SENSORTS
S STATIC PRESSURE SENSOR
NATURAL GAS
X=CENTERLINE OF PIPEXOR BOTTOM OF DUCT
THERMOSTATTN
NIGHT SETBACK
MAKE-UP WATER
XY
X=SECTION NUMBERSHOWN ON DRAWING SHEET Y
DEW POINT SENSORDP
CONNECT TO EXISTING
TEMP. CONTROL VALVE
CHECK VALVE
FLOW CONTROL VALVE
COMBINATION VALVE
AUTO MAKE-UP VALVE
PRESS. RELIEF VALVE
PRESS. REDUCING VALVE
FLOW CONTROL/SHUTOFF VALVE
DRAIN VALVE
3-WAY VALVE(MOTOR ACTUATED)
HWS
HWR
CWS
CWR
DW
V
D
G
MUW
26/12
SG-2(110)
F
S
FS
D
ROUND DUCT (R)ISE / (D)ROP
REHEAT COIL
ACCESS DOOR
FLEXIBLE CONNECTION
PIPE TAKE-OFF
DSD DUCT SMOKE DETECTOR
SINGLE LINE AIR DUCT
HIGH PRESSURE CONDENSATEHPC
HIGH PRESSURE STEAMHPS
LOW PRESSURE CONDENSATELPC
LOW PRESSURE STEAMLPS
SQUARE TO ROUND TRANSITION
REMOVE EXISTING
REFRIGERANT LIQUID
PUMPED CONDENSATE
RETURN
CHILLED/HOT WATER SUPPLY
CHILLED/HOT WATER RETURN
GLYCOL SUPPLY
REFRIGERANT SUCTION
OIL RETURN
GLYCOL RETURN
OIL SUPPLY
CHWR
CHWS
PCR
RL
GS
OR
RS
GR
OS
CONDENSER SUPPLYCS
CONDENSER RETURNCR
BOILER FEEDBF
CHEMICAL FEEDCF
COMPRESSED AIR
LP GAS
A
LP
OUTSIDE AIR DUCT
APPLICABLE CODES AND STANDARDSTHE MECHANICAL SYSTEMS SPECIFICATIONS WILL REFERENCE THE FOLLOWING CODES, GUIDELINES AND STANDARDS AND ARE DESIGNED TO MEET OR EXCEED THESE STANDARDS.
INTERNATIONAL BUILDING CODE - 2015 EDITION.INTERNATIONAL ENERGY CONSERVATION CODE - 2015 EDITION.INTERNATIONAL MECHANICAL CODE - 2015 EDITION.INTERNATIONAL FUEL GAS CODE - 2015 EDITION.NATIONAL ELECTRICAL CODE - 2017 EDITION.BOILER AND PRESSURE VESSELS CODE, WISCONSIN ADMINISTRATIVE CODE SPS 341 - MOST CURRENT.FACILITY GUIDELINES INSTITUTE GUIDELINES FOR HEALTH CARE - 2014 EDITION.ASHRAE 170-2008 WITH ADDENDUMS ADOPTED BY THE STATE OF WISCONSIN DHS.NATIONAL FIRE PROTECTION ASSOCIATION (NFPA) CODE - 2010 EDITION.AMERICAN SOCIETY OF HEATING, REFRIGERATION AND AIR CONDITIONING ENGINEERS (ASHRAE).AMERICAN SOCIETY OF MECHANICAL ENGINEERS (ASME).AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI).SHEET METAL AND AIR CONDITIONING CONTRACTORS NATIONAL ASSOCIATION, INC. (SMACNA).DEPARTMENT OF NATURAL RESOURCES (DNR).AMERICAN DISABILITIES ACT (ADA).
a.b.c.d.e.f.g.h.i.j.k.l.m.n.o.
1. CERTAIN AREAS OF THE BUILDING UTILIZE A
RETURN AIR PLENUM. ALL MATERIALS IN PLENUM
SPACES SHALL MEET NFPA 90 AND IMC 602.
2. INSTALL ALL DUCTWORK AND PIPING TO BEST
SUIT FIELD CONDITIONS; DRAWINGS ARE
DIAGRAMMATIC AND SHALL NOT BE SCALED TODETERMINE EXACT LOCATION.
3. ALL RECTANGULAR DUCTWORK DIMENSIONS ARE
INTERIOR DIMENSIONS, ADJUST SHEET METALSIZE FOR DUCT LINING WHERE APPLICABLE.
4. CERTAIN OFFSETS ARE SHOWN IN THE
DUCTWORK AND PIPING TO INDICATE THEGENERAL POSITION AND RELATIONSHIP OF THE
SYSTEMS. PROVIDE ADDITIONAL OFFSETS,
SIMILAR TO THOSE SHOWN, AS REQUIRED BY
FIELD CONDITIONS.
5. ALL BRANCH DUCTWORK TAKEOFFS SHALL BE
EXPANDED AT 45° ANGLE, FOR BOTH HORIZONTAL
AND VERTICAL TAKEOFFS.
6. PROVIDE TRANSITIONS FOR TAKEOFFS FROM
BRANCH DUCTWORK TO GRILLES AND DIFFUSERS
AS REQUIRED. SEE GRILLE AND DIFFUSERSCHEDULES FOR SIZES.
7. CONTRACTOR MAY USE SPIRAL ROUND
DUCTWORK FOR RECTANGULAR TOILET ANDMISCELLANEOUS EXHAUST DUCTWORK. ROUND
DUCTWORK SHALL BE EQUIVALENT SIZE AS
RECTANGULAR DUCT.
8. CONTRACTOR MAY USE UP TO FIVE (5) FEET OF
FLEXIBLE DUCT FOR CONNECTION OF EXHAUST
GRILLES TO TOILET AND MISCELLANEOUS
EXHAUST DUCTWORK. ONLY ONE (1) 90° BENDALLOWED PER SECTION OF FLEX.
9. COORDINATE ALL DUCT AND PIPE CONNECTIONS
REQUIRED FOR OWNER FURNISHED EQUIPMENT.PROVIDE DAMPERS, SHUTOFF VALVES, ETC. AS
REQUIRED FOR COMPLETE INSTALLATION AND
RECOMMENDED BY EQUIPMENT MANUFACTURER.
VERIFY EXACT REQUIREMENTS WITH EQUIPMENTMANUFACTURER.
GENERAL NOTES
17400 West Capitol DriveBrookfield, WI 53045Phone: 414.778.1700Fax: 414.778.2360E-Mail: [email protected]
REV DATE DESCRIPTION OF ISSUE
SHEET NAME
DRAWN APPROVED
DATE
R&D PROJECT NO.
SHEET NUMBER
PROJECT TITLE
MILWAUKEE INTERMODAL
STATION REHABILITATION
PROJECT 2019
MECHANICALSYMBOLS,
ABBREVIATIONS,SHEET INDEX
02/22/2019
218089.00
M000
R&D R&D
MECHANICAL SHEET INDEX
M000 MECHANICAL SYMBOLS, ABBREVIATIONS, SHEET INDEX
M100 PENTHOUSE MECH. DEMOLITION PLANS
M200 PENTHOUSE MECH. NEW CONSTRUCTION PLANS
M210 BASEMENT AND SECOND MECH. FLOOR PLANS
M500 MECHANICAL DETAILS
M501 MECHANICAL DETAILS
M600 MECHANICAL SCHEDULES
1 02/22/19 BIDDING DOCUMENTS
T
2
M100
MOD
MOD
EXISTING PRE-HEAT
COILS WITH BY-PASS.(2-STACKED)
EXIST. DX
COOLING COILS(4-STACKED)
EXISTING
SUPPLY FAN (EXSAF-1)
60/18 SA DN.
60/18 SA DN. INTERNAL DIVIDER
EXIST. 72/18
RELIEF DAMPER
MOD
EXISTING
RETURNRELIEF FAN
REFR. COMP.
NO. 2
REFR.
COMP. NO. 1
EXIST. CONTROL
PANEL(S)STARTERS, ETC.
26/42 DN TO 1ST FLOOR.
36/42 DN TO 3RD FLOOR.
26/42 DN TO 2ND FLOOR.
F
EX-EF
EXIST. FILTER
CLEANING TANK
F EXTG
60/46
EXISTING
EVAPORATIVECONDENSER
3 1/8"
3 1/8"
3 5/8"
3 5/8"
2 1/8"
2 1/8"
ELECTRICAL EQUIPMENT
ROOM
PENTHOUSE
STAIRS
-
RS
RS
RS
RS
RL
RL
RL
RL
HG
RL
RL
HGRL
RL
RL
RL
RL
RL
HG
HG
4"
2"
2"
1"
TCV
2" EXLPR DN.
4" EXLPS DN.
EXISTING
AHU(AC-1)
1
1
22
2
2
2
2
22
4 3
5
5
6
6
2
2
6
6
EXIST. 72/18
RELIEF DAMPER
7
7
22
6
6
2
2
1 11
8
8MOD
9
10
11
11
12
2
M200
10
10
10
GV
11
EXIST. CONTROL
PANEL(S)STARTERS, ETC.
15
EXIST. LOUVER
AND DAMPER
16
16
16
17
19
17
EXIST. ACCESS TO
REMAIN.
EXIST. FILTER
BANK TO REMAIN.
EXIST. ACCESS TO
REMAIN.
EXISTING 2"
DRAIN
EXIST. BAFFLE
PLATE TO REMAIN.
D E F G H
11
EXIST. SILENCER
18
18
18
18
1717
1717
T.O. PLANK146' - 6"
T.O. JOIST (PENTHOUSEROOF)
160' - 10"
22
2 2
222
3
3
3
3
4
EXAC-1
13
EXIST. INTAKE
LOUVER
14 14
14
11
11
11
11
12
12
9
9
10
10
10
10
10
EXIST. 2" LPR
DN.
EXIST. 4" LPS
DN.
11
REFR.
COMP. NO. 2
REFR. COMP.
NO. 1
EXIST. CONTROL
PANEL(S)STARTERS, ETC.
1
11
22
EXIST. CONTROL
PANEL(S)STARTERS, ETC.
2 EXISTING
PRE-HEAT COIL
EXIST. DX
COOLING COILS(4-STACKED)
7
77
2
2
2
2
EXIST.
RECEIVER
2
2
EXIST.
EVAPORATIVE CONDENSING UNIT
16
8
17
17
EXISTING
PRE-HEAT COIL
EXISTING FILTER BANK
EXISTING BAFFLE PLATE
D E F G H
DEMOTION KEYED NOTES
1
2
3
REMOVE EXISTING REFRIGERANT
COMPRESSORS AND ASSOCIATED CONTROL
PANELS (STARTERS, GAUGES, ETC.) IN ITS ENTIRETY INDICATED AS DASHED. (EXIST. CONC.
BASE TO REMAIN.)
REMOVE EXISTING REFRIGERANT SUCTION AND LIQUID LINES INDICATED AS DASHED.
REMOVE EXISTING REFRIGERATION COOLING
COILS AND ASSOCIATED COIL SUPPORT INDICATED AS DASHED. TOTAL OF (4) STACKED
COILS.
REMOVE EXISTING COPPER COOLING COIL GUTTER(S) TYPICAL OF THREE.
REMOVE EXISTING COOLING COIL BLANK-OFF
PANELS AS REQUIRED.
REMOVE HOT GAS (REFRIGERANT) LINES
INDICATED AS DASHED.
REMOVE EXISTING LIQUID REFRIGERANT
RECEIVERS, AND ASSOCIATED RACK SUPPORTS,
DRAINS, REFRIGERANT PIPING AND SPECIALTIES
ETC., INDICATED AS DASHED.
REMOVE EXISTING EVAPORATIVE CONDENSING
UNIT AND ASSOCIATED SPRING VIBRATION
ISOLATION INDICATED AS DASHED.
REMOVE EXISTING MIN. O.A. STEAM PREHEAT
COILS, ASSOCIATED COIL SUPPORT INDICATED
AS DASHED. TYP. OF (2) COILS.
REMOVE EXISTING LOW PRESSURE STEAM AND
LOW PRESSURE RETURN PIPING AND
ASSOCIATED VALVES AS INDICATED.
REMOVE EXISTING MOTOR OPERATED DAMPERS
INDICATED AS DASHED.
REMOVE EXISTING FILTER RACK INDICTED AS
DASHED.
EXISTING AHU COOLING COIL OFFSET. PRESERVE OFFSET TO ACCOMMODATE NEW
CHILLED WATER COILS. SEE NEW
CONSTRUCTION PLANS FOR FURTHER
INFORMATION.
EXISTING UNIT DRAIN PAN AND 2" DRAIN TO
REMAIN.
REMOVE EXISTING EVAP. COND. PUMP,
ASSOCIATED PIPING, CONTROLS AND
ELECTRICAL CONNECTIONS INDICTED AS
DASHED.
REMOVE EXISTING 4" CONC. BASE AND
SUPPORT PLATFORM INDICATED AS DASHED.
SELECTIVELY REMOVE EXISTING SLOPED
INSULATED METAL PANEL AND EXISTING METAL
PANEL CLADDING AND ACCESSORIES FROM
STRUCTURAL STEEL BEAMS AND COLUMNS. REMOVE AT THE EXISTING VERTICAL JOINT
NEAREST TO THE EXISTING CONCRETE BLOCK
WALL. PROVIDE PRE-FINISHED WHITE, 16 GA.
BREAK METAL END CLOSURE TO FINISH OFF
THE PANEL TO REMAIN CONDITIONS.
EXISTING STEEL COLUMNS AND BEAMS TO
REMAIN IN PLACE.
SAND AND WIRE BRUSH ALL RUST FROM
EXISTING BEAMS AND COLUMNS, PRIVE AND
PAINT WITH HIGH PERFORMANCE EXTERIOR
COATING. 2 COATS.
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
NORTH
17400 West Capitol DriveBrookfield, WI 53045Phone: 414.778.1700Fax: 414.778.2360E-Mail: [email protected]
REV DATE DESCRIPTION OF ISSUE
SHEET NAME
DRAWN APPROVED
DATE
R&D PROJECT NO.
SHEET NUMBER
KEY PLAN
PROJECT TITLE
MILWAUKEE INTERMODAL
STATION REHABILITATION
PROJECT 2019
PENTHOUSEMECH.
DEMOLITIONPLANS
02/22/2019
218089.00
M100
R&D R&D
1/4" = 1'-0"1 PENTHOUSE - MECHANICAL DEMOLITION PLAN
1/4" = 1'-0"2 MECHCANICAL SECTION AT PENTHOUSE - DEMOLITION
1 02/22/19 BIDDING DOCUMENTS
T
2
M100
26/42 DN TO 1ST FLOOR.
36/42 DN TO 3RD FLOOR.
26/42 DN TO 2ND FLOOR.
F
EX-EF
F
60/46
ELECTRICAL EQUIPMENT
ROOM
PENTHOUSE
STAIRS
2" LPR DN.
4" LPS DN.
EXIST. SILENCER
EXIST. 72/18
RELIEF DAMPER
EXIST. 72/18
RELIEF DAMPER
EXISTING
RETURNRELIEF FAN
2
M200
11
2
2
CC-1
5" GS
5" GR
4
3
EXIST. ACCESS TO
REMAIN.
EXIST. ACCESS TO
REMAIN.
EXIST. FILTER
BANK TO REMAIN.
M.O.D.
M.O.D.
M.O.D.
F-1 & F-2 5
HC-1 6
EXISTING
SUPPLY FAN (EXSAF-1)
EXISTING
AHU(AC-1)
60/18 SA DN.
60/18 SA DN.
INTERNAL DIVIDER
EXISTING 2"
DRAIN
6
4" LPS
4" LPS
8 9
2" LPR
EXIST. FILTER
CLEANING TANK
5" GS
5" GS
5" GS
5" GR
AS-1
CWP-1CWP-2
11
11
5" GS
5" GR
RISE
5" GS
5" GR
CWST-1
GSF-1
ET-1
NEW 4" CONC.
EQUIP. PAD5" GS
5" GS
ACC-1
12 12
12
12
CWP-1
(VFD)
CWP-2
(VFD)
TCP-1
TCP-2
EXIST. BAFFLE
PLATE TO REMAIN.
17
17
17 17
18
18
D E F G H
20
M.O.D.13
1313
13
10
10
ISOLATION
DAMPER WITH MOD
ISOLATION
DAMPER WITH MOD
SD
T.O. PLANK146' - 6"
T.O. JOIST (PENTHOUSEROOF)
160' - 10"
HC-1
HC-1
MIN. O.A.
(7255)
MIN. O.A.
(7255)
13
13
13
1414
EXAC-1
EXISTING FILTER BANK
EXISTING BAFFLE PLATE
15
15
4" LPS
4" LPS
13
2" LPR
2" LPR
985" GS
1
1
1
CC-1CC-1
CC-1
CC-1
3
1616
1111
5" GR
5" GR
5" GS
5" GR
5" GR
PERSON
(6'-0" )
5" GR
5" GR
CWP-1CWP-2
10
GSF-1
AS-1
ET-1
NEW 4" CONC.
EQUIP. PAD.
CWST-1
5" GSWFMS-1
5" GR
5" GS
5" GR
5" GS
1818
12
12
ACC-1
19
D E F G H
20
19
NEW CONSTRUCTION KEYED NOTES
1
2
3
NEW BUILT-UP AHU COOLING COIL DRAIN PAN.
SEE DETAIL #2 ON SHEET M501.
NEW GLYCOL COOLING COIL BLANK-OFF PANEL.
M.C. SHALL FIELD VERIFY EXACT SIZE
REQUIRED.
NEW GLYCOL CHILLED WATER COIL(S) CC-1.
TYPICAL OF FOUR STACKED COILS.
SEE AHU GLYCOL CHILLED WATER COIL DETAIL #2 ON SHEET M500 FOR INDIVIDUAL COIL PIPING
SIZE DATA.
NEW BUILT-UP FILTER FRAME. SEE FILTER SCHEDULE ON SHEET M600 FOR FURTHER
INFORMATION.
NEW STEAM O.A. MIN. PRE-HEAT COIL(S) HC-1. TYPICAL OF TWO STACKED COILS.
SEE AHU STEAM COIL DETAIL #3 ON SHEET M500
FOR INDIVIDUAL COIL PIPING SIZE DATA.
NEW STEAM BY-PASS GLOBE VALVE.
NEW STEAM TEMPERATURE CONTROL VALVE.
DUCT SMOKE DETECTOR. PROVIDED BY E.C.
EXISTING CONCRETE EQUIP. PADS.
AIR-COOLED CHILLER REQUIRED CLEARANCE.
NEW MOTOR OPERATED DAMPER.
EXISTING UNIT DRAIN PAN AND 2" DRAIN TO
REMAIN.
EXISTING AHU COOLING COIL OFFSET. MODIFY OFFSET AS REQUIRED TO ACCOMMODATE NEW
GLYCOL CHILLED WATER COILS.
M.C. SHALL PROVIDE NEW STRUCTURALSUPPORTS AS INDICATED.
CODE REQUIRED MIN. ELECTRICAL PANEL
CLEARANCE.
MODIFY EXISTING WALL OPENINGS TO
ACCOMMODATE NEW GLYCOL CHILLED WATER
PIPING. PATCH EXISTING OPENINGS AS REQUIRED.
NEW STRUCTURAL CHILLER SUPPORT STAND.
SEE STRUCTURAL DRAWINGS AND DETAILS FOR ACTUAL SUPPORT INFORMATION.
THE GLYCOL STORAGE TANK REFLECTED HAS
BEEN SIZED TO ACCOMMODATE THE BASIS OF DESIGN CHILLER. PER BASIS OF DESIGN
CHILLER MANUFACTURE, A TWO MINUTE LOOP
IS REQUIRED. DEPENDING ON PURCHASED
CHILLER, THE M.C. SHALL CONFIRM THE MIN. VOLUME REQUIREMENTS OF THE CHILLER, AND
PROVIDE A STORAGE TANK AS REQUIRED BY
THE CHILLER MANUFACTURE AT NO ADDITIONAL
COST TO THE PROJECT. M.C. SHALL ALSO
PROVIDE ALL NECESSARY STRUCTURAL ANALYSIS AS NEEDED.
4
5
6
7
8
9
10
11
12
13
14
15
17
16
18
19
20
NORTH
17400 West Capitol DriveBrookfield, WI 53045Phone: 414.778.1700Fax: 414.778.2360E-Mail: [email protected]
REV DATE DESCRIPTION OF ISSUE
SHEET NAME
DRAWN APPROVED
DATE
R&D PROJECT NO.
SHEET NUMBER
KEY PLAN
PROJECT TITLE
MILWAUKEE INTERMODAL
STATION REHABILITATION
PROJECT 2019
PENTHOUSEMECH. NEW
CONSTRUCTIONPLANS
02/22/2019
218089.00
M200
R&D R&D
1/4" = 1'-0"1 PENTHOUSE - HVAC NEW CONSTRUCTION
1/4" = 1'-0"2 MECHCANICAL SECTION AT PENTHOUSE -NEW CONSTRUCTION
1 02/22/19 BIDDING DOCUMENTS
J K
J K
DEMOTION KEYED NOTES
1
2
3
REMOVE EXISTING LPS PIPING & VALVES
INDICATED AS DASHED.
REMOVE EXISTING. LPR PIPING INDICATED AS
DASHED.
EXISTING DOMESTIC HOT WATER HEATER
REMOVAL BY P.C.. SEE PLUMBING DRAWING FOR
ADDITIONAL INFORMATION.
REMOVE EXISTING DUCTWORK INDICATED AS
DASHED.
REMOVE EXISTING DOOR TRANSFER GRILLES INDICATED AS DASHED.
REMOVE EXISTING COND. COOLER, RECEIVER,
METER, PIPING , VALVES AND PLATFORM IN ITS ENTIRETY INDICATED AS DASHED.
4
5
6
NEW CONSTRUCTION KEYED NOTES
1
2
NEW STEAM HOT WATER HEATER (BY P.C.)
MC SHALL CONNECT NEW 5" LPS TO NEW HOT WATER HEATER (BY P.C.). COORDINATE WORK
WITH PC.
M.C. SHALL CONNECT NEW 2" LPR TO HOTWATER HEATER (BY P.C.). COORDINATE WORK
WITH P.C.
3
6"
LP
S6
"L
PS
6" LPS
EXISTING
DOMESTIC
HOT WATERHEATER
3
2
1
CAP
J K
2" LPR
1-1
/4"
LP
R
CAP
6
66
EXISTING UTILITY TUNNEL
MECHANICAL EQUIPMENT
-
6"
LP
S6
"L
PS
6" LPS
2
1
J K
5" LPS
2" LPR
3
2" LPR
EXISTING UTILITY TUNNEL
MECHANICAL EQUIPMENT
-
16/6
16/6
24/14
24/1
0
EXTG
EXTG5
5
16/6
EXEG(300)
EXEG(300)
4
4
14/6
EXEG(300)
EXEG(300)
14/6
16/6
16/6
16/624/14
24/1
0
A
NEW TRANSFER
ASSEMBLY BELOWEXISTING EXHAUST
AVOLUME
DAMPER (TYP.)
WOMEN
205
MEN
204
NORTH
17400 West Capitol DriveBrookfield, WI 53045Phone: 414.778.1700Fax: 414.778.2360E-Mail: [email protected]
REV DATE DESCRIPTION OF ISSUE
SHEET NAME
DRAWN APPROVED
DATE
R&D PROJECT NO.
SHEET NUMBER
KEY PLAN
PROJECT TITLE
MILWAUKEE INTERMODAL
STATION REHABILITATION
PROJECT 2019
BASEMENT ANDSECOND MECH.FLOOR PLANS
02/22/2019
218089.00
M210
R&D R&D
1/4" = 1'-0"1 PARTIAL BASEMENT - DEMOLITION
1/4" = 1'-0"2 PARTIAL BASEMENT - NEW WORK
1/4" = 1'-0"3 SECOND FLOOR EXISTING TOILET ROOMS - HVAC DEMOLITION PLAN
1/4" = 1'-0"4 SECOND FLOOR EXISTING TOILET ROOMS - HVAC NEW CONSTRUCTION PLAN
1 02/22/19 BIDDING DOCUMENTS
NO SCALE
NO SCALE
NO SCALE
NO SCALE
TS
P
FSTS
TS
TS
TS
NO SCALE
CHILLED WATER SYSTEM SCHEMATIC
AHU CHILLED WATERCOOLING COIL PIPING DETAIL
HYDRONIC AIR REMOVAL AND EXPANSION CONTROLSYSTEM PIPING SCHEMATIC
WATER FILTER & CHEMICAL FEEDER PIPING DETAIL
AIR COOLED CHILLER PIPING DETAILNO SCALE
AHU STEAM HEATING COIL PIPING DETAIL
NO SCALE
6
1
2
7
4
5LOW PRESSURE STEAM END OF MAINDRIP TRAP DETAIL
3
AIR SEPARATOR AS-1
PIPE THERMOMETER (TYP.)
SRV-1
GR
376 GPM
VFD
ACC-1
ROOF
STRUCTURALSTEEL SUPPORTSTANDBY G.C.
AIR COOLEDCHILLER(SEE PIPING DETAIL)
GS
GR
N.C.
N.O.
N.O.
GS
ET-130% P.G.
B
SUPPORT PIPE ATFLOOR (FOR PIPES6" AND OVER)
VALVE (TYP.)3/4" DRAIN
LOCATION (FORHOUSING WALL
BUILT-UP UNITS)
F
2 WAY
CONTROL VALVE
COOLING COIL PIPING DATA
REQUIRED (TYP.)
REQ'D FORVALVES NOT
UNITS (TYP.)SINGLE COIL
UNION/FLANGE
TEST CONN.(TYP.)
(TYP.)
F
REDUCER AS
AIR VENT
THERMOMETER
MANUAL
(TYP.)
THREE WAY
CONTROL VALVEARRANGEMENT
TEMPERATURE
NOTE:NC
CWR
CWS
N.O.
E
COILNO. A
79.8CC-1
COIL GPM
B
79.8
E
5"
PIPE SIZE
F
2-1/2"
COIL
COIL
FOR PACKAGED
REMOVAL (TYP.)PERMIT COILUNITS TO
A
PIPING OFFSET
SHUTOFF VALVE (TYP.)
WHERE SCHEDULED
FLOW CONTROL VALVE
BALANCE VALVE (TYP.)
E
CWS
CWR
TWO WAY TEMPERATURECONTROL VALVE
PIPE PER MFR'S SPEC.)
DISTANCES OF STRAIGHT
SCHEDULED (MIN.
FLOW METER WHERE
VALVE NO.
-
3 WAY
X -
METERNO.
FLOWCONTROLFLOW
.
REMARKS
.
D
F
F
COIL
COIL
C
C
79.8
D
79.8
E
376 GPM
2"
VFD
2"
5"
5"
5" 5"
GS
5"
SAFETY RELIEF VALVE(CHILLED WATER SYSTEM
FROM GLYCOL FILLSYSTEM (GSF-1)
PIPE DISCHARGE TONEAREST FLOOR DRAIN
SHUTOFF VALVELOCK OPEN OR REMOVEHANDLE AFTER CHARGING
- NOT ALL COMPONENTS ARE AT SAME LOCATION. REFER TO FLOOR PLAN FOR EXACT LOCATIONS.
- CONNECTIONS TO DOMESTIC WATER AND GLYCOL FILL SYSTEMS ARE SHOWN FOR INFORMATION ONLY.
- SRV SETTING APPLIES TO SRV'S INDICATED IN THIS SCHEMATIC AND TO ALL SRV'S INSTALLED IN THE SYSTEM.
MANUAL AIR
AS AIR SEPARATOR
TO NEAREST FLOOR DRAIN
AUTOMATIC AIR VENTPIPE DISCHARGE (3/4")
FOR GLYCOL SYSTEMSOR TO GLYCOL FILL TANK
PRESSURE GAUGE w/GAUGE COCK (TYP.)
SUPPORT INDEPENDENT
- HORIZONTAL AND VERTICAL EXPANSION TANKS ARE SHOWN FOR INFORMATION ONLY.PROVIDE STYLE OF EXPANSION TANK AS INDICATED ON THE SCHEDULE AND DRAWINGS.
CONNECT ALL SYSTEMS TO DOMESTIC WATER UNLESS THEY ARE FILLED WITH GLYCOL.
NOTES:
TANK
VERTICALEXPANSION
CONNECTIONCHARGE
OF PIPING
EXPANSIONTO OTHER
TANKS
AIR SEPARATOR
A
TAPPING
RETURN FROM
PIPE SIZE SAME
SYSTEM
MIN
.12"
D
1/2" DRAINVALVE (TYP.)
TANK
C
SIDE OF MAINCONNECT TO
ONLY
A
3/4"
VENT (TYP.)
ONLY)
A
B
SCHEMATIC PIPING DATA
SYSTEMSERVED
EXP. TANKGLYCOL%
NO.(s)
EXP. TANKCHARGEPSIG A
SRVSETTINGPSIGNO.(s)
SRVB C D
TO PUMPS
REMARKS
30 P.G. 1 12 1
1. COORDINATE SAFETY RELIEF VALVE SETTING WITH OWNER.
GLYCOL CHILLED WATER SYSTEM 5" 1/2" 1" -100 SEE NOTES 1 BELOW
PITCH DOWN (TYP.)
5" GS
5" GR
AIR COOLED CHILLER
STRAINER
TEMPERATURE SENSOR (TYP.)
PADDLE SWITCH FLOW SENSOR
TEST WELL (TYP.)
BALANCING VALVE
PRESSURE GAUGE
GAUGE COCK (TYP.)NOTE:
P/T TAP (TYP.)
UNION (TYP.)
SHUT-OFF VALVE (TYP.)
PROVIDE DRAIN VALVE AND BRASSCAP AT EACH DRAIN CONNECTION ONCHILLER EVAPORATOR HEAD (TYP.)
1. PITCH CWS AND CWR PIPING TOWARDSPIPING PENETRATION THROUGH ROOF.
2. ARRANGE PIPING TO PERMIT TUBECLEANING
PROVIDE MANUAL AIR VENT ATEACH VENT CONNECTION ONCHILLER EVAPORATOR HEAD (TYP.)
12" MIN. (TYP.)LPC
TRAP (TYP.)
E
COIL
COIL
C
B
COIL
A
A
HEATING COIL PIPING DATA
NO.COIL
D
D
COIL #/HR
B C D
PIPE SIZE
E F G H
STRAINER (TYP.)
SHUTOFF VALVE (TYP.)
D
VACUUM BREAKER (TYP.)
LPS
REMARKS
GLOBE VALVE
YES
T.C.V. BYPASS
JI NO
3/4" DRAIN VALVE (TYP.)
367 367 - 4" 3" 3" - 2" 2" - X - O.A. MIN. PREHEAT
VALVE NOT REQUIREDFOR COILS WITHOUTT.C.V. BYPASS
UNION/FLANGE (TYP.)
REDUCER ASREQUIRED (TYP.)
TEMPERATURECONTROL VALVE
TEMPERATURE CONTROL VALVEBYPASS (WHERE SCHEDULED)
VALVE NOT REQ'DFOR SINGLE COILUNITS (TYP.)
HOUSING WALLLOCATION (FORBUILT-UP UNITS)
DIRT LEG FULL SIZE OFCOIL OUTLET (TYP.)
UNION (TYP.)
LPC TO CONDENSATE PUMP
SHUTOFF VALVE (TYP.)
LPS
STRAINER
1"
NIPPLE & END CAP (TYP.)
TRAP (3/4" UNLESSNOTED OTHERWISE)
3/4" BLOWDOWN VALVE
1" PIPE SIZE UNLESSNOTED OTHERWISE
BLOW DOWNVALVE
DIRT LEG SAMESIZE AS MAIN
12"MIN.
HC-1 & 2
GR
5"
GS
5"
DIFFERENTIAL PRESSURESENSOR (FLOW DETECTION)
F
H
I
G
J
PIPING OFFSET FORPACKAGED UNITS TO PERMITCOIL REMOVAL (TYP.)
HIGH DENSITY INSULATION INSERTOR FOR APPLICATIONS PERMITTED INSPECIFICATION, STEEL SADDLEFILLED WITH INSULATION. (TYP.)
HIGH DENSITY INSULATION INSERTOR FOR APPLICATIONS PERMITTEDIN SPECIFICATION, STEEL SADDLEFILLED WITH INSULATION. (TYP.)
INSULATION AND NEOPRENEMOUNTS FOR COLD PIPES.
180° SHIELD
SECTION ELEVATION
PROVIDE HANGER OF SIZE TO FIT PIPE COVERINGO.D. ALSO PROVIDE FOR LOWERING HANGER WHENPIPE COVERING IS APPLIED. (GRINNEL FIG.260SHOWN)
PIPE COVERING PROTECTOR (SHIELD) SHALL BE 18 GA.GALV. SHEET METAL. LENGTH SHALL BE 8" LONG FORPIPES 1-1/2" & SMALLER AND SHALL BE AT LEAST 12"LONG FOR PIPES 2" & LARGER.
(2) DEEP CUP DUO STRAINERW/O BASKET (JONES NO.STR200) INSTALL AT THIRDPOINTS ON DRAIN PANS.PITCH DRAIN PAN TO DRAINS
1 1/2" PIPE DRAINS6" 24"
MIN.
MIXING & STORAGETANK (55 US GALLONS)
1/2"NPT FLEXIBLESYSTEM CONNECTORHOSE WITH CHECKVALVE. (SEE CHILLEDWATER SCHEMATIC FORSYSTEM CONNECTIONPOINT).
GSF-1
REDUCER (TYP.)
VALVE (TYP.)BUTTERFLY
(TYP.)
AND BALANCE VALVE (TYP.)COMBINATION SHUT-OFF CHECK
EXISTING CONCRETE EQUIPMENT PAD (TYP.)
PUMP INLET AND SUCTION(TAP INTO PUMP DISCHARGE,PRESSURE GAUGE (TYP.)
(TYP.)
1/2" CAPPED DRAIN VALVE (TYP.)
1/4" BALL VALVE
WITH SUPPORT LEGSUCTION DIFFUSER
CONCENTRIC
DIFFUSER INLET)
END SUCTION PUMP
C B
C
B
A
A
A
A
PUMP PIPING DATAPIPE SIZES
PUMPNO. A B C
CWP-1
CWP-2 5"
5"
INCREASER (TYP.)
CONCENTRIC
CONNECTOR (TYP.)FLEXIBLE PIPE
END SUCTION PUMP
5"
5"
5"
5"
PIPE
GROUT
PIPE INSULATION
EXTERIOR WALL- CUTWALL AS NEATLY ASPOSSIBLE FOR SLEEVE
END OF ALUM.JACKET FLANGE
GALV. PIPE SLEEVE
FIBERGLASS INSULATION
PIPE INSULATION W/ALUM. JACKET
CAULK ALL AROUND TOMIN. 1" DEPTH W/
NON-HARDENING CAULK
UNIT DRAIN PAN
TRANSFERGRILLE
ACOUSTICALLYLINED DUCT
RANGE
CFM
SYMBOL NO.
TG
A TG-1 0-300
DUCT SIZE
HORIZONTAL
14/6
17400 West Capitol DriveBrookfield, WI 53045Phone: 414.778.1700Fax: 414.778.2360E-Mail: [email protected]
REV DATE DESCRIPTION OF ISSUE
SHEET NAME
DRAWN APPROVED
DATE
R&D PROJECT NO.
SHEET NUMBER
PROJECT TITLE
MILWAUKEE INTERMODAL
STATION REHABILITATION
PROJECT 2019
MECHANICALDETAILS
02/22/2019
218089.00
M501
R&D R&D
1 02/22/19 BIDDING DOCUMENTS
AIR SEPARATOR SCHEDULE (A.S.)LINE
TAG LOCATION SERVICE DESCRIPTION SIZE (IN.) GPM REMARKS
AS-1 PENTHOUSE CHILLED WATER SYSTEM 5" 376 COALESCING AIR & DIRT
GLYCOL SYSTEM FEEDER (G.S.F.)SYSTEM FLUID PUMP HEAD MOTOR CONTAINER SIZE
REMARKSTAG SERVED TYPE GPM (PSIG) H.P. (GALLONS)
GSF-1CHILLER GLYCOL 30% PRE-MIXED
1 50 0.7 AMPS 55 SEE NOTES BELOWLOOP PROPYLENE GLYCOL
(1) UNIT UTILIZES A 3-PRONG PLUG AND CORD.
(2) PROVIDE UNIT WITH ALARM PANEL.
EQUIPMENT ELECTRICAL SCHEDULEEQUIPMENT ELECTRICAL DATA MOTOR CONTROLLER DISCONNECT AT EQUIPMENT
REMARKSSYMBOL TYPE LOCATION V/PH HP KW FLA MCA MOP
EMERGENCY POWER
LOCATION TYPE DISCONNECTVFD
RESTARTFURN.
BYINST.BY ACCESSORIES TYPE
FURN.BY
INST.BYYES NO STANDBY
ACC-1 AIR COOLED CHILLER ROOF 460/3 - 192.9 - 342 A 450 A - X - INTEGRAL MAGNETIC - - MFR. MFR. - - - (OUTDOOR) (NF) MFR. MFR. SINGLE POINT UNIT POWER (SCR MIN. RATING 65kA)
CWP-1 CHILLED WATER SYSTEM DISTRIBUTION PUMP PENTHOUSE 460/3 20 - - - - - X NO PENTHOUSE VFD (NO BYPASS) YES - MC EC (HOA) (PL) - NOT REQUIRED MOUNT VFD IN LINE OF SIGHT OF EQUIP.
CWP-2 CHILLED WATER SYSTEM DISTRIBUTION PUMP PENTHOUSE 460/3 20 - - - - - X YES PENTHOUSE VFD (NO BYPASS) YES - MC EC (HOA) (PL) - NOT REQUIRED MOUNT VFD IN LINE OF SIGHT OF EQUIP.
-
GSF-1 GLYCOL SYSTEM FEEDER PENTHOUSE 120/1 0.7 AMPS - - - - - X - INTEGRAL MAGNETIC - - MFR. MFR. - - - SEE REMARKS UNIT UTILIZES A 3-PRONG PLUG AND CORD
INDICATES OUTLET MOUNTING HEIGHT.(CLG) MOUNTED IN OR ABOVE CEILING(F) MOUNTED IN FLOOR BOX
SHOWN ON POWER PLAN(M) MOUNTED IN MULTI-OUTLET ASSEMBLY
SHOWN ON POWER PLAN(P) MOUNTED IN POKE-THRU
SHOWN ON POWER PLAN(S) SPECIAL MOUNTING HEIGHT EITHER INDICATED
ON THE DRAWINGS OR AS INDICATED IN THEASSOCIATED ARCHITECTURAL ELEVATIONS.
(TP) MOUNTED IN TELEPOWER POLESHOWN ON POWER PLAN
(T) MOUNTED IN AV/TELEVISION BOXSHOWN ON POWER PLAN
X
X
SYSTEM EQUIPMENT CABINET
DENOTES THE FOLLOWING:(DB) DOOR BELL(CA) CABLE TELEVISION(CB) CODE BUTTON(CC) CLOSED CIRCUIT TELEVISION(CLK) CLOCK SYSTEM(DV) DIGITAL TELEVISION(FA) FIRE ALARM(HP) HOUSE PAGING(IC) INTERCOM(IS) INFANT SECURITY(LM) LOCAL MUSIC(LP) LOCAL PAGING(MA) MASTER ANTENNAE TELEVISION(MS) MUSIC SYSTEM(NC) NURSE CALL(P1) PROCEDURE ROOM - TWO WAY COMMUNICATION(P2) PROCEDURE ROOM - MUSIC SYSTEM(PA) PUBLIC ADDRESS(SA) SECURITY ACCESS(SC) SYSTEM CLOCK(TC) TELECOMMUNICATIONS(TV) TELEVISION(RA) RESCUE ASSISTANCE(VD) VOICE DATA(WR) WIRED RADIO
DENOTES THE FOLLOWING:(AN) ANNUCIATOR(BB) BACKBOARD(CP) CONTROL PANEL(ER) EQUIPMENT RACK(TC) TERMINAL CABINET(WF) WALL FIELD
FXX/X
FIRE ALARM
DENOTES THE FOLLOWING:(C) CEILING MOUNTED(ALL DEVICES SHALL BE WALL MOUNTED UNLESS NOTEDOTHERWISE BELOW OR ON PLANS)
DENOTES THE FOLLOWING:(CMX) CONTROL MODULE - SEE CONTROL MODULE SCHEDULE
DENOTES THE FOLLOWING:(CR) CARD READER(CXX) CLOSED CIRCUIT CAMERA - SEE CAMERA SCHEDULE
(XX - DENOTES SPECIFIC UNIT)(DB) DURESS BUTTON(DC) DOOR CONTACT(DP) DOOR POSITION INDICATOR SWITCH(EL) ELECTRONIC LATCH/LOCK(ES) ELECTRIC STRIKE(GB) GLASS BREAK DETECTOR(KE) KEYLESS ENTRY(KP) KEYPAD - SECURITY SYSTEM(KS) KEYED SWITCH(LM) LATCHBOLT MONITOR(MD) MOTION SENSOR - DUAL TECHNOLOGY(MI) MOTION SENSOR - INFRARED(ML) MAGNETIC LOCK(MO) CLOSED CIRCUIT TELEVISION MONITOR(MU) MOTION SENSOR - ULTRASONIC(RC) CLOSED CIRCUIT TELEVISION REMOTE CAMERA CONTROLS(RM) REQUEST FOR EXIT - MOTION(RP) REQUEST FOR EXIT - PUSH BUTTON(VC) VIDEO RECORDER
ELECTRICAL CIRCUITING:
LIGHTING FIXTURES:
A1a,X-3b
AX-3b,1a
A1a,3b
AX-3*
INDICATES FIXTURE TYPE (TYPICAL)
.
SECOND DESIGNATOR (TYPICAL)
FIRST DESIGNATOR (TYPICAL)SINGLE DESIGNATOR (TYPICAL)
1. FIRST DESIGNATOR INDICATES THE CIRCUIT AND CONTROL MEANS ASSOCIATED WITH THEOUTBOARD LAMPS.
2. SECOND DESIGNATOR INDICATES THE CIRCUIT AND CONTROL MEANS ASSOCIATED WITH THEINBOARD LAMPS.
3. SINGLE DESIGNATOR INDICATES THE CIRCUIT AND MEANS OF CONTROL FOR THE ENTIREFIXTURE.
4. DESIGNATOR SHOWN WITHIN ( ) INDICATES CIRCUITING AND/OR CONTROL VIA ANEMERGENCY LIGHTING CONTROL UNIT. REFER TO LIGHTING DETAILS FOR WIRING DIAGRAM(S).
5. SHADING INDICATES LAMP(S) SERVED FROM EMERGENCY, CRITICAL CARE OR LIFE SAFETYBRANCH (TYPICAL).
LIGHTING CIRCUITING NOTES -
DESIGNATOR DESCRIPTION:
X-3b LOWER CASE LETTERS INDICATE SWITCH DESIGNATION CONTROLLING ASSOCIATED LAMP(S). ABSENCE OF ANY LETTER INDICATES FIXTURE/LAMP(S) CONTROLLED VIA SWITCH(ES) IN THE ASSOCIATED ROOM. UPPERCASE "U" INDICATES ASSOCIATED LAMP(S) ARE UNSWITCHED.
INDICATES THE CIRCUIT NUMBER SERVING FIXTURE/LAMP(S).
INDICATES BRANCH PANELBOARD SERVING THE DEVICE. SEE PLAN FOR AREAS SERVED BY PANELBOARD(S).
ELECTRICAL DEVICES:
X-3
DESIGNATOR
XXX-3
.
SPECIAL OUTLETDESIGNATOR
DESIGNATOR DESCRIPTION:
X-3
INDICATES THE CIRCUIT NUMBER SERVING DEVICE.
INDICATES BRANCH PANELBOARD SERVING THE DEVICE. SEE PLAN FORAREAS SERVED BY PANELBOARD(S).
GENERAL NOTES - NOTES THAT APPLY TO ALL DRAWINGS WITHIN THE DRAWING SET.SHEET NOTES - NOTES THAT APPLY TO THE SHEET ON WHICH THEY APPEAR.KEYED NOTES - NOTES THAT APPLY TO AN AREA, ITEM AND/OR DEVICE ON A FLOOR PLAN OR DETAIL.DETAIL NOTES - NOTES THAT APPLY TO A SPECIFIC DETAIL.
NOTE DESCRIPTIONS -
ABBREVIATIONS:
(ALL ABBREVIATIONS SHOWN MAY NOT APPEAR ON DRAWINGS)
ABV ABOVEAFF ABOVE FINISHED FLOORAFG ABOVE FINAL GRADEALT ALTERNATEALT SW ALTERNATE SWITCHARCH ARCHITECTBFC BELOW FINISHED CEILINGBFG BELOW FINISHED GRADEBLDG BUILDINGBOL BUILT IN OVERLOADBPC BOLTED PRESSURE CONTACT SWITCHBRKR BREAKERCB CIRCUIT BREAKERCKT CIRCUITCLG CEILINGCP CONTROL PANELCS COMBINATION STARTERDE DUAL ELEMENT FUSESDIR DIRECTDISC DISCONNECTDN DOWNEC ELECTRICAL CONTRACTORELEV ELEVATIONEMER EMERGENCYEMT ELECTRIC METALLIC TUBINGEOL END OF LINE RESISTOREP EXPLOSION PROOFER EXISTING REMOVE FROM SERVICEERL EXISTING RELOCATEDES EXPOSED STRUCTUREETR EXISTING TO REMAINEX EXISTINGEWC ELECTRIC WATER COOLERF FLUSHFBO FURNISHED BY OTHERSFDR FEEDERFIXT FIXTUREFLUOR FLUORESCENTFLR FLOORFS FLOW SWITCHFVNR FULL VOLTAGE NON-REVERSINGGC GENERAL CONTRACTORGFI GROUND FAULT INTERRUPTEDGRC GALVANIZED RIGID CONDUITGRD GROUNDGRDG GROUNDINGGYP GYPSUM BOARDHOA HAND-OFF-AUTO SWITCHHVAC HEATING, VENTILATING, & AIR CONDITIONINGHW HEAVYWALLIL INTERLOCKIMC INTERMEDIATE METALLIC CONDUITJB JUNCTION BOXkVA KILO VOLTAMPERELG LAY-IN GRIDLTG LIGHTINGLV LOW VOLTAGELVT LINE VOLTAGE THERMOSTATMAG MAGNETIC STARTERMAN MANUAL STARTERMC MECHANICAL CONTRACTORMCB MAIN CIRCUIT BREAKERMCC MOTOR CONTROL CENTERMDP MAIN DISTRIBUTION PANELMLO MAIN LUGS ONLYMSB MAIN SWITCHBOARDMTD MOUNTEDNIC NOT IN CONTRACTNU NEAR UNITOU ON UNITP POLEPB PUSH BUTTONPEND PENDANTPC PLUMBING CONTRACTORPE SW PNEUMATIC SWITCHPLBG PLUMBINGPNL PANELPVC POLYVINYL CHLORIDER RELAYRAI REMAIN AS ISRE/CKT RECONNECT TO EXISTING CIRCUITRECEPT RECEPTACLERM ROOMRVS REDUCED VOLTAGE STARTINGS SPLINESEL SW SELECTOR SWITCHSP SW SPEED SWITCHSURF SURFACESW SWITCHTC TIME CLOCKTCC TEMPERATURE CONTROL CONTRACTORTCP TEMPERATURE CONTROL PANELTYP TYPICALUG UNDERGROUNDUNIV UNIVERSALUSS UNIT SUBSTATIONWP WEATHERPROOFXFMR TRANSFORMER
OS OCCUPANCY SENSOR - SHOWN WITHIN A SPACE ARE TO CONTROL ALL THE LIGHTING WITHIN THAT SPACE, INCLUDINGBUT NOT LIMITED TO GENERAL AMBIENT LIGHTING ANDUNDERCABINET TASK LIGHTING
X/X,a
SWITCH DESIGNATION
DUPLEX RECEPTACLE(DD) DOUBLE DUPLEX(GFI) GROUND FAULT INTERRUPTING(IG) ISOLATED GROUND(SH) SWITCHED TOP HALF(TD) TRIPLE DUPLEX(TR) TAMPER RESISTANCE(USB) DUPLEX RECEPTACLE WITH USB CHARGING(WP) WEATHERPROOF W/ GFI RECEPTACLE
DETAIL INDICATES A TYPICAL OCCUPANCY SENSOR WIRING DIAGRAM. SEE FLOOR PLANS FOR THE REQUIRED LIGHTING CONTROL CONFIGURATION. PROVIDE THE NECESSARY CONTROL COMPONENTS AND WIRING FOR A COMPLETE SYSTEM.
SEE FLOOR PLANS FOR QUANTITIES, TYPES AND LOCATIONS OF OCCUPANCY SENSORS.
ALL FIXTURES LOCATED IN THE ROOM MONITORED BYOCCUPANCY SENSORS SHALL BE CONTROLLED BY THESE SENSORS.
17400 West Capitol DriveBrookfield, WI 53045Phone: 414.778.1700Fax: 414.778.2360E-Mail: [email protected]
REV DATE DESCRIPTION OF ISSUE
SHEET NAME
DRAWN APPROVED
DATE
R&D PROJECT NO.
SHEET NUMBER
PROJECT TITLE
MILWAUKEE INTERMODAL
STATION REHABILITATION
PROJECT 2019
SYMBOLS,
ABBREVIATIONS
& SHEET INDEX
02/22/2019
218089.00
E000
R&D R&D
ELECTRICAL SHEET INDEX
No. TITLEE000 SYMBOLS, ABBREVIATIONS & SHEET INDEX
E100 OVERALL SECOND FLOOR PLAN - ELECTRICAL
E200 PENTHOUSE - ELECTRICAL
E210 PARTIAL BASEMENT AND SECOND FLOOR - ELECTRICAL
17400 West Capitol DriveBrookfield, WI 53045Phone: 414.778.1700Fax: 414.778.2360E-Mail: [email protected]
REV DATE DESCRIPTION OF ISSUE
SHEET NAME
DRAWN APPROVED
DATE
R&D PROJECT NO.
SHEET NUMBER
KEY PLAN
PROJECT TITLE
MILWAUKEE INTERMODAL
STATION REHABILITATION
PROJECT 2019
OVERALL
SECOND FLOOR
PLAN -
ELECTRICAL
02/22/2019
218089.00
E100
R&D R&D
1/8" = 1'-0"E100
1 OVERALL SECOND FLOOR PLAN - ELECTRICAL
1 02/22/19 BIDDING DOCUMENTS
F
F
F
F
2
D E F G H
2
D E F G HD E F G H
EVAPORATORCOND. FAN
REFR.COMP #2
REFR.COMP #1
EVAP. COND.PUMP
EVAPORATORCOND. FAN
2
D E F G H
Space
1
ELECTRICAL
EQUIPMENT ROOM
-
PENTHOUSE
-
STAIRS
-
ACC-1
CWP-1 CWP-2
TCP-1 TCP-2
PHPD
ETR
PHPP
ETR
GSF-1
DP
DP
CM
1
DP
NORTH
17400 West Capitol DriveBrookfield, WI 53045Phone: 414.778.1700Fax: 414.778.2360E-Mail: [email protected]
REV DATE DESCRIPTION OF ISSUE
SHEET NAME
DRAWN APPROVED
DATE
R&D PROJECT NO.
SHEET NUMBER
KEY PLAN
PROJECT TITLE
MILWAUKEE INTERMODAL
STATION REHABILITATION
PROJECT 2019
PENTHOUSE -ELECTRICAL
02/22/2019
218089.00
E200
R&D R&D
1/4" = 1'-0"1PENTHOUSE - DEMOLITION
1.
2.
3.
4.
5.
6.
7.
8.
9.
DEMOLITION PLAN NOTES -
ALL INFORMATION SHOWN ON THE PLANS WAS GATHERED FROM FIELD OBSERVATION AND EXISTING DRAWINGS. EC SHALL FIELD VERIFY EXISTING CONDITIONS AND IS RESPONSIBLE FOR ANY ADDITIONAL TRACING, REMOVING, RELOCATION AND EXTENDING CIRCUITS AND DEVICES NECESSARY TO MAINTAIN CONTINUITY OF EXISTING EQUIPMENT NOT IN THE AREA OF WORK. EC SHALL FIELD VERIFY EXACT DEMOLITION REQUIREMENTS AND INCLUDE ALL ASSOCIATED COSTS. ALL ABANDONED WIRING, CONDUITS, FITTINGS, BOXES, SUPPORTS, ETC. SHALL BE REMOVED FROM THE DEVICES BACK TO THE RESPECTIVE SOURCE PANEL. UPDATE PANEL DIRECTORIES. REFER TO THE SPECIFICATIONS FOR ADDITIONAL ELECTRICAL DEMOLITION REQUIREMENTS.
ALL ELECTRICAL EQUIPMENT SHOWN ON THE DEMOLITION PLANS ARE "EXISTING TO BE REMOVED" UNLESS OTHERWISE NOTED. IN ADDITION TO REMOVING DEVICES, REMOVE ALL ASSOCIATED ELECTRICAL CIRCUITS BACK TO SOURCE. REFER TO THE SPECIFICATIONS FOR ELECTRICAL DEMOTION REQUIREMENTS.
EC SHALL SUPPORT AND PROTECT ELECTRICAL EQUIPMENT EXISTING TO REMAIN, INCLUDING BUT NOT LIMITED TO CONDUITS, WIRING, DEVICES, AND FIXTURES AS REQUIRED.
DASHED WALLS ON THE DEMOLITION PLANS INDICATE IN GENERAL EXISTING WALLS BEING DEMOLISHED. DO NOT RELY ON ELECTRICAL DRAWINGS TO DETERMINE EXTENT OF GENERAL CONSTRUCTION DEMOLITION. REFER TO ARCHITECTURAL DEMOLITION PLANS FOR THE EXACT EXTENT OF GENERAL CONSTRUCTION DEMOLITION REQUIRED BY THIS CONTRACT.
REFER TO DEMOLITION DRAWINGS OF OTHER TRADES. WHERE MOTORS, CONTROL PANELS, AND OTHER LOADS THAT HAVE AN ELECTRICAL CONNECTION ARE BEING REMOVED, INCLUDE THE DISCONNECTION AND REMOVAL OF ASSOCIATED ELECTRICAL FEEDS, CIRCUITS, AND LOOSE CONTROL EQUIPMENT IN THIS CONTRACT.
EXISTING TO REMAIN "ETR" ON THIS DEMOLITION PLANS REFERS TO THE STATUS OF BASIC ELECTRICAL DEVICES. THERE MAY BE SOME WORK REQUIRED IN THESE SPACES INVOLVING BACK-FEEDING EXISTING CIRCUITS OR OTHER MODIFICATIONS. SEE ALL DOCUMENTS THAT MAKE UP THIS CONTRACT FOR THE TOTAL EXTENT OF WORK REQUIRED IN ALL SPACES.
EC SHALL COORDINATE REMOVAL AND REPLACEMENT OF ANY ELECTRICAL CEILING DEVICES (I.E. LIGHT FIXTURES, FIRE ALARM, ETC.) OUTSIDE THE AREA OF WORK TO ACCOMMODATE THE NEW CONSTRUCTION.
EXISTING DEVICES MAY BE REUSED, IN-LIEU OF PROVIDING NEW DEVICES SHOWN ON ELECTRICAL DRAWINGS IN THIS SET, PROVIDED THE DEVICES ARE CLEAN, IN WORKING CONDITION AND ACCEPTABLE TO BE REUSED PER THE OWNER.
ELECTRICAL CONTRACTOR SHALL REFER TO THE ARCHITECTURAL PLANS FOR LOCATIONS OF SMOKE PARTITIONS AND FIRE RATED WALLS, FLOORS, AND CEILINGS AND THEIR HOURLY RATINGS. ELECTRICAL CONTRACTOR SHALL PROVIDE FIRE STOPPING FOR ALL CONDUIT AND OTHER PENETRATIONS COVERED UNDER DIVISION 26 IN THESE SURFACES. FIRESTOPPING SHALL MEET OR EXCEED THE RATING OF THE SURFACE BEING PENETRATED.
1.
2.
PENTHOUSE POWER NOTES -
CIRCUIT NUMBERS INDICATED DO NOT REFLECT THE ACTUAL POSITION OF THE CIRCUIT BREAKERS IN THE PANEL; RATHER, THE NUMBERS INDICATE WHICH DEVICES ARE CONNECTED TO A COMMON CIRCUIT. E.C. SHALL UTILIZE SPARES, SPACES AND CIRCUITS RELIEVED FROM DUTY TO PROVIDE THE INDICATED NUMBERS OF CIRCUITS.
EXISTING TO REMAIN, "ETR", ON THIS PLAN REFERS TO THE STATUS OF BASIC ELECTRICAL DEVICES. THERE MAY BE SOME WORK REQUIRED IN THESE SPACES INVOLVING BACK-FEEDING EXISTING CIRCUITS OR OTHER MODIFICATIONS. SEE ALL DOCUMENTS THAT MAKE UP THIS CONTRACT FOR THE TOTAL EXTENT OF WORK REQUIRED IN ALL SPACES.
1/4" = 1'-0"2PENTHOUSE - POWER
KEYED NOTES -
1. CONTROL MODULE INITIATES UNIT SHUT DOWNPROCEDURES UPON ALARM SIGNAL FROM ANY DUCT UNIT,SHAFT DUCT OR AREA SMOKE DETECTOR. SEESPECIFICATION 28 31 06 FOR ADDITIONAL INFORMATION.
1 02/22/19 BIDDING DOCUMENTS
FF
OS
OS
F
F
F
VESTIBULE
MECHANICAL EQUIPMENT
VESTIBULE
MECHANICAL EQUIPMENT
2
3
K
2
2
3
K
3
K
46''GFI
46''GFI
1
1
3
XH
AA
AA AA
AA
AA
AA
AA
B
B
4
5
a
1
SV1
SV1
SV1
2
3
J
WH-1
CP-1
S
ETR
6
6
2
3
J
CIRC.PUMP
WATERHEATER
NORTH
17400 West Capitol DriveBrookfield, WI 53045Phone: 414.778.1700Fax: 414.778.2360E-Mail: [email protected]
REV DATE DESCRIPTION OF ISSUE
SHEET NAME
DRAWN APPROVED
DATE
R&D PROJECT NO.
SHEET NUMBER
KEY PLAN
PROJECT TITLE
MILWAUKEE INTERMODAL
STATION REHABILITATION
PROJECT 2019
PARTIAL
BASEMENT AND
SECOND FLOOR
- ELECTRICAL
02/22/2019
218089.00
E210
R&D R&D
1/4" = 1'-0"1PARTIAL SECOND FLOOR PLAN - DEMOLITION
1/4" = 1'-0"2PARTIAL SECOND FLOOR PLAN - ELECTRICAL
1/4" = 1'-0"3PARTIAL BASEMENT PLAN - ELECTRICAL
1/4" = 1'-0"4PARTIAL BASEMENT PLAN - DEMOLITION
KEYED NOTES -
1.
2.
3.
4.
5.
6.
EC SHALL REUSE EXISTING CIRCUIT RELIEVED FROM DEMOLITION OF EXISTING BATHROOMS TO FEED NEW LIGHTING AND RECEPTACLES.
THE CEILING IN THIS ROOM HAS PREVIOUSLY BEEN DEMOLISHED.
EXTEND THE EXISTING CIRCUIT CURRENTLY SERVING EXIT LIGHTING ON THIS FLOOR.
EXTEND EXISTING SECOND FLOOR NORMAL CORRIDOR LIGHTING CIRCUIT WIRE THROUGH MOMENTARY SWITCH ''a'' AND LIGHTING CONTROL PANEL LCP2. SEE SHEET E100 FOR PANEL LOCATION.
EXTEND EXISTING SECOND FLOOR EMERGENCY CORRIDOR LIGHTING CIRCUIT LIGHT FIXTURE SHALL BE UNSWITCHED.
EC SHALL REUSE EXISTING CIRCUIT RELIEVED FROM DEMOLITION OF EXISTING EQUPMENT. EQUIPMENT WAS FED FROM EXISTING PANEL ''S''.
1.
2.
3.
4.
5.
6.
7.
8.
9.
DEMOLITION PLAN NOTES -
ALL INFORMATION SHOWN ON THE PLANS WAS GATHERED FROM FIELD OBSERVATION AND EXISTING DRAWINGS. EC SHALL FIELD VERIFY EXISTING CONDITIONS AND IS RESPONSIBLE FOR ANY ADDITIONAL TRACING, REMOVING, RELOCATION AND EXTENDING CIRCUITS AND DEVICES NECESSARY TO MAINTAIN CONTINUITY OF EXISTING EQUIPMENT NOT IN THE AREA OF WORK. EC SHALL FIELD VERIFY EXACT DEMOLITION REQUIREMENTS AND INCLUDE ALL ASSOCIATED COSTS. ALL ABANDONED WIRING, CONDUITS, FITTINGS, BOXES, SUPPORTS, ETC. SHALL BE REMOVED FROM THE DEVICES BACK TO THE RESPECTIVE SOURCE PANEL. UPDATE PANEL DIRECTORIES. REFER TO THE SPECIFICATIONS FOR ADDITIONAL ELECTRICAL DEMOLITION REQUIREMENTS.
ALL ELECTRICAL EQUIPMENT SHOWN ON THE DEMOLITION PLANS ARE "EXISTING TO BE REMOVED" UNLESS OTHERWISE NOTED. IN ADDITION TO REMOVING DEVICES, REMOVE ALL ASSOCIATED ELECTRICAL CIRCUITS BACK TO SOURCE. REFER TO THE SPECIFICATIONS FOR ELECTRICAL DEMOTION REQUIREMENTS.
EC SHALL SUPPORT AND PROTECT ELECTRICAL EQUIPMENT EXISTING TO REMAIN, INCLUDING BUT NOT LIMITED TO CONDUITS, WIRING, DEVICES, AND FIXTURES AS REQUIRED.
DASHED WALLS ON THE DEMOLITION PLANS INDICATE IN GENERAL EXISTING WALLS BEING DEMOLISHED. DO NOT RELY ON ELECTRICAL DRAWINGS TO DETERMINE EXTENT OF GENERAL CONSTRUCTION DEMOLITION. REFER TO ARCHITECTURAL DEMOLITION PLANS FOR THE EXACT EXTENT OF GENERAL CONSTRUCTION DEMOLITION REQUIRED BY THIS CONTRACT.
REFER TO DEMOLITION DRAWINGS OF OTHER TRADES. WHERE MOTORS, CONTROL PANELS, AND OTHER LOADS THAT HAVE AN ELECTRICAL CONNECTION ARE BEING REMOVED, INCLUDE THE DISCONNECTION AND REMOVAL OF ASSOCIATED ELECTRICAL FEEDS, CIRCUITS, AND LOOSE CONTROL EQUIPMENT IN THIS CONTRACT.
EXISTING TO REMAIN "ETR" ON THIS DEMOLITION PLANS REFERS TO THE STATUS OF BASIC ELECTRICAL DEVICES. THERE MAY BE SOME WORK REQUIRED IN THESE SPACES INVOLVING BACK-FEEDING EXISTING CIRCUITS OR OTHER MODIFICATIONS. SEE ALL DOCUMENTS THAT MAKE UP THIS CONTRACT FOR THE TOTAL EXTENT OF WORK REQUIRED IN ALL SPACES.
EC SHALL COORDINATE REMOVAL AND REPLACEMENT OF ANY ELECTRICAL CEILING DEVICES (I.E. LIGHT FIXTURES, FIRE ALARM, ETC.) OUTSIDE THE AREA OF WORK TO ACCOMMODATE THE NEW CONSTRUCTION.
EXISTING DEVICES MAY BE REUSED, IN-LIEU OF PROVIDING NEW DEVICES SHOWN ON ELECTRICAL DRAWINGS IN THIS SET, PROVIDED THE DEVICES ARE CLEAN, IN WORKING CONDITION AND ACCEPTABLE TO BE REUSED PER THE OWNER.
ELECTRICAL CONTRACTOR SHALL REFER TO THE ARCHITECTURAL PLANS FOR LOCATIONS OF SMOKE PARTITIONS AND FIRE RATED WALLS, FLOORS, AND CEILINGS AND THEIR HOURLY RATINGS. ELECTRICAL CONTRACTOR SHALL PROVIDE FIRE STOPPING FOR ALL CONDUIT AND OTHER PENETRATIONS COVERED UNDER DIVISION 26 IN THESE SURFACES. FIRESTOPPING SHALL MEET OR EXCEED THE RATING OF THE SURFACE BEING PENETRATED.
1.
2.
3.
SHEET NOTES -
EC SHALL REFER TO ARCHITECTURAL ELEVATIONS AND FLOOR PLANS FOR EXACT LOCATIONS AND MOUNTING HEIGHTS OF ELECTRICAL DEVICES.
CIRCUIT NUMBERS INDICATED DO NOT REFLECT THE ACTUAL POSITION OF THE CIRCUIT BREAKERS IN THE PANEL; RATHER, THE NUMBERS INDICATE WHICH DEVICES ARE CONNECTED TO A COMMON CIRCUIT. E.C. SHALL UTILIZE SPARES, SPACES AND CIRCUITS RELIEVED FROM DUTY TO PROVIDE THE INDICATED NUMBERS OF CIRCUITS.
EXISTING TO REMAIN, "ETR", ON THIS PLAN REFERS TO THE STATUS OF BASIC ELECTRICAL DEVICES. THERE MAY BE SOME WORK REQUIRED IN THESE SPACES INVOLVING BACK-FEEDING EXISTING CIRCUITS OR OTHER MODIFICATIONS. SEE ALL DOCUMENTS THAT MAKE UP THIS CONTRACT FOR THE TOTAL EXTENT OF WORK REQUIRED IN ALL SPACES.
AUTOMATIC TRANSFER SWITCHKEY INTERLOCKING - KEY #KEY NORMALLY REMOVED
SEE EQUIPMENT SCHEDULE
"AF" - DENOTES AMP FRAME
"XXX" - DENOTES AMP RATING
GP - GROUND FAULT PROTECTION - PERSONNEL
UVT - UNDER VOLTAGE TRIPST - SHUNT TRIP
MC - MOLDED CASE CIRCUIT BREAKER
SS - SOLID STATE MOLDED CASE CIRCUIT BREAKER
IC - INSULATED CASE CIRCUIT BREAKERPC - LOW VOLTAGE POWER CIRCUIT BREAKER
GE - GROUND FAULT PROTECTION - EQUIPMENT
ALS - ALARM SWITCHAXS - AUXILIARY SWITCHEOP - ELECTRIC OPERATOR
AF - ARC FAULT CIRCUIT INTERRUPTER (RESIDENTIAL ONLY)
CL - CURRENT LIMITING
DOUBLE CONVERSION SINGLE INPUTUNINTERRUPTIBLE POWER SUPPLY (UPS)
(MODIFY TO MAKE JOB SPECIFIC)
(XX) DEVICE DESIGNNATION
DENOTES THE FOLLOWING:
DENOTES THE FOLLOWING:
(CB) CIRCUIT BREAKER
(CON) CONTACTOR
(DS) DISCONNECT SWITCH
(VM)
(AM)
VOLTMETER
AMMETER
DENOTES THE FOLLOWING:
(VS) VOLTMETER SWITCH
(AS) AMMETER SWITCH
(M) KWHR METER
(DM) DIGITAL METER
XX
(XX) DEVICE DESIGNATION TYPE -
DENOTES THE FOLLOWING:
SEE SPECIFICATION
-SEE SCHEDULE & DETAILS
"AS" - DENOTES AMP SENSOR
"AT" - DENOTES AMP TRIP
GS - GROUND FAULT SENSING / ALARMHC - HEATING, COOLING, AIR CONDITIONING, REFRIGERATION - HCARHM - HIGH MAGNETIC - HID, MOTORS
MS - MOLDED CASE SWITCHMP - MOTOR CIRCUIT PROTECTOR
L1 - LONG TIME / INSTANTANEOUS - LIL2 - LONG TIME / SHORT TIME / INSTANTANEOUS - LSIL3 - LONG TIME / SHORT TIME / INSTANTANEOUS / GROUND FAULT TRIP - LSIGL4 - LONG TIME / SHORT TIME / INSTANTANEOUS / GROUND FAULT SENSING - LSIASC - SYSTEM COMMUNICATIONSD - SYSTEM DIAGNOSTICSSM - SYSTEM MONITORINGZS - ZONE SELECTIVE INTERLOCKING
"XXX" - DENOTES AMP RATING
VW - VIEWING WINDOW
AXS - AUXILIARY SWITCHDL - DOUBLE LUGSPL - PILOT LIGHT
DS - UNFUSED DISCONNECT SWITCHEDS - ELEVATOR DISCONNECT SWITCH
DOUBLE CONVERSION DUAL INPUTUNINTERRUPTIBLE POWER SUPPLY (UPS)
(MODIFY TO MAKE JOB SPECIFIC)
CONDITIONER
FR - FULLY RATED (100%)
1. ALL ITEMS INDICATED BY A DARK SOLID LINE AS SHOWN BELOWARE NEW.
2. ALL ITEMS INDICATED BY A LIGHT DASHED LINE AS SHOWN BELOWARE EXISTING TO REMAIN.
3. ALL ITEMS INDICATED BY A DARK DASH-DOT-DASH LINE AS SHOWNBELOW ARE EXISTING TO BE REMOVED.
4. ALL ITEMS INDICATED BY A LIGHT DASH-DOT-DASH LINE AS SHOWNBELOW ARE TYPICAL EQUIPMENT DIVISIONS.
5. ALL ITEMS INDICATED BY A LIGHT SOLID LINE AS SHOWN BELOWARE FUTURE.
6. ALL DOWNTIME SHALL BE SCHEDULED WITH THE OWNER ANDSHALL BE KEPT TO AN ABSOLUTE MINIMUM.
7. THE PANELS AND SWITCHBOARDS INDICATED ON THE ONE LINEDIAGRAM SHALL BE PROTECTED FROM AVAILABLE FAULTCURRENT SHOWN BY EITHER OF THE FOLLOWINGMETHODS:
- PROVIDE BREAKERS WITH A MINIMUM AIC RATING GREATERTHAN INDICATED
- THE SERIES RATING METHOD IS NOT ACCEPTABLE
1 - NON VENTILATED ENCLOSURE2 - INTEGRAL STRIP HEATER3 - WEATHER SHIELD
OPTIONS
TEMPERATURE RISE
SECONDARY VOLTAGE
PRIMARY VOLTAGE
kVA
TRANSFORMER ID
RATING
TYPEDT - DRY TYPELF - LIQUID FILLEDDP - DRY TYPE PAD MOUNTLP - LIQUID FILLED PAD MOUNT
GP - GENERAL PURPOSEK-# - K-RATED
EE - ENERGY EFFICIENT
4 - NEMA 3R5 - STAINLESS STEEL
CR - CAST RESINEC - ENCAPSULATED CORE
N - NORMAL BRANCHLS - LIFE SAFETY BRANCHCR - CRITICAL CARE BRANCH
BRANCH
EQ - EQUIPMENT BRANCHEM - EMERGENCY BRANCH
TRANSFER SWITCH ID
ES - ESSENTIAL SYSTEMSNES - NON ESSENTIAL SYSTEMS
AMPS
VOLTAGE
CLOSING & WITHSTAND AIC RATING
TRANSFERAUTO - AUTOMATICMAN - MANUAL
POLES
TRANSFER SWITCH TYPE
OPTIONS1 - LOAD SHED RELAY2 - BLOCK TRANSFER RELAY3 - SYNCH CHECK RELAY4 - PEAK READING AMMETER5 - STANDARD METER6 - VOLTMETER7 - COMPRESSION LUGS8 - ELEVATOR INTERFACE RELAY
TCP-1 TEMPERATURE CONTROL PANEL PENTHOUSE 120/1 0.6 PHPP 20 N CB 20 1 2 12 Y 3/4 12 - - - - - - - - - - - - 3 -
TCP-2 TEMPERATURE CONTROL PANEL PENTHOUSE 120/1 0.6 PHPP 22 N CB 20 1 2 12 Y 3/4 12 - - - - - - - - - - - - 3 -
CP-1 CIRCULATION PUMP BSMT 120/1 0.06 1.3 S SFP N CB 15 1 2 12 Y 1/2 12 PC EC EC NU CS - EC EC EC NU 7,9 - 3,10 -
WH-1 WATER HEATER BSMT 120/1 0.6 S SFP N CB 20 1 2 12 Y 3/4 12 - - - - - - EC EC EC NU 7,9 - 3,10 -
ABBREVIATIONS:
N = NORMAL BRANCH CB = AMPERE RATED CIRCUIT BREAKER MFR = MANUFACTURER 2SP = 2 SPEED MAGNETIC CONTROLLER SFS = SEE FOOD SERVICE PLANS SA = SEE ARCHITECTURAL DETAILS
LS = LIFE SAFETY BRANCH F = AMPERE RATED FUSES PC = PLUMBING CONTRACTOR VFD = VARIABLE FREQUENCY DRIVE SD = SEE ONELINE DIAGRAM
CR = CRITICAL CARE BRANCH OCPD = OVERCURRENT PROTECTIVE DEVICE MAN = MANUAL CONTROLLER IU = IN UNIT BOL = BUILT-IN OVERLOAD
EQ = EQUIPMENT SYSTEM EC = ELECTRICAL CONTRACTOR MAG = MAGNETIC CONTROLLER NU = NEAR UNIT WP = WEATHER PROOF
EM = EMERGENCY SYSTEM FSEC = FOOD SERVICE EQUIP. CONTRACTOR CS = COMBINATION CONTROLLER OU = ON UNIT FD = FUSIBLE DISCONNECT
ES = ESSENTIAL SYSTEM MC = MECHANICAL CONTRACTOR RVS = REDUCE VOLTAGE CONTROLLER SFP = SEE FLOOR PLANS LMRS = LOCKABLE MOTOR RATED SWITCH
OPTIONS:
1 = SINGLE RECEPTACLE 4 = NON FUSIBLE DISCONNECT 7 = LOCKABLE 10 = VERIFY WITH MANUFACTURER PRIOR TO INSTALLATION 13 = GFI RECEPTACLE
VOLT MOUNTSURFACE FIXTURE FIXTURE SPECIFICATION AND ACCEPTABLE MANUFACTURERS
OPTIONSSEE
ID DESCRIPTION TYPE NO. DESCRIPTION WATTS K CRI (MIN.) TYPE CONTROL NO. WATTS TYPE DEPTH MANUFACTURER CATALOG SERIES NOTE
AA
2X4 TROFFER 4000 LITHONIA 2TL
FROSTED PRISMATIC LENS #A19 PATTERN LED - DELIVERED WATTS K 80 DR 1 WATTS VOLT R CEILING <5" COLUMBIA LLT 7,12
LUMENS
XH
EXIT SIGN - SINGLE FACE LITHONIA TL
THERMOPLASTIC HOUSING LED - IN UNIT 3 - - - - - 3 VOLT S V - METALUX GRLED 61
UNIVERSAL MOUNTING DAYBRITE, COLUMBIA TG,LLT
NOTE:
SEE SPECIFICATION SECTIONS 26 50 00 FOR ADDITIONAL INFORMATION REGARDING LIGHTING FIXTURE AND INSTALLATION REQUIREMENTS. PROVIDE OPTIONS AND ACCESSORIES REFERENCED BY THE COLUMN TITLED "OPTIONS".
MANUFACTURERS AS ACCEPTABLE SHALL MEET ALL REQUIREMENTS AND FEATURES INDICATED. ACCEPTABLE MANUFACTURERS MUST MEET THE PHOTOMETRIC PERFORMANCE OF THE LISTED UNIT.
ABBREVIATIONS:
AR = AS REQUIRED DMX = ADDRESSABLE, DIMMING <1-100% FD10 = FLUORESCENT DIMMING 10-100% OT = OTHER STN = STONE
BL = BI-LEVEL SWITCHING DR = DRIVER GRD = GRADE PD = PENDANT SUSP = SUSPENDED
BT = BLUETOOTH DW = DRYWALL H = HID PL = PLASTER SW = SWITCHING
CAB = UNDERCABINET ELV = ELECTRONIC LOW VOLTAGE DIMMING HAL = HALOGEN PS = PULSE START T = CERAMIC/GLASS TILE
CL = CLEAR EM = EMERGENCY HBF = HIGH BALLAST FACTOR R = RECESS TW = TUNABLE WHITE LED
DALI = ADDRESSABLE, DIMMING <1-100% ES = EXPOSED STRUCTURE I = INCANDESCENT RGB = RED, GREEN, BLUE LEDS V = VARIES
DM0 = LED DIMMING 0-10V, 0 -100% ET = ELECTRONIC BALLAST LBF = LOW BALLAST FACTOR RM = REMOTE W = WALL MOUNTED
DM1 = LED DIMMING 0-10V, 1 -100% F = FLUORESCENT LG = LAY-IN GRID S = SURFACE WD = WOOD
DM5 = LED DIMMING 0-10V, 5 -100% FD1 = FLUORESCENT DIMMING 1-100% MLV = MAGNETIC LOW VOLTAGE DIMMING SPEC = SPECIAL XFMR = TRANSFORMER
DM10 = LED DIMMING 0-10V, 10 -100% FD5 = FLUORESCENT DIMMING 5-100% NBF = NORMAL BALLAST FACTOR ST = STANDARD
DMW = DIM TO WARM LED
OPTIONS:
1 = POST PAINTED FINISH 21 = FURNISH WITH AIR HANDLING CAPABILITY 41 = MATTE DIFFUSE LOW IRIDESCENT REFL. 61 = FURNISH WITH UNIVERSAL ARROWS AND GREEN STENCIL FACE
2 = REGRESSED ALUMINUM DOOR FRAME 22 = FURNISH WITH WIRE GUARD 42 = FURNISH WITH SYMMETRICAL REFLECTOR 62 = FURNISH WITH FIELD ADJUSTABLE CHEVRONS
3 = FLAT STEEL DOOR FRAME 23 = FURNISH WITH ENDCAPS 43 = FURNISH WITH ASYMMETRICAL REFLECTOR 63 = FURNISH WITH MIRRORED BACKGROUND
4 = FLAT ALUMINUM DOOR FRAME - MITERED CORNERS 24 = FURNISH IN LENGTH AS SHOWN 44 = FURNISH WITH TOP AND BOTTOM LENS 64 = FURNISH WITH INTEGRAL BATTERY
5 = STAINLESS STEEL TRIM AND DOOR FRAME 25 = FURNISH WITH SOLID FRONT 45 = FURNISH WITH LOUVER 65 = FURNISH WITH INTEGRAL HIGH CAPACITY BATTERY (FOR REMOTE HEADS)
6 = FURNISH WITH SPRING LOADED LATCHES 26 = FURNISH WITH DUST COVER 46 = FURNISH WITH PERFORATED DIFFUSER 66 = FURNISH WITH SELF DIAGNOSTICS
7 = FURNISH WITH HINGED DOOR 27 = CUSTOM FINISH - SELECTION TBD 47 = FURNISH WITH EGGCRATE LOUVER 67 = FURNISH WITH AUXILIARY EMERGENCY BATTERY BALLAST/DRIVER
8 = DAMP LOCATION CONSTRUCTION 28 = STANDARD FINISH - SELECTION TBD 48 = FURNISH WITH SOFTENING LENS 68
9 = WET LOCATION CONSTRUCTION 29 = FURNISH WITH HOUSE SIDE SHIELD 49 = FURNISH WITH PRISMATIC LENS 69
10 = IP65 RATING 30 50 = FURNISH WITH LINEAR SPREAD LENS 70
11 = IP66 RATING 31 51 = FURNISH WITH SPREAD LENS 71 = FURNISH WITH ANTI-MICROBIAL FINISH
13 = NEMA 4X RATED 33 = FURNISH WITH CHAIN MOUNTING 53 73 = FURNISH WITH RF NOISE SUPPRESSORS (ADVANCE RIF-1) FOR EACH DRIVER
14 = IC RATING 34 = FURNISH WITH RIGID STEM MOUNTING 54 = FURNISH WITH ROCKER SWITCH 74 = FURNISH WITH ACRYLIC LENS WITH INTEGRAL RFI SHIELDING
15 = ADA COMPLIANT 35 = FURNISH WITH SWIVEL CANOPY 55 = FURNISH WITH INTEGRAL OCC. SENSOR 75 = FURNISH WITH LOW VOLTAGE CONTROL (LVC)
16 = DOUBLE GASKETED-LENS TO TRIM TO CEILING 36 = FURNISH WITH ADJUSTABLE AIRCRAFT CABLE MOUNTING 56 = FURNISH WITH INTEGRAL DAYLIGHT SENSOR
17 = TRIPLE GASKETED-LENS TO DOOR TO HOUSING TO CEILING 37 = FURNISH WITH ADJUSTABLE MOUNTING HARDWARE 57 = FURNISH WITH INTEGRAL PHOTOCELL
18 = FURNISH WITH TAMPER RESISTANT HARDWARE 38 = FURNISH WITH MANUFACTURER'S CUSTOM JUNCTION BOX 58 = FURNISH WITH REMOTE DRIVER
19 39 = FURNISH WITH RECESSED SLOPE ADAPTER 59 = FURNISH WITH CURRENT LIMITING DEVICE
20 40 60
GENERAL NOTES:
1. VERIFY CEILING T-BAR WIDTH (I.E. 9/16", 15/16", 1.5") WITH THE ARCHITECT/INTERIORS SPECIFICATION PRIOR TO ORDERING LAY-IN FIXTURES.
2. IN ALL INSULATED OR FIRE RATED CEILINGS, THE EC SHALL BE RESPONSIBLE FOR THE PROPER TENTING (OR FIRE BOXING) OF THE RECESSED FIXTURES. FOR PREFAB PRODUCTS REFER TO TENMAT OR SPECIALTY PRODUCTS AND INSULATION.
3. VERIFY DIMMING BALLAST / DRIVER COMPATIBILITY WITH DIMMING CONTROL.
4. REFER TO ARCHITECTURAL ELEVATIONS FOR EXACT LOCATION AND MOUNTING HEIGHT.
5. TO MEET SPECIFIED DELIVERED LUMEN PACKAGE PROVIDE PROGRAMMED DRIVER AS REQUIRED.
6. FIXTURE PERFORMANCE TOLERANCES: CCT +/- 200 DEGREES; DELIVERED LUMENS +/- 5%; ENERGY CONSUMPTION +/- 5%; BEAM SPREAD DISTRIBUTION +/- 5 DEGREES AND AS OUTLINED IN 26 50 00.
7. IF SUBMITTING A FIXTURE FOR APPROVAL AS AN EQUAL, PROVIDE CUT SHEET AND IES PHOTOMETRIC FILE PRIOR TO BIDDING. A WORKING SAMPLE OF THE FIXTURE IS REQUIRED FOR APPROVAL BY THE A/E.
LIGHT FIXTURE SCHEDULE NOTES:
1. MANUFACTURERS, PRODUCTS, AND DESCRIPTIONS LISTED IN THE LIGHTING FIXTURE SCHEDULE ARE THE BASIS OF DESIGN SPECIFICATION FOR EACH FIXTURE TYPE. EQUAL PRODUCTS WILL BE ENTERTAINED UNLESS OTHERWISE NOTED. ALL PROPOSED EQUAL PRODUCTS ARE REQUIRED TO MEET OR EXCEED ALLOF THE SPECIFICATION REQUIREMENTS LISTED IN THE LIGHTING FIXTURE SCHEDULE INCLUDING BUT NOT LIMITED TO: PRODUCT GRADE, LIGHT SOURCE TECHNOLOGY, CONTROL TECHNOLOGY, OPTICAL PERFORMANCE (DELIVERED LUMENS OR CBCP), DISTRIBUTION, FIXTURE ACCESSORIES, CONSTRUCTION,DIMENSIONS, MOUNTING, FINISH, ENERGY PERFORMANCE, AND LISTINGS/RATINGS.
THE SPECIFIER HAS EVALUATED ALL OF THE MANUFACTURERS LISTED BELOW AND CONSIDERS THESE MANUFACTURERS TO BE OF A QUALITY THAT MEET GENERAL SPECIFICATION REQUIREMENTS FOR THE CATEGORY OF PRODUCT UNDER WHICH THEY ARE LISTED. ALTHOUGH MANUFACTURERS ARE LISTED BELOWIT DOES NOT ENSURE THAT THEY HAVE PRODUCTS THAT MEET ALL OF THE SPECIFICATION REQUIREMENTS FOR EACH FIXTURE TYPE. IT MEANS THAT THESE MANUFACTURERS HAVE ALREADY BEEN EVALUATED AND HAVE PRODUCTS THAT SHALL BE REVIEWED FOR APPLICABILITY AS EQUALS. MANUFACTURERS THATARE NOT LISTED BELOW WILL REQUIRE A WORKING SAMPLE FOR SPECIFIER TO REVIEW IN ORDER TO BE EVALUATED FOR APPLICABILITY.
THE BURDEN OF MEETING THE BASIS OF DESIGN SPECIFICATION IS ON THE DISTRIBUTOR QUOTING THE PROJECT. DETERMINATION OF EQUIVALENCY IS THE RESPONSIBILITY OF THE SPECIFIER. EVEN IF A PROPOSED EQUAL PRODUCT IS FROM ONE OF THE MANUFACTURERS LISTED BELOW, IF IT DOES NOT MEET THEBASIS OF DESIGN SPECIFICATION REQUIREMENTS THEN IT WILL BE REJECTED. THERE SHALL BE NO ADDITIONAL COST ASSOCIATED WITH REJECTION OF A FIXTURE NOT DEEMED EQUIVALENT BY THE SPECIFIER.
A. COMMERCIAL TROFFERS AND WHITEGOODS – COLUMBIA, CREE, DAYBRITE, DAY-O-LITE, HE WILLIAMS, LITHONIA, METALUX, MERCURY , PMC
B. EXIT AND EMERGENCY – CHLORIDE, DUAL-LITE, EMERGI-LITE, EVENLITE, HE WILLIAMS, ISOLITE, LITHONIA, MULE, SURE-LITES
17400 West Capitol DriveBrookfield, WI 53045Phone: 414.778.1700Fax: 414.778.2360E-Mail: [email protected]