Metropolitan Regional Housing Authority Tender No. MET19-115 Richmond Manor Generator ADDENDUM No. 3 June 25, 2019 The Tender Documents shall be amended and will become part of the Contract Documents. This addendum shall form an integral part of the Tender Documents. Part 1 AMENDMENTS 1) New, feeders and conduit system to the new, generator location shall be run wall mount instead of underground. Refer to the revised drawings set. 2) Electrical Specifications: Remove section 2.9. Junction / Pull Box. 3) Electrical Specifications: Add to section 2.3. Wires & Cables Use approved connectors to connect existing wiring with new wiring for safe electrical installation as per applicable CEC sections and AHJ regulations. Part 2 Revised drawings follow this page and form part of this addendum. The closing date and time remains the same. END OF ADDENDUM 19-115 ADDENDUM #3 Richmond Manor generator Page 1 of 8
10

Metropolitan Regional Housing Authority Tender No. MET19 ... · NEW CONCRETE PAD & FENCING CHECKED BY: SHEET NUMBER: DRAWN BY: PROJECT NO: SCALE NOVA SCOTIA PROJECT Property & Facilities

Oct 07, 2020

Download

Documents

dariahiddleston
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: Metropolitan Regional Housing Authority Tender No. MET19 ... · NEW CONCRETE PAD & FENCING CHECKED BY: SHEET NUMBER: DRAWN BY: PROJECT NO: SCALE NOVA SCOTIA PROJECT Property & Facilities

Metropolitan Regional Housing Authority

Tender No. MET19-115 Richmond Manor Generator

ADDENDUM No. 3

June 25, 2019

The Tender Documents shall be amended and will become part of the Contract Documents.

This addendum shall form an integral part of the Tender Documents.

Part 1

AMENDMENTS

1) New, feeders and conduit system to the new, generator location shall be run wallmount instead of underground. Refer to the revised drawings set.

2) Electrical Specifications: Remove section 2.9. Junction / Pull Box.

3) Electrical Specifications: Add to section 2.3. Wires & Cables – Use approvedconnectors to connect existing wiring with new wiring for safe electrical installationas per applicable CEC sections and AHJ regulations.

Part 2

Revised drawings follow this page and form part of this addendum.

The closing date and time remains the same.

END OF ADDENDUM

19-115 ADDENDUM #3 Richmond Manor generator Page 1 of 8

Page 2: Metropolitan Regional Housing Authority Tender No. MET19 ... · NEW CONCRETE PAD & FENCING CHECKED BY: SHEET NUMBER: DRAWN BY: PROJECT NO: SCALE NOVA SCOTIA PROJECT Property & Facilities

A-0R

AS NOTED1 OF 7ISSUED FOR TENDER

08/MAY/2019

NEW CONCRETE PAD & FENCING

CHECKED BY:

SHEET NUMBER:

DRAWN BY:

PROJECT NO:

SCALE

PR

OJE

CT

NOVA SCOTIAProperty & Facilities

RICHMOND MANOR

NEW GENERATOR INSTALLATION

5594 NORTH RIDGE RD., HALIFAX, N.S.

PF-2019-005

T. WARREN

M. CONRAD

08/MAY/2019DATE:

TENDER ADDENDUM24/JUNE/2019

19-115 ADDENDUM #3 Richmond Manor generator Page 2 of 8

AutoCAD SHX Text
Richmond Manor, Halifax
AutoCAD SHX Text
THE CONTRACTOR WILL PROVIDE A WORK PLAN TO THE PROJECT MANAGER THAT COORDINATES ELECTRICAL, GROUNDWORK, DISCONNECTS AND REACTIVATIONS AND ANY TEMPORARY MEASURES REQUIRED FOR THE WORK. THE PROJECT MANAGER SHALL REVIEW AND APPROVE THE WORK PLAN BEFORE ANY WORK COMMENCES. THE CONTRACTOR IS TO PROVIDE A WORK PLAN FOR TRANSPORTATION AND REMOVAL OF DEBRIS FROM SITE, CONFLICT OF WORK AREAS AND OCCUPIED TENANT AREAS, ENSURE MEANS OF EGRESS, AND TEMPORARY PROTECTION OF ADJACENT AREAS. THE PROJECT MANAGER SHALL REVIEW AND APPROVE THE WORK PLAN BEFORE ANY WORK COMMENCES.
AutoCAD SHX Text
ALL EXISTING PRODUCTS & WASTE MATERIALS REMOVED AS A RESULT OF THIS CONTRACT, ARE TO BE DISPOSED OF AS PER HRM GUIDELINES OFF SITE UNLESS OTHERWISE DIRECTED.
AutoCAD SHX Text
1)
AutoCAD SHX Text
2)
AutoCAD SHX Text
THE CONTRACTOR SHALL OBTAIN AND PAY FOR ANY AND ALL PERMITS AS REQUIRED BY THE AHJ, LOCAL CODES AND REGULATIONS, AND ARRANGE FOR REQUIRED INSPECTIONS. PROVIDE THE OWNER WITH ALL INSPECTION CERTIFICATES.
AutoCAD SHX Text
3)
AutoCAD SHX Text
ALL DIMENSIONS ARE IN IMPERIAL UNLESS OTHERWISE NOTED. IT IS THE CONTRACTORS RESPONSIBILITY TO CHECK AND VERIFY THAT ALL DIMENSIONS AND SIZES ARE CORRECT, AND TO REPORT IN WRITING ANY ERRORS OR OMISSIONS TO THE PROJECT MANAGER PRIOR TO PROCEEDING WITH THE WORK. DO NOT SCALE DRAWINGS.
AutoCAD SHX Text
4)
AutoCAD SHX Text
READ ALL DRAWINGS IN CONJUNCTION WITH ALL SPECIFICATIONS. APPROVED EQUIVALENTS ARE PERMITTED FOR BIDDING DURING THE TENDER PERIOD.
AutoCAD SHX Text
5)
AutoCAD SHX Text
IT IS NOT THE INTENTION OF THESE DRAWINGS AND SPECIFICATIONS TO REITERATE THE CODE. DO ALL WORK IN ACCORDANCE WITH ALL CURRENT APPLICABLE CODES AND IN COMPLIANCE WITH ALL REGULATIONS OF AUTHORITIES HAVING JURISDICTION INCLUDING, BUT NOT LIMITED TO THE NATIONAL BUILDING CODE CANADA, NOVA SCOTIA BUILDING CODE REGULATIONS, NATIONAL PLUMBING CODE, AND CANADIAN ELECTRICAL CODE. WHERE THERE IS A CONFLICT AMONGST REFERENCED SPECIFICATIONS, STANDARDS AND CODES, THE MOST STRINGENT WILL APPLY.
AutoCAD SHX Text
6)
AutoCAD SHX Text
ALL NEW MATERIALS, PRODUCTS AND ALL RELATED ACCESSORIES SHALL BE INSTALLED, AS PER SPECIFICATIONS, DRAWINGS AND MANUFACTURER SPECIFICATIONS. CONFLICTS BETWEEN DOCUMENTS SHALL BE REPORTED TO THE PROJECT MANAGER.
AutoCAD SHX Text
7)
AutoCAD SHX Text
GENERAL NOTES
AutoCAD SHX Text
Drawing Title
AutoCAD SHX Text
Cover Sheet
AutoCAD SHX Text
E-1
AutoCAD SHX Text
A-0
AutoCAD SHX Text
A-2
AutoCAD SHX Text
New Generator, Slab & Conduit Locations
AutoCAD SHX Text
A-1
AutoCAD SHX Text
New Concrete Pad & Fencing
AutoCAD SHX Text
GENERATOR REPLACEMENT
AutoCAD SHX Text
Existing Pad, Fence & Generator Removal
AutoCAD SHX Text
Existing Elec. Plan & Demolition
AutoCAD SHX Text
E-2
AutoCAD SHX Text
Proposed Electrical Plan & Schematic
AutoCAD SHX Text
E-3
AutoCAD SHX Text
Revised Electrical Schematic
AutoCAD SHX Text
S-201
AutoCAD SHX Text
Generator Pad - Engineering Dwgs
AutoCAD SHX Text
New Generator, Pad, Fencing & Electrical
Page 3: Metropolitan Regional Housing Authority Tender No. MET19 ... · NEW CONCRETE PAD & FENCING CHECKED BY: SHEET NUMBER: DRAWN BY: PROJECT NO: SCALE NOVA SCOTIA PROJECT Property & Facilities

CHECKED BY:

SHEET NUMBER:

DRAWN BY:

PROJECT NO:

SCALE

PR

OJE

CT

NOVA SCOTIAProperty & Facilities

RICHMOND MANOR

NEW GENERATOR INSTALLATION

5594 NORTH RIDGE RD., HALIFAX, N.S.

PF-2019-005

T. WARREN

M. CONRAD

08/MAY/2019

A-1R

AS NOTED2 OF 7ISSUED FOR CONSTRUCTION

08/MAY/2019

NEW GENERATOR, PAD & CONDUIT LOCATIONS

DATE:

3/16" = 1'-0"

NEW GENERATOR & SLAB

1

3/16" = 1'-0"

CONDUIT LOCATIONS

2

A

-

2

1

TENDER ADDENDUM24/JUNE/2019

19-115 ADDENDUM #3 Richmond Manor generator Page 3 of 8

AutoCAD SHX Text
EXISTING FUEL STORAGE TANK, SLAB & FENCE TO REMAIN
AutoCAD SHX Text
EXISTING GABION WALL
AutoCAD SHX Text
NEW DIESEL GENERATOR ON NEW CONCRETE BASE. CLEARANCE OF 915mm MINIMUM AROUND GENERATOR CABINET & A MINIMUM OF 1830mm FROM ANY BUILDING OPENING. (REFER TO PGS. E-1 TO E-3 FOR GENERATOR INFORMATION)
AutoCAD SHX Text
NEW GALVANIZED CHAIN LINK FENCE. FENCE SHALL BE 6'HIGH w/42" WIDE DOUBLE DOOR OPENING. POSTS SHALL BE MOUNTED TO CONCRETE SLAB w/BASE PLATES.
AutoCAD SHX Text
EXISTING GENERATOR & CONCRETE PAD
AutoCAD SHX Text
EXISTING FENCE
AutoCAD SHX Text
EXISTING GENERATOR, CONCRETE PAD, CHAIN LINK FENCE & CONCRETE SUPPORTS SHALL BE REMOVED
AutoCAD SHX Text
THIS WINDOW SHALL BE MADE INOPERABLE. WINDOW MUST BE PERMANENTLY SEALED SO TO NOT ALLOW ENTRANCE OF EXHAUST FROM GENERATOR..
AutoCAD SHX Text
NON-POROUS, WATER RESISTANT GASKET (min. 3/8" THICK) INSTALLED BETWEEN EXISTING BUILDING FOUNDATION AND NEW CONCRETE SLAB.
AutoCAD SHX Text
NEW CONCRETE SLAB. REFER TO DETAIL 1/A-2 & PG S-201 FOR CONSTRUCTION INFORMATION
AutoCAD SHX Text
SECTION OF FENCE AND GATE SHALL BE REPURPOSEDFROM SECTION REMOVED AROUND EXISTING GENERATOR. CONTRACTOR SHALL PROVIDE ANY ADDITIONAL PARTS REQUIRED TO JOIN FENCING SECTIONS.
AutoCAD SHX Text
1% SLOPE
AutoCAD SHX Text
1% SLOPE
AutoCAD SHX Text
3'-0" MINIMUM CLEARANCE BETWEEN GENERATOR AND FENCE
AutoCAD SHX Text
NOTE: ALL DISTURBED AREAS CAUSED BY NEW CONSTRUCTION OR REMOVAL OF FENCE & PAD SHALL BE REINSTATED & FINISHED WITH SOD-GRADE SOIL AND NEW GRASS SODS INSTALLED.
AutoCAD SHX Text
NEW CONDUITS (SEE ELECTRICAL FOR DETAILS) A - 1 1/2" RPVC B - 3/4" RPVC C - 3/4" RPVC CONDUIT SHALL BE SPACED min. 3" APART. CONDUIT SHALL BE INSTALLED BELOW WINDOWS AND AS CLOSE TO BOTTOM OF SIDING AS POSSIBLE.
AutoCAD SHX Text
EXISTING FUEL STORAGE TANK
AutoCAD SHX Text
EXISTING GABION WALL
AutoCAD SHX Text
EXISTING CONCRETE PAD TO BE REMOVED
AutoCAD SHX Text
EXISTING CONDUIT & CABLES TO BE REMOVED
AutoCAD SHX Text
C
AutoCAD SHX Text
B
AutoCAD SHX Text
A
AutoCAD SHX Text
STUB UP SECTION OF GENERATOR FUEL TANK
AutoCAD SHX Text
CONDUIT SHALL EXTEND min. 1" ABOVE SURFACE OF CONCRETE SLAB.
AutoCAD SHX Text
NOTE: ALL DISTURBED AREAS CAUSED BY NEW CONSTRUCTION, TRENCHING OR REMOVAL OF FENCE & PAD SHALL BE REINSTATED & FINISHED WITH SOD-GRADE SOIL AND NEW GRASS SODS INSTALLED.
Page 4: Metropolitan Regional Housing Authority Tender No. MET19 ... · NEW CONCRETE PAD & FENCING CHECKED BY: SHEET NUMBER: DRAWN BY: PROJECT NO: SCALE NOVA SCOTIA PROJECT Property & Facilities

A-2R

AS NOTED3 OF 7ISSUED FOR TENDER

08/MAY/2019

NEW CONCRETE PAD & FENCING

CHECKED BY:

SHEET NUMBER:

DRAWN BY:

PROJECT NO:

SCALE

PR

OJE

CT

NOVA SCOTIAProperty & Facilities

RICHMOND MANOR

NEW GENERATOR INSTALLATION

5594 NORTH RIDGE RD., HALIFAX, N.S.

PF-2019-005

T. WARREN

M. CONRAD

08/MAY/2019

3/8" = 1'-0"

GRAVEL BASE & FENCE DETAIL

1

TENDER ADDENDUM24/JUNE/2019

19-115 ADDENDUM #3 Richmond Manor generator Page 4 of 8

AutoCAD SHX Text
COMPACTED SUBGRADE
AutoCAD SHX Text
COMPACTED TYPE 2 STONE
AutoCAD SHX Text
COMPACTED TYPE 1 STONE
AutoCAD SHX Text
FINISHED GRADE
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
NEW GALVANIZED METAL CHAIN LINK FENCE. POSTS SHALL BE ANCHORED TO CONCRETE SLAB USING BASE ANCHOR SHOES & GALVANIZED WEDGE ANCHORS. ANCHORS TO BE SECURED TO CONCRETE USING ANCHORING EPOXY (QUIKRETE 8620-30, OR APPROVED EQUAL). ANCHORS FOR BASE PLATES TO BE INSTALLED SO TO AVOID METAL REINFORCEMENT IN CONCRETE SLAB. TERMINAL POSTS: MIN. 1 7/8" DIAM. LINE POSTS: MIN. 1 7/8" DIAM. TOP RAIL: MIN. 1 5/8" POST SPACING: MAX. 8'
AutoCAD SHX Text
NEW CONCRETE PAD, AS PER ENGINEER DRAWINGS, PG. S-201
AutoCAD SHX Text
NOTE: - CONTRACTOR SHALL REMOVE SOD AND CONTRACTOR SHALL REMOVE SOD AND ORGANIC FILL AND PROVIDE A LEVEL & COMPACTED SUBGRADE. - HOUSING AUTHORITY SHALL HAVE SOIL HOUSING AUTHORITY SHALL HAVE SOIL COMPACTION TESTED PRIOR TO INSTALLATION OF STONE. - CONTRACTOR SHALL INSTALL MIN. 12" OF TYPE 2 CONTRACTOR SHALL INSTALL MIN. 12" OF TYPE 2 STONE AND MIN. 6" TYPE 1 STONE. EACH LAYER SHALL BE COMPACTED AND LEVELED. - HOUSING AUTHORITY SHALL PROVIDE FINAL HOUSING AUTHORITY SHALL PROVIDE FINAL COMPACTION TEST PRIOR TO INSTALLATION OF CONCRETE SLAB.
Page 5: Metropolitan Regional Housing Authority Tender No. MET19 ... · NEW CONCRETE PAD & FENCING CHECKED BY: SHEET NUMBER: DRAWN BY: PROJECT NO: SCALE NOVA SCOTIA PROJECT Property & Facilities

19-115 ADDENDUM #3 Richmond Manor generator Page 5 of 8

Page 6: Metropolitan Regional Housing Authority Tender No. MET19 ... · NEW CONCRETE PAD & FENCING CHECKED BY: SHEET NUMBER: DRAWN BY: PROJECT NO: SCALE NOVA SCOTIA PROJECT Property & Facilities

E-1

2

}DATE:

CHECKED BY:

SHEET NUMBER:

DRAWN BY:

PROJECT NO:

SCALE

PR

OJE

CT

NOVA SCOTIAProperty & Facilities

RICHMOND MANOR

NEW GENERATOR INSTALLATION

5594 NORTH RIDGE RD., HALIFAX, N.S.

PF-2019-005

TAPAN KATWALA

TAPAN KATWALA

08/MAY/2019

E-1R

N.T.S

EXISTING SITE LAYOUT

1

AS NOTED5 OF 7ISSUED FOR TENDER

08/MAY/2019

EXISTING ELECTRICAL PLAN AND SCHEMATIC /

DEMOLITION PLAN

N.T.S

EXISTING POWER SYSTEM SCHEMATIC

3

N.T.S

EXISTING U/G CONDUIT DETAILS

2

TENDER ADDENDUM24/JUNE/2019

19-115 ADDENDUM #3 Richmond Manor generator Page 6 of 8

AutoCAD SHX Text
Richmond Manor 5594 Northridge Rd.
AutoCAD SHX Text
EXISTING HEATING FUEL-OIL STORAGE TANK
AutoCAD SHX Text
GABION WALL
AutoCAD SHX Text
GABION WALL
AutoCAD SHX Text
EXISTING GABION WALL
AutoCAD SHX Text
EXISTING, 10KW, DIESEL GENERATOR C/W SUB-BASE FUEL TANK AND ENCLOSURE ON CONCRETE BASE.
AutoCAD SHX Text
ELECTRICAL ROOM
AutoCAD SHX Text
GENERATOR PANEL
AutoCAD SHX Text
PANEL 'B'
AutoCAD SHX Text
ATS
AutoCAD SHX Text
DECK
AutoCAD SHX Text
1
AutoCAD SHX Text
2
AutoCAD SHX Text
3
AutoCAD SHX Text
4
AutoCAD SHX Text
5
AutoCAD SHX Text
NATIVE BACKFILL MATERIAL
AutoCAD SHX Text
A
AutoCAD SHX Text
B
AutoCAD SHX Text
GRADE
AutoCAD SHX Text
ESTIMATED CABLE/CONDUIT DETAILS: A. 3C #6 AWG CABLE IN 1 1/4" RPVC - FEEDER FROM 3C #6 AWG CABLE IN 1 1/4" RPVC - FEEDER FROM GENERATOR TO ATS B. 2 x (2C #12 AWG CABLE IN 3/4" RPVC) - 2 x (2C #12 AWG CABLE IN 3/4" RPVC) - - FEEDER FROM GENERATOR BLOCK HEATER & FEEDER FROM GENERATOR BLOCK HEATER & BATTERY CHARGER TO B-28 (PANEL B) - GENERATOR START SIGNAL TO ATS GENERATOR START SIGNAL TO ATS
AutoCAD SHX Text
ATS
AutoCAD SHX Text
GFI
AutoCAD SHX Text
LEGEND: EXISTING ELECTRICAL PANEL EXISTING AUTOMATIC TRANSFER SWITCH NEW 15A, 120V, GFI TYPE, WEATHER-RATED, ELECTRICAL OUTLET INSTALLED WITHIN THE NEW GENERATOR ENCLOSURE EXISTING, INTERIOR JUNCTION BOX
AutoCAD SHX Text
40A/2P
AutoCAD SHX Text
60A/2P
AutoCAD SHX Text
N
AutoCAD SHX Text
L
AutoCAD SHX Text
E
AutoCAD SHX Text
EXISTING, ASCO, ATS RATED @70A, 120/240V
AutoCAD SHX Text
EXISTING, KOHLER, 10KW, 1-PHASE, GENERATOR (SEE NOTES 1 & 2)
AutoCAD SHX Text
60A/2P
AutoCAD SHX Text
EXISTING GENERATOR PANEL 125A, 1-PHASE, 120/240V
AutoCAD SHX Text
EXISTING PANEL B 100A, 1-PHASE, 120/240V
AutoCAD SHX Text
PANEL B (GENERATOR BLOCK HEATER AND BATTERY CHARGER)
AutoCAD SHX Text
A
AutoCAD SHX Text
B
AutoCAD SHX Text
B
AutoCAD SHX Text
C
AutoCAD SHX Text
C
AutoCAD SHX Text
DEMOLITION NOTES:
AutoCAD SHX Text
DE-COMMISSION & REMOVE THE EXISTING, 10kW DIESEL GENERATOR. TERMINATE AND REMOVE ALL EXISTING WIRING IN U/G CONDUITS AS PER APPLICABLE CODES AND AHJ REGULATIONS. COORDINATE THE DISCONNECTION & REMOVAL OF THE EXISTING GENERATOR SYSTEM WITH THE INSTALLATION OF THE NEW GENERATOR SYSTEM TO MINIMIZE SERVICE DISRUPTION. REMOVE THE EXISTING, GENERATOR CONCRETE PAD. REMOVE EXISTING FENCE (OR SECTION OF FENCE) NEAR THE EXISTING GENERATOR TO GAIN ACCESS FOR REMOVAL WORK AS PER THE ARCHITECTURAL PLANS. REMOVE BRANCH CIRCUIT WIRING FOR GENERATOR BLOCK HEATER AND BATTERY CHARGER FROM EXISTING CIRCUIT B-28 (PANEL B). RE-LOCATE THE EXISTING BRANCH CIRCUIT WIRING TO NEW, 15A/1P CIRCUIT BREAKER IN THE EXISTING GENERATOR PANEL. MAKE THE CIRCUIT BREAKER (B-28) IN PANEL B SPARE AND LABEL ACCORDINGLY. REMOVE EXISTING UNDERGROUND FEEDERS AND CONDUITS.
AutoCAD SHX Text
1
AutoCAD SHX Text
2
AutoCAD SHX Text
3
AutoCAD SHX Text
4
AutoCAD SHX Text
5
AutoCAD SHX Text
ESTIMATED EXISTING CABLE SCHEDULE: A. 3C #6 AWG CABLE IN 1 1/2" RPVC. IT 3C #6 AWG CABLE IN 1 1/2" RPVC. IT TRANSITIONS INTO 1 1/2" EMT CONDUIT UPON ENTERING THE BUILDING. B. 2C #12 AWG CABLE IN 3/4" RPVC. IT 2C #12 AWG CABLE IN 3/4" RPVC. IT TRANSITIONS INTO 2C #12 AWG AC90 CABLE UPON ENTERING THE BUILDING. C. 3C #3 AWG AC90 CABLE.3C #3 AWG AC90 CABLE.
AutoCAD SHX Text
EXISTING SCHEMATIC NOTES: 1. DISCONNECT AND REMOVE THE GENERATOR DISCONNECT AND REMOVE THE GENERATOR AFTER THE NEW GENERATOR SYSTEM IS READY FOR SWITCH-OVER. 2. TURN OVER THE EXISTING GENERATOR TO TURN OVER THE EXISTING GENERATOR TO MRHA AFTER DE-COMMISSIONING. AT THE DIRECTION OF THE PROJECT MANAGER, DISPOSE OFF THE GENERATOR C/W FUEL TANK AS PER THE MOST RECENT VERSION OF APPLICABLE MUNICIPAL, PROVINCIAL, AND FEDERAL CODES AS WELL AS AHJ REGULATIONS. 3. ALL NON-OPERATIONAL LOAD CIRCUITS ON ALL NON-OPERATIONAL LOAD CIRCUITS ON THE EXISTING GENERATOR PANEL SUCH AS SOLAR PUMP 1, SOLAR PUMP 2, AND SOLAR CONTROL PANEL SHALL BE IDENTIFIED AS "SPARE" AND ALL APPLICABLE WIRING FROM THESE BRANCH CIRCUITS SHALL BE REMOVED.
Page 7: Metropolitan Regional Housing Authority Tender No. MET19 ... · NEW CONCRETE PAD & FENCING CHECKED BY: SHEET NUMBER: DRAWN BY: PROJECT NO: SCALE NOVA SCOTIA PROJECT Property & Facilities

DATE:

CHECKED BY:

SHEET NUMBER:

DRAWN BY:

PROJECT NO:

SCALE

PR

OJE

CT

NOVA SCOTIAProperty & Facilities

RICHMOND MANOR

NEW GENERATOR INSTALLATION

5594 NORTH RIDGE RD., HALIFAX, N.S.

PF-2019-005

TAPAN KATWALA

TAPAN KATWALA

08/MAY/2019

E-2R

N.T.S

PROPOSED SITE LAYOUT

1

AS NOTED6 OF 7ISSUED FOR TENDER

08/MAY/2019

PROPOSED ELECTRICAL PLAN AND SCHEMATIC

N.T.S

GENERATOR WIRING DETAILS

2

TENDER ADDENDUM24/JUNE/2019

19-115 ADDENDUM #3 Richmond Manor generator Page 7 of 8

AutoCAD SHX Text
Richmond Manor 5594 Northridge Rd.
AutoCAD SHX Text
EXISTING HEATING FUEL-OIL STORAGE TANK
AutoCAD SHX Text
NEW, 15KW, DIESEL GENERATOR C/W SUB-BASE FUEL TANK AND ENCLOSURE ON NEW CONCRETE BASE.
AutoCAD SHX Text
ELECTRICAL ROOM
AutoCAD SHX Text
ATS
AutoCAD SHX Text
GENERATOR PANEL
AutoCAD SHX Text
PANEL 'B'
AutoCAD SHX Text
GABION WALL
AutoCAD SHX Text
GABION WALL
AutoCAD SHX Text
EXISTING GABION WALL
AutoCAD SHX Text
DECK
AutoCAD SHX Text
1
AutoCAD SHX Text
2
AutoCAD SHX Text
C
AutoCAD SHX Text
B
AutoCAD SHX Text
A
AutoCAD SHX Text
60A/2P
AutoCAD SHX Text
CONCRETE PAD
AutoCAD SHX Text
MAIN BREAKER ON GENERATOR
AutoCAD SHX Text
#6 AWG GROUND TO AWG GROUND TO AWG GROUND TO GROUND TO GROUND TO TO TO FUEL PIPING
AutoCAD SHX Text
#4 BARE CU GROUND
AutoCAD SHX Text
2 x (3/4" X 10') CU CLAD GROUND ROD MOUNTED MIN. 10' APART
AutoCAD SHX Text
GFI
AutoCAD SHX Text
GFI
AutoCAD SHX Text
GENERAL NOTES: 1. MAINTAIN MANUFACTURER RECOMMENDED AND AHJ REQUIRED MAINTAIN MANUFACTURER RECOMMENDED AND AHJ REQUIRED CLEARANCES AROUND THE NEW GENERATOR LOCATION. REFER TO ARCHITECTURAL PLANS FOR REFERENCE. 2. REFER TO ARCHITECTURAL PLANS FOR DETAILS ON NEW FENCING, REFER TO ARCHITECTURAL PLANS FOR DETAILS ON NEW FENCING, GENERATOR SYSTEM CLEARANCES, AND CONCRETE PAD DETAILS INCLUDING SCALING DETAILS. 3. COORDINATE ALL U/G WORK WITH OTHER TRADES AND EXISTING COORDINATE ALL U/G WORK WITH OTHER TRADES AND EXISTING UTILITY LINES. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL UTILITY LOCATES AND SCOPING. 4. PATCH AND MAKE GOOD LANDSCAPING TO THE PROJECT MANAGER'S PATCH AND MAKE GOOD LANDSCAPING TO THE PROJECT MANAGER'S SATISFACTION.
AutoCAD SHX Text
CONSTRUCTION NOTES: 1. SUPPLY & INSTALL NEW FEEDERS & SUPPLY & INSTALL NEW FEEDERS & CONDUIT. TO BE INSTALLED ALONG PERIMETER OF EXTERIOR WALL TO THE NEW GENERATOR LOCATION. 2. NEW CONDUITS SHALL STUB-UP FROM THE NEW CONDUITS SHALL STUB-UP FROM THE NEW CONCRETE PAD VIA COMPATIBLE SLEEVES, INTO THE NEW GENERATOR ENCLOSURE VIA THE ELECTRICAL STUB-UP SECTION OF THE FUEL TANK / GENERATOR.
AutoCAD SHX Text
CABLE SCHEDULE: A. 3C #6 AWG CU RW90 + #10 AWG CU BOND IN 1 1/2" RPVC TO EXISTING 3C #6 AWG CU RW90 + #10 AWG CU BOND IN 1 1/2" RPVC TO EXISTING INTERIOR JUNCTION BOX FOR GENERATOR POWER CONNECTION. B. 3C #12 AWG CU RW90 + #12 AWG CU BOND IN 3/4" RPVC TO EXISTING 3C #12 AWG CU RW90 + #12 AWG CU BOND IN 3/4" RPVC TO EXISTING INTERIOR JUNCTION BOX FOR GENERATOR START FROM ATS C. 2C #12 AWG CU RW90 + #12 AWG CU BOND IN 3/4" RPVC TO EXISTING 2C #12 AWG CU RW90 + #12 AWG CU BOND IN 3/4" RPVC TO EXISTING INTERIOR JUNCTION BOX 120V, 1-PHASE, CONNECTION FOR GENERATOR BLOCK HEATER AND BATTERY CHARGER. NOTE: CONTRACTOR SHALL VERIFY ALL GENERATOR WIRING REQUIREMENTS WITH THE SYSTEM MANUFACTURER PRIOR TO ROUGH-IN.
Page 8: Metropolitan Regional Housing Authority Tender No. MET19 ... · NEW CONCRETE PAD & FENCING CHECKED BY: SHEET NUMBER: DRAWN BY: PROJECT NO: SCALE NOVA SCOTIA PROJECT Property & Facilities

DATE:

CHECKED BY:

SHEET NUMBER:

DRAWN BY:

PROJECT NO:

SCALE

PR

OJE

CT

NOVA SCOTIAProperty & Facilities

RICHMOND MANOR

NEW GENERATOR INSTALLATION

5594 NORTH RIDGE RD., HALIFAX, N.S.

PF-2019-005

TAPAN KATWALA

TAPAN KATWALA

08/MAY/2019

E-3R

N.T.S

REVISED POWER SCHEMATIC

1

AS NOTED7 OF 7ISSUED FOR TENDER

08/MAY/2019

REVISED ELECTRICAL SCHEMATIC

TENDER ADDENDUM24/JUNE/2019

19-115 ADDENDUM #3 Richmond Manor generator Page 8 of 8

AutoCAD SHX Text
N
AutoCAD SHX Text
L
AutoCAD SHX Text
E
AutoCAD SHX Text
EXISTING, ASCO, ATS RATED @70A, 120/240V
AutoCAD SHX Text
NEW, KOHLER, 15KW, 1-PHASE, GENERATOR
AutoCAD SHX Text
EXISTING GENERATOR PANEL 125A, 1-PHASE, 120/240V
AutoCAD SHX Text
EXISTING PANEL B 100A, 1-PHASE, 120/240V
AutoCAD SHX Text
G
AutoCAD SHX Text
A
AutoCAD SHX Text
C
AutoCAD SHX Text
E
AutoCAD SHX Text
B
AutoCAD SHX Text
D
AutoCAD SHX Text
F
AutoCAD SHX Text
F
AutoCAD SHX Text
G
AutoCAD SHX Text
60A/2P (NEW)
AutoCAD SHX Text
60A/2P (EXISTING)
AutoCAD SHX Text
60A/2P (EXISTING)
AutoCAD SHX Text
15A/1P (NEW)
AutoCAD SHX Text
EXISTING, INTERIOR JUNCTION BOX
AutoCAD SHX Text
EXISTING, INTERIOR JUNCTION BOXES
AutoCAD SHX Text
SCHEMATIC NOTES: 1. THE CONTRACTOR SHALL FIRE STOP ALL NEW THE CONTRACTOR SHALL FIRE STOP ALL NEW AND REDUNDANT ELECTRICAL OPENINGS INTO THE BUILDING. 2. INSTALL THE GENERATOR SYSTEM IN INSTALL THE GENERATOR SYSTEM IN COMPLIANCE WITH NSP BULLETIN B-28-900, SOLIDLY GROUNDED NEUTRAL CONFIGURATION. ENSURE THE NEUTRAL IS BONDED TO FRAME. 3. ENSURE SLEEVES ARE CAST-IN-PLACE IN THE ENSURE SLEEVES ARE CAST-IN-PLACE IN THE CONCRETE PAD FOR THE CONDUCTORS ENTERING THE GENERATOR.
AutoCAD SHX Text
CABLE SCHEDULE: A. NEW, 3C#6 AWG CU RW90 + #10 AWG CU BOND NEW, 3C#6 AWG CU RW90 + #10 AWG CU BOND IN 1 1/2" RPVC. B. EXISTING, FEEDER AND CONDUIT SYSTEM. EXISTING, FEEDER AND CONDUIT SYSTEM. C. NEW, 2C#12 AWG CU RW90 + #12 AWG CU BOND IN NEW, 2C#12 AWG CU RW90 + #12 AWG CU BOND IN 3/4" RPVC. D. EXISTING, FEEDER AND CONDUIT SYSTEM. EXISTING, FEEDER AND CONDUIT SYSTEM. E. NEW, 3C#12 AWG CU RW90 + #12 AWG CU BOND IN NEW, 3C#12 AWG CU RW90 + #12 AWG CU BOND IN 3/4" RPVC. F. EXISTING, 2C#12 AWG CU AC90 CABLE. EXISTING, 2C#12 AWG CU AC90 CABLE. G. EXISTING FEEDER AND CONDUIT SYSTEM.EXISTING FEEDER AND CONDUIT SYSTEM.
Page 9: Metropolitan Regional Housing Authority Tender No. MET19 ... · NEW CONCRETE PAD & FENCING CHECKED BY: SHEET NUMBER: DRAWN BY: PROJECT NO: SCALE NOVA SCOTIA PROJECT Property & Facilities

Metropolitan Regional Housing Authority

Tender No. MET19-115 Richmond Manor Generator

ADDENDUM No. 2

June 18, 2019

The Tender Documents shall be amended and will become part of the Contract Documents. This addendum shall form an integral part of the Tender Documents.

1. Existing fence around existing fuel storage tank shall remain however existing fence shall be repaired. Three new posts (2 end posts & 1 line post) shall be set in minimum 3’ depth, minimum 10’’ diameter concrete on existing generator side to enclose the tank. Reinstall existing surplus chain link enclosing fuel storage tank. Existing gate shall be reused however repaired for proper alignment and sizing in new opening.

2. Contractor shall complete all sub grade locates before work begins.

3. Contractor shall decommission and remove the existing generator and transport to Transportation Infrastructure Renewal, 10 Acadia St, Dartmouth N.S, B2Y- 4H3. Decommissioning involves the removal of all fuel, oil and coolant before transporting. Transporting needs to be pre-arranged with Project Manager.

The closing date and time remains the same.

END OF ADDENDUM

Page 10: Metropolitan Regional Housing Authority Tender No. MET19 ... · NEW CONCRETE PAD & FENCING CHECKED BY: SHEET NUMBER: DRAWN BY: PROJECT NO: SCALE NOVA SCOTIA PROJECT Property & Facilities

Metropolitan Regional Housing Authority

Tender No. MET19-115 Richmond Manor Generator

ADDENDUM No. 1

June 17, 2019

The Tender Documents shall be amended and will become part of the Contract Documents.

This addendum shall form an integral part of the Tender Documents.

The closing date and time for this tender has been changed to Friday June 28, 2019 by 2:00pm.

END