Top Banner
INDUSTRY TERTIARY UTILITIES OIL & GAS HYDRO POWER PLANTS BIOMASS PLANTS PHOTOVOLTAIC PLANTS WIND PLANTS TRANSPORTATION FOGGIA RAVENNA MILANO
2

MILANO RAVENNA FOGGIA - donar.messe.de · industry tertiary utilities oil & gas hydro power plants biomass plants photovoltaic plants wind plants transportation foggia ravenna milano

Oct 08, 2019

Download

Documents

dariahiddleston
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: MILANO RAVENNA FOGGIA - donar.messe.de · industry tertiary utilities oil & gas hydro power plants biomass plants photovoltaic plants wind plants transportation foggia ravenna milano

INDUSTRY TERTIARY UTILITIES

OIL & GAS HYDRO POWER PLANTS BIOMASS PLANTS

PHOTOVOLTAIC PLANTS WIND PLANTS TRANSPORTATION

FOGGIA

RAVENNA

MILANO

Page 2: MILANO RAVENNA FOGGIA - donar.messe.de · industry tertiary utilities oil & gas hydro power plants biomass plants photovoltaic plants wind plants transportation foggia ravenna milano

ECOSMART Protection Relay

Protection, monitoring and control relays for MV users series ECOSMART TPR-1 and TPR-2: phase overcurrent protection for overload and short circuit (50 51), homopolar overcurrent protection for single phase fault and double earth single-phase (50N 51N) directional earth fault overcurrent (67N), communication interface RS232 & MODBUS RS485.

QMM90N Smart Motor Starter

Withdrawble functional unit.

Gas insulated line switch disconnector.

ECOSMART PB

Up to:

24 kV

1250 A *

25 kA 3 sec.

*off load

Air Insulated Earthing Switch Disconnector.

ECOSMART ES

Up to:

24 kV

20 kA 1 sec.

Outdoor gas insulated, pole mounted, switch disconnector.

ECOSMART OSD

Up to:

24 kV

630 A

25 kA 1 sec.

Vacuum circuit breaker with side operating mechanism for secondary distribution.

ECOSMART VCB L

Up to:

24 kV

1600 A

25 kA 3 sec.

Vacuum circuit breaker with front operating mechanism for primary distribution.

ECOSMART VCB F

Up to:

12 kV

3150 A

40 kA 3 sec.

24 kV

2500 A

31,5 kA 3 sec.

17,5 kV

3150 A

40 kA 3 sec.

Withdrawable vacuum circuit breaker with front operating mechanism and enclosure for primary distribution.

ECOSMART VCB FP

Up to:

12 kV

3150 A

40 kA 3 sec.

24 kV

2500 A

31,5 kA 3 sec.

17,5 kV

3150 A

40 kA 3 sec.

Air insulated medium voltage switchgear with gas insulated switch-disconnector and vacuum circuit breaker.

ECOSMART MIX

Up to:

24 kV

1250 A

25 kA 1 sec.

Type LSC2A-PM according to IEC 62271-200

Prefabricated mobile substation with modular metal structure suitable to contain medium - low voltage equipments and monitoring and control systems.

SUBSTATION WITH MODULAR METAL STRUCTURE

Arc proof air insulated medium voltage switchgear for primary distribution.

QMTC

Up to:

Type LSC2B-PM according to IEC62271-200

12 kV

4000 A

50 kA 3 sec.

50 kA 1 sec. Internal arc AFLR

17,5 kV

3600 A

50 kA 3 sec.

50 kA 1 sec. Internal arc AFLR

24 kV

2500 A

31,5 kA 3 sec.

31,5 kA 1 sec. Internal arc AFLR