  • Technical Guide P12y/EN T04/A11

    MiCOM P125/P126/P127

    CHAPTER 4Technical Data and

    Characteristic Curves

  • Technical Guide P12y/EN T04/A11Technical Data CHAPTER 4MiCOM P125/P126/P127 Page 1/40

    CONTENTS

    1. RATINGS 3

    1.1 Power supply 3

    1.2 Frequency 3

    1.3 Current Inputs 3

    1.4 Voltage Inputs 4

    1.5 Logic inputs 4

    1.6 Output relay contacts 4

    2. HIGH VOLTAGE WITHSTAND 5

    3. ELECTRICAL ENVIRONMENT 5

    4. ENVIRONMENT 5

    5. PROTECTION ACCURACY 6

    6. AUTOMATION FUNCTIONS ACCURACY TIMERS 8

    7. MEASUREMENT ACCURACY 8

    8. PROTECTION SETTING RANGES 9

    8.1 [67/50/51] Directional/non directional phase Overcurrent (P127 only) 9

    8.1.1 Synchronous polarisation 9

    8.1.2 Protection setting ranges (Only P127) 9

    8.2 [50/51] Phase Overcurrent Protection (P126 Only) 10

    8.2.1 Protection setting ranges (Only P126) 10

    8.3 [67N/50N/51N] Neutral/Ground/Earth Directional/non Directional EarthOvercurrent Protection (P125, P126 & P127) 10

    8.3.1 Protection setting ranges 11

    8.4 Earth Wattmetric Protection (P125, P126 & P127) 13

    8.5 Functionality mode 13

    8.5.1 Protection setting ranges 13

    8.6 Undercurrent protection (P126 & P127 only) 15

    8.6.1 Protection setting ranges 15

    8.7 Negative sequence overcurrent protection (P126 & P127 only) 15

    8.7.1 Protection Setting Ranges 15

    8.8 Thermal overload protection (P126 & P127 only) 15

    8.8.1 Protection setting ranges 15

  • P12y/EN T04/A11 Technical GuideCHAPTER 4 Technical DataPage 2/40 MiCOM P125/P126/P127

    8.9 Under Voltage protection (P127 only) 16

    8.9.1 Protection setting ranges (only P127) 16

    8.10 Over Voltage protection (P127 only) 17

    8.10.1 Protection setting ranges (only P127) 17

    8.11 Residual Over Voltage protection (P125, P126 & P127) 18

    8.11.1 Protection setting ranges 18

    8.12 Multishot Autorecloser function (P126 & P127) 18

    8.12.1 Multishot Autorecloser settings 19

    9. AUTOMATION CONTROL FUNCTIONS 20

    9.1 Cold load pickup (P126 & P127) 20

    9.2 Auxiliary timers (P126 & P127) 20

    9.3 Broken conductor detection (P126 & P127) 20

    9.3.1 Broken conductor detection setting ranges 20

    9.4 Circuit breaker failure (P126 & P127) 20

    9.4.1 CB Fail setting ranges 20

    9.5 Trip circuit supervision (P126 & P127) 20

    9.5.1 Trip circuit supervision setting ranges 20

    9.6 Circuit breaker control and monitoring (P126 & P127) 21

    9.6.1 Setting ranges 21

    9.7 AND logic equation (P126 & P127) 21

    9.7.1 Timer setting ranges 21

    10. RECORDING FUNCTIONS (P126 & P127) 22

    10.1 Event recorder 22

    10.2 Fault recorder 22

    10.3 Disturbance recorder 22

    10.3.1 Triggers; Data; Setting Ranges 22

    11. COMMUNICATION (P125, P126, P127) 23

    12. CURVES 24

    12.1 General 24

    12.1.1 Inverse Time Curves : 24

    12.1.2 Reset timer 25

    12.2 IDMT Curves 26

    12.2.1 IEC Curves 26

    12.2.2 RI Curves 32

    12.2.3 IEEE/ANSI CURVES 33

    12.3 Thermal overload curves 39

  • Technical Guide P12y/EN T04/A11Technical Data CHAPTER 4MiCOM P125/P126/P127 Page 3/40

    1. RATINGS

    1.1 Power supply

    Power Supply range 24-60Vdc48-150Vdc130-250Vdc / 100-250Vac 50/60Hz

    Power supply variations D.C. 20 %A.C. 20%, +10%

    Ripple 12%

    Power off withstand 50 ms

    Burden P125 Stand by:

  • P12y/EN T04/A11 Technical GuideCHAPTER 4 Technical DataPage 4/40 MiCOM P125/P126/P127

    1.4 Voltage Inputs

    Voltage input range 57 to 130V

    Operating range 0 to 260V (measuring range)

    Burden Resistive 44 kohm: 0.074W/57Veff0.38W/130Veff 1.54W/260Veff

    Thermal Withstand

    Continuous 260Vph - ph eff

    10 seconds 300Vph - ph eff

    Voltage input range 220 to 480V

    Operating range 0 to 960V (measuring range)

    Burden 438 kohm: 0.1102W/220Veff0.525W/480Veff2.1W/960Veff

    Thermal Withstand

    Continuous 960V ph-ph eff

    10 seconds 1300V ph-ph eff

    1.5 Logic inputs

    Logic input type Independent optically insulated

    Logic input burden 10 mA per input

    Logic input recognition time

  • Technical Guide P12y/EN T04/A11Technical Data CHAPTER 4MiCOM P125/P126/P127 Page 5/40

    2. HIGH VOLTAGE WITHSTAND

    Dielectric withstand IEC 60-255-5 2 kV common mode1 kV differential mode

    Impulse voltage IEC 60-255-5 5 kV common mode1 kV differential mode

    Insulation resistance IEC 60-255-5 > 1000 M

    3. ELECTRICAL ENVIRONMENT

    High frequency IEC 1000-4-1 2.5 kV common mode, class 3disturbance 1 kV differential mode, class 3

    Fast transient IEC 1000-4-4 4 4 kV auxiliary voltage, class 4ANSI C37.90.1 2 kV others, class4

    Electrostatic IEC 1000-4-2 8 kV, class 4discharge

    Radio frequency ANSI C37.90.2 35 V/mimpulse IEC 1000-4-3 10 V/m

    4. ENVIRONMENT

    Temperature IEC 60-255-6 Storage -25C to +70COperation -25C to + 55 C

    Humidity IEC 600-68-2-3 56 days at 93% RH and 40C

    Enclosure protection IEC 60-529 IP 52, IK 07

    Vibrations IEC 60-255-21-1 Response and endurance, class 2

    Shocks and bumps IEC 60-255-21-11 Response and withstand, class 1

    Seismic IEC 60-255-21-3 Class 1

  • P12y/EN T04/A11 Technical GuideCHAPTER 4 Technical DataPage 6/40 MiCOM P125/P126/P127

    5. PROTECTION ACCURACY

    Glossary

    I : Phase current

    Is : I>, I>> & I>>>

    I2s : I2>, I2>> & I2>>>

    Ies : Ie>, Ie>> & Ie>>>

    Iescos : Iecos> & Iecos>>

    Pe : Earth fault Power

    Pes : Pe> & Pe>>

    Us : U>, U>>, U>, Ue>>>, Ue>>>>

    DT : Definite time

    IDMT : Inverse time

    Element Range Accuracy Trigger Reset Time accuracy

    Phase OvercurrentelementsI> & I>> & I>>>

    0.1 to 40 In 2% DT: Is 2%IDMT: 1.1Is 2%

    0.95 Is 2%1.05 Is 2%

    2% +3050ms 5% +3050ms

    Relay CharacteristicAngle (Torque angle)

    0 to 359 2

    Trip zone 10 to 170 2

    Earth Fault OvercurrentelementsIe> & Ie>> & Ie>>>

    0.002 to 1Ien0.01 to 8 Ien0.1 to 40 Ien

    2% DT: Ies 2%IDMT: 1.1Ies 2%

    0.95 Ies 2%1.05 Ies 2%

    2% +3050ms 5% +3050ms

    Wattmetric Earth Faultelements

    57 to 130V0.2 to 20W1 to 160W10 to 800W

    4% erroron cos

    DT: Pes accuracyIDMT: 1.1Pes accuracy

    0.95 Pes accuracy1.05 Pes accuracy

    2% +3050ms

    5% +3050ms

    Wattmetric Earth FaultelementsPe> & Pe>>

    220 to 480V1 to 80W4 to 640W40 to 3200W

    4% erroron cos

    DT: Pes accuracyIDMT: 1.1Pes accuracy

    0.95 Pes accuracy1.05 Pes accuracy

    2% +3050ms

    5% +3050ms

    Active Earth faultovercurrent elements.Iecos> & Iecos>>

    0.002 to 1Ien0.01 to 8 Ien0.1 to 40 Ien

    2% erroron cos

    DT: Iescos accuracyIDMT: 1.1 Iescos accuracy

    0.95 Iescos accuracy1.05 Iescos accuracy

    2% +3050ms

    5% +3050ms

    Negative SequencePhase OvercurrentelementsI2>, I2>> & I2>>>

    0.1 to 40 In 2% DT: I2s 2%IDMT: 1.1I2s 2%

    0.95 Is 2%1.05 Is 2%

    2% +3050ms 5% +3050ms

    Phase Undercurrentelement I, Alarm, Trip

    0.10 to 3.2 In 3% DT: I> 3% 0.97 I>3% 2% +3050ms

  • Technical Guide P12y/EN T04/A11Technical Data CHAPTER 4MiCOM P125/P126/P127 Page 7/40

    Element Range Accuracy Trigger Reset Time accuracy

    Over voltageU> & U>>

    57 to 130V2 to 260V

    2% DT: Us 2% 0.95 Is 2% 2% +2040ms

    Over voltageU> & U>>

    220 to 480V10 to 960V

    2% DT: Us 2% 0.95 Is 2% 2% +2040ms

    Under voltageU< & U>, Ue>>>,Ue>>>>

    57 to 130V

    1 to 260V1 to 260V

    2% DT: Urs 2% 0.95 Urs 2% 2% +2040ms

    Residual Over voltage(Direct Input)Ue>, Ue>>, Ue>>>,Ue>>>>

    220 to 480V

    4 to 960V5 to 960V

    2% DT: Urs 2% 0.95 Urs 2% 2% +2040ms

    Derived Residual OvervoltageUe>, Ue>>, Ue>>>,Ue>>>>

    57 to 130V

    1 to 260V1 to 260V

    greater of 2%or 0.2V

    DT: Urs 2% 0.95 Urs 2% 2% +2040ms

    Derived Residual OvervoltageUe>, Ue>>, Ue>>>,Ue>>>>

    220 to 480V

    4 to 960V5 to 960V

    greater of 2%or 1V

    DT: Urs 2% 0.95 Urs 2% 2% +2040ms

  • P12y/EN T04/A11 Technical GuideCHAPTER 4 Technical DataPage 8/40 MiCOM P125/P126/P127

    6. AUTOMATION FUNCTIONS ACCURACY TIMERS

    Recloser timers tDs, tR, tI 2% +1030ms

    CB fail & CB monitoring timers 2% +1030ms

    Auxiliary timers t_AUX1 & t_AUX2 2% +1030ms

    Cold load Pick Up 2% +2040ms

    Programmable AND logic 2% +1030ms

    7. MEASUREMENT ACCURACY

    Measurement Range Accuracy

    Phase Current 0.1 to 40 In Typical 0.5% at In

    0.002 to 11Ien Typical 0.5% at Ien

    0.01 to 8 Ien Typical 0.5% at Ien

    Earth current

    0.1 to 40 Ien Typical 0.5% at Ien

    57 to 260V Typical 0.5% at UnVoltage

    220 to 960V Typical 0.5% at Un

    Active Power and Active Energy Reactive Power and Reactive Energy

    Cos Accuracy Sin Accuracy

    0.866 < 1.5% 0.866 < 3%

    0.5 < 3% 0.5 < 1.5%

  • Technical Guide P12y/EN T04/A11Technical Data CHAPTER 4MiCOM P125/P126/P127 Page 9/40

    8. PROTECTION SETTING RANGES

    8.1 [67/50/51] Directional/non directional phase Overcurrent (P127 only)

    Phase current Fundamental only

    Phase or phase to phase voltage Fundamental only

    Minimum voltage operating 0.6V

    8.1.1 Synchronous polarisation

    Minimum phase voltage fixed threshold enabling synchronous polarising:0.6V

    Synchronous polarising permanence time phase voltage thresholds:5s

    8.1.2 Protection setting ranges (Only P127)

    [67] Phase OC Setting Range

    I> No or DIR non DIR

    I> Current set 0.1 In 25 In 0.01 In

    Delay type DT or IDMT (IEC_STI, IEC_SI, IEC_VI,IEC_EI, IEC_LTI, C02, C08, IEEE_MI,IIEEE_VI, IEEE_EI, RI curve)

    I> Trip delay time 0 s 150s 0.01s

    I> TMS 0.025 1.5 0.025

    I> Reset char DT or IDMT

    I> RTMS 0.025 1.5 0.025

    I> tReset 0.00 s 100 s 0.01 s

    Interlock I> byI>>I>>>

    No or Yes

    I> Torque angle 0 359 1

    I> Trip zone 10 170 1

    I>> No or Yes or DIR

    I>> Current set 0.5 In 40 In 0.01 In

    I>> Trip delay time 0 s 150s 0.01s

    I>> Torque angle 0 359 1

    I>> Trip zone 10 170 1

    I>>> No or Yes or DIR

    I>>> Current set 0.5 In 40 In 0.01 In

    I>>>Trip delay time 0 s 150s 0.01s

    I>>> Torque angle 0 359 1

    I>>> Trip zone 10 170 1

  • P12y/EN T04/A11 Technical GuideCHAPTER 4 Technical DataPage 10/40 MiCOM P125/P126/P127

    8.2 [50/51] Phase Overcurrent Protection (P126 Only)

    Phase current Fundamental only

    8.2.1 Protection setting ranges (Only P126)

    [51] Phase OC Setting Range

    I> No or Yes

    I> Current set 0.1 In 25 In 0.01 In

    Delay type DT or IDMT (IEC_STI, IEC_SI, IEC_VI,IEC_EI, IEC_LTI, C02, C08, IEEE_MI,IIEEE_VI, IEEE_EI, RI curve)

    I> Trip delay time 0 s 150s 0.01s

    I> TMS 0.025 1.5 0.025

    I> Reset char DT or IDMT

    I> RTMS 0.025 1.5 0.025

    I> tReset 0.00 s 100 s 0.01 s

    Interlock I> byI>>I>>>

    No or Yes

    I>> No or Yes or DIR

    I>> Current set 0.5 In 40 In 0.01 In

    I>> Trip delay time 0 s 150s 0.01s

    I>>> No or Yes

    I>>> Current set 0.5 In 40 In 0.01 In

    I>>>Trip delay time 0 s 150s 0.01 s

    8.3 [67N/50N/51N] Neutral/Ground/Earth Directional/non Directional EarthOvercurrent Protection (P125, P126 & P127)

    Earth Current Fundamental only

    Earth current ranges See following table

    Residual voltage Fundamental only

    Residual voltage range See following table

    Minimum Residual voltage operation 1V (Uen: 57 to 130V)

    Minimum Residual voltage operation 3V (Uen: 220 to 480V)

  • Technical Guide P12y/EN T04/A11Technical Data CHAPTER 4MiCOM P125/P126/P127 Page 11/40

    8.3.1 Protection setting ranges

    [67N] Earth OC Setting Range

    High sensitivitycurrent set

    Cortec code P12-C-X---X

    Ie> 0.002 Ien 1 Ien 0.001 Ien

    Ie>> 0.002 Ien 1 Ien 0.001 Ien

    Ie>>> 0.002 Ien 1 Ien 0.001 Ien

    Med. sensitivitycurrent set

    Cortec code P12-B-X---X

    Ie> 0.01 Ien 1 Ien 0.005 Ien

    Ie>> 0.01 Ien 8 Ien 0.005 Ien

    Ie>>> 0.01 Ien 8 Ien 0.005 Ien

    Low sensitivitycurrent set

    Cortec code P12-A-X---X

    Ie> 0.1 Ien 25 Ien 0.1 Ien

    Ie>> 0.5 Ien 40 Ien 0.1 Ien

    Ie>>> 0.5 Ien 40 Ien 0.1 Ien

    Ie> No or Yes or DIR

    Delay type DT or IDMT (IEC_STI, IEC_SI, IEC_VI,IEC_EI, IEC_LTI, C02, C08, IEEE_MI,IIEEE_VI, IEEE_EI, RI curve)

    Ie> Trip delay time 0 s 150s 0.01s

    Ie> TMS 0.025 1.5 0.025

    Ie> Reset char DT or IDMT

    Ie> RTMS 0.025 1.5 0.025

    Ie> tReset 0.00 s 100 s 0.01 s

    Interlock Ie> byIe>>Ie>>>

    No or Yes

    Ie> Torque angle 0 359 1

    Ie> Trip zone 10 170 1

    Input residual voltage with range from 57 to 130V

    Ue> 1 V 260 V 0.1 V

    Input residual voltage with range from 220 to 480V

    Ue> 4 V 960 V 0.5 V

    Ie>> No or Yes or DIR

    Ie>> Trip delay time 0 s 150s 0.01s

    Ie>> Torque angle 0 359 1

    Ie>> Trip zone 10 170 1

    Ie>> tReset 0.00 s 100 s 0.01 s

    Input residual voltage with range from 57 to 130V

  • P12y/EN T04/A11 Technical GuideCHAPTER 4 Technical DataPage 12/40 MiCOM P125/P126/P127

    [67N] Earth OC Setting Range

    Ue>> 1 V 260 V 0.1 V

    Input residual voltage with range from 220 to 480V

    Ue>> 4 V 960 V 0.5 V

    Ie>>> No or Yes or DIR

    Ie>>>Trip delay time 0 s 150s 0.01s

    Ie>>> Torque angle 0 359 1

    Ie>>> Trip zone 10 170 1

    Ie>>> tReset 0.00 s 100 s 0.01 s

    Input residual voltage From 57 to 130V

    Ue>>> 1 V 260 V 0.1 V

    Input residual voltage From 220 to 480V

    Ue>>> 4 V 960 V 0.5 V

    ATTENTION : THE UE THRESHOLDS SETTING DEPEND ON THE ADOPTEDWIRING SCHEME. IN CONFIGURATION/GENERAL OPTIONMENU OF THE P127 RELAY YOU CAN SET THE VE INPUTDIRECTLY FROM A VT(I.E. FROM A DELTA VT) OR DERIVED FROMTHE MEASUREMENT OF THE THREE PHASE TO NEUTRALVOLTAGE (3VPN). IN THIS CASE THE UE IS CALCULATED AS:

    CUBUAxUUe

    ++=31

    THE SETTING OF THE UE THRESHOLDS MUST TAKE IN ACCOUNTTHE ABOVE FORMULA.

  • Technical Guide P12y/EN T04/A11Technical Data CHAPTER 4MiCOM P125/P126/P127 Page 13/40

    8.4 Earth Wattmetric Protection (P125, P126 & P127)

    Earth current Fundamental only

    Residual Voltage Fundamental only

    8.5 Functionality mode

    This protection can work in Pe or Iecos mode.

    8.5.1 Protection setting ranges

    [32N] Earth Wattmetric

    Setting range

    Mode Pe or Iecos

    High sensitivity: Current input from 0.002 to 1 Ien

    57130V Input voltage Cortec code: P12-CAX---X

    Pe> (*) 0.2 x k W 20 x k W 0.02 x k W

    Pe>> (*) 0.2 x k W 20 x k W 0.02 x k W

    220480V Input voltage Cortec code: P12-CBX---X

    Pe> (*) 1 x k W 80 x k W 0.1 x k W

    Pe>> (*) 1 x k W 80 x k W 0.1 x k W

    Med. sensitivity Current input from 0.01 to 8 Ien

    57130V Input voltage Cortec code: P12-BAX---X

    Pe> (*) 1 x k W 160 x k W 0.1 x k W

    Pe>> (*) 1 x k W 160 x k W 0.1 x k W

    220480V Input voltage Cortec code: P12-BBX---X

    Pe> (*) 4 x k W 640 x k W 0.5 x k W

    Pe>> (*) 4 x k W 640 x k W 0.5 x k W

    Low sensitivity Current input from 0.1 to 40 Ien

    57130V Input voltage Cortec code: P12-AAX---X

    Pe> (*) 10 x k W 800 x k W 1 x k W

    Pe>> (*) 10 x k W 800 x k W 1 x k W

    220480V Input voltage Cortec code: P12-ABX---X

    Pe> (*) 40 x k W 3200 x k W 5 x k W

    Pe>> (*) 40 x k W 3200 x k W 5 x k W

    Pe> No or Yes

    Delay type DT or IDMT (IEC_STI, IEC_SI, IEC_VI,IEC_EI, IEC_LTI, C02, C08, IEEE_MI,IIEEE_VI, IEEE_EI,RI curve)

    tPe> Trip delay time 0 s 150s 0.01s

    Pe> TMS 0.025 1.5 0.025

    Pe> Reset char DT or IDMT

    Pe> RTMS 0.025 1.5 0.025

  • P12y/EN T04/A11 Technical GuideCHAPTER 4 Technical DataPage 14/40 MiCOM P125/P126/P127

    [32N] Earth Wattmetric

    Pe> tReset 0.00 s 100 s 0.01 s

    Pe>> No or Yes

    tPe>> Trip delay time 0 s 150 s 0.01 s

    Pe>> tReset 0.00 s 100 s 0.01 s

    High sensitivity Iecos Cortec code P12-C-X---X

    IeCos> 0.002 Ien 1 Ien 0.001 Ien

    IeCos>> 0.002 Ien 1 Ien 0.001 Ien

    Med. sensitivity Iecos Cortec code P12-B-X---X

    IeCos> 0.01 Ien 8 Ien 0.005 Ien

    IeCos>> 0.01 Ien 8 Ien 0.005 Ien

    Low sensitivity Iecos Cortec code P12-A-X---X

    IeCos> 0.1 Ien 25 Ien 0.01 Ien

    IeCos>> 0.5 Ien 40 Ien 0.01 Ien

    IeCos> Yes or No

    Delay type DT or IDMT (IEC_STI, IEC_SI, IEC_VI,IEC_EI, IEC_LTI, C02, C08, IEEE_MI,IIEEE_VI, IEEE_EI, RI curve)

    IeCos> Trip delay time 0 s 150s 0.01s

    IeCos> TMS 0.025 1.5 0.025

    IeCos> Reset type DT or IDMT

    IeCos> RTMS 0.025 1.5 0.025

    IeCos> tReset 0.00 s 100 s 0.01 s

    IeCos>> Yes or No

    IeCos>>Trip delay time 0 s 150s 0.01s

    IeCos> tReset 0.00 s 100s 0.01s

    Pe/IeCos Angle 0 359 1

    (*) ATTENTION : THE PE THRESHOLDS ARE DISPLAYED IN THE FORMAT: ##.## X K WTHE THRESHOLD VALUE WILL BE IN WATT SECONDARY.E.G. YOU ARE SETTING PE> THRESHOLD ON THE RELAY DISPLAY;YOU HAVE WRITTEN 20.IF IEN = 1A, THE INTERNAL RELAY SETTING VALUE WILL BE EQUAL TO20 X 1 = 20W.IF IEN = 5A, THE INTERNAL RELAY SETTING VALUE WILL BE EQUAL TO20 X 5 = 100W.

  • Technical Guide P12y/EN T04/A11Technical Data CHAPTER 4MiCOM P125/P126/P127 Page 15/40

    8.6 Undercurrent protection (P126 & P127 only)

    Undercurrent associated to the breaker failure function

    Phase current: Fundamental only

    8.6.1 Protection setting ranges

    [37] Under Current Setting ranges

    I< No or Yes

    I< 0.1 In 1 In 0.01 In

    tI< 0 s 150 s 0.01 s

    8.7 Negative sequence overcurrent protection (P126 & P127 only)

    Phase current: Fundamental only

    8.7.1 Protection Setting Ranges

    [46] Neg.Seq. OC Setting ranges

    I2> No or Yes

    I2> 0.1 In 25 In 0.01 In

    Delay type DT or IDMT (IEC_STI, IEC_SI, IEC_VI,IEC_EI, IEC_LTI, C02, C08, IEEE_MI,IIEEE_VI, IEEE_EI, RI curve)

    I2> Trip delay time 0 s 150s 0.01s

    I2> TMS 0.025 1.5 0.025

    I2> Reset char DT or IDMT

    I2> RTMS 0.025 1.5 0.025

    I2> tReset 0.04 s 100 s 0.01 s

    I2>> No or Yes

    I2>> Current set 0.5 In 40 In 0.01 In

    I2>> Trip delay time 0 s 150s 0.01s

    I2>>> No or Yes

    I2>>> Current set 0.5 In 40 In 0.01 In

    I2>>>Trip delay time 0 s 150s 0.01s

    8.8 Thermal overload protection (P126 & P127 only)

    Phase Current: RMS

    8.8.1 Protection setting ranges

    [49]Therm. OL Setting ranges

    Therm. OL No or Yes

    I 0.1 In 3.2 In 0.01Te 1 mn 200 mn 1mn

    k 1 1,5 0.01

    Trip 50% 200% 1% Alarm No or Yes Alarm 50% 200% 1%

  • P12y/EN T04/A11 Technical GuideCHAPTER 4 Technical DataPage 16/40 MiCOM P125/P126/P127

    8.9 Under Voltage protection (P127 only)

    Phase or phase to phase voltage Fundamental only

    Thresholds selection mode AND or OR (*)

    8.9.1 Protection setting ranges (only P127)

    [27] Phase Under Voltage

    Setting ranges

    57130V Inputvoltage.

    Cortec code: P127-AX---X

    U< No or AND or OR

    U< 2 V 130 V 0.1 V

    tU< 0 s 600 s 0.01 s

    U

  • Technical Guide P12y/EN T04/A11Technical Data CHAPTER 4MiCOM P125/P126/P127 Page 17/40

    8.10 Over Voltage protection (P127 only)

    Phase or phase to phase voltage Fundamental only

    Thresholds selection mode AND or OR (*)

    8.10.1 Protection setting ranges (only P127)

    [59] Phase Over Voltage

    Setting ranges

    57130V Inputvoltage.

    Cortec code: P127-AX---X

    U> No or AND or OR

    U> 2 V 260 V 0.1 V

    tU> 0 s 260 s 0.01 s

    U>> No or AND or OR

    U>> 2 V 260 V 0.1 V

    tU>> 0 s 600 s 0.01 s

    220480V Inputvoltage.

    Cortec code: P127-BX---X

    U> No or AND or OR

    U> 10 V 960 V 0.5 V

    tU> 0 s 600 s 0.01 s

    U>> No or AND or OR

    U>> 10 V 960 V 0.5 V

    tU>> 0 s 600 s 0.01 s

    (*) OR = trip caused by one or two or three phase start.AND = trip only caused by three phase start

  • P12y/EN T04/A11 Technical GuideCHAPTER 4 Technical DataPage 18/40 MiCOM P125/P126/P127

    8.11 Residual Over Voltage protection (P125, P126 & P127)

    Residual voltage: Fundamental only

    8.11.1 Protection setting ranges

    [59] Residual Over Voltage

    Setting ranges

    57130V Inputvoltage.

    Cortec code: P127-AX---X

    Ue>>>> No or Yes

    Ue>>>> 1 V 260 V 0.1 V

    TUe>>>> 0 s 600 s 0.01 s

    220480V Inputvoltage.

    Cortec code: P127-BX---X

    Ue>>>> No or Yes

    Ue>>>> 5 V 960 V 0.5 V

    tUe>>>> 0 s 600 s 0.01 s

    ATTENTION : THE UE THRESHOLDS SETTING DEPEND ON THE ADOPTEDWIRING SCHEME. IN CONFIGURATION/GENERAL OPTIONMENU OF THE P127 RELAY YOU CAN SET THE VE INPUTDIRECTLY FROM A VT(I.E. FROM A DELTA VT) OR DERIVED FROMTHE MEASUREMENT OF THE THREE PHASE TO NEUTRALVOLTAGE (3VPN). IN THIS CASE THE UE IS CALCULATED AS:

    CUBUAxUUe

    ++=31

    THE SETTING OF THE UE THRESHOLDS MUST TAKE IN ACCOUNTTHE ABOVE FORMULA.

    8.12 Multishot Autorecloser function (P126 & P127)

    Main shots 4 independent shots

    External logic inputs 6 inputs (CB opened signal, CB closedsignal, manual opening command, manual closing command, blocking order,cycle activation)

    Internal programmable trigger from phase and earth fault on all reclosingcycles

    External trigger from digital input.

    Inhibit time on manual closing.

    Programmable dead and reclaim time setting.

  • Technical Guide P12y/EN T04/A11Technical Data CHAPTER 4MiCOM P125/P126/P127 Page 19/40

    8.12.1 Multishot Autorecloser settings

    [79] Autoreclose Setting ranges

    Autoreclose Yes or No

    Ext. CB Fail Yes or No

    Ext. CB Fail time 0.01s 600s 0.01 s

    Ext. Aux1 ((I>) Yes or No

    Ext. Aux2 (Ie>) Yes or No

    Ext. Block Yes or No

    td1 Dead time 1 0.01 s 300 s 0.01 s

    td2 Dead time 2 0.01 s 300 s 0.01 s

    td3 Dead time 3 0.01 s 600 s 0.01 s

    td4 Dead time 4 0.01 s 600 s 0.01 s

    tR Reclain time 0.02 s 600 s 0.01 s

    Inhib Time tI 0.02 s 600 s 0.01 s

    Phase Cycle 0 4 1

    E/Gnd Cycle 0 4 1

  • P12y/EN T04/A11 Technical GuideCHAPTER 4 Technical DataPage 20/40 MiCOM P125/P126/P127

    9. AUTOMATION CONTROL FUNCTIONS

    9.1 Cold load pickup (P126 & P127)

    Cold Load Pick Up Setting ranges

    Level 100% 500% 1%

    tCL 0.1 s 3600 s 0.1 s

    9.2 Auxiliary timers (P126 & P127)

    Auxiliary timer 2 associated to the logic Inputs Aux 1, Aux2

    Auxiliary timers Setting ranges

    tAux1 0 200s 0.01s

    tAux2 0 200s 0.01s

    9.3 Broken conductor detection (P126 & P127)

    Principle used I2/I1

    9.3.1 Broken conductor detection setting ranges

    Broken Conductor Setting ranges

    Brkn.Cond Yes or No

    Brkn.Cond 20% 100% 1%

    Brkn.Cond Time 0 s 14400 s 1 s

    9.4 Circuit breaker failure (P126 & P127)

    9.4.1 CB Fail setting ranges

    CB Fail Setting ranges

    CB Fail Yes or No

    CB Fail Time tBF 0 s 10 s 0.01 s

    9.5 Trip circuit supervision (P126 & P127)

    9.5.1 Trip circuit supervision setting ranges

    TC Supervision Setting ranges

    TC Supervision Yes or No

    t Trip Circuit 0.1 s 10 s 0.1 s

  • Technical Guide P12y/EN T04/A11Technical Data CHAPTER 4MiCOM P125/P126/P127 Page 21/40

    9.6 Circuit breaker control and monitoring (P126 & P127)

    9.6.1 Setting ranges

    CB Supervision Setting ranges

    CB Open Svision Yes or No

    CB Open time 0.05 s 1 s 0.01 s

    CB Close Svision Yes or No

    CB Close time 0.05 s 1 s 0.01 s

    CB Open Alarm Yes or No

    CB Open NB 0 50000 1

    Amps(n) 0 E6 A 4000 E6A

    1E6 A

    n 1 2 1

    CB Open pulse Yes or No

    tOpen Pulse 0.1 s 5 s 0.1 s

    tClose Pulse 0.1 s 5 s 0.1 s

    9.7 AND logic equation (P126 & P127)

    For the AND logic equations a setting value 1 assigns the function to the equation, asetting value 0 does not assign the function to equation.

    9.7.1 Timer setting ranges

    AND LOGIC EQUATTdelay

    EQU. A Toperator 0 s 3600 s 0.1 s

    EQU. A Treset 0 s 3600 s 0.1 s

    EQU. B Toperator 0 s 3600 s 0.1 s

    EQU. B Treset 0 s 3600 s 0.1 s

    EQU. C Toperator 0 s 3600 s 0.1 s

    EQU. C Treset 0 s 3600 s 0.1 s

    EQU. D Toperator 0 s 3600 s 0.1 s

    EQU. D Treset 0 s 3600 s 0.1 s

  • P12y/EN T04/A11 Technical GuideCHAPTER 4 Technical DataPage 22/40 MiCOM P125/P126/P127

    10. RECORDING FUNCTIONS (P126 & P127)

    10.1 Event recorder

    Capacity 75 events

    Time-tag 1 millisecond

    Triggers Any selected protection alarm andthreshold

    Logic input change of state

    Setting changes

    Self test events

    10.2 Fault recorder

    Capacity 5 faults

    Time-tag 1 millisecond

    Triggers Any selected protection alarm andthreshold

    Data Fault date

    Protection thresholds

    Setting Group

    AC inputs measurements (RMS)

    Fault measurements

    10.3 Disturbance recorder

    10.3.1 Triggers; Data; Setting Ranges

    DisturbanceRecord

    P126 P127

    Triggers Any selected protection alarm and threshold, Logic input

    Remote command

    Data AC input channels

    Digital input and output states

    Frequency value

    Default value Setting ranges

    Pre-Time 2.5 2.5 0.1 3 0.1

    Post-Time 0.5 0.5 0.1 3 0.1

    Disturb rec Trig ON TRIP ON TRIP ON TRIP or ON INST.

  • Technical Guide P12y/EN T04/A11Technical Data CHAPTER 4MiCOM P125/P126/P127 Page 23/40

    11. COMMUNICATION (P125, P126, P127)

    TypePort

    Relayposition Physical Link Connectors Data Rate Protocol

    RS485 Rear port Screened twisterpair

    Screws orsnap-on

    300 to 38400 baud(programmable)

    ModBus RTU,Courier,IEC60870-5-103,DNP3

    RS232 Front port Screened twisterpair

    SubD 9 pinfemaleconnector

    300 to 38400 baud(programmable)

    ModBus RTU

  • P12y/EN T04/A11 Technical GuideCHAPTER 4 Technical DataPage 24/40 MiCOM P125/P126/P127

    12. CURVES

    12.1 General

    Although the curves tend towards infinite when the current approaches Is (generalthreshold), the minimum guaranteed value of the operating current for all the curveswith the inverse time characteristic is 1.1Is (with a tolerance of 0,05Is.

    12.1.1 Inverse Time Curves :

    The first phases (earth) overcurrent threshold can be selected with a dependent timecharacteristic. The time delay is calculated with a mathematical formula.

    In all, there are eleven inverse time characteristics available.

    The mathematical formula applicable to the first ten curves is :

    ( )

    +

    = LIIKTtS 1

    Where:

    t operation time

    K Coefficient (see table)

    I Value of measured current

    Is Value of the programmed threshold (Pick-up value)

    constant

    L ANSI/IEEE constant (zero for IEC curves)

    T Time Multiplier Setting

    Type of curve Standard K factor factor L factor

    Short Time Inverse ALSTOM 0.05 0.04 0

    Standard inverse IEC 0.14 0.02 0

    Very inverse IEC 13.5 1 0

    Extremely inverse IEC 80 2 0

    Long time inverse ALSTOM 120 1 0

    Short Time Inverse C02 0.02394 0.02 0.00169

    Moderately Inverse ANSI/IEEE 0.0515 0.02 0.114

    Long Time Inverse C08 5.95 2 0.18

    Very Inverse ANSI/IEEE 19.61 2 0.491

    Extremely Inverse ANSI/IEEE 28.2 2 0.1215

    The RI curve has the following definition:

    ( )IsIK = t

    236,0339,0

    1

  • Technical Guide P12y/EN T04/A11Technical Data CHAPTER 4MiCOM P125/P126/P127 Page 25/40

    K setting: from 0,10 to 10 in steps of 0,05.The equation is valid for 1.1 I/Is 20.

    12.1.2 Reset timer

    The first stage of the phase and earth overcurrent protections, negative sequenceovercurrent and wattmetric/IeCos are provided with a timer hold facility "t Reset".

    It may be set to a definite time value or to an inverse time characteristic (IEEE/ANSIcurves only). This may be useful in certain applications, for example when gradingwith upstream electromechanical overcurrent relays which have inherent reset timedelays.

    The second and third stages for the wattmetric/Iecos protection and earth faultovercurrent protection have a definite time reset.

    A possible situation where the reset timer may be used is to reduce fault clearancetimes where intermittent faults occur.

    An example may occur in a plastic insulated cable.

    In this application it is possible that the fault energy melts and reseals the cableinsulation extinguishing the fault.

    The permanence of the fault current pulses reduce intervals between the pulses untilthe fault becomes permanent.

    When the reset time of the relay is to minimum setting, the relay will be repeatedlyreset and not be able to trip until the fault becomes permanent. By using the resettimer hold facility the relay will integrate the fault current pulses, thereby reducingfault clearance time.

    The mathematical formula applicable to the five curves is:

    ( )

    =

    SIIKTt

    1

    Where:

    t : Reset time

    K : Coefficient (see table)

    I : Value of the measured current

    Is : Value of the programmed threshold (pick-up value)

    : Coefficient (see table)

    T : Reset Time Multiplier (Rtms) between 0.025 and 1.5.

    Type of curve Standard K factor factor

    Short Time Inverse C02 0.02394 2

    Moderately Inverse ANSI/IEEE 0.0515 2

    Long Time Inverse C08 5.95 2

    Very Inverse ANSI/IEEE 19.61 2

    Extremely Inverse ANSI/IEEE 28.2 2

  • P12y/EN T04/A11 Technical GuideCHAPTER 4 Technical DataPage 26/40 MiCOM P125/P126/P127

    12.2 IDMT Curves

    12.2.1 IEC Curves

  • Technical Guide P12y/EN T04/A11Technical Data CHAPTER 4MiCOM P125/P126/P127 Page 27/40

  • P12y/EN T04/A11 Technical GuideCHAPTER 4 Technical DataPage 28/40 MiCOM P125/P126/P127

  • Technical Guide P12y/EN T04/A11Technical Data CHAPTER 4MiCOM P125/P126/P127 Page 29/40

  • P12y/EN T04/A11 Technical GuideCHAPTER 4 Technical DataPage 30/40 MiCOM P125/P126/P127

  • Technical Guide P12y/EN T04/A11Technical Data CHAPTER 4MiCOM P125/P126/P127 Page 31/40

  • P12y/EN T04/A11 Technical GuideCHAPTER 4 Technical DataPage 32/40 MiCOM P125/P126/P127

    12.2.2 RI Curves

  • Technical Guide P12y/EN T04/A11Technical Data CHAPTER 4MiCOM P125/P126/P127 Page 33/40

    12.2.3 IEEE/ANSI CURVES

  • P12y/EN T04/A11 Technical GuideCHAPTER 4 Technical DataPage 34/40 MiCOM P125/P126/P127

  • Technical Guide P12y/EN T04/A11Technical Data CHAPTER 4MiCOM P125/P126/P127 Page 35/40

  • P12y/EN T04/A11 Technical GuideCHAPTER 4 Technical DataPage 36/40 MiCOM P125/P126/P127

  • Technical Guide P12y/EN T04/A11Technical Data CHAPTER 4MiCOM P125/P126/P127 Page 37/40

  • P12y/EN T04/A11 Technical GuideCHAPTER 4 Technical DataPage 38/40 MiCOM P125/P126/P127

  • Technical Guide P12y/EN T04/A11Technical Data CHAPTER 4MiCOM P125/P126/P127 Page 39/40

    12.3 Thermal overload curves

  • P12y/EN T04/A11 Technical GuideCHAPTER 4 Technical DataPage 40/40 MiCOM P125/P126/P127

    BLANK PAGE

    RATINGSPower supplyFrequencyCurrent InputsVoltage InputsLogic inputsOutput relay contacts

    HIGH VOLTAGE WITHSTANDELECTRICAL ENVIRONMENTENVIRONMENTPROTECTION ACCURACYAUTOMATION FUNCTIONS ACCURACY TIMERSMEASUREMENT ACCURACYPROTECTION SETTING RANGES[67/50/51] Directional/non directional phase Overcurrent (P127 only)[50/51] Phase Overcurrent Protection (P126 Only)[67N/50N/51N] Neutral/Ground/Earth Directional/non Directional Earth Overcurrent Protection (P125, P126 & P127)Earth Wattmetric Protection (P125, P126 & P127)Functionality modeUndercurrent protection (P126 & P127 only)Negative sequence overcurrent protection (P126 & P127 only)Thermal overload protection (P126 & P127 only)Under Voltage protection (P127 only)Over Voltage protection (P127 only)Residual Over Voltage protection (P125, P126 & P127)Multishot Autorecloser function (P126 & P127)

    AUTOMATION CONTROL FUNCTIONSCold load pickup (P126 & P127)Auxiliary timers (P126 & P127)Broken conductor detection (P126 & P127)Circuit breaker failure (P126 & P127)Trip circuit supervision (P126 & P127)Circuit breaker control and monitoring (P126 & P127)AND logic equation (P126 & P127)

    RECORDING FUNCTIONS (P126 & P127)Event recorderFault recorderDisturbance recorder

    COMMUNICATION (P125, P126, P127)CURVESGeneralIDMT CurvesThermal overload curves