Maestro Sensor 369666d 1 09.27.17 SPECIFICATION SUBMITTAL Page Job Name: Job Number: Model Numbers: Switch with Occupancy/Vacancy Sensor Maestro Occupancy Sensing Switch The Lutron Maestro Occupancy sensing switch combines a Maestro switch with a passive infrared occupancy or vacancy sensor. The sensor detects the heat from occupants moving within an area to determine whether the space is occupied. Based on the feedback from the sensor, the occupancy sensing switch will adjust the load accordingly. Features • Passive infrared sensors with exclusive Lutron XCT Technology for fine motion detection • 180° sensor field-of-view • Up to 30 ft x 30 ft (9 m x 9 m) [900 ft 2 (81 m 2 )] major motion coverage and 20 ft x 20 ft (6 m x 6 m) [400 ft 2 (36 m 2 )] minor motion coverage • Occupancy version can be set to Auto-ON / Auto-OFF or Manual-ON / Auto-OFF • Vacancy version available to meet CA Title 24 requirements • Adjustable timeout (1, 5, 15, or 30 minutes) and high/low sensitivity adjustment • Occupancy sensing switch loads: incandescent, halogen, ELV, MLV, CFL, LED, magnetic fluorescent, electronic fluorescent, and fan. Note: "XX" in model number represents color/finish code. Models available MS-OPS2-XX 1 MS-OPS2H-XX-C 2 MS-OPS5M-XX 3 MS-OPS5MH-XX-C 2 MS-OPS6M2-DV-XX MS-OPS6M2N-DV-XX UMS-OPS6M-DV-XX MS-VPS2-XX 1 MS-VPS5M-XX 3 MS-VPS6M2-DV-XX MS-VPS6M2N-DV-XX UMS-VPS6M-DV-XX MS-OPS2 MS-OPS2H-XX-C MS-OPS5M MS-OPS5MH-XX-C MS-OPS6M2-DV MS-OPS6M2N-DV MS-VPS2 MS-VPS5M MS-VPS6M2-DV MS-VPS6M2N-DV UMS-OPS6M-DV UMS-VPS6M-DV 1 For clamshell packaging, add an "H" after the "2". Available in AL, IV, LA, and WH. 2 Clamshell packaged product for Canada. Available in AL, IV, LA, and WH. 3 For clamshell packaging, add an "H" after the "M". Available in AL, IV, LA, and WH.
17
Embed
Maestro Occupancy Sensing Switch - Lutron Electronics, … · Maestro Occupancy Sensing Switch ... , LED, magnetic fluorescent, electronic fluorescent, and fan. Note: "XX" in model
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Maestro Sensor
369666d 1 09.27.17
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Switch with Occupancy/ Vacancy Sensor
Maestro Occupancy Sensing SwitchThe Lutron Maestro Occupancy sensing switch combines a Maestro switch with a passive infrared occupancy or vacancy sensor. The sensor detects the heat from occupants moving within an area to determine whether the space is occupied. Based on the feedback from the sensor, the occupancy sensing switch will adjust the load accordingly.
• LutronPatentedSoftswitchcircuit—eliminatesarcingat mechanical contacts when loads are switched. Extendsrelaylifetoanaverageof1,000,000cycles(on/off)forresistive,capacitive,orinductivesources
XCT TechnologyAdvancedsensingtechnologyforfinemotiondetection ensures that the lights stay on while the room is occupied, and that the sensor does not turn on falsely when there is no occupancy in the room.Formoreinformation,seewww.lutron.com/TechnicalDocumentLibrary/white%20paper%20XCT%204-23-09%20B.pdf
Custom SettingsAmbient Light DetectionLights turn on only if natural light in room is low.
• Smart—Ambientlightthresholdadjustspreciselytothe user’s preference.Instructions:Ifswitchturnsonwhenthereisenoughnaturallight,orifswitch does not turn on when there is not enough natural light, press thelargebuttonwithin5secondsofenteringtheroom.Overtime,thisinteraction will “teach” the switch your preferred setting.
automatically turned off, during which the lights will automatically turn back on in response to motion. This grace period is provided as a safety and convenience feature in the event that the lights turn off while the room is still occupied, so that the user does not need to manually turn thelightsbackon.After15seconds,thegraceperiodexpiresandthelights must be manually turned on.
Occupancy Sensing Switch Placement and Operation• TheabilityoftheOccupancysensingswitchtodetectmotionrequiresline-of-sightofroomoccupants.The
Occupancy sensing switch must have an unobstructed view of the room.• HotobjectsandmovingaircurrentscanaffecttheperformanceoftheOccupancysensingswitch.• TheperformanceoftheOccupancysensingswitchdependsonatemperaturedifferentialbetweentheambient
roomtemperatureandthatofroomoccupants.WarmerroomsmayreducetheabilityoftheOccupancysensingswitch to detect occupants.
DefinitionsMajor motion: movement of a person entering or passing through an area.Minor motion:movementofapersonoccupyinganareaandengaginginsmallactivities(e.g.,reachingforatelephone,turningthepagesofabook,openingafilefolder,pickingupacoffeecup).
Sensor LED(behindlens) Pulsesduringconfigurationof custom settings and in the Test mode.
IMPORTANT NOTICEFASS—Front Accessible Service Switch— Toserviceload,removepowerbypullingtheFASSswitch out completely on either the Dimmer orCompanion Dimmer. After servicing load, pushtheFASSswitchbackinfullytorestorepowertothe control.
Status LEDIndicatesloadstatus;glowssoftlyas night light when light is off
Sensor LEDPulsestoacknowledge motion when theloadisON.
1 Asinglestandardmechanical3-wayswitchorupto9companionswitchesmaybeconnectedtomostOccupancysensingswitches. Standardmechanical3-wayswitchcannotbecombinedwithcompanionswitch.Totalblueterminalwirelengthmaybeupto150 ft(46 m).
2 OnlyoneOccupancysensingswitchcanbeusedpermulti-locationcircuit.3 Fanloadappliesto120V~only(notfor277V~).4 Occupancy sensing switch can be installed in any location.
Continued on next page...
3-way Installation with Standard Mechanical Switch (277 V~)1, 2, 3
-OPS6M2-DV,-VPS6M2-DV
Black
Blue
Green
Ground
Occupancy sensing switch
Ground
277V~ 50/60Hz
Hot/Live
Neutral
Load
Standard mechanical switch
Black
Jumper wireBare
Differentcolor screw (Common)
Wiring Diagram 4
Black
Blue
Ground
Occupancy sensing switch
Green
Ground277V~ 50/60Hz
Hot/Live
Load
Standard mechanical switch
Black
Jumper wireBare
Differentcolor screw (Common)
Neutral
OR
Greenscrew
Greenscrew
Maestro Sensor
369666d 11 09.27.17
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Switch with Occupancy/ Vacancy Sensor
1 Asinglestandardmechanical3-wayswitchorupto9companionswitchesmaybeconnectedtomostOccupancysensingswitches. Standardmechanical3-wayswitchcannotbecombinedwithcompanionswitch.Totalblueterminalwirelengthmaybeupto150 ft(46 m).
2 OnlyoneOccupancysensingswitchcanbeusedpermulti-locationcircuit.3 Occupancy sensing switch can be installed in any location.4 Fanloadappliesto120V~only(notfor277V~).
3-way Installation with Standard Mechanical Switch (277 V~)1, 2, 3
-OPS6M2N-DV,-VPS6M2N-DV
Wiring Diagram 9
OR
Black
Blue
WhiteGround
Occupancy sensing switch
Ground
277V~ 50/60Hz
Hot/Live
Neutral
Load
Standard mechanical switch
Black
Jumper wireBare
Differentcolor screw (Common)
Greenscrew
Black
Blue
Ground
Occupancy sensing switch
White
Ground277V~ 50/60Hz
Hot/Live
Neutral
Load
Standard mechanical switch
Black
Jumper wireBare
Differentcolor screw (Common)
Greenscrew
Maestro Sensor
369666d1409.27.17
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Switch with Occupancy/ Vacancy Sensor
Wiring Diagrams (continued)
1 Asinglestandardmechanical3-wayswitchorupto9companionswitchesmaybeconnectedtomostOccupancysensingswitches. Standardmechanical3-wayswitchcannotbecombinedwithcompanionswitch.Totalblueterminalwirelengthmaybeupto150 ft(46 m).
2 OnlyoneOccupancysensingswitchcanbeusedpermulti-locationcircuit.3 Occupancy sensing switch can be installed in any location.4 Fanloadappliesto120V~only(notfor277V~).
1 Whenusingcontrolsinsinglelocationinstallations,tightentheblueterminalorcapbluewire.Donotconnecttheblueterminal/wiretoanyotherwireortoground.2 Fanloadappliesto120V~only(notfor277V~).3 OptionalshuntcapacitormustbeinstalledinsidetheloadfixtureorinaseparateJ-box.4 Upto9companionswitchesmaybeconnectedtoanOccupancysensingswitch.Totalblueterminalwirelengthmaybeupto250 ft(76 m).5 OnlyoneOccupancysensingswitchcanbeusedpermulti-locationcircuit.6 Occupancy sensing switch can be installed in any location.
Single Location Installation with Shunt Capacitor1, 2, 3
1 OptionalshuntcapacitormustbeinstalledinsidetheloadfixtureorinaseparateJ-box.2 Upto9companionswitchesmaybeconnectedtoanOccupancysensingswitch.Totalblueterminalwirelengthmaybeupto250 ft(76 m)3 OnlyoneOccupancysensingswitchcanbeusedpermulti-locationcircuit.4 Occupancy sensing switch can be installed in any location.5 Fanloadappliesto120V~only(notfor277V~).
Wiring Diagrams (continued)
Multi-Location Installation with Shunt Capacitor (120 V~)1, 2, 3, 4