Page 1: MEASUREMENT OF WATER HEATER EFFICIENCY. MEASURE EFFECTIVENESS APPLICATION – RETIREMENT VILLAGE CURRENT SYSTEM (CONTROL) CONTROLLER (NEW SYSTEM) ACCOUNT.

MEASUREMENT OFWATER HEATER

EFFICIENCY

Page 2: MEASUREMENT OF WATER HEATER EFFICIENCY. MEASURE EFFECTIVENESS APPLICATION – RETIREMENT VILLAGE CURRENT SYSTEM (CONTROL) CONTROLLER (NEW SYSTEM) ACCOUNT.

MEASURE EFFECTIVENESS

• APPLICATION – RETIREMENT VILLAGE

• CURRENT SYSTEM (CONTROL)

• CONTROLLER (NEW SYSTEM)

• ACCOUNT FOR USE PATTERNS

Page 3: MEASUREMENT OF WATER HEATER EFFICIENCY. MEASURE EFFECTIVENESS APPLICATION – RETIREMENT VILLAGE CURRENT SYSTEM (CONTROL) CONTROLLER (NEW SYSTEM) ACCOUNT.

CONSTRAINTS

• NO LOSS OF HOT WATER SERVICE

• TWO WEEKS FOR EXPERIMENT

Page 4: MEASUREMENT OF WATER HEATER EFFICIENCY. MEASURE EFFECTIVENESS APPLICATION – RETIREMENT VILLAGE CURRENT SYSTEM (CONTROL) CONTROLLER (NEW SYSTEM) ACCOUNT.

COLD WATERSUPPLY

WATERMETER

GASMETER

SOLENOID

TO SPACEHEATING

GAS SUPPLY WATERHEATER

HOT WATERSUPPLY

LARGE

CONSUMPTION

Page 5: MEASUREMENT OF WATER HEATER EFFICIENCY. MEASURE EFFECTIVENESS APPLICATION – RETIREMENT VILLAGE CURRENT SYSTEM (CONTROL) CONTROLLER (NEW SYSTEM) ACCOUNT.

COLD WATERSUPPLY

WATERMETER

GASMETER

SOLENOID CONTROLLER

TO SPACEHEATING

GAS SUPPLY WATERHEATER

Page 6: MEASUREMENT OF WATER HEATER EFFICIENCY. MEASURE EFFECTIVENESS APPLICATION – RETIREMENT VILLAGE CURRENT SYSTEM (CONTROL) CONTROLLER (NEW SYSTEM) ACCOUNT.

CONCERNS

• GAS METER MEASURED BOTH HOT WATER AND SPACE HEATING USAGE

• WAS BURNER CONSUMPTION RATE CONSTANT?

• HOW TO ACCOUNT FOR GREATER USAGE ON MONDAY AND FRIDAY?

• HOW TO ACCOUNT FOR STANDBY LOSSES?

Page 7: MEASUREMENT OF WATER HEATER EFFICIENCY. MEASURE EFFECTIVENESS APPLICATION – RETIREMENT VILLAGE CURRENT SYSTEM (CONTROL) CONTROLLER (NEW SYSTEM) ACCOUNT.

GAS METER MEASURED BOTH HOT WATER AND SPACE HEATING USAGE

MONOTOR TIME THAT GAS SOLENOID IS OPEN.

Page 8: MEASUREMENT OF WATER HEATER EFFICIENCY. MEASURE EFFECTIVENESS APPLICATION – RETIREMENT VILLAGE CURRENT SYSTEM (CONTROL) CONTROLLER (NEW SYSTEM) ACCOUNT.

COLD WATERSUPPLY

WATERMETER

GASMETER

TIMER

SOLENOID CONTROLLER

TO SPACEHEATING

GAS SUPPLY WATERHEATER

Page 9: MEASUREMENT OF WATER HEATER EFFICIENCY. MEASURE EFFECTIVENESS APPLICATION – RETIREMENT VILLAGE CURRENT SYSTEM (CONTROL) CONTROLLER (NEW SYSTEM) ACCOUNT.

WAS BURNER CONSUMPTION RATE CONSTANT?

CALIBRATE BURNER GAS CONSUMPTION

• MEASURE HOT WATER GAS CONSUMPTION WITH SPACE HEATING OFF

• REPLICATE

Page 10: MEASUREMENT OF WATER HEATER EFFICIENCY. MEASURE EFFECTIVENESS APPLICATION – RETIREMENT VILLAGE CURRENT SYSTEM (CONTROL) CONTROLLER (NEW SYSTEM) ACCOUNT.

WEEKLY USAGE

0

100

200

300

400

500

600

700

800

SUNDAY TUESDAY THURSDAY SATURDAY

Page 11: MEASUREMENT OF WATER HEATER EFFICIENCY. MEASURE EFFECTIVENESS APPLICATION – RETIREMENT VILLAGE CURRENT SYSTEM (CONTROL) CONTROLLER (NEW SYSTEM) ACCOUNT.

HOW TO ACCOUNT FOR GREATER USAGE ON MONDAY AND

FRIDAY?

USE BLOCKING

• INSTALL CONTROLLER• ACTIVATE FIRST WEEK• DEACTIVATE SECOND WEEK

Page 12: MEASUREMENT OF WATER HEATER EFFICIENCY. MEASURE EFFECTIVENESS APPLICATION – RETIREMENT VILLAGE CURRENT SYSTEM (CONTROL) CONTROLLER (NEW SYSTEM) ACCOUNT.

HOW TO ACCOUNT FOR STANDBY LOSSES?

• USE BLOCKING IN TIME

• EXAMINE EFFECT OF USAGE

Page 13: MEASUREMENT OF WATER HEATER EFFICIENCY. MEASURE EFFECTIVENESS APPLICATION – RETIREMENT VILLAGE CURRENT SYSTEM (CONTROL) CONTROLLER (NEW SYSTEM) ACCOUNT.

RESULTS

Page 14: MEASUREMENT OF WATER HEATER EFFICIENCY. MEASURE EFFECTIVENESS APPLICATION – RETIREMENT VILLAGE CURRENT SYSTEM (CONTROL) CONTROLLER (NEW SYSTEM) ACCOUNT.

CONTROLLER OFF

CONTROLLER OFF

DAY GAS WATER GAS/WATERSCF GAL SCF/GAL

1 3515 3020 1.1642 3356 2830 1.1863 3745 3420 1.0954 3437 3050 1.1275 3617 3300 1.0966 3443 3085 1.1167 3260 3005 1.085

Page 15: MEASUREMENT OF WATER HEATER EFFICIENCY. MEASURE EFFECTIVENESS APPLICATION – RETIREMENT VILLAGE CURRENT SYSTEM (CONTROL) CONTROLLER (NEW SYSTEM) ACCOUNT.

BALANCE CHECK

REASONABLE RESULTS?

CHECK CONSERVATION OF ENERGYEQUATION:

Q

Qout

in

Page 16: MEASUREMENT OF WATER HEATER EFFICIENCY. MEASURE EFFECTIVENESS APPLICATION – RETIREMENT VILLAGE CURRENT SYSTEM (CONTROL) CONTROLLER (NEW SYSTEM) ACCOUNT.

BALANCE CHECK

S E N S I B L E H E A T O F W A T E R P E R G A L L O N :

Qm C T

Vo u tp

Q C To u t p

Page 17: MEASUREMENT OF WATER HEATER EFFICIENCY. MEASURE EFFECTIVENESS APPLICATION – RETIREMENT VILLAGE CURRENT SYSTEM (CONTROL) CONTROLLER (NEW SYSTEM) ACCOUNT.

H E A T I N G V A L U E O F F U E L :

Q V H vi n *

Page 18: MEASUREMENT OF WATER HEATER EFFICIENCY. MEASURE EFFECTIVENESS APPLICATION – RETIREMENT VILLAGE CURRENT SYSTEM (CONTROL) CONTROLLER (NEW SYSTEM) ACCOUNT.

CONTROLLER OFF

CONTROLLER OFF

DAY GAS WATER GAS/WATERSCF GAL SCF/GAL

1 3515 3020 1.1642 3356 2830 1.1863 3745 3420 1.0954 3437 3050 1.1275 3617 3300 1.0966 3443 3085 1.1167 3260 3005 1.085

Page 19: MEASUREMENT OF WATER HEATER EFFICIENCY. MEASURE EFFECTIVENESS APPLICATION – RETIREMENT VILLAGE CURRENT SYSTEM (CONTROL) CONTROLLER (NEW SYSTEM) ACCOUNT.

CALCULATION

Q SCFBtu

SCFin 1164 1000. *

galBtuQin /1164

Page 20: MEASUREMENT OF WATER HEATER EFFICIENCY. MEASURE EFFECTIVENESS APPLICATION – RETIREMENT VILLAGE CURRENT SYSTEM (CONTROL) CONTROLLER (NEW SYSTEM) ACCOUNT.

CALCULATION

Qlbm

gal

Btu

lbm FFout

8 32 1 150 55. * * ( )

QBtu

galout 792

Page 21: MEASUREMENT OF WATER HEATER EFFICIENCY. MEASURE EFFECTIVENESS APPLICATION – RETIREMENT VILLAGE CURRENT SYSTEM (CONTROL) CONTROLLER (NEW SYSTEM) ACCOUNT.

CALCULATION

68%

Page 22: MEASUREMENT OF WATER HEATER EFFICIENCY. MEASURE EFFECTIVENESS APPLICATION – RETIREMENT VILLAGE CURRENT SYSTEM (CONTROL) CONTROLLER (NEW SYSTEM) ACCOUNT.

CONTROLLER ON

CONTROLLER ON

DAY GAS WATER GAS/WATERSCF GAL SCF/GAL

1 3286 3175 1.0352 3247 3370 0.9643 2907 2860 1.0164 3559 3625 0.9825 2672 2550 1.0486 2867 2865 1.0017 3289 3380 0.973

Page 23: MEASUREMENT OF WATER HEATER EFFICIENCY. MEASURE EFFECTIVENESS APPLICATION – RETIREMENT VILLAGE CURRENT SYSTEM (CONTROL) CONTROLLER (NEW SYSTEM) ACCOUNT.

CONTROLLER OFF CONTROLLER ON

DAY GAS WATER GAS/WATERDAY GAS WATER GAS/WATERSCF GAL SCF/GAL SCF GAL SCF/GAL

1 3515 3020 1.164 1 3286 3175 1.0352 3356 2830 1.186 2 3247 3370 0.9643 3745 3420 1.095 3 2907 2860 1.0164 3437 3050 1.127 4 3559 3625 0.9825 3617 3300 1.096 5 2672 2550 1.0486 3443 3085 1.116 6 2867 2865 1.0017 3260 3005 1.085 7 3289 3380 0.973

COUNT 7 AVG 1.124 COUNT 7 AVG 1.003CHAV. 1.8 ST.DEV. 0.038 CHAV. 1.8 ST.DEV. 0.032

OUTLIER MAXIMUM 1.390 OUTLIER MAXIMUM 1.226OUTLIER MINIMUM 0.858 OUTLIER MINIMUM 0.779

Page 24: MEASUREMENT OF WATER HEATER EFFICIENCY. MEASURE EFFECTIVENESS APPLICATION – RETIREMENT VILLAGE CURRENT SYSTEM (CONTROL) CONTROLLER (NEW SYSTEM) ACCOUNT.

t-TEST

OFF ON t-Test: Two-Sample Assuming Equal Variances

GAS/WATERGAS/WATER Variable 1 Variable 2SCF/GAL SCF/GAL Mean 1.124143 1.002586

1.164 1.035 Variance 0.001444 0.0010181.186 0.964 Observations 7 71.095 1.016 Pooled Variance0.0012311.127 0.982 Hypothesized Mean Difference01.096 1.048 df 121.116 1.001 t Stat 6.4813361.085 0.973 P(T<=t) one-tail1.51E-05

t Critical one-tail1.782287P(T<=t) two-tail3.02E-05t Critical two-tail2.178813

Page 25: MEASUREMENT OF WATER HEATER EFFICIENCY. MEASURE EFFECTIVENESS APPLICATION – RETIREMENT VILLAGE CURRENT SYSTEM (CONTROL) CONTROLLER (NEW SYSTEM) ACCOUNT.

EFFECT OF WATER USAGE

0.8

0.85

0.9

0.95

1

1.05

1.1

1.15

1.2

2000 2500 3000 3500 4000

WATER CONSUMPTION

GA

S C

ON

SU

MP

TIO

N

OFF

ON

Page 26: MEASUREMENT OF WATER HEATER EFFICIENCY. MEASURE EFFECTIVENESS APPLICATION – RETIREMENT VILLAGE CURRENT SYSTEM (CONTROL) CONTROLLER (NEW SYSTEM) ACCOUNT.

CONCLUSIONS

• CONTROLLER REDUCES GAS CONSUMPTION BY 11%

• DIFFERENCE IS STATISTICALLY SIGNIFICANTLY

• GAS CONSUMPTION PER GALLON OF HOT WATER REDUCES WITH GREATER CONSUMPTION