Page 1: Mass DEP Waste Site Cleanup Advisory Committee

Mass DEP

Waste Site Cleanup

Advisory Committee

Resolving Vapor Intrusion Challenges via

Automated Continuous Real-Time Monitoring

Blayne Hartman Ph.D.

858-204-6170

www.hartmaneg.com

Page 2: Mass DEP Waste Site Cleanup Advisory Committee

Presentation Summary

• Brief System Description

• IA Temporal Variation

• Applications of Monitoring

Page 3: Mass DEP Waste Site Cleanup Advisory Committee

The Fundamental Problem with VI

Assessments & Remedies:

You Get: With These:

Page 4: Mass DEP Waste Site Cleanup Advisory Committee
Page 5: Mass DEP Waste Site Cleanup Advisory Committee

R

I

N

N N

E

Category: Song

Page 6: Mass DEP Waste Site Cleanup Advisory Committee

Continuous Monitoring System

Sample Inlets 12” High

Page 7: Mass DEP Waste Site Cleanup Advisory Committee

System Capability

• Fully Quantitative! EPA Method TO-14

• Can Reach Ultra-Low Levels (<1 ug/m3) for

TCE, PCE, Vinyl Chloride & others

• <10 min Analysis Time for TCE & PCE

• Multiple Sample Locations (16 to 30)

• Very Stable - holds calibration for months

• Real-Time Data – Web-Based Dashboard

• Discrete Sampling Mode

Page 8: Mass DEP Waste Site Cleanup Advisory Committee

Data

• Concentrations

• Pressure Differential

• Barometric, Temp., Wind Speed, etc.

• Daily Summary Reports (by e-mail)

• Trigger Relays

• User Friendly Dashboard – VOC Conc vs Time

– Contour/Isopleth Images

– Moving Averages

– Plots in Seconds

Page 9: Mass DEP Waste Site Cleanup Advisory Committee

User Friendly Web-Based Data

Page 10: Mass DEP Waste Site Cleanup Advisory Committee

10

Former Dry Cleaner

PCE

BP

WS

Page 12: Mass DEP Waste Site Cleanup Advisory Committee

Simple Set-Up Logistics

• GC Setup – Small footprint (~2’ x 4’ table required)

– Standard wall power (115v)

– Room with some temperature control

• Sampling Lines – Up to 100m from instrument possible

– Small diameter tubing (1/8” or ¼”)

• O&M – Change nitrogen every 3 to 5 months

• Internet Connectivity – Ethernet cable, site Wifi or cellular modem

Page 13: Mass DEP Waste Site Cleanup Advisory Committee

IA Values Are Not Like This

0

10

20

30

40

50

60

70

80

1 21 41 61 81 101 121 141 161 181 201 221 241 261 281 301 321 341 361 381 401 421 441 461 481 501 521 541 561 581

ug

/m

3

Run #

Office Area (P2)

PCE

Time (min)

Page 14: Mass DEP Waste Site Cleanup Advisory Committee

Print Shop Air - PCE– June 2014

0

10

20

30

40

50

60

70

80

1 21 41 61 81 101 121 141 161 181 201 221 241 261 281 301 321 341 361 381 401 421 441 461 481 501 521 541 561 581

ug

/m3

Run #

Office Area (P2)

PCE

10x-15x

Page 15: Mass DEP Waste Site Cleanup Advisory Committee

Freon 11 - Office Bldg – 10 Days

Page 16: Mass DEP Waste Site Cleanup Advisory Committee

0

50

100

150

200

250

300

350

400

450

500

0 50 100 150 200 250 300 350 400 450

tce

Large Industrial Building

20x to 50x

300 ug/m3

Page 17: Mass DEP Waste Site Cleanup Advisory Committee

Determining Exposures to VOCs

How High?

How Often?

For How Long?

Page 18: Mass DEP Waste Site Cleanup Advisory Committee

0

0.5

1

1.5

2

2.5

3

3.5

4

0 50 100 150 200 250 300 350 400 450 500 550 600

Co

nc

(ug

/m

3)

Run Number

PCE - 420 1st Floor Air

PCE

Monitoring Indoor Air VOCs

12/2012 3/2013 1/2013 2/2013

~24 hours

21 days

Page 19: Mass DEP Waste Site Cleanup Advisory Committee

Finding VOC Entry Points

• Discrete Sample Mode: 40-50 samples/day

• Continuous Mode: 16 locations at a time

19 Minimizes False Negatives

Page 20: Mass DEP Waste Site Cleanup Advisory Committee

Time

ug/m3

0

2

4

6

8

10

12

14

16

18

0 10 20 30 40 50 60 70 80 90 100

Room103IndoorAir- TCE(ug/m3)

Room Closed:17:00

Door Opened

8:00 am

Door Closed

8:20 am

VOC Entry Point Determination

15 hours

Page 21: Mass DEP Waste Site Cleanup Advisory Committee

Determining IA vs VI Source

0

10

20

30

40

50

60

70

80

1 21 41 61 81 101 121 141 161 181 201 221 241 261 281 301 321 341 361 381 401 421 441 461 481 501 521 541 561 581

ug

/m3

Run #

Office Area (P2)

PCE

Page 22: Mass DEP Waste Site Cleanup Advisory Committee

Typical Data After 14 Days

0

10

20

30

40

50

60

70

80

1 21 41 61 81 101 121 141 161 181 201 221 241 261 281 301 321 341 361 381 401 421 441 461 481 501 521 541 561 581

ug

/m3

Run #

Office Area (P2)

PCE

15 ug/m3

Page 23: Mass DEP Waste Site Cleanup Advisory Committee

Determining IA vs VI Source

0

50

100

150

200

250

300

350

400

450

500

0 10 20 30 40 50 60 70 80

TCE

TCE

7:00 am 5:00 pm 5:00 pm

7:00 am

5:00 pm

Page 24: Mass DEP Waste Site Cleanup Advisory Committee

Assessing Effectiveness of Remedies

• Can Try Various Remedies & See Effects

24

Can put VI Issue to Rest in Days

Rather than Months or Years!!

– HVAC modifications

– Fans on/off

– Air filtration units

– Sealing sumps & cracks

–Optimizing vapor recovery systems

Page 25: Mass DEP Waste Site Cleanup Advisory Committee

Proving the Effectiveness of a Remedy

SSD System

Page 26: Mass DEP Waste Site Cleanup Advisory Committee

Remedy Effectiveness Air Filtration Units

0

5

10

15

20

25

30

35

40

0 50 100 150 200 250 300 350

Trailer - 1st Floor

TCE

Filters On Filters Off

2 ug/m3

Page 27: Mass DEP Waste Site Cleanup Advisory Committee

0

2

4

6

8

10

12

14

16

18

20

0 50 100 150 200 250

TCE

-B

ZD 2

4 (u

g/m

3)

Run #

Location BZD24

24 vs 22

Remedy Effectiveness

4 ug/m3

14 ug/m3

2/24/17 3/21/17

Seal Sumps

Page 28: Mass DEP Waste Site Cleanup Advisory Committee

Air filtration units off

0

2

4

6

8

10

12

14

16

18

20

0 100 200 300 400

SSD Off

Remedy Effectiveness Residential SSD

Page 29: Mass DEP Waste Site Cleanup Advisory Committee

Determining Cause & Effect

Correlation with Barometric Pressure Change

Correlation with Differential Pressure

Page 30: Mass DEP Waste Site Cleanup Advisory Committee

30

Determining Cause & Effect

PCE

BP

WS

Page 31: Mass DEP Waste Site Cleanup Advisory Committee

Monitoring Remediation

• Remediation & Mitigation System Monitoring

– Thermal Heating - ERH

– In-Situ GW/Soil Remediation - Peroxide

– Sub-Slab Depressurization Systems

31

Page 32: Mass DEP Waste Site Cleanup Advisory Committee

0

10

20

30

40

50

60

70

80

0 20 40 60 80 100 120 140

Vin

yl c

hlo

rid

e (

ug/

m3

)

Run #

Location EF-1 - Vinyl Chloride

Remediation Monitoring Vinyl Chloride Effluent

73 ug/m3

Energized

Before Energized

3/11/17 3/21/17 2/27/17

Page 33: Mass DEP Waste Site Cleanup Advisory Committee

Summary

• High Resolution Data Gives Pattern

• Pattern = Opportunity

• Opportunity to:

– Differentiate Indoor vs Subsurface Source

– Find VOC entry locations, preferential pathways

– Determine best remedy

– Evaluate effectiveness of mitigation systems

– Evaluate effectiveness of remediation systems

Within Days!

Page 34: Mass DEP Waste Site Cleanup Advisory Committee

The Obvious Questions:

• What Does it Cost? $1000 - $2000/day (~$10/analysis)

10 canisters: $5000

• Do Agencies Accept? EPA Regions 1, 9, 10

MA, CA, NH, IN, AZ, OH, Navy

Upcoming: EPA-R5, NC, USACE

• How do Results Compare to TO-15? No complaints to date

Page 35: Mass DEP Waste Site Cleanup Advisory Committee

Blayne Hartman, Ph.D. [email protected]

0

2

4

6

8

10

12

14

16

18

20

0 100 200 300 400