Manual MPA 4112 PF No. 271 958 - GB Edition: 12.15 GB
1 … 90
Prin
ted
in G
erm
any
• Edi
tion
12.1
5 • N
r. 27
1 95
8
ManualMPA 4112 PF
No. 271 958 - GB
Edition: 12.15 GB
3 … 902 … 90
Table of contents
Data sheet ............................................................................................................................................................ 5-8Approval overview ...................................................................................................................................................9System description/Variants/Accessories ..........................................................................................................10General technical data ..........................................................................................................................................11Connection diagram ..............................................................................................................................................12Technical data outputs/inputs ........................................................................................................................ 13-15Flame detection/Flame detector connection ................................................................................................ 15-16Installation MPA 412x17Dimensions MPA 412x18Description of the functionsUnlocking functionExtended unlockingAccess level ...........................................................................................................................................................19Description of the functionsGas valvesFlame detectorAir pressure switchHT signal, gas pressure switch or proof-of-closure contactParameterisation mode (manual operation)Automatic/Parameterisation mode function switch ..........................................................................................20Flow Chart ........................................................................................................................................................ 21-22Description of the states ................................................................................................................................ 23-26Parameters/Parameter change ............................................................................................................................27Parameters/Parameter description ................................................................................................................ 28-36Parameters/Factory setting ............................................................................................................................ 37-38Status information ........................................................................................................................................... 39-40MPA 41x2/Version with display ............................................................................................................................41MPA 41x2/Overview of the display modes ..........................................................................................................42MPA 41x2/On-screen display ...............................................................................................................................43MPA 41x2/Operation display ................................................................................................................................44MPA 41x2/Operation display additional information .........................................................................................45MPA 41x2/Operation display parameterisation and service box .....................................................................46MPA 41x2/Info display ...........................................................................................................................................47MPA 41x2/Error display ........................................................................................................................................48MPA 41x2/Error memory display .........................................................................................................................49MPA 41x2/Parameterisation display .............................................................................................................. 50-56MPA 41x2/Reset display ................................................................................................................................. 57-58MPA 41xx errors without error ID ........................................................................................................................59MPA 41xx errors from the basic system ....................................................................................................... 60-61MPA 41xx errors from the extension system ......................................................................................................62Errors from the application ..................................................................................................................................63Annex ......................................................................................................................................................................64Setting the bus address, bus termination .................................................................................................... 65-66Profibus ............................................................................................................................................................ 67-71Modbus ............................................................................................................................................................. 72-80Flame detector ................................................................................................................................................. 81-82UV 41 (HE). ....................................................................................................................................................... 83-84Ignition transformers ...................................................................................................................................... 85-87VisionBox ...............................................................................................................................................................88
Prin
ted
in G
erm
any
• Edi
tion
12.1
5 • N
r. 27
1 95
8
3 … 902 … 90
Prin
ted
in G
erm
any
• Edi
tion
12.1
5 • N
r. 27
1 95
8
The target group of this manual is qualified personnel of the gas safety and regulating technology, skilled per-sonnel or the persons instructed by them.Due to their specialist training, knowledge and experience and knowledge of standard regulations, they are capable of evaluating the work assigned to them and recognising possible dangers. Only they are permitted to carry out as-sembly, commissioning, settings and maintenance on the devices in compliance with the recognised rules for occupa-tional safety.
Instruction manual
MPA 4112 PF
2. Warnings
Never carry out work as long as gas pressure or voltage is applied. Avoid open fire. Please observe public regula-tions.
The device must be protected from vibrations and mechanical impacts.
All adjustments and settings should only be performed in accordance with the instruction manuals of the connect-ed machines.
The recognised occupational safety rules and accident prevention regula-tions must be observed and, if neces-sary, personal protective measures must be taken.
Connected line systems must be free from dirt and contamination.
Hang this instruction manual in a readily visible place inside the installation room! Do not carry out any work until you have read the safety instructions of this instruction manual.
The device may only be operated in compliance with the operating condi-tions stated on the type plate.
Prior to assembly, the device must be inspected for transport damage.
The device must not be used in areas with increased seismic risk.
Protection from environmental impacts and weather conditions (corrosion, rain, snow, icing, humidity (e.g. by conden-sation), mould, UV radiation, harmful insects, poisonous, corrosive solutions/liquids (e.g. cutting and cooling fluids), must be guaranteed. Depending on the installation site, it may be necessary to take protective measures.
The device must not be exposed to open fire. Protection against lightning strikes must be guaranteed.
2.1 General warnings
1. Target group
Explanation of the symbols1, 2, 3,... = Order of action• = Instruction
GB
5 … 904 … 90
Prin
ted
in G
erm
any
• Edi
tion
12.1
5 • N
r. 27
1 95
8
2.2 Designated use
The device is used in accordance with its designated use if the following instructions are observed:• Use only in compliance with the operating conditions
stated on the type plate.• Use in perfect condition only.
2.3 Risks in case of misuse
• If used in accordance with their designated use, the devices are safe to operate.
• Non-observance of the regulations may result in personal injuryormaterialdamage,financialdamageorenviron-mental damage.
• Operator errors or misuse present risks to life and limb of the operators and also to the device and other material property.
• Malfunctions and faults must be eliminated immediately.• Use only in observance of the instructions given in this
instruction manual and of national regulations.
5 … 904 … 90
µP Automatic burner control systemMPA 4112 PF
Automatic burner control system for high-speed burners with fast On/Off switching (pulse firing)
DescriptionMicroprocessor-controlled automatic burner control system for the intermittent operation of high-speed burners with fast On/Offswitching(pulsefiring).The program sequence and times can be customised by setting software pa-rameters.
Versions• MPA4112PFwithintegrateddisplay
ApplicationForhigh-speedburnerswithfastOn/Offswitching(pulsefiring).Inparticularforindustrial thermoprocessing equipment toEN746-2.
ApprovalsECtype-examinationcertificateaccord-ing to the EC gas appliances directive:MPA41xx CE-0085BU0487
ECtype-examinationcertificateaccord-ingtotheECPressureEquipmentDirec-tive:MPA41xx CE0036
Suitable for applicationsup toSIL3.Meets the requirement according to IEC 61508(2ndEd.2011)CertifiedbyTÜVSüd
CSAcertifiedproductaccordingtoCSA22.2
ULRecognizedComponentperUL372,UL 1998.Pr
inte
d in
Ger
man
y • E
ditio
n 12
.15
• Nr.
271
958
• Automatic burner control system for pulse firing applications
• Fast On/Off switching
• High number of switching cycles possible
• High temperature operation pos-sible
• Configurable
7 … 906 … 90
TheMPA4112PFissuitableforusewithhigh-speed burners with fast On/Offswitching(pulsefiring).Flamemonitoringiscarriedoutbymeansof an ionisation input.
• MPA4112PFcanbeconfiguredviadisplaywithoutlaptop/PC
• High temperature operation can be activated using an external switching signal
• Extension module for Profibus andModbus communication
• Airpurgefunction(viabus)
Connection diagram MPA 4112 PF
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
P
N G
P
6.3A T (10A F)
L1
N
PEG
L1N
PEG
L1
5A T
Ionisation
Not used
SupplyVentilation
Safety chain
Operation
Fault
Ignition transform
er High temperature NC
High temperature NO
Air pressure switch
Heat request
Reset
V1V2
Not used
Flame detector
supply
*Theconnectioncablesusedmustbesuitableforanambienttemperatureofatleast75°C(167°F).
Prin
ted
in G
erm
any
• Edi
tion
12.1
5 • N
r. 27
1 95
8
7 … 906 … 90
Display modesOperation display
• Display of the current operating state
• Display of the program state• Display of bus address
Info display
• Displayofflamequality• Display of resettable counters for
start-up, operating hours and switch-ing cycles
Error displayDisplay of the error memory
• Automaticactivationoferror messages
• Additionalinformationaboutfaults• Query of the ten last errors
Parameterisation display
• Password-protected functional lev-els for service and OEM parameter settings
• Setting important parameters such as: Pre-venting timeSafety time for start-upPost-venting timeBehaviour after flamefailure
Accessories
UV 41 (HE) UVflamedetector forhighmechani-cal load; metallic version. Suitable for intermittent operation.
Communication
MPA 41 extension module EM2/4Additionalcircuitboardandconnectorset forProfibusDPandModbuscom-munication.
Parameter setting and serviceMPA 41 parameterisation and service boxUniversal support for device checking in thefield;forproducingsmallandmediumseries.
MPA Vision BoxAsadditiontoMPA41parameterisationand service box for setting parameters viaaPC/laptop.
The program sequence and times can bemodifiedonthemounteddisplaytomatch each application.A laptop or PC is not required for themodification.The automatic systems are protected by passwords against unauthorised access.AllsettingsfortheMPA4112PFauto-matic burner control system can also be
madebymeansofalaptop/PCviaMPAVisionBox.
Prin
ted
in G
erm
any
• Edi
tion
12.1
5 • N
r. 27
1 95
8
9 … 908 … 90
Subjecttotechnicalmodificationintheinterestoftechnicalprogress.
µP-Automatic burner control systemMPA 4112 PF
Automatic burner control system for one-stage and modulating gas burn-ers
Technical dataRatedvoltage 115VAC-15%...+10%(dependingonthemodel) 230VAC-15%...+10%Frequency 50Hz...60HzPowerconsumption max.10VAFuse max.6.3Aslow-blowor10Afast-blowOperatingsignal max.1AInterferingsignal max.1AGasvalves max.2AFan max.1AIgnition max.1AFlamedetectorsupply 230VAC/10mAFlamedetector lonisationlonisationcurrent/operation 10-20µAShutdownsensitivity 1.2µAShortcircuitcurrentlimiting approx.280µAUnlockingduetofault PushbuttonsandremoteunlockingProtectiontype IP54Ambienttemperature -40°C-+70°C Ordering dataMPA4112/230VAC Articleno.270520MPA4112/115VAC Articleno.270528
Extension module on requestEM2/4MPA411xProfibusDP,Modbus
FlamedetectorUV41 Articleno.256692UV41HE Articleno.260575
Company addressKarl Dungs GmbH & Co. KGSiemensstraße 6-10D-73660 Urbach, GermanyPhone +49 (0)7181-804-0Fax +49 (0)7181-804-166
Postal addressKarl Dungs GmbH & Co. KGPostfach 12 29D-73602 Schorndorf, Germanye-mail [email protected]: www.dungs.com
152.5
77
151.
5
Dimensions [mm]MPA 4112 PF
Prin
ted
in G
erm
any
• Edi
tion
12.1
5 • N
r. 27
1 95
8
9 … 908 … 90
MPA4112 PF UV41 (HE) Components SIL SFF PFHX Ionisation input 3 99.48% 1,80E-09X Input HT 3 99.39% 1,80E-09X X UV41+ionisationinput 2 96.91% 1,50E-07
Prin
ted
in G
erm
any
• Edi
tion
12.1
5 • N
r. 27
1 95
8Overview of approvals Article
numberCE FM UL
recog-nized
UL listed
CSA C22.2
EAC AGA
MPA4112PF/AC230V 270520 x x x xMPA4112PF/AC115V 270528 x x x x xExtension moduleEM2/4MPA411x 257960 x x x x x (x)*Flame detectorUV41 256692 x x x x x xUV41 HE 260575 x x x x x (x)*Ignition transformersDEZ 1xx all x (x)* xDEZ 2xx all x (x)* x
Overview of approvals
Safety Integrity Level (SIL)* on request
11 … 9010 … 90
Prin
ted
in G
erm
any
• Edi
tion
12.1
5 • N
r. 27
1 95
8
1 MPA 4112 PF system description
TheMPA4112PFissuitableforusewithhigh-speed burners with fast On/Offswitching(pulsefiring).Flamemonitoringiscarriedoutbymeansof an ionisation input. High temperature operation can be activated using an external switching signal.
TheMPA41xxparameterisationandservice box is available for the produc-tion of small series and for checking the system when service is required.
Foroperationinburnernetworks,aProfibus/ModbuscommunicationovertheextensionmoduleEM-2/4ispos-sible.
Designation Article no. Voltage DisplayMPA4112PF 270520 230VAC 3-digit
7-segment displayMPA4112PF 270528 115VAC 3-digit
7-segment display
System variants
Accessories
Ignition transformers:- DEZ xxx- Mains connection line- Ignition line
Flamedetector:-UV:UV41,UV41HE
Extension module EM-EM2/4:ProfibusDP,Modbus
11 … 9010 … 90
Prin
ted
in G
erm
any
• Edi
tion
12.1
5 • N
r. 27
1 95
8General MPA 4112 PFProtectiontype
MPA4112PF IP54/NEMA12AmbienttemperatureMPA4112PF
-20°C...+60°CwithULapproval-40°C...+70°C
Storage and transport -40°C...+80°CHumidity DIN60730-1,nodewingadmissibleAltitude Suitableforuseupto2000mabovethebaseheightlevelLifetime Switching outputs
Atleast2.5millionswitchingoperationsdependingonthecontactload
Mounting position as desiredDimensions MPA4112PFin mm
MPA4112(LxHxD):approx.152.5x151.5x77mm
Technical data
Electrical dataRated voltage 230VAC-15%...+10%or
115VAC-15%...+10%,dependingontheversionFrequency 50Hz/60HzFuse 6.3Aslow-blowor10Afast-blow,integrated,5Aslow-blowinthefuseholder,replaceableIsolation Nogalvanicisolationbetweenmainsand24VDCor5VDCElectrical connection Correct (!) phase connection and protective earth conductor according to the wiring
diagramThe contact protectionfortheUVsensormustbeguaranteedbymountingitintheoper-ating equipment
Powerconsumption(ownconsumption)
Maximum10W
Typically115V230VStandby2.7W3.6WOperation3.4W6.1W
WithextensioncardEM2/4:Standby4.0W...4.7WOperation4.6W...7.4W
Short-circuit current ION against N
280µA
13 … 9012 … 90
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
P
N G
P
6.3A T (10A F)
L1
N
PEG
L1N
PEG
L1
5A T
Ionisation
Not used
SupplyVentilation
Safety chain
Operation
Fault
Ignition transform
er High temperature NC
High temperature NO
Air pressure switch
Heat request
Reset
V1V2
Not used
Flame detector
supply
*Theconnectioncablesusedmustbesuitableforanambienttemperatureofatleast75°C(167°F)
Prin
ted
in G
erm
any
• Edi
tion
12.1
5 • N
r. 27
1 95
8
Connection diagramMPA 4112 PF
Attention:
After having removed the hood, you might get in contact with the elec-trical connections in the terminal socket. Risk of fatal electric shocks!Therefore, you must interrupt the power supply before removing the hood.
Do not remove the jumper between terminals 1 and 2, which was mounted in the factory. It is required for the intended use of the automat-ic burner control system.
13 … 9012 … 90
Prin
ted
in G
erm
any
• Edi
tion
12.1
5 • N
r. 27
1 95
8OutputsDesignation Connec-
tion XSafety-related
Type of output Line length Electrical data
V1Safety valve
13 x Relay contact Max.100m For250000switchingcycles:115/230VAC/2Acosϕ=1For2.5millionswitchingcycles:115/230VAC/1Acosϕ=1Minimum load 0.5 W
V2configurable 14 x Relay contact Max.100m For250000switchingcycles:115/230VAC/2Acosϕ=1For2.5millionswitchingcycles:115/230VAC/1Acosϕ=1Minimum load 0.5 W
Ignition 15 x Relay contact Max.100m For250000switchingcycles:115/230VAC/1Acosϕ=0,4corresp.115/230VAC/2.5Acosϕ=1For2.5millionswitchingcycles:115/230VAC/1Acosϕ=1Minimum load 0.5 W
Ventilation 8 - Relay contact Max.100m For250000switchingcycles:115/230VAC/1Acosϕ=0,4corresp.115/230VAC/2.5Acosϕ=1For2.5millionswitchingcycles:115/230VAC/1Acosϕ=1
HT function or AUXoutMultifunction out-putconfigurable
11 - Relay contact Max.100m 115/230VAC/1Acosϕ=1
FaultAlarm
12 - Relay contact Max.100m 115/230VAC/1Acosϕ=1
FLWpower 7 - ForUV41(HE) Max.100m 230VAC/10mA*1
Technical data
*1:Theflamedetectorisalwayssuppliedwith230VAC,eventhe115VACversion,viathe"Flamedetectorsupply"connection7.
Thesumofthecurrentsofallsafety-relatedconsumersmustnotexceed5A(observethevalueofthefuse)Thesumofthecurrentsofallconsumersmustnotexceed6.3A(10A).
15 … 9014 … 90
Prin
ted
in G
erm
any
• Edi
tion
12.1
5 • N
r. 27
1 95
8
*1Safety-relevantintheflameoperation,notsafety-relevantintheHTmode(flamedetectionoff).
*2Forspecialapplications,ionisationcablelengthsofupto50marepossibleuponrequest.
*3TheRemoteunlockfunctionissafety-relevant.
InputsDesignation Connec-
tion XSafety-related
Type of output Line length Electrical data
L1 1 ContactN 3 ContactPE/Earth 4 ContactInput safety chain(fromL1,se-cured via fuse in fuse holder)
10 x Contact Max.100m 115/230VAC/max.5A
FlamedetectorIonisation*1
5 x Ionisation for one or two-probe operation
Max.10m*2 Thresholdvalue:approx.1.2μA
Temperature signal NO
16 x Switching contact Max.100m 115/230VAC"normallyopen"
Temperature sig-nalNCorProofof closure or gas pressure switch min.
17 x Switching contact Max.100m 115/230VAC"normallyclosed"
Heat request 19 Switching contact Max.100m 115/230VAC
Airpressureswitch
18 X Switching contact Max.100m 115/230VAC
Remote unlock-ing*3
20 Switching contact Max.100m 115/230VAC
15 … 9014 … 90
Prin
ted
in G
erm
any
• Edi
tion
12.1
5 • N
r. 27
1 95
8General informationDesignation Type of input Electrical dataL1 connection over exchangeable backup fuse
6.3Aslow-blowor10Afast-blow
Safety chain connection via exchangeable backup fuse in the fuse holder
5Aslow-blow
TWIinterface TWI ConnectiononlyforVisionBoxandparam-eter setting boxNOT galvanically isolated!
Switch for parameterisation mode Bistable switch SelectorswitchinsidetheMPA(mayonlybeswitchedafterhavingremovedMPAfromthe base)
"Display"unit Inside the housing for inte-grated display
3x7segment+4keys
Spark generator connection The MPA 4112 PF does not have abuilt-in ignition transformer. Forsuitableignitiontransformers,see accessory list.
Attention: A special spark generatoris required depending on the electrode arrangement (e.g. operation with oneelectrode)
Technical data
17 … 9016 … 90
Prin
ted
in G
erm
any
• Edi
tion
12.1
5 • N
r. 27
1 95
8
One-electrode operation ionisation
*WhenusingaDUNGSDEZ1xxSEOignitiontransformerforsingle-electrodeoperation,the green/yellow cable must be connected to terminal 5.
Two-electrode operation ionisation
Flame detector UV41 (HE)
Flame monitoring and ignitionFlame detector connection
Flame
MPA connection
15: Ignition
3:N
4:PE
5: ION
7:FLWpower
Flame
MPA connection
15: Ignition
3:N
4:PE
5: ION
7:FLWpower
Flame
UV41(HE)
MPA connection
15: Ignition
3:N
4:PE
5: ION*
7:FLWpower
17 … 9016 … 90
Prin
ted
in G
erm
any
• Edi
tion
12.1
5 • N
r. 27
1 95
8
MPA 4112 PF installation
MPA4112PFinstallationoptions:
- Direct screw connection of the base to the installation surface Breakoffinstallationholesusing,for
example, a suitable screwdriver or borethemusingadrill4.2mm(M4)or5.5mm(M5).
- Hatrailmounting(lockingthebase into place on a hat rail)
Mounting bores
Hat rail mounting
ScrewM4
Screw M5Attention: Use plastic screws only!
19 … 9018 … 90
Prin
ted
in G
erm
any
• Edi
tion
12.1
5 • N
r. 27
1 95
8
DimensionsMPA 4112 PF
151.
5
77 152.5
19 … 9018 … 90
Prin
ted
in G
erm
any
• Edi
tion
12.1
5 • N
r. 27
1 95
8
Description of the functions
Unlocking functionWhentheMPAislocked(state0),itcanbe unlocked by pressing the unlock key. In order to distinguish the function from possible EMC interfering impulses, the key must be kept depressed for at least 0.5s(max.5s).The same applies to the unlocking via 230Vandtotheunlockingviafieldbusmodules.
AccordingtoDINEN14459(annexJ),the number of possible unlocking pro-cesses is limited to 5 in 15 minutes, that means the automatic system denies furtherunlocking if theMPAhasbeenunlocked more than 5 times within a short time period. Only after a waiting timeduringwhichtheMPAisprovidedwith energy is it possible to unlock the MPAagain.
Thewaitingtimeis15minutesor3min-utes for each unlocking.
Extended unlockingThe described limitation to 5 unlocking operations in 15 minutes can be reset bymeansof "Extendedunlocking".Todo this, the unlock key must be pressed foratleast5s(max.10s)(after5sec-onds,thedisplaywillstartflashing).
The "Extended unlocking" is active inall operational states of theMPA, thatmeans that a safety shutdown with re-start of the MPA in operation can becarried out via the "Extended unlock-ing"alsointhepresenceofaflame.
The"Extendedunlocking"functionisnotpossibleviathe230Vunlockinginputorthefieldbusmodules!
Access levelWriteaccesstoMPAisdefinedondif-ferent access levels.Each parameter is assigned an access level. In order to modify a parameter, the MPA must be at the assigned orhigher level.If the access level is not sufficient tomodifyaparameter,theVisionBoxindi-cates it, or a message is output on the MPAdisplaypromptingtheusertoen-terthevalidpassword.Athigherlevels,theusersmustpressakey toconfirmthat they are "on site". The display isflashingfor30suntilakeyispressed;otherwise,theMPAremainsinthepre-vious level.
To change the access level, the cor-rect password must be entered via the displayorVisionBox→MPAsettings→Access level. The access level is au-tomatically reset after 5 hours or after power failure. Exception: If the auto-matic system performs a restart during these 5 hours, for example due to an error, these 5 hours for the current ac-cess level are counted again from the beginning.
NOTICEWe recommend resetting the accesslevel after having configured theauto-matic system.
Level Designa-tion
Key con-firmation required
1 Dungs yes2 OEM
Expertyes
3 OEM yes4 Service yes5 Operator no
21 … 9020 … 90
Prin
ted
in G
erm
any
• Edi
tion
12.1
5 • N
r. 27
1 95
8
Gas valve V1 X13ThegasvalveV1switchesdepend-ingonthestate,seelineV1intheflowchart.
V2 boost, energy interrupt X14TheoutputcanbeusedasV2boostfunction, as energy interrupt function or as"HTactive".ConfigurableviaparameterP80:Depending on the parameter value, anotherlineintheflowchartisvalid.
Flame detectorSeeAnnexFlamedetector.
Air pressure switch X18The input can be used for the connec-tionofanairpressureswitch.Configur-ableviaparametersP84andP16.
HT signal, gas pressure switch or POC X17Theinputcanbeconfiguredviaparam-eterP18.ThehightemperatureNCsignal can be connected to the input. Ifthisfunctionisused,theX16mustbe assigned to the respective inverse signal(NO).Asanoption,theinputcanbeusedfor the connection of a gas pressure switchorasPOCfunction.
Parameterisation mode (manual operation)Aswitchintheconnectionchamberis used for switching between param-eterisation and automatic mode.TheMPAregistersaswitchingopera-tion not before a restart.
Afterconnectingthemainssupply,amessages is prompted on the display in the parameterisation mode request-ing you to enter the code. Enter the password for service or OEM level.
Afterhavingchangedthelevel,these-lected parameters are activated one af-tertheother.Anoverviewoftheparam-eters and their order can be found in sectionParameterisationdisplay.Theparametervaluesmaybemodifiedbypressingthekeys+and-.Theunlockkey is used for saving the displayed value.Pressthe←keytoreturntotheprevious position or parameter.Asthedisplayhastwopositionsonly,some values are represented in an optimised resolution. If the set value cannot be displayed in this resolution, thedisplayshows"––".Thevaluemaybe changed in a resolution that can be displayed.
Once all parameters are set, all values mustbeconfirmedonceagain.Thiscompletessettingtheparameters(H5is displayed) and the parameter switch canberesetto"Auto"position.
Ifyoudonotpressanykeyfor30minutes in parameterisation mode, the program tries a restart.
Switch to "Auto"Withthisswitchposition,theMPAisworking in normal operation. If moni-tored parameters were changed and notreleased,theMPAswitchestofaultmodewith0x60error.
ParameterswitchLeft"Auto"positionRight"Para"position
21 … 9020 … 90
Prin
ted
in G
erm
any
• Edi
tion
12.1
5 • N
r. 27
1 95
8
Note
Parameter
Terminal x
Safety relevant
Error
Manual operation - Pause 1 (H5)
Main switch-on delay
Activate standard position
Internal state
Watchdog loading phase
Idle state control air pressure sw.
Waiting for heat request
External light monitoring
Waiting for air pressure
Pre-purge
Pre-ignition
First safety time of flame detection
Flame A stabilisation
Stabilisation
Operation
Post-purge
Extraneous light
Restart protection
Activate checking operation
Activate operation HT
Internal state
Activate operation HT
Activate checking start
HT idle state control
HT idle state control air press. sw.
HT waiting for heat request
HT external light check
HT waiting for air pressure
HT pre-purge
HT stabilisation
HT mode
HT post-purge
HT restart protection
Lack of gas pressure switch min.
Safety chain open
Stat
e N
umbe
r:0
12
34
56
78
910
1112
1314
1516
1718
1920
2122
2324
2526
2728
2930
3132
3334
35St
ate
Disp
lay
Info
:Fx
xM
enu
0000
0001
A4A0
A1A1
A1A1
A1A1
A2A3
A4A4
A4Ab
AbAb
Ab0b
0bb4
b0b1
b1b1
b2b3
b4b4
D2D1
Mod
e:*A
flam
e op
erat
ion
*B*B
*B*B
*B*B
Not
e:*1
4*6
*6*1
3*1
0*2
, *15
*2*2
*2*2
*12
*12
*13
*10
*15
P22
P15
Para
met
er:
P83
P88
P30
P31
P34
P51
P52
P87
P88
P87
P85
P89
P90
P91
P20
Max
imum
tim
e:0.
.30
m10
m30
0s3s
3s60
s24
h60
s60
s68
m10
m14
.5s
0.5s
10m
24h
68m
68m
68m
10s
300s
10s
300s
10s
300s
60s
24h
60s
60s
300s
300s
24h
68m
68m
0..
68m
Safe
ty C
hain
P15,
P20
10SR
Heat
Req
uest
P17
19
Flam
e 1
*11
P41
5*1
1*2
0*2
0*2
0*5
, *20
HT m
ode
*1P1
8, P
8616
& 1
7SR
*19
*19
*19
*2*2
*3*3
*3*3
*3*3
*3*3
*3*3
*3*3
*3*3
Proo
f-of-c
losu
re (o
n V1
)*1
6P1
817
SR
Gas p
ress
ure
*16
P18,
P22
17SR
*23
*23
*23
*23
*23
Air S
w In
*4, *
16P1
6, P
8418
SR
V1 O
ut13
SR
V2 B
oost
*8, *
18P8
014
SREn
ergy
inte
rrup
t*8
P8
014
SRHT
act
ive
*8, *
9P8
014
SR*1
7
Op0
: hea
t req
uest
wai
t*7
P19
11O
p5: p
re-p
urgi
ng*7
P19
11O
p3: f
lam
e on
*7P1
911
Op1
: fla
me
op st
able
*7P1
911
Op2
: HT
op st
able
*7P1
911
Op4
: ope
rate
(any
mod
e)*7
P19
11Ai
r Boo
st*7
P19
11Re
actio
n on
AB0
, Bit
3*7
P19
11*2
2*2
2*2
2*2
2*2
2*2
2*2
2*2
2*2
2*2
2*2
2*2
2*2
2*2
2*2
2*2
2*2
2*2
2*2
2*2
2*2
2*2
2*2
2*2
2*2
2*2
2*2
2*2
2*2
2*2
2*2
2*2
2*2
2*2
2*2
2*2
2
Igni
tion
Out
15SR
Air O
ut8
*21
*21
*21
*21
*21
Alar
m O
ut12
Inte
rnal
sign
als
Wat
chdo
gIo
nisa
tion
inpu
t act
ive
P32
HT o
pera
tion
initi
aliza
tion
P50
Capt
ion
see
page
22
Flow
Cha
rt
23 … 9022 … 90
Prin
ted
in G
erm
any
• Edi
tion
12.1
5 • N
r. 27
1 95
8
Lege
nd:
Off
Mus
t be
off b
y en
d of
stat
e
On
Mus
t be
on b
y en
d of
stat
e
Don'
t car
eW
ait u
ntil
inpu
t off,
Fai
l > t m
ax
Inex
isten
tW
ait u
ntil
inpu
t on,
Fai
l > t m
ax
Out
put d
epen
ds o
n fla
g in
bus
sign
al
*A)
Failu
re /
Lock
-out
mod
e*B
)Ju
mp
from
flam
e to
HT
mod
e
*1)
Ope
ratio
n m
ode
High
-tem
p. is
det
ecte
d by
bot
h te
rmin
als X
16 a
nd X
17 a
s an
EXO
R sig
nal a
nd m
ode
tran
sitio
n is
afte
r a to
lera
nce
time
of 1
s.
High
-tem
p m
ode
is se
lect
ed o
r disa
bled
by
para
met
er P
86.
*2)
If th
e sy
stem
cha
nges
to H
T m
ode
(>1
s) w
hile
ope
ratin
g in
flam
e m
ode,
the
sequ
ence
jum
ps to
the
4 st
ates
mar
ked
with
"Ab"
,th
en ju
mps
dire
ctly
to st
ate
"HT
stab
ilize
".*3
)If
the
syst
em c
hang
es to
flam
e m
ode
(>1
s) w
hile
ope
ratin
g in
Hig
h-te
mp
mod
e, th
e se
quen
ce ju
mps
to st
ate
"Sta
ndar
d po
sitio
n" a
nd th
e bu
rner
star
ts in
flam
e m
ode.
*4
)Pa
ram
eter
P84
(with
resp
ect t
o P1
9, P
80) d
eter
min
es th
e fu
nctio
n of
inpu
t ter
min
al X
18 a
nd P
16 d
eter
min
es th
e st
ates
for s
uper
visio
n of
the
air s
witc
h.
*5)
If fla
me
signa
l app
ears
dur
ing
stat
e "H
T op
erat
e", t
he se
quen
ce ju
mps
, if a
ir bo
ost o
r V2
boos
t is a
ctiv
e to
the
four
stat
es m
arke
d w
ith "A
b"
and
then
jum
ps d
irect
ly to
stat
e "H
T st
abili
ze".
Th
e nu
mbe
r of H
T re
cycl
e at
tem
pts p
er st
art/
stop
sequ
ence
for a
ir bo
ost,
or V
2 bo
ost d
ue to
flam
e ap
pear
ance
is li
mite
d by
par
amet
er P
81.
Afte
r the
last
pos
sible
recy
cle
atte
mpt
(P81
) the
bur
ner s
tays
in o
pera
tion
and
a w
arni
ng m
essa
ge v
ia b
us a
nd d
ispla
y is
gene
rate
d.Fl
ame
appe
aran
ce a
t typ
e en
ergy
inte
rrup
t will
gen
erat
e al
so a
war
ning
mes
sage
via
bus
and
disp
lay.
The
bur
ner s
tays
in o
pera
tion.
The
war
ning
mes
sage
and
disp
lay
info
rmat
ion
will
disa
ppea
r whi
le H
T st
artu
p se
quen
ce (e
nd o
f sta
te "b
1"),
and
afte
r a sw
itch
to fl
ame
oper
atio
n.A
tole
ranc
e tim
e of
P42
is a
ccep
ted.
If th
e fla
me
appe
ars a
nd d
isapp
ears
for a
per
iod
shor
ter t
han
the
time
spec
ified
in P
42 n
o ac
tion
will
follo
w*6
) -
*7)
The
actio
n of
the
outp
ut a
t ter
min
al X
11 is
sele
cted
by
para
met
er P
19.
*8)
The
actio
n of
the
outp
ut a
t ter
min
al X
14 is
sele
cted
by
para
met
er P
80.
*9)
-*1
0)Th
e fla
me
signa
l mus
t be
cons
tant
ly o
ff fo
r a m
inim
um ti
me
of 5
s be
fore
adv
anci
ng to
the
next
stat
e an
d if
not a
chie
ved
with
in 1
min
ute
durin
g st
ate,
then
Fai
l.
*11)
Th
e fla
me
(ioni
zatio
n) in
put i
s saf
ety
rele
vant
for f
lam
e op
erat
ion
mod
e, n
on sa
fety
rele
vant
in H
igh
tem
p op
erat
ion
mod
e.
*12)
The
stat
es m
arke
d w
ith "0
b" a
re n
eces
sary
aft
er a
syst
em re
star
t (i.e
. aft
er p
ower
on,
24-
hour
self-
chec
k, ..
.).
Afte
r the
initi
aliza
tion
stat
es a
nd w
ith th
e sy
stem
still
in H
T op
erat
ion
mod
e, th
e se
quen
ce ju
mps
to th
e 2
stat
es m
arke
d w
ith "0
b"W
hen
the
heat
requ
est c
omes
bac
k O
N a
fter
a n
orm
al sh
ut d
own,
the
sequ
ence
skip
s the
2 st
ates
mar
ked
with
"0b"
and
goe
s to
"HT
Chec
k im
prop
er fl
ame"
. *1
3)
If th
e tim
e sin
ce th
e la
st se
lf ch
eck
exce
eds t
he ti
me
in p
aram
eter
P82
, the
sequ
ence
will
jum
p to
do
all s
elf c
heck
s whe
n th
e "h
eat r
eque
st" i
s off.
Th
is ac
tion
rese
ts th
e au
tom
atic
24
hour
self
chec
k op
erat
ion
time
(see
not
e *1
5). F
or se
lf ch
ecks
, the
sequ
ence
jum
ps to
the
stat
e "S
tand
ard
posit
ion"
. *1
4)Th
e "P
ower
on
star
t del
ay" s
tate
is e
xecu
ted
for t
he d
urat
ion
spec
ified
in p
aram
eter
P83
onl
y af
ter p
ower
on.
W
hen
the
star
t seq
uenc
e is
initi
ated
from
a sa
fety
shut
dow
n, th
e du
ratio
n of
this
stat
e is
<0.5
s.
*15)
If th
e el
apse
d tim
e ex
ceed
s 24
hour
s sin
ce th
e la
st se
lf ch
eck,
the
sequ
ence
forc
es a
nor
mal
shut
dow
n, p
erfo
rms t
he se
lf ch
ecks
, and
then
star
ts a
gain
if th
e he
at re
ques
t is s
till a
ctiv
e.
*16)
Te
rmin
als X
17 a
nd X
18 in
put f
unct
ions
tole
rate
s fau
lty si
gnal
s of u
p to
1 s.
The
Pro
of-o
f-Clo
sure
sign
al is
tole
rate
d fo
r 1.5
s.
*17)
-
*18)
Te
rmin
al X
14 fo
r V2
boos
t can
be
inde
pend
ent o
f Air
boos
t on
term
inal
X11
.
*19)
If th
e Hi
gh-t
emp
mod
e is
ON
dur
ing
the
mar
ked
flam
e st
ate,
the
sequ
ence
jum
ps to
the
HT m
ode
stat
es m
arke
d w
ith "0
b"*2
0)If
P95
is se
t to
0 th
e fla
me
inpu
t is i
ngno
red
com
plet
ely
whi
le H
T op
erat
ion
(no
chec
k fo
r im
prop
er fl
ame
and
no c
heck
of f
lam
e ap
pear
ance
)*2
1)Th
e ai
r out
put d
epen
ds o
n a
flag
in th
e fie
ld b
us si
gnal
. If n
o fie
ld b
us is
ava
ilabl
e th
e ai
r out
put i
s off
in th
is st
ates
.*2
2)Te
rmin
al X
11 d
epen
ds o
n a
flag
in th
e fie
ld b
us si
gnal
(AB0
Bit
3). I
f no
field
bus
is a
vaila
ble
term
inal
X11
is o
ff.*2
3)N
o er
ror i
s sav
ed to
the
erro
r hist
ory
if ga
s pre
ssur
e ch
eck
fails
23 … 9022 … 90
Prin
ted
in G
erm
any
• Edi
tion
12.1
5 • N
r. 27
1 95
8
State descriptionMPA 4112 PFState xx Designation Description
00 Error(Fxx)
If the automatic system is in this state, there is an error. The display automatically shows an error message and indi-catesthecurrenterror(e.g."F11")insteadofthestatenum-ber.Theairvalve(X8)canbeswitchedonandoffbymeansofabus command.
01 Manual operation - Pause 1(H5)
Iftheswitchison"Para"fortheparameterisationmode,theMPAstopsinthisstate.Theusermustconfirmtheindicatedparameterbypressingthe"Next"key(unlockkey).Ifyoudonotpressanykeyduring30minutes, theautomaticsystemrestarts or indicates an error.If you reset the parameter switch before reaching the H5 dis-playandyouhavemodifiedparameters,theyarenotyetap-plied, and the automatic system indicates an error.
02 Mains switch-on delay(00)
Afterhavingswitchedthemainson,theMPAhastowaitfora defined time before going to the next state, see chapterP83:Durationoftheswitch-ondelayafterhavingswitchedthepower on.
03 Activate standard position(00)
Fromthisstateon,thegaspressureischeckedP18:Operat-ingmodeX17.Ifnopressureisactive,theMPAgoesintothelowgasstatewithoutdisplayinganerrormessage(i.e.noFMlock).
04 Internal state05 Watchdog loading phase
(01)Acheckiscarriedoutwhetherthesafetychainisstillopen.Ifthisisthecase,thestate35"Safetychainopen"isactivated.If the safety chain is OK, the safety-relevant watchdog circuit is activated.WhenopeningthesafetychainaftertheactivationoftheWDrelay until the restart protection HT, a safety shutdown takes place,therestartattemptdependsonP15:Lockingwithopensafety chain.
06 Idle state control air pressure switch (A4)
Depending on the operating mode of air pressure switch (P16), it ischeckedwhetherairpressureswitchreports"noairpressure".Themaximumstatetimeis60seconds.Iftheidlestateoftheair pressure switch is not reached within this period, a safety shutdown followed by a restart attempt takes place or the au-tomaticsystemdisplaysafaultiftheFMmodeisactive,seeP22:ConfigurationoftheFMmode.IftheHTmodeisallowed(P18andP86correctlyconfigured),the system reacts to a HT signal and goes into the HT mode viathestates"0b"(state23and24).
07 Waiting for heat request(A0)
The automatic system is ready for operation, but there is no heat request.Outofthisstate,theMPAcanstartavoluntaryself-test,seeP82:Self-test.Theairvalve(X8)canbeswitchedonandoffbymeansofabus command.Untilthisstateisreached,theMPAalwaysgoestothelowgasstate without displaying an error message in case of missing gas pressure.IftheHTmodeisallowed(P18andP86correctlyconfigured),the control reacts to a HT signal and goes into the HT mode viathestates"0b"(state23and24).
*In()ondisplay
25 … 9024 … 90
Prin
ted
in G
erm
any
• Edi
tion
12.1
5 • N
r. 27
1 95
8
State descriptionMPA 4112 PFState xx Designation Description
08 External light monitoring(A1)
Theflamemaynotbedetectedwithinthestatetimeofmax.1min. Otherwise, the automatic system tries to restart.Asofthisstate,theairvalveisactiveandcannotbedeacti-vated via the bus.
09 Waiting for air pressure(A1)
IftheMPAisconfiguredfortheconnectionofanairpressureswitch via X18, see operatingmode X18, the air pressuremustbeactivewithinastatetimeofmax.60s.Otherwiseasafety shutdown followed by a restart attempt depending on P22takesplace(seeP22:ConfigurationoftheFMmode).Anexternallightcontrolcanbemadefortheentiredurationof this state.
10 Pre-purge(A1)
This state provides sufficient pre-venting. For the durationdefined inparameterpre-venting,seeP30:Durationofpre-venting.Anexternal lightcheckcanbemade for theentireduration of this state.Uptothisstate,ajumpismadetotherestartprotectionflamein case of a missing heat request.IftheHTmodeisallowed(P18andP86correctlyconfigured),the system reacts to a HT signal and goes into the HT mode viathestates"0b"(state23and24).
11 Pre-ignition(A1)
Theignitionisactivated(terminal15)forthedurationspeci-fiedinparameterP31withoutopeningvalveV1.Iffromthisstateontheheatrequestceasestoexist,theflamepost-venting is activated.
12 First safety time of flame detection (A1)
Thegas valveV1 is opened in this state.Gas flowsandaflamecanbegenerated.ThedurationofthisstateisP32-0.5s.
13 Flame A stabilisation(A1)
Afterdeactivatingtheignition,theprocessforflamedetectionisstarted.Ifanionisationcurrentisdetected,theMPAreportsaflame.Thedurationofthisstateis0.5s.
14 Stabilisation(A2)
Theflamecanstabiliseinthisstate.Thedurationofthisstabi-lizationphaseisconfiguredviaP34,(stabilisationtime).IftheHTmodeisallowed(P18andP86correctlyconfigured),the system reacts to a HT signal and goes into the HT mode viathestates"Ab"(states19to22).
15 Operation(A3)
The automatic system is now operating. After24hoursinthisstate,aforcedregularshutdownisauto-matically carried out because theMPAworksintheintermittentoperation.IftheHTmodeisallowed(P18andP86correctlyconfigured),the automatic burner control reacts to a HT signal and goes intotheHTmodeviathestates"Ab"(states19to22).Iftheheatrequestceasestoexist,theMPAgoesintothepost-vent-ing state.
16 Post-purge(A4)
In this state, the post-venting of the combustion chamber is carriedout, seeP51:Post-venting time.Thegasvalves re-main closed from this state on. The air valve remains open in thisstate;itisswitchedoffinthenextone.
17 Extraneous light time(A4)
Duringthistime(P50-P51if>0),aflamesignalmaybepre-sent from the previous mode caused by e.g. existing residual gas in the combustion chamber. The external light monitoring is only started in the following state.The after-burn time starts in the post-venting state if the post-venting is equal to or greater than the after-burn time; then the after-burn time state is skipped.
25 … 9024 … 90
Prin
ted
in G
erm
any
• Edi
tion
12.1
5 • N
r. 27
1 95
8
State descriptionMPA 4112 PFState xx Designation Description
18 Restart protection(A4)
Inthisstate,thesystemwaitsuntilparameterP52isfinished;this prevents an immediate restart of the automatic system if a heatrequestisactive.Theflamemaynolongerbedetectedinthisstate;otherwise,MPAreportsanexternallighterror.
19 Activate checking operation(Ab)
If theHT signal is deactivated from this state on, theMPAgoes into the post-venting HT since the gas valves are open.Thestates19,20,21and22arecarriedoutoneaftertheoth-er.Afterwardsthestate30StabilisationHTbecomesactive.
20 Activate operation HT(Ab)
ThestatetimeisconfiguredwithP87.If theV2boost function isactive,seeP80:OperatingmodeX14,theX14outputisactivatedforthisstateduration.
21 Internal state22 Activate operation HT (Ab) Afterthisstate,achangeovertothethestabilisationoftheHT
mode takes place.23 Activate checking start
(Ob)Ajumptothisstatetakesplaceafterapoweruporarestartoriftheburnerisnotyetintheflameoperationwhenasignalis sent by HT.If theHT signal is deactivated from this state on, theMPAgoesintostate3(activatestandardposition).
24 Activate start HT(Ob)
AftertheendofthetimeinparameterP87,thestateIdlestatecontrol air pressure switch for HT mode is activated.
25 HT idle state controlair pressure switch(b4)
Depends on the operating mode of the air pressure switch, seeP16:Operatingmodeairpressureswitch,theairpres-sureindifferentstatesismonitored.Thisparametersettingdefineswhetheranidlestatecontroliscarriedoutinthisstate.Themaximumstatetimeis60s.Iftheidlestateoftheair pressure switch is not reached within this period, a safety shutdown followed by a restart attempt takes place or the automaticsystemdisplaysafaultiftheFMmodeisactive,seeP22:ConfigurationoftheFMmode.
26 HT waiting for heat request(b0)
The automatic system is in the HT mode ready for operation, but there is no heat request.Outofthisstate,theMPAcanstartavoluntaryself-test,seeP82:Self-test.Theairvalve(X8)canbeswitchedonandoffbymeansofabus command.
27 HT external light check(b1)
IfactivatedfortheHTmode,aflamemustnotbedetectedwithinthestatetimeofmax.60s,seeP95:HT:Externallightmonitoring.Ifaflameisdetectedafterthistimeperiod,asafetyshut-down followed by a fault lock takes place.Asofthisstate,theairvalveisactiveandcannotbedeacti-vated via the bus.
28 HT waiting for air pressure(b1)
IftheMPAisconfiguredfortheconnectionofanairpressureswitchviaX18,seeP84operatingmodeX18,theairpres-suremustbeactivewithinastatetimeofmax.60s.Other-wise a safety shutdown followed by a restart attempt de-pendingonP22takesplace:ConfigurationoftheFMmode.During the entire duration of this state, an external light checkiscarriedoutifactivatedfortheHTmode,seeP95:HT: External light monitoring.
29 HT pre-purge(b1)
Thisstateprovidessufficientpre-venting.Forthedurationdefinedinparameterpre-venting,seeP85:Pre-ventingtimeHT. During the entire duration of this state, an external light checkiscarriedoutifactivated,seeP95:Up to this state, a jump is made to the restart protection flameincaseofamissingheatrequest.
27 … 9026 … 90
Prin
ted
in G
erm
any
• Edi
tion
12.1
5 • N
r. 27
1 95
8
State descriptionMPA 4112 PFState xx Designation Description
30 HT stabilisation(b2)
The HT mode can stabilise in this state. The duration of this stabilizationphaseisconfiguredviaP89.If from this state on the heat request ceases to exist again, the HT post-venting is activated.IftheHTsignalisdeactivatedfromthisstateon,theMPAgoes into the post-venting HT.
31 HT mode(b3)
The automatic system is now in the HT mode. After24hoursinthisstate,aforcedregularshutdownisautomatically carried out because theMPAworksintheintermittentoperation.During the entire duration of this state, an external light checkiscarriedoutifactivated,seeP95:HT:Externallightmonitoring.Ifaflamehasbeendetected,attemptsarestarted to blow it out according to the burner type, see chap-terP81:anti-oscillationcounterforflamedetectionduringHT.Iftheheatrequestceasestoexist,theMPAgoesintothepost-venting HT state.
32 HT post-purge(b4)
In this state, the post-venting of the combustion chamber iscarriedout,seechapterP90:HTpost-ventingtime.Thegas valves remain closed from this state on. The air valve remainsopeninthisstate;itisswitchedoffinthenextone.
33 HT restart protection(b4)
Inthisstate,theautomaticsystemwaitsuntilparameterP91isfinished;thispreventsanimmediaterestartoftheauto-matic system if a heat request is active again.
34 Lack of gas gas pressure switch min(d2)
Iftheautomaticsystemisconfiguredfortheuseofagaspressureswitch(seeP18:operatingmodeX17),achangeo-ver to this state is carried out from all states as soon as a low gasflowisdetected.Itleavesitinstate3aftersufficientgaspressurehasbeenbuiltup.Afterhavingwaitedforaheatrequest,theMPAgeneratesanerrormessageduringthejump from all states.
35 Safety chain open(d1)
The automatic system remains in this state during the time setinparameterP20ifthesystemdoesnotdetectaclosedsafetychain.Afterthetimehaslapsed,itdecidesbasedonP15whetheritlocksimmediatelyortriestorestart.IfthesafetychainisclosedbeforethetimeofP20haslapsed,theMPAchangestostate3tocheckthesafetychainagain in state 5.
27 … 9026 … 90
Prin
ted
in G
erm
any
• Edi
tion
12.1
5 • N
r. 27
1 95
8
ParameterParameter changeParametertypes1-bitparameter(U1)-setting0and1(displayedasON/OFF),nolimits8-bitparameter(U8)-valuesettingwithin variable limits16-bitparameter(U16)-valuesettingwithin variable limits.
AparametermaybemodifiedonthedisplayofMPAorviatheVisionBoxsoftwareonaPC.
In order to change a parameter, you need to set the access level assigned to the parameter.
The value must be within the variable limits; a value outside these limits is not possible. Depending on the access level, it is possible to change the variable upper and lower limits. The variable limits may only be changed by means of VisionBox,notontheMPAdisplay.Thevariable limits are restricted by means offixedlimits.Thesefixedlimitscannotbe changed.
To change parameters that cannot be changed during normal operation, it is necessarytochangetostate"Waitingforheatrequest".Most of the parameters are monitored inautomaticmode(switchontheboardon"Auto").TheMPAdetectschanges of the values and immediately changestofaultlock(error0x60).Anyvalue changes must be released in the parameterisation mode of a manual programrun(seealsoparametertable).
29 … 9028 … 90
Prin
ted
in G
erm
any
• Edi
tion
12.1
5 • N
r. 27
1 95
8
ParameterParameter description
Parameter Designation Description Setting / Examples
P11 Field bus address configuration
SettingthebusslaveaddressofMPAIf an invalid address for the connect-edbusmoduleissetandtheMPAisin automaticmode, it restarts (error0x18).
If an invalid value for the connected busmoduleissetandtheMPAisinparameter mode, an error message is generated.
During operation and error messag-es, the current bus address may be seenbypressingthe←key.
Valuerange:OFF(nofieldbusavailable)1to254(e.g.Profibusadjustmentrangefrom1to126)
Note:Amodifiedvalueforthisparam-eter is not applied before a restart.
P12 Number of restart at-tempts or anti-oscilla-tion counter
Number of restart attempts of the MPA.Afterafailedlaststart,theMPAlocksinfaultswitch-off(state0"error").The anti-oscillation counter is reset when returning to operating state or whenunlockingtheMPA.
Valuerange:0-5attempts
P13 Number of restart attempts when flame is missing after the start-gas flame prov-ing period
The number of restart attempts after creating a flame (P12) can be lim-itedforthecasethattheflameisstillmissingafter thefirstsafety time forstart-up.The restart counter and the anti-oscillation counter are reset when changing to the operating state or af-ter unlocking.
Valuerange:0-5attempts
Example:P12=5,P13=1Flame is still missing after the firstrestart→1.Restart attempt→Erroridle state control LDW→ 2. Restartattempt → Error idle state controlLDW → 3. Restart attempt → LDWOK after the third attempt, there is stillnoflame→Automaticsystemislocked although the number of re-startattempts(P12)hasnotyetbeenreached but the number of restart at-temptsaftermissingflamehasbeenreached.
P14 Number of restart at-tempts after a flame-out or missing flame after the second safety time for start-up
Thenumberofrestartattempts(P12)can be limited for the case that there isaflame lift-offor that theflame isstill missing after the safety time for start-up.The restart counter and the anti-oscillation counter are reset when changing to the operating state or af-ter unlocking.
Valuerange:0-5attempts
Example:P12=5,P14=1Missing flame during operation →1.Restartattempt→Error idlestatecontrolLDW→2.Restartattempt→ErroridlestatecontrolLDW→3.Re-startattempt→AfterthethirdattemptLDWOK,thereisstillnoflame→Au-tomatic system is locked.
P15 Locking with open safety chain
If the safety chain is not closed, the MPAwaits in state 35 (safety chainopen). If the adjustable time (P20) haslapsed and the safety chain is still open, the system changes to fault lockdue toanerroror restarts (de-pending on the anti-oscillation coun-ter).
This setting is also valid if the safety chainisopenedafterstate4.
Setting:0:Restartattemptdependingontheanti-oscillation counter1: Immediate fault lock
29 … 9028 … 90
Prin
ted
in G
erm
any
• Edi
tion
12.1
5 • N
r. 27
1 95
8
ParameterParameter description
Parameter Designation Description Setting / Examples
P16 Air pressure switch: Operating mode
The air pressure monitoring can be madeineightdifferentstateranges.• Idlestatecontrolflamemode (state6)
• Flameoperation(states14and15).• Startflameoperation(states9to11).• Post-ventingflame(state16)• IdlestatecontrolHTmode(state25)• HTmode(states30and31)• StartHTmode(states28and29)• Post-ventingHT(state32)Several ranges can be activated at thesame time.For this, the respec-tive values must added in the column "Value"andthetotalmustbeenteredinP16.
e.g. monitoring desired for • Idle state control Flamemode=1• Idle state control HTmode=16• HToperation=32ValueforP16=1+16+32=49
Setting0to255
Value Function1 Monitoringoftheidlestatecontrolintheflamemode2 Monitoringintheflamemode4 Monitoringduringthestartphaseofflamemode8 Monitoringduringthepost-ventingofflamemode16 Monitoring of the idle state control in the HT mode32 Monitoring in the HT mode64 Monitoring in the start phase of HT mode
128 Monitoring during the post-venting of HT mode
31 … 9030 … 90
Prin
ted
in G
erm
any
• Edi
tion
12.1
5 • N
r. 27
1 95
8
ParameterParameter description
Parameter Designation Description Setting / Examples
P17 Temperature controller operating mode
This parameter can be used to con-figurethebehaviouroftheMPAandthe way it accepts the heat request viabusorviatheHWinputHeatre-quest/temperaturecontroller(X19).
Setting0:Only the hardware input Heat request is active, the bus signal Heat request is ignored.Note:Withthissetting,theairpurge(bussignal)cannothavepriorityoverheatrequest(P241Bit0=1),thiswillleadtoerrorconfiguration,seeerrorsfromthebasicsystemforerror0x18Setting 1: The bus signal Heat request is active, the burner can only be started if the HW signal is also active. If the busconnectionisinterrupted,theMPAisswitchedoff inaregularwayafteratolerancetimeof10s.Setting 2: The bus signal Heat request is active. If the bus connection is interrupted, the control system is switched to the HW signal after a tolerance time of10s.Setting3:The bus signal Heat request is rel-evant. If the bus connection is inter-rupted, theMPA isswitchedoff inaregular way after a tolerance time of 10s.Setting4:The bus signal Heat request is rel-evant. If the bus connection is inter-rupted, the MPA performs a safetyshutdown with fault lock after a toler-ancetimeof10s.ATTENTION: In contrast to Profibus, Modbus isnot equipped with a cyclic commu-nication. The MPA, however, waitsfor one Modbus request per minute, therefore an interrupted communica-tion cannot be detected immediately. If the request is missing, the bus module reports the automatic system thatthereisabusinterruptionandF9flashesonthedisplay.OnlyafterthistheparameterP17becomesactive.
31 … 9030 … 90
Prin
ted
in G
erm
any
• Edi
tion
12.1
5 • N
r. 27
1 95
8
ParameterParameter description
Parameter Designation Description Setting / Examples
P18 Operating mode X17 This parameter defineswhetherHTmode is used, a gas pressure switch is connected or a Proof of closurecontact(POC).
Setting0: Inputhasno function, theHT mode is deactivated.Setting 1:HT NC mode, therefore the signal onX16mustbeinverse.Thissettingenables the HT mode.Setting 2: The input is used for the connection of the gas pressure switch, the HT mode is deactivated.Setting3:TheinputisusedforthePOCsignalforvalveV1,theHTmodeisdeacti-vated.
P19 Configuration of the output mode
The output may be switched on in differentstatesbymeansof the fol-lowing parameter settings. On means 115VACor 230VAC, for all others,Off,i.e.0V.
Setting0:"Waiting for heat request": Outputison instate7 (Waiting forheat re-quest)andinstate26(HTwaitingforheat request).Setting 1:"Flame stable" output is on in state15(operation).Setting 2:"HT stable" output is on in state 31(HTmode).Setting3:"Flameon":Output is on fromstate14 (stabilisation) tostate15 (opera-tion).Setting4:"Operation": Output is on in state15 (operation) and in state 31 (HTmode).Setting 5:"Pre-venting":Outputisoninstate10(pre-venting)andinstate29(HTpre-venting).Setting6-9:reservedSetting10:"Airboost":Output ison instate20(ActivateoperationHT).Setting 11:Depending on the bus: The output depends on the bus, that means if bit 3issettoAB0,theoutputisswitchedon, independently of the state of the MPA,evenifitreportsafault.
33 … 9032 … 90
Prin
ted
in G
erm
any
• Edi
tion
12.1
5 • N
r. 27
1 95
8
ParameterParameter description
Parameter Designation Description Setting / Examples
P20 Duration safetychain open
Thisparametercanbeusedtodefinethedurationofstate25(safetychainopen). Time until the automatic sys-tem restarts or changes to lockout, depending on the anti-oscillation counterandP15 (lockingwithopensafety chain).
Valuerange:0to65534(resolutionin1/16s).65535:Infinitestateduration
P22 FM mode Immediatefaultswitch-offincaseof:Lack of gas, error limit switch main gas,Error of idle state control air pressure switch and error no air pressure
Setting0:not activeSetting 1:active
P30 Duration of pre-vent-ing
Thisparametercanbeusedtodefinethedurationofstate10(pre-venting).
Valuerange:0to65534(resolutionin1/16s).
P31 Duration of pre-igni-tion time
Thisparameterdefines thedurationofstate11(pre-ignition).During thistime, the ignition is already active, the gas valve is closed.
Valuerange:2to65534(resolutionin1/16s).
P32 Safety time for start-up / first safety time
Defines the duration of the safetytime for start-up. Maximum time from opening the gas valvestodetectingaflame.
NOTE: This duration is divided into states12and13.State13isalways0.5seconds.
Valuerange:16to240(resolutionin1/16s).Attention:WithFMapplications,thefollowing times must not be exceed-ed.Burners with direct ignition:<2,500,000Btu/h≤15s(setvaluemax.240)>2,500,000Btu/h≤10s(setvaluemax.160)
P34 Stabilisation time A Durationofstate14"FlameAstabi-lisation"
Valuerange:0to65534(resolutionin1/16s).
P41 Operation safety time DefinesthedurationofthesafetytimeforMPAduringoperationforflame1.Timeuntilgasvalvesclosewhenthereisnotanyflame.
Valuerange:12to56(resolutionin1/16s).
ATTENTION: The entire reaction time after there is not any flameduringoperation iscombinedofP41andpossiblereac-tiontimesofexternalflamedetectors,seeAnnexFlamedetector.
P42 HT tolerance time flame signal
IfaflameisdetectedintheHTmodefor a longer period than the tolerance time,theMPAgoestostate19andtriesto"blowout"theflame.Operating modes in which the flameisblownout(intheremainingoperatingmodes,theMPAdoesnotchange its state):-AirboostonX11,seeP19-V2boostonX14,seeP80If it is not successful, the process is repeated,seeP81:anti-oscillationcounterforflamedetectionduringHT.TheflamedetectionduringHTcanbedeactivated,seeP95:HT:External light monitoring.
Setting12to80(resolutionin1/16s)NOTE: The parameter value is the minimum reaction time. Depending on the marginal conditions, the ac-tual reaction time can be extended.
33 … 9032 … 90
Prin
ted
in G
erm
any
• Edi
tion
12.1
5 • N
r. 27
1 95
8
ParameterParameter description
Parameter Designation Description Setting / Examples
P50 Extraneous light Definesthedurationoftheafter-burntime(state17),thetimemeteringstarts already during the post-vent-ing(state16).That means that if the after-burn time is shorter/equal to the post-venting time, the state after-burn time is skipped.
Valuerange:16to65534(resolutionin1/16s).
P51 Post-venting time Definesthedurationofthepost-ventingtime(state16).
Valuerange:0to65534(resolutionin1/16s).
P52 Restart protection Definesthedurationoftherestartprotection(state18).
Valuerange:0to65534(resolutionin1/16s).
P80 Operating mode X14 ThisparameterdefinesthefunctionoftheoutputX14and,therefore,theburner type.
Setting0:reservedSetting 1: High temperature activeSetting 2: V2boostSetting3:Energy interrupt
P81 Anti-oscillation coun-ter with flame detec-tion during HT (8-bit parameter)
IftheflamedetectionisactiveduringHT(P95:HT:externallightmonitor-ing), the attempt is made consider-ingthetolerancetimeoftheflamedetection(HT:tolerancetimeflamesignal)to"blowout"theflame.ThenumberofattemptsisconfiguredviaparameterP81.If the number of attempts is reached, theMPAremainsintheHTmode,awarning is transmitted to the display (seeErrorfromprocessor2)andviafieldbus(seeInputdataofthemasterfromtheMPA).The error message is reset at the end of the state of the HT pre-venting, that means after the regular shutdown and a subsequent restart in the HT mode.Moreover, it is also reset after having changedtotheflamemodeinthewatchdog loading phase state.The attempts for energy interrupt are notcarriedout,theMPAremainsinoperation and the warning is im-mediately emitted. The parameter hasnoeffectfortheseburnertypes(P80:operatingmodeX14).
Setting0to5
35 … 9034 … 90
Prin
ted
in G
erm
any
• Edi
tion
12.1
5 • N
r. 27
1 95
8
ParameterParameter description
Parameter Designation Description Setting / Examples
P82 Self-test SincetheMPA41xxPFisanintermit-tent automatic system, a self-test mustbecarriedoutevery24h(jumptostate3andinternalself-test).ThisparametercandefineatimeatwhichtheMPAistoperformapremature, voluntary self-test if it isintheWaitforheatrequeststate(flameorHT)inordertoavoidalaterinterruption of the heat request.IftheMPAremainsinoperationforalongerperiodthandefinedinthepa-rameter, a forced shutdown followed by a self-test is carried out.
Setting1to1439(resolutionin1/16s).
P83 Duration of the switch-on delay after power On (16-bit parameter)
Afterhavingswitchedonthemains,the automatic system waits for a time perioddefinedinP83,thatmeansthat the switch-on is delayed. In case of a safety shutdown followed by a restart or an unlocking after a fault, there is no waiting time and the parameterhasnoeffect.
Setting0to9600(resolutionin1/16s).
P84 Operating mode X18 DefinesthefunctiontypeoftheinputX18
Setting0:Inputfortheconnectionofan air pressure switch, the param-eterP16(P16operatingmodeAirpressureswitch)thatdefinesthemonitoring areas must be observed.Setting 1: reservedSetting 2: reservedSetting3:Theinputisignored/nofunction
P85 Pre-venting time HT Thisparameterdefinesthedurationofstate29(HTpre-venting).
Setting0to4800(resolutionin1/16s).
P86 Operating mode HT allowed
This parameter can be used to pro-hibit the HT mode.
Setting0:HTmodenotallowed.Thestates of the HT mode cannot be reached even if the signal HT is ac-tiveonX16andX17.Setting 1: HT mode allowed.
P87 Jump duration from flame or power On to HT
Definesthedurationforstate20.That means that the length of the boostfunction(ifused)isdefinedviaoutputX14orX11.
Setting16to4800(resolutionin1/16s).
P89 HT: Stabilisation time DefinesthedurationofthestateHTstabilisationtime(state30,HTstabilisation).
Setting8to4800(resolutionin1/16s).
P90 HT: Post-venting time Definesthedurationofthepost-ventingtime(state32,HTpost-venting).
Setting0to65534(resolutionin1/16s.
P91 HT: Duration restart protection
Definesthedurationoftherestartprotection(state33,HTrestartprotection).
Setting8to65534(resolutionin1/16s).
35 … 9034 … 90
Prin
ted
in G
erm
any
• Edi
tion
12.1
5 • N
r. 27
1 95
8
ParameterParameter description
Parameter Designation Description Setting / Examples
P92 Maintenance interval WD
Acountercountsthereactionsofthewatchdogrelayinstate5(watch-dog loading phase). If the counter reachesthevaluedefinedinparam-eterP92*1000,amessageisoutputviafieldbus(seechapterInputdataofthemasterfromtheMPA)andviathedisplay(seechapterErrorswithouterrorID).TheMPA,however,continuesworking.Aftermaintenance work, the message can be reset via the display, see reset display.
Setting1to65534(resolution1000).
P93 Maintenance interval V1
AcountercountsthenumberofreactionsoftherelayV1.IfthecounterreachesthevaluedefinedinparameterP93*1000,amessageisoutputviafieldbus(seechapterInput data of the master from the MPA)andviathedisplay(seechap-terErrorswithouterrorID).TheMPA,however,continuesworking.Aftermaintenance work, the message can be reset via the display, see reset display.
Setting1to65534(resolution1000).
P94 Maintenance interval air output
Acountercountsthenumberofreactions of the relay for the air out-put. If the counter reaches the value definedinparameterP94*1000,amessageisoutputviafieldbus(seechapter Input data of the master fromtheMPA)andviathedisplay(seechapterErrorswithouterrorID).TheMPA,however,continuesworking.Aftermaintenancework,the message can be reset via the display, see reset display.
Setting1to65534(resolution1000).
P95 External light monitor-ing
This parameter can be used to deac-tivate the external light monitoring in the HT mode, that means that no "blowoutattempts"arestartedbe-causenoflameisdetected.Thepa-rametersP81anti-oscillationcounterforflamedetectionduringHTandP42,HT:Toleranceperiodflamesignaldoesnothaveanyeffect.
Setting0to1
P240 Extension module If an extension module is installed, thisparametermustbesetto>0,otherwisetheMPAwillperformsafety shutdown with restart attempt witherror0x18.
Setting0: Module not requiredSetting>=1:Moduleinstalled
37 … 9036 … 90
Prin
ted
in G
erm
any
• Edi
tion
12.1
5 • N
r. 27
1 95
8
ParameterParameter description
Parameter Designation Description Setting / Examples
P241 Bit functions priority switchingCooling/heating
Bit0:OFF=heatrequestoverwritesventilationrequest,theMPAstartsoperation despite the ventilation requestON=ventilationrequestoverwritesheat requestIfventilationrequestisset(onlyviabuspossible)inoperation,theMPAshuts down in a regular way and waits for heat request with ventilationNote: If the bit is set, the setting oftheheatrequestviaHWinput(P17=0)is not possible. This will lead to error configuration,seechapterErrorsfromthebasicsystemforerror0x18.Bits1-15=nofunction
P242-P249 Reserved parameters*P260 ff Internal parameters Pleasedonotchange!
*P244valuemustbe"0"
37 … 9036 … 90
Prin
ted
in G
erm
any
• Edi
tion
12.1
5 • N
r. 27
1 95
8
ParameterFactory settingsPara-meter
Designation Factory setting
Unit Accesslevel
Comfortparameter setting
Min. value Max. value
P11 Field bus ad-dress configura-tion
255=OFF OPERATOR x 0 255
P12 Number of re-start attempts or anti-oscillation counter
0 OEM x 0 5
P13 Number of restart attempts when flame is missing after the start-gas flame proving period
0 OEM x 0 5
P14 Number of restart attempts after a flameout.
0 OEM x 0 5
P15 Locking with open safety chain
ON OEM x
P16 Air pressure switch operating mode
255 OEM x 0 255
P17 Temperature controller oper-ating mode
2 OPERATOR x 0 4
P18 Operating mode X17(NC, POC, gas pressure)
1 OEM x 0 3
P19 Configuration of the output oper-ating mode
4 SERVICE x 0 255
P20 Duration of safety chain open
65635 1/16s OEM 0 65535
P22 FM mode OFF OEMP30 Duration of pre-
venting0 1/16s OEM x 0 65534
P31 Duration of pre-ignition time
0 1/16s OEM x 0 9600
P32 Safety time for start-up
16 1/16s OEM x 16 240
P34 Stabilisation time A
16 1/16s SERVICE x 0 9600
P41 Operation safety time
12 1/16s OEM x 12 56
P42 HTTolerance timeFlame signal
16 1/16s OEM 12 80
P50 After-burn time 80 1/16s OEM 16 65534P51 Post-venting
time0 1/16s SERVICE x 0 65534
P52 Restart protec-tion
8 1/16s SERVICE x 8 65534
39 … 9038 … 90
Prin
ted
in G
erm
any
• Edi
tion
12.1
5 • N
r. 27
1 95
8
ParameterFactory settingsPara-meter
Designation Factory setting
Unit Accesslevel
Comfortparameter setting
Min. value Max. value
P80 Operating mode output X14
2 SERVICE 0 3
P81 Anti-oscillation counter for flame detection during HT mode
0 SERVICE 0 5
P82 Self-test 1380 min. SERVICE 1 1439P83 Duration of
switch-on delay voltage on
0 1/16s SERVICE x 0 9600
P84 Operating mode output x18
0 OEM 0 3
P85 Pre-venting time HT mode
0 1/16s SERVICE x 0 4800
P86 Operating mode HT On/Off
ON OEM
P87 Duration of volt-age on or flame operation on HT mode
16 1/16s SERVICE x 16 4800
P89 HT mode stabili-sation time
16 1/16s SERVICE 8 4800
P90 HT mode post-venting time
0 1/16s SERVICE 0 65534
P91 HT duration re-start protection
8 1/16s SERVICE 8 65534
P92 Maintenance in-terval watchdog (WD)
250 1000 SERVICE 1 65534
P93 Maintenance interval V1
1000 1000 SERVICE 1 65534
P94 Maintenance interval output air
1000 1000 SERVICE 1 65534
P95 HT mode exter-nal light moni-toring
OFF OEM
P240 Extension mod-ule yes/no
0 OEM 0 65535
P241 Extension mod-ule bit functions
0 OEM 0 65535
39 … 9038 … 90
Prin
ted
in G
erm
any
• Edi
tion
12.1
5 • N
r. 27
1 95
8
Status informationMPA 41xx PFDesignation Description displayed
viaVisionBox
displayed viadisplay
General informationFaultswitch-off Automaticsystemislocked ● LED
State number Current state of the automatic system, key combination +and -
● 7-segment
Current access level ●Flame Flamedetected ● LEDManual mode Automaticsysteminmanualmode ● 7-segmentFlamequality Value>49goodflame(forionisation) ● InfoHardware input for temperature controller Signal for temperature controller input ●
Bus connection present Connection OK ● 7-segment
Heat request Signal combination from bus setpoint input and hardware input
● LED
Fieldbuspresentdebounced 10sdebouncedsignal ●Temperature controller (HW+parameter/bus)
Signal combination from bus setpoint input and hardware input
● LED
WarningflameinHT X18 ● FxInputsAirpressureswitch SignalfrominputX18 ●Flame1 Signalfromflame1input ●Signal HT-NO SignalfrominputX16 ●Signal HT-NC / Gas pressure switch/POC SignalfrominputX17 ●
OutputsValve1 OutputX13 ●OutputX14 OutputX14/V2boost(energyint./HTactive) ●Ignition OutputX15 ●Fan OutputX8(airvalve) ●OutputX11 OutputX11 ●CounterUseful life counter Time since switching on the automatic system ●Runtime meter Operatingtimeflameoperation,notresettable ● InfoRuntime meter Resettable FlameandHTresettableviaVisionBoxanddisplay ● Info
Resettable start counter Startcounterflamemode,resettableviaVBanddispl. ● InfoStart counter Startcounterflamemode,notresettable ●Runtime meter HT Operating time HT mode, not resettable ●Start counter HT Start counter HT, not resettable ●SwitchingcyclescounterWD Switching cycles watchdog relay, resettable via display ●SwitchingcyclescounterV1 SwitchingcyclesV1relay,resettableviadisplay ●Switching cycles air valve Switching cycles air valve, resettable via display ●Internal informationState timer in minutes Displayedstatetimerrunsinminutes,otherwisein1/16sec. ●Initialisation phase The automatic system is being initialised ●Multi-function switch Is"ON"whenunlockkeyispressed ●Accesslevelchange CCCorvalueflashesondisplay,↵keyexpected ● 7-segmentSafetyswitch-offflag Automaticsystemislocked ●Error index Internal error counter ●Remaining state time is65535ifunlimitedremainingtime ●
41 … 9040 … 90
Prin
ted
in G
erm
any
• Edi
tion
12.1
5 • N
r. 27
1 95
8
LED:Indicatedbyoneofthe3LEDsonthedisplay7-segment: Indicated by one or several characters of the 7-segment displayInfo: Displayed in informative display mode
Status informationMPA 41xx PFDesignation Description displayed
viaVisionBox
displayed viadisplay
Cycl. state counter Counts in 1/128 s cycle ●Processorload ●Nominal modulation degree No function ●Actualmodulationdegree No function ●
41 … 9040 … 90
Prin
ted
in G
erm
any
• Edi
tion
12.1
5 • N
r. 27
1 95
8
DisplayThecustomermaycustomizetheMPA4112PFontheintegrateddisplaytomatch the desired burner.Allimportantparametersmaybesetbymeans of the four operating keys.
The parameters of the device are eithersetbymeansofVisionBoxorby means of the parameterisation and service box.
3x7segmentdisplay
LED: Blue: Heat requestYellow:Flamequality(flashesiftheflamequalityispoor)Red:Fault
Release buttonRESETfunctionandconfirmationofthe entry
Back
PlusIncreases the displayed value
MinusReduces the displayed value
Depending on the operating state of the automatic burner control system, differentinformationisdisplayed:
43 … 9042 … 90
Prin
ted
in G
erm
any
• Edi
tion
12.1
5 • N
r. 27
1 95
8
Overview of the display modes
Mode
Operation display
Error display
Info display
Display of the error memory
Parameterisationdisplay
Reset display
Flashingdisplay
Active
in normal operation if no error is active.
if the automatic system is in fault lock.
Fromoperationdisplaybypressingashortcut
and
Fromoperationdisplaybypressingashortcut
Fromoperationdisplaybypressingashortcut
Fromoperationdisplaybypressingashortcut
Depending on the display mode:
1.Requesttoconfirmtheaccesslevelchange2.Keeptheunlockkeydepressedformorethan5storestarttheMPA("Extend-edunlocking")
3.Processor2error,seeerrorlist4.Newpasswordafterpasswordchange5.Restartoftheautomaticsystem,allsegmentsandLEDsareflashing
43 … 9042 … 90
Prin
ted
in G
erm
any
• Edi
tion
12.1
5 • N
r. 27
1 95
8
Heatrequestblue
Flameyellow
Faultred
Characterblue
Display
▶ Displayed operating state for setting parameters and troubleshooting
AttentionObserve indication on 7-segment display
1. Digits
6=
8=
0=
2. Letters
Borb=
Dord=
Ooro=
45 … 9044 … 90
Prin
ted
in G
erm
any
• Edi
tion
12.1
5 • N
r. 27
1 95
8
Operation display MPA 4112 PF
▶ Shows the operating state of the automatic system
11.7 Operating state
OperationState 15
WaitingforgaspressureState34
with open safety chain
StabilisationtimeState14
External lightcheckuntilflameisdetected states8-13
Waitingforheatrequeststate 7
Watchdogloadingphase and decision flameorHTstates6-7
Switch-on delayuntiltestterminals11&14state2-4
Safety chainclosed1
Idle state controlLDW(airpressureswitch)State6
Post-ventingandrestart delay. states16-18
withinsufficientgasGas pressure present
Safety chainclosed
Safety chain openState35
JumptoHTstates23-24
OperationState31
Stabilisation timeState30
External light check until pre-venting states 27-29
Waitingforheatrequeststate26
IdlestatecontrolLDW(airpressureswitch)State 25
Post-ventingandrestart delay. states32-33
Flame states HT states
Ifflamedetected
Temperature too lowor24helapsed24helapsed
Temperature reached
Ab:Jumpfromflameto HTstates20or21
Temperature already reached
45 … 9044 … 90
Prin
ted
in G
erm
any
• Edi
tion
12.1
5 • N
r. 27
1 95
8
Operation display
Operation display additional information
▶ Display of state number▶ Display and setting the bus address
Display of state number
Pressthekeyssimultaneouslytochangethestate display
DisplayofbusaddressorOFF
Display of bus address while pressing a key
Operation display
Reduce the value
Increase the value
Next digit
PreviousdigitCancelif100thpositionisflashing
Deactivate/activate OFF
Back to operation displayKey released again
after less than 5 s
Key pressed for more than 5 s (displayflashes)
Change of the value
Confirmvalues(lastdigits)
Back to operation display
47 … 9046 … 90
Prin
ted
in G
erm
any
• Edi
tion
12.1
5 • N
r. 27
1 95
8
Parameters are loaded from theparameterisation and service box intoMPA
Operation display
Operation display / parameterisation and service box
▶ Display of the automatic system state during parameterisation or checking in the service box
TheMPA is in testmode initialisedby theparam-eterisation and service box.Note: The parameter and reset display is locked dur-ing the test
47 … 9046 … 90
Prin
ted
in G
erm
any
• Edi
tion
12.1
5 • N
r. 27
1 95
8
Info display
▶ The information display is activated out of the operation display (not during automatic parameter setting).
▶ The information display allows you to see the flame quality, the resettable runtime meter, the resettable start counter and the switching cycles counter.
▶ This mode is quit after 60 seconds due to a timeout if you do not press any key within this time period.
Info display
Display of flamequalityMax 58<50flashingsee also:Annex-Flamedetector
Display of the resettable runtime meterflameandHT10,000thposition
Display of the resettable runt-imemeterflameandHT100thposition
Display of the resettable runtime meter FlameandHT1st position
Displayofresettableflamestartcounter 10,000thposition
Displayofresettableflamestartcounter 100thposition
Displayofresettableflamestart counter1st position
Display of the switching cycles counter watchdog relay10,000thresolutionValuesgreaterthan999999aredisplayedas"--"
Display of switching cycle counterV110,000thresolutionValuesgreaterthan999999are displayedas"--"
Display of switching cycle counter air valve10,000thresolutionValuesgreaterthan999999are displayedas"--"
Back to operation display
from each info display state
Back to operation display
49 … 9048 … 90
Prin
ted
in G
erm
any
• Edi
tion
12.1
5 • N
r. 27
1 95
8
Error display
▶ An error message is automatically displayed as soon as the automatic system goes to the fault lock position.
▶ The last occurred error is displayed.
▶ F1 to F9 are also displayed in standby and operation. F5 to F9 can be acknowledged by pressing simultaneously.
Error display
Aslongastheplusbuttoniskeptpressed, the state number is displayed
Aslongastheminuskeyiskeptpressed,the addition error message (additionalbyte1)isdisplayed
Automaticactivationif a fault is active
Aslongasthebackkeyiskeptpressed,thecurrentbusaddressorOFFisdisplayed
Unlocking
Aslongastheplusandminuskeysarekept pressed together, the additional error message (additionalbyte4)isdisplayed
49 … 9048 … 90
Prin
ted
in G
erm
any
• Edi
tion
12.1
5 • N
r. 27
1 95
8
Display of the error memory
▶ The display of the error memory is used to call the last 10 errors.▶ The error that has occurred last is displayed.
▶ The error memory display is activated out of the operation display (not during parameterisation dis-play).
▶ The error code is displayed on the two-digit seven-segment display.▶ This error memory display is quit after 60 s due to a timeout if you do not press any key within this time period.▶ If there is not any error for the error position, -- is displayed.
Display of the error memory
Aslongastheplusbuttoniskeptpressed,the state number is displayed
Switches to the operation display
Last error occurred
If the key is pressed, the previous error is displayed
Fromeacherror display state
Aslongastheplusbuttoniskeptpressed,the state number is displayed
Back to operation display
Last error of the last ten errors
...
Aslongastheplusandminuskeysarekept pressed together, the additional error message (additionalbyte4)isdisplayed
Aslongastheplusandminuskeysarekept pressed together, the additional error message (additionalbyte4)isdisplayed
Aslongastheminusbuttoniskeptpressed, the additional error message (additionalbyte1)isdisplayed
Aslongastheminusbuttoniskeptpressed, the additional error message (additionalbyte1)isdisplayed
51 … 9050 … 90
Prin
ted
in G
erm
any
• Edi
tion
12.1
5 • N
r. 27
1 95
8
Displaynumber
Parameter Valuerange
Unit
0 P30-Durationpre-venting 0...99 1 s1 P31-Pre-ignitiontime 0...99 1 s2 P32-Firstsafetytime 1...15 1 s3 P12-Restartattempts 1...54 P34-StabilisationtimeA 0...99 1 s5 P83-Durationoftheswitch-ondelayafterpoweron 0...99 1 s6 P41-OperationsafetytimeFLW1 08...35(=0.75...3.5s) 0.1s*1
7 P85-Pre-ventingtimeHT 0...99 1 s8 P51-Post-ventingtimeflame 0...99 1 s9 P14-Restartattemptsafteraflameout 0...5A P13-Restartattemptsafteramissingflame 0...5b P15-Faultswitch-offincaseofopeningthesafetychain 0=Off/1=OnC P16-LDW:Operatingmode 0...99d P18-OperatingmodeX17 0...3E P87-JumpdurationfromflameorpowerOntoHT 1...99 1 sh P17-Temperaturecontroller:Operatingmode 0...4L P19-Operatingmodeoutputoperation 0...99o P52-Off-periodbeforerestartflame 1...99 1 sn *2 P11-Fieldbusaddress 0...99*2
*1Adjustableinincrements: 08=0.75s 12/16 (onlypossibleforFLW1,smallestpossibleadjustment) oP=0.8125s 13/16 09=0.875s 14/16 (forUV41with0.125sreactiontime) 10=1s 16/16 15=1.5s 24/16 18=1.8125s 29/16 19=1.875s 30/16 (forUV41with0.125sreactiontime) 20=2s 32/16 25=2.5s 40/16 28=2.8125s 45/16 29=2.875s 46/16 (forUV41with0.125sreactiontime) 30=3s 48/16 35=3.5s 56/16
*2Usetheshortcut-and+toswitchbetweenOFF(display=oF)andtheaddress.Addressesover99mustbesetbymeansofVisionBox.Donotuseaddress"0".
Parameterisation display
Parameterisation display
▶ After activating the automatic parameter setting, 19 parameter values must be defined; see parameter list.
▶ This parameterisation is quit after 30 min. due to a timeout. ▶ A password is required for changing the parameters.
▶Attention: Some parameter values are displayed in another resolution than in the parameterisation mode using VisionBox. If it is not possible to display the parameter value in the resolution, -- is dis-played; nevertheless, the value may be changed in the resolution that can be displayed.
▶ To change service or OEM parameters, the required password or a higher-level password must be entered (e.g. all service parameters may also be changed using the OEM password).
51 … 9050 … 90
Prin
ted
in G
erm
any
• Edi
tion
12.1
5 • N
r. 27
1 95
8
flashing(30stimeout)
Passwordentry1. character
Passwordentry2. character
flashing(30stimeout)
Parameterswitchto"Para",powersupply"On"Passwordentry
Parameterisation display
▶ Attention: Press the "Back" button to return to previous steps in the parameterisation mode.
53 … 9052 … 90
Prin
ted
in G
erm
any
• Edi
tion
12.1
5 • N
r. 27
1 95
8
Parameter0(P30)Pre-ventingtime(0-99s/1s)
Parameter1(P31)Pre-ignition(0-99s/1s)
Parameter2(P32)Firstsafetytimeforstart-up(1-15s/1s)
Parameter3(P12)Numberofrestartattempts(0-5)
53 … 9052 … 90
Prin
ted
in G
erm
any
• Edi
tion
12.1
5 • N
r. 27
1 95
8
Parameter4(P34)StabilisationtimeA(0-99s/1s)
Parameter5(P83)Durationofswitch-ondelayaftervoltageon(0-99s/ 1 s)
Parameter6(P41)Operationsafetytimeforflamedetector1(0.75-3.5s/0.1s)
Parameter7(P85)Pre-ventingtimeHTmode(0-99s/1s)
55 … 9054 … 90
Prin
ted
in G
erm
any
• Edi
tion
12.1
5 • N
r. 27
1 95
8
Parameter8(P51)Post-ventingtimeflame(0-99s/1s)
Parameter9(P14)Numberofpermittedrestartsafterflamelift-offdur-ingoperation(0-5)
ParameterA(P13)Number of permitted restarts aftermissingflame(0-5)
Parameterb(P15)Locking after opening the safety chain0=No(Off)1=Yes(On)
55 … 9054 … 90
Prin
ted
in G
erm
any
• Edi
tion
12.1
5 • N
r. 27
1 95
8
ParameterC(P16)Operatingmodeoftheairpressureswitch(0-99)
Parameterd(P18)InputX17(0-3)
ParameterE(P87)Duration voltage on after operating mode HT (1-99/1s)
Parameterh(P17)Operating modeTemperaturecontroller(0-4)
57 … 9056 … 90
Prin
ted
in G
erm
any
• Edi
tion
12.1
5 • N
r. 27
1 95
8
ParameterL(P19)Outputoperatingmode(0-11)
Restartprotectionparameter(P52)Duration of the restart protection operating modeflame(0-99s/1s)
Parametern(P11)Fieldbusaddress(0-99,donotset"0")
(Press+and-together to switchfieldbusOnorOff)
Back to parameter0
Parameterreleased
If values are not changed
Ifvalue(s)arechangedbacktoparameter0
Back to parameter0
57 … 9056 … 90
Prin
ted
in G
erm
any
• Edi
tion
12.1
5 • N
r. 27
1 95
8
Reset display
Reset display
▶ The reset display is activated out of the operation display (not during automatic parameter setting).
▶The reset display can be used to delete the error memory, the access level, the resettable runtime meter, the start counter or switching cycles counter and to change the passwords for the service and OEM level.
▶ This mode is quit after 60 seconds due to a timeout if you do not press any key within this time period.▶ If the test mode of the parameter setting and service box is active, the reset display is locked.
Activationof theresetdisplaybysimultaneouspressingof the keys
Previousaction
Next action
Cancel action
Action0,1,2,3,6,7,8,9,10
Actiontobecarriedout:0Deletetheerrormemory1 Reset the access level2Deletetheresettableruntimemeterflame
and HT3Deleteresettable start counter4Changepasswordforservicelevel5 Change password for OEM level6Deleteswitchingcyclecounter ReseterrorF67.DeleteswitchingcyclecounterV1 ReseterrorF78. Delete switching cycle counter output air ReseterrorF8
Back to operation display
Execute action
Action4.5
1
59 … 9058 … 90
Prin
ted
in G
erm
any
• Edi
tion
12.1
5 • N
r. 27
1 95
8
Correct password
Entry1. character
Incorrect password
Back to operation display
Entry2. character
Entry of the previous password1. character
Entry of the previous password2. character
Display of new password
Display of new password
operation display
1
59 … 9058 … 90
Prin
ted
in G
erm
any
• Edi
tion
12.1
5 • N
r. 27
1 95
8
Error overviewMPA 4112 PF errors without error IDErrorID
Internalerror
Error descriptionPlease see the tables above for more information about the individual errors.
F1flashing x Low voltage
Internal errorF2
flashing x Internal error display
F3flashing
Thepasswordhasbeenenteredincorrectlywhentryingtochangeitorhasnotbeenconfirmedby means of the unlock key
F4flashing
The signal of the remote unlocking via bus is active for too long
F5flashing
WarningFlamehasbeendetectedintheHTmodeandnumberofattemptstoextinguishfireelapsed. Theerrormessageflashesthreetimesevery5s,alternativelytothestatenumber(andpossiblyother error messages)
F6flashing
Warningmaintenanceintervalforthewatchdogrelayhaselapsed.Theerrormessageflashesthreetimesevery5s,alternativelytothestatenumber(andpossiblyother error messages)
F7flashing
WarningmaintenanceintervalforV1elapsed.Theerrormessageflashesthreetimesevery5s,alternativelytothestatenumber(andpossiblyother error messages)
F8flashing
Warningmaintenanceintervalforairvalveelapsed.Theerrormessageflashesthreetimesevery5s,alternativelytothestatenumber(andpossiblyother error messages)
F9 flashing
Connectiontofieldbusmissing.P11wassettoON.
61 … 9060 … 90
Prin
ted
in G
erm
any
• Edi
tion
12.1
5 • N
r. 27
1 95
8
Error overviewMPA 4112 PFErrors from the basic system (0x01 to 0x3F)ErrorID
Internalerror
Error description
0x01 x0x02 x
0x03
INTERNALERROR:WATCHDOGPossiblecauseoftheerror:Too high ambient temperatureOvervoltage
0x04
LOCK-OUTRELEASEDENIEDPossiblecauseoftheerror:Morethan5unlockingoperationsinthelast15minutes,remedy:Waitorcarryoutanextendedunlocking
0x05 x0x06 x0x07 x0x08 x0x09 x0x0A x0x0B x0x0C x0x0D x0x0E x0x0F x0x10 x
0x11LOWVOLTAGEPossiblecauseoftheerror:The admissible lower voltage limit was not reached at least for a short time
0x12POWERFAILUREPossiblecauseoftheerror:Thesupplyvoltagewasinterruptedduringstart-up,operationorregularswitch-off
0x13
SAFETYCIRCUITNOTPOTENTIAL-FREESafety chain not potential-free.Possiblecauseoftheerror:The fan continues running too long, remedy: Increase the time for the restart protection
0x14 x0x15 x
0x16
COMMUNICATIONTWIPossiblecauseoftheerror:VisionBoxwasconnectedtotheTWIbusorseparatedfromthebuswhiletheMPAwasnotde-energised.TheTWIlineissubjecttoEMCinterferences.
0x17 x
61 … 9060 … 90
Prin
ted
in G
erm
any
• Edi
tion
12.1
5 • N
r. 27
1 95
8
Error overviewMPA 4112 PFErrorID
Internalerror
Error description
0x18
ERRORFROMEXTERNALAPPLICATIONPossiblecauseoftheerror:Timeoutofparametermode/manualmode(0.5hwithoutpressingakey)-detailerror4.Byte=0xA0AninvalidfieldbusaddresshasbeenenteredinP11fortheconnectedbusmodule.Detailerror4.Byte=0xA1and6.Byte=setaddressP11
Additional byte 1: 0xB4 (error of the VisionBox)Switch-offwascausedexternallybyselectingthe"switch-off"functioninthePCsoftwareoftheVisionBox
Additional byte 1: 0x90 (internal MPA error P2) Additionalbyte4:0x01InternalerrorAdditionalbyte4:0x08InternalerrorAdditionalbyte4:0x09InternalerrorAdditionalbyte4:0x0CErrorconfigurationwith5. Byte=0x13: 6.Byte=parameterofallocationnumber,e.g.0x13=P19 7.Byte=parametervalueoflowbyte 8.Byte=parametervalueofhighbyte Errorconfigurationwith5. Byte = 0x14: HeatrequestviaHWinput(P17=0)andairpurge has priority over heat request (P241:Bit0=1)notpossibleAdditionalbyte4:0x16InternalerrorAdditionalbyte4:0x1DInternalerrorAdditionalbyte4:0x1EInternalerrorAdditionalbyte4:0xE8ExtensionmodulenotrecognizedAdditionalbyte4:0xEEInterruptionofcommunicationtotheMPAAdditionalbyte4:0xEFExtensionmodulenotcompatiblewiththeMPAversionAdditionalbyte4:0xA0TimeoutparameterisationmodeAdditionalbyte4:0xA1InvalidbusaddressAdditionalbyte4:0xA2ErrorparameteradjustmentoftheserviceboxAdditionalbyte4:0xA5TheextensionmoduledoesnotrespondAdditional byte 1 0xC2 (extension module error) Additionalbyte4:0x08InternalerrorAdditionalbyte4:0x09InternalerrorAdditionalbyte4:0x0AInternalerrorAdditionalbyte4:0x1BInternalerror
0x19 reserved0x1A x0x1B reserved0x1C x
0x1DSYSTEMCRASHEDPossiblecauseoftheerror:ThereisstrongEMCinterferenceonMPA
0x1E x
63 … 9062 … 90
Prin
ted
in G
erm
any
• Edi
tion
12.1
5 • N
r. 27
1 95
8
Error overviewMPA 4112 PFErrors from the extended functions (0x40 to 0x9F)ErrorID
Internalerror
Error description
0x40 - 0x42
reserved
0x43 x0x44 - 0x55
reserved
0x56 x0x57 - 0x58
reserved
0x59
INTERFACEP2Possiblecauseoftheerror:ThebusconnectionhasbeeninterruptedandtheparameterP17hasbeenconfiguredinawaythatabusinterruptiontriggersasafetyshutdownfollowedbyafaultlock,seeP17:Temperaturecontroller operating mode
0x5A - 0x5F
reserved
0x60 CHANGEOFPARAMETERNOTRELEASEDAmonitoredparameterhasbeenchanged
Errors from the application (from 0xA0)
0xA0 x STATEDURATIONTOOLINGTime in the parameterisation mode has elapsed
0xA1 reserved
0xA2
SAFETYCIRCUITOPENPossiblecauseoftheerror:The safety chain has been opened or is not closedThe wires of the safety chain are interrupted
0xA3 reserved0xA4 x INTERNALERROR:FEEDBACKSIGNAL(V1)0xA5 x INTERNALERROR:FEEDBACKSIGNAL(V2)
63 … 9062 … 90
Prin
ted
in G
erm
any
• Edi
tion
12.1
5 • N
r. 27
1 95
8
Error overviewMPA 4112 PFErrors from the application (from 0xA0)ErrorID
Internalerror
Error description
0xA6
EXTRANEOUSLIGHTUPONSTARTUPPossiblecauseoftheerror:Earth connection to an ionisation electrodeGasflowsoutandisburnedforexamplebyneighbouringburnersDefectiveUVtubeConnectedflamedetector(UV,...)detectslightorisdefective
0xA7
NOFLAMEDURINGSAFETYPERIODAdditionalinformationbyte0:Bit0=FlameonFLW1Additionalinformationbyte1:FlamequalityforFLW1Possiblecauseoftheerror:Ionisation electrode incorrectly setIgnition electrodes incorrectly setInsulated lines of the ignition electrodes or defective ionisation electrodeGasvalvesdonotopenthegasflowConnectedflamedetector(UV,...)doesnotdetectlightorisdefectiveLinesofmainsconnectionontheMPAexchanged("N"and"L1")
0xA8
FLAMEFAILUREDURINGOPERATIONAdditionalinformationbyte0:Bit0=FlameonFLW1Additionalinformationbyte1:FlamequalityforFLW1Possiblecauseoftheerror:FlamebodydefectiveConnectedflamedetector(UV,...)doesnotdetectlightorisdefective
0xA9FLAMEFAILUREDURINGSTABILIZATIONAdditionalinformationbyte0:Bit0=FlameonFLW1Additionalinformationbyte1:FlamequalityforFLW1
0xAA
AIRPRESSURESWITCHISNOTIN"OFF"POSITIONPossiblecauseoftheerror:The air pressure switch is defectiveThereisairpressureduringtheidlestatecontrol,forexampleduetoanairflowfromtheexhaust line,... The threshold value of the air pressure switch is set incorrectly
0xAB AIRPRESSURESWITCHFAILURE0xAC x INTERNALERROR:FEEDBACKIGNITION0xAD LACKOFGASPRESSURESWITCHMIN.0xAE–0xAF
reserved
0xB0 x0xB1-0xB5
reserved
0xB6 PROOFOFCLOSURE0xB7–B9 reserved
0xBA EXTRANEOUSLIGHTUPONSTARTUPExternallight>1min.afterheatrequest
0xBB-0xD1
reserved
0xD2 REMONTE RESET DENIEDTheMPAmustbeunlockedbymeansoftheunlockkeyofthedisplay
0xD3 HTSIGNALOUTDI0xD4 x INTERNALERROR:FEEDBACKSROUTPUT
65 … 9064 … 90
Setting the bus address, bus termination .................................................................................................... 65-66Profibus ............................................................................................................................................................ 67-71Modbus ............................................................................................................................................................. 72-80Flame detector ................................................................................................................................................. 81-82UV 41 (HE). ....................................................................................................................................................... 83-84Ignition transformers ...................................................................................................................................... 85-87VisionBox ...............................................................................................................................................................88
Prin
ted
in G
erm
any
• Edi
tion
12.1
5 • N
r. 27
1 95
8
Annex
65 … 9064 … 90
Prin
ted
in G
erm
any
• Edi
tion
12.1
5 • N
r. 27
1 95
8
Setting the fieldbus addressIf you want to connect the automatic system to the bus, a valid address mustbeenteredinparameterP11.ThedisplayshowsOFFduringparametersetting if you have not set any address. Pressthekeys-and+toswitchtothechange mode. Now the desired ad-dress can be set.If you want to change the address later on, it is possible during operation. -Profibus1to126-Modbus1to247Attention:Whenchangingthefieldad-dress,theerrorF18(0x18)mayoccur.
Important:Anymodificationsareap-plied after a restart or an extended unlocking of the automatic system.AbusconnectionisnotrequiredforoperatingtheMPA.Ifabusisnotconnected,theMPAcanonlyreceivea heat request via the hardware input "Temperaturecontroller".If there is a bus connection, which can berecognisedbyaflashingdigitonthe display, the heat request is given bymeansofbit0inAB0.Whentheautomatic system is disconnected from thebusagain,thebehavioursetinP17is used:Temperature controller operating modeDuring operation and error messages, the current bus address may be seen bypressingthe←key.
If an invalid address for the connected busmoduleissetandtheMPAisinau-tomaticmode,itrestarts(error0x18).
If an invalid value for the connected bus moduleissetandtheMPAisinparam-eter mode, an error message is gener-ated.
Bus terminationAterminatorisrequiredonthefirstandlast device on the bus.
The shielding of the bus cable should be placed onto PEtoavoidelectromagneticradiation.
Pinassignment(M12-5B-coded)
Pin no. Signal1 +5Vsupplyforbustermination2 Datalineminus(Aconductor)3 Earth4 Datalineplus(Bconductor)5 not usedThread Shielding(earthconnection)recom-
mended
Pin Socket
1
2
3
4
3
1
2 4
5 5
67 … 9066 … 90
Prin
ted
in G
erm
any
• Edi
tion
12.1
5 • N
r. 27
1 95
8
Extension module MPA 41xx EM 2/4 Profibus DP interface,Modbus RTU / ASCII
Universal extension module for inte-gratingtheMPA4112PFinfieldbussystemswithupto31slaves(withoutrepeater).
Integrated functions:-ProfibusDPinterface-ModbusRTU/ASCII
The bus protocol can be selected by meansoftheDIPswitch.Viathebus,commandscanbetrans-mittedtotheMPAandstatusinforma-tion can be queried.
BUS protocol presettings
The4-pinDIPswitchisusedtoselectthe bus protocol and to activate the respective line termination. The bus protocol must be selected onlywithdeadvoltage.Modificationsare impossible during operation.
Bus protocol selection
DIP switch No. 4:
OFFposition=ProfibusONposition=Modbus
Bus termination
If the termination is activated via theDIPswitch,externalterminationresistors must not be plugged into the output connectors.
If a termination is activated, the termi-nation of the alternative bus protocol has to be deactivated in any case.Modbus termination
DIP switch No. 1:
ONposition=Modbusterminationresistor120Ohm
Profibus termination
DIP switches No. 2 and 3:
ONposition=Profibustermination220Ohm. Important: Switch both of them
Setting the bus address
ThebusaddressisenteredintheP11parameter(displayindication"n").OFFisdisplayedifnoaddresshasbeen entered. Anaddressbetween1and99(upto126viaVisionBox)canbeenteredintheparametermode.Anymodificationswilltakeeffectonlyafterarestart.
During operation and error messages, the current bus address may be seen bypressingthe←key.
Bus interruption
ModbusThe bus module requires at least one request per minute. If it is missing, the behavioursetinP17isused
ProfibusIf the cyclic data stream is interrupted, afteraProfibusWatchdogperioddefinedbythemaster(e.g.2.5s)thebehavioursetinP17isused:Tempera-ture controller operating mode
Profibus data
The amount of the input and output dataisdefinedbythemodulesintheenclosedGSDfileforProfibus.Profibus output data master to MPA
The output data have 8 bits, see table
Command contents of assigned bits:
Bit 0(heatrequest)setto1bymaster=heatrequest.
Bit 1Ifbit1(ventilation)issetto1bythe master, the air valve is activated in thestates0(error),7(flame:waitingforheatrequest)orstate26(HT:waitingforheatrequest)(P241).
Bit 2(remoteunlocking)setto1bymaster(atleast0.5smax.5s)=MPAis unlocked.
Bit 3Ifbit3issetto1bymaster,theoutputX11isswitchedon(P19=11).
Bit 4-6 not used
Bit 7 is reserved. Pleasesetto0
Eight modules are integrated in the deliveredGSDfile.Four,amoduleforBasic, Standard, Extended and Spe-cial Extended, do not receive an output bytebutonlyinputbytes(informationaboutMPA,seebelow);however,theycannotgivecommandstoMPA.
Bit Output byte AB00 Heat request1 Ventilation2 Remote unlocking3 OutputX11(P19=11)4 Not used5 Not used6 Not used7 Reserve(pleasesetto0)
ON 1 2 3 4
1 2 3 4 ON
1 2 3 4ON
67 … 9066 … 90
Prin
ted
in G
erm
any
• Edi
tion
12.1
5 • N
r. 27
1 95
8
Profibus input data MPA to master
Input data is information about the stateoftheMPA.Theinputdatacontainadifferentnumberofbytes,depending on the data transfer module used. The lower bytes are always the same, i.e. Basic transfer is included in Standard transfer, Standard transfer in Extended transfer.
Basic transfer 2 bytes EB0andEB1
Standardtransfer4bytesEB0toEB3
Extended transfer 12 bytes EB0toEB11
SpecialExtendedtransfer20bytesEB0toEB19
ThebytesEB0andEB1containbitinformation.If the bit is set to 1, the condition is included in the description of the bits.Some bits are active during the fault (markedwith"X"),othersare0.
69 … 9068 … 90
Prin
ted
in G
erm
any
• Edi
tion
12.1
5 • N
r. 27
1 95
8
Basic transfer areaMPA 4112 PFBit Input byte EB0 Description During fault0 Flameinput X5 01 Input HT X16 X
2 Input HT NC / Gas pressureswitch/POC
X17 X
3 Warningflamein HT
FlamedetectedintheHTmode X
4 InputAirpressureswitch X18 X
5 Input for temperature controller
X19 X
6 Output valve 1 X13 X
7 V2boost/energyint./HT active
X14 X
Bit Input byte EB1 Description During fault
0 Spark generator (ignitionactive)
X15 X
1 WarningswitchingcyclesV1
Parametervaluereached 0
2 Outputairvalve(airout)
X8 X
3 Output options X11 X
4Evaluation tem-
perature controller (HW+bus)
Evaluation between temperature controller hardware input and busspecification
X
5 Warningswitchingcycles air valve
Parametervaluereached 0
6 Warningswitchingcycles watchdog relay
Parametervaluereached 0
7 Fault X12 X
69 … 9068 … 90
Prin
ted
in G
erm
any
• Edi
tion
12.1
5 • N
r. 27
1 95
8
Standard transfer areaMPA 4112 PFBit Input byte EB2 Description During fault
0-7 State number or error code
Current state number or error code if there is a fault X
Bit Input byte EB3 Description During fault0-7 Flamequality Qualityoftheflameviaionisationinput 0
Bit Input byte EB5 Description During fault
0-7Resettable
runtime meterfor flame and HT
Byte1ofthe32-bitruntimemeter(unit:s)
X
Bit Input byte EB6 Description During fault
0-7Resettable
runtime meter for flame and HT
Byte2ofthe32-bitruntimemeter(unit:s)
X
Bit Input byte EB7 Description During fault
0-7Resettable
runtime meter for flame and HT
Highbyte(byte3)ofthe32-bitruntimemeter(unit:s)
X
Bit Input byte EB8 Description During fault
0-7Resettable
start counter for flame operation
Lowbyte(byte0)ofthe32-bitstartcounter X
Bit Input byte EB9 Description During fault
0-7Resettable
start counter for flame operation
Byte1ofthe32-bitstartcounter X
Bit Input byte EB10 Description During fault
0-7Resettable
start counter for flame operation
Byte2ofthe32-bitstartcounter X
Bit Input byte EB11 Description During fault
0-7Resettable
start counter for flame operation
Highbyte(byte3)ofthe32-bitstartcounter X
Extended transfer areaMPA 4112 PFBit Input byte EB4 Description During fault
0-7Resettable
runtime meter for flame and HT
Lowbyte(byte0)ofthe32-bitruntimemeter(unit:s)
X
71 … 9070 … 90
Prin
ted
in G
erm
any
• Edi
tion
12.1
5 • N
r. 27
1 95
8
Bit Input byte EB13 Description During fault
0-7 Maintenance counter V1
Highbyte(byte1)ofthe16-bitmaintenancecounter,Resolution1000switchingcycles
X
Bit Input byte EB14 Description During fault
0-7 Maintenance counterAirvalve
Lowbyte(byte0)ofthe16-bitmaintenancecounter,Resolution1000switchingcycles
X
Bit Input byte EB15 Description During fault
0-7 Maintenance counterAirvalve
Highbyte(byte1)ofthe16-bitmaintenancecounter,Resolution1000switchingcycles
X
Bit Input byte EB16 Description During fault
0-7 Maintenance counterWatchdogrelay
Lowbyte(byte0)ofthe16-bitmaintenancecounter,Resolution1000switchingcycles
X
Bit Input byte EB17 Description During fault
0-7 Maintenance counterWatchdogrelay
Highbyte(byte1)ofthe16-bitmaintenancecounter,Resolution1000switchingcycles
X
Bit Input byte EB18 Description During fault0-7 not used 0
Bit Input byte EB19 Description During fault0-7 not used 0
Special Extended transfer areaMPA 4112 PFBit Input byte EB12 Description During fault
0-7 Maintenance counter V1
Lowbyte(byte0)ofthe16-bitmaintenancecounter,Resolution1000switchingcycles
X
71 … 9070 … 90
Prin
ted
in G
erm
any
• Edi
tion
12.1
5 • N
r. 27
1 95
8
Declaration of the Profibus interfaceMPA 4112 PFManufactureridentification IDnumberOxOCF1(KarlDungsGmbH&Co.KG)ASCICtype VPC3+C
Sync and freeze modeIs supported(Synccommand:FreezealloutputsoftheaddressedslavesFreezecommand:Freezeallinputsoftheaddressedslaves)
Cycle time
Maximum time until there is a response to a request telegram, depending on the bus transfer rate:9.6kBit/sto500kBit/s→15bittimes1500kBit/s→20bittimes3000kBit/s→35bittimes6000kBit/s→50bittimes12000kBit/s→95bittimes
Diagnosis
TheProfibusmodulecreatesanexternaldiagnosisifitdetectsaninternaler-ror.ThediagnosisinformationoftheDPslaveconsistsofstandarddiagnosisinformation(6bytes).Octet 1: Bit0=Diagnosisstationdoesnotexist(setsmaster)Bit1=Diagnosisstationnotready:Theslaveisnotreadyfordataexchange.Bit2=Diag.cfg_Fault:ConfigurationdatadonotmatchBit3=Diag.ext_diag:SlavehasexternaldiagnosisdataBit4=Diag.notsupported:RequestedfunctionisnotsupportedinslaveBit5=Diag.invalid_slave_response(setsslavefixedto0)Bit6=Diag.prm_fault:Wrongparameters(IDnumber,etc.)Bit7=Diag.master_lock(setsmaster):Parametersofslavearesetbyan-other masterOctet 2:Bit0=Diag.Prm_req:SlaverequiresnewparametersBit1=Diag.Stat_diag:Staticaldiagnosis(bytediag-bits)Bit2=fixedto1Bit3=Diag.WD_ON:ReactionmonitoringactiveBit4=Diag.freeze_mode:FreezecommandreceivedBit5=Sync_mode:SynccommandreceivedBit6=reservedBit7=Diag.deactivated(setsmaster)Octet3:Bit0-Bit6=reservedBit7=Diag.ext_overflowOctet4:Diagmaster_add:Masteraddressaftersettingparameters(FFwith-out parameter setting)Octet 5: High byte ID numberOctet6:LowbyteIDnumber
Parameter Only cyclical communication supportedAutomaticbaudratedetection is supported
73 … 9072 … 90
Prin
ted
in G
erm
any
• Edi
tion
12.1
5 • N
r. 27
1 95
8
Modbus dataModbus RTU or ASCII mode
The modbus protocol can be switched overtoASCIImodeusingthefunctioncode0x41.The setting is permanently saved in the slave. Standard value (delivery) ismodbusRTU,19200BandandEvenParity.
Modbus output data master to MPA
The output data are commands to the MPA.Usethefollowingfunctioncodestowritethesespecifications.05(0x05)writeSingleCoil06(0x06)writeSingleRegisterTheoutputdatahave16bits,seetable
Bit Register address 00 Heat request1 Ventilation2 Remote unlocking3 Output terminal 11
(ifP19=11)4 Not used5 Not used6 Not used7 Not used8 Not used9 Not used10 Not used11 Not used12 Not used13 Not used14 Not used15 Not used
Command contents of assigned bits:
Bit 0(heatrequest)setto1bymaster=heat request.
Bit 1Ifbit1(ventilation)issetto1bythemaster, the air valve is activated in the states0(error),7(flame:waitingforheatrequest)orstate26(HT:waitingforheatrequest)(P241).
Bit 2 (remote unlocking) set to 1 bymaster(atleast0.5smax.5s)=MPAisunlocked.
Bit 3 Ifbit3 isset to1bymaster, theoutputX11isswitchedon(P19=11).
Bit 4-15 not used
Modbus input data MPA to master
Input data is information about the state oftheMPA.AnEBxcontains16bits.
Use the following function codes to read this information.03(0x03)ReadHoldingRegisters01(0x01)ReadCoils.
73 … 9072 … 90
Prin
ted
in G
erm
any
• Edi
tion
12.1
5 • N
r. 27
1 95
8
Bit Register address 0 Description During Fault
0 Flameinput X5 01 Input HT X16 X2 Input HT NC / Gas pressure
switch/POCX17 X
3 WarningflameinHT FlamedetectedintheHTmode X4 InputAirpressureswitch X18 X5 Input for temperature controller
(HW)X19 X
6 Output valve 1 X13 X7 V2boost/energyint./HTac-
tiveX14 X
8...15 Not used
Bit Register address 1 Description During Fault
0 Spark generator X15(ignitionactive) X1 WarningswitchingcyclesV1 Parametervaluereached 02 Outputairvalve(airout) X8 X3 Outputoptions0-11 X11 X4 Evaluation temperature control-
ler(HW+bus)Evaluation between temperature controller hardware input and bus specification
X
5 Warningswitchingcyclesairvalve
Parametervaluereached 0
6 Warningswitchingcycleswatchdog relay
Parametervaluereached 0
7 Fault X12 X8...15 Not used
Bit Register address 2 Description During Fault
0-7 State number or error code Current state number OR error code if there is a fault X8...15 Not used Not used
Bit Register address 4 Description During Fault
0-7 Resettable runtime meter for flameandHT
Lowbyte(byte0)ofthe32-bitruntimemeter(ins) X
8...15 Not used Not used
Bit Register address 3 Description During Fault
0-7 Flamequality Qualityoftheflamesignal/ionisationinput 08...15 Not used Not used
75 … 9074 … 90
Prin
ted
in G
erm
any
• Edi
tion
12.1
5 • N
r. 27
1 95
8
Bit Register address 5 Description During Fault
0-7 Resettable runtime meter for flameandHT
Byte1ofthe32-bitruntimemeter(ins) X
8...15 Not used Not used
Bit Register address 6 Description During Fault
0-7 Resettable runtime meter for flameandHT
Byte2ofthe32-bitruntimemeter(ins) X
8...15 Not used Not used
Bit Register address 7 Description During Fault
0-7 Resettable runtime meter for flameandHT
Highbyte(byte3)ofthe32-bitruntimemeter(ins) X
8...15 Not used Not used
Bit Register address 8 Description During Fault
0-7 Resettable start counter for flameoperation
Lowbyte(byte0)ofthe32-bitstartcounter X
8...15 Not used Not used
Bit Registration address 9 Description During Fault
0-7 Resettable start counterforflameoperation
Byte1ofthe32-bitstartcounter X
8...15 Not used Not used
Bit Register address 10 Description During Fault
0-7 Resettable start counterforflameoperation
Byte2ofthe32-bitstartcounter X
8...15 Not used Not used
Bit Register address 11 Description During Fault
0-7 Resettable start counterforflameoperation
Highbyte(byte3)ofthe32-bitstartcounter X
8...15 Not used Not used
Bit Register address 12 Description During Fault
0-7 MaintenancecounterV1 Lowbyte(byte0)ofthe16-bitmaintenancecounter,Resolution1000switchingcycles
X
8...15 Not used Not used
Bit Register address 13 Description During Fault
0-7 MaintenancecounterV1 Highbyte(byte1)ofthe16-bitmaintenancecounter,Resolution1000switchingcycles
X
8...15 Not used Not used
Bit Register address 14 Description During Fault
0-7 Maintenance counter air valve Lowbyte(byte0)ofthe16-bitmaintenancecounter,Resolution1000switchingcycles
X
8...15 Not used Not used
75 … 9074 … 90
Prin
ted
in G
erm
any
• Edi
tion
12.1
5 • N
r. 27
1 95
8
Bit Register address 15 Description During Fault
0-7 Maintenance counter air valve Highbyte(byte1)ofthe16-bitmaintenancecounter,Resolution1000switchingcycles
X
8...15 Not used Not used
Bit Register address 16 Description During Fault
0-7 Maintenance counter Watchdogrelay
Lowbyte(byte0)ofthe16-bitmaintenancecounter,Resolution1000switchingcycles
X
8...15 Not used Not used
Bit Register address 17 Description During Fault
0-7 Maintenance counter Watchdogrelay
Highbyte(byte1)ofthe16-bitmaintenancecounter,Resolution1000switchingcycles
X
8...15 Not used
Bit Register address 18 Description During Fault
0-7 Not used Not used8...15 Not used Not used
Bit Register address 19 Description During Fault
0-7 Not used Not used8...15 Not used Not used
Bit Register address 20 Description During Fault
0-7 Additionalerrorinformation Firstinfobyteofadditionalerror X8...15 Not used Not usedInthefollowing,theinformationissummarisedtoallowcompleteuseofthe16-bitregister.Query if the bus load is to be reduced.
Bit Register address 21 Description During Fault
0 Flameinput X5 01 Input HT X16 X2 Input HT NC / Gas pressure
switch/POCX17 X
3 WarningflameinHT FlamedetectedintheHTmode X4 Input air pressure switch X18 X5 Input for temperature controller X19 X6 Output valve 1 X13 X7 V2boost/energyint./HTac-
tiveX14 X
8 Spark generator X15(ignitionactive) X9 WarningswitchingcyclesV1 Parametervaluereached 010 Outputairvalve(airout) X8 X11 Outputoptions0-11 X11 X12 Evaluation temperature control-
ler(HW+bus)Evaluation between temperature controller hardware input and bus specification
X
13 Warningswitchingcyclesairvalve
Parametervaluereached 0
14 Warningswitchingcycleswatchdog relay
Parametervaluereached 0
15 Fault X12 X
77 … 9076 … 90
Prin
ted
in G
erm
any
• Edi
tion
12.1
5 • N
r. 27
1 95
8
Bit Register address 22 Description During Fault
0-7 State number orError code
Current state number OR error code if there is a fault X
8-15 Flamequality Qualityoftheflameviaionisationinput 0
Bit Register address 23 Description During Fault
0-7 ResettableRuntimemeterforflameandHT
Lowbyte(byte0)ofthe32-bitruntimemeter(ins) X
8-15 ResettableRuntimemeterforflameandHT
Byte1ofthe32-bitruntimemeter(ins) X
Bit Register address 24 Description During Fault
0-7 ResettableRuntimemeterforflameandHT
Byte2ofthe32-bitruntimemeter(ins) X
8-15 ResettableRuntimemeterforflameandHT
Highbyte(byte3)ofthe32-bitruntimemeter(ins) X
Bit Register address 25 Description During Fault
0-7 Resettable start counter forflameoperation
Lowbyte(byte0)ofthe32-bitstartcounter X
8-15 Resettable start counter forflameoperation
Byte1ofthe32-bitstartcounter X
77 … 9076 … 90
Prin
ted
in G
erm
any
• Edi
tion
12.1
5 • N
r. 27
1 95
8
Bit Register address 26 Description During Fault
0-7 Resettable start counterforflameoperation
Byte2ofthe32-bitstartcounter X
8-15 Resettable start counterforflameoperation
Highbyte(byte3)ofthe32-bitstartcounter X
Bit Register address 27 Description During Fault
0-15 MaintenancecounterV1 16-bitmaintenancecounter,resolution1000switchingcycles X
Bit Register address 28 Description During Fault
0-15 Maintenance counter air valve 16-bitmaintenancecounter,resolution1000switchingcycles X
Bit Register address 29 Description During Fault
0-15 Maintenance counterWatchdogrelay
16-bitmaintenancecounter,resolution1000switchingcycles X
Bit Register address 30 Description During Fault
0-15 not used
Bit Register address 31 Description During Fault
0-7 Additionalerrorinformation 1. Detailed information on the error message X8-15 Not used Not used
Bit Register address 32 Description During Fault
0-7 ArticlenumberSWP1 Byte0(lowbyte)ofthe24-bitarticlenumber X8-15 ArticlenumberSWP1 Byte1ofthe24-bitarticlenumber X
Bit Register address 33 Description During Fault
0-7 ArticlenumberSWP1 Byte0(highbyte)ofthe24-bitarticlenumber X8-15 IndexarticlenumberSWP1 e.g.0x5F="_";0x41="A",0x42="B"… X
Bit Register address 34 Description During Fault
0-7 Day of production ofMPA41xxPF X8-15 Month of production ofMPA41xxPF X
Bit Register address 35 Description During Fault
0-7 Year of production ofMPA41xxPF X8-15 Not used
Bit Register address 36 Description During Fault
0-7 Device number Byte0(lowbyte)ofthe32-bitdevicenumber X8-15 Device number Byte1ofthe32-bitdevicenumber X
Bit Register address 37 Description During Fault
0-7 Device number Byte2ofthe32-bitdevicenumber X8-15 Device number Byte3(highbyte)ofthe32-bitdevicenumber X
79 … 9078 … 90
Prin
ted
in G
erm
any
• Edi
tion
12.1
5 • N
r. 27
1 95
8
Bit Register address 38 Description During Fault
0-7 ArticlenumberHW Byte0(lowbyte)ofthe24-bitarticlenumber X8-15 ArticlenumberHW Byte1ofthe24-bitarticlenumber X
Bit Register address 39 Description During Fault
0-7 ArticlenumberHW Byte2(highbyte)ofthe24-bitarticlenumber X8-15 IndexarticlenumberHW e.g.0x5F="_";0x41="A",0x42="B"... X
Bit Register address 40 Description During Fault
0-7 Articlenumberdevice Byte0(lowbyte)ofthe24-bitarticlenumber X8-15 Articlenumberdevice Byte1ofthe24-bitarticlenumber X
Bit Register address 41 Description During Fault
0-7 Articlenumberdevice Byte2(highbyte)ofthe24-bitarticlenumber X8-15 Index article number device e.g.0x5F="_";0x41="A",0x42="B"… X
Bit Register address 42 Description During Fault
0-7 ArticlenumberSWEM Byte0(lowbyte)ofthe24-bitarticlenumber X8-15 ArticlenumberSWEM Byte1ofthe24-bitarticlenumber X
Bit Register address 43 Description During Fault
0-7 ArticlenumberSWEM Byte2(highbyte)ofthe24-bitarticlenumber X8-15 ArticlenumberSWEM e.g.0x5F="_";0x41="A",0x42="B"… X
Bit Register address 44 Description During Fault
0-7 Day of production ofEM2/4 X8-15 Month of production ofEM2/4 X
Bit Register address 45 Description During Fault
0-7 Year of production EM ofEM2/4 X8-15 Not used
Bit Register address 46 Description During Fault
0-7 Device number EM Byte0(lowbyte)ofthe32-bitdevicenumber X8-15 Device number EM Byte1ofthe32-bitdevicenumber X
Bit Register address 47 Description During Fault
0-7 Device number EM Byte2ofthe32-bitdevicenumber X8-15 Device number EM Byte3(highbyte)ofthe32-bitdevicenumber X
Bit Register address 48 Description During Fault
0-7 ArticlenumberHW-EM Byte0(lowbyte)ofthe24-bitarticlenumber X8-15 ArticlenumberHW-EM Byte1ofthe24-bitarticlenumber X
79 … 9078 … 90
Prin
ted
in G
erm
any
• Edi
tion
12.1
5 • N
r. 27
1 95
8
Bit Register address 49 Description During Fault
0-7 ArticlenumberHW-EM Byte2(highbyte)ofthe24-bitarticlenumber X8-15 IndexarticlenumberHW-EM e.g.0x5F="_";0x41="A",0x42="B"… X
Bit Register address 50 Description During Fault
0-7 ArticlenumberdeviceEM Byte0(lowbyte)ofthe24-bitarticlenumber X8-15 ArticlenumberdeviceEM Byte1ofthe24-bitarticlenumber X
Bit Register address 51 Description During Fault
0-7 ArticlenumberdeviceEM Byte2(highbyte)ofthe24-bitarticlenumber X8-15 Index article number device EM e.g.0x5F="_";0x41="A",0x42="B"… X
Bit Register address 52 Description During Fault
0-7 Additionalerrorinformation 4.Detailedinformationontheerrormessage X8-15 Not used
81 … 9080 … 90
Prin
ted
in G
erm
any
• Edi
tion
12.1
5 • N
r. 27
1 95
8
Line lengths
Designation Line length Electrical dataProfibusDP Max.1200m Galvanicallyisolated4kV
Modbus Max.1000m Galvanicallyisolated4kV
Supported baud rates
Profibus
ThefollowingtableisonlyvalidforlinetypeAtoEN50170
Transfer speed kBit/s
9.6 19.2 45.45 93.75 187.5 500 1500 3000 6000 12000
max. line length in m
1200 1200 1200 1200 1000 400 200 100 100 100
Modbus
9600bauds,19200bauds,19200baudsand57600bauds
The baud rate can be changed during operation by means of the function code0x41andispermanentlysavedinthe slave.The relative parity bit can also be defined.None,EvenandOddaresup-ported.Defaultvalues(upondelivery)are19200baudsandEvenParity.
Pin assignment MPA 4112 PF (M12–5 B-coded)
Pin no. Signal1 +5Vsupplyforbustermination2 Datalineminus(Aconductor)3 Earth4 Datalineplus(Bconductor)5 not used
Thread Shielding(earthconnection)recommended
Pin Socket
1
2
3
4
3
1
2 4
5 5
Bus termination
Aterminationresistorisrequiredonthefirstandthelastdeviceofthebusstructure.Alternativelytointernaltermination(seeabove),anexternalbustermina-tion resistor can be connected instead of another bus cable.
The bus cable shielding is to be con-nectedtoPEtoavoidelectromagneticradiation.
81 … 9080 … 90
Prin
ted
in G
erm
any
• Edi
tion
12.1
5 • N
r. 27
1 95
8
Flame detector
Operation requirements of separate flamedetectorsontheMPA4112PF:
Theflamedetectorsmustbetestedand approved for monitoring gas burn-ers.
The reaction times must be ob-served!
Totalreactiontime=reactiontimeMPA+reactiontimeflamedetector.Aproofaboutthecompliancewiththerequirements of EN 298 is required.
Thereactiontimeafteraflamelift-offofanexternalflamedetectormaynotbelonger than the start-gas safety time.WhenconnectedtoFLW1,theioni-sationbehaviourofaflamemustbesimulated(rectifiereffect).Thefollow-ing values are active on the ionisation inputandoutputoftheMPA:230VAC+10%-15%.TheinternalresistanceoftheMPAisapprox1MΩ.Forsafetyreasons,theflamesensormustworkproperlyalsowithaninternalresistanceof360kΩ.Under these conditions, the simulation circuitintheflamedetectormustreachatleastadirectcurrent3µA.If an alternating current with a DC com-ponent is simulated, the DC compo-nentshouldnotdropbelow25%.ThecurrentcanbederivedtoN,PEorreturnedtoNontheMPA.The EMC regulations must be ob-served(EN298).Theentiresystemmust not produce inadmissible emis-sions. MPA41xxPFisnotgalvanicallyiso-lated. MPA4112PFandtheflamedetectormust be connected according to the correct phase.
AttentionDUNGS cannot be held liable if the flamedetectorandtheautomaticburn-er control system do not work orderly together. Especially if the electromag-netic behaviour is not according to the regulations or if the time-dependent behaviour is not correct.
Thequalityoftheflamesignalisdisplayedforflamedetector1asanumberbetween0and58.Evaluationoftheflamesignalisonlypossiblewithionisationflamemonitor-ingandmonitoringwithUV41(HE).WhenusingtheUV42,FLW10IRorFLW20UV,themaximumvalueisalways displayed.
25
ION
/ μA
20
15
10
5
0
10 20 30 40 50 60
ION vs. digits MPA41
digits
83 … 9082 … 90
Prin
ted
in G
erm
any
• Edi
tion
12.1
5 • N
r. 27
1 95
8
Manufac-turer
Designa-tion
Type Output signal
Safety timeFlame de-tector
Total reac-tion time after flame lift-off
Intermittent Continu-ousoperation
– Ionisation electrode
Ionisation Ionisation 0s P41 Yes No
DUNGS UV41(HE)UVtube Ionisation 0.125s
(=2/16s)P41+0.125s Yes No
Flame detectors released by DUNGS:
FlamedetectorsthatarenotincludedinthislistmustbeauthorisedbeforeusebyDUNGS.
83 … 9082 … 90
Prin
ted
in G
erm
any
• Edi
tion
12.1
5 • N
r. 27
1 95
8
UV 41 (HE)TheUV41(HE)isaflamedetectorwithUVtubeinmetaldesignforhighmechanical stress.TheflamedetectorisconnectedtotheionisationinputoftheMPA41xxandissuitable for intermittent operation.Foruseincontinuousoperationappli-cations,theUV4xshutterisaddition-ally required.TheadapterUV4x-EM1/xmustbeusedformountingtheUV41(HE).
Technical data
Dimensions
UV 41 (HE)
UV4xEM1/xAdapter
UV 41 GeneralRated voltage 230VAC-15%...+10%Frequency 50…60HzPowerconsumption <1WProtectiontype IP54Ambienttemperature -40°C...+60°C
-40°C...+80°CwithreducedlifetimeoftheUVtubeStorage and transport -40°C...+80°CHumidity DIN60730-1,nodewingadmissibleLifetime 10,000operatinghours(design(HE)reducedlifetime)Mounting position as desiredDimensions in mm Diameter:44.5mm
Length:94mmLengthwithUV4x-EM1:approx.128-143mm
Max. line length 10m
M16x1.5
94 ø44.5
ø42
39.5
28.5
50
50
36
50
3628.5
G1/8"
EM1/3 EM1/4EM1/6
EM 1/5EM 1/7
EM 1/8EM 1/9
1/4"NPT 1/2"
NPT
G1/8" G3/4"
85 … 9084 … 90
Prin
ted
in G
erm
any
• Edi
tion
12.1
5 • N
r. 27
1 95
8
MountingTheUV41(HE)mustbemountedascloselyaspossibletotheflametobemonitored. FormountingtheUV41ontheburnera suitable EM1/x adaptor is required.Whenmountingit,makesurethattherubber sealing ring enclosed with the UV41(HE)isinsertedbetweentheUV41(HE)andthemountingadapter.TheUV41(HE)sensorwillalsodetectexternallightasaflame,whichiswhytheUV41(HE)mustbemountedsuchthat, for example, no daylight, ignition sparksorUVsourcescanbedetected.TheUV41(HE)tubeissensitivetoimpacts, vibrations, etc., which is why it must be mounted without vibrating it.Afterthemountingworkiscomplete,allscrewsmustbecheckedfortightfit.Iftemperaturesofmorethan60°CarereachedattheUV41(HE),anadapterfittedwithaquartzcoverglassand,if necessary, an additional purging airconnectionmustbeused(uponrequest).
AttentionThe maximum allowed line lengths must not be exceeded. Supply and signal lines must be laid separately, as far as possible.
AttentionTheflamedetectorUV41(HE)isdeliv-ered without cable screw connection. To guarantee the required traction relief andIPprotectionclassIP54,acablescrewconnectionM16x1.5forcablediameters5-9mmisrequired(3x0.75mm²,whichcorrespondstoanAWGof20,to3x1.5mm²,whichcor-respondstoanAWGof16).The protective earth conductor must be connected using an insulated female connector according to DIN 46245.
Electrical connection
G
G
G
G
L (PIN3)
L (PIN3)
N�(PIN2)
N�(PIN2)
O�(PIN1)
O�(PIN1)
PE�(6,3x0.8)
PE�(6,3x0.8)
11
11
22
22
33
33
X101 X101
Connection UV 41 (HE) MPA 41xxPin1 Out Ionisation(5)Pin2 N NPin3 L Vers.FLW(7)PE
85 … 9084 … 90
Prin
ted
in G
erm
any
• Edi
tion
12.1
5 • N
r. 27
1 95
8
DEZ ignition transformers
Technical description
The DUNGS DEZ are electronic high-performance ignition transformers with high-frequency oscillation technology.Compared with conventional induc-tive ignition transformers, the DEZ are much smaller and lighter.Designs for one or two ignition elec-trodesareavailableindifferentvoltageversions.
Application
Foroilandgasburners,ignitiontakesplace, depending on design, with one ignition electrode against the burner mass or with two ignition electrodes between the electrodes.
Approval
73/23/EECLow-VoltageDirective89/336/EECEMCDirective
87 … 9086 … 90
Prin
ted
in G
erm
any
• Edi
tion
12.1
5 • N
r. 27
1 95
8
DEZ function
The DEZ ignition transformers are available in two versions.Eitherwithahigh-voltageoutput(DEZ1xx) for ignition against the burner mass or with two high-voltage outputs (DEZ2xx)forignitionbetweentheelectrodes.
Bothversionsareavailablewithdiffer-ent performance data.Foruseinburnersystemsinwhichignitionandionisationflamemonitoringtakes place via a common electrode, the"SEO"versionsmustbeused.
DEZ 1xx DEZ 2xx
DEZ Versions
DEZ 100 DEZ 101 DEZ 100 SEO DEZ 101 SEO DEZ 200
High-voltage outputs 1 1 1 1 2Mainsvoltage[VAC] 230/240 120 230 120 230/240Frequency[Hz] 50/60 50/60 50/60 50/60 50/60Currentconsumption[A] 0.3 0.5 0.3 0.5 0.14Powerconsumption[VA] 69 55 69 60 32Secondaryvoltage[kV]+/-10%
1 x 15 1 x 15 1 x 15 1 x 15 2x10
Secondaryfrequency[kHz] 10 13 10 16 10Short-circuitcurrent[mA] 30 30 30 30 20Dutycycle3min. 33% 33% 33% 33% 100%Protectiontype IP54 IP54 IP54 IP54 IP54Ambienttemperatureta[°C] -20…60°C -20…60°C -20…60°C -20…60°C -20…60°CWeight[kg] 0.32 0.32 0.32 0.32 0.32Articleno. 252113 255018 257126 257 127 252114
Electrical connectionConnection to the mains is made through pre-fabricated connection lines DEZ 1xx/2xx, which are available in differentlengths.
The ignition electrodes are connected viapre-fabricatedcarbonfibreignitionlines. The high line resistance of 10kOhm/meffectivelysuppressesEMC faults.
Theignitionlinesarefittedwithaninsulated6.5mmangleplugontheelectrode side.
DEZ connection
PowersupplyconnectionL1: blackN: blue : green-yellow
87 … 9086 … 90
Prin
ted
in G
erm
any
• Edi
tion
12.1
5 • N
r. 27
1 95
8
Dimensions
AttentionThe operation of the DEZ ignition transformers produces very high volt-ages. The ignition transformers may only be put into operation if the ignition electrodes were built into the burner / burner chamber touch-proof and all live connections by means of the lines provided for this purpose were made touch-proof.
Thelengthoftheignitionline(s)mustnot exceed 1 m.
Connecting the protective earth is mandatory.Inthe"SEO"versionforsingle-elec-trode operation, the protective earth isconnectedtoterminal5oftheMPA41xx.
DEZ connection Electrode connectionø6.3mm
89 … 9088 … 90
Prin
ted
in G
erm
any
• Edi
tion
12.1
5 • N
r. 27
1 95
8
VisionBoxTheVisionBoxisusedforaccesstotheMPAviaaPC.www.dungs.com/softwaretools
89 … 9088 … 90
Prin
ted
in G
erm
any
• Edi
tion
12.1
5 • N
r. 27
1 95
8
90 … 9090 … 90
Prin
ted
in G
erm
any
• Edi
tion
12.1
5 • N
r. 27
1 95
8
www.dungs.com
Karl Dungs GmbH & Co. KGSiemensstraße 6-10D-73660 Urbach, GermanyPhone +49(0)7181-804-0Fax +49(0)[email protected]