www.danfoss.us <3 years payback When combined with air-to-air heat exchangers, Danfoss VSH variable- speed compressors are helping Annexair’s rooftop makeup air units use less energy and are expected to have less than a 3-year payback. Medical Centers Keep Cool With Variable Speed Compressors As the oldest inland city in South Carolina dating back to King George III, Camden is proud of its stately homes, steeplechase racing and southern resort hospitality. It’s also proudly celebrating the 100-year anniversary of its hospital -- today known as KershawHealth Medical Center. This modern, multi-story, 215-bed facility provides general medical and surgical care for 65,000 residents in Kershaw County and surrounding communities. It’s also keeping up with the times by using energy-efficient, dedicated outdoor air systems employing Danfoss VSH variable-speed compressors. “Today’s hospitals are built to comply with ASHRAE Standard 62-2007, which sets the minimum ventilation requirements for acceptable indoor air quality,” notes Anthony Palucci, director of sales for Annexair, the system manufacturer. “Our goal was to provide a product that could not only meet the outside air requirements, but also provide energy savings.” The ASHRAE standard requires operating rooms to have 25 air changes per hour. At least five of those air changes must use 100 percent outside air to maintain positive pressure to keep unhealthy air from leaking into the surgical suite. Other hospital areas require two changes per hour to control odors and provide ventilation for comfort. But using a traditional mechanical cooling for that amount of outside air is extremely expensive. Annexair’s solution was to use a recuperative dehumidification design in the makeup air-handling systems. Each unit employed a Danfoss VSH variable-speed compressor to supply a cooling coil used in conjunction with a fixed plate heat exchanger to recycle thermal energy. “There are several ways to meet requirements for 100 percent outdoor air without paying a high price for electricity,” says Palucci. “Typically, a unit like this will use a fixed-speed compressor and slow fan speed to increase time through the cooling section to pull more moisture from the supply air. But that makes the air too cold. Then you’ve got to use hot gas reheat to raise the sensible temperature, which is extremely inefficient.” Palucci proposed a dedicated outdoor unit package that takes advantage of a fixed plate heat exchanger to provide free pre-cooling and free-reheat functions to handle dehumidification at full load. The variable-speed compressor provides the balance of cooling needed at part loads. This design takes advantage of Camden’s maritime climate,” says Palucci. “In the summer, humidity is high and temperatures average 78 degrees Fahrenheit, peaking in the 90s in July. The heat exchanger does double Case Story MAKING MODERN LIVING POSSIBLE
2
Embed
Medical Centers Keep Cool With Variable Speed Compressorsfiles.danfoss.com/technicalinfo/dila/17/MedicalCenterCaseStudy... · systems employing Danfoss VSH variable-speed compressors.
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
www.danfoss.us
<3years payback
When combined with air-to-air heat exchangers, Danfoss VSH variable-speed compressors are helping Annexair’s rooftop makeup air units use less energy and are expected to have less than a 3-year payback.
Medical Centers Keep CoolWith Variable Speed Compressors As the oldest inland city in South Carolina dating back to King George III,
Camden is proud of its stately homes, steeplechase racing and southern
resort hospitality. It’s also proudly celebrating the 100-year anniversary of
its hospital -- today known as KershawHealth Medical Center. This modern,
multi-story, 215-bed facility provides general medical and surgical care for
65,000 residents in Kershaw County and surrounding communities. It’s also
keeping up with the times by using energy-efficient, dedicated outdoor air
systems employing Danfoss VSH variable-speed compressors.
“Today’s hospitals are built to comply with ASHRAE Standard 62-2007,
which sets the minimum ventilation requirements for acceptable indoor air
quality,” notes Anthony Palucci, director of sales for Annexair, the system
manufacturer. “Our goal was to provide a product that could not only meet
the outside air requirements, but also provide energy savings.”
The ASHRAE standard requires operating rooms to have 25 air changes per
hour. At least five of those air changes must use 100 percent outside air to
maintain positive pressure to keep unhealthy air from leaking into the
surgical suite. Other hospital areas require two changes per hour to control
odors and provide ventilation for comfort. But using a traditional
mechanical cooling for that amount of outside air is extremely expensive.
Annexair’s solution was to use a recuperative dehumidification design in
the makeup air-handling systems. Each unit employed a Danfoss VSH
variable-speed compressor to supply a cooling coil used in conjunction
with a fixed plate heat exchanger to recycle thermal energy.
“There are several ways to meet requirements for 100 percent outdoor air
without paying a high price for electricity,” says Palucci. “Typically, a unit
like this will use a fixed-speed compressor and slow fan speed to increase
time through the cooling section to pull more moisture from the supply air.
But that makes the air too cold. Then you’ve got to use hot gas reheat to
raise the sensible temperature, which is extremely inefficient.”
Palucci proposed a dedicated outdoor unit package that takes advantage
of a fixed plate heat exchanger to provide free pre-cooling and free-reheat
functions to handle dehumidification at full load. The variable-speed
compressor provides the balance of cooling needed at part loads.
This design takes advantage of Camden’s maritime climate,” says Palucci.
“In the summer, humidity is high and temperatures average 78 degrees
Fahrenheit, peaking in the 90s in July. The heat exchanger does double
Palucci explains that in an air-to-air recuperative
unit, the outdoor air passes through the fixed
plate heat exchangers twice (2-pass). The heat
exchange occurs between the incoming fresh
warm air and the cool air leaving the cooling
coil. On the first pass, the fixed plate pre-
conditions the air reaching the cooling coil by
reducing the sensible temperature, thereby
requiring less mechanical cooling.
At part-load conditions, the VSH compressor
supplies the DX coil with exactly the required
cooling capacity to drop the sensible
temperature even further as needed. The
cooling coil maintains a constant leaving air
dewpoint with the help of the VSH compressor,
without the use of energy wasting hot gas
by-pass. Then in the second pass, the cooled air
is reheated by absorbing heat from the
incoming air stream. Again as needed, a hot gas
reheat coil will raise the sensible temperature to
maintain a neutral dry supply air. But because
the heat exchanger is about 65 percent effective
in handling both precooling and reheating
functions simply through thermal transfer,
electric consumption for additional cooling and
reheats is minimized.
Annexair provided two rooftop makeup air units
(MAU), each using one 22-ton Danfoss VSH
compressor and each delivering 3,800 cfm.
Another MAU employs a 12-ton compressor and
provides 1,700 cfm. The compressors supply the
mechanical cooling section to enable the MAU
to deliver dry air when dry bulb energy air
temperatures range from 95 degrees to 55
degrees and wet bulb temperatures range from
78 degrees to 53 degrees.
“We prefer VSH series compressors for our
dedicated MAU systems because they are a
variable-speed scroll designed specifically for air
conditioning and heat pumps,” says Palucci.
“They come with all the features completely
packaged to make it easy to integrate a
variable-speed compressor into our systems.”
With a 3:1 turndown ratio, the VSH compressors
are ideal for dehumidification. “We take
advantage of the variable-speed control to
deliver only the required cooling capacity,”
notes Palucci. “Even in South Carolina, over 90
percent of operating hours occur at part-load
conditions. The turndown ratio allows
compressor speed to be reduced to match lower
capacity requirements. Between the two MAU
designs, we can go from 22 to 7.5 tons and 12 to
4.”
“Anytime the compressor can reduce capacity, it
makes the size of the cooling coils
thermodynamically larger,” explains Palucci.
“And when the airstream is exposed to more coil
surface area, more water vapor is pulled out of
the air.”
The speed control allows each unit to operate
within +0.2 degrees of setpoint. Fixed-speed
compressors run at full speed and have to be
cycled on/off or use someother capacity-
reduction method that wastes energy -- and
creates more noise.
Noise reduction is a major benefit in a hospital
setting. In the evenings, when sound is critical
and loads are typically low, the VSH compressors
operate at their slowest and quietest -- unlike
fixed-speed compressors that frequently cycle
on and off. The VSH drive controller also
provides a soft start that ramps up the inrush
current slowly. Avoiding a huge amperage surge
makes it easier on the motor winding, thus
extending the life of the motor.
Reliability of the Annexair MAU design is also
enhanced because the air-to-air design’s heat
exchangers involve no moving parts, use no
external connections to water or glycol loops,
and do not use a heat-transfer fluid that could
be subject to freezing.
“We prefer VSH series compressors for our dedicated MAU systems because they are avariable-speed scroll designed specifically for air conditioning and heat pumps. They come with all the features completely packaged to make it easy to integrate a variablespeed compressor into our
systems.”
Anthony Palucci, director of salesfor Annexair
www.danfoss.us
“The facility went through some scorching
summer heat with these units,” says Palucci. “But
a 100 percent dedicated air-to-air MAU design is
ideal for this application. The units can hit
temperature and humidity setpoints exactly.
And compared to the old, generic units they
replaced, they’re using a lot less electricity. In