20042 Addendum No. 02 Page 1 of 2 THE SEAL APPEARING ON THIS DOCUMENT WAS AUTHORIZED ADDENDUM NO. 02 BY JUAN CANTU, AIA 28594 Issued: MARCH 5, 2021 DATED MARCH 5, 2021 To Plans and Specifications dated FEBRUARY 12, 2021. SAN CARLOS ELEMENTARY GYMNASIUM ADDITION EDINBURG CISD ERO Project No.: 20042 NOTICE TO PROPOSERS A. Receipt of this Addendum shall be acknowledged on the Proposal Form. B. This Addendum forms part of the Contract documents for the above referenced project and shall be incorporated integrally therewith. C. Each proposer shall make necessary adjustments and submit his proposal with full knowledge of all modifications, clarifications, and supplemental data included therein. Where provisions of the following supplemental data differ from those of the original Contract Documents, this Addendum shall govern. D. This addendum is generally separated into sections for convenience; however, all contractors, subcontractors, material men and other parties shall be responsible for reading the entire addendum. The failure to list an item or items in all affected sections of this addendum does not relieve any party affected from performing as per instructions, providing that the information is set forth one time in this addendum. PROJECT MANUAL Item No. S01 Project Manual, Division 11 – Gymnasium Equipment, Section 11 66 23, Parts 2 Products 2.01 Manufacturer: Acceptable Manufacturer ALLCO Manufacturing Item No. S02 Project Manual, Division 13 – Metal Building Systems, Section 13 34 19, Parts 2 Products 2.01 Manufacturer: Acceptable Manufacturer Strong Structural Steel, Ltd. Item No. S03 Project Manual, Division 26 – Lighting Controls, Section 26 09 23, Parts 2 Products 2.01 Manufacturers: Acceptable Manufacturer Replace specifications in its entirety. Refer to attachment. PLANS Item No. P01 Sheet MP01 – MECHANICAL FLOOR PLAN – Replace this sheet in its entirety. 1. Main return air grilles changed in size to 36”x20” 2. Added keyed notes to: a) Office A113 transfer grille into Gymnasium A101. b) Supply air devices serving Storage A114. 3. Revised keyed notes for fabric duct, outside duct, and outside duct stands. Item No. P02 Sheet MP02 – MECHANICAL SECTIONS – Replace this sheet in its entirety. 1. Revised sections in relation to above mentioned grilles and keyed notes 0 03.05.21
27
Embed
MARCH 5, 2021 DATED MARCH 5, 2021 - ECISD Addendum 2.pdfFeb 24, 2021 · 20042 Addendum No. 02 Page 1 of 2 THE SEAL APPEARING ON THIS DOCUMENT WAS AUTHORIZED ADDENDUM NO. 02 BY JUAN
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
20042 Addendum No. 02 Page 1 of 2
THE SEAL APPEARING ON THIS
DOCUMENT WAS AUTHORIZED
ADDENDUM NO. 02 BY JUAN CANTU, AIA 28594
Issued: MARCH 5, 2021 DATED MARCH 5, 2021
To Plans and Specifications dated FEBRUARY 12, 2021. SAN CARLOS ELEMENTARY GYMNASIUM ADDITION EDINBURG CISD ERO Project No.: 20042 NOTICE TO PROPOSERS A. Receipt of this Addendum shall be acknowledged on the Proposal Form. B. This Addendum forms part of the Contract documents for the above referenced project and shall be
incorporated integrally therewith. C. Each proposer shall make necessary adjustments and submit his proposal with full knowledge of all
modifications, clarifications, and supplemental data included therein. Where provisions of the following supplemental data differ from those of the original Contract Documents, this Addendum shall govern.
D. This addendum is generally separated into sections for convenience; however, all contractors, subcontractors, material men and other parties shall be responsible for reading the entire addendum. The failure to list an item or items in all affected sections of this addendum does not relieve any party affected from performing as per instructions, providing that the information is set forth one time in this addendum.
Manufacturers: Acceptable Manufacturer Replace specifications in its entirety. Refer to attachment.
PLANS
Item No. P01 Sheet MP01 – MECHANICAL FLOOR PLAN – Replace this sheet in its entirety.
1. Main return air grilles changed in size to 36”x20” 2. Added keyed notes to:
a) Office A113 transfer grille into Gymnasium A101. b) Supply air devices serving Storage A114.
3. Revised keyed notes for fabric duct, outside duct, and outside duct stands.
Item No. P02 Sheet MP02 – MECHANICAL SECTIONS – Replace this sheet in its entirety. 1. Revised sections in relation to above mentioned grilles and keyed notes
02.26.2103.05.21
20042 Addendum No. 02 Page 2 of 2
Item No. P03 Sheet EG01 – ELECTRICAL LEGEND – Replace this sheet in its entirety. 1. Lighting electrical information was modified to match model number. Lighting Fixture
Schedule Notes: Lighting Manufacturers that can be used as acceptable manufactures was modified. Acceptable lighting manufacturers are as follows: Refer to attached.
Item No. P04 Sheet EL01 – ELECTRICAL FLOOR PLAN – Replace this sheet in its entirety. 1. Data drops were added with mounting heights with revised keyed notes. All locations and
mounting heights shall be coordinated with owner/district prior to installation. 2. Speaker infrastructure was added. Refer to attachment. 3. General note added to coordinate all new electrical devices shown in plan with owner/district.
Refer to attachment. 4. Disconnect location for stepdown transformer is now shown on plans. 5. Detail #1 Electrical lighting plan, All light switches shall include a 277V circuit for the lighting
controls. The circuit shall be H-42. Provide1-20Amp 1- pole breaker, wiring shall be 2#10, 1#10G, ¾”C.
Item No. P05 Sheet ER01 – ELECTRICAL RISER – Replace this sheet in its entirety. 1. Wiring for SPD shall be 4#10, 1#10G, ¾”C and wiring for H-11 shall be 2#10, 1#10G, ¾”C
was added. Refer to attachment.
END OF ADDENDUM NO. 2 (25 pages of Attachments Follow)
Architect: ERO Architects Project Name: San Carlos Gymnasium Addition Project Number: 20.4.18 Date: 3/5/2021
Note: The work shall be carried out in accordance with the following supplemental instructions issued in accordance with the Contract Documents without change in Contract Sum or Contract Time Proceeding with the Work in accordance with these instructions indicates your acknowledgement that there will be no change in the Contract Sum or Contract Time.
I. Specifications:
A. Section 260923 – Lighting Control added acceptable manufacturers, refer to
attachment.
II. General: N/A
III. Mechanical:
A. Sheet MP01 – the following revisions were made to this sheet, refer to attached:
1. Main return air grilles changed in size to 36”x20”.
2. Added keyed notes to:
a. OFFICE A113 transfer grille into GYMNASIUM A101.
b. Supply air devices serving STORAGE A114.
3. Revised keyed notes for fabric duct, outside duct, and outside duct
stands.
B. Sheet MP02 – revised sections in relation to above mentioned grilles and keyed
notes.
IV. Electrical:
A. Sheet EL01 – Data drops were added with mounting heights with revised keyed
notes. All Devices locations and mounting heights shall be coordinated with
owner/district prior any installations. Refer to attachment.
B. Sheet EL01 – Speaker infrastructure was added. Refer to attachment.
C. Sheet EL01 – General note added to coordinate all new electrical devices shown
in plan with owner/district. Refer to attachment.
D. Sheet EL01- Disconnect location for stepdown transformer is now shown on plans.
authorized Service Representative to conduct site visit upon completion of lighting
control system installation to perform system startup and verify proper operation:
ISSUE FOR BIDDING AND CONSTRUCTION 02/12/2021
SAN CARLOS ELEMENTARY GYM ADDITION
EDINBURG CONSOLIDATED INDEPENDENT SCHOOL DISTRICT
Edinburg, Texas 17 of 18
TRINITY MEP ENGINEERING, LLC
260923 Lighting Controls
a. Where Lighting Control Manufacturer Sensor Layout and Tuning service is
specified in Part 2 under "LIGHTING CONTROLS - GENERAL
REQUIREMENTS", authorized Service Representative to verify sensor
locations, in accordance with layout provided by Lighting Control
Manufacturer; Lighting Control Manufacturer may direct Contractor regarding
sensor relocation should conditions require a deviation from locations
indicated.
b. Verify connection of power wiring and load circuits.
c. Verify connection and location of controls.
d. Energize wireless hubs.
e. Associate occupancy/vacancy sensors, daylight sensors, wireless remotes, and
wall stations to load control devices.
f. Provide initial rough calibration of sensors; fine-tuning of sensors is
responsibility of Contractor unless provided by Lighting Control Manufacturer
as part of Sensor Layout and Tuning service where specified in Part 2 under
"LIGHTING CONTROLS - GENERAL REQUIREMENTS".
g. Program timeclock schedules per approved sequence of operations.
h. Configure load shed parameters per approved sequence of operations.
i. Verify system operation control by control.
j. Obtain sign-off on system functions.
k. Train Owner's representative on system capabilities, operation, and
maintenance, as specified in Part 3 under "Closeout Activities".
E. Correct defective work, adjust for proper operation, and retest until entire system complies
with contract documents.
3.05 ADJUSTING
A. On-Site Scene and Level Tuning; Lutron LSC-AF-VISIT: Include additional costs for
Lighting Control Manufacturer to visit site to conduct meeting with Owner's
representative; to make required lighting adjustments to the system for conformance with
original design intent.
B. Sensor Fine-Tuning: Where Lighting Control Manufacturer Sensor Layout and Tuning
service is specified in Part 2 under "LIGHTING CONTROLS - GENERAL
REQUIREMENTS", Lighting Control Manufacturer to provide up to two additional post-
startup on-site service visits for fine-tuning of sensor calibration. Where Lighting Control
Manufacturer Sensor Layout and Tuning service is not specified, Contractor to provide fine-
tuning of sensor calibration.
3.06 CLEANING
A. Clean exposed surfaces to remove dirt, paint, or other foreign material and restore to match
original factory finish.
3.07 COMMISSIONING
A. Title 24 Acceptance Testing Service; Lutron LSC-SPV-DOC-T24: Include additional costs
for Lighting Control Manufacturer to perform lighting control acceptance testing in
accordance with CAL TITLE 24 P6. Submit required documentation.
3.08 CLOSEOUT ACTIVITIES
A. See Section - Closeout Submittals, for closeout submittals.
B. See Section - Demonstration and Training, for additional requirements.
C. Demonstration:
ISSUE FOR BIDDING AND CONSTRUCTION 02/12/2021
SAN CARLOS ELEMENTARY GYM ADDITION
EDINBURG CONSOLIDATED INDEPENDENT SCHOOL DISTRICT
Edinburg, Texas 18 of 18
TRINITY MEP ENGINEERING, LLC
260923 Lighting Controls
1. Demonstrate proper operation of lighting control devices to Engineer / Owner, and
correct deficiencies or make adjustments as directed.
2. On-Site Performance-Verification Walkthrough; Lutron LSC-WALK: Include
additional costs for lighting control manufacturer to provide on-site demonstration of
system functionality to facility representative.
D. Training:
1. Include services of manufacturer's certified service representative to perform on-site
training of Owner's personnel on operation, adjustment, and maintenance of lighting
control system as part of on-site system start-up services.
2. Customer-Site Solution Training Visit; Lutron LSC-TRAINING-SP: Include
additional costs for Lighting Control Manufacturer to provide one day(s) of additional
on-site system training.
E. On-Site Warranty Audit Visit; Lutron LSC-WNTY-AUD: Where Manufacturer On-Site
Full-Scope Start-Up Service is not provided, include services of manufacturer to perform on-
site verification that system meets manufacturer’s requirements as necessary for validation
of specified enhanced warranty.
3.09 MAINTENANCE
A. See Section – Execution and Closeout Requirements, for additional requirements relating
to maintenance service.
B. System Optimization Visit; Lutron LSC-SYSOPT-SP: Include additional costs for Lighting
Control System Manufacturer to visit site six months after system start-up to evaluate
system usage and discuss opportunities to make efficiency improvements that will fit with
the current use of the facility.
3.10 PROTECTION
A. Protect installed products from subsequent construction operations.
END OF SECTION
GENERAL DEMOLITION NOTESA. THE EXTENT OF DEMOLITION WORK IS INDICATED ON THE ARCHITECTURAL DRAWINGS AND BY THE
REQUIREMENTS OF THIS SECTION. A VISIT TO THE SITE WILL BE REQUIRED TO PROPERLY BID THEDEMOLITION WORK.
B. PROVIDE ALL DEMOLITION WORK REQUIRED FOR THE REMOVAL AND/OR RELOCATION OF HVACFIXTURES AND EQUIPMENTS AND ASSOCIATED SERVICES TO PROVIDE A COMPLETE AND OPERABLESYSTEM UPON COMPLETION OF THE PROJECT.
C. MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE TO REVIEW THE ARCHITECTURAL DOCUMENTS INADDITION TO THE DIVISION 15 AND 16 DOCUMENTS TO DETERMINE THE COMPLETE SCOPE OF WORK.
D. WHERE EQUIPMENT IS INDICATED OR REQUIRED TO BE REMOVED, THE ASSOCIATED SERVICES SHALL BECAPPED AT A CONCEALED LOCATION.
E. WHERE SERVICES RUN ABOVE INACCESSIBLE CEILINGS OR IN WALLS WHICH ARE TO REMAINUNDISTURBED, SERVICES SHALL BE CAPPED AT CONCEALED LOCATION AND ABANDONED
F. WHERE THE REMOVAL OF EQUIPMENT RENDERS EQUIPMENT DOWNSTREAM INOPERABLE, SERVICESSHALL BE EXTENDED TO THE DOWNSTREAM EQUIPMENT SO THAT THE FIXTURES ARE LEFT IN OPERATINGCONDITION.
G. COORDINATE DEMOLITION OF DIVISION 15 SYSTEMS AS REQUIRED WITH ALL OTHER TRADES.
H. ALL EXISTING H.V.A.C. AND EQUIPMENT REMOVED DURING CONSTRUCTION THAT ARE NOT TO BEREUSED SHALL BE REMOVED FROM THE JOB SITE AND PROPERLY RETURNED TO THE OWNER, IF DESIREDBY OWNER.
I. WHERE EXISTING EQUIPMENT IS TO BE RELOCATED, BE CAUTIOUS TO PREVENT DAMAGE DURING THEREMOVAL AND REINSTALLATION. WHERE DAMAGE OCCURS, THE EQUIPMENT SHALL BE REPLACED ORREPAIRED TO THE SATISFACTION AND APPROVAL OF THE ARCHITECT AT NO ADDITIONAL COST TO THEOWNER.
J. EXISTING EQUIPMENT TO BE REUSED SHALL BE CLEANED AND REPAIRED AT THE DISCRETION OF THEARCHITECT WHERE APPLICABLE.
K. ALL DEVICES ATTACHED TO WALLS OR CEILINGS SHALL BE REMOVED PER DEMOLITION NOTE A - LWHETHER SHOWN ON DRAWINGS OR NOT.
GYMNASIUMA101
GIRLSA108
JANITORA109
VESTIBULEA110
BOYSA111
FACULTY TOILETA112
OFFICEA113
STORAGEA114
2MP02
3MP02
8"ø
B 125
6"ø
B 756"ø
A 75
8"ø
B 125
8"ø
B 125
8"ø
A 150
8"ø
A 150
34"x16"
34"x16"
34"x16"
24"ø24"ø
24"ø24"ø
DXPU-1
DXPU-2
12"x
12"
10"x
10"
36"x20"
E 4000
36"x20"
E 4000
1MP02
T
T
18"x6"
D 350
EF-1
EF-2
EF-3
EF-4
8"ø
6"ø
6"ø
18"x6"
E 300
10"ø
C 300
10"ø
24"x12"L-124/12
8"x6
"
8"x6"
34"x16"
16"x
34"
34"x16"
18"x6"
E 350
1
1
2
2
3
3
3
44
4 4
5
5
5
5
6
6
6
67
7
8
8
9
10
11
10
11
12
12
13
14
14
15
14
14
14
14
14
14
15
1515
1616
LA ENOIS N
121939
F
N
PR
SCEF
LI
O
E
ATTE
S
O
ER
INSG
EED
S
TEXA
Wilford L. McGee III
MEP ENGINEERING3533 Moreland Dr. Ste A l Weslaco, Tx78596 p:956.973.0500 l f:956-351-5750www.trinitymep.com I Copyright 2020Texas Registered Engineering Firm - F10362Project number:
PROJECT NO.:ISSUE DATE:
Project Status:
A Sheet Number
SHEET NAME
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19
B
C
D
E
F
G
H
J
K
L
M
N
P
DRAWN BY:CHECKED BY:
300 S. 8th Street, McAllen, Tx 78501T 956-661-0400 | goero.com
No.
Date
Desc
riptio
n
Q
R
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19
BIM
360
://20
042
San
Car
los
Gym
Add
ition
/20.
4.18
_Sam
Car
los
Gym
Adi
ttion
_CEN
TRAL
_202
0.rv
t3/
5/20
21 2
:58:
33 P
M
MP01
MECHANICAL FLOOR PLAN
2004203.05.21
100% CONSTRUCTION DOCUMENTS
AuthorChecker
SAN
CARL
OS G
YMNA
SIUM
ADD
ITION
505 S
. 83R
D ST
, EDI
NBUR
G TX
7853
9ED
INBU
RG C
ONSO
LIDAT
ED IN
DEPE
NDEN
T SCH
OOL D
ISTR
ICT
03.05.21
1/8" = 1'-0"1 MECHANICAL FLOOR PLAN
MECHANICAL KEYED NOTES
1 CONTROLS FOR A/C UNIT WILL BE BY MEANS OF A 24 VOLT 7-DAY PROGRAMMABLE THERMOSTAT WITH HEAT-OFF-COOL ANDFAN ON-AUTO CAPABILITIES SHOWN ON A DIGITAL DISPLAY. MOUNT THERMOSTAT AT 48" ABOVE FINISHED FLOOR. PROVIDEWITH KEYED CLEAR PLASTIC COVER. TO BE WEB ENABLED. TO HAVE OCCUPANCY SENSOR/ TEMPERATURE SETBACK. TO BE"HONEYWELL VISION PRO 8000 SERIES WITH REDLINK, MODEL NUMBER:TH8320R1003" OR EQUAL.
2 UNIT TO BE MOUNTED ON A METAL FRAME PLATFORM, 36" HIGH. REFER TO DETAILS.3 ROUND EXHAUST DUCT OUT TO LOUVER.4 FABRIC DUCT TO BE EQUAL TO "DUCTSOX TUFTEX". PROVIDE W/ HIGH FLOW ORIFICES TO DISPERSE 3500 CFM THROUGH ENTIRE
LENGTH OF DUCT. DUCT TO BE SUSPENDED W/ SUSPENDED H-TRACK CONNECTING TO A 3X1 SUSPENSION SYSTEM TO HANGFROM ABOVE, OR EQUAL. INDICATED SECTION OF FABRIC DUCT TO HAVE THROW @ 45 DEGREES BELOW HORIZON.
5 OUTDOOR DUCT INSULATION (CLOSED CELL FLEXIBLE ELASTOMERIC INSULATION); 1 INCH THICK MATERIAL THAT HAS A SERVICETEMPERATURE RANGE FROM -60 DEGREES F TO 180 DEGREES F.
6 THE INSULATION AND OUTSIDE SURFACE MUST BE PROTECTED WITH A WHITE THERMO PLASTIC RUBBER MEMBRANEFORMULATED TO: 1. BE RESISTANT TO UV, AND OZONE, ACID RAIN, AND PHYSICAL ELEMENTS PRODUCED FROM OUTDOORWEATHER PER ASTM E 96 PROCEDURE A. 2. HAVE AFLAME SPREAD RATING OF 25 OR LESS AND A SMOKE DEVELOPED RATINGOF 50 OR LESS WHEN TESTED IN ACCORDANCE WITH THE TEST METHOD FOR SURFACE BURNING IN ASTM E 84. 3. SHOW NOEVIDENCE OF CONTINUED EROSION, DELAMINATING, CRACKING, FLAKING, OR PEELING WHEN TESTED IN ACCORDANCE WITHTHE TEST METHOD FOR EROSION RESISTANCE IN UL181. BE RESISTANT TO MOLD GROWTH RESISTANCE, ASTM G 21/C 1338RESISTANT TO FUNGI, AND RESISTANT TO BACTERIA GROWTH PER ASTM G 22. 4. SHALL BE EQUAL TO "THERMADUCT, R-8 INBOTH CONSTRUCTION INTEGRITY AND INSULATIVE VALUES OR BETTER.
7 PROVIDE W/ ROUND ESCUTCHEON PLATE WHERE ROUND DUCT PENETRATES WALL.8 MOUNT UNIT OVER A 6" CONCRETE PAD.9 COORDINATE LOCATION OF LOUVERS TO NOT CONFLICT WITH CONTROL JOINTS AND DOWNSPOUTS.10 PROVICE W/ DUCT SUPPORT STANDS. EQUAL TO 'MICRO IND. 6DS-P' PROVIDE W/ TAP FRAME TO ENCLOSE DUCT. COORDINATE
W/ STRUCTURAL ENGINEER FOR ANCHORING.11 PROVIDE W/ DUCT SUPPORTS ON WALL. EQUAL TO 'MICRO IND. 6DS-HDG' PROVIDE W/ ACCESSORY SUPPORT PAD UNDER
POLYBASE SPACE AS PER DUCT SUPPORT MANUFACTURER RECOMMENDATIONS. (4' SPACING RECOMMENDED)12 CONTRACTOR TO COORDINATE POSSIBLE CONFLICTS WITH ACOUSTIC PANELS.
1/8" = 1'-0"2 MECHANICAL DEMO PLAN
MECHANICAL DEMOLITION NOTES
14 DEMOLISH AND REMOVE EXISTING SUPPLY AIR AND RETURN AIR DUCTWORK.15 RETURN INDICATED EQUIPMENT TO OWNER.16 REMOVE ALL DUCTWORK, AIR DEVICES, AND ASSOCIATED ACCESSORIES AND HARDWARE AND RETURN TO
OWNER IF OWNER SO DESIRES.
203
/05/
202 1
ADD
END
UM
#2
2
2
2
2
22
2 2
2
2
2
2
2
22
22
2
2
2
2
2
2
F.F.100' - 0"
F.F.100' - 0"
1 2
EXT. EAVE114' - 0"
NEW EAVE111' - 8"
33
MP02
24"ø
24"ø
DXPU-21
2
3
4
GIRLSA108
GYMNASIUMA101
16"x34"
16"x
34"
5
5
6
36"x20"
E 4000
8"ø
B 125EF-1
2
7
7
8
F.F.100' - 0"
F.F.100' - 0"
1 2
EXT. EAVE114' - 0"
NEW EAVE111' - 8"
33
MP02
24"ø 24"ø
16"x
34"
DXPU-1
36"x20"
E 4000
16"x34"
18"x6"
D 350
18"x6"
E 350
STORAGEA114
GYMNASIUMA101
4
1
6
5
5
2 7
9
83
F.F.100' - 0"
ROOF PLAN130' - 0"
F.F.100' - 0"
ABCDE
EXT. EAVE114' - 0"
NEW EAVE111' - 8"
2MP02
1MP02
12"x12"10"x10"
18"x6"
D 350 18"x6"
E 350
34"x16"34"x16"
GIRLSA108
VESTIBULEA110
BOYSA111
FACULTY TOILETA112
OFFICEA113
STORAGEA114
8"x18"
34"x16" 34"x16"
9
LA ENOIS N
121939
F
N
PR
SCEF
LI
O
E
ATTE
S
O
ER
INSG
EED
S
TEXA
Wilford L. McGee III
MEP ENGINEERING3533 Moreland Dr. Ste A l Weslaco, Tx78596 p:956.973.0500 l f:956-351-5750www.trinitymep.com I Copyright 2020Texas Registered Engineering Firm - F10362Project number:
PROJECT NO.:ISSUE DATE:
Project Status:
A Sheet Number
SHEET NAME
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19
B
C
D
E
F
G
H
J
K
L
M
N
P
DRAWN BY:CHECKED BY:
300 S. 8th Street, McAllen, Tx 78501T 956-661-0400 | goero.com
No.
Date
Desc
riptio
n
Q
R
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19
BIM
360
://20
042
San
Car
los
Gym
Add
ition
/20.
4.18
_Sam
Car
los
Gym
Adi
ttion
_CEN
TRAL
_202
0.rv
t3/
5/20
21 2
:58:
37 P
M
MP02
MECHANICAL SECTIONS
2004203.05.21
100% CONSTRUCTION DOCUMENTS
AuthorChecker
SAN
CARL
OS G
YMNA
SIUM
ADD
ITION
505 S
. 83R
D ST
, EDI
NBUR
G TX
7853
9ED
INBU
RG C
ONSO
LIDAT
ED IN
DEPE
NDEN
T SCH
OOL D
ISTR
ICT
03.05.21
1/4" = 1'-0"1 Section 1
1/4" = 1'-0"2 Section 2
1/4" = 1'-0"3 Section 3
MECHANICAL KEYED NOTES
1 UNIT TO BE MOUNTED ON A METAL FRAME PLATFORM, 36" HIGH. REFER TO DETAILS.2 OUTDOOR DUCT INSULATION (CLOSED CELL FLEXIBLE ELASTOMERIC INSULATION); 1
INCH THICK MATERIAL THAT HAS A SERVICE TEMPERATURE RANGE FROM -60 DEGREESF TO 180 DEGREES F.
3 FABRIC DUCT TO BE EQUAL TO "DUCTSOX TUFTEX". PROVIDE W/ HIGH FLOW ORIFICESTO DISPERSE 3500 CFM THROUGH ENTIRE LENGTH OF DUCT. DUCT TO BE SUSPENDEDW/ SUSPENDED H-TRACK CONNECTING TO A 3X1 SUSPENSION SYSTEM TO HANG FROMABOVE, OR EQUAL. INDICATED SECTION OF FABRIC DUCT TO HAVE THROW @ 45DEGREES BELOW HORIZON.
4 MOUNT UNIT OVER A 6" CONCRETE PAD.5 PROVIDE W/ DUCT SUPPORTS ON WALL. EQUAL TO 'MICRO IND. 6DS-HDG' PROVIDE W/
ACCESSORY SUPPORT PAD UNDER POLYBASE SPACE AS PER DUCT SUPPORTMANUFACTURER RECOMMENDATIONS. (4' SPACING RECOMMENDED)
6 PROVICE W/ DUCT SUPPORT STANDS. EQUAL TO 'MICRO IND. 6DS-P' PROVIDE W/ TAPFRAME TO ENCLOSE DUCT. COORDINATE W/ STRUCTURAL ENGINEER FOR ANCHORING.
7 THE INSULATION AND OUTSIDE SURFACE MUST BE PROTECTED WITH A WHITE THERMOPLASTIC RUBBER MEMBRANE FORMULATED TO: 1. BE RESISTANT TO UV, AND OZONE,ACID RAIN, AND PHYSICAL ELEMENTS PRODUCED FROM OUTDOOR WEATHER PER ASTME 96 PROCEDURE A. 2. HAVE AFLAME SPREAD RATING OF 25 OR LESS AND A SMOKEDEVELOPED RATING OF 50 OR LESS WHEN TESTED IN ACCORDANCE WITH THE TESTMETHOD FOR SURFACE BURNING IN ASTM E 84. 3. SHOW NO EVIDENCE OF CONTINUEDEROSION, DELAMINATING, CRACKING, FLAKING, OR PEELING WHEN TESTED INACCORDANCE WITH THE TEST METHOD FOR EROSION RESISTANCE IN UL181. BERESISTANT TO MOLD GROWTH RESISTANCE, ASTM G 21/C 1338 RESISTANT TO FUNGI,AND RESISTANT TO BACTERIA GROWTH PER ASTM G 22. 4. SHALL BE EQUAL TO"THERMADUCT, R-8 IN BOTH CONSTRUCTION INTEGRITY AND INSULATIVE VALUES ORBETTER.
8 PROVIDE W/ ROUND ESCUTCHEON PLATE WHERE ROUND DUCT PENETRATES WALL.9 MOUNT/TAP SA DEVICE OFF BOTTOM OF SA DUCT.
203
/05/
202 1
ADD
END
UM
#2
2
2
2
2
2
2
2
2
2
J
X, X, XX/X/X
SEC
ACC
GENERAL ELECTRICAL NOTES
c
CR
ML
S
C
C
KP
G
MD
DC
I
S
ICIC
av
TV TV
HD
T
#
#
P
S
SD SD
D
A
SYMBOL DESCRIPTION
ELECTRICAL LEGEND-LIGHTING
SYMBOL DESCRIPTION
ELECTRICAL LEGEND-SPECIAL SYSTEMS
SYMBOL DESCRIPTION
ELECTRICAL LEGEND-FIRE ALARM
SYMBOL DESCRIPTION
ELECTRICAL LEGEND-GENERAL
MOUNTING HEIGHT DETAIL
DESCRIPTIONELECTRICAL ABBREVIATIONS:
ABBV:
ELECTRICAL LEGEND -WIRING DEVICES
DESCRIPTIONABBV:
S
S
S
S
S
S
S
CP-1
S
S
M
J
PC
LC
TC
K
P
2
3
D
4
EXIT LIGHT SAME AS ABOVE, EXCEPT WITH AN EMERGENCY UNIT AS
LED, FLUORESCENT, OR HID FIXTURE WITH EMERGENCY BATTERY PACK.
2'X2' LIGHT FIXTURE W/EMERGENCY BATTERY PACK, REFER TO LUMINAIRE SCHEDULE
2'X4' LIGHT FIXTURE W/EMERGENCY BATTERY PACK, REFER TO LUMINAIRE SCHEDULE
TRACK LIGHT WITH HEADS AS INDICATED
INCANDESCENT, LED, FLUORESCENT, OR HID FIXTURE CLG. OR WALL MTD,
INCANDESCENT, LED, FLUORESCENT, OR HID WALL WASHER LIGHT
STRIP UTILITY STRIP LIGHT WITH EMERGENCY BATTERY PACK,
EXIT LIGHT, CEILING OR WALL MOUNTED - SHADING INDICATINGSINGLE OR DOUBLE FACE; DIRECTIONAL ARROWS AS INDICATED
---ALL SYMBOLS SHOWN MAY NOT APPEAR IN ALL DRAWINGS.SYMBOLS ARE SHOWN SCHEMATIC AND MAY NOT BE TO SCALE.
DOUBLE POLE TOGGLE SWITCH, 20A/120/277V
WALL DIMMER SWITCH
4-WAY WALL SWITCH, 20A,120/277V
3-WAY WALL SWITCH, 20A,120/277V
WALL SWITCH SPST, 20A,120/277V
STRIP UTILITY LIGHT FIXTURE, REFER TO LUMINAIRE SCHEDULE
CLG. OR WALL MTD, REFER TO LUMINAIRE SCHEDULE
2'x2' LIGHT FIXTURE, REFER TO LUMINAIRE SCHEDULE
FIXTURE CEILING MTD, REFER TO LUMINAIRE SCHEDULE
1'X4' LIGHT FIXTURE, REFER TO LUMINAIRE SCHEDULE
2'x4' LIGHT FIXTURE, REFER TO LUMINAIRE SCHEDULE
A COMBO, REFER TO LUMINAIRE SCHEDULE
CEILING FAN
WALL SWITCH SPST, 20A,120/277V - PILOT LIGHT SWITCH
WALL SWITCH SPST, 20A,120/277V - KEYED SWITCH, X = 3 OR 4 WAY
REFER TO LUMINAIRE SCHEDULE
REFER TO LUMINAIRE SCHEDULE
REFER TO LUMINAIRE SCHEDULE
HEAVY DUTY COMBINATION DISCONNECT/MOTOR STARTER
THERMOSTAT WALL MOUNTED - STUB 1/2"C ABOVE CEILING FROMOUTLET BOX. COORDINATE EXACT LOCATION AND HEIGHT WITH
OR INSULATED GROUND. ALPHANUMERIC DESCRIPTION INDICATES
HATCH INDICATES NEUTRAL CONDUCTOR, LONG HATCHES INDICATEUNDERGROUND CONDUIT AND WIRE HOMERUN TO PANEL. SHORT
INDICATES NEUTRAL CONDUCTOR, LONG HATCHES INDICATE PHASECONDUCTORS, AND LONG HATCH WITH CIRCLE INDICATES ISOLATES
ISOLATED OR INSULATED GROUND. ALPHANUMERIC DESCRIPTIONPHASE CONDUCTORS, AND LONG HATCH WITH CIRCLE INDICATES
CONDUIT AND WIRE HOMERUN TO PANEL. SHORT HATCH
WALL MOUNTED TELEPHONE/DATA OUTLET. FURNISH AND INSTALL1.25"C., WITH PULLSTRING AND INSULATED BUSHING, STUBBED ABOVE CEILING.+24" UNLESS OTHERWISE NOTE. BOX TO BE MINIMUM 2 1/8" DEEP.
WALL MOUNTED TELEPHONE OUTLET. FURNISH AND INSTALL 1"C, WITH PULLSTRING AND INSULATED BUSHING, STUBBED ABOVE CEILING.
+24" UNLESS OTHERWISE NOTE. BOX TO BE MINIMUM 2 1/8" DEEP., WITH PULLSTRING AND INSULATED BUSHING, STUBBED ABOVE CEILING.WALL MOUNTED DATA OUTLET. FURNISH AND INSTALL 1.25"C
+24" UNLESS OTHERWISE NOTE. BOX TO BE MINIMUM 2 1/8" DEEP.
TELEVISION OUTLET. CLG. OR WALL MOUNTED - STUB 1" C.ABOVE CEILING FROM OUTLET BOX
PUSHBUTTON WALL MOUNTED.
PUBLIC TELEPHONE OUTLET.: J-BOX & 1"C
MECHANCIAL DIVISION.
INDICATES PANEL AND BREAKER.
DETAIL NUMBER
SHEET NUMBER
HEAVY DUTY MOTOR STARTER
PANEL AND BREAKER.
ELECTRICAL CONDUIT
UNDERGROUND ELECTRICAL CONDUIT
MULTI-POLE DEVICE CIRCUIT NUMBERS
THREE SINGLE POLE DEVICE CIRCUIT NUMBERS
SWITCH LEGPANELBOARD, CLEARANCE AS PER LATEST NEC
MOTOR
HEAVY DUTY DISCONNECT SWITCH FUSED
HEAVY DUTY DISCONNECT SWITCH NONFUSED
PAD-X
FACP
FAAP
TIME CLOCK (MFR.TORK#7202Z)
LIGHTING CONTACTOR, NEMA-1, W/H.O.A. SWITCH
CIRCULATING PUMP
INTERCOM - CALL SWITCH- JBOX WITH 3/4"C
PHOTO CELL(MFR.INTERMATIC #K4136M)
TELEPHONE BOARD- 3/4"x8' FIRE RATED
ENCLOSED BREAKER, RE: TO SCH. FOR MORE INFO.---ALL SYMBOLS SHOWN MAY NOT APPEAR IN ALL DRAWINGS.SYMBOLS ARE SHOWN SCHEMATIC AND MAY NOT BE TO SCALE.
---ALL SYMBOLS SHOWN MAY NOT APPEAR IN ALL DRAWINGS.SYMBOLS ARE SHOWN SCHEMATIC AND MAY NOT BE TO SCALE.
---ALL SYMBOLS SHOWN MAY NOT APPEAR IN ALL DRAWINGS.SYMBOLS ARE SHOWN SCHEMATIC AND MAY NOT BE TO SCALE.
A-1
A-1
THERMOSTAT,RE:DIV.15
FIRE
80"MAX.
CEILING
FINISHED FLOOR
CEILING
FINISHED FLOOR
CEILING
FINISHED FLOOR
48" MAX. UNLESS LOCATEDABOVE "OBSTRUCTION"
SUCH AS A COUTER, THEN42" MAXIMUM.
12" MAX.AND 6" MIN.
4" MIN.
SWITCH
TELEPHONE OULET
DATA OUTLET
RECEPTACLE
FIRE ALARM PULL SWITCH
FIRE ALARM STROBE/AUDIO
WALL MOUNTED SMOKE DETECTOR
PROVIDE 18"AFF UNLESSOTHERWISE NOTED.
RECEPTACLE
DATA OUTLET
TELEPHONE OULET
DUPLEX RECEPTACLE(S)
SHARE CIRCUIT
SHUNT TRIP
UNDERFLOOR
SPACE ONLY
WIRE GUARD
UNLESS NOTED OTHERWISE
UNDERGROUND
TRANSFORMER
WEATHERPROOF
CB CIRCUIT BREAKER
ABOVE COUNTER
GROUND FAULT INTERRUPTER
NOT IN CONTRACT
GROUND (EQUIPMENT)
MOUNT OR MOUNTED
EMPTY CONDUIT
HT.ACNL
MOUNTINGHEIGHT
NIGHT LIGHT
MTD
GFI
NF
NICH.D
F
G
EC
EX
NONFUSED
HEAVY DUTY
FUSE
EXISTING
XFMR
UNO(U.N.O.)
ST (S.T.)
SO (S.O.)
UF
WG
WP
UG
SW
SP
SWITCH
SPARE
BELOW FINISHED CEILING
ABOVE FINISHED FLOOR
BFC
C
AFF
CONDUIT
(S.C.)
RCPT(S)
PNL PANEL
MAIN BREAKERMB
MAIN LUGS ONLYMLO
MTD.
FEEDERFDR.
RIGID METAL CONDUITRMC
RIGID NONMETALLIC CONDUITRNC
ELECTRICAL METALLICEMT
MANUFACTURERMFR.
CIRCUITCKT.
LIGHTINGLTG.
LIGHTING CONTACTORLC
EACHEA.TUBING CONDUIT
ISOLATED GROUNDIG
I.G. RECEPTACLE(S)CRCPT(S)
QUAD I.G. RECEPTACLE(S)QCRCPT(S)
QUAD RECEPTACLE(S)QRCPT(S)
SOLID NEUTRALS/N
ABOVE COUNTERAC
ALL OTHER MOUNTING HEIGHTS REFER TO CENTERLINE OF DEVICE.
48" AFF INDICATES TO TOP OF DEVICE;15" AFF INDICATES TO BOTTOM OF DEVICE;
AC INDICATES 6" ABOVE COUNTER TO BOTTOM OF DEVICE.
NOTES:
1.)
DOUBLE SIDED CLOCK,J-BOX W/3/4"C
SINGLE SIDED CLOCK, J-BOX W/3/4"C
96" AFF MIN.
96" AFF MIN.
SECURITY DOOR CONTACT SENSOR - STUB 1/2"CABOVE CEILING FROM OUTLET BOX
MAGNETIC LOCK BOX - STUB 3/4"CABOVE CEILING LEVEL FROM OUTLET BOX
- - - -
SYSTEM BY OTHERS
SYSTEM BY OTHERS
ACCESS CONTROL PANEL JUNCTION BOX - BY OTHERS 54"
---ALL SYMBOLS SHOWN MAY NOT APPEAR IN ALL DRAWINGS.SYMBOLS ARE SHOWN SCHEMATIC AND MAY NOT BE TO SCALE.
NEMA-1N1NEMA-3RN3RNEMA-4XN4X
SD
AV
V
F
H
DH
TS
FS
MINIMUM OF 4" SQUAREJUNCTION BOX - SIZE & MOUNTING AS REQUIRED
208V RECEPTACLE, VERIFY NEMA NO. WITH EQUIPMENT SUPPLIER
ISOLATED GROUND QUADPLEX RECEPTACLE
DUPLEX RCPT. GFI - 20A/125V/2P/3W/G NEMA 5-20R
DUPLEX RECEPTACLE - 20A/125V/2P/3W/G NEMA 5-20R
SINGLE RECEPTACLE - 20A/125V/2P/3W/G NEMA 5-20R
ISOLATED GROUND DUPLEX RECEPTACLE - 20A/125V NEMA 5-20R
SPECIAL PURPOSE RECEPTACLE (NEMA NO. AS INDICATED)
QUADRAPLEX RECEPTACLE
"IN-USE"WP/
J-BOX - AIR HAND DRYER: (RECESSED HAND DRYERS TO BEPROVIDED BY DIVISION 16, ELECTRICAL)#B-750 AUTOMATICHANDCRAFT AS MANUFACTURER BY BOBRICK. (COLOR WHITE)QUANTITY: REFER TO DRAWINGS (MIN. ONE PER LAV. COMPLETEW/ ELE. CONNECTIONS TYP.)
HH / HOSPITAL GRADE DUPLEX RECEPTACLE/GFI - 20A/125V/2P/3W/G NEMA 5-20R
ROTARY TYPE DISCONNECT SWITCHR
120/277-208/480V,20AMP, MOTOR RATED SWITCH, NEMA-1(INTERIOR)
CAMERA J-BOX W/ 3/4" CONDUIT - - - -
AUDIO VIDEO DROP, REFER TO DETAIL
AHUTHORITY HAVINGAHJJURISDICTION
FIRE ALARM PULL STATION: STUB 3/4"C ABOVE CEILING FROM J-BOX
FIRE ALARM AUDIBLE/VISUAL SIGNAL: STUB 3/4"C ABOVE CEILING FROMJ-BOXFIRE ALARM VISUAL SIGNAL: STUB 3/4"C ABOVE CEILING FROM J-BOX
FIRE ALARM SMOKE DETECTOR CEILING OR WALL MOUNTED: STUB 3/4"CABOVE CEILING FROM J-BOXHEAT DETECTOR CEILING OR WALL MOUNTED: STUB 3/4"C ABOVE CEILINGFROM J-BOX
DUCT SMOKE DETECTOR: STUB 3/4"C ABOVE CEILING FROM J-BOX
FIRE ALARM CONTROL PANEL, ADDRESSABLE, SURFACE MTD UNO, INCLUDEA FIRE DOCUMENT BOX EQUAL TO MFR. SPACE AGE ELECTRONICS#FDB-ACE-11.
FIRE ALARM REMOTE ANNUNCIATOR PANEL, FLUSH MOUNTED UNO
POWER SUPPLY, DEDICATED 110V
DOOR HOLDER DEVICE: STUB 3/4"C ABOVE CEILING FROM J-BOX
TAMPER SWITCH: STUB 3/4"C ABOVE CEILING FROM J-BOX
FLOW SWITCH: STUB 3/4"C ABOVE CEILING FROM J-BOX
NOTE: VERIFY WITH ARCHITECTURAL FOR ADA REQUIREMENTS.
F FIRE ALARM OUTDOOR SPEAKER, WEATHER PROOF: STUB 3/4"C ABOVECEILING FROM J-BOX
INTERCOM/PAGING LAY-IN SPEAKER
PA EXTERIOR SPEAKER 10'-6" AFF
INTRUSION EXTERIOR SPEAKER 10'-6" AFF
ALL SYMBOLS AND ABBREVIATIONS SHOWN ON THIS LEGEND MAY NOTAPPEAR ON THIS SET OF DRAWINGS.
USE DIRECTIONAL ARROW ON EXIT SIGNS AS REQUIRED.
IEEE STANDARD C37.2-1991, ELECTRICAL POWER SYSTEM DEVICE FUNCTIONNUMBERS.
CONTRACTOR SHALL NOT INSTALL MORE THAN THREE CURRENT CARRYINGCONDUCTORS IN A COMMON RACEWAY. IF CONTRACTOR IS PLANNING ONGROUPING MULTIPLE CIRCUITS IN A SINGLE RACEWAY, THE CONTRCATORMUST SUBMIT ALL DERATING CALCULATIONS FOR THE PROPOSEDINSTALLATION IN ACCORDANCE WITH NEC ARTICLE 310.15 (B) (2) FORAPPROVAL PRIOR TO INSTALLATION. NON APPROVED INSTALLATIONS WILLBE REMOVED AND REINSTALLED BY THE CONTRACTOR IN ACCORDANCE WITHTHE NEC AT NO ADDITIONAL COST TO THE OWNER.
THERE SHALL NOT BE MORE THAN THE EQUIVALENT OF THREE 90° BENDS(270 DEGREES TOTAL) BETWEEN PULL POINTS. WHERE THERE ARE MORETHAN THREE QUARTER BENDS, CONTRACTOR SHALL PROVIDE PULL BOXESAS SPECIFIED AND SIZED IN ACCORDANCE WITH NEC.
COMPLY WITH NEC REQUIREMENTS FOR ELECTRICAL INSTALLATIONS. ALLELECTRICAL EQUIPMENT AND MATERIAL TO BE APPROVED, LISTED, LABELED,IDENTIFIED AND INSTALLED PER RECOGNIZED ELECTRICAL TESTINGLABORATORY.
ALL RECEPTACLES, SWITCHES AND JUNCTION BOXES SERVED BYEMERGENCY BRANCH CIRCUITS SHALL BE "RED" IN COLOR. COVERPLATESSHALL BE LABELED IN ACCORDANCE WITH SPECIFICATIONS TO INDICATEPANELBOARD AND CIRCUIT NO. (IE: ET*LA-3).
1.
2.
3.
4.
5.
6.
7.
SD SMOKE DETECTOR WITH AN AUDIBLE BASE: STUB 3/4"C ABOVE CEILINGFROM J-BOX
STAINLESS STEELSS
DUPLEX RCPT.,WEATHER RESISTANT "WR", GFI INSTALLED IN A"IN-USE" WEATHER PROOF STEEL ENCLOSURE- 20A/125V/2P/3W/GNEMA 5-20R WP/"IN-USE" SHALL BE EQUAL TO MFR. CARLON,METALLIC SERIES SINGLE GANG, VERTICAL MOUNT #ME9UVMGDOUBLE GANG, VERTICAL MOUNT #ME9U2VMG
ELECTRICAL DEVICE AS SHOWN ON PLANS SURFACE MOUNTRACEWAY. SURFACE MOUNT RACEWAY SHALL BE WIREMOLD #V700SERIES. PROVIDE ALL RELATED #V700 SERIES ACCESSORIES FOR ANOPERABLE SYSTEM.
FACP-EVS FIRE ALARM CONTROL PANEL WITH EMERGENCY VOICE SYSTEM,ADDRESSABLE, FLUSH MTD UNO, INCLUDE A FIRE DOCUMENT BOXEQUAL TO MFR. SPACE AGE ELECTRONICS #FDB-ACE-11.
SFIRE ALARM CEILING MOUNT SPEAKER STROBE, UL LISTED, : J-BOX WITH 3/4"C
VS FIRE ALARM CEILING WALL MOUNT OUTDOOR SPEAKER STROBE, UL LISTED, :J-BOX WITH 3/4"C
ENCLOSURE, NEMA-3R(EXTERIOR) ENCLOSURE. VOLTAGE TO BE SELECTEDPER EQUIPMENT CIRCUIT REQUIREMENTS.
EVES FIRE ALARM EMERGENCY VOICE EVACUATION SYSTEM, FLUSH ORSURFACE.
6P
8P
COMMUNICATION CONDUIT AND WIRING
6G
6JP
TAMPER PROOFT
T DUPLEX RECEPTACLE TAMPER RESISTANT -20A/125V/2P/3W/G NEMA 5-20R
V
CEILING MOUNTED WIFI ACCESS POINT
4-GANG FLOOR MOUNTED BOX, 2-DUPLEX RECEPTACLE(INCLUDERECEPTACLE WITH COVER PLATE)/2-GANG FOR DATA - FLUSHMOUNTED UNO FLOOR BOX = MFR.-HUBBELLMODEL#CFB4G30RCR-CFBS1R8CVRNKL(COVER)-(2)FBMPDUP-FBMP6KS -CFBHUB2(MULTISERVICE STEEL RECESSED FLOOR BOX-VERIFY FLOOR FINISH PRIOR TO ORDER SAME BOX FOR DATAOUTLETS.
6" FIRE RATED POKE-TRHOUGHS BOX, 2-DUPLEXRECEPTACLE(INCLUDE RECEPTACLE WITH COVER PLATE)-MFR.-HUBBELL MODEL#S1R6PTFIT-S1R6SPE-S1R6SPL-S1R6SPH(50/50DEVICE PLATE COMBINATION)-S1R6CVRALU(COVER) -VERIFYFLOOR FINISH PRIOR TO ORDER SAME BOX FOR DATA OUTLETS.
8" FIRE RATED POKE-TRHOUGHS BOX, 2-DUPLEXRECEPTACLE(INCLUDE RECEPTACLE WITH COVER PLATE)-MFR.-HUBBELLMODEL#S1R8PTFIT3-S1R8CSPK-S1R8CSPK-S1R8PSPZ(50/50 DEVICEPLATE COMBINATION)-S1R8CVRALU(COVER) -VERIFY FLOOR FINISHPRIOR TO ORDER SAME BOX FOR DATA OUTLETS.
6-GANG FLOOR MOUNTED BOX, 2-DUPLEX RECEPTACLE(INCLUDERECEPTACLE WITH COVER PLATE)/2-GANG FOR DATA - FLUSHMOUNTED UNO FLOOR BOX = MFR.-HUBBELLMODEL#CFB6G30RCR-CFBS1R8CVRNKL(COVER)-(3)FBMPDUP-FBMP6KS-CFBHB2(MULTISERVICE STEEL RECESSED FLOOR BOX-VERIFY FLOORFINISH PRIOR TO ORDER SAME BOX FOR DATA OUTLETS.
6" FIRE RATED POKE-TRHOUGHS BOX, FURNITURE FEED,-MFR.-HUBBELL MODEL#S1R6PTFFALU( ALUMINUM COVER) -VERIFYFLOOR FINISH PRIOR TO ORDER.
CONTRACTOR SHALL PERFORM THE TASK BELOW TO COMMISSION THE LIGHTING CONTROL SYSTEM.CONTRACTOR SHALL SUBMIT A DOCUMENTATION DETAILING THE LIGHTING CONTROL SYSTEM,SETTING/CONDITION, ACTIONS PERFORMED AND FINAL SETTING CONDITION. SUBMITDOCUMENTATION AT OR BEFORE SUBSTANTIAL COMPLETION TO FACILITATE OBTAINING THECERTIFICATE OF OCCUPANCY.
A. ENSURE ALL LIGHTING FIXTURES FIXTURES HAVE LAMPS INSTALLED AND ARE FUNCTIONAL.B. TEST ALL EXIT SIGNS, EMERGENCY LIGHTING FIXTURES, AND EMERGENCY BALLASTS FURNISHEDINTEGRAL TO FIXTURES.C. ENSURE ALL OCCUPANCY SENSORS HAVE BEEN INSTALLED AND ARE OPERATIONAL.D. VERIFY ALL WALLBOX AND SCENE CONTROLLERS ARE INSTALLED AND OPERATIONAL.E. TEST EACH INDIVIDUAL DEVICE FOR OCCUPANCY SENSOR TYPES OS1, OS2 AND TEST THE LIGHTINGCONTROL RELAY PANEL SYSTEM.F. TEST 10% OF ALL THE DEVICES FOR OCCUPANCY SENSOR TYPE: WSX-PDT-SA.G. VERIFY THE FOLLOWING:1. ALL SENSORS ARE LOCATED AND AIMED PER THE MANUFACTURER'S RECOMMENDATIONS.2. STATUS INDICATORS ON DEVICES ARE OPERATIONAL AND CORRECT.3. DEVICES CONTROL LIGHTING FIXTURES AS INDICATED ON DRAWINGS.
4. TIME DELAYS HAVE BEEN SET AS PER CODE AND PER OWNERS DIRECTIONS.5. MOVEMENT IN ADJACENT AREAS AND/ CYCLING OF HVAC SYSTEMS DOES NOT FALSE TRIGGERSENSORS.6. PHOTOCELL LOCATION AND AIMED PER MANUFACTURERS RECOMMENDATIONS.7. PROGRAM INTERIOR RELAYS WITH A TIME FUNCTION ACCEPTABLE TO OWNER.8. PROGRAM INTERIOR OVERRIDE SWITCH WITH A TIME FUNCTIONAL ACCEPTABLE BY OWNER.
LA ENOIS N
LEONARDO MUNOZ
97437
F
N
PR
SCEF
LI
O
E
ATTE
S
O
ER
INSG
EED
S
TEXA
MEP ENGINEERING3533 Moreland Dr. Ste A l Weslaco, Tx78596 p:956.973.0500 l f:956-351-5750www.trinitymep.com I Copyright 2020Texas Registered Engineering Firm - F10362Project number:
PROJECT NO.:ISSUE DATE:
Project Status:
A Sheet Number
SHEET NAME
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19
B
C
D
E
F
G
H
J
K
L
M
N
P
DRAWN BY:CHECKED BY:
300 S. 8th Street, McAllen, Tx 78501T 956-661-0400 | goero.com
No.
Date
Desc
riptio
n
Q
R
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19
BIM
360
://20
042
San
Car
los
Gym
Add
ition
/20.
4.18
_Sam
Car
los
Gym
Adi
ttion
_CEN
TRAL
_202
0.rv
t3/
5/20
21 2
:58:
24 P
M
EG01
ELECTRICAL LEGEND
2004203.05.21
100% CONSTRUCTION DOCUMENTS
AuthorChecker
SAN
CARL
OS G
YMNA
SIUM
ADD
ITION
505 S
. 83R
D ST
, EDI
NBUR
G TX
7853
9ED
INBU
RG C
ONSO
LIDAT
ED IN
DEPE
NDEN
T SCH
OOL D
ISTR
ICT
03.05.21
Light Fixture Schedule
Tag Lamp Voltage Mounting Description Manufacturer ModelA LED (4800LM) (37W) 277V RECESSED 2X4 LAY-IN LED FLUXPANEL WITH LENS AND LED DRIVER INCLUDE ALL NECESSARY
AE LED (4800LM) (37W) 277V RECESSED 2X4 LAY-IN LED FLUXPANEL WITH LENS AND LED DRIVER INCLUDE ALL NECESSARYMOUNTING ACCESSORIES.
DAY-BRITE 2FPZ48L840-4-DS-UNV-DIM-BSL10LST
B LED (3800LM) (29W) 277V RECESSED 2X4 LAY-IN LED FLUXPANEL WITH LENS AND LED DRIVER INCLUDE ALL NECESSARYMOUNTING ACCESSORIES.
DAY-BRITE 2FPZ38L840-4-DS-UNV-DIM
BE LED (3800LM) (29W) 277V RECESSED 2X4 LAY-IN LED FLUXPANEL WITH LENS AND LED DRIVER AND EMERGENCY BATTERYBACKUP INCLUDE ALL NECESSARY MOUNTING ACCESSORIES.
DAY-BRITE 2FPZ38L840-4-DS-UNV-DIM-BSL10LST
C LED (18000 LM) (133W) 277V SURFACE LED HIGHBAY SMART LUMINAIRE WITH MOTION/DAYLIGHT SENSOR DAY-BRITE FBY-18L-840-UNV-XXCE LED (18000 LM) (133W) 277V SURFACE LED HIGHBAY SMART LUMINAIRE WITH MOTION/DAYLIGHT SENSOR DAY-BRITE FBY-18L-840-UNV-XX-BSL10LSTE2 LED 277V SURFACE @
F LED (5500LM) (45W) 277V SURFACE 4' LED STRIP LIGHT DAY-BRITE FSS455L840-UNV-DIMFE LED (5500LM) (45W) 277V SURFACE 4' LED STRIP LIGHT WITH EMERGENCY BATTERY BACKUP DAY-BRITE FSS455L840-UNV-DIM-EMLEDX1 INCLUDED 277V SURFACE THERMOPLASTIC EXIT/EMERGENCY UNIT WITH SELF-DIAGNOSTICS CHLORIDE VLTCR3RAA LED (3800LM) 37W 277V SURFACE
@10'-0"WALL MOUNTED FIXTURE RATED FOR WET LOCATION. FIXTURE SHALL BE MOUNTED10'-0" A.F.F. COORDINATE WITH ALL DISCIPLINES AND ARCHITECTURAL DOCUMENTSPRIOR TO ROUGH-INS.
GARDCO 107L-16L-700-NWG1-3-UNV
GENERAL NOTES:1.) EQUAL MANUFACTURER SHALL BE ACCEPTABLE WITH EQUAL PERFORMANCE OF SPECIFIED EQUIPMENT AND APPROVED BY ENGINEER.2.) SUBMIT EQUAL MANUFACTURERS TO ENGINEER 10 DAYS PRIOR TO BID DATE.3.) SUBMIT LIGHT FIXTURES CUTSHEETS TO OWNER FOR APPROVAL PRIOR TO ORDER.4.) CONTRACTOR SHALL VERIFY THAT ANY IRRIGATION SPRINKLER HEAD IS AWAY FROM ANY LIGHT POLE A MINIMUM OF 75' TO AVOID CONSISTENT WATER TO LIGHT POLE. COORDINATE WITHIRRIGATION CONTRACTOR PRIOR TO ANY WORK.5.) ANCHOR BOLTS SHALL BE OF NON-CORROSIVE MATERIAL (STAINLESS STEEL).6.) ACCEPTABLE MANUFACTURES; PHILIPS, LITHONIA, GOTHAM.
FIRE ALARM SYSTEM - HOCKIKI FireNetINTERCOM/PA SYSTEM - VALCOM DUALPATH INTERCOM SYSTEMHVAC CONTROLS - REFER TO DIVISION -15SECURITY INTRUSION SYSTEMS - HONEYWELL VISTA 128BPT
NOTES:1. ALL SPECIAL SYSTEMS CONDUIT SHALL INCLUDE MULTIPLE PULLSTRINGS.2. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING SPECIAL SYSTEMSCONDITIONS PRIOR TO BID DATE. INCLUDE ALL COST IN BID FOR A COMPLETEOPERABLE CODE COMPLIANT SYSTEMS.3. SPECIAL SYSTEM CONTRACTORS SHALL BE CERTIFIED VENDOR/INSTALLER OFTHE EXISTING MANUFACTURER. CONTRACTOR SHALL PROVIDE PROOF INSUBMITTAL PHASE.
WIRELESS OCCUPANCY SENSOR - LUTRON MODEL #LRF2-OCR2B-P-WH
CLG.
ABOVE CEILING
48" AFF
CORNER OCCUPANCY SENSOR - LUTRON LRF2-OKLB-P-WH
48" AFF
LIGHTING CONTROLS SYMBOLS LEGEND
CLG.
POWER PACK MODULE - LUTRON RMJ-16R-DV-B ABOVE CEILING
GIRLSA108
JANITORA109
VESTIBULEA110
BOYSA111
FACULTY TOILETA112
OFFICEA113
STORAGEA114
SW3
SW2
SW3
SW4
SW4
SW4
BE B
X1
X1 X1
X1 X1FE
E2E2
E2
E2 E2
C C CECE
CE C CC
C CE CC
C C CECE
BE
B B
BE
B
BE
BEB
A
A
AE
SW2
SW2
SW2
SW2
SW2
SW2
SW2
SW2
SW2
SW4
ZONE 1
ZONE 2
ZONE 3
SW2SW2
10111011
11
10
12
11
1211
10
H-7
H-15
H-9
(S.C.)H-13
SW3
(S.C.)H-13
(S.C.)H-13
(S.C.)H-13
(S.C.)H-13
F
F F
FEF
AA
AA
AA AA
AA AA
AA
AA
H-8
23
TYP.26
TYP.26 GYMNASIUM
A101
GIRLSA108
VESTIBULEA110
BOYSA111
FACULTY TOILETA112
OFFICEA113
STORAGEA114
+42"
+42"
+42"
1
2
3
R-12
R-10
AC
AC
AC
WP/"IN-USE"
WP/"IN-USE"R-13
(S.C.)R-4
PANEL-R
R-6
R-7
R-8
4
5
6
R-9
R-18
R-3
7
EF-2
EF-3
EF-4
8
9
89
EF-1
R-15
EX
EX
EX
EX
EX
EX
EX
1314
15
H-1,3,5
PANEL-H
H-2,4,6
AC
AC
DXPU-1
DXPU-2
R-14
R-16
R-17
R-2
16
16
16
16
16
16
16
16
16
17
17
17
JANITORA109
17
R-19
WH-1
R-20
(S.C.)R-4
R-21
TYP.18
TYP.18
TYP.18 TYP.
18
TYP.18
19
R-11
20
TYP.21
22
R-22
R-5
2424
EX EX
EXEX EXEX
TYP.25
TX-R
T
T
32 34
36
2R-24
GYMNASIUMA101
GIRLSA108
VESTIBULEA110
BOYSA111
FACULTY TOILETA112
OFFICEA113
STORAGEA114
AC
AC
DXPU-1
DXPU-2
JANITORA109
27
EXEX
EXEX
EX EX
EXEX EXEX EXEX
EX
EX
25
TYP.28
TYP.28
TYP.29
TYP.25
25
T
T
2
2
2
2
1
30
30
31
31
31
31
14
14
33
31
2 94" AFF15"AFF
15"AFF
15"AFF
15"AFF
35
3535
35
LA ENOIS N
LEONARDO MUNOZ
97437
F
N
PR
SCEF
LI
O
E
ATTE
S
O
ER
INSG
EED
S
TEXA
MEP ENGINEERING3533 Moreland Dr. Ste A l Weslaco, Tx78596 p:956.973.0500 l f:956-351-5750www.trinitymep.com I Copyright 2020Texas Registered Engineering Firm - F10362Project number:
PROJECT NO.:ISSUE DATE:
Project Status:
A Sheet Number
SHEET NAME
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19
B
C
D
E
F
G
H
J
K
L
M
N
P
DRAWN BY:CHECKED BY:
300 S. 8th Street, McAllen, Tx 78501T 956-661-0400 | goero.com
No.
Date
Desc
riptio
n
Q
R
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19
BIM
360
://20
042
San
Car
los
Gym
Add
ition
/20.
4.18
_Sam
Car
los
Gym
Adi
ttion
_CEN
TRAL
_202
0.rv
t3/
5/20
21 2
:58:
29 P
M
EL01
ELECTRICAL FLOOR PLAN
2004203.05.21
100% CONSTRUCTION DOCUMENTS
AuthorChecker
SAN
CARL
OS G
YMNA
SIUM
ADD
ITION
505 S
. 83R
D ST
, EDI
NBUR
G TX
7853
9ED
INBU
RG C
ONSO
LIDAT
ED IN
DEPE
NDEN
T SCH
OOL D
ISTR
ICT
03.05.21
1/8" = 1'-0"1 ELECTRICAL LIGHTING PLAN
ELECTRICAL KEYNOTES
1 FURNISH AND INSTALL 4-INCH SQUARED DEEP JUNCTION BOX FOR MULTIMEDIA OUTLET WITH MUDRINGS.INSTALL AT 15" TO BOTTOM OF DEVICE.
2 FURNISH AND INSTALL 1.5" EMT CONDUIT WITH PULLSTRING FOR MULTIMEDIA CABLING.3 FURNISH AND INSTALL 4-INCH SQUARE DDEP JUNCTION WITH 3/4" CONDUIT WITH PULL FROM WINCH TO
CONTROL SWITCH FOR KEY SWITCH CONTROL FOR ELECTRIC WINCH.4 3/4"X8'HX4'W PLYWOOD TELEPHONE BOARD FINISHED ONE SIDE. PROVIDE GROUND BAR AND TIE INTO
ELECTRICAL GROUNDING SYSTEM VIA WIRE #4.5 POWER FOR FIRE ALARM EXPANDER PANEL. FIELD VERIFY EXACT LOCATION PRIOR TO ANY ROUGH-INS.6 POWER FOR INTRUSION/INTERCOM CIRCUITS. FIELD VERIFY EXACT LOCATION PRIOR TO ANY ROUGH-INS.7 REPLACE EXISTING DUPLEX RECEPTACLES WITH NEW 120V, 20AMP, TAMPER PROOF RECEPTACLES.8 PROVIDE J-BOX AND 3/4"C WITH PULLSTRING FOR FIRE ALARM. ROUTE CONDUIT TO FIRE ALARM
CONTROLLER.9 PROVIDE J-BOX AND 3/4"C WITH PULLSTRING FOR HVAC CONTROLS. ROUTE CONDUIT TO UNIT
CONTROLLER.10 CONTROL SWITCH SHALL CONTROL ON/OFF AND DIMMING OF ZONE 3.11 CONTROL SWITCH SHALL CONTROL ON/OFF AND DIMMING OF ZONE 2.12 CONTROL SWITCH SHALL CONTROL ON/OFF AND DIMMING OF ZONE 1.13 PROVIDE J-BOX AND 1"C ABOVE CEILING FOR FIBER OPTIC CABLE. ROUTE TO EXISTING 1" CONDUIT
OUTSIDE ABOVE CANOPY. REFER TO KEYED NOTE #15.14 PROVIDE J-BOX 12" AFF WITH 1"C STUBBED OUT ABOVE CEILING FOR DATA CABLING. ALL DATA CABLING
TO BE PROVIDED BY OWNER.15 EXISTING 1" CONDUIT LOCATED ABOVE COVERED WALKWAY TO BE USED FOR NEW FIBER OPTIC CABLE.
FIELD VERIFY EXISITNG CONDITIONS PRIOR TO ANY WORK.16 REPLACE EXISTING QUAD RECEPTACLES WITH NEW 120V, 20AMP, TAMPER PROOF RECEPTACLES.17 TIE INTO ROOMS LIGHTING CIRCUIT AND INTERLOCK FAN WITH ROOMS LIGHTS. WIRING SHALL BE 2#12,
1#12G, 1/2"C.18 PROVIDE J-BOX FOR LAVATORY OR FLUSH SENSOR. COORDINATE EXACT LOCATION AND ELECTRICAL
REQUIREMENTS WITH EQUIPMENT SUPPLIER PRIOR TO ANY WORK.19 FURNISH AND INSTALL POWER FOR ELECTRIC WINCH CONSISTING OF 2#10, 1#10G, 3/4"C. FURNISH AND
INSTALL NEMA L14-20 TWIST LOCK RECEPTACLE. MOUNT ADJACENT TO WINCH.20 PROVIDE J-BOX POWER FOR MOTORIZED SCREEN. COORDINATE EXACT LOCATION WITH OWNER PRIOR
ANY WORK.21 PROVIDE POWER AND DATA FOR PROJECTOR. CORDINATE EXACT LOCATION WITH OWNER PRIOR TO ANY
WORK.22 COORDINATE EXACT LOCATION FOR CLOCK NEW LOCATION WITH OWNER PRIOR TO ANY WORK.23 EXTERIOR LIGHTING TO BE CONTROLLED VIA LIGHTING CONTACTOR.24 COORDINATE EXACT LOCATION WITH PLUMBER TO CONCEAL CORD BEHIND ELECTRIC DRINKING
FOUNTAIN PRIOR TO ANY ROUGH-IN.25 PROVIDE NEW FIRE ALARM DEVICES, ALL NEW FIRE ALARM DEVICES TO BE TIE INTO EXISTING FIRE ALARM
SYSTEM. FIELD VERIFY EXISTING CONDITIONS PRIOR TO ANY WORK.26 MOUNT LIGHT FIXTURE TO EXISTING STRUCTURAL. PROVIDE ADDITIONAL STRUCTURAL FOR SUPPORT.27 PROVIDE SURFACE MOUNT INTERCOM/PA SPEAKERS WITH WIREGUARD.28 ALL NEW INTERCOM DEVICES TO BE TIE INTO EXISTING INTERCOM SYSTEM. FIELD VERIFY EXISTING
CONDITIONS PRIOR TO ANY WORK.29 ALL NEW INTRUSION DEVICES TO BE TIE INTO EXISTING INTRUSION SYSTEM. FIELD VERIFY EXISTING
CONDITIONS PRIOR TO ANY WORK.30 PROVIDE SINGLE GANG J-BOX WITH 1"C TO ABOVE CEILING OR WHERE ACCESS IS AVAILABLE.
COORDINATE EXACT LOCATION AND MOUNTING HEIGHT WITH OWNER PRIOR TO ANY WORK. NUMBERNEXT TO DATA BOX REPRESENTS THE NUMBER OF DATA DROPS. ALL DATA CABLING TO BE PROVIDED BYOWNER.
31 PROVIDE SINGLE GANG J-BOX WITH 1"C TO ABOVE CEILING OR WHERE ACCESS IS AVAILABLE.COORDINATE EXACT LOCATION AND MOUNTING HEIGHT WITH OWNER PRIOR TO ANY WORK. NUMBERNEXT TO DATA BOX REPRESENTS THE NUMBER OF DATA DROPS. ALL DATA CABLING TO BE PROVIDED BYOWNER.
32 PROVIDE DUPLEX RECEPTACLE ABOVE IT CABINET 7'-6" AFF. FIELD VERIFY EXACT LOCATION ANDMOUNTING HEIGHT WITH OWNER PRIOR TO ANY WORK.
33 APPROXIMATE LOCATION OF IT CABINET TO BE MOUNTED 6'-0" AFF. IT CABINET TO BE PROVIDED BYOWNER.
34 100A, 480V, 3-PHASE, 4W, S/N. N3R HEAVY DUTY FUSED DISONNECT, FUSED AT 70A. LOCATE DISCONNECTWITHIN 5'-0" OF TX-R. REFER TO RISER DIAGRAM IN SHEET ER01.
35 PROVIDE BRACKETS FOR SPEAKERS. SPEAKERS TO BE PROVIDED BY OWNER. COORDINATE SPEAKERMAKE/MODEL AND EXACT LCOATION AND MOUNTING HEIGHT WITH OWNER/DISTRICT.
36 ELECTRICAL CIRCUIT FOR SOUND SYSTEM. MOUNT @ 48" A.F.F.
1/8" = 1'-0"2 ELECTRICAL POWER FLOOR PLAN
GENERAL NOTES
A. SWITCH LEGS ARE NOT SHOWN ALL EXIT FIXTURES TYPE-"X1 & X2",EMERGENCY LIGHT FIXTURE TYPE-"E" AND ALL EMERGENCY BALLASTSHALL BE ON CIRCUIT "H-11". FIXTURE TYPE LABEL WITH AN "_E" ARELIGHT FIXTURES WITH EMERGENCY BALLAST. REFER TO LIGHTFIXTURE SCHEDULE.WHERE SWITCHING SCHEME IS OBVIOUS.
B. VERIFY CEILING TYPES AND COORDINATE WITH FIXTURE TYPE LIGHTFIXTURE SHALL BE COMPATIBLE WITH CEILING TYPE AS INDICATED ONTHE ARCHITECTURAL DOCUMENTS. NOTIFY ENGINEER IFDISCREPANCIES EXIST PRIOR TO ORDERING FIXTURES.
C. COORDINATE EXACT ROUTING OF ALL CONDUIT ABOVE CEILING INBUILDING. TYPICAL FOR ALL BUILDING EXTERIOR LIGHTING.
D. COORDINATE LOCATION OF LIGHTS WITH DIFFUSERS AND GRILLES.E SWITCH LEGS ARE NOT SHOWN WHERE SWITCHING SCHEME IS
OBVIOUS.F. NEMA RATED OUTLETS, REFER TO BREAKER SIZE AND COORDINATE
WITH EQUIPMENT REQUIREMENTS PRIOR TO BID.G. COORDINATE EXACT LOCATION AND MOUNTING HEIGHT OF ALL POWER
SOURCE WIRING IN ACCORDANCE WITH ARCHITECTURAL MILLWORKPRIOR TO ANY ROUGH-INS.
H. ELECTRICAL CONTRACTOR SHALL MAKE FINAL CONNECTION TOH.V.A.C EQUIPMENT, PLUMBING EQUIPMENT, REFER TO PANELSCHEDULE FOR WIRE SIZE.
I. ELECTRICAL CONTRACTOR SHALL PROVIDE STARTERS, RELAYS,CONTACTORS AND THE REQUIRED ELECTRICAL ACCESSORIES FORMECHANICAL SYSTEM AS REQUIRED.
J. COORDINATE EXACT LOCATION OF ALL MECHANICAL EQUIPMENT INACCORDANCE W/MECHANICAL DRAWINGS TO MEET ELECTRICAL ANDMECHANICAL REQUIRED CLEARANCE BY THE LATEST CODE.
K. ALL EXISTING EXPOSED CONDUIT THAT IS NOTED TO REMAIN SHALLREINSTALLED TO BE CONCEAL BEHING WALL PANEL. PROVIDE NEWCONDUIT AS NEEDED. REFER TO ARCHITECTURAL DRAWINGS FORMORE INFORMATION.
L. ELECTRICAL CONTRACTOR SHALL PROVIDE J-BOX AND CONDUIT FORH.V.A.C. CONTROLS AND THERMOSTATS. COORDINATE EXACTLOCATION WITH MECHANICAL CONTRACTOR.
M. CONTACTOR TO REMOVE AND SALVAGE INTERIOR WOOD SIDINGPANELS AS REQUIRED TO INSTALL NEW CONDUIT TO BE CONCEALEDBEHIND WALL PANELS.
O. ALL NEW CONDUITS SHALL RUN ALONG OR IN THE PARLINGSTRUCTURAL.
P. COORDINATE ALL LOCATIONS AND MOUNTING HEIGHT OF ALLELECTRICAL DEVICES WITH OWNER PRIOR TO INSTALLATION.
1/8" = 1'-0"3 ELECTRICAL SPECIAL SYSTEMS PLAN
203
/05/
202 1
ADD
END
UM
#2
2
2
2
2
2
2
2
2
2
2
2
2
2
THE CONTRACTOR SHALL FURNISH SHORT-CIRCUIT AND PROTECTION DEVICE COORDINATESTUDIES WHICH SHALL BE PREPARED BY THE EQUIPMENT GEAR MANUFACTURER ANDSUBMITTED AS PART OF THE ELECTRICAL GEAR SUBMITTALS.
THE CONTRACTOR SHALL FURNISH AN ARC FLASH HAZARD ANALYSIS STUDY PER NFPA 70E-STANDARD FOR ELECTRICAL SAFETY IN THE WORKPLACE, REFERENCE ARTICLE 130.3 ANDANEEX D.
J.
I.
ROUTE TO EXISTING SWITCHBOARD (MDP). REUSE EXISTING CONDUIT FOR NEW 4#3/0,1#6G. FIELD VERIFY EXISTING CONDITIONS.
PROVIDE NEW 200A 3-PHASE, 4W FUSE SWITCH BUCKET IN EXISTING SQUARE-D, QED,2000 AMP SWITCHBOARD. INCLUDE NEW MOUNT HARDWARE.
100AMPS, 480V, 3-PHASE, 4W, S/N, N3R, HEAVY DUTY FUSED DISCONNECT, FUSED AT70A. LOCATE DISCONNECT WITHIN 5'-0" OF ASSOCIATED TRANSFORMER.1#6G, GROUND ELECTRODE CONDUCTOR, CALDWELD CONNECTION TO BUILDINGREBAR AND STRUCTURE STEEL.
30AMP, 3-PHASE, 4W, N1,480V, S/N, N.F., H.D. ROTARY TYPE DISCONNECTWH-1
TX-R
NOTE: ALL DRY-TYP TRANSFORMER SHALL BE ENERGY EFFICIENT MODELS AND MEET 2016 ENERGY EFFICIENT REQUIREMENTS.
TYPE-DT-3: GENERAL, 45KVA, COPPER WINDINGS,3-PHASE, (P)480V-(S)208/120V,115°RISE,NEMA-3R
LABEL TRANSFORMER DESCRIPTION PRIMARY VOLTAGE FEEDER -
4#4, 1#8G,1 1/2
SECONDARY VOLTAGE FEEDER -
4#2, 1#8G,2"C
480V, 3� 120/208V, 3�, 4W
SPD
GENERAL NOTES:A. PROVIDE GROUND /BONDING AS INDICATED ON THE NATIONAL ELECTRICAL
CODE.NAME PLATES SHALL BE PROVIDED FOR ALL ELECTRICAL SWITCH GEAR, PANEL BOARDS,LIGHTING CONTACTORS, LIGHTING CONTROL PANELS, ETC.. BY ELECTRICAL CONTRACTOR.
NEW ELECTRICAL METERING AND SERVICE EQUIPMENT SHALL BE PROVIDED AND INSTALLED ACCORDING TO THE LOCAL POWER UTILITY CO. AND CITY REQUIREMENTS. VERIFY ANDCOORDINATE WITH POWER UTILITY CO. AND AHJ BEFORE BID AND INSTALLATION.
COMPLY WITH NFPA 70E SAFETY REQUIREMENTS.
B.
C.
D.
PANELBOARDS WITH MORE THAN 42 CIRCUITS SHALL BE IN ONE CABINET ENCLOSURE,UNLESS OTHERWISE NOTED.
E.
PROVIDE 4"CONCRETE PAD FOR ALL DRY-TYPE TRANSFORMERS.F.
ALL TWO SECTION PANELBOARDS SHALL BE FEED THRU LUGS.G.
CONTRACTOR SHALL BE RESPONSIBLE FOR DELIVERY OF ELECTRICAL SERVICE TO THE NEWBUILDING WITHIN PROJECT SCHEDULE. COORDINATE ALL COST FOR LABOR ANDMATERIALS WITH LOCAL ELECTRICAL UTILITY COMPANY PRIOR TO BID. ALL COSTASSOCIATED WITH THE DELIVERY OF ELECTRICAL SERVICE INCLUDING ALL MATERIALSSHALL BE INCLUDED IN BID. TRANSITION OF NEW ELECTRICAL SERVICE SHALL PROCEED INWEEKENDS OR HOLIDAYS, INCLUDE ALL COST IN BID FOR OVERTIME FROM ELECTRIC UTILITYCOMPANY. NO ADDITIONAL PAYMENT WILL BE MADE FOR SERVICE DELIVERY COSTSAFTER CONTRACT HAS BEEN AWARDED.
H.
1
1
2
2
4
3
3
4
ELECTRICAL RISER
DRY-TYPE TRANSFORMER SCHEDULE
LA ENOIS N
LEONARDO MUNOZ
97437
F
N
PR
SCEF
LI
O
E
ATTE
S
O
ER
INSG
EED
S
TEXA
MEP ENGINEERING3533 Moreland Dr. Ste A l Weslaco, Tx78596 p:956.973.0500 l f:956-351-5750www.trinitymep.com I Copyright 2020Texas Registered Engineering Firm - F10362Project number:
PROJECT NO.:ISSUE DATE:
Project Status:
A Sheet Number
SHEET NAME
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19
B
C
D
E
F
G
H
J
K
L
M
N
P
DRAWN BY:CHECKED BY:
300 S. 8th Street, McAllen, Tx 78501T 956-661-0400 | goero.com
No.
Date
Desc
riptio
n
Q
R
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19
BIM
360
://20
042
San
Car
los
Gym
Add
ition
/20.
4.18
_Sam
Car
los
Gym
Adi
ttion
_CEN
TRAL
_202
0.rv
t3/
5/20
21 2
:58:
30 P
M
ER01
ELECTRICAL RISER
2004203.05.21
100% CONSTRUCTION DOCUMENTS
AuthorChecker
SAN
CARL
OS G
YMNA
SIUM
ADD
ITION
505 S
. 83R
D ST
, EDI
NBUR
G TX
7853
9ED
INBU
RG C
ONSO
LIDAT
ED IN
DEPE
NDEN
T SCH
OOL D
ISTR
ICT
03.05.21
1) PROVIDE INTEGRAL SURGE PROTECTION DEVICE, 100KA
Notes:
EMERGENCY LIGHTING 25 VA 100.00% 25 VA
Lighting 2650 VA 125.00% 3313 VA Total Est. Demand: 147 A
Power 1500 VA 100.00% 1500 VA Total Conn.: 149 A
Receptacle 13920 VA 85.92% 11960 VA Total Est. Demand: 122490 VA
Other 2650 VA 100.00% 2650 VA Total Conn. Load: 123788 VA
HVAC 103044 VA 100.00% 103044 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel TotalsTotal Amps: 154 A 146 A 148 A
Total Load: 42498 VA 40368 VA 40922 VA
H-41 -- -- -- -- 0 VA 0 VA 1 20 A Spare H-42H-39 -- -- -- -- 0 VA 0 VA 1 20 A Spare H-40H-37 1) SPD 30 A 3 0 VA 0 VA 1 20 A Spare H-38H-35 Spare 20 A 1 0 VA 0 VA 1 20 A Spare H-36H-33 Spare 20 A 1 0 VA 0 VA 1 20 A Spare H-34H-31 Spare 20 A 1 0 VA 0 VA 1 20 A Spare H-32H-29 Spare 20 A 1 0 VA 0 VA 1 20 A Spare H-30H-27 Spare 20 A 1 0 VA 0 VA 1 20 A Spare H-28H-25 Spare 20 A 1 0 VA 0 VA 1 20 A Spare H-26H-23 Spare 20 A 1 0 VA 0 VA 1 20 A Spare H-24H-21 -- -- -- -- 5300 VA 0 VA 1 20 A Spare H-22H-19 -- -- -- -- 6220 VA 0 VA 1 20 A Spare H-20H-17 45 kVA, 277 V/480 V, Three Phase, 4... 70 A 3 4#4, 1#8G,1.5"C 6550 VA 0 VA 1 20 A Spare H-18H-15 Lighting 20 A 1 2#12, 1#12G,1/2"C 240 VA 0 VA 1 20 A Spare H-16H-13 Lighting 20 A 1 2#12, 1#12G,1/2"C 890 VA 0 VA 1 20 A Spare H-14H-11 EMERGENCY LIGHTING 20 A 1 2#10, 1#10G,3/4"C 25 VA 0 VA 1 20 A Spare H-12H-9 Lighting 20 A 1 2#12, 1#12G,1/2"C 480 VA 0 VA 1 20 A Spare H-10H-7 Lighting 20 A 1 2#12, 1#12G,1/2"C 240 VA 800 VA 2#10, 1#10G,3/4"C 1 20 A Lighting H-8H-5 -- -- -- -- 17174 VA 17174 VA -- -- -- -- H-6H-3 -- -- -- -- 17174 VA 17174 VA -- -- -- -- H-4H-1 DXPU-1 70 A 3 4#4, 1#8G,1.5"C 17174 VA 17174 VA 4#4, 1#8G,1.5"C 3 70 A DXPU-2 H-2CKT Circuit Description Trip Poles Comments A B C Comments Poles Trip Circuit Description CKT
Power 1500 VA 100.00% 1500 VA Total Est. Demand: 16110 VA
Receptacle 13920 VA 85.92% 11960 VA Total Conn. Load: 18070 VA
Other 2650 VA 100.00% 2650 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel TotalsTotal Amps: 56 A 53 A 44 A
Total Load: 6550 VA 6220 VA 5300 VA
R-41 Spare 20 A 1 0 VA 0 VA 1 20 A Spare R-42R-39 Spare 20 A 1 0 VA 0 VA 1 20 A Spare R-40R-37 Spare 20 A 1 0 VA 0 VA 1 20 A Spare R-38R-35 Spare 20 A 1 0 VA 0 VA 1 20 A Spare R-36R-33 Spare 20 A 1 0 VA 0 VA 1 20 A Spare R-34R-31 Spare 20 A 1 0 VA 0 VA 1 20 A Spare R-32R-29 Spare 20 A 1 0 VA 0 VA 1 20 A Spare R-30R-27 Spare 20 A 1 0 VA 0 VA 1 20 A Spare R-28R-25 Spare 20 A 1 0 VA 0 VA 1 20 A Spare R-26R-23 Spare 20 A 1 0 VA 1200 VA 2#10, 1#10G,3/4"C 1 20 A Receptacle R-24R-21 Other 20 A 1 2#12, 1#12G,1/2"C 400 VA 1200 VA 2#10, 1#10G,3/4"C 1 20 A Receptacle R-22R-19 WH-1 20 A 1 2#10, 1#10G,3/4"C 1500 VA 250 VA 2#12, 1#12G,1/2"C 1 20 A Other R-20R-17 Receptacle 20 A 1 2#12, 1#12G,1/2"C 400 VA 1500 VA 2#12, 1#12G,1/2"C 1 20 A Receptacle R-18R-15 Receptacle 20 A 1 2#12, 1#12G,1/2"C 180 VA 800 VA 2#12, 1#12G,1/2"C 1 20 A Receptacle R-16R-13 Receptacle 20 A 1 2#8, 1#10G,3/4"C 1600 VA 1600 VA 2#6, 1#10G,1"C 1 20 A Receptacle R-14R-11 MOTORIZED SCREEN 20 A 1 2#12, 1#12G,1/2"C 400 VA 400 VA 2#12, 1#12G,1/2"C 1 20 A PROJECTOR R-12R-9 Receptacle 20 A 1 2#4, 1#8G,1.5"C 1500 VA 1200 VA 2#10, 1#10G,3/4"C 1 20 A ELECTRIC WINCH R-10R-7 FIRE ALARM 20 A 1 2#12, 1#12G,1/2"C 200 VA 200 VA 2#12, 1#12G,1/2"C 1 20 A INTRUSION/INTERCOM R-8R-5 E.D.F. 20 A 1 2#12, 1#12G,1/2"C 1200 VA 200 VA 2#12, 1#12G,1/2"C 1 20 A TELEPHONE R-6R-3 Receptacle 20 A 1 2#12, 1#12G,1/2"C 400 VA 540 VA 2#12, 1#12G,1/2"C 1 20 A Receptacle R-4R-1 Receptacle 20 A 1 2#12, 1#12G,1/2"C 600 VA 600 VA 2#12, 1#12G,1/2"C 1 20 A Receptacle R-2CKT Circuit Description Trip Poles Comments A B C Comments Poles Trip Circuit Description CKT