This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
CS
RE
VIS
ION
TA
BL
EN
UM
BE
RD
AT
ER
EV
ISE
D B
YD
ES
CR
IPT
ION
SHEET:
SCALE:
T.M
.P.
52
-10
-93
HE
CK
LE
R T
RA
CT
WE
ST
RO
CK
HIL
L T
OW
NS
HIP
BU
CK
S C
OU
NT
Y
73
5 M
insi T
rail
Pe
rka
sie
, P
A 1
89
44
Ph
on
e: 2
15
-79
4-5
39
1E
ma
il:in
fo@
lyn
nb
uild
ers
llc.c
om
DATE:
AS NOTED
SE
AL
Ridge Valley Road Residence
LO
T #
3R
IDG
E V
AL
LE
Y R
D
A.P. ACCESS PANEL LIN LINEN
LAMINATED VENEER LUMBER
ORIENTED STRAND BOARDOVERFLOW SCUPPEROVERFLOW RAIN WATER CONDUCTOR
Vertical load transfer = 2000 plf max along load bearing wall.
SQUASH BLOCKS AT INTERIOR BEARING
of high lateral load.
Check local building code for appropriate details in areas
Bearing wall, G-P Lam LVL or Glulam Beam
(2x4 minimum)
Squash block
F10
8d nails
1/16"
side at bearing.sinker nail eachOne 10d box or
G-P Lam LVL or
Glulam Beam
JOIST TO BEAM CONNECTION
stiffener requirements.
detail F18 for bearing
be substituted. See
mount hangers may
* Appropriate face
hangers *Top mount
A
F15
Steel Beam
B
flush with inside face of beam.
Bearing plate. Keep plate
Top mount hangers *
JOIST TO BEAM CONNECTION, STEP DOWN
APA Rated Sheathing
or STURD-I-FLOOR
requirements.for blockingSee detail F7
Hanger
G-P approved
Sheathing or
APA Rated
23/32" 48/24
8d nails.
rim.
F17
Glulam Beam
G-P Lam LVL or
Bearing stiffeners may be required at hangers.
(See detail F18)
JOIST TO BEAM CONNECTION, STEP DOWN
sheathing attachment
Ledger for floor
F16
G-P Lam LVL or
Glulam Beam
Note: Bearing stiffeners
(see detail F18)
may be required.
Hanger
4'-0" m
ax.2x8 min. (designed by others)
nailed to backer block & web with
2 rows of 10d nails at 6" o.c.
and clinched when possible.
L
Uniform
loads only
Load bearing wallnot allowed.
X-bridging or Wood I Beam blocking panels (see
detail F2) required at cantilevers and continuing
for 4' on each side of cantilevered area.
CANTILEVER, DROPPEDC5
6"1 1/2 x L
4'-0" m
in.
Backer block depth (see detail F13) to
match that of full-depth filler blocking
(see detail F11). Install backer tight to
bottom flange. Nail with 2 rows of 10d
3"
2"
nails at 6" o.c. and clinch.
NOTES:
1 3/4" + 3 1/2"
Screws for 3-ply and 4-ply members must be from both sides of beam.
Screws are USP WS series or Simpson Strong-Tie SDS installed per manufacturer instructions.
B (Nails)THREE ROWS 12" O.C.
LVL FASTENING SCHEDULE
Confirm adequacy of the beam (depth and number of pieces) for carrying the
designated load.Stress level for nail and bolt values is 100%. Increases of 15% for snow loaded or 25%for non-snow loaded roof conditions are permitted.Top and bottom row of connectors should be 2" from edge.Bolt holes are to be the same diameter as the bolt. Every bolt must extend throughthe full thickness of the member. Use washers under head and nut.For three-piece member, specified nailing is from the each side.To minimize rotation, four-piece members should only be used when loads are appliedto both sides, or completely across the top of the member.Four-piece members must be bolted or attached with 6" screws from both sides.Floor joists must be attached with approved metal hangers.
1 3/4" Multiple Plies
TWO ROWS 12" O.C.A (Nails) & F (Screws)
12" o.c.
2 PLY(2A Connection)(3B Connection)
3 PLY 4 PLY(4E Connection)(4C Connection)
4 PLY 2 PLY(2A Connection)
Either or Both Outside Pieces
Maximum Uniform Load Applied to
(Pounds per lineal foot)
Pieces
Member2 ROWS
12" o.c.
505
380
Not Permitted4
3
2
570
3 ROWS
12" o.c.
760
16d NAILS
inA B
SCREWS (Note 9)
2 ROWS
24" o.c.
500
375
330
380
340
2 ROWS
24" o.c.
505
675
760
2 ROWS
12" o.c.
1015
1/2" BOLTS
C D
665
745
995
2 ROWS
12" o.c.
FE3.
2.
1.
TWO ROWS 12" O.C.D (Bolts) & F (Screws)
C (Bolts) & E (Screws)TWO ROWS 24 IN. O.C. STAGGERED
12" o.c.24" o.c.
(4E Connection)3 PLY
(3C Connection)2 PLY
3 1/2"
12" o.c.
bearing, typical for all wood bearings.
1 1/2" from end. Drive nails at an angle to To avoid splitting flange, start nails at least
One 10d box or sinker nail each side at
ATTACHMENT AT END BEARING
prevent splitting of bearing plate.
F1
1 1/2" min.
at all floor and roof details1 3/4" minimum bearing length
BLOCKING PANEL, EXTERIOR
blocking panel
Vertical load transfer = 2000 plf max.
Wood I Beam
F2
TM
fessional's specs., but complying with
Installation Note D, p. 18 G-P Product Guide.)
8d nails at 6"o.c. (or per design pro-
3 rows of 10d nails at 12" o.c. from each side; offset opposite side nailing by 6" o.c. Clinch nails when possible.
of 10d nails at 12" o.c. from each side; offset opposite side nailing by 6". For flange widths greater than 2 1/2", use
Note: Block together full length with full-depth filler blocking. See detail F11 for filler size. Use 2 rows
or FiberStrong rim board23/32" APA rated sheathing 6"
X-bridging or Wood I Beam blocking panels (seedetail F2) required at cantilevers and continuing
6"
3-8d nailsat corners
rim board G-P FiberStrong
R
RIM BOARD CLOSUREVertical load transfer = 4850 plf
FIBERSTRONG
diaphragm nailing
rim board for
or FiberStrong
* Optional blocking
R
F5R
bottom flange8d nail top and
toe-nail to plate, typical8d nails at 6" on center
1/2" sheathing
Siding
Check local building code for appropriate detail in areas of high lateral load.
See detail F7 for blocking requirements.
SQUASH BLOCKS & SINGLE RIM JOIST
(2x4 minimum)
1/16"
F4
rated sheathing
23/32" 48/24 APA
Squash blocks
R
along load bearing wall based on bearing Vertical load transfer = 2000 plf max.
stress of 390 psi.
8d nails
8d nail top and
toe-nail to plate, typical
8d nails at 6" on center
rim board G-P FiberStrong
bottom flange
R
DECK ATTACHMENTF6
and over siding
Fill holes with high quality caulking.
in FiberStrong rimboard.
and therefore should be avoided.the lateral resistance of the screwOver-torquing can significantly reducea wrench, not by driving with a hammer.inserted in a lead hole by turning withCAUTION: The lag screw should be
lag screws). 350# per bolt.with washers and nuts (or 1/2" x 4"1/2" diameter x 4" through bolts
2x_ PT ledger attached with
Lower fastener may alternately be located
1/2" sheathing
flashingMetal
2" (min.)
Extend flashingbelow 2x_ ledger
steel washersfor spacers
2-4 galvanizedor stainless
2x_ PT ledger
rim boardG-P FiberStrong
Sheathing
R
* Maintain 2"
rimboardof FiberStrongall edges/ends minimum from
NOTCH NOT GREATER THAN
50% OF PLATE WIDTH
TOP PLATES
PIPE
PLATE NOTCHING FOR
EXTERIOR AND BEARING WALLS
18 GA. x 1\" WIDE METAL TIE
ACROSS NOTCH NAILED TO EACH
SIDE OF NOTCH WITH 8-16d NAILS
EACH SIDE
STUD
TO EDGE
INTERIOR NON-BEARING
WALL:
BORED HOLE MAX.
DIAMETER 40%OF STUD
DEPTH
2"x4": 1.4"
2"x6": 2.2"
NOTCH MUST
NOT EXCEED
25% OF STUD
DEPTH
BORED HOLES SHALL
NOT BE LOCATED IN
SAME CROSS SECTION
OF CUT OR NOTCH IN
STUD
IF HOLE IS BETWEEN 40% AND 60%
OF STUD DEPTH, THEN STUD MUST
BE DOUBLED AND NO MORE THAN
TWO SUCCESSIVE STUDS ARE
DOUBLED AND SO BORED
(2"x4": 1.4-2.1") (2"x6": 2.2-3.3")
NOTCHING AND BORING HOLE LIMITATIONS
FOR INTERIOR AND EXTERIOR, BEARING AND NON-BEARING WALLS
1 - SUPPORT BACK OF WEB DURING NAILING TO PREVENT
DAMAGE TO WEB-FLANGE CONNECTION.
2 - LEAVE 1/8" GAP BETWEEN TOP OF FILLER BLOCKING AND
BOTTOM OF FLANGE.
3 - BLOCK SOLID BETWEEN JOISTS. FILLER NEED NOT BE ONE
CONTINUOUS LENGTH, BUT MUST EXTEND THE ENTIRE
LENGTH OF THE SPAN.
4 - PLACE JOISTS TOGETHER AND NAIL FROM EACH SIDE
WITH TWO (2) ROWS OF 10d NAILS AT 12" OC CLINCHED WHEN
POSSIBLE. STAGGER ROWS FROM OPPOSITE SIDES BY 6".
DO NOT
DO
DO
DO
DODO NOT
DO NOT
DOUBLE
JOIST
CONSTRUCTION
DO
DO
DO NOT
DO NOT BEVEL
CUT JOISTS
BEYOND INSIDE
FACE OF WALL
RAFTER
I-JOIST BLOCK'G OR RIM
B'D REQ'D AT BEAR'G FOR
LATERAL SUPPORT
EXTEND FLOOR SHEATHING TO
OUTSIDE FACE OF WALL
RAFTER
RAFTER
HANGER
FILLERBLOCKING
DO NOT
HANGER I-
JOISTS BY
TOP FLANGE
OR WEB
RIM BOARD
HANGER
DO NOT CUT
OR NOTCH
FLANGES
ALL WORK TO BE PERFORMED INACCORDANCE WITH THE 2009INTERNATIONAL RESIDENTIAL CODE
3/16"
1/16"
0'
0'
3/4"
0'
RE
VIS
ION
TA
BL
EN
UM
BE
RD
AT
ER
EV
ISE
D B
YD
ES
CR
IPT
ION
SHEET:
SCALE:
T.M
.P.
52
-10
-93
HE
CK
LE
R T
RA
CT
WE
ST
RO
CK
HIL
L T
OW
NS
HIP
BU
CK
S C
OU
NT
Y
A-7
73
5 M
insi T
rail
Pe
rka
sie
, P
A 1
89
44
Ph
on
e: 2
15
-79
4-5
39
1E
ma
il:in
fo@
lyn
nb
uild
ers
llc.c
om
DATE:
AS NOTED
SE
AL
LO
T #
3R
IDG
E V
AL
LE
Y R
D
3/15/2017
10" THK. CONCRETE FOUNDATION
IN CRUSH STONETIED TO SUMP
3" DIA. PERF. DRAIN SET
4" CRUSHED STONE6 MIL. POLY. VAPOR BARRIER
TYP. CONC. SLAB CONSTR.4" CONC. SLAB
CONTROL JOINT AT CL. OF FLR. & OFFSETS
TOWNSHIP AUTHORITY)REQ'D. BY CODE OR LOCALAND DISCHARGED TO SUMP CROCK OR DAYLIGHT (AS
OPTIONAL 4''~ PERF. DRAIN SET IN CRUSH STONE
DAMP-PROOFING
WALL ON 20" X 8" CONT CONCFTG, SOIL BRG. MIN. 3000 PSF
UN
BA
LA
NC
ED
FIL
L
MA
X H
T.
OF
VARIES
WOOD BASE (TYP.)
GLUED & NAILED TO FLOOR JOISTS
1/2" GWB CEILING (TYP.)
R-19 BATT INSULATION
FOR EACH 8'-0" SPAN )(W/ AT LEAST ONE LINE OF BRIDGING
FLOOR JOIST
1/2" GWB CEILING (TYP.)
3/4" SUBFLOOR T&G
TYP. FLR./CLG. CONSTR.
AS REQUIREDPROPER VENT
OR BLOWN INSULATION (TYP.)R-38 BATT INSULATION
12
ANCHOR STRAPS AT 4'-0" O.C.
2 X 6 P.T. SILL PLATE PER PLANSILL SEALER W/ APPROVED GALV.
11. Interior stair riser height shall be 7 3/4"maximum and 10" tread
minimum with 1"nosing.
12. Exterior stair riser height shall be 7" maximum and 11" treads
minimum.
13. Emergency escape and rescue required in all basements, habitable
attics and every sleeping room shall have at least one operable
emergency escape and rescue opening. Where basements contain
one or more sleeping areas, emergency egress and rescue openings
shall be required in each sleeping room, but shall not be required in
adjoining areas of the basement. Where emergency escape and
rescue openings are provided they shall have a sill height of not more
than 44" AFF.
14. Emergency openings with a finished sill height below the adjacent
ground elevation shall be provided with a window well.
15. All emergency openings shall have a minimum net clear opening of 5.7
s.f with the exception of grade floor openings which shall have a
minimum net clear opening of 5s.f. The minimum net clear opening
height shall be 24" and the minimum net clear opening width shall be
20"
16. All emergency openings shall be operational from the inside of the
room without the use of keys or tools.
17. Emergency escape windows under decks and porches are allowed
provided the location of the decks allow the emergency escape window
to be fully opened and provides a path not less than 36" in height to a
yard or court.
18. Garage door shall be tested in accordance with either ASTM E 330 or
ANSI/DSMA108, and shall meet the acceptance criteria of ANSI/DSMA
108.
19. Penetrations throughout the required garage separation shall be
protected by filling the opening around the penetrating item with
approved material to resist the free passage of flame and products of
combustion.
Duct Tightness Complies by either:
1. A post-construction test: leakage to outdoors shall be less than or equal to 8 cfm per
100s.f. of conditioned floor area or a total leakage less than or equal to 12 cfm per 100
s.f. ofconditioned floor area when tested at a pressure differential of .1 inch w.g. (25 pa)
acrossthe entire system, inclduing the manufacruere's air handler end closure. All
register bootsshall be taped or otherwise sealed during the test.
2. Rough-in test: total leakage shall be less than or equal to 6 cfm per 100 s.f. of
conditionedfloor area when tested at a pressure differential of .1 inch w.g. (25 pa) across
the entiresystem, including the manufacurere's air handler end closure. All register boots
shall be tapedor othersie sealed during the test. If air handler is not installed at the time
of the test, totalleakage shall be less than or equal to 4 cfm per 100 s.f. of conditioned
floor area.EXCEPTION - duct tightness test is not required if the air handler and all ducts
are locatedwithin conditioned spaceBuilding envelope air tightness and insulation complies by either:
1. A post rough-in blower door test result of less than 7 ach at 33.5 psf or:
2. The following items have been satisfied:
2.1. Air barriers and thermal barrier: installed on outside of air-permeable insulation
andbreaks or joints in the air barrier are filled or repaired.
2.2. Ceiling/attic: air barrier in any dropped ceiling/soffit is substantially aligned with
insulationand any gaps are sealed.
2.3. Above-grade walls: insulation is installed in substantial contact and continuous
alignmentwith the building envelope air barrier.
2.4. Floors: air barrier is installed at any exposed edge of insulation.
2.5. Plumbing and wiring: insulation is placed between outside and pipes, batt insulation
is cutto fit around wiring and plumbing, or sprayed/blown insulation extends behind piping
andwiring.
2.6. Corners, headers, narrow framing cavities and rim joists are insulated.
2.7. Shower/tub on exterior wall: insulation exists between showers/tubs and exterior
walls.
DUCT & BUILDING ENVELOPE REQUIREMENTS
CODE CONFORMANCE NOTES
CODE: 2009 INTERNATIONAL RESIDENTIAL CODE
CLIMATIC AND GEOGRAPHIC DESIGN CRITERIA
NOTE: THE JURISDICTION SHALL FILL IN ALL CATEGORIES LEFT BLANK AS PER THE 2009 IRC
GROUND
SNOW
LOAD30
WIND DESIGN
SEISMIC
DESIGN
CATEGORY
TOPOGRAPHIC
EFFECTS
SPEED
(mph)
90 B
SUBJECT TO DAMAGE FROM
WEATHERINGFROST
LINE
DEPTH
TERMITE
SEVERE 3'-0" MOD HIGH
WINTER
DESIGN
TEMP
ICE SHIELD
UNDER-LAYMENT
REQUIRED
FLOOD
HAZARDS
AIR
FREEZING
INDEX
MEAN
ANNUAL
TEMP
11 DEG. F YES, AVG. LOW 24
DEG F1000 51 DEG F
GENERAL NOTES
GENERAL
1. These plans and specifications are the sole property of Lynn Builders,
LLC.Any unauthorized use of these plans without written consent is prohibited.
2. Work performed shall comply with the following:
2.1. The general notes and typical details apply throughout the job
unlessotherwise noted or shown.
2.2. The 2009 IRC.
2.3. Contractor and Sub-contractor must comply with all state and federalOSHA
safety regulations during all phase of the construction andinstallation of building
components.
3. In areas where the drawings do not address methodology, the contractorshall
be bound to perform in strict compliance with manufacturer'sspecifications and
industry recommended procedures.
4. The Designer shall not be responsible for the safety and
constructionprocedures, techniques, means, methods or the failure of the Builder
tocarry out the work in accordance with the drawings or required buildingcodes. All
contractors shall be responsible for initiating, maintaining andsupervising al safety
precautions and programs necessary for the protectionof persons and property in
accordance with applicable governingregulations.
5. Verification of the plan dimensions and site conditions shall be
theresponsibility of the general contractor and his sub-contractors prior
toconstruction. Noted dimensions take precedence over scale.
6. Discrepancies and omissions: The contractor shall compare and
coordinateall drawings. When in the opinion of the contractor, a discrepancy
oromission exists, he shall promptly report it to the Designer for properadjustment
before proceeding with the work.
RE
VIS
ION
TA
BL
EN
UM
BE
RD
AT
ER
EV
ISE
D B
YD
ES
CR
IPT
ION
SHEET:
SCALE:
T.M
.P.
52
-10
-93
HE
CK
LE
R T
RA
CT
WE
ST
RO
CK
HIL
L T
OW
NS
HIP
BU
CK
S C
OU
NT
Y
A-9
73
5 M
insi T
rail
Pe
rka
sie
, P
A 1
89
44
Ph
on
e: 2
15
-79
4-5
39
1E
ma
il:in
fo@
lyn
nb
uild
ers
llc.c
om
DATE:
AS NOTED
SE
AL
LO
T #
3R
IDG
E V
AL
LE
Y R
D
3/15/2017
Hot Water Heater
WATER LINE DIAGRAMALL LINES TO BE 1/2" PEX UNLESS OTHERWISE NOTED
1"
1"3/4"
3/4"
Cold Manifold
Hot Manifold
1/2" PEX SUPPLY LINES
TO EACH FIXTURE (HOME
RUNS)
From Well
RANGE
H.W.H.
REGULATOR
1" TRU-FLEX TUBING
HOUSE WALL LINE
FURNACE
1" TRU-FLEX TUBING
1" TRU-FLEX TUBING
MANIFOLD
FIREPLACE
GAS LINE DIAGRAMNTS
RE
VIS
ION
TA
BL
EN
UM
BE
RD
AT
ER
EV
ISE
D B
YD
ES
CR
IPT
ION
SHEET:
SCALE:
T.M
.P.
52
-10
-93
HE
CK
LE
R T
RA
CT
WE
ST
RO
CK
HIL
L T
OW
NS
HIP
BU
CK
S C
OU
NT
Y
P-1
73
5 M
insi T
rail
Pe
rka
sie
, P
A 1
89
44
Ph
on
e: 2
15
-79
4-5
39
1E
ma
il:in
fo@
lyn
nb
uild
ers
llc.c
om
DATE:
AS NOTED
SE
AL
LO
T #
3R
IDG
E V
AL
LE
Y R
D
3/15/2017
NOTES:
1. TYPICAL PRESSURE DROP AT EACH
FIXTURE =0.5" W.C.
2. SPECIFIC GRAVITY OF NATURAL GAS AT
60 DEG.= 0.60-0.70
3. AGA GAS VALVE TO BE LOCATED AT
EACH APPLIANCE.
All drainage and vent piping to be PVCPLUMBING RISER DIAGRAMNTS
MASTER BATH HALL BATH
KITCHEN
POWDER ROOM
LAUNDRY
WC
SHOWER
LAV
3"2"
2" 2"
3"
3"
3"
TUB
LAV
2"2" 2"
WC
3"
3"
3"3"
WC3"
3"
LAV
2"
TUB
2" 2"
WASH2"
KIT SINK
3"
3"
CO
4"
TO SEPTIC
WH
UP
SD CO
3
3
EP
ALL BASEMENT OUTLETSTO BE GFI PROTECTED ASPER E3901.9 & E3902.5 (IRC
2009)
ELECTRIC PANEL
SUMP
DN
COSD
SD
SD
SD
SD
GFI
GFI
GFI
3
DN
UP
SD CO
SD HD
GFIGFI GFI
WP
GFI
3
GFI
GFI
3
GFI
GFI
3
GFI
3
3
WP
GD
RE
VIS
ION
TA
BL
EN
UM
BE
RD
AT
ER
EV
ISE
D B
YD
ES
CR
IPT
ION
SHEET:
SCALE:
T.M
.P.
52
-10
-93
HE
CK
LE
R T
RA
CT
WE
ST
RO
CK
HIL
L T
OW
NS
HIP
BU
CK
S C
OU
NT
Y
E-1
73
5 M
insi T
rail
Pe
rka
sie
, P
A 1
89
44
Ph
on
e: 2
15
-79
4-5
39
1E
ma
il:in
fo@
lyn
nb
uild
ers
llc.c
om
DATE:
AS NOTED
SE
AL
LO
T #
3R
IDG
E V
AL
LE
Y R
D
3/15/2017
FIRST FLOOR ELECTRICAL
SMOKE DETECTOR W/110V. JUNCTION BOX
D
S
J
J
TELEPHONE OUTLET (CAT-5E)
ELECTRICAL PANELE.P.
TELEVISION OUTLET
WALL EXHAUST FAN
GARBAGE DISPOSAL
220V. JUNCTION BOX
110V. JUNCTION BOX
FOUR WAY SWITCH
THREE WAY SWITCH
CEILING FAN
220
3
GENERAL
DISTANCE ABOVE FLOOR : OTHER THAN 12"
110V. DUPLEX OUTLET : 12" ABOVE FLOOR-TYPICAL
ELECTRICAL SYMBOLS
CONVENIENCE OUTLETS
FLUORESCENT FIXTURE W/NO. OF TUBES INDICATED
RECESSED IN CEILING OR SOFFIT
EXTERIOR BRACKET ON TIMER
WITH 110V. CONVENIENCE OUTLET
LIGHTED SWITCH
GROUND FAULT INTERRUPTER
WATERPROOF OUTLET
220V. OUTLET
SWITCHED OUTLET
G.F.I.
44"
W.P.
220
SWITCHES
UNDER CABINET LIGHT
WALL BRACKET
CEILING MOUNTED
4
T.
LIGHT FIXTURES
HEAT DETECTOR W/110V. JUNCTION BOXH
(LOCATED IN GARAGE AND ATTIC)
EXHAUST FANF
4
TIMER SWITCHT.
HALF-SWITCHED OUTLETH.
ETHERNET OUTLET (CAT-5E)
T.
E.
SINGLE POLE SWITCH
L.
CARBON MONOXIDE DETECTOR W/110V. JUNCTION BOXC
ELECTRICAL NOTES:1. LIGHTING SCHEDULE SHOWN IS SCHEMATIC IN NATUREONLY AND SUBJECT TO CHANGE BY BUILDER (PURSUANT TOCONSTRUCTION CONTRACT).
2. 50% OF ALL LIGHTING FIXTURES SHALL BE HIGH EFFICACYLAMPS AS PER N1104.1 OF THE 2009 IRC.
3. ALL RECEPTACLES SHALL BE TAMPER RESISTANT AS PERE4002.14 OF THE 2009 IRC.
4. BATHTUB AND SHOWER AREA LUMINARIES (IF ANY)SUBJECT TO SHOWER SPRAY SHALL BE MARKED FOR WETLOCATIONS.
5. ARC-FAULT CIRCUIT INTERRUPTER PROTECTION TO BEPROVIDED AS PER E3902.11 OF THE 2009 IRC.
6. LAUNDRY, UTILITY AND BAR SINK RECEPTACLES SHALL BEAS PER E3902.7 OF THE 2009 IRC.
7. OUTDOOR RECEPTACLES SHALL BE AS PER E 3901.7 OF THE2009 IRC (MINIMUM OF ONE IN FRONT AND REAR OFDWELLING).
8. UNFINISHED PORTIONS OF THE BASEMENT SHALL HAVE GFIPROTECTION AS PER E3901.9 & E3902.5 OF THE 2009 IRC.
9. GARBAGE DISPOSAL WIRE SHALL HAVE A FLEXCONNECTION TO THE MOTOR OR CORD & PLUG CONNECTIONAS PER E4101.3 OF THE 2009 IRC.
10. IF DISHWASHER IS HARDWIRED A LOCKOUT DEVICE SHALLBE INSTALLED ON THE CIRCUIT BREAKER OR A GROUNDEDCORD & PLUG CONNECTION SHALL BE PROVIDED AS PERE4101.3 & E4101.5 OF THE 2009 IRC.
11. WEATHER RESISTANT RECEPTACLES TO BE PROVIDED ASPER E4002.8 & E4002.9 OF THE 2009 IRC.
SECOND FLOOR ELECTRICALFOUNDATION ELECTRICAL
1/4" = 1'
1/4" = 1'1/4" = 1'
WH
UP
GAS HEATER
(SEE MFG. SPEC.)
16" x 8" DUCT
20" x 8" DUCT
24" X 10" DUCT
24" X 10" DUCT
GAS WATER HEATER
50 GAL. CAPACITY
(SEE MFG. SPEC.)
A/C UNIT TO BE LOCATED ON
SITE BY CONTRACTOR
(MOUNTED ON PAD)
VENT PIPES, LOCATE PER CODE
AND MFG. SPEC. MIN. CLEARANCE
FROM WINDOWS
SPILL A/C CONDENSATE
RUN-OFF INTO FLOOR SUMP
DN
UP
14" x 6" RETURN
150 CFM
14" x 6" RETURN
150 CFM
30" x 6" RETURN
400 CFM
14" x 6" RETURN
150 CFM
4" x 10" FLOOR REG.
100 CFM
6" SUPPLY PIPE
4" x 10" FLOOR REG.
100 CFM
6" SUPPLY PIPE
4" x 10" FLOOR REG.
100 CFM
6" SUPPLY PIPE
4" x 10" FLOOR REG.
100 CFM
6" SUPPLY PIPE
4" x 10" FLOOR REG.
100 CFM
6" SUPPLY PIPE
VENT PIPE, LOCATE PER CODE
AND MFG. SPEC. MIN. CLEARANCE
FROM WINDOWS
DN 30" x 6" RETURN
400 CFM
14" x 6" RETURN
150 CFM
14" x 6" RETURN
150 CFM
14" x 6" RETURN
150 CFM
4" x 10" FLOOR REG.
100 CFM
6" SUPPLY PIPE
4" x 10" FLOOR REG.
100 CFM
6" SUPPLY PIPE
4" x 10" FLOOR REG.
100 CFM
6" SUPPLY PIPE
4" x 10" FLOOR REG.
100 CFM
6" SUPPLY PIPE4" x 10" FLOOR REG.
100 CFM
6" SUPPLY PIPE
4" x 10" FLOOR REG.
100 CFM
6" SUPPLY PIPE
4" x 10" FLOOR REG.
100 CFM
6" SUPPLY PIPE
RE
VIS
ION
TA
BL
EN
UM
BE
RD
AT
ER
EV
ISE
D B
YD
ES
CR
IPT
ION
SHEET:
SCALE:
T.M
.P.
52
-10
-93
HE
CK
LE
R T
RA
CT
WE
ST
RO
CK
HIL
L T
OW
NS
HIP
BU
CK
S C
OU
NT
Y
H-1
73
5 M
insi T
rail
Pe
rka
sie
, P
A 1
89
44
Ph
on
e: 2
15
-79
4-5
39
1E
ma
il:in
fo@
lyn
nb
uild
ers
llc.c
om
DATE:
AS NOTED
SE
AL
LO
T #
3R
IDG
E V
AL
LE
Y R
D
3/15/2017
HVAC GENERAL NOTES:
1. ALL FEEDER AND RETURNS TO BE 6" INSULATED
FLEXIBLE PIP UNLESS OTHERWISE NOTED.
2. ALL GAS LINES TO HEATER, WATER HEATER, STOVE,
DRYER AND FIREPLACE TO HAVE AGA GAS VALVE
LOCATED BEHIND APPLIANCE.
3. NO CUTTING OF BEARING WALLS FOR PIPES OR
DUCTS. USE 2"X6" TO FRAME WALL OR BUILD FALSE
2"X4" WALL IN FRONT OF BEARING WALL TO RUN
PIPES AND DUCT WORK.
4. ALL MAIN DUCTS TO BE SHEET METAL W/1"
INSULATION BOARD OR ANY APPROVED DUCT
BOARD.
5. SUBCONTRACTORS SHALL VERIFY ALL DIMENSIONS,
STRUCTURE AND MATERIALS AND SHALL BRING
ANY DISCREPANCIES TO THE IMMEDIATE
ATTENTION OF THE GENERAL CONTRACTOR.FIRST FLOOR HVAC