No.1 Jalan TP 7/7, Sime UEP Industrial Park, 40400 Shah Alam, Selangor, Malaysia.Website: www.itmikro.com Tel: +60-3-5192-7155 Fax: +60-3-5192-7166
Mikro® reserves the right to make changes without further notice to any products herein to improve reliability, function or design. The figures shown are without obligation.
MK2200L
Technical Data
RATINGS
Auxiliary SupplyModel MK2200L-150DRated voltage : 30 ~ 120 V DCOperating voltage : 24 ~ 150 V DC
Model MK2200L-240ADRated voltage : 100 ~ 240 V AC or 140 ~ 340 V DCOperating voltage : 85 ~ 265 V AC or 110 ~ 370 V DCRated frequency : 50 or 60 HzOperating frequency : 45 ~ 65 HzPower consumption : 8 VA max
Current Inputs Rated current, In, Ion : 1 or 5 A by connectionFrequency : 50 or 60 Hz nominalBurden : < 0.025 VA (1 A) : < 0.3 VA (5 A)Thermal withstand : 4 x In continuous : 40 x In for 2s : 100 x In for 1s
Digital Inputs Input type : Optically isolatedRated voltage : 20 ~ 380 V DC : 50 ~ 270 V AC
Output Contacts Trip Contact Relay R1, R2, R3, R4, IRF RelayRated voltage : 250 V AC / DCContinuous carry : 5 AExpected electrical life : 100,000 operations at rated loadExpected mechanical life : 5 x 106 operations
RECORDS Fault Record : Up to 50 recordsEvent Record : Up to 250 recordsAlarm Record : Up to 30 records
SETTING RANGES
General Line CT primary : 1 to 10,000 AEarth CT primary : 1 to 10,000 AFrequency : 50 or 60 Hz
Phase Overcurrent I> : 0.1 to 25 x In (Recommended up to
2 x In for IDMT delay)I>Delaytype:IDMTordefinitetimetI> : 0 to 100 sI> IDMT curve : NI, VI, EI, LTI, NI 1.3/10ktI :0.01to1.00I>> : 0.5 to 40 x IntI>> : 0 to 100 sI>>> : 0.5 to 40 x InI>>> Sample : Yes or NotI>>> : 0 to 100 s
Earth Fault Io> : 0.02 to 2 x Ion (Recommended up
to 0.5 x Ion for IDMT delay)Io> Delay type :IDMTordefinitetimetIo> : 0 to 100 sIo> IDMT curve : NI, VI, EI, LTI, NI 1.3/10ktIo : 0.01 to 1.00Io>> : 0.1 to 10 x IontIo>> : 0 to 100 s
Thermal Overload Iq > : 0.1 to 3 x InTq : 1 to 200 minutesk :1to1.5q Trip : 50 to 200%q Alarm : 50 to 200%
MEASUREMENT RANGES Phase Current Secondary:5 A input : 0 to 200 A1 A input : 0 to 40 A
Earth Current Secondary:5 A input : 0 to 50 A1 A input : 0 to 10 A
ENVIRONMENTAL CONDITIONS Temperature :-5˚Cto55˚CHumidity :56daysat93%RHand40˚C
non-condensing
MECHANICAL Mounting : Panel mountingDimension (mm) : 142(w) x 165(h) x 198(d)Enclosure protection : IP54 at the panelApproximateweight : 2.9kg
MK 2200L
Ordering Information
MK2200L-150D For50/60Hz,auxiliaryvoltage24~150VDCMK2200L-240AD For50/60Hz,auxiliaryvoltage85~265VAC or 110 ~ 370 V DC
MODEL DESCRIPTION
Case Dimensions
Normal Inverse Very Inverse Extremely Inverse
Long Time InverseTypical Application Diagram 1
Typical Application Diagram 2Com
bined Overcurrent & Earth Fault Relay
142 mm
165
mm
Front
Panel Cutout
198 mm34 mm
136
mm
Side
139
±1 m
m
129 ±1 mm
MK 2200L
MK2200
Technical DataINPUTS Measuring input: Rated current In : 1 A or 5 ARated frequency : 50 or 60 HzThermal withstand : 4 x In continuous 25 x In for less than 10 sec 100 x In for less than 1 secBurden : < 0.3VA at In
RATINGSRated current ( In ) : 5 ARated frequency : 50 or 60 HzBurden : < 0.3 VA at InThemal withstand : 4 x In continuous
AUXILIARY SUPPLYModelMK1000A-240A(6) : 198~265VACModelMK1000A-240AD(6): 85~265VAC 110 V DC ~ 340 V DCModelMK1000A-150D(6) : 24~150VDCSupply frequency : 50 or 60 HzV A rating : 3 VA typical
ACCURACYProtection thresholds : ± 5%Time delay : ± 5% with a
minimum of 50 ms
OUTPUT CONTACTSTrip Contacts ( R1 & R2 )Rated voltage : 250V AC / DCContact rating : 5 AExpected electrical life : 100,000 operations
at rated currentExpected mechanical life : 5 x 106 operations
Positive safety contact*:Activatedwhenpower-up and relay function correctly
Alarm contact* : Activated when measuredleakagecurrent exceeded 50% of IΔn.
OUTPUT CONTACTSRated voltage : 250 V ACContact rating : 5 A (NO)
3 A (NC)Expected electrical life : 100,000 operations at
rated currentExpected mechanical life : 5 x 106 operations
INDICATORSPre-faultalarm :Redindicator
(Normalblink)Time delay : Red indicator
(Fastblink)Leakagetrip : 7-segmentdisplay
and red indicatorZCTconnectionerror : 7-segmentdisplay
and red indicatorReal-timeleakagecurrent: 7-segmentdisplay
ZERO - PHASE CURRENT TRANSFORMERTooperatewithMikro’sZCTseriesofcurrenttransformer
MECHANICALMounting : Panel mountingDimension (mm) : 96(w) x 96(h) x 90(d)Enclosure protection : IP54 at the panelApproximateweight : 0.4kg(excludingZCT)
red indicatorRe-closelockout : 7-segmentdisplayand
red indicatorZCTconnectionerror: 7-segmentdisplayand
red indicatorReal-timeleakagecurrent:7-segmentdisplay
ZERO-PHASE CURRENT TRANSFORMERTooperatewithMikro’sZCTseriesofcurrenttransformer
MECHANICALMounting : Panel mountingDimension (mm) : 96(w) x 96(h) x 90(d)Enclosure protection : IP54 at the panelApproximateweight : 0.6kg(excludingZCT)
ENVIRONMENTAL CONDITIONSTemperature : -5˚Cto+55˚CHumidity : 56 days at 93% RH and
40˚Cnon-condensing
MECHANICALMounting : DIN rail mountingDimension (mm) : 71(w) x 85(h) x 70(d)Enclosure protection : IP54 at the panelApproximateweight : 0.4kg(excludingZCT)
* Applicable to DIN300E model only
OUTPUT CONTACTSContacts(Trip/50%pre-fault*)Rated voltage : 250 V ACContact rating : 5 AExpected electrical life : 100,000 operations at
rated currentExpected mechanical life : 5 x 106 operations
D d3, 3 wire d4, 4 wire MODEL ZCT inner Up till wire Up till wire diameter (mm) diameter (mm) diameter (mm)
MODEL DESCRIPTION WEIGHT
40S
60S
80S
120S 210S
D
d3
3 wire
Dd4
4 wire
Example:ForasinglecoreCU/PVCinsulated,non-sheathed450/750V50mm2 conductor, it’snominaloveralldiameteris11.7mm.Topass4wiresthroughtheZCT,wecanuseZCT40S as the maximum diameter it can support is up till 12mm.
DVMFeatures• Built-inselectorswitch
• Easy-to-read,14.2mmdigitdisplay
• DINsizecasing
Technical Data
Auxiliary supply : 198 ~ 265 V AC : 94 ~ 127 V ACVA rating : 3 VAInput frequency : 47 ~ 66 HzMaximum input voltage : 500 VrmsApproximateweight :0.6kg
CURRENT MEASUREMENT (TRMS) Nominal current : 5 A Min. measurement : 5 mA Accuracy : 0.2% of full scaleBurden : < 0.05 VA at 5 AMeasurement range : 10 APulsed withstand : 100 A for 1 secCT primary : 5 ~ 50,000 A
VOLTAGE MEASUREMENT (TRMS) Nominal phase voltage : 0 ~ 300 V AC Minimum measurement : 10 V Accuracy : 0.2% at full scalePhase voltage via VT : 60 ~ 50,000 V
POWER MEASUREMENT Real power, apparent power, reactive power Accuracy : 0.5%
POWER FACTOR MEASUREMENT Total and displacement power factor Accuracy : 0.5%
POWER & THERMAL CURRENT DEMANDInterval : 1 ~ 30 mins
VOLTAGE AND CURRENT SEQUENCECOMPONENTSPositive, negative and zero sequence
FREQUENCY MEASUREMENT Measurement range : 45 ~ 65 Hz Accuracy : 0.2%
ENERGY MEASUREMENT ACCURACYActive :IEC62053-22class0.5Reactive :IEC62053-23class2
HARMONICS DISPLAY Fundamental up to 32nd order
VOLTAGE & CURRENT WAVEFORMDISPLAY Simultaneous3-phasevoltageorcurrent waveforms
AUXILIARY POWER SUPPLY AC voltage : 90 ~ 415 V AC Frequency : 50 / 60 Hz DC voltage : 100 ~ 300 V DC Power consumption : 3W typicalSustained overload : 500 V AC
CURRENT MEASUREMENT (TRMS)CT primary : 5 ~ 8000 ACT secondary : 5 AMinimum measurement : 5 mAAccuracy : 0.5% from 1A to 6 A (secondary)Burden : < 0.05 VA at 5 ASustained overload : 6 A
VOLTAGE MEASUREMENT (TRMS)Nominal phase voltage : 20 ~ 300 V AC Minimum measurement : 10 V Accuracy : 0.5% at full scalePhase voltage via VT : 60 ~ 33,000 V
POWER MEASUREMENTReal power, apparent power, reactive power measurementMeasuring updating period : 1 sAccuracy : 1.0%
ACTIVE POWER DEMANDInterval : 1 ~ 30 mins
POWER FACTOR MEASUREMENTTotal and displacement power factor Accuracy : 1.0%
FREQUENCY MEASUREMENT Measurement range : 45 ~ 65 HzMeasurement updating period : 1sAccuracy : 0.5%
ENERGY ACCURACYActive(accordingtoIEC62053-21) :class1Reactive(accordingtoIEC62053-23):class2
AUXILIARY POWER SUPPLYAC voltage : 90 ~ 415 V ACFrequency : 50 / 60 HzDC voltage : 100 ~ 300 V DCPower consumption : <3 VA
MECHANICALMounting : DIN railDimension (mm) : 65(w) x 85(h) x 50(d)Approximateweight : 0.3kg
Digital Power M
eterDM
38
Digital Power M
eter
65 mm
85 mm
45.5 mm
71 mm
Front
15.5 mm
50 mm
Side
Case Dimensions
Typical Application Diagram
1 2 3 4 5 6
S1 S2 S1 S2 S1 S2
7 8 9 10 11
12 13 14 15 16 17 18 19 20 21 22
LnL3L2L1
RS 485Modbus-RTU
NOTE: Current transformer secondaryterminal MUST NOT be earthed.
S1P1
P2S2 DM38
120 Ohm
I1 I2 I3
L3L1 L2 Ln
DM 38 CONNECTION DIAGRAM
!X
+-GN
D
LOAD
Ordering Information
Electromagnetic Compatibility (EMC)
DM38-240A SelfPowered100~240VAC
Immunity for industrial environments.
Emission standard for industrial environments.
MODEL DESCRIPTION
Part 6-2: Generic Standards IEC61000-6-2
Part 6-4: Generic Standards IEC61000-6-4
DM 38
MU350
Technical Data
SETTING RANGESUndervoltage : Off, 1% to 25%Time delay for undervoltage : 0.1s to 30sOvervoltage : Off, 1% to 20%Time delay for overvoltage : 0.1s to 30sStart time delay : 0s to 999sUnbalance : Off, 3% to 20%Time delay for unbalance : 0.5s to 30sPhase loss : Fixed time <0.5sPhase sequence : Fixed time <0.5s
AUXILIARY SUPPLYMU350-415V:380V(-25%)to415V(+20%)ACSupply frequency : 45 Hz to 65 HzMaximum power consumption: 3VA
SETTING RANGESUndervoltage : 1% to 25%Time delay for undervoltage : 0.1s to 30sOvervoltage : 1% to 20%Time delay for overvoltage : 0.1s to 30sStart time delay : 0s to 999s
For MU250 only:Unbalance : 3% to 20%Time delay for unbalance : 0.1s to 30sPhase loss : Fixed time <0.1sPhase sequence : Fixed time <0.1s
POWER SUPPLY INPUTInput voltage:MU150-110V&MU250-110V : 100V(-25%)to120V(+20%)ACMU150-240V&MU250-220V : 220V(-25%)to240V(+20%)ACMU250-415V : 380V(-25%)to415V(+20%)Supply frequency : 45 Hz to 65 Hz
Maximum power consumption:MU250 : 3VAMU150 : 2.5VA
OUTPUT CONTACTSRated voltage : 250 V ACContact rating : 5 AExpected electrical life : 100,000 operations at
rated currentExpected mechanical life : 5 x 106 operations
OUTPUT CONTACTSRated voltage : 250 V ACContact rating : 5 AExpected electrical life : 100,000 operations at
rated currentExpected mechanical life : 5 x 106 operations
INDICATORSPowersupplyON :GreenindicatorOutput ON : Red indicatorUnder voltage limit (U<) * : Red indicatorOver voltage limit (U>) ** : Red indicator
ENVIRONMENTAL CONDITIONSTemperature : -5˚Cto+55˚CHumidity : 56 days at 93% RH and
40˚Cnon-condensing
MECHANICALMounting : Circular11-pinplug-in
socketDimension (mm) : 35(w) x 80(h) x 72.5(d)Approximateweight : 0.3kg
* Applicable to MX160A and MX200A only
** Applicable to MX180A and MX200A only
*** For single phase connection, short pin 5,6 & 7
Features• Electronicmonitoringrelay
• Voltagemonitoringforsingle 3-phasesystem
• Phasefailuremonitoring
• Adjustablevoltagelimit
• Adjustabledelaytime
• Indicatorsforvoltagefault
• IndicatorsforpowerandoutputON
• ANSICode:27,47,59
Product Description
MX160A, MX180A & MX200A are single or 3-phasemonitoring relays.The relaysare designed for application where it required to maintain the voltage within setlimits.Abuilt-inadjustabletimedelayprevents nuisance tripping.
Voltage RelayM
X 200A / 180A / 160A
Voltage Relay
Case Dimensions Ordering Information
80 mm
72.5 mm
35 mm
MX160A-380
MODELUnder
VoltageMonitoring
YES
MX160A-400 YES
MX160A-415 YES
OverVoltage
Monitoring
NO
NO
NO
SupplyVoltage
V AC
380
400
415
MX180A-380 NO YES 380
MX180A-400 NO YES 400
MX180A-415 NO YES 415
MX200A-380 YES YES 380
MX200A-400 YES YES 400
MX200A-415 YES YES 415
FUNCTION
Wiring Diagram
Operations Diagram
L3L2L1N
5 6 78
9
10111
2
3
4
LN
5 6 78
9
10111
2
3
4
Single-Phase System
i ) Over Voltage Function**
3-Phase System
ii ) Under Voltage Function*
T
Over Voltage LimitHysteresis
RelayON
RYB
>U LED ON
T
Under Voltage Limit
Hysteresis
RelayON
<U LED ON
RYB
MX 200A / 180A / 160A
MX100MK50MX 100
Phase Sequence &Phase Failure monitoring
MX 50Phase Failure monitoring
Technical Data
POWER SUPPLY INPUTPhase-to-phasevoltage : 230VAC±20% : 400 V AC ±20%Frequency range : 45 to 65 HzMax power consumption : 3 VAInput connections : Phase L1 to pin 5 Phase L2 to pin 6 Phase L3 to pin 7 Neutral (optional) to
pin 11
OUTPUT CONTACTSRated voltage : 250 V ACContact rating : 5 AExpected electrical life : 100,000 operations at
rated currentExpected mechanical life : 5 x 106 operations
INDICATORSPowersupplyON :GreenindicatorOutput ON : Red indicator
ENVIRONMENTAL CONDITIONSTemperature : -5˚Cto+55˚CHumidity : 56 days at 93% RH and
40˚Cnon-condensing
MECHANICALMounting : Circular11-pinplug-in
socketDimension (mm) : 35(w) x 80(h) x 72.5(d)Approximateweight : 0.3kg
Voltage RelayM
X 100 / 50
Features• Electronic monitoring relay
• Phase sequence monitoring*
• Phase failure monitoring
• Plug-intypemodule
• Indicators for power and alarm status
• ANSICode:47
Product Description
This phase sequence and phase failure relay is designed for application where the 3-phasesupplyneedstobecontinuouslymonitored for proper sequencing and phase loss. Commonly used to protect a 3-phasemotor.
Voltage RelayMODEL
MX100-230
MX100-400
MX50-230
MX50-400
DESCRIPTION
Auxiliary voltage 184~276 V AC
Auxiliary voltage 320~480 V AC
Auxiliary voltage 184~276 V AC
Auxiliary voltage 320~480 V AC
Wiring Diagram
Function Table
Example 2
L3L2L1N
5 6 78
9
10111
2
3
4
3 ~L3
Example 1
L2L1
5 6 78
9
10111
2
3
4
3 ~
Condition1
2
3
4
5
6
Pin 5L1
Loss
L1
L1
L2
L3
Pin 6L2
L2
Loss
L2
L1
L2
Pin 7L3
L3
L3
Loss
L3
L1
RelayON
OFF
OFF
OFF
OFF
OFF
RemarkSystem healthy
Phase failure
Phase failure
Phase failure
Sequence fault*
Sequence fault** Applicable to MX100 model only
Case Dimensions Ordering Information
80 mm
72.5 mm
35 mm
MX 100 / 50
Technical Data
INPUTRatedPhase-neutralvoltage :220Vto240VACRatedPhase-phasevoltage :380Vto415VACRated frequency : 50 or 60 HzRated current (In) : 5ABurden : < 0.3 VA at InThermal withstand : 1.2 x Un , 2 x In continuous : 1.2 x Un , 10 x In for 3 secPower consumption : 3 VA maximum
OUTPUT CONTACTSRated voltage : 250 V AC/DCContact rating : 5 AExpected electrical life: 100,000 operations at
rated currentExpected mechanical life: 5 x 106 operations
SETTING RANGESRange : 2% to 20% reverse current
with 1% HysteresisTime delay : 0 sec to 20 sec3-Phase4-wire(star)or3-Phase3-wire(delta)
MECHANICALMounting : DIN railDimension (mm) : 71(w) x 85(h) x 70(d)Approximateweight : 0.3kg
Reverse Power Relay
RPR 415A
RPR415AFeatures• Reverse power monitoring
• 3-phase,3or4-wiresystem
• Adjustable reverse power setting
• Adjustable tripping time delay
• Indicators for auxiliary power, trip delay and trip status
• Test button
• ANSI Code: 32
Product Description
RPR 415A relay is a directionally controlled timing relay used to protect AC generators from motoring. When such condition occurs and the reverse current exceeded the customer adjustable preset limit for a predetermined delay time, the trip relay operates to disconnect the circuit.
INPUTRated voltage (Un) : 380 ~ 440 V ACRated current (In) : 5 ARated frequency : 50 or 60 HzOverload : 1.2 x Un , 2 x In continuous 1.2 x Un , 10 x In for 3 sec
OUTPUT CONTACTSRated voltage : 250 V AC/DCContact rating : 5 AExpected electrical life: 100,000 operations at
rated currentExpected mechanical life: 5 x 106 operations
SETTING RANGESRange : 2% to 20% reverse current with
1% HysteresisTime delay : 0 sec to 20 sec
INDICATORSAuxiliarysupply :GreenindicatorDelay : Red indicatorTrip : Red indicator
MECHANICALMounting : Panel mountingDimension (mm) : 96(w) x 96(h) x 142(d)Approximateweight : 0.8kg
Reverse Power Relay
RPR 415
RPR415Features• Reverse power monitoring
• 3-phase-4-wiresystem
• Adjustable reverse power setting
• Adjustable tripping time delay
• Indicators for auxiliary power, trip delay and trip status
• Test button
• ANSICode:32
Product Description
The RPR 415 relay is a directionally controlled timing relay used to protect AC generators from motoring. When such a condition occurs and the reverse current exceeded the customer adjustable preset limit and the current persists for a predetermined delay time, the trip relay operates to diconnect the circuit.
Reverse Power Relay
Case Dimensions142 mm
132 mm
Side
96 m
m
96 mm
Front
91.0 ± 0.5 mm
91.0
± 0
.5 m
m
Panel Cutout
Ordering Information
RPR415 Auxiliary voltage 380 ~ 440 V AC
MODEL DESCRIPTION
2 3 4 5 6 7 8
9 10 11 12 13 14 15
1
16
NC
P1
S1
COM
DIRECTION OF CURRENT FOR OPERATION
NO
L1
L2
L3
N
Typical Application Diagram
RPR 415
Power Factor Regulator
PFR 140 / 120 / 80 / 60
Technical Data
RATINGS AUXILIARY POWER SUPPLYCurrent Supply voltage : 220~240 V AC /
380~415 V ACOperatingLimits : -15%+10%Consumption : 10 VA maxRated frequency : 50 Hz or 60 Hz
Rated voltage : 250 V ACContact rating : 5 AExpected electrical life : 100,000 operations at
rated currentExpected mechanical life : 5 x 106 operationsMax current for the common terminals : 12 A continuous
CURRENT INPUTRated current ( In ) : 5 AOperating Limits : 0.05 A to 6.5 ARated Frequency : 50 Hz or 60 Hz
CONTROL RANGEPowerfactorsetting :0.8Ind-0.8CapC/Ksetting :0.03-1.20/AutomaticSwitchingsensitivity :5-600s/stepReconnection time for samestep :5-240sTHDthreshold :0.20-3.00(20%-300%)/
• Displayofpowerfactor,current&totalharmonicdistortion of current
• Programmablesensitivity
• Last step can be used as alarm/fan output
• Under/overvoltagealarm,under/overcompensatealarm & high harmonic distortion alarm
• User-friendlysetting
• ComplieswithIEC61000-6-2standard
ENVIRONMENTAL CONDITIONSTemperature :-5˚Cto+55˚CHumidity : 56 days at 93% RH and
40˚Cnon-condensing
MECHANICALMounting : Panel mountingDimension (mm) : 144(w) x 144(h) x 90(d)Enclosure protection : IP54 at the panelApproximateweight :1.2kg
MAIN
P1
P2
FUSE
K14 K13 K2 K1
24232221201918171615
14
13
12111098
14131211
7654321
10987654321
AUXVOLTAGE
CURRENT/ 5 A
Pow
er F
acto
r Reg
ulat
or
L1L2L3N
380~415 V AC
1615
14
13 AUXVOLTAGE
For 220~240 V AC Model Only
220~240 V AC
LOAD
Typical Application Diagram
Case Dimensions Ordering Information144 mm
138 mm
138
mm
76 mm90 mm
144
mm
Front
Side
PanelCutout
MODEL
PFR60-415-50
PFR80-415-50
PFR120-415-50
PFR140-415-50
PFR60-220-50
PFR80-220-50
PFR120-220-50
PFR140-220-50
PFR60-415-60
PFR80-415-60
PFR120-415-60
PFR140-415-60
PFR60-220-60
PFR80-220-60
PFR120-220-60
PFR140-220-60
DESCRIPTION
6 Steps, 50 Hz system, auxiliary voltage 380~415 V AC
8 Steps, 50 Hz system, auxiliary voltage 380~415 V AC
12 Steps, 50 Hz system, auxiliary voltage 380~415 V AC
14 Steps, 50 Hz system, auxiliary voltage 380~415 V AC
6 Steps, 50 Hz system, auxiliary voltage 220~240 V AC
8 Steps, 50 Hz system, auxiliary voltage 220~240 V AC
12 Steps, 50 Hz system, auxiliary voltage 220~240 V AC
14 Steps, 50 Hz system, auxiliary voltage 220~240 V AC
6 Steps, 60 Hz system, auxiliary voltage 380~415 V AC
8 Steps, 60 Hz system, auxiliary voltage 380~415 V AC
12 Steps, 60 Hz system, auxiliary voltage 380~415 V AC
14 Steps, 60 Hz system, auxiliary voltage 380~415 V AC
6 Steps, 60 Hz system, auxiliary voltage 220~240 V AC
8 Steps, 60 Hz system, auxiliary voltage 220~240 V AC
12 Steps, 60 Hz system, auxiliary voltage 220~240 V AC
14 Steps, 60 Hz system, auxiliary voltage 220~240 V AC
Power Factor Regulator
PFR 140 / 120 / 80 / 60
Technical Data
RATINGS AUXILIARY POWER SUPPLYModel PFR96 : 110 ~ 120 V AC / 220 ~ 240 V ACModel PFR96P : 380 ~ 415 V ACOperatingLimits :-15%+10%Consumption : 10 VA maxRated frequency : 50 Hz or 60 Hz
OUTPUT CONTACTSNumbers of outputs : 6Rated voltage : 250 V ACContact rating : 5 AExpected electrical life : 100,000 operations at
rated currentExpected mechanical life : 5 x 106 operationsMax current for the common terminals : 12 A continuous
CURRENT INPUTRated current ( In ) : 5 AOperating Limits : 0.15 A to 6.5 ARated frequency : 50 Hz or 60 Hz
CONTROL RANGEPowerfactorsetting :0.8Ind-0.8CapC/Ksetting :0.03-1.20/AutomaticSwitchingsensitivity :5-600s/stepReconnection time for samestep :5-240sSwitching Program : Automatic / Automatic
ENVIRONMENTAL CONDITIONSTemperature :-5˚Cto+55˚CHumidity : 56 days at 93% RH and
40˚Cnon-condensing
MECHANICALMounting : Panel mountingDimension (mm) : 96(w) x 96(h) x 90(d)Approximateweight :0.6kg
For PFR 96• Forsingle-phasesystem
For PFR 96P• For3-phasesystem
Power Factor Regulator
PFR 96 / 96P
K1 K6K5
FUSE
Pow
er F
acto
r Re
gula
tor
VOLTAGE380~415V AC
MAINL1L2L3N
8
7
6
5
4
3
2
1
CURRENT/ 5 A
6
5
4
3
2
1
16
15
14
13
12
11
10
9P2
P1
FUSE
LOAD
K1 K6K5
FUSE
FUSE
Pow
er F
acto
r Re
gula
torVOLTAGE
220 V AC /110 V AC
MAINL1L2L3N
8
7
6
5
4
3
2
1
CURRENT/ 5 A
6
5
4
3
2
1
16
15
14
13
12
11
10
9P2
P1
LOAD
Typical Application Diagram
Ordering Information
Diagram 2 - For model PFR96PDiagram 1 - For model PFR96
Case Dimensions96 mm
91.0 ± 0.5 mm
91.0
± 0
.5 m
m
70 mm90 mm
96m
m Front
Side
PanelCutout
MODEL
PFR96 - 220 - 50
PFR96 - 220 - 60
PFR96 - 110 - 50
PFR96 - 110 - 60
PFR96P - 415 - 50
PFR96P - 415 - 60
DESCRIPTION
6 Steps, for 50 Hz system, auxiliary voltage 220~240 V AC
6 Steps, for 60 Hz system, auxiliary voltage 220~240 V AC
6 Steps, for 50 Hz system, auxiliary voltage 110~120 V AC
6 Steps, for 60 Hz system, auxiliary voltage 110~120 V AC
6 Steps, for 50 Hz system, auxiliary voltage 380~415 V AC
6 Steps, for 60 Hz system, auxiliary voltage 380~415 V ACPow
er Factor RegulatorPFR 96 / 96P
Typical Application Diagram
Power Factor Regulator
PFR LCD
PFRLCDFeatures• 2” inch, 64 x 128 dot matrix LCD display
withbacklighting
• Three phase and single phase detection of reactive power
• 12 (or 8 for 8 step model) output with two additional
• Independent contact for signal alarm output and fan output
• Three phase compensation mode
• 5 different switching program
• Automatic detection of C/K and rated step value
• No Voltage release
• Variousconfigurablealarmsettings
• Alarmlinkedsignalcontact
• Programmable fan control
• ModBus-RTUcommunication
• Active, reactive, apparent power
• Temperature
• Phase voltage and phase current
• Frequency
• Up till 31st order Harmonics measurement in graphical and table format
• Power Factor and Displacement Power Factor (Cosφ)
Measurement Parameters
L1 L2 NL3
3435
3344
3243
4241
3938
3736
40
2120
2214
2313
1211
98
76
104
32
15
SIGFAN
12
45
67
39
1011
128
2430 Thermistor
T1
P+
N-RP
T2
31
GND
PFR
LC
D
FANSIG
AUX
NL
S2S2
S1S1
S2S1
L3L2
L1N
CT2
CT1
CT3
RS485 Modbus-RTU
FUSE
FUSE
P1P2
P1P2 P1
P2
K12 K2 K1
PFRLCD120P3-230-50
LOAD
L1 L2 NL3
3435
3344
3243
4241
3938
3736
40
2120
2214
2313
1211
98
76
104
32
15
SIGFAN
12
45
67
39
1011
128
2430 Thermistor
T1
P+
N-RP
T2
31
GND
PFR
LC
D
FANSIG
AUX
NL
Out
InL3
L2L1
NC
T1
RS485 Modbus-RTU
FUSE
FUSE
P1P2
K12 K2 K1
PFRLCD120P1-230-50
LOAD
PFRLCD Connection diagram for 3 Phase 12 Step model PFRLCD Connection diagram for 1 Phase 12 Step model
Ordering Information
Case Dimensions
Front View
Panel Cutout
144mm
Side View
122mm102mm
144m
m
138mm
138mm
Power Factor Regulator
Technical DataCURRENT INPUT (EACH PHASE)Nominal Current : 5 A rmsOperatingLimits :0.01-10ArmsRated frequency : 50 Hz or 60 Hz
VOLTAGE INPUT (EACH PHASE with respect to neutral)Nominal Voltage : 230 VrmsOperatingLimits :0-277VL-NConsumption : 0.05 VARated Frequency : 50 Hz or 60 HzCatagory : III
THERMISTOR INPUT Thermistor Temperature range : 0 – 100 °C
AUXILIARYAuxiliaryInputVoltageRange :85-265VrmsConsumption : 10 VA maxRated Frequency : 50 Hz or 60 Hz
OUTPUT CONTACTSNumber of outputs : 14 (model dependent)Rated voltage : 250 V ACContact rating : 5 AExpected electrical life : 100,000 operations at
rated currentExpected mechanical life : 5 x 106 operations
CONTROL RANGETarget Power factor : 0.80 Inductive – 0.80
Capacitive C/K setting : 0.03 – 1.20 / Automatic
detectSensitivity :5-300s/StepReconnection time : 5 – 240s Switching program : Automatic/ Manual/
ALARM SETTING RANGE%THDI :20-300%/OFFOver Voltage : 253 – 264 V/ OFFUnder Voltage : 195 – 204 V/ OFFOver Current : 5.50 – 7.00 A/ OFFUnder Current : 0.01 – 0.15 A/ OFFUnder Compensate : On / OFFOver Compensate : On / OFF*CT Polarity Error : On / OFFStep Error : On / OFFTemperature : 36 – 70 °C / OFF
DISPLAY %THDI & %THDV : 0 – 500%Harmonics Resolution : Up till 31st Harmonics Active power : 0– 3000 WReactive power : 0 – 3000 VARApparent power : 0 – 3000 VAVoltage : 0 – 300 VACCurrent : 0.00 – 10.0 A rmsTemperature : 0 – 100 °CFrequency : 45 – 65HzPowerFactor :-1.00–1.00DisplacementPowerFactor:-1.00–1.00
ENVIRONMENT CONDITIONSTemperature :-5°Cto+55°CHumidity : 56 days at 93%RH and
40°Cnon-condensingPollution Degree : IIDielectricWithstand :IEC61010-1Altitude : 2000 m
ELECTROMAGNETIC COMPATIBILITY (EMC)Part6-2:Genericstandards :IEC61000-6-2Immunity for industrial environmentsPart6-4:Genericstandards :IEC61000-6-4Emission standard for industrial environments
MECHANICAL Mounting : Panel mountingDimension (mm) : 144(w) x 144(h) x 122(d)Enclosure protection : IP54 at the panel IP20 at the bodyApproximateweight :1.2kg (for three phase model), 1kg (for single phase model)
MODEL
PFRLCD120P3-230-50
PFRLCD80P3-230-50
PFRLCD120P1-230-50
PFRLCD80P1-230-50
PFRLCD120P3-230-60
PFRLCD80P3-230-60
PFRLCD120P1-230-60
PFRLCD80P1-230-60
DESCRIPTION
12 Step, 3 Phase, 230Vrms, 50Hz Model
8 Step, 3 Phase, 230Vrms, 50Hz Model
12 Step, 1 Phase, 230Vrms, 50Hz Model
8 Step, 1 Phase, 230Vrms, 50Hz Model
12 Step, 3 Phase, 230Vrms, 60Hz Model
8 Step, 3 Phase, 230Vrms, 60Hz Model
12 Step, 1 Phase, 230Vrms, 60Hz Model
8 Step, 1 Phase, 230Vrms, 60Hz Model
PFR LCD
Tests And StandardsElectrostaticdischargeIEC61000-4-2,ClassIII,airdischarge 8KVElectrostaticdischargeIEC61000-4-2,ClassIII,contactdischarge 6KVElectricalfasttransientIEC61000-4-4 4KV,5/50nsSurgeimmunityIEC61000-4-5 4KV,LtoEEnclosure protection when panel mounted Front: IP41 Enclosure: IP30
AN112AN120AN128
AnnunciatorAN 112 / 120 / 128
Features• 12,20or28windows.Replaceablesuper-
bright LED modules, with choice of amber or red illumination
• 11AlarmSequencesasperISA-18.1standard
• Eachchannel/windowfullyfieldprogrammable,eitherfromfrontpanelbuilt-inpushbutton or using PC
• Repeatrelayforeachwindowaswellasnumerousconfigurablemultifunctionoutputrelays for connection to external equipment to form alarm management system
• Sleeporunattendedmodefeatureisavailable,for stations not permanently manned
• Auto-silenceandauto-acknowledgefeatures,with delay settable from 1 – 255 s
• Otheramountofwindowsavailableuponrequest.
The AN112/120 series Alarm Annunciator provides ideal solution for all your alarm system management and requirement. It comes with either 12, 20 or 28 windows, andduetotheuseofmicroprocessor-baseddesign,thealarmannunciatorishighlyflexibleintermsoffunctionalityandprogrammability,suitableforallapplicationand industries.
Programmable Alarm Annunciator
Technical Data
WINDOWWindow Dimension : 50 x 30 mm.Type: White translucent lens.Colours: Red, Amber. Coloured
CT RATINGSRatedcurrent : 2-10ARated frequency : 50 Hz or 60 HzBurden : <0.3 VA at rated currentThermal withstand : Continuous : 2x max rated 45s : 6x max rated 1s : 10x max rated
BINARY INPUTRated input voltage : 12V (Supplied internally)
AUXILIARY SUPPLYModelMPR500-240AD :85~265VAC 110 ~ 370 V DCSupply frequency : 50 or 60 HzMaximum power consumption : 3 VA typical
OUTPUT CONTACTSRated voltage : 250V ACContact rating : 5 AExpected electrical life : 100,000 operations at
rated currentExpected mechanical life : 5 x 106 operations