ADDRESSING SAFETY SYSTEMS WITH INTELLIGENCE Protec Fire Detection plc Protec Algo-Tec ™ 6300 INTERACTIVE DIGITAL ADDRESSABLE FIRE CONTROL SYSTEM MED0248 CI/SfB 68 92-048-61 8/2001 MANUFACTURING ACCOUNTS • R & D Protec Algo-Tec TM 6300 INTERACTIVE DIGITAL ADDRESSABLE FIRE CONTROL SYSTEM
8
Embed
MANUFACTURING Protec Fire Detection plc Protec Algo-Tec · Protec Fire Detection plc Protec Algo-Tec ... The Protec Algo-Tec™ 6300 system is on site programmable. All of the commissioning
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
A D D R E S S I N G S A F E T Y S Y S T E M S W I T H I N T E L L I G E N C E
Protec F i re Detect ion p lc
Protec Algo-Tec™ 6300INTERACTIVE DIGITAL ADDRESSABLE
FIRE CONTROL SYSTEM
MED0248
CI/SfB 68
92-048-61 8/2001
MANUFACTURINGACCOUNTS • R & D
Pro
tec
Alg
o-T
ecT
M
63
00
INTE
RA
CTIV
E D
IGIT
AL
AD
DR
ESS
AB
LEF
IRE
C
ON
TR
OL
S
YS
TE
M
A D D R E S S I N G S A F E T Y S Y S T
Protec F i re Detect ion p lc
Protec Algo-Tec™ 6300INTERACTIVE DIGITAL ADDRESSABLE
FIRE CONTROL SYSTEM
The Protec Algo-Tec™ 6300 InteractiveDigital Addressable System unwrapped:
The Protec Algo-Tec™ 6000 protocol developedby Protec’s in-house Research and Developmentteam is utilised by the Protec Algo-Tec™ 6300interactive digital addressable fire controlsystems. Immunity to false alarms, moreresponsive fire detection, and ease of use has allbeen achieved to develop one of the mostreliable systems available.
Protec Algo-Tec™ 6300
The name Algo-Tec™ is a derivative of Protecalgorithms. Algorithms are logical mathematicalprocedures for solving problems. Protec havedeveloped fire detection algorithms coupledwith fuzzy logic specifically designed to reduceunwanted fire alarms and to enhance thesensitivity of the system to true firephenomenon. The Algo-Tec™ algorithms areexclusively utilised by the Protec Algo-Tec™
6400 and 6300 Interactive Digital AddressableFire Control Systems.
Interactive
Algo-Tec™ evaluates the data of each fire sensorand is able to learn from the informationreceived. This may simply be to recognise that asensor is becoming contaminated or in a dirtyenvironment and to automatically increase thealarm threshold to compensate for thebackground levels (Threshold Compensation).More complex Algo-Tec™ functions include theability to discriminate between certain fire andnon-fire conditions, filtering out certainenvironmental stimuli, and increasing thesensitivity of a sensor when an increase intemperature is detected.The net effect of the interaction between thesensors and the Algo-Tec™ decision making isenhanced performance, through immunity tofalse alarms and more responsive fire detection.
Digital Addressable
The data communication between the sensorsand the control equipment is Digital. The Algo-Tec™ protocol utilised by the 6000system enables high levels of data to betransferred, providing far more detailedinformation than was previously achievablewith analogue addressable systems. It shouldhowever be noted that many analogueaddressable systems use digital communicationbut do not transfer the high levels of dataassociated with the Algo-Tec™ protocol. Speed,stability, excellent EMC and security all serve toenhance the Algo-Tec™ Digital signalling. Whygo analogue addressable when you can nowchoose Algo-Tec™ Digital Addressable.
Typical 6300 Network System
BUILDING
BUILDING 1
BUILDIBUILDING 5B
Algo-Tec™ 6300Control Panel
Algo-Tec™ 6300Control Panel
6300
Zonal Mimic
230v AC
24v DC From Panel or P.S.U. 230v AC
Up to 32 panels
2 Core RS485 Secure Network
E M S W I T H I N T E L L I G E N C E
FEATURES & BENEFITS
• Cost Effective -High spec i f i ca t ion in teract ive d ig i ta laddressable fire detection and alarm system,providing a cost effective solution for small,medium and large sized buildings and sites.
• Design Flexibility -Up to 32 control panels, repeats andilluminated zonal mimics can be networkedenabling system design and expansion to beeasily achieved to suit the site for economicwiring and operational convenience.
• Secure Network - Wired as a loop, the network’s dual channelRS485 link ensures that no single fault willaffect the system.
• Easy to Install -An extensive range comprising Loop PoweredAlarm Sounders, Beacons, Interfaces, ManualCall Points and Sensors can all be connected tothe nearest control panel using a single 2-corecable for each of the high capacity Loops (up to4), accommodating up to 191 devices perLoop, 512 maximum per panel.
• Reduced False Alarms -The Protec Algo-Tec™ 6000 interactive firesensors utilise advanced discriminatingalgorithms for maximum reliability andimmunity to false alarms.
• Enhanced Performance -The Protec Algo-Tec™ 6000 sensors learn fromtheir environment, applying interactive decisionmaking algorithms to provide stability,threshold compensation and optimisedperformance.
• Secure Detection Loops -Many Protec Algo-Tec™ 6000 devicesincorporate built-in short circuit isolator units.These can be located as required.
• Easy to Address -‘FAST’ addressing (Firmware Addressed SecureTechnology) ELIMINATES troublesome and timeconsuming setting of address cards and DILswitches.
• Devices Display Address Number -‘RVAV’ Remote Visual Address Verification.Confirmation of the correct location of eachdevice can be easily identified, using thedevices in-built LED to indicate the deviceaddress number.
• On Site Flexibility -Configuration of all system functions is fully siteprogrammable.
• Reduced Maintenance Costs - Early indication and reporting of sensorsapproaching contamination level reduce falsealarms and enable dirty sensors to be cleanedor replaced.
Designed to EN54 parts 2 & 4 1998 Pro
tec
Alg
o-T
ecT
M
63
00
INTE
RA
CTIV
E D
IGIT
AL
AD
DR
ESS
AB
LEF
IRE
C
ON
TR
OL
S
YS
TE
M
2
BUILDING 3
BUILDING 4ING 5A
Algo-Tec™ 6300Control Panel
Algo-Tec™ 6300Control Panel
Algo-Tec™ 6300Control Panel
230v AC 230v AC
230v AC
on a network
A D D R E S S I N G S A F E T Y S Y S T
Protec F i re Detect ion p lc
Protec Algo-Tec™ 6300INTERACTIVE DIGITAL ADDRESSABLE
FIRE CONTROL SYSTEM
User MenuThe MENU button enables the user to access the user menu functions.The functions available include isolation menu, set up time and walktest and advanced options which include printer menus, display theevent log, read analogue data and view device address text.The isolation menu enables the user to easily isolate individual devicesor zonal areas. During any isolation the disablement indicator will turnon accompanied by details of the isolations displayed on the LCD.
6300 Illuminated Zonal MimicThe Protec 6300 customised, illuminated zonal mimic can beconnected to the 6300 control panel in the same way as the 6300repeat panel. The Illuminated mimic is housed in a matching enclosureto the control and repeat panels. The fascia is manufactured fromKemco finished in anodised aluminium effect and can be engraved toour clients scaled drawing typically detailing the building outline andzonal areas and has a viewing area of 360mm W x 340mm H . Up to32 LED’s can be placed on the fascia and will be illuminated by theappropriate zone activation. The illuminated mimic is available assurface or recessed mounted with a hinged door finished in storm grey,or optionally with a polished solid brass or brushed stainless steel finishrecess mounting enclosure and an engraved Kemco fascia in anodisedaluminium or brushed brass effect finish.
CONTROLS & DISPLAYS
System Features
The Protec Algo-Tec™ 6300 is an interactivedigital addressable fire detection and alarmsystem ideally suited for small , medium & largesized buildings such as nursing homes, hotelsand offices. The control panel is designed andmanufactured by Protec to comply with EN54parts 2 & 4 1998. The control panel is availableas surface or recessed mounted with a mouldedpolycarbonate hinged door finished in stormgrey, or optionally with polished solid brass orbrushed stainless steel finish for recessmounting only.
Secure NetworkUp to 32 Algo-Tec™ 6300 control and repeatpanels and illuminated zonal mimics can beinterconnected using the optional add in 6300network card. Wired as a loop the networksdual channel fault tolerant RS485 ensures thatno single fault can disable the system. In theevent of multiple faults, each panel will functionindependently. The network can be wired usingcopper or fibre optic cables.
Non Networked Stand Alone SystemFor small single panel systems, the serialcommunication link can be utilised to signal, upto 4 repeat panels using a 4 core screenedcable. A network card is not required.
LoopsEach 6300 control panel is equipped with 1,2or 4 high capacity Algo-Tec™ digital addressabledata loops, with up to 191 address capacity perloop. Total panel devices is restricted to 512inputs to comply with EN54 part 2. In additionto sensors, interfaces and manual call points theloop can also support loop poweredSOUNDERS, BEACONS and OPTICAL BEAMDETECTORS. Loop powered sounder basesadopt the sensor address to increase thecapacity of the loops still further, resulting inreduced cabling requirements, simplifiedinstallation and associated cost savings.
AlarmsIn addition to loop powered sounders andbeacons, 4 programmable fully monitoredalarm outputs are provided at the panel foralternative wiring arrangements.
Auxiliary ContactsOne set of double pole changeover contacts,which are programmable.
Isolation
MenuIsolate
Address Printer
Menu
Analogue
Data
Event
Log
Device
Data
Delay
Data
Printer
Menu
Active
Event
Program
Matrix
Abort
Print-Out
Display
Event log
Read Analogue
Data
View Text
Engineers Test
RVAV
Exchange
Devices
View Address
Isolated
Fire Link
Disablement
IsolateZone
View Zones
Isolated
Normalise
Disablements
Set-up
Time
Advanced
Options
Clear
Proc. Fault
Simple Menu Structure Zoned Mimic Panel
E M S W I T H I N T E L L I G E N C E
6300 Repeat PanelThe Protec 6300 repeat panel can be connected to the 6300 controlpanel’s serial communications link connection, using a 4-core screenedcable. If the 6300 secure network is utilised then the repeat panel should beconnected to the secure network by adding the integral 6300 networkcard. The repeat panel has an identical display to the control panelincluding 80 character LCD and 32 zone fire LED’s. Full control ofsilence, accept, sound alarms and reset is included and can bedisabled. The repeat panel is available as surface or recessed mountedwith a moulded polycarbonate hinged door finished in storm grey, oroptionally with polished solid brass or brushed stainless steel finish forrecess mounting only.
On Site Programming The Protec Algo-Tec™ 6300 system is on site programmable. All of thecommissioning configuration data can be entered and/or backed upusing the Protec 6300/WINPROG windows based programmingsoftware via a P.C. This feature enables the system to be re-configuredand checked prior to attending site simplifying commissioning workson site, enabling text amendments to be carried out whilst on site andproviding an invaluable remote backup should the need arise. Thesystem configuration data can also be printed using the control panelsoptional in-built thermal printer.
Pro
tec
Alg
o-T
ecT
M
63
00
INTE
RA
CTIV
E D
IGIT
AL
AD
DR
ESS
AB
LEF
IRE
C
ON
TR
OL
S
YS
TE
M
Controls and Display
All the functions of the Control Panel are
accessed via a modern styled hinged
lockable door, moulded from polycarbonate
with a clear display viewing window. When
opened the door reveals the panel controls
and easy to follow operating instructions.
These controls are SILENCE, SOUND
ALARMS, RESET and ACCEPT plus a MENU
push button to enable access to the user
menu facilities. The control panel display
consists of an 80 large character liquid
crystal display, twin common fire LED
indicators, 32 separate zonal fire LED’s,
power on, pre-alarm, system fault, common
fault, test and disablement LED’s. An
optional integral low noise thermal printer is
also available.
Liquid Crystal DisplayThe 80, large character liquid crystal display
will under normal quiescent conditions
display the current date and time with the
option to also display a 40-character user’s
message such as site name.
In an alarm or fault condition the LCD will
display the device loop, address and zone
number and up to 40 characters of user
definable location text, programmable on
site using Protec 6300/WINTEXT windows
based software.
Device Location TextWindows based text software is supplied
free of charge to our clients to enable you to
enter the location text on to the disk
supplied and hand to our commissioning
engineer for loading into the panel during
commissioning. This simple process allows
you more flexibility enabling you to make
any last minute changes & speed up the
entire process.
PrinterThe integral printer is a 40-character low
noise thermal printer. In operation the
printer will provide on demand real time
data of fire and fault conditions including
time and date of events along with the
device number and location text. By
accessing the appropriate function from the
user menu facility a variety of reports can be
printed including the previous 100 incidents
from the event log, the system devices
configuration and programming matrix,
devices which are becoming due for
cleaning and the current status of all devices.
Power SupplyThe 6301, 6302 and 6304 control panels
can be supplied with an integral 3A DC
switch mode charger and a 24V 10 a/h
sealed lead acid battery. The system is also
available, suitable for use with Protec
6000/BC range remote power supplies
with an extensive range of battery and
charger sizes.
Repeat Panel On-Site Programming
SI
LSI
LSI
LSO
SO
ISIS
L
L
L
Ionisation Smoke Sensor
Beam Detector Control Unit
Beam Detector Receiver Unit
Beam Detector Transmitter Unit
Loop Isolator
Loop Sounder
Standard Sounder
Optical Smoke Sensor
Optical Smoke Sensor with dual isolator base
Optical Smoke Sensor with loop sounder base
Ionisation Smoke Sensor with dual isolator base
Ionisation Smoke Sensorwith loop sounder base
Temp Sensor with dual isolator base
Temp Sensor with loop sounder base
Duct probe unit c/w smoke sensor
Sprinkler flow switch
Manual call point
Interface
DP
SI
SI
SI
SO
SO
H
H
SO
IS
RX
TX
L
L
c™ 6300ol Panel
LOOP 2
230v AC Supply
4 Programmable monitored alarm outputs
2 Auxiliary fire C/O contacts
Fault C/O contacts
24V Aux. Output
Bomb alert/Class change input
Plant shutdown output(Rated at 240v 5A)
Sprinkler delayinterface 6000/MICCO
EOL
24V supply (4C)
Power supply unit
230v
BCI/2.8
6000/ZAIMonitoredinput/outputinterface
Monitored Fire Station output
}
}
Pro
tec
Alg
o-T
ecT
M
63
00
INTE
RA
CTIV
E D
IGIT
AL
AD
DR
ESS
AB
LEF
IRE
C
ON
TR
OL
S
YS
TE
M
6000/BGK FAST™ Addressable Manual CallPoint - Key operated test facility, aloop short circuit isolator isincorporated.
6000/DP Ventilation Duct Smoke SensorAssembly - Single pipe air samplingunit for air speeds from 0.2 to 15m persec. supplied with 6000/BASE suitablefor use with 6000/OP FAST™
interactive optical smoke sensor.
6000/BEAM FAST™ Addressable Loop PoweredBeam Detector - Comprising of acontrol unit, receiver unit andtransmitter unit. With a beam range of10-100 metres.
6000/SYM2R FAST™ Addressable Loop PoweredElectronic Sounder - 100dBA soundoutput at 1m, 8mA loop alarm load. 3sounder tone options; constant, pulseor warble, selectable by the controlpanel.
6000/SRZ2R FAST™ Addressable Loop PoweredWeatherproof Electronic Sounder -100dBA sound output at 1m, 20mAloop alarm load. 3 sounder toneoptions; constant, pulse or warble,selectable by a DIL switch on the unit.
6000/SRZ4R FAST™ Addressable 4-WireWeatherproof Electronic Sounder -100dBA sound output at 1m, 20mAauxiliary 24vdc from local powersupply. 3 sounder tone options;constant, pulse or warble, selectableby a DIL switch on the unit.
6000/FIU Flush Mounted Short CircuitIsolator Unit - To isolate a short circuitfault on either the incoming oroutgoing loop cables. Suitable for a30mm deep electrical mounting box.
6000/ZAI FAST™ Addressable Flush MountedZone Alarm Interface Unit - With amonitored detection circuit suitable foruse with Protec 3000 series detectiondevices. Line continuity maintained.Monitored alarm output circuit rated at
24Vdc 1A max. Suitable for a 45mm deep electricalmounting box. A loop short circuit isolator is included.
6000/MICCO FAST™ Addressable Flush MountedLoop Powered Monitored Input,Clean Contact Output InterfaceUnit - With a monitored input circuitsuitable for use with simple switchdevices and the output is a cleanchangeover contact 5amp rated at
240Vac. A link can be cut to provide a 7-second delay tothe input. Suitable for a 45mm deep electrical mountingbox. A loop short circuit isolator is incorporated.
Multi-way Input/Output Interfaces - A range of 16way input/output interfaces areavailable with monitored alarmoutputs or clean changeover contacts.All interfaces are FAST™ addressable.
6000/PVR2R FAST™ Addressable Loop PoweredXenon Beacon - 0.4J flash energy,45mA loop alarm load. Red beaconbody and lens.
Heavy duty plant shutdown signal (Rated at 240v 5A)
4C
Single 2 wire loop cable
4 Core serialcommunications link(up to 4 Repeaters)
6300ZONALMIMIC
6300REPEATPANEL
2 Core RS485 Network Using 6300 Netcardin Each Panel/Repeater (up to 32 panels)
6300CONTROL
PANEL
6300CONTROL
PANEL
6300ZONALMIMIC
6300CONTROL
PANEL
6300REPEATPANEL
6300CONTROL
PANEL
6300 Serial Communication Link
6300 Secure Network
NOTE: The Serial Communication Link cannot be used if the secure network (option 2) is chosen.
Option 1
OR
Option 2
6000/ASB2 FAST™ Addressable Loop PoweredElectronic Sounder Base - 90dBAsound output at 1m, 5mA loop alarmload. 3 sounder tone options;constant, pulse or warble, selectableby the control panel. A loop shortcircuit isolator is incorporated.
Protec F i re Detect ion p lc
Protec Algo-Tec™ 6300INTERACTIVE DIGITAL ADDRESSABLE
FIRE CONTROL SYSTEM
A D D R E S S I N G S A F E T Y S Y S T
Loop Devices
The Protec Algo-Tec™ 6000 protocol utilises FAST™
addressing (Firmware Addressed Secure Technology).Every FAST™ device is manufactured with a uniqueserial number.FAST™ addressing ELIMINATES troublesome and timeconsuming address cards and DIL switching whilstbeing far more secure than “soft addressing”.
6000/OPHT FAST™ Interactive Optical Smokeand Heat Multi-Sensor - UtilisingProtec Algo-Tec™ 6000 interactiveprogrammable algorithms, the sensorsare suitable for use in all smokedetection applications.
interactive programmable algorithms,the sensors give a fast response totemperature increases.
6000/BASE Low Profile Common MountingBase - Compatible with the aboverange of Protec Algo-Tec™ 6000sensors.
6000/DIB Dual Loop Short Circuit IsolatorBase - To isolate a short circuit fault oneither the incoming or outgoing loopcable and maintain the operation ofthe sensor head inserted into the dualisolator base.
6000/ASB4 FAST™ Addressable 4-WireElectronic Sounder Base - 90dBAsound output at 1m, 8mA auxiliary24vdc from local power supply. 3sounder tone options; constant, pulseor warble. A loop short circuit isolatoris incorporated.
6000/ASBEA2 FAST™ Addressable Loop PoweredElectronic Sounder Beacon Base -90dBA sound output at 1m, beacon flashrate: 0.25 sec on, revolving LED lightpattern. 11mA loop alarm load. 3 soundertone options, constant, pulse, or warble,selectable by the control panel. A loop shortcircuit isolator is incorporated.
Table detailing the loop standby and alarm load for typical
Algo-tec™ 6000 devices.
Note: The following Loop Parameters should be observed1) The total number of addressable devices should not exceed 191 per loop.2) The total loop alarm load should not exceed 600mA per loop.* Auxiliary 24Vdc supply required.
Protec F i re Detect ion p lc
A D D R E S S I N G S A F E T Y S Y S T E M S W I T H I N T E L L I G E N C E
Company policy is one of continuous improvement, we reserve the right to change specifications without prior notice.
Specification:-Power Supply Mains 230V AC nominal ± 10%.Working Voltage 21.5 - 30V DC.Temperature Range 0 - 40 degrees centigrade.Maximum Humidity 85% Non-condensing.Panel Model 6301 6302 6304Standby Load (Mains Fail Condition) 90mA 115mA 170mAAlarm Load (Mains Fail Condition) 210mA 260mA 345mA
Display Backlit liquid crystal display 2 lines of 40 characters.Digital Addressable Loops 1,2 or 4 loops, each with 191 address capacity. Total panel capacity is restricted to
512 Input addresses to comply with EN54 part 2. Algo-Tec™ 6000 Protocol.Total Loop Load 600mA per loop including all loop connected devices.Zones 32 Zone LED’s plus twin red common fire indicators.Integral Charger 3Amp DC Switch-mode.Integral Battery 10 ampere-hour 24V sealed lead acid.Remote Power Supply The Protec 6000/BC range of power supplies are compatible with the 6300 panels.
Dual path outputs and fault signalling, (4 wire plus 2 wire, 2 primary power, 2 signals, 2 secondary power).
Programmable Alarm Outputs 4 Monitored - Internal sounder circuits (1A rated @ 24V)1 Set of non-monitored double-pole changeover contacts (1A rated @ 24V).Up to 191 alarm outputs per loop with the use of additional loop O/P devices.
Alarm Load Maximum 3A with integral power supply unit.Fault Monitoring Fully fault monitored to EN 54 Pt 2 1998.Fault Output Single pole changeover contacts (1A rated @ 24V).Serial Communications Interface 4 wire (2 power, 2 data) for up to 4 repeat/mimic panels.Secure Network To replace above serial interface when optional 6300 network card fitted to allow
up to 32 panels/repeaters to be securely networked. (2 wire loop).Auxiliary Output Supply 24V DC fused at 250mA.Common Fire Output (fire station) 24V DC fully monitored output rated at 20mA. 1K EOL.Common Fault Output (fire station) 24V DC fully monitored output rated at 20mA. 1K EOL. RS232 Communications Interface 9 way 'D' type connector (Male). For program/text software upload/download.Optional Integral Printer 40 character low noise thermal printer. Dimensions 440 X 385 X 144mm.
Programmability96 Input Groups System Wide First 32 have an independent programmable time-out delay.96 Output Groups per Panel First 32 have an independent programmable delay for first 32 input groups.
Each is programmable as an alarm or control output.32 Zonal Output Groups per Panel Each is activated by a separate zone input for zones 1 to 32.
6300 Repeat Panel/6300 Illuminated Zonal MimicPower Supply 24V DC from local power supply or internal charger and battery (230v AC required)Standby Load 50mA.Alarm Load 50mA.Serial Communications Link 4 wire (2 power, 2 data) for up to 4 repeat/mimic panels.Secure Network To replace above serial interface when optional 6300 network card fitted to allow up to
32 panels/repeats to be securely networked. (2 wire loop).Dimensions 440 X 385 X 144mm.
6300 Netcard Optional network card fitted to each control panel and repeat to be networked.The network card replaces the serial communication link. Up to 32 panels/repeatscan be securely networked (2 wire loop).