Many BIDOYNG units installed 250 Reclose operations after faults > 80% customer supplies restored successfully
11

Many BIDOYNG units installed ~ 250 Reclose operations after faults > 80% customer supplies restored successfully.

Jan 02, 2016

Download

Documents

Damon Ryan
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: Many BIDOYNG units installed ~ 250 Reclose operations after faults > 80% customer supplies restored successfully.

Many BIDOYNG units installed

~ 250 Reclose operations after faults

> 80%customer supplies

restored successfully

Page 2: Many BIDOYNG units installed ~ 250 Reclose operations after faults > 80% customer supplies restored successfully.

They said it would never fit there...

Page 3: Many BIDOYNG units installed ~ 250 Reclose operations after faults > 80% customer supplies restored successfully.

but it did!

Design of BIDOYNG means it fits in 90% of UK substations

but there are always exceptions...

Page 4: Many BIDOYNG units installed ~ 250 Reclose operations after faults > 80% customer supplies restored successfully.

“Fitting to an open indoor board will be easy”

words I may have uttered once

These stalks are part of an indoorLV fuse board. Check out the U shapedobstruction around the feeder stalk!!!

Page 5: Many BIDOYNG units installed ~ 250 Reclose operations after faults > 80% customer supplies restored successfully.

Fuse panels, layout, enclosures at LV substations vary greatly.

We created a solution for the obstructed stalks, at the same time solving a problem

for installation of REZAP

Page 6: Many BIDOYNG units installed ~ 250 Reclose operations after faults > 80% customer supplies restored successfully.

Kelvatek Web

Very successful for managing LV faults, notifications of fault events & reclose operations, and shows necessary BIDOYNG fuse replacements

Also has a button for access to power quality data

Page 7: Many BIDOYNG units installed ~ 250 Reclose operations after faults > 80% customer supplies restored successfully.

And we should get a nice data plot like this:

Page 8: Many BIDOYNG units installed ~ 250 Reclose operations after faults > 80% customer supplies restored successfully.

Dense data, taken every minute

Stockport produced over 22M data points in first month

Kelvatek Web data plotting slowed, and slowed, then stopped

Page 9: Many BIDOYNG units installed ~ 250 Reclose operations after faults > 80% customer supplies restored successfully.

Voltage and current are sampled at 51.2kHz (1024 samples per cycle)

Transients are recorded, along with pre-fault data, on all 3 phases

3 phase data is fed to SELF - Single Ended Location of Faults

Page 10: Many BIDOYNG units installed ~ 250 Reclose operations after faults > 80% customer supplies restored successfully.

Example SELF Algorithm result : Malwood Road Substation

Fault was arcing P-P, P-P-N, 3P & 3P-N

5 transient events recorded over 3 days

SELF Calculated a maximum distance of 99m

Fault located at 90m

Accuracy > 90 %

Page 11: Many BIDOYNG units installed ~ 250 Reclose operations after faults > 80% customer supplies restored successfully.

Short term outputs:

- Continued development of fault location algorithm

- Fault location available to all field staff

- Ease of access for power quality data

- Fast interactive data presentation