LP 500
GENERATOR SPECIFICATION
Power Rating (KVA) 500
Electric Power (KWe) 400
Rated Current (A) 695
Output voltage (V) 415
Frequency (Hz) 50
Power factor (lag) 0.8
No of Phases 3
System Voltage (VDC) 24
Dimensions (L X W X H, mm x mm x mm) 5500 x 2000 x 2235
Open Set including panel stand & W/O Silencer (mm x mm x mm)
4000 x 1800 x 2200
ENGINE SPECIFICATION
Make Perkins UK
Model 2506A-E15TAG2
Engine Output Prime Net (Kwm / bhp) 435 / 583
Engine Output Prime Gross (Kwm / bhp) 451 / 605
Aspiration Turbocharged charge-cooled
No of Cylinder 6 Verticle Inline
Rated speed (RPM) 1500
Bore & stroke (mm x mm) 137 x 171
Compression ratio 16:1
Displacement (Litres) 15.2
Dry weight of Engine (kg) 1633
Exhaust Temperature (ºC) 550
Gross break mean effective pressure (kpa) 2405
Governor/class Electronic
Cooling system Water cooled
Page 2
Radiator Cu Brass with Charge Air cooler
Lub oil specs 15 W 40 CF 4
Lub oil sump capacity Max (Litres) 53
Lub oil sump capacity Min (Litres) 45
Typical lub oil consumption 0.10%
Total coolant capacity (Litres) 58
System Voltage (DC) 24
Battery capacity/rating 150 AH, (12v DC X 2 Nos)
Fuel Consumption 75% (g/KWh) 201
Fuel Consumption 100% (g/kWh) 199
Fuel Consumption @ 75 % load with Fan & charging alternator (Lit/Hr)**
76
Fuel Consumption 100% (Lit/Hr) 100
** Fuel Consumption of Genset @75% of load is considering specific gravity of fuel 0.8355 at NTP
condition, Tolerance will be +5%
ALTERNATOR SPECIFICATION
Make Stamford*
Frame size/model No. HCI544D1
Voltage regulation ± 0.5 %
Class of insulation Class H
Standard Enclosure IP 23
Winding Pitch 2/3
Telephonic Interference Factor Better than 50
Efficiency 94.8
Total Harmonic Factor Better Than 2%
SPECIFICATION FOR STANDARD MANUAL PANEL
Cubical type made of CRCA sheet, Powder coated, mounted inside canopy with hinged type doors
SWITCH GEAR 3pole MCB / MCCB
Controller used for start stop panel & MAN panel • Display
Page 3
DSE 6010 & 6020
• Engine Parameters - RPM, Oil Presssure, coolant temprature Hour Meter, battery volt, running status
• Electrical parameters - Voltage, current, Hz, KW, KVA, Pf, kWh
Digital Multifunction meter Voltage/Ampere/Frequency
Fault Indication (LED Type on Engine safety Unit)
• Low Oil pressure
• Battery Charger Failure
• High Engine Temperature
• Low fuel level
Current Transformers of suitable rating
Indications (LED):
• DG ON
• Load on DG
Control Key switch for Start/Stop
SPECIFICATION FOR STANDARD AMF PANEL
Cubical type made of CRCA sheet, Powder coated, mounted inside canopy with hinged type doors
SWITCH GEAR
• 4 Pole Contactor for DG
• 4 Pole Contactor for MAINS
• MCCB for short circuit protection
Features • Supports Engine equipped with electronic control unit
• Graphic back lit LCD Display
• Supervision of Mains and DG voltage
• Mains and DG contactor interlock
• Provision for Remote start / stop
• Over / under voltage protection
• Over / under frequency protection
Page 4
• Current / voltage asymmetry
• Over current protection
• Parameter setting by front panel key board
• Auto / Manual mode operation
• Programmable parameters / timers
• Configurable input and outputs
• Alarm history
• Displays Voltage, Current, frequency, PF, kW, kWH
• Displays engine parameters like Oil pressure, coolant temperature, Engine RPM, fuel consumption, Engine running hours
• Indication LED for Mains ok, Load on Mains, DG set running, Load on Dg set
Multifunction meter
• Voltage
• Ampere
• Frequency
Analogue meter
• Oil pressure
• Water Temperature
• Engine RPM
Indication Lamps
• Mains On
• DG On
• Load on Mains
• Load on DG
SMPS based battery charger with float boost charging.
Manual mode controls • DG start
Page 5
• DG stop
• Load transfer
POWER RATING
Power rating as per Standard reference condition as per BS 5514/ISO 3046/ISO 8528
Reference condition (Dec C Ambient Temp) 27
Atmospheric Condition (KPA -750mm of Hg) 100
Humidity 60% - As per IS10002, ISO 3046
LP 725
GENERATOR SPECIFICATION
Power Rating (KVA) 725
Electric Power (KWe) 580
Rated Current (A) 1008
Output voltage (V) 415
Frequency (Hz) 50
Power factor (lag) 0.8
No of Phases 3
System Voltage (VDC) 24
Dimensions (L X W X H, mm x mm x mm) 7500 x 2500 x 2930
Open Set including panel stand & W/O Silencer (mm x mm x mm)
4000 x 1800 x 2400
ENGINE SPECIFICATION
Make Perkins UK
Model 4006-23TAG2A
Engine Output Prime Net (Kwm / bhp) 632 / 847
Engine Output Prime Gross (Kwm / bhp) 658 / 882
Aspiration Turbocharged charge-cooled
No of Cylinder 6 Verticle Inline
Page 6
Rated speed (RPM) 1500
Bore & stroke (mm x mm) 160 x 190
Compression ratio 13.6:1
Displacement (Litres) 22.92
Dry weight of Engine (kg) 2524
Exhaust Temperature (ºC) 430
Gross break mean effective pressure (kpa) 2247
Governor/class Electronic
Cooling system Water cooled
Radiator Cu Brass with Charge Air cooler
Lub oil specs 15 W 40 CF 4
Lub oil sump capacity Max (Litres) 113.4
Lub oil sump capacity Min (Litres) 90.7
Typical lub oil consumption 0.25%
Total coolant capacity (Litres) 105
System Voltage (DC) 24
Battery capacity/rating 150 AH, (12v DC X 2 Nos)
Fuel Consumption 75% (g/KWh) 211
Fuel Consumption 100% (g/kWh) 209
Fuel Consumption @ 75 % load with Fan & charging alternator (Lit/Hr)**
121
Fuel Consumption 100% (Lit/Hr) 157
** Fuel Consumption of Genset @75% of load is considering specific gravity of fuel 0.8355 at NTP
condition, Tolerance will be +5%
ALTERNATOR SPECIFICATION
Make Stamford*
Frame size/model No. HCI634W1
Voltage regulation ± 0.5%
Class of insulation Class H
Page 7
Standard Enclosure IP 23
Winding Pitch 2/3
Telephonic Interference Factor Better than 50
Efficiency 94.6
Total Harmonic Factor Better Than 2%
SPECIFICATION FOR STANDARD MANUAL PANEL
Cubical type made of CRCA sheet, Powder coated, mounted inside canopy with hinged type doors
SWITCH GEAR 3pole MCB / MCCB
Controller used for start stop panel & MAN panel DSE 6010 & 6020
• Display
• Engine Parameters - RPM, Oil Presssure, coolant temprature Hour Meter, battery volt, running status
• Electrical parameters - Voltage, current, Hz, KW, KVA, Pf, kWh
Digital Multifunction meter Voltage/Ampere/Frequency
Fault Indication (LED Type on Engine safety Unit)
• Low Oil pressure
• Battery Charger Failure
• High Engine Temperature
• Low fuel level
Current Transformers of suitable rating
Indications (LED):
• DG ON
• Load on DG
Control Key switch for Start/Stop
SPECIFICATION FOR STANDARD AMF PANEL
Cubical type made of CRCA sheet, Powder coated, mounted inside canopy with hinged type doors
SWITCH GEAR • 4 Pole Contactor for DG
• 4 Pole Contactor for MAINS
Page 8
• MCCB for short circuit protection
Features
• Supports Engine equipped with electronic control unit
• Graphic back lit LCD Display
• Supervision of Mains and DG voltage
• Mains and DG contactor interlock
• Provision for Remote start / stop
• Over / under voltage protection
• Over / under frequency protection
• Current / voltage asymmetry
• Over current protection
• Parameter setting by front panel key board
• Auto / Manual mode operation
• Programmable parameters / timers
• Configurable input and outputs
• Alarm history
• Displays Voltage, Current, frequency, PF, kW, kWH
• Displays engine parameters like Oil pressure, coolant temperature, Engine RPM, fuel consumption, Engine running hours
• Indication LED for Mains ok, Load on Mains, DG set running, Load on Dg set
Multifunction meter • Voltage
• Ampere
• Frequency
Page 9
Analogue meter
• Oil pressure
• Water Temperature
• Engine RPM
Indication Lamps
• Mains On
• DG On
• Load on Mains
• Load on DG
SMPS based battery charger with float boost charging.
Manual mode controls
• DG start
• DG stop
• Load transfer
POWER RATING
Power rating as per Standard reference condition as per BS 5514/ISO 3046/ISO 8528
Reference condition (Dec C Ambient Temp) 27
Atmospheric Condition (KPA -750mm of Hg) 100
Humidity 60% - As per IS10002, ISO 3046
LP 1010
GENERATOR SPECIFICATION
Power Rating (KVA) 1010
Electric Power (KWe) 808
Rated Current (A) 1403.9
Output voltage (V) 415
Frequency (Hz) 50
Power factor (lag) 0.8
No of Phases 3
System Voltage (VDC) 24
Page 10
Dimensions (L X W X H, mm x mm x mm) -
Open Set including panel stand & W/O Silencer (mm x mm x mm)
5300 x 2000 x 2700
ENGINE SPECIFICATION
Make Perkins UK
Model 4008 TAG2A
Engine Output Prime Net (Kwm / bhp) 861 / 1155
Engine Output Prime Gross (Kwm / bhp) 899 / 1206
Aspiration Turbocharged charge-cooled
No of Cylinder 8 Inline
Rated speed (RPM) 1500
Bore & stroke (mm x mm) 160 x 190
Compression ratio 13.6:1
Displacement (Litres) 30.56
Dry weight of Engine (kg) 4270
Exhaust Temperature (ºC) 438
Gross break mean effective pressure (kpa) 2320
Governor/class Electronic
Cooling system Water cooled
Radiator Cu Brass with Charge Air cooler
Lub oil specs 15 W 40 CF 4
Lub oil sump capacity Max (Litres) 153
Lub oil sump capacity Min (Litres) 127
Typical lub oil consumption (g/kwH) 0.52
Total coolant capacity (Litres) 149
System Voltage (DC) 24
Battery capacity/rating 180 AH, (12v DC x 2 Nos)
Fuel Consumption 75% (g/KWh) 202
Page 11
Fuel Consumption 100% (g/kWh) 208
Fuel Consumption @ 75 % load with Fan & charging alternator (Lit/Hr)**
160
Fuel Consumption 100% (Lit/Hr) 220
** Fuel Consumption of Genset @75% of load is considering specific gravity of fuel 0.8355 at NTP
condition, Tolerance will be +5%
ALTERNATOR SPECIFICATION
Make Stamford*
Frame size/model No. HCI634Y1
Voltage regulation ± 0.5%
Class of insulation Class H
Standard Enclosure IP 23
Winding Pitch 2/3
Telephonic Interference Factor Better than 50
Efficiency 95.3
Total Harmonic Factor Better Than 2%
SPECIFICATION FOR STANDARD MANUAL PANEL
Cubical type made of CRCA sheet, Powder coated, mounted inside canopy with hinged type doors
SWITCH GEAR 3pole MCB / MCCB
Controller used for start stop panel & MAN panel DSE 6010 & 6020
• Display
• Engine Parameters - RPM, Oil Presssure, coolant temprature Hour Meter, battery volt, running status
• Electrical parameters - Voltage, current, Hz, KW, KVA, Pf, kWh
Digital Multifunction meter Voltage/Ampere/Frequency
Fault Indication (LED Type on Engine safety Unit) • Low Oil pressure
• Battery Charger Failure
• High Engine Temperature
Page 12
• Low fuel level
Current Transformers of suitable rating
Indications (LED):
• DG ON
• Load on DG
Control Key switch for Start/Stop
SPECIFICATION FOR STANDARD AMF PANEL
Cubical type made of CRCA sheet, Powder coated, mounted inside canopy with hinged type doors
SWITCH GEAR
• 4 Pole Contactor for DG
• 4 Pole Contactor for MAINS
• MCCB for short circuit protection
Features • Supports Engine equipped with electronic control unit
• Graphic back lit LCD Display
• Supervision of Mains and DG voltage
• Mains and DG contactor interlock
• Provision for Remote start / stop
• Over / under voltage protection
• Over / under frequency protection
• Current / voltage asymmetry
• Over current protection
• Parameter setting by front panel key board
• Auto / Manual mode operation
• Programmable parameters / timers
• Configurable input and outputs
• Alarm history
Page 13
• Displays Voltage, Current, frequency, PF, kW, kWH
• Displays engine parameters like Oil pressure, coolant temperature, Engine RPM, fuel consumption, Engine running hours
• Indication LED for Mains ok, Load on Mains, DG set running, Load on Dg set
Multifunction meter
• Voltage
• Ampere
• Frequency
Analogue meter
• Oil pressure
• Water Temperature
• Engine RPM
Indication Lamps
• Mains On
• DG On
• Load on Mains
• Load on DG
SMPS based battery charger with float boost charging.
Manual mode controls
• DG start
• DG stop
• Load transfer
POWER RATING
Power rating as per Standard reference condition as per BS 5514/ISO 3046/ISO 8528
Reference condition (Dec C Ambient Temp) 27
Atmospheric Condition (KPA - 750mm of Hg) 100
Humidity 60% - As per IS10002, ISO 3046
Page 14
LP 1250
GENERATOR SPECIFICATION
Power Rating (KVA) 1500
Electric Power (KWe) 1200
Rated Current (A) 2085
Output voltage (V) 415
Frequency (Hz) 50
Power factor (lag) 0.8
No of Phases 3
System Voltage (VDC) 24
Dimensions (L X W X H, mm x mm x mm) -
Open Set including panel stand & W/O Silencer (mm x mm x mm)
5300 x 2000 x 2800
ENGINE SPECIFICATION
Make Perkins UK
Model 4012-46TAG0A
Engine Output Prime Net (Kwm / bhp) 1053 / 1412
Engine Output Prime Gross (Kwm / bhp) 1117 / 1497
Aspiration Turbocharged charge-cooled
No of Cylinder 12 'Vee'
Rated speed (RPM) 1500
Bore & stroke (mm x mm) 160 x 190
Compression ratio 13.6:1
Displacement (Litres) 45.84
Dry weight of Engine (kg) 6086
Exhaust Temperature (ºC) 425
Gross break mean effective pressure (kpa) 1949
Governor/class Electronic
Cooling system Water cooled
Page 15
Radiator Cu Brass with Charge Air cooler
Lub oil specs 15 W 40 CF 4
Lub oil sump capacity Max (Litres) 159
Lub oil sump capacity Min (Litres) 136
Typical lub oil consumption (g/kwH) 0.52
Total coolant capacity (Litres) 210
System Voltage (DC) 24
Battery capacity/rating 180 AH, (12v DC x 4 Nos)
Fuel Consumption 75% (g/KWh) 204
Fuel Consumption 100% (g/kWh) 199
Fuel Consumption @ 75 % load with Fan & charging alternator (Lit/Hr)**
199
Fuel Consumption 100% (Lit/Hr) 259
** Fuel Consumption of Genset @75% of load is considering specific gravity of fuel 0.8355 at NTP
condition, Tolerance will be +5%
ALTERNATOR SPECIFICATION
Make Stamford*
Frame size/model No. PI734B1
Voltage regulation ± 0.5%
Class of insulation Class H
Standard Enclosure IP 23
Winding Pitch 2/3
Telephonic Interference Factor Better than 50
Efficiency 95
Total Harmonic Factor Better Than 2%
SPECIFICATION FOR STANDARD MANUAL PANEL
Cubical type made of CRCA sheet, Powder coated, mounted inside canopy with hinged type doors
SWITCH GEAR 3pole MCB / MCCB
Controller used for start stop panel & MAN panel • Display
Page 16
DSE 6010 & 6020
• Engine Parameters - RPM, Oil Presssure, coolant temprature Hour Meter, battery volt, running status
• Electrical parameters - Voltage, current, Hz, KW, KVA, Pf, kWh
Digital Multifunction meter Voltage/Ampere/Frequency
Fault Indication (LED Type on Engine safety Unit)
• Low Oil pressure
• Battery Charger Failure
• High Engine Temperature
• Low fuel level
Current Transformers of suitable rating
Indications (LED):
• DG ON
• Load on DG
Control Key switch for Start/Stop
SPECIFICATION FOR STANDARD AMF PANEL
Cubical type made of CRCA sheet, Powder coated, mounted inside canopy with hinged type doors
SWITCH GEAR
• 4 Pole Contactor for DG
• 4 Pole Contactor for MAINS
• MCCB for short circuit protection
Features • Supports Engine equipped with electronic control unit
• Graphic back lit LCD Display
• Supervision of Mains and DG voltage
• Mains and DG contactor interlock
• Provision for Remote start / stop
• Over / under voltage protection
Page 17
• Over / under frequency protection
• Current / voltage asymmetry
• Over current protection
• Parameter setting by front panel key board
• Auto / Manual mode operation
• Programmable parameters / timers
• Configurable input and outputs
• Alarm history
• Displays Voltage, Current, frequency, PF, kW, kWH
• Displays engine parameters like Oil pressure, coolant temperature, Engine RPM, fuel consumption, Engine running hours
• Indication LED for Mains ok, Load on Mains, DG set running, Load on Dg set
Multifunction meter
• Voltage
• Ampere
• Frequency
Analogue meter
• Oil pressure
• Water Temperature
• Engine RPM
Indication Lamps
• Mains On
• DG On
• Load on Mains
• Load on DG
SMPS based battery charger with float boost charging.
Page 18
Manual mode controls
• DG start
• DG stop
• Load transfer
POWER RATING
Power rating as per Standard reference condition as per BS 5514/ISO 3046/ISO 8528
Reference condition (Dec C Ambient Temp) 27
Atmospheric Condition (KPA-750mm of Hg) 100
Humidity 60% - As per IS10002, ISO 3046
LP 1500GENERATOR SPECIFICATION
Power Rating (KVA) 1500
Electric Power (KWe) 1200
Rated Current (A) 2085
Output voltage (V) 415
Frequency (Hz) 50
Power factor (lag) 0.8
No of Phases 3
System Voltage (VDC) 24
Dimensions (L X W X H, mm x mm x mm) -
Open Set including panel stand & W/O Silencer (mm x mm x mm)
5300 x 2000 x 2800
ENGINE SPECIFICATION
Make Perkins UK
Model 4012TAG2A
Engine Output Prime Net (Kwm / bhp) 1267 / 1700
Engine Output Prime Gross (Kwm / bhp) 1309 / 1756
Aspiration Turbocharged charge-cooled
No of Cylinder 12 'Vee'
Page 19
Rated speed (RPM) 1500
Bore & stroke (mm x mm) 160 x 190
Compression ratio 13.6:1
Displacement (Litres) 45.84
Dry weight of Engine (kg) 6026
Exhaust Temperature (ºC) 490
Gross break mean effective pressure (kpa) 2260
Governor/class Electronic
Cooling system Water cooled
Radiator Cu Brass with Charge Air cooler
Lub oil specs 15 W 40 CF 4
Lub oil sump capacity Max (Litres) 159
Lub oil sump capacity Min (Litres) 136
Typical lub oil consumption (g/kwH) 0.52
Total coolant capacity (Litres) 210
System Voltage (DC) 24
Battery capacity/rating 180 AH, (12v DC x 4 Nos)
Fuel Consumption 75% (g/KWh) 202
Fuel Consumption 100% (g/kWh) 203
Fuel Consumption @ 75 % load with Fan & charging alternator (Lit/Hr)**
231
Fuel Consumption 100% (Lit/Hr) 309
** Fuel Consumption of Genset @75% of load is considering specific gravity of fuel 0.8355 at NTP
condition, Tolerance will be +5%
ALTERNATOR SPECIFICATION
Make Stamford*
Frame size/model No. P1734C1
Voltage regulation ± 0.5%
Class of insulation Class H
Page 20
Standard Enclosure IP 23
Winding Pitch 2/3
Telephonic Interference Factor Better than 50
Efficiency 95.5
Total Harmonic Factor Better Than 2%
SPECIFICATION FOR STANDARD MANUAL PANEL
Cubical type made of CRCA sheet, Powder coated, mounted inside canopy with hinged type doors
SWITCH GEAR 3pole MCB / MCCB
Controller used for start stop panel & MAN panel DSE 6010 & 6020
• Display
• Engine Parameters - RPM, Oil Presssure, coolant temprature Hour Meter, battery volt, running status
• Electrical parameters - Voltage, current, Hz, KW, KVA, Pf, kWh
Digital Multifunction meter Voltage/Ampere/Frequency
Fault Indication (LED Type on Engine safety Unit)
• Low Oil pressure
• Battery Charger Failure
• High Engine Temperature
• Low fuel level
Current Transformers of suitable rating
Indications (LED):
• DG ON
• Load on DG
Control Key switch for Start/Stop
SPECIFICATION FOR STANDARD AMF PANEL
Cubical type made of CRCA sheet, Powder coated, mounted inside canopy with hinged type doors
SWITCH GEAR • 4 Pole Contactor for DG
• 4 Pole Contactor for MAINS
Page 21
• MCCB for short circuit protection
Features
• Supports Engine equipped with electronic control unit
• Graphic back lit LCD Display
• Supervision of Mains and DG voltage
• Mains and DG contactor interlock
• Provision for Remote start / stop
• Over / under voltage protection
• Over / under frequency protection
• Current / voltage asymmetry
• Over current protection
• Parameter setting by front panel key board
• Auto / Manual mode operation
• Programmable parameters / timers
• Configurable input and outputs
• Alarm history
• Displays Voltage, Current, frequency, PF, kW, kWH
• Displays engine parameters like Oil pressure, coolant temperature, Engine RPM, fuel consumption, Engine running hours
• Indication LED for Mains ok, Load on Mains, DG set running, Load on Dg set
Multifunction meter • Voltage
• Ampere
• Frequency
Page 22
Analogue meter
• Oil pressure
• Water Temperature
• Engine RPM
Indication Lamps
• Mains On
• DG On
• Load on Mains
• Load on DG
SMPS based battery charger with float boost charging.
Manual mode controls
• DG start
• DG stop
• Load transfer
POWER RATING
Power rating as per Standard reference condition as per BS 5514/ISO 3046/ISO 8528
Reference condition (Dec C Ambient Temp) 27
Atmospheric Condition (KPA-750mm of Hg) 100
Humidity 60% - As per IS10002, ISO 3046
LP 2000
GENERATOR SPECIFICATION
Power Rating (KVA) 2000
Electric Power (KWe) 1600
Rated Current (A) 2780
Output voltage (V) 415
Frequency (Hz) 50
Power factor (lag) 0.8
No of Phases 3
System Voltage (VDC) 24
Page 23
Dimensions (L X W X H, mm x mm x mm) -
Open Set including panel stand & W/O Silencer (mm x mm x mm)
6150 x 2300 x 3800
ENGINE SPECIFICATION
Make Perkins UK
Model 4016TAG2A
Engine Output Prime Net (Kwm / bhp) 1715 / 2300
Engine Output Prime Gross (Kwm / bhp) 1766 / 2367
Aspiration Turbocharged charge-cooled
No of Cylinder 16 'Vee'
Rated speed (RPM) 1500
Bore & stroke (mm x mm) 160 x 190
Compression ratio 13.6:1
Displacement (Litres) 61.12
Dry weight of Engine (kg) 8010
Exhaust Temperature (ºC) 493
Gross break mean effective pressure (kpa) 2310
Governor/class Electronic
Cooling system Water cooled
Radiator Cu Brass with Charge Air cooler
Lub oil specs 15 W 40 CF 4
Lub oil sump capacity Max (Litres) 214
Lub oil sump capacity Min (Litres) 147
Typical lub oil consumption (g/kwH) 0.52
Total coolant capacity (Litres) 316
System Voltage (DC) 24
Battery capacity/rating 180 AH, (12v DC x 4 Nos)
Fuel Consumption 75% (g/KWh) 209
Page 24
Fuel Consumption 100% (g/kWh) 213
Fuel Consumption @ 75 % load with Fan & charging alternator (Lit/Hr)**
326
Fuel Consumption 100% (Lit/Hr) 447
** Fuel Consumption of Genset @75% of load is considering specific gravity of fuel 0.8355 at NTP
condition, Tolerance will be +5%
ALTERNATOR SPECIFICATION
Make Stamford*
Frame size/model No. PI734F1
Voltage regulation ± 0.5%
Class of insulation Class H
Standard Enclosure IP 23
Winding Pitch 2/3
Telephonic Interference Factor Better than 50
Efficiency 96
Total Harmonic Factor Better Than 2%
SPECIFICATION FOR STANDARD MANUAL PANEL
Cubical type made of CRCA sheet, Powder coated, mounted inside canopy with hinged type doors
SWITCH GEAR 3pole MCB / MCCB
Controller used for start stop panel & MAN panel DSE 6010 & 6020
• Display
• Engine Parameters - RPM, Oil Presssure, coolant temprature Hour Meter, battery volt, running status
• Electrical parameters - Voltage, current, Hz, KW, KVA, Pf, kWh
Digital Multifunction meter Voltage/Ampere/Frequency
Fault Indication (LED Type on Engine safety Unit) • Low Oil pressure
• Battery Charger Failure
• High Engine Temperature
Page 25
• Low fuel level
Current Transformers of suitable rating
Indications (LED):
• DG ON
• Load on DG
Control Key switch for Start/Stop
SPECIFICATION FOR STANDARD AMF PANEL
Cubical type made of CRCA sheet, Powder coated, mounted inside canopy with hinged type doors
SWITCH GEAR
• 4 Pole Contactor for DG
• 4 Pole Contactor for MAINS
• MCCB for short circuit protection
Features • Supports Engine equipped with electronic control unit
• Graphic back lit LCD Display
• Supervision of Mains and DG voltage
• Mains and DG contactor interlock
• Provision for Remote start / stop
• Over / under voltage protection
• Over / under frequency protection
• Current / voltage asymmetry
• Over current protection
• Parameter setting by front panel key board
• Auto / Manual mode operation
• Programmable parameters / timers
• Configurable input and outputs
• Alarm history
Page 26
• Displays Voltage, Current, frequency, PF, kW, kWH
• Displays engine parameters like Oil pressure, coolant temperature, Engine RPM, fuel consumption, Engine running hours
• Indication LED for Mains ok, Load on Mains, DG set running, Load on Dg set
Multifunction meter
• Voltage
• Ampere
• Frequency
Analogue meter
• Oil pressure
• Water Temperature
• Engine RPM
Indication Lamps
• Mains On
• DG On
• Load on Mains
• Load on DG
SMPS based battery charger with float boost charging.
Manual mode controls
• DG start
• DG stop
• Load transfer
POWER RATING
Power rating as per Standard reference condition as per BS 5514/ISO 3046/ISO 8528
Reference condition (Dec C Ambient Temp) 27
Atmospheric Condition (KPA-750mm of Hg) 100
Humidity 60% - As per IS10002, ISO 3046