usd2017L394.docx May 1, 2017 Department of Environmental Protection Domestic Wastewater Program DEP DW Shared Mailbox [email protected]Re: Martin County Utilities Tropical Farms WWTF, Facility # FL0043214 Somatic coliphage monitoring report Dear DEP: Attached please see the report and supplemental documents on somatic coliphage monitoring of the Neutralizer biosolids treatment process prepared by BCR Environmental. Submittal of this report is a condition of permit revision FL0043214-016-DW1P-RM, Section VI, Schedules, #3. Coliphage monitoring was performed by BCR for one year subsequent to placing the new Neutralizer process into operation at the facility. If you have any questions, please contact William Thiel, Laboratory Manager, at (772) 223- 7926 or by email [email protected]. Sincerely, Todd Leyland Treatment Plant Operations Administrator TL/wt/cb Enclosures C: Curtis D. Robinson, P.E., Senior Engineer, Holtz Consulting Engineers, Inc., [email protected]Jeff Christian, Environmental Specialist, DEP, [email protected]William Thiel, Laboratory Manager, [email protected]Robert Plummer, Treatment Plant Operations Manager, [email protected]Nino Rodriguez, Chief Plant Operator, [email protected]DOUG SMITH Commissioner, District 1 ED FIELDING Commissioner, District 2 HAROLD E. JENKINS II Commissioner, District 3 SARAH HEARD Commissioner, District 4 EDWARD V. CIAMPI Commissioner, District 5 TARYN KRYZDA, CPM County Administrator SARAH W. WOODS Acting County Attorney TELEPHONE 772-288-5400 WEB ADDRESS http://www.martin.fl.us MARTIN COUNTY BOARD OF COUNTY COMMISSIONERS UTILITIES & SOLID WASTE DEPARTMENT PO Box 9000 Stuart, FL 34995-9000 John E. Polley Director Phone (772) 221-1442 Fax (772) 221-1447 1 of 37
37
Embed
MARTIN COUNTY - documents.martin.fl.us · MARTIN COUNTY BOARD OF COUNTY COMMISSIONERS UTILITIES & SOLID WASTE DEPARTMENT PO Box 9000 Stuart, FL 34995-9000 John E. Polley Director
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
usd2017L394.docx
May 1, 2017
Department of Environmental ProtectionDomestic Wastewater ProgramDEP DW Shared [email protected]
Re: Martin County Utilities Tropical Farms WWTF, Facility # FL0043214Somatic coliphage monitoring report
Dear DEP:
Attached please see the report and supplemental documents on somatic coliphage monitoring of the Neutralizer biosolids treatment process prepared by BCR Environmental. Submittal of this report is a condition of permit revision FL0043214-016-DW1P-RM, Section VI, Schedules, #3.
Coliphage monitoring was performed by BCR for one year subsequent to placing the new Neutralizer process into operation at the facility.
If you have any questions, please contact William Thiel, Laboratory Manager, at (772) 223-7926 or by email [email protected].
4/27/2017 Laura Boczek EPA 26 West Martin Luther King Drive Cincinnati OH 45268 Dear Laura, On November 11th 2010, BCR Environmental submitted an equivalent PFRP process proposal and was approved by the PEC as a process that was equivalent to a PFRP process in accordance with 40 CFR 503.32(a)(8). In order for the Neutralizer to be operating as an equivalent PFRP process, the following conditions must be met:
The Neutralizer process is to be used to treat waste activated sludge with a total solids
concentration less than or equal to 4%
Process Operations must be at a temperature greater than or equal to 15°C (59°F)
Following addition of stage 1 Oxidant (chlorine dioxide) ORP is required to be maintained
at a value greater than or equal to +100 mV ORP with a contact time at +100 mV ORP ≥ 1
hour
Stage 1 treatment is followed by Stage 2 treatment which is defined as Nitrite dose = 1500
mg/L sodium nitrite (NaNO2) with pH during NaNO2 contact time ≤ to 2.3s.u.
ORP during stage 2 must be > +100 mV and nitrite contact time at specified pH and ORP is
at least 6 hours
A limitation on the evaluation of the process was claimed by the EPA because the three facilities that conducted Neutralizer testing were done within the same county (Clay). Therefore, new installations of a Neutralizer process must demonstrate pathogen reduction by verifying somatic coliphage reduction when operating as above. Sampling and analysis of somatic phage must be conducted for a period of at least one year in accordance to the sampling method described at 40 CFR 503.16 (a). This approval letter is attached for your reference. BCR performed this testing over a period of 12 months at North Jenson WWTP (3100 NW Hillman Drive, Jensen Beach, FL 34957) and all analyses resulted in ‘non-detect’ or greater than a 3-log reduction (greater than 99.9% reduction) for somatic phage using ASTM 4994, the test results are summarized below:
2 of 37
North Jensen
Sample Date Raw Treated
10/21/2015 8440 0.9
2/9/2016 5710 ≤2
4/6/2016 3870 ≤3.7
7/12/2016 893 ≤10.1
10/11/2016 846 ≤4.6
BCR also performed five (5) somatic phage tests at Tropical Farms WWTP (8595 SW Kansas Avenue, Stuart, FL 34997) over a period of 12 months in 2015-2016. The table below summarizes these results:
Tropical Farms
Sample Date
Raw (PFU/dry gram)
Treated (PFU/dry gram)
10/21/2015 1580 ≤0.9
1/5/2016 17200 ≤1.2
4/6/2016 5420 ≤3.4
7/12/2016 1380 ≤9.4
10/11/2016 2250 ≤3.7
All samples were taken in accordance with sampling procedures detailed in the Neutralizer Process QAPP, which was previously approved by the PEC. All lab reports are also attached for your review. As BCR Environmental has met the requirements of this monitoring condition as specified in the National Equivalency approval letter dated Nov 16, 2010, we are requesting removal of the somatic phage sampling and analysis provision for the Neutralizer® process at these facilities. Sincerely,
We have completed the analysis of the submitted samples as outlined below.
Following, you will find our report on the results of the analysis coducted on the referenced samples. Should you have any questions, please do not hesitate to contact me.
Sincerely,
George Lukasik, Ph.D. Laboratory Director
Biological Consulting Services
of North Florida, Inc.
Project Name: MCUA Tropical Farms
Analysis Method
Fecal Coliforms MPN EPA 1681; SM 9221E; BCS SOP B-4
Coliphage BCS SOP V-11
Page 1 of 6
Final Report BCS ID 1510295, 1510296, 1510297, 1510298
4609 NW 6th Street, Ste. A, Gainesville, Florida 32609
This report shall not be reproduced, except in full, without the written consent of BCS Laboratories
5 of 37
Client: BCR Environmental
Project Name: MCUA Tropical Farms
Analysis Start: October 23, 2015 11:35
PFU/mL sample analyzed
Secondary Value: 1,580
Analysis: Coliphage
Primary Value: 3,632
Amount Sampled: 50
Qualifier:
Analysis Stop Date: October 24, 2015 15:00
g
PFU /dry gram
Analysis Notes: None
Client Sample ID: TF-Raw BCS Sample ID: 1510295
Sampling Date: October 21, 2015 9:16
Analyst: David Sekora
Percent Solids: 4.6
Date Received: October 23, 2015 9:37 deg C7.9
Biosolids liquid
Ice: NoReceipt Temperature:
Sample Description:
Client: BCR Environmental
Project Name: MCUA Tropical Farms
Analysis Start: October 23, 2015 10:23
Fecal Coliforms MPN/mL sample analyzed
Secondary Value: ≤0.4
Analysis: Fecal Coliforms MPN
Primary Value: ≤0.02
Amount Sampled: 198
Qualifier: U
Analysis Stop Date: October 24, 2015 10:30
mL
Fecal coliforms/dry gram
Analysis Notes: Undetected: Analyte was not detected in the sample analyzed; Value represents the method's detection limit for the amount of sample analyzed as per the method's standard reporting units
This report shall not be reproduced, except in full, without the written consent of BCS Laboratories
6 of 37
Client: BCR Environmental
Project Name: MCUA Tropical Farms
Analysis Start: October 23, 2015 11:35
PFU/mL sample analyzed
Secondary Value: ≤0.9
Analysis: Coliphage
Primary Value: ≤2.00
Amount Sampled: 50
Qualifier: U
Analysis Stop Date: October 24, 2015 15:00
g
PFU /dry gram
Analysis Notes: None; Undetected: Analyte was not detected in the sample analyzed; Value represents the method's detection limit for the amount of sample analyzed as per the method's standard reporting units
This report shall not be reproduced, except in full, without the written consent of BCS Laboratories
7 of 37
Client: BCR Environmental
Project Name: MCUA North Jensen
Analysis Start: October 23, 2015 10:20
Fecal Coliforms MPN/mL sample analyzed
Secondary Value: ≤0.4
Analysis: Fecal Coliforms MPN
Primary Value: ≤0.02
Amount Sampled: 183
Qualifier: U
Analysis Stop Date: October 24, 2015 10:30
mL
Fecal coliforms/dry gram
Analysis Notes: Undetected: Analyte was not detected in the sample analyzed; Value represents the method's detection limit for the amount of sample analyzed as per the method's standard reporting units
Analysis Notes: None; Undetected: Analyte was not detected in the sample analyzed; Value represents the method's detection limit for the amount of sample analyzed as per the method's standard reporting units
This report shall not be reproduced, except in full, without the written consent of BCS Laboratories
8 of 37
I certify that I have personally examined and am familiar with the information submitted herein. Based on my inquiry of those individuals immediately responsible for obtaining the information, I believe the submitted information is true, accurate, and complete. The above results relate only the collected and referenced sample(s) and to their condition at the time of process. The analysis results are not indicative or representative of a process. Sampling and field data information was submitted by the client. The analysis and presented results in this report meet the requirements of The NELAC Institute (TNI), ISO 17025, and The State of Florida Department of Public Health’s Laboratory Certification Program, as applicable unless otherwise noted.
Client: BCR Environmental
Project: MCUA Tropical Farms
Signature of Laboratory Director/Authorized Rep. _________________________ Date: ___________________October 26, 2015
Method Detection Limit: 1 microorganism/ unit weight or volume analyzed
Practical Quantitation Limit: 1 microorganism/ unit weight or volume analyzed
Report Notes: None to report
Page 5 of 6
Final Report BCS ID 1510295, 1510296, 1510297, 1510298
4609 NW 6th Street, Ste. A, Gainesville, Florida 32609
We have completed the analysis of the submitted samples as outlined below.
Following, you will find our report on the results of the analysis conducted on the referenced samples. Should you have any questions, please do not hesitate to contact me.
Sincerely,
George Lukasik, Ph.D. Laboratory Director
Biological Consulting Services
of North Florida, Inc.
Project Name: MCUA Tropical Farms
Analysis Method
Fecal Coliforms MPN EPA 1681; SM 9221E; BCS SOP B-4
Coliphage BCS SOP V-11
Page 1 of 5
Final Report BCS ID 1601008, 1601009
4609 NW 6th Street, Ste. A, Gainesville, Florida 32609
This report shall not be reproduced, except in full, without the written consent of BCS Laboratories
11 of 37
Client: BCR Environmental
Project Name: MCUA Tropical Farms
Analysis Start: January 07, 2016 10:25
PFU/mL sample analyzed
Secondary Value: 17,200
Analysis: Coliphage
Primary Value: 6,068
Amount Sampled: 10.08
Qualifier:
Analysis Stop Date: January 08, 2016 10:08
g
PFU /dry gram
Analysis Notes: None
Client Sample ID: TF-Raw BCS Sample ID: 1601008
Sampling Date: January 05, 2016 15:00
Analyst: David Sekora
Percent Solids: 3.5
Date Received: January 07, 2016 9:38 deg C2.9
Biosolids
Ice: YesReceipt Temperature:
Sample Description:
Client: BCR Environmental
Project Name: MCUA Tropical Farms
Analysis Start: January 07, 2016 10:09
Fecal Coliforms MPN/mL sample analyzed
Secondary Value: ≤0.4
Analysis: Fecal Coliforms MPN
Primary Value: ≤0.02
Amount Sampled: 84
Qualifier: U
Analysis Stop Date: January 08, 2016 9:00
mL
Fecal coliforms/dry gram
Analysis Notes: Undetected: Analyte was not detected in the sample analyzed; Value represents the method's detection limit for the amount of sample analyzed as per the method's standard reporting units
This report shall not be reproduced, except in full, without the written consent of BCS Laboratories
12 of 37
Client: BCR Environmental
Project Name: MCUA Tropical Farms
Analysis Start: January 07, 2016 10:25
PFU/mL sample analyzed
Secondary Value: ≤1.2
Analysis: Coliphage
Primary Value: ≤2.5
Amount Sampled: 50
Qualifier: U
Analysis Stop Date: January 08, 2016 10:08
mL
PFU /dry gram
Analysis Notes: Undetected: Analyte was not detected in the sample analyzed; Value represents the method's detection limit for the amount of sample analyzed as per the method's standard reporting units
This report shall not be reproduced, except in full, without the written consent of BCS Laboratories
13 of 37
I certify that I have personally examined and am familiar with the information submitted herein. The results presented pertain only to the samples analyzed associated identifier number(s). Based on my inquiry of the individuals immediately responsible for obtaining the information, I believe the submitted data are true, accurate, and complete. Sampling field data information was obtained from the submitted sampling documents. The analysis was authorized commissioned by the client. The data provided is strictly representative of the analysis conducted on the material/samples/articles provided by the client (or client’s representative) it’s (their) condition at the time of test. The sample(s) were analyzed in accordance with the method described for each analyte, however due to the inherent limitation(s) of method(s), microorganisms may avoid detection. Thus, BCS Laboratories offers no express or implied warranties concerning the quality, safety, and/or purity of any sample, batch, source, or the process they are derived from. Positive, negative, and blank controls were performed as outlined in the method and as per Good Laboratory Practices. The analysis results presented in this report meet the requirements of The NELAC Institute (TNI), ISO 17025, The State of Florida Department of Public Health’s Laboratory Certification Program, as applicable unless otherwise noted.
Client: BCR Environmental
Project: MCUA Tropical Farms
Signature of Laboratory Director/Authorized Rep. _________________________ Date: ___________________January 13, 2016
Method Detection Limit: 1 microorganism/ unit weight or volume analyzed
Practical Quantitation Limit: 1 microorganism/ unit weight or volume analyzed
Report Notes: None to report
Page 4 of 5
Final Report BCS ID 1601008, 1601009
4609 NW 6th Street, Ste. A, Gainesville, Florida 32609
We have completed the analysis of the submitted samples as outlined below.
Following, you will find our report on the results of the analysis conducted on the referenced samples. Should you have any questions, please do not hesitate to contact me.
Sincerely,
George Lukasik, Ph.D. Laboratory Director
Biological Consulting Services
of North Florida, Inc.
Project Name: Tropical Farms
Analysis Method
Fecal Coliforms MPN EPA 1681; SM 9221E; BCS SOP B-4 (ISO17025 and TNI Accredited)
Coliphage BCS SOP V-11 (ISO17025 and TNI Accredited)
Page 1 of 5
Final Report BCS ID 1604064, 1604065
4609 NW 6th Street, Ste. A, Gainesville, Florida 32609
This report shall not be reproduced, except in full, without the written consent of BCS Laboratories
17 of 37
Client: Nuterra Management
Project Name: Tropical Farms
Analysis Start: April 08, 2016 11:00
PFU/mL sample analyzed
Secondary Value: ≤3.4
Analysis: Coliphage
Primary Value: ≤7.0
Amount Sampled: 50.16
Qualifier: U
Analysis Stop Date: April 09, 2016 9:45
g
PFU /dry gram
Analysis Notes: None; Undetected: Analyte was not detected in the sample analyzed; Value represents the method's detection limit for the amount of sample analyzed as per the method's standard reporting units
This report shall not be reproduced, except in full, without the written consent of BCS Laboratories
18 of 37
I certify that I have personally examined and am familiar with the information submitted herein. The results presented pertain only to the samples analyzed associated identifier number(s). Based on my inquiry of the individuals immediately responsible for obtaining the information, I believe the submitted data are true, accurate, and complete. Sampling field data information was obtained from the submitted sampling documents. The analysis was authorized commissioned by the client. The data provided is strictly representative of the analysis conducted on the material/samples/articles provided by the client (or client’s representative) it’s (their) condition at the time of test. The sample(s) were analyzed in accordance with the method described for each analyte, however due to the inherent limitation(s) of method(s), microorganisms may avoid detection. Thus, BCS Laboratories offers no express or implied warranties concerning the quality, safety, and/or purity of any sample, batch, source, or the process they are derived from. Positive, negative, and blank controls were performed as outlined in the method and as per Good Laboratory Practices. The analysis results presented in this report meet the requirements of The NELAC Institute (TNI), ISO 17025, The State of Florida Department of Public Health’s Laboratory Certification Program, as applicable unless otherwise noted.
Client: Nuterra Management
Project: Tropical Farms
Signature of Laboratory Director/Authorized Rep. _________________________ Date: ___________________April 11, 2016
Method Detection Limit: 1 microorganism/ unit weight or volume analyzed
Practical Quantitation Limit: 1 microorganism/ unit weight or volume analyzed
Report Notes: None to report
Page 4 of 5
Final Report BCS ID 1604064, 1604065
4609 NW 6th Street, Ste. A, Gainesville, Florida 32609
We have completed the analysis of the submitted samples as outlined below.
Following, you will find our report on the results of the analysis conducted on the referenced samples. Should you have any questions, please do not hesitate to contact me.
Sincerely,
Bonnie Mull, MPH Laboratory Operations Manager
Biological Consulting Services
of North Florida, Inc.
Project Name: Tropical Farms
Analysis Method
Fecal Coliforms MPN EPA 1681; SM 9221E; BCS SOP B-4 (ISO17025 and TNI Accredited)
Coliphage (male specific & somatic) Total Coliphage BCS SOP V-11 (ISO17025 and TNI Accredited)
Page 1 of 6Final Report BCS ID 1607091, 1607092
4609 NW 6th Street, Ste. A, Gainesville, Florida 32609
This report shall not be reproduced, except in full, without the written consent of BCS Laboratories
22 of 37
Client: Nuterra Management
Project Name: Tropical Farms
Analysis Start: July 14, 2016 12:11
PFU/mL sample analyzed
Secondary Value: 1,380
Analysis: Coliphage (male specific & somatic)
Primary Value: 3,088
Volume Analyzed: 49.93
Qualifier: None
Analysis Stop Date: July 15, 2016 10:30
g
PFU /dry gram
Analysis Notes: None
Client Sample ID: Tropical Farm/Raw
BCS Sample ID: 1607091
Sample Date/Time: July 12, 2016 12:00
Analyst: David Sekora, M.S.
Percent Solids: 4.5Date Received: July 14, 2016 9:50
deg C2.2
Biosolids
Ice: YesReceipt Temperature:
Sample Description:
Client: Nuterra Management
Project Name: Tropical Farms
Analysis Start: July 14, 2016 10:17
Fecal Coliforms MPN/mL sample analyzed
Secondary Value: ≤0.5
Analysis: Fecal Coliforms MPN
Primary Value: ≤0.02
Volume Analyzed: 97.96
Qualifier: U
Analysis Stop Date: July 15, 2016 9:50
mL
Fecal coliforms/dry gram
Analysis Notes: Undetected: Analyte was not detected in the sample analyzed; Value represents the method's detection limit for the amount of sample analyzed as per the method's standard reporting units
Client Sample ID: Tropical Farm/Treated
BCS Sample ID: 1607092
Sample Date/Time: July 13, 2016 13:00
Analyst: Monique Bessette, MPH
Percent Solids: 3.6Date Received: July 14, 2016 9:50
deg C2.2
Biosolids
Ice: YesReceipt Temperature:
Sample Description:
Page 2 of 6Final Report BCS ID 1607091, 1607092
4609 NW 6th Street, Ste. A, Gainesville, Florida 32609
This report shall not be reproduced, except in full, without the written consent of BCS Laboratories
23 of 37
Client: Nuterra Management
Project Name: Tropical Farms
Analysis Start: July 14, 2016 12:11
PFU/mL sample analyzed
Secondary Value: ≤9.4
Analysis: Coliphage (male specific & somatic)
Primary Value: ≤16.9
Volume Analyzed: 49.97
Qualifier: U
Analysis Stop Date: July 15, 2016 10:30
g
PFU /dry gram
Analysis Notes: Undetected: Analyte was not detected in the sample analyzed; Value represents the method's detection limit for the amount of sample analyzed as per the method's standard reporting units
Client Sample ID: Tropical Farm/Treated
BCS Sample ID: 1607092
Sample Date/Time: July 13, 2016 13:00
Analyst: David Sekora, M.S.
Percent Solids: 3.6Date Received: July 14, 2016 9:50
deg C2.2
Biosolids
Ice: YesReceipt Temperature:
Sample Description:
Page 3 of 6Final Report BCS ID 1607091, 1607092
4609 NW 6th Street, Ste. A, Gainesville, Florida 32609
This report shall not be reproduced, except in full, without the written consent of BCS Laboratories
24 of 37
Client: Nuterra Management
Project: Tropical Farms
Method Detection Limit: 1 microorganism/ unit weight or volume analyzed
Practical Quantitation Limit: 1 microorganism/ unit weight or volume analyzed
Report Notes:
Sample(s) were received well preserved and in excellent condition. Sample(s) were analyzed following receipt as per the described analytical methodology. End of report notes.
Page 4 of 6Final Report BCS ID 1607091, 1607092
4609 NW 6th Street, Ste. A, Gainesville, Florida 32609
This report shall not be reproduced, except in full, without the written consent of BCS Laboratories
25 of 37
I certify that I have examined I am familiar with the information submitted herein. The results pertain only to analyzed sample(s) associated identifier #(s). Based on my inquiry of the individuals responsible for the analysis, I believe the data to be true, accurate, complete. Sampling field data was obtained from submitted documents. The analysis was authorized commissioned by the client. The resulting data are representative of the analysis conducted on the material/samples/articles provided by the client (or client’s representative) it’s/their condition at the time of analysis. The sample(s) were analyzed in accordance with the appropriate method , however due to the inherent limitations of the methods, microorganisms may avoid detection. BCS Laboratories offers no express or implied warranties concerning the quality, safety, and/or purity of any sample, batch, source, or the process they are derived from. Quality assurance controls were performed as outlined in the method and as per Good Laboratory Practices. The analysis results presented in this report meet the requirements of The NELAC Institute (TNI), ISO 17025, and The FL Public Health’s Laboratory Certification Program, as applicable unless otherwise noted.
Signature of Laboratory Director/Authorized Rep. _________________________ Date: ___________________July 15, 2016
Page 5 of 6Final Report BCS ID 1607091, 1607092
4609 NW 6th Street, Ste. A, Gainesville, Florida 32609
We have completed the analysis of the submitted samples as outlined below.
Following, you will find our report on the results of the analysis conducted on the referenced samples. Should you have any questions, please do not hesitate to contact me.
Sincerely,
Bonnie Mull, MPH Laboratory Operations Manager
Biological Consulting Services
of North Florida, Inc.
Project Name: Tropical Farms
Analysis Method
Fecal Coliforms MPN EPA 1681; SM 9221E; BCS SOP B-4 (ISO17025 and TNI Accredited)
Coliphage (male specific & somatic) Total Coliphage BCS SOP V-11 (ISO17025 and TNI Accredited)
Page 1 of 6Final Report BCS ID 1610178, 1610179
4609 NW 6th Street, Ste. A, Gainesville, Florida 32609
This report shall not be reproduced, except in full, without the written consent of BCS Laboratories
29 of 37
Client: Nuterra Management
Project Name: Tropical Farms
Analysis Start: October 13, 2016 11:30
PFU/mL sample analyzed
Secondary Value: 2,250
Analysis: Coliphage (male specific & somatic)
Primary Value: 716
Amount Analyzed: 25.06
Qualifier: None
Analysis Stop Date: October 15, 2016 11:45
g
PFU /dry gram
Analysis Notes: None
Client Sample ID: TF Raw
BCS Sample ID: 1610178
Sample Date/Time: October 11, 2016 9:00
Analyst: David Sekora, M.S.
% Solids: 1.3Date Received: October 13, 2016 9:40
deg C7.6
Biosolids
Preserved: YesReceipt Temperature:
Sample Description:
Amount Submitted:125 ml
Client: Nuterra Management
Project Name: Tropical Farms
Analysis Start: October 13, 2016 10:15
Fecal Coliforms MPN/mL sample analyzed
Secondary Value: ≤4.3
Analysis: Fecal Coliforms MPN
Primary Value: ≤0.18
Amount Analyzed: 109.36
Qualifier: U
Analysis Stop Date: October 13, 2016 10:15
mL
Fecal coliforms/dry gram
Analysis Notes: Undetected: Analyte was not detected in the sample analyzed; Value represents the method's detection limit for the amount of sample analyzed as per the method's standard reporting units
Client Sample ID: TF Treated
BCS Sample ID: 1610179
Sample Date/Time: October 12, 2016 17:00
Analyst: Melanie O'Rourke, B.S.
% Solids: 4.2Date Received: October 13, 2016 9:40
deg C7.6
Biosolids
Preserved: YesReceipt Temperature:
Sample Description:
Amount Submitted:125 ml
Page 2 of 6Final Report BCS ID 1610178, 1610179
4609 NW 6th Street, Ste. A, Gainesville, Florida 32609
This report shall not be reproduced, except in full, without the written consent of BCS Laboratories
30 of 37
Client: Nuterra Management
Project Name: Tropical Farms
Analysis Start: October 13, 2016 11:30
PFU/mL sample analyzed
Secondary Value: ≤3.7
Analysis: Coliphage (male specific & somatic)
Primary Value: ≤3.9
Amount Analyzed: 25.18
Qualifier: U
Analysis Stop Date: October 15, 2016 11:45
g
PFU /dry gram
Analysis Notes: Undetected: Analyte was not detected in the sample analyzed; Value represents the method's detection limit for the amount of sample analyzed as per the method's standard reporting units
Client Sample ID: TF Treated
BCS Sample ID: 1610179
Sample Date/Time: October 12, 2016 17:00
Analyst: David Sekora, M.S.
% Solids: 4.2Date Received: October 13, 2016 9:40
deg C7.6
Biosolids
Preserved: YesReceipt Temperature:
Sample Description:
Amount Submitted:125 ml
Page 3 of 6Final Report BCS ID 1610178, 1610179
4609 NW 6th Street, Ste. A, Gainesville, Florida 32609
This report shall not be reproduced, except in full, without the written consent of BCS Laboratories
31 of 37
Client: Nuterra Management
Project: Tropical Farms
Method Detection Limit: 1 microorganism/ unit weight or volume analyzed
Practical Quantitation Limit: 1 microorganism/ unit weight or volume analyzed
Report Notes:
Sample(s) were received well preserved and in excellent condition. Sample(s) were analyzed following receipt as per the described analytical methodology. End of report notes.
Page 4 of 6Final Report BCS ID 1610178, 1610179
4609 NW 6th Street, Ste. A, Gainesville, Florida 32609
This report shall not be reproduced, except in full, without the written consent of BCS Laboratories
32 of 37
I certify that I have examined I am familiar with the information submitted herein. The results pertain only to analyzed sample(s) associated identifier #(s). Based on my inquiry of the individuals responsible for the analysis, I believe the data to be true, accurate, complete. Sampling field data was obtained from submitted documents. The analysis was authorized commissioned by the client. The resulting data are representative of the analysis conducted on the material/samples/articles provided by the client (or client’s representative) it’s/their condition at the time of analysis. The sample(s) were analyzed in accordance with the appropriate method , however due to the inherent limitations of the methods, microorganisms may avoid detection. BCS Laboratories offers no express or implied warranties concerning the quality, safety, and/or purity of any sample, batch, source, or the process they are derived from. Quality assurance controls were performed as outlined in the method and as per Good Laboratory Practices. The analysis results presented in this report meet the requirements of The NELAC Institute (TNI), ISO 17025, and The FL Public Health’s Laboratory Certification Program, as applicable unless otherwise noted.
Signature of Laboratory Director/Authorized Rep. _________________________ Date: ___________________October 17, 2016
Page 5 of 6Final Report BCS ID 1610178, 1610179