Tampereen teknillinen yliopisto. Konstruktiotekniikan laitos. Tutkimusraportti 1 Tampere University of Technology. Department of Mechanics and Design. Research Report 1 Petri Pylsy & Timo KalemaConcepts for Low-Energy Single-Family Houses Heating Energy Use 50 100 150 200 Effect of thermal insulation, efficiency of heat recovery and air tightness on the use of heating energykWh/m 2 Water based floor heatingElectric radiatorsEnergy performance classes: A BC DTampereen teknillinen yliopisto. Konstruktiotekniikan laitos. Tampere 2008
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
The aim of this research is to find cost-effective low-energy house concepts, which can be
implemented in Nordic climate.
The cost-effective concepts for low-energy single-family houses include a good thermal
insulation and tightness of the envelope, an efficient heat recovery from exhaust air and an
efficient heating system. Heating energy need and use as well as delivered heating energy
and primary energy of heating are calculated for these different cases. The study shows
many economically feasible cases for low-energy single-family houses.
Increase of energy price, energy policy and the target of reduction of CO2- emissions in
the European Union will accelerate the motivation to build low energy houses also inindustrial level. This kind of research is giving some answers to find best concepts for
low-energy builders.
The research was conducted at Tampere University of Technology. The responsible
director was Prof. Timo Kalema. The research was done by M.Sc. Petri Pylsy.
2.1 Ways of expressing energy performance ............................................................. 7
2.2 Low energy houses and passive houses................................................................ 9
2.3 Demands on the component level....................................................................... 10
3 European low-energy houses...................................................................................... 11
4 Finnish low-energy house concepts............................................................................ 13
4.1 Target levels for heating energy use................................................................... 134.2 Exterior envelope, heat recovery and air tightness of the building.................... 13
4.3.3 Oil and wood pellet heating........................................................................ 20
5 Investment costs of low-energy houses ...................................................................... 22
5.1 Marginal costs of additional thermal insulation ................................................. 22
5.2 Investment costs for heat recovery and for tightness of the envelope................ 23
5.3 Investment costs for heating systems ................................................................. 246 Input data of calculations............................................................................................ 26
7 House Concepts with low energy consumption ......................................................... 29
7.1 Energy quantities analysed ................................................................................. 29
7.2 Concepts with low space heating energy need and heating energy use ............. 30
7.3 Concepts with low delivered heating energy...................................................... 32
7.4 Concepts with low primary energy consumption of heating.............................. 34
8 Costs savings due to energy saving measures ............................................................ 37
10 Interior temperatures of low energy houses ........................................................... 4911 Summary and Conclusions ..................................................................................... 53
1 INTRODUCTION The global warming and the aims to reduce carbon dioxide emissions have enthroned the
energy consumption as major issue. Also the rise in energy price is a very good reason totry to reduce heating energy consumption. European Union has set a target for CO2-
reduction as 20 % by the year 2020 when compared with the year 1990. This means that
also the energy efficiency of buildings must be improved and the heating energy
consumption has to be decreased by 20 %. Thus low-energy buildings are getting more
and more interesting options for constructors all over the Europe. (Panorama of Energy
2007, Kellner 2008)
There has been made a lot of studies about the energy efficiency of buildings. Most of
these studies are considering the heating energy need and how to reduce it. In this research
also different kind of heating systems are considered. Also unconventional heatingsystems, such as a window heating, and their suitability for low-energy houses is
discussed. The aim of this study is to find cost-effective low-energy house concepts, which
can be implemented in Nordic countries.
In this study it was created various combinations of thermal insulation of the exterior
envelope, efficiency of heat recovery from exhaust air, air tightness of the building’s
envelope and heating systems for a wooden-framed single-family house. The heating
energy need and the use as well as the delivered heating energy and primary energy
consumption of heating were calculated for these different cases. The energy performance
classes are calculated according to prEN 15217 (2005). Also the cost-effectiveness wasconsidered by calculating the additional investment costs and the total costs for a 30 years
period. Some sensitivity analyses were done for the length of the calculation period, the
increase of the energy prices, the real interest rate and the primary energy conversion
factors. Also an optimization of the thermal insulation of the exterior envelope was
studied. With these calculations the most cost-effective concepts for low-energy houses
could be found. Also the thermal comfort of the low energy house concepts were studied
by calculating duration curves for interior temperatures.
Heating energy calculations are made with DOF-Energy, which is based on the
calculation method of Finnish building regulations (Dof-Energy, The National BuildingCode of Finland D5 2007). The method of Finnish building regulations is based on the
standard SFS-EN 13790. Window heating and heat pumps were calculated according to
Ch. 4.3. Simulation program TASE was used to calculate interior temperatures. TASE is a
dynamic, multiroom model for energy analysis of buildings, but in this study only a one
room model is used. TASE was verified in the Annex 21 of International Energy Agency
(IEA). Optimization is made by MS Excel program Optix, in which the energy calculation
is based on SFS-EN 13790 and the optimisation on the Solver of Excel. The weather data
2 DEFINITIONS 2.1 Ways of expressing energy performance
There are many different ways to express the energy performance of buildings. The space
heating energy need Qn describes how good the thermal insulation of the exterior
envelope, the ventilation heat recovery and the air tightness of envelope are. The space
heating energy need is defined in Equation (2.1). (ISO/DIS 13790 2005)
GG Ln QQQ η −= (2.1)
nQ space heating energy need, [kWh]
LQ total heat loss, [kWh]
GQ total heat sources, [kWh]
Gη gain utilisation factor
The total heat loss includes heat conduction QT , infiltration Q x and ventilation Qv
v xT L QQQQ ++= (2.2)
Heat recovery is taken into account when the heat loss of ventilation Qv is calculated. Theair change rate of infiltration n x is calculated according to Finnish building regulations
(The National Building Code of Finland D5 2007):
25
50nn x = (2.3)
50n air change rate when pressure difference is 50 Pa, [h-1]
The total heat sources QG is
siG QQQ += (2.4)
iQ internal heat sources: people, lightning, electrical
appliancies and heating system, [kWh]
sQ solar radiation, [kWh]
The heating energy use Qu includes the space heating energy need Qn as well as the
domestic hot water heating energy need Q DHW and the heat losses of heating system Qhs
In this study the energy performance classes of the single-family houses studied are
based on the heating energy use (Eq. 2.5). The energy performance EP is equal to the
heating energy use per gross floor area:
Qu per gross floor area according to Eq. (2.6).
A
Q EP u=
(2.6)
A Gross floor area, [m2]
The energy performance criteria selected for this work describes the efficiency of the
building’s envelope and the heat recovery from ventilation air. It also takes into account
the heat losses of the heating system. However, it does not take into account the
generations efficiency of the heating system, e.g. the coefficient of performance of a heat
pump, and not the primary energy consumption. This selected method is according to the
present Finnish building regulations.
Two reference values are needed to define the energy performance classes according
to prEN 15217 (2005): Rr and Rs. Rr is a national building regulation reference and Rs is a
national building stock reference. The national building regulation reference is the heatingenergy use calculated with the reference values of present Finnish building regulations.
The building stock reference is the heating energy use reached by approximately 50 % of
the Finnish single-family houses. Table 2.1 presents the energy performance rating of
prEN 15217 (2005).
Table 2.1 Energy performance rating according to prEN 15217 (2005). In this study EP
is equal to the heating energy use Qu per gross floor area.
The delivered heating energy Qd is the total heating energy supplied into the building. It is
calculated by using the annual efficiency of the heat generation system ηhs (Eq. 2.7).
(prEN 15217, 2005)
hs
ud
QQ
η = (2.7)
The primary heating energy E p is calculated from the delivered heating energy using the
primary energy conversion factor f
d p fQ E = (2.8)
2.2 Low energy houses and passive houses
A definition of a low energy house is not unambiguous. There are different kinds of
definitions for low energy houses. The Finnish Association of Civil Engineers has defined
a low energy house having a space heating energy need less than 75 kWh/m 2 (RIL 216-
2001). The minimum energy house is defined having the space heating energy less than 25
kWh/m2. On the other hand in Switzerland it has been developed the Minenergi- concept
in which the space heating energy need is less than 35 kWh/m2 (Minenergi). In the Finnish
building regulations there is also definition for low energy houses: the total heat loss
should not be greater than 60 % of the reference heat loss calculated by the Finnishreference values for the thermal insulation and the efficiency of the heat recovery (The
National Building Codes of Finland C3 and D3, 2007).
German Passive House Institut has created a definition for passive houses. There are
three main criteria for passive houses: the space heating energy need, the total primary
energy consumption and the air tightness of envelope. First the space heating energy need
calculated per floor area must be less than 15 kWh/m2. Second the total primary energy
consumption including the electricity consumption of appliances must be less than 120
kWh/m2. Third the tightness of the envelope (n50- value) must be less than 0.6 h-1. (Passive
House Institut) The energy consumption of buildings generally and the German passivehouse definition can be evaluated by the fact that if a German low energy house situated in
the middle parts of Germany is moved to Middle-Finland, its space heating energy is
approximately doubled.
Technical Research Centre of Finland (VTT) has proposed a passive house definition
for the Finnish climate; the space heating energy need must be less than 20 … 30 kWh/m2
and the primary energy consumption less than 120 … 140 kWh/m2. The upper limits of
the definition are for Northern Finland and the lower limits for Southern Finland. The air
tightness of envelope is in VTT’s definition the same as that in the Passive House
In Scandinavia and in Germany, more low-energy houses have been built than in Finland
so far. Table 3.1 shows five examples of low-energy single-family houses and somedetails of them. There are examples from Denmark, Sweden, Norway, Germany and
Finland. There was a measured space heating energy consumption available only for the
Finnish low-energy house. This energy was 58 kWh/m2. In other cases only a calculated
annual space heating need was presented and this was from 10 to 15 kWh/m2. In
calculations local weather data were used.
U-values of exterior walls in these low-energy houses are between 0.09 W/m2K and
0.13 W/m2K in all examples. Thermal transmittances of the ceiling and the floor are from
0.07 to 0.10 W/m2K and from 0.08 to 0.15 W/m2K respectively. Also the U-values of
windows are very low, 0.8…1.0 W/m2K, except in the Finnish low-energy house. The air tightness of the envelope is not measured or measurement results published but only in
two cases: for a Danish and for the Finnish house. In the Danish house the n 50-value is
only 0.5 h-1 and in the Finnish one it is 1.5 h-1.
In all cases there is a ventilation system with a heat recovery from exhaust to supply
air. The efficiencies of the heat recovery are informed to be from 60 to 90 %. In low-
energy houses in Denmark and Norway the supply air is preheated by a ground coupled
heat exchanger. In all five cases the heating system or the heat distribution system is
different. The heat is distributed via supply air, water radiators or floor heating. The heat
generation is based on electric resistance, heat pump, district heating or boiler. Also solar collectors are used for heating of domestic hot water (DHW).
The energy performance classes (ratings) of the building concepts analysed are defined for
the heating energy use according to prEN 15217 (2005) (Table 2.1). This includes the
energy needs for space heating and hot water heating and the heat losses of technical
systems excluding the losses in heat generation. In this study the national building
regulation reference Rr is 160 kWh/m2 for electric heating. (The National Building Code
of Finland C3 2007 and D5 2007). The national building stock reference is estimated to be
230 kWh/m2. This estimation is calculated using for the walls, the ground floor, the ceiling
and the windows U-values 0.54 W/m2K, 0.29 W/m2K, 0.20 W/m2K and 2.0 W/m2K
respectively. These values approximately correspond to insulation thickness of 70 mm, 50
mm and 200 mm for the exterior walls, the ground floor and the ceiling respectively.
Windows are assumed to be triple glazed. The ventilation system is assumed to be a
natural ventilation and its air change rate is 0.3 h -1. It is assumed that the domestic hot
water heating energy need and the heat losses of heating systems are the same as in the
building reference value Rr .
Table 4.1 Energy performance classes based on heating energy use (prEN 15217 2005)
Heating energy use, [kWh/m2] Energy performance class
EP< 80 A
80 ≤ EP < 160 B
160 ≤ EP < 190 C
190 ≤ EP < 215 D
215 ≤ EP < 270 E
270 ≤ EP < 320 F
EP ≥ 320 G
4.2 Exterior envelope, heat recovery and air tightness of the
building
Four different exterior envelopes (Cases) have been defined for this study; Cases 1, 2, 3
and 4. Their U-values and solar transmission coefficients of windows are shown in Table
4.2 for each case. In Case 1 for the envelope and for the heat recovery system of
ventilation references values of the Finnish building regulation have been used (Table
2.1). Case 4 is the most energy efficient case in which the U-values of the exterior envelope fulfil the common practice of passive houses. Cases 2 and 3 are between Cases 1
replaces a typical mechanical supply and exhaust air equipment with heat recovery. The
heat distribution system is a water based floor heating.
The heat effect of the condenser of an exhaust air heat pump can be calculated by
Eq. (4.2):
cQ&
( )211
hhV Q EHP
EHPc −
−= ρ ε
ε && (4.2)
EHPε coefficient of performance of exhaust air pump
V & exhaust air flow, [m3/s]
ρ density of exhaust air, [kg/m3]
1h enthalpy of exhaust air before evaporator, [kJ/kg]
2h enthalpy of exhaust air after evaporator, [kJ/kg]
Enthalpies in Eq. (4.2) can be read from the Mollier diagram when the temperatures of
exhaust air are known before and after the evaporator as well as the relative humidity of
air before and after the evaporator. The temperature of the exhaust air after the evaporator
is approximately 2...8 °C depending on the dimensioning (Alasimonen 2008). The
coefficient of performance of an exhaust air pump is 2…2.2 according to the Finnish
Association of Heat pumps (SULPU).
In this study the condenser effect of the exhaust air heat pump is assumed to be
constant during the whole year. It is also assumed that the temperature before theevaporator is the same as the interior temperature 21 °C and that after the evaporator 2 °C.
The relative humidity of indoor air is 30 %, that after the evaporator 100 %. Enthalpies
corresponding these temperatures are 33 kJ/kg and 11 kJ/kg before and after the
evaporator respectively. When the exhaust air flow is 0.047 m
cQ&
3/s and the coefficient of
performance of the heat pump is 2.2 the condenser effect is about 2.3 kW.cQ&
The delivered heating energy of the exhaust air pump Qd,EHP is calculated monthly by
Eq. (4.3) depending on if the average condenser effect Qc is lower or higher than the
average heating energy use Qu:
⎪⎪
⎩
⎪⎪
⎨
⎧
<
≥+−
=
cu
EHP
u
cu
EHP
c
cu
EHPd
QQwhenQ
QQwhenQ
QQ
Q
,
,
,
ε
ε (4.3)
The energy use for heating for the exhaust air heat pump is calculated with the annual
efficiency of heat recovery as 0 %, because in this case there is no separate plate heat
AHPε coefficient of performance of air-to-air heat pump
saQ energy need for heating supply air in rooms, [kWh]
sr Q energy need for heating supply air to set point temperature, [kWh]
V & mechanical ventilation air flow rate, [m3/s]
a ρ density of air, [kg/m3]
a pc , specific heat capacity of air, [J/kgK]
iT interior temperature, [°C]
set T temperature of supply air, [°C]
HRC T temperature of supply air after heat recovery, [°C]
The delivered energy of the exterior-air-to-air heat pump Qd,AHP is calculated using
monthly duration curves for the exterior air temperature. These duration curves are
obtained from the Finnish building regulations (The National Building Code of Finland
D5 2007).
4.3.3 Oil and wood pellet heating
Oil and wood pellet heating have a lot of similarities: In both systems a boiler, a burner, a
chimney, a fuel storage and control devices are needed. In practise there are differences
between the oil and the wood pellet heating. Due to different kind of fuels the burners are
different. Oil can be stored into an oil tank but for the wood pellet system a storage silo or
an own storage room is needed. In addition the wood pellet heating needs a conveyor to
transport wood pellets from the storage to the burner.
In this study the oil and the wood pellet heating have as the heat distribution systemthe water based floor heating. For oil heating the annual heat generation efficiency is 85 %
Table 5.2 Investment cost of the heat recovery system from exhaust air to supply air
(LVI-Dahl)
Annual efficiency of the heat recovery Investment cost€
30 % 1100
55 % 1500
70 % 1900
5.3 Investment costs for heating systems
A heating system affects noticeable on the total investment costs (Table 5.3). An electric
radiator heating with a hot water heater is the most inexpensive option. Also a windowheating with a hot water heater is at same cost level as electric radiator heating if the
window-area is about 16 m2. A heat pump using a drilled well as a heat source is the most
expensive heating system. The combination of electric radiator heating and an exterior air-
to-air heat pump needs a separate hot water heater. District heating, exhaust air heat pump,
drilled well heat pump, wood pellet heating and oil heating systems use a water based
floor heating as the heat distribution system in this study.
Table 5.3 Investment and service costs of various heating systems (Motiva, Nibe Haato,
Saukko 2007, Helsinki Energy)
System Investment costService cost over a
30 years period
€ €
Electric radiators 2700 100
District heating 6300...6400 800
Electric radiators + air-to-air heat pump 5300 1200
The simplified floor plan of the 130 m2 single-family house, which is used in calculations,
is shown in Figure 6.1. The house is a wooden-framed building with a concrete groundfloor slab. The thermal capacity of the house is 27 Wh/m 3K. The areas of the exterior
envelope are shown in Table 6.1. The window area is 12 % from the floor area. The room
height is 2.6 m and the indoor volume 340 m3. The house is located in Helsinki and
therefore weather data of Helsinki is used (Appendix 1). The interior temperature of
calculations is 21 °C.
15584
8384
N
S
EW
Figure 6.1 Simplified floor plan for calculations
Table 6.1 Areas of the exterior envelope in various directions
Exterior
wall
Ground
FloorCeiling Windows
Exterior
doors
m2
m2
m2
m2
m2
North 32.4 6.0 2.1
East 20.8 1.1 0.0South 30.3 8.3 1.9
West 21.4 0.4 0.0
Total 104.9 130.7 130.7 15.8 4.0
The angle from the building to the surrounding buildings and environment is 15°. The
curtain factor is 0.3 from May to September and 1.0 the rest of the year. There are four
cases (Cases 1 – 4) for the thermal insulation level of the exterior envelope (Table 4.2) and
four cases for the air tightness (IF1 – IF4, Table 4.4). The heating energy need is also
influenced by the efficiency of heat recovery, for which three values have been used
(Table 4.3). The specific transmission heat losses and gross floor areas are represented in
Table 6.2.
Table 6.2 Specific transmission heat losses of the envelopes and the gross floor areas
for various levels of thermal insulation
Level of thermal insulationQuantity Unit
Case 1 Case 2 Case 3 Case 4
Specific heat loss of
the envelope
W/K 104 86 62 51
Gross floor area m2 142 145 151 155
The specific transmission heat loss of the best insulated Case 4 is only about 50 % of the
corresponding heat loss of Case 1, which is according to the present Finnish buildingregulations. The increase of the insulation thickness of exterior walls also increases the
gross floor area calculated according to the outer dimensions.
The building is equipped with a balanced mechanical supply and exhaust ventilation
system. The mechanical ventilation air flow rate is 47 dm3/s. The temperature of supply air
is 18 °C during the heating season. The annual efficiencies of heat recovery systems are 30
– 70 % (Table 4.3).
It is assumed that a four persons’ family is living in the single-family house. The number
of inhabitants is taken into account in the internal heat gains as well as in the consumption
of domestic hot water which is 200 dm3/day. The average internal heat gains calculated per floor area are 7 W/m2 including the heat gains from the inhabitants, electric devices
and the heating system. assumed to be
The heat losses of space heating systems are shown in Table 6.3 for the Cases 1 - 4 of
the envelope’s thermal insulation. For the Cases 1 and 2 the heat losses are according to
the present Finnish building regulation (The National Building Code of Finland D5 2007).
For the Cases 3 and 4 the heat losses of the space heating system are reduced due to a
better thermal insulation of the building’s envelope, in which case the supplied heat and
size of the heat distribution system are smaller and the temperature level lower.
Table 6.3 The heat losses of heating system for chosen exterior envelopes
The analyses have been made for four different energy quantities, which describe various
views of energy consumption:
Space heating energy need
The space heating energy need is the net energy for space heating, which must be
transferred from the heat distribution system into rooms. In this study the heat distributionsystems have been radiator heating and floor heating. Other heat distribution systems are
e.g. ceiling heating and air heating.
The space heating energy need describes the efficiency of the thermal insulation of the
envelope, that of the heat recovery and the tightness of the building’s envelope. This
energy describes somehow the permanent energy consumption level.
Heating energy use
The heating energy use is obtained by adding the distribution heat losses to the spaceheating and the hot water heating energy needs. This takes into account also the efficiency
of heat distribution. From the systems studied in this work, the electric radiator heating has
the lowest distribution losses and the water based floor heating the highest. The
distribution heat losses are calculated utilising the Finnish Building Regulations.
Delivered heating energy
The delivered heating energy is the space and hot water heating energy use divided by the
generation efficiency. The delivered heating energy is also the purchased heating energyand it determines the energy costs. Heat pump systems having a high coefficient of
performance have lowest values of delivered energy. The delivered heating energy
describes well the efficiency of heat generation.
Primary energy consumption of heating
The primary energy consumption of heating describes in one way together with the CO2-
emissions environmental effects of heating. This is calculated from the delivered heating
energy using the primary energy conversion factors of Table 6.4. Usually electricity has
the highest primary energy conversion factor (in this study 2.5) and biofuels the lowest (in
this study for the pellet 0.12).
7.2 Concepts with low space heating energy need and heating
energy use
Figures 7.1 and 7.2 present the space the energy need and the heating energy use for
different alternatives of thermal insulation of the envelope (Cases 1 – 4), for the efficiency
of the heat recovery from the exhaust air (30 – 70 %) and for the air tightness of the
envelope (0.6 – 4 1/h). Figure 7.2 also presents the energy performance classes (energy
performance ratings) according to Table 2.1. For the Case 1, in which the efficiency of the
heat recovery is 30 % and the tightness of the envelope 4.0 h-1, the space heating energy
need is the highest; 99 kWh/m2. This case corresponds a building, which just fulfils the present reference values of Finnish building regulations concerning the thermal insulation
of the envelope and the efficiency of heat recovery.
The lowest space heating energy need of the cases studied is 19 kWh/m2. This energy
consumption is reached using the exterior envelope of Case 4, the efficiency of heat
recovery of 70 % and the air tightness of the envelope of 0.6 h-1. These values correspond
to the common practice of passive houses excluding the efficiency of the heat recovery,
which is higher for the passive houses. Hence the criteria for a passive house of the
Passive House Institut for space heating energy need 15 kWh/m2 can not be fulfilled by
any of our cases. To fulfil the criteria of the Minenergi - concept the exterior envelope of Case 4 as well as the efficiency of heat recovery of 55 % are required.
When the level of thermal insulation is improved from the basic case (Case 1) to the
best case (Case 4), the space heating energy need is reduced by about 50 kWh/m2. An
increase in the efficiency of the heat recovery from 30 % to 70 % reduces the space
heating energy need approximately by 20 kWh/m2. A better air tightness decreases the
space heating energy need from 10 to 15 kWh/m2 when the n50-value is reduced from 4.0
to 0.6 h-1. Thus, from the individual energy saving methods of our study the effect of the
envelope’s thermal insulation is highest. Its effect is approximately a double compared
with those of the heat recovery and the tightness of the envelope.The heating energy use for the electric radiator system varies from 55 to 158
kWh/m2. For the water based floor heating system the heating energy use is slightly
higher, 63 - 182 kWh/m2, due to higher heat distribution losses. The heat distribution
losses are 10 - 29 kWh/m2 for the electric radiator system and 20 - 53 kWh/m2 for the
water based floor heating system.
When the thermal insulation of the envelope, the efficiency of the heat recovery and
the air tightness of the envelope are according to the reference values of Finnish building
regulations, the energy performance classes B and C are achieved by electric radiator and
water based floor heating systems. If the energy performance class A is wanted to achieve,the thermal insulation of the envelope should be according to Cases 3 or 4 and the
The delivered or the purchased heating energy includes the space and the hot water
heating energy use and the heat generation efficiency. In this study the domestic hot water
heating energy need is 4260 kWh which is about 30 kWh/m2. Values for the deliveredheating energy for various cases of thermal insulation and air tightness of the envelope and
efficiency of the heat recovery are shown in Figures 7.3 - 7.5. Figure 7.3 presents results
for electric radiator, window and district heating systems, Figure 7.4 the corresponding
results for all heat pump systems and Figure 7.5 for fuel heating systems.
Heat pump systems have the lowest delivered energy consumptions due to their high
coefficients of performance and heat generation systems using fuels (oil, pellet) the
highest consumptions due to their low heat generation efficiencies. The lowest delivered
heating energy of the heat pump utilising a drilled well as a heat source is 25 kWh/m2 and
correspondingly the highest delivered energy for the wood pellet heating 228 kWh/m2.
The delivered heating energy of the electric radiator heating system and the district
heating system are equal due to the fact the generation efficiency of both systems is the
same (100 %).
Window heating increases slightly the delivered heating energy compared with the
electric radiator heating due to higher heat losses in windows. For Cases 1 and 2 the
increase of the delivered heating energy is 10 - 13 kWh/m2 and 7 - 10 kWh/m2
respectively (calculated per floor area). For Cases 3 and 4 this increase is only 2 - 4
kWh/m2 or 1 - 2 kWh/m2 correspondingly. Thus there is no significant difference in the
delivered heating energy between the window heating and the electric radiator heating
when the exterior envelope is well insulated (according to Case 4).
The delivered heating energy varies from 50 to 127 kWh/m2 when the exterior air-to-
air heat pump is used. The use of this heat pump decreases the delivered heating energy by
approximately 9 - 20 % compared with the electric radiator heating. The energy saving
effect of an exterior air-to-air heat pump is reduced when the total heat losses are
decreased.
The delivered heating energy of an exhaust air heat pump is between 49 to 133
kWh/m2. The use of an exhaust air heat pump decreases the delivered heating energy by
approximately 10 - 16 % compared with the electric radiator heating. The delivered
heating energy of the exhaust air pump is smaller than that of the exterior air-to-air heat
pump for the well-insulated envelopes (Cases 3 and 4). The reason for this is that the
exhaust air heat pump is capable to heat effectively also in wintertime, if the transmission
heat loss is small due to a good thermal insulation.
When the drilled well heat pump is used, the delivered heating energy is between 25
kWh/m2 and 73 kWh/m2. The delivered heating energy can be reduced by 60 % or 54 %
using the drilled well heat pump compared with the district heating and the electric
radiator heating systems. However, the absolute saving in heating energy by using the
drilled well heat pump is reduced when the heating energy use is reduced.
Cost effects of optimising the thermal insulation of the building’s envelope is studied
for the thermal insulation levels Case 3 and 4. In these analysis electric radiator, districtand drilled well heat pump heating have been used. The reference case of these
calculations is the electric radiator heating in a building fulfilling the minimum demands
Finnish building regulations (envelope Case 1, efficiency of heat recovery 30 % and
tightness of the envelope 4 1/h). Also a sensitivity analysis for the primary energy
conversion factors and for the measurements used in calculations (interior or intermediate)
has been done.
Figure 9.1 shows the heating primary energy consumption when the primary energy
factors are according to DIN 4701-10 (2001). The primary energy factor for electricity is
in DIN 4701-10 (2001) about 20 % greater than in that of Helsinki Energy (HelsinkiEnergy: Primary energy factors) and the primary energy factor for district heating is about
55 % greater correspondingly. This difference is naturally due to differences in fuels and
structures of the energy production. For all three heating systems mentioned above district
heating has clearly the smallest primary energy consumption and electric heating the
highest.
Instead of fixing arbitraly the U-values of the exterior envelopes of Case 2 – 3 they can
be optimised (Kalema) so, that a certain energy consumption level is obtained with
minimum costs. In principle this means that for heating systems having a high
performance, such as the drilled well heat pump, a less insulated envelope than buildingshaving a poorer heating system is optimal. Also the optimisation solves the problem how
to ideally distribute the thermal insulation between the exterior walls, the floor, the ceiling
and the windows for a certain level of delivered energy.
Figures 9.2 and 9.3 show the results of an optimisation for the thermal insulation level
of the envelope. The optimisation is made keeping the Cases 3 and 4 of the envelope’s
thermal insulation as a starting point so, that the delivered space heating energy is kept
constant, either 25 kWh/m2 or 19 kWh/m2 for Cases 3 and Case 4 respectively. The
efficiency of heat recovery is 70 % and the air tightness of the envelope 0.6 h-1 for all
optimization cases. Other constraints in the optimisation are the minimum U-values for thecomponents of the exterior envelope: exterior walls and the ground floor 0.07 W/m2K, the
ceiling 0.06 W/m2K and the windows 0.85 W/m2K. Approximately 1500 – 10 000 € extra
savings can be achieved by optimisating the envelope. A building in which a drilled well
heat pump is used gives now biggest savings because in it a poorly insulated envelope can
be used.
When the insulation thicknesses are high the difference between in the inner,
intermediate and the exterior dimensions of the structures are high. The transmission heat
losses of this study have been calculated using the interior dimensions, which are constant.
The most right way would be to use intermediate dimensions in calculations, whichchange when the insulation thicknesses change.
The increase of heating energy prices and the general concern of the global warminghave made low energy houses a very interesting option for house builders and
constructors. Also the national and the EU’s energy policy will accelerate the motivation
to build low energy houses. In order to somehow realise these very general goals the
purpose of this study was to find out cost-effective concepts for low energy houses in
Nordic climate. These concepts include the thermal insulation and the air tightness of the
building’s envelope, the effectiveness of the heat recovery from exhaust air and the
heating system.
Four different thermal insulation levels are used in this research: The worst case (Case
1) is according to the reference values of Finnish building regulations and the best case(Case 4) is according to the common practice of passive houses. Three values are used for
the efficiency of heat recovery (30, 55 and 70 %) and four values for the air tightness (n 50)
of the envelope (0.6, 1.0, 2.0 to 4.0 h-1). Eight heating systems having different energy
performance and energy price are studied: Electric radiator heating, which is usually the
basic case for comparisons, district heating, oil heating, wood pellet heating, exterior air-
to-air heat pump, exhaust air heat pump, drilled well heat pump and window heating as a
non-conventional heating system.
For the energy analysis of the concepts four energy quantities have been used in order
take into account the various aspects of energy consumption: Space heating energy need,space heating energy use, delivered heating energy and primary energy consumption of
heating. The first one describes the thermal properties of the building’s envelope, the
second takes into account also the distribution heat losses, the third one takes into account
also the heat generation efficiency and also affects directly on the energy costs and the last
one describes the environmental effects of the energy consumption.
Also the investment and energy costs for the concepts have been analysed and on the
basis of these analysis the profitability of various energy saving methods have been
estimated. The cost-effectiveness is considered using the present values of total costs for a
30 years period. The reference case of calculations is Case 1 building just fulfilling the present Finnish building regulations on the thermal insulation, the tightness of the
envelope and the efficiency of heat recovery and having an electric radiator heating.
Heating energy calculations are made by Dof-Energy and interior temperatures are
simulated by TASE. Weather data of Helsinki is used in calculations.
The space heating energy need varies between 19 kWh/m2 and 99 kWh/m2 for the
concepts studied. This means that the criteria for a passive house (space heating energy
need less than 15 kWh/m2) is not fulfilled. The space heating energy need can be reduced
by 50 kWh/m2, when the thermal insulation of the envelope is improved from reference
values of Finnish building regulations the best level of our study, which approximatelycorresponds to the common practice of the thermal insulation of passive houses. If the
ISO/DIS 13790. 2005. Thermal performance of buildings: Calculation of energy use for space heating and cooling. 98 pp.
Isover pricelista/product catalogue 1.5.2007. Hyvinkää, Saint-Gobain Isover Oy. 35 pp.
Janson, U. 2008. Experiences from three Swedish passive house projects. Passivhus
Norden 2008- conference 2.-4.2008, Trondheim. Conference proceedings. 15-21 pp.
Jokiranta, K. Kurnitski, J. Palonen, J. 2001. Sähkölasilämmityksen käyttäminen
lämpöolojen hallintaan lasijulkisivujen yhteydessä. Espoo, Helsinki University of Technology. 100 pp. (In Finnish)
Kalema, T., Optimisation of the thermal performance of buildings – The OPTIX program.Int. Journal of Low Energy and Sustainable Buildings, Vol 2, 2001 – 2002.http://www.ce.kth.se/bim/leas/
Kellner, K. 2008. Energy Policy of Europe: Action Plan 2007-2009. Passivhus Norden
Pellettikirja: Ajatuksia ja ohjeita taloudelliseen puulämmitykseen. 2006. Jyväskylä, Vapo
Oy. 68 pp. (In Finnish)
Rakennusosien kustannuksia 2006. 2006. Helsinki, Rakennustieto. (In Finnish)
Reijonen, P. 2007. Properties, prices and U-values of various window glasses. Vantaa,
Finnglass. Unpublished memo.
RIL 216-2001. 2001. Rakenteiden elinkaaritekniikka. Helsinki, Finnish Association of
Civil Engineers. 301 pp. (In Finnish)
Rose, J. Svendsen, S. 2005. Classification of low energy houses in Danish buildingregulation [pdf]. http://www.byv.kth.se/avd/byte/reykjavik/pdf/ art_051.pdf
Ruuskanen, A. Kalema, T. 1994. Electrically heated window – Effects on energy
consumption and interior thermal comfort. Vantaa, Imatran voima Oy. 62 pp. (In Finnish)