1MR
K 5
11 2
22-S
US
Cop
yrig
ht 2
006
AB
B. A
ll rig
hts
rese
rved
. Im
agen
eerin
g 3/
2009
MicroSCADA Pro SYS 600CThe Compact System
Substation Automation Products
-
Power automation with industrial design
The Compact System, SYS 600C provides proven MicroSCADA Pro
functionality for real-time monitoring and control of primary and
secondary equipment. Robust and compact, it offers an ideal
solution for harsh and demanding environments in both transmission
and distribution substations. Depend on it whenever real-time
process information as well as state-of-the-art monitoring and
control capabilities are crucial.
The MicroSCADA Pro SYS 600C does not contain moving or otherwise
vulnerable parts. With high scalability and modern architecture, it
is easy to adapt and expand: You can enjoy its ease of use as a
communication gateway, as a control system HMI or communication
server in both industrial and electrical utility applications.
Pre-configured from the factoryThe SYS 600C is delivered from
the factory with tested and pre-installed software, containing an
order-specific configura-tion. With the help of the ready-to-use
library of symbols and control dialogs, the SYS 600C requires only
minimal engi-neering before installation and commissioning. In
addition, copy and paste functions allow, for instance, easy system
extension. This way, the MicroSCADA Pro SYS 600C ensures efficient
engineering and system integration.
Right actions at the right time The operator interface of the
MicroSCADA Pro SYS 600C enables you to easily and safely interact
with the process, via protection and control IEDs (Intelligent
Electronic Device), RTUs or other types of sensors. As a result,
your MicroSCADA Pro SYS 600C will effectively help you take the
right actions and achieve the maximum power system
avail-ability.
2
-
3The high availability can be further secured by using
redun-dant SYS 600C computers, redundant power supplies, as well as
by the support for redundant communication.
IEC 61850 compliantThe MicroSCADA Pro SYS 600C is compliant with
the IEC 61850 standard for substation automation. This means that
it can operate together with IEC 61850-compliant IEDs, tools and
systems, which simplifies system engineering. With IEC 61850
support, the MicroSCADA Pro SYS 600C creates seamless communication
and connectivity opportunities for its users.
Seamless integration and connectivityThe MicroSCADA Pro SYS 600C
ensures optimized control and reliable operation of your switchyard
through the seam-less integration and connectivity between
different devices and systems. SYS 600C also supports an extensive
range of standard and de facto standard communication protocols and
interfaces.
Application areasCommunication GatewayThe MicroSCADA Pro SYS
600C provides a scalable commu-nication gateway solution, including
support for a Hot Stand-by configuration. The communication gateway
functionality provides mapping of data and signals between the
various substation equipment and upper level system. It features a
wide selection of communication protocols and interfaces and is
thus open for any master system (SCADA or DCS systems). It further
offers versatile connection to IEDs through both standard and de
facto standard communication protocols.
Control System HMI The MicroSCADA Pro SYS 600C is also designed
to be used as a complete control system HMI to enable smooth
monitor-ing and control of the connected process in both
transmission and distribution substations. One SYS 600C computer is
capable of accommodating both a full fledged control system HMI and
a communication gateway, including Hot Stand-by configuration.
Communication ServerIn SCADA applications, MicroSCADA Pro SYS
600C offers an excellent solid state Front-End solution with
support for Hot Stand-by configuration. The large number of master
commu-nication protocols enables easy connection to RTUs, gate-ways
and other process interface units.
-
SYS 600C EMI/EMS and Environmental Type Test report
4
STANDARD COMPLIANCE TYPE TEST DESCRIPTION SEVERITY LEVEL
IEC61850-3
IEC 61000-4-2-2001 Electrostatic Discharge Level 4 - 8KV
Contact/15KV Air
IEC 61000-4-3-2006 Radiated RF Succeptibility Level 3 - 18V/m, 6
directions
IEC 61000-4-4-2004 Fast Transient (Burst Immunity)Level 4 - 4KV
5KHz Power Supply Line/2KV 5KHz Signal Line
IEC 61000-4-5-2005 Surge Immunity Level 4 4KV line-to-earth/2KV
line-to-line
IEC 61000-4-6-2006 Conducted RF Immunity Level 3 - 10Vrms
IEC 61000-4-8-2001 Magnetic Field Immunity Level 5 - 100A/m
5min/1000A/m 1s
IEC 61000-4-10-1993 Damped Magnetic Immunity Level 4 - 30A/m
IEC 61000-4-12-1995 Damped Oscillatory BurstLevel 3 - 2.5KV
common/Differential 1.25KV for Substation
IEC 61000-4-16-2002 Conducted RF Immunity Level 3 - 15Hz ~
150KHz
IEC 61000-4-29-2000 Voltage Dips & Interrupts 30% 120ms/ 70%
10ms 100% 3ms (cycle 3)
CISPR22-2008Conducted and Radiated Emissions
Class A
FCC 15Conducted and Radiated Emissions
Class A
EN55022AConducted and Radiated Emissions
Class A
IEC 60255-5Insulation resitance measurement
500VDC, 1min, 999Mohm>100Mohm
IEC 60255-27 Protective bonding resistance 25Amps, 1min,
0.021ohm
-
Main Control Center
Application examples
5
Communication GatewayCommunication Gateway
Remote Access
Office Access
SYS 600C
SYS 600C
SYS 600CSYS 600C
SYS 600C
SYS 600C
Hardware characteristics
CPU Intel Core 2 Duo 2,2GHz
Memory 2GB DDR2 memory
Storage device 1 x Compact Flash 16GB
Expansion slot 3 x PCI v2.3 slots
Serial port 16 x RS232 serial ports at rear panel
LAN port6 x Gigabit Ethernet (RJ45 or LC) at rear panel1 x
Gigabit Ethernet at front panel (RJ45)
USB2 x USB 2.0 at rear panel1 x USB 2.0 at front panel1 x USB
2.0 internal
Power Supply88-132VAC/45-160VDC176-264VAC/200-370VDCRedundant
power supply is optional
Dimensions3U height, 19 rack mountable438W x 130H x 312D mm
(excluding rack mount accessories)
Temperature
Operating temperature -30C - +65C (-22 - 149 F)Maximum
continuous CPU burden 50% of lowest/highest operating
temperatureStorage temperature -40C - +75C (-40 - 167 F)
Humidity 5% - 95% (+40C) non-condensing
Protection class IP40
Software functions and features
Controlandmonitoringoftheprimaryprocess
Singlelinediagramwithbusbarcoloring
Alarm/event/blockinglists
Trends
Systemsupervision
Settingofrelayparameters
Uploadingandevaluationofdisturbancerecordfiles
Power-qualitymonitoring
Dataconcentrationandsignalgrouping
SolutionlibrariesforefficientintegrationofABBsSubstation
Automation IEDs
Standardsolutionsandopeninterfacesandprotocolsfor
integration of 3rd party IEDs
Adaptationtocustomer-specificrequirements:displays,signal
handling etc.
Integratedon-lineconfigurationtools
GPStimesynchronization
Versatilelanguagesupport,includingoperator-specificlanguages
Extensivemulti-leveluser-authorizationhandling
Highperformanceandavailability
Remoteworkstations(alsoweb-based)
MicrosoftWindowsoperatingsystems
Masterprotocols:LON,SPA,IEC61850-8-1,IEC60870-5-101,
IEC 60870-5-103, IEC 60870-5-104, RP 570/571,
DNP 3.0 Serial/LAN, Modbus RTU, Modbus TCP/IP, I35/P214,
ADLP 180, RCOM
Slaveprotocols:IEC60870-5-101,IEC60870-5-104,
DNP 3.0 Serial/LAN, RP 570/571
Openinterfaces:OPCDAandA&Eclientandserver,ODBCclient,
Application programming interfaces for application &
communication
extensions
SystemperformanceverifiedattheABBSystemVerificationCenter
Communication Gateway and Control System HMI
Redundant Communication Gateway with Integrated Control System
HMI
-
Contact us
1MR
S 7
5683
3
Cop
yrig
ht 2
006
AB
B. A
ll rig
hts
rese
rved
. Im
agen
eerin
g 10
/200
9
Software functions and features
Controlandmonitoringoftheprimaryprocess
Singlelinediagramwithbusbarcoloring
Alarm/event/blockinglists
Trends
Systemsupervision
Settingofrelayparameters
Uploadingandevaluationofdisturbancerecordfiles
Power-qualitymonitoring
Dataconcentrationandsignalgrouping
SolutionlibrariesforefficientintegrationofABBsSubstation
Automation IEDs
Standardsolutionsandopeninterfacesandprotocolsfor
integration of 3rd party IEDs
Adaptationtocustomer-specificrequirements:displays,signal
handling etc.
Integratedon-lineconfigurationtools
GPStimesynchronization
Versatilelanguagesupport,includingoperator-specificlanguages
Extensivemulti-leveluser-authorizationhandling
Highperformanceandavailability
Remoteworkstations(alsoweb-based)
MicrosoftWindowsoperatingsystems
Masterprotocols:LON,SPA,IEC61850-8-1,IEC60870-5-101,
IEC 60870-5-103, IEC 60870-5-104, RP 570/571,
DNP 3.0 Serial/LAN, Modbus RTU, Modbus TCP/IP, I35/P214,
ADLP 180, RCOM
Slaveprotocols:IEC60870-5-101,IEC60870-5-104,
DNP 3.0 Serial/LAN, RP 570/571
Openinterfaces:OPCDAandA&Eclientandserver,ODBCclient,
Application programming interfaces for application &
communication
extensions
SystemperformanceverifiedattheABBSystemVerificationCenter
ABB ABSubstation Automation ProductsP.O. Box 699FI-65101 VAASA,
FinlandTel. +358 10 22 11Fax +358 10 22 41094
www.abb.com/substationautomation