Top Banner
66 V6.2 03.2015• Subject to modification UL marked actuators is optional, please contact your local Sales Representative for details. Mechanical Fail-Safe Damper Actuator EF24A-S2 Electrical data Nominal voltage AC 24V, 50/60Hz / DC 24V Nominal voltage range AC 19.2...28.8V / DC 21.6...28.8V Power consumption In operation At rest For wire sizing 9.5W @ nominal torque 4.5W 16VA Auxiliary switch 2 x SPDT, 1 x 10% / 1 x 11...90% Connection Motor Auxiliary switch Cable 1m, 2 x 0.75mm ² Cable 1m, 6 x 0.75mm ² Functional data Torque Motor Spring return Min. 30Nm @ nominal voltage Min. 30Nm Direction of rotation Can be selected by mounting L / R Manual override With hand crank and interlocking switch Angle of rotation Max. 95° , can be limited with adjustable mechanical end stop Running time Motor Spring return ≤75s (0...30Nm) ≤20s @ –20...50°C / max. 60s @ –30°C Sound power level Motor Spring return ≤55dB(A) ≤71dB(A) Service life Min. 60,000 emergency positions Position indication Mechanical Safety Protection class III Extra low voltage UL Class 2 Supply Degree of protection IP54 NEMA2, UL Enclosure Type 2 EMC Low-voltage directive CE according to 2004/108/EC CE according to 2006/95/EC Certification Certified to IEC/EN 60730-1 and IEC/EN 60730-2-14 cULus according to UL 60730-1A and UL 60730-2-14 and CAN/CSA E60730-1:02 Mode of operation Type 1.AA.B Rated impulse voltage Actuator Auxiliary switch 0.8kV 2.5kV Control pollution degree 3 Ambient temperature –30...+50°C Non-operating temperature –40...+80°C Ambient humidity 95% r.h., non-condensating Maintenance Maintenance-free Dimensions / Weight Dimensions See «Dimensions» Weight Approx. 4.4kg Spring return actuator with emergency function for adjusting air dampers in ventilation and air conditioning systems in buildings • Torque 30Nm • Nominal voltage AC/DC 24V • Control: Open-close Two integrated auxiliary switches Dimensional drawings Technical data Damper spindle Length ≥117 12...26.7 >12 < 25.2 ≥20 12...26.7 >12 < 25.2 35 50 35 143 188 238 272 322 112 138 Dimensions [mm] 80 27 13.5 12.5 12 ... 22 mm 12 ... 18 mm 22 ... 26.7 mm 12 ... 18 mm
6

Mechanical Fail-Safe Damper Actuator EF24A-S266 V6.2 03.2015•Subject to modification UL marked actuators is optional, please contact your local Sales Representative for details.

Feb 28, 2021

Download

Documents

dariahiddleston
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: Mechanical Fail-Safe Damper Actuator EF24A-S266 V6.2 03.2015•Subject to modification UL marked actuators is optional, please contact your local Sales Representative for details.

66

V6.

2 03

.201

5•S

ubje

ct to

mod

ifica

tion

UL marked actuators is optional, please contact your local Sales Representative for details.

Mechanical Fail-Safe Damper Actuator EF24A-S2

Electrical data Nominal voltage AC 24V, 50/60Hz / DC 24VNominal voltage range AC 19.2...28.8V / DC 21.6...28.8VPower consumption

In operationAt restFor wire sizing

9.5W @ nominal torque4.5W16VA

Auxiliary switch 2 x SPDT, 1 x 10% / 1 x 11...90%Connection Motor

Auxiliary switchCable 1m, 2 x 0.75mm²Cable 1m, 6 x 0.75mm²

Functional data Torque MotorSpring return

Min. 30Nm @ nominal voltageMin. 30Nm

Direction of rotation Can be selected by mounting L / RManual override With hand crank and interlocking switchAngle of rotation Max. 95° , can be limited with

adjustable mechanical end stopRunning time Motor

Spring return≤75s (0...30Nm)≤20s @ –20...50°C / max. 60s @ –30°C

Sound power level

MotorSpring return

≤55dB(A)≤71dB(A)

Service life Min. 60,000 emergency positionsPosition indication Mechanical

Safety Protection class III Extra low voltageUL Class 2 Supply

Degree of protection IP54NEMA2, UL Enclosure Type 2

EMCLow-voltage directive

CE according to 2004/108/ECCE according to 2006/95/EC

Certification Certified to IEC/EN 60730-1 and IEC/EN 60730-2-14cULus according to UL 60730-1A and UL 60730-2-14and CAN/CSA E60730-1:02

Mode of operation Type 1.AA.BRated impulse voltage

ActuatorAuxiliary switch

0.8kV2.5kV

Control pollution degree 3Ambient temperature –30...+50°CNon-operating temperature –40...+80°CAmbient humidity 95% r.h., non-condensatingMaintenance Maintenance-free

Dimensions / Weight Dimensions See «Dimensions» Weight Approx. 4.4kg

Spring return actuator with emergency function for adjusting air dampers in ventilation and air conditioning systems in buildings• Torque 30Nm• Nominal voltage AC/DC 24V• Control: Open-close• Two integrated auxiliary switches

Dimensional drawings

Technical data

Damper spindle Length≥117 12...26.7 >12 < 25.2≥20 12...26.7 >12 < 25.2

35

50

35 143

188

238

272

322

112 138

Dimensions [mm]

8027

13.5

12.5

12 ... 22 mm 12 ... 18 mm

22 ... 26.7 mm 12 ... 18 mm

Page 2: Mechanical Fail-Safe Damper Actuator EF24A-S266 V6.2 03.2015•Subject to modification UL marked actuators is optional, please contact your local Sales Representative for details.

67

V6.

2 03

.201

5•S

ubje

ct to

mod

ifica

tion

UL marked actuators is optional, please contact your local Sales Representative for details.

Mechanical Fail-Safe Damper Actuator EF24A-SR

Modulating spring return actuator with emergency function for adjusting air dampers in ventilation and air conditioning systems in buildings• Torque 30Nm• Nominal voltage AC/DC 24V• Control: modulating DC (0)2...10V• Position feedback DC 2...10V

Electrical data Nominal voltage AC 24V, 50/60Hz / DC 24VNominal voltage range AC 19.2...28.8V / DC 21.6...28.8VPower consumption

In operationAt restFor wire sizing

7W @ nominal torque4.5W12VA

Connection Cable 1m, 4 x 0.75mm²

Functional data Torque MotorSpring return

Min. 30Nm @ nominal voltageMin. 30Nm

Control Control signal YOperating range

DC (0)2…10V, input impedance 100kΩDC 2…10V

Position feedback (measuring voltage U)

DC 2…10V, max. 0.5mA

Position accuracy ±5%Direction of rotation

MotorSpring return

Reversible with switch / Can be selected by mounting L / R

Manual override With hand crank and interlocking switchAngle of rotation Max. 95° , can be limited with

adjustable mechanical end stopRunning time Motor

Spring return150s (0...30Nm)≤20s @ –20...50°C / max. 60s @ –30°C

Sound power level MotorSpring return

≤45dB(A) @ 150s running time≤71dB(A)

Service life Min. 60,000 emergency positionsPosition indication Mechanical

Safety Protection class III Extra low voltageUL Class 2 Supply

Degree of protection IP54NEMA2, UL Enclosure Type 2

EMC CE according to 2004/108/ECCertification Certified to IEC/EN 60730-1 and IEC/EN 60730-2-14

cULus according to UL 60730-1A and UL 60730-2-14and CAN/CSA E60730-1:02

Mode of operation Type 1.AARated impulse voltage 0.8kVControl pollution degree 3Ambient temperature –30...+50°CNon-operating temperature –40...+80°CAmbient humidity 95% r.h., non-condensatingMaintenance Maintenance-free

Dimensions / Weight Dimensions See «Dimensions» Weight Approx. 5.3kg

Technical data

Dimensions [mm]

Damper spindle Length≥117 12...26.7 >12 < 25.2≥20 12...26.7 >12 < 25.2

35

50

35 143

188

238

272

322

112 138

12 ... 22 mm 12 ... 18 mm

22 ... 26.7 mm 12 ... 18 mm

Dimensional drawings

8027

13.5

12.5

Page 3: Mechanical Fail-Safe Damper Actuator EF24A-S266 V6.2 03.2015•Subject to modification UL marked actuators is optional, please contact your local Sales Representative for details.

68

V6.

2 03

.201

5•S

ubje

ct to

mod

ifica

tion

UL marked actuators is optional, please contact your local Sales Representative for details.

Spring return actuator with emergency function for adjusting air dampers in ventilation and air conditioning systems in buildings• Torque 30Nm• Nominal voltage AC 230V• Control: Open-close• Two integrated auxiliary switches

Electrical data Nominal voltage AC 230V, 50/60HzNominal voltage range AC 90...264VPower consumption

In operationAt restFor wire sizing

9W @ nominal torque4.5W21VA

Auxiliary switch 2 x SPDT, 1 x 10% / 1 x 11...90%Connection Motor

Auxiliary switchCable 1m, 2 x 0.75mm²Cable 1m, 6 x 0.75mm²

Functional data Torque MotorSpring return

Min. 30Nm @ nominal voltageMin. 30Nm

Direction of rotation Can be selected by mounting L / RManual override With hand crank and interlocking switchAngle of rotation Max. 95° , can be limited with

adjustable mechanical end stopRunning time Motor

Spring return≤75s (0...30Nm)≤20s @ –20...50°C / max. 60s @ –30°C

Sound power level MotorSpring return

≤56dB(A)≤71dB(A)

Service life Min. 60,000 emergency positionsPosition indication Mechanical

Safety Protection class II Totally insulated Protection mode IP54

NEMA2, UL Enclosure Type 2EMCLow-voltage directive

CE according to 2004/108/ECCE according to 2006/95/EC

Certification Certified to IEC/EN 60730-1 and IEC/EN 60730-2-14cULus according to UL 60730-1A and UL 60730-2-14and CAN/CSA E60730-1:02

Mode of operation Type 1.AA.BRated impulse voltage

ActuatorAuxiliary switch

2.5kV2.5kV

Control pollution degree 3Ambient temperature –30...+50°CNon-operating temperature –40...+80°CAmbient humidity 95% r.h., non-condensatingMaintenance Maintenance-free

Dimensions / Weight Dimensions See «Dimensions» Weight Approx. 5.4kg

Mechanical Fail-Safe Damper Actuator EF230A-S2

Technical data

35

50

35 143

188

238

272

322

112 138

Damper spindle Length≥117 12...26.7 >12 < 25.2≥20 12...26.7 >12 < 25.2

12 ... 22 mm 12 ... 18 mm

22 ... 26.7 mm 12 ... 18 mm

Dimensional drawings

Dimensions [mm]

8027

13.5

12.5

Page 4: Mechanical Fail-Safe Damper Actuator EF24A-S266 V6.2 03.2015•Subject to modification UL marked actuators is optional, please contact your local Sales Representative for details.

88

V6.

2 03

.201

5•S

ubje

ct to

mod

ifica

tion

UL marked actuators is optional, please contact your local Sales Representative for details.

Wiring diagrams-Mechanical Fail-Safe Damper Actuator

Wiring diagrams: Open/Close actuators

Notes:• Parallel connection of several actuators is possible.• Power consumption must be observed.

T

– +

~

AC/DC 24V

S1 S2 S3

TF230-S, TF24-SM

TF230, TF24M

AC 100...240V (for TF230..)

> x

< xx = 0...100%

N L

1 2

T

– +

~ AC/DC 24V

S1 S2 S3

LF230-S, LF24-SM

LF230, LF24M

AC 230V (for LF230..)

> x

< xx = 0...100%

N L

1 2T

– +

~

DC 24...125V

S1 S2 S3

NFU-S2, SFU-S2M

NFU, SFUM

AC 24...240V

S4 S5 S6

10%...90% adjustable10%

N L

1 2

T

– +

~

AC 230V (for EF230A-S2) AC/DC 24V

S1 S2 S3

EFU24-S2, EFU230-S2M

S4 S5 S6

10%...90% adjustable10%

N L

1 2

Connection via safetyisolated transformer!

Connection via safetyisolated transformer!

Connection via safetyisolated transformer!

Connection via safetyisolated transformer!

Wiring diagrams: Open/Close actuators

NFA-S2, SFA-S2

NFA, SFA

EF24A-S2,EF230A-S2

Page 5: Mechanical Fail-Safe Damper Actuator EF24A-S266 V6.2 03.2015•Subject to modification UL marked actuators is optional, please contact your local Sales Representative for details.

89

V6.

2 03

.201

5•S

ubje

ct to

mod

ifica

tion

UL marked actuators is optional, please contact your local Sales Representative for details.

Wiring diagrams-Mechanical Fail-Safe Damper ActuatorWiring diagram: 3-point actuators

Notes:• Connection via safety isolating transformer.• Parallel connection of several actuators is possible.• Power consumption must be observed.

Connection via safetyisolated transformer!

1 2

AC 24VDC 24V

5

T

– +

~

LF24-3

T

– +

~

Connection via safetyisolated transformer!

Mounting side

Reversing switch

L0

.2

.4

.6

.8

1

R0

.2

.4

.6

.8

1

a(Y 1)

b(Y 2)

stop stop stop stop

3

a b

1 2

AC 24V

5

T ~

T ~

3

a b

TF24-3Y1 Y2

Y1 Y2

Mounting side

Reversing switch

L0

.2

.4

.6

.8

1

R0

.2

.4

.6

.8

1

a(Y 1)

b(Y 2)

stop stop stop stop

R L R L

Wiring diagrams: 3-point actuators

Page 6: Mechanical Fail-Safe Damper Actuator EF24A-S266 V6.2 03.2015•Subject to modification UL marked actuators is optional, please contact your local Sales Representative for details.

90

V6.

2 03

.201

5•S

ubje

ct to

mod

ifica

tion

UL marked actuators is optional, please contact your local Sales Representative for details.

Wiring diagram: modulating actuators

Notes:• Connection via safety isolating transformer.• Parallel connection of several actuators is possible.• Power consumption must be observed.

1 2 3

Y U

AC 24VDC 24V

5

T

– +

~

Y

U

DC (0)2...10V

DC 2...10V

LF24-SR

NFU24-SR, SFU24-SREFU24-SR

T– +

~

Connection via safetyisolated transformer!

1 2 3

Y U

AC 24VDC 24V

5

T

– +

~

Y

U

DC (0)2...10V

DC 2...10V

T

– +

~

Connection via safetyisolated transformer!

1 2 3

Y U

AC 24VDC 24V

5

T

– +

~

Y

U

DC (0)2...10V

DC 2...10V

TF24-SR

T

– +

~

Connection via safetyisolated transformer!

withY = 0

withY = 0

withY = 0

withY = 0

L0

.2

.4

.6

.8

1

R0

.2

.4

.6

.8

1

Mounting side

Reversing switch

withY = 0

withY = 0

withY = 0

withY = 0

L0

.2

.4

.6

.8

1

R0

.2

.4

.6

.8

1

Mounting side

Reversing switch

withY = 0

withY = 0

withY = 0

withY = 0

L0

.2

.4

.6

.8

1

R0

.2

.4

.6

.8

1

Mounting side

Reversing switch

R L R L

Wiring diagrams-Mechanical Fail-Safe Damper Actuator

Wiring diagrams: modulating actuators

NF24A-SR, SF24A-SREF24A-SR