Some Faults
Are Easy
to Find
Page 3
Flashed Insulators Are Hard to Find
Page 4
Accurately Locate Faults With
Traveling Waves
For a fault at 38.16 miles
Method Distance (miles) Difference (miles)
Impedance 34.03 4.13
Traveling wave (TW) 37.98 0.18
Page 5
Estimate Location From Current
Set 1 3 5 10 15 20
Measured 0.97 3.00 4.7 10 14 20
Not bad for 77 years!!!
“JM Drop” circa 1936
Adheres to Standard
SIS 12 AWG/10-32/5A
Quick Test, 2013
Page 6
Estimate Location From Impedance
VS
m 1 – mVR
IFIS IR
Line Impedance = ZL
Page 7
Impedance-Based Methods
• Widely available in line relays today
• No communications required, but need
voltages and currents
• Transients: faster relays and breakers
• Series compensation, mutual coupling,
transposition
• CCVT accuracy and transient response
Page 8
L Rm ℓ – m
2m
m
3m2(ℓ – m)
Faults Launch Traveling Waves
Page 9
Currents and Bewley Lattice Diagram BG Fault, June 04, 2013
Mic
rose
co
nd
s
-20 0 20 40 60
Goshen B
(A)
0 20 40 60 80 100
km-10 0 10
0
100
200
300
400
500
600
700
800
900
1000
Drummond B
(A)
Page 10
Two-End TWFL Method
L R
m
BECKY BECKY
tL tR
L R
1m t – t v
2 l
Page 11
Automatic Fault Locator (BPA, 1972)
L R
Counter
Start
Stop
Microwave
Receiver
Microwave
Transmitter
Master Terminal Remote Terminal
Wave L Wave R
TW Processing
Unit
TW Processing
Unit
Page 12
Practical Considerations
• CTs are pretty “hi-fi”, bandwidth > 100 kHz
• CCVTs are not, except at the capacitive
voltage divider tap, but that means new
cabling
• Use currents and two-end method
• Fit naturally in current differential relays
• Re-use same communications channel
Page 13
Nature of Traveling Waves
• Lightning surges coupling onto line
• Wave launched by fault
• Reflections from discontinuities
• “Messy” electrical breakdown
• Can’t expect “textbook” waveshapes
Page 14
340 360 380 400 420 440 460–500
–400
–300
–200
–100
0
100
200
300
400
500C
urr
en
t (A
)
Time (μs)
Clean Breakdown: CG Fault
Page 15
340 360 380 400 420 440 460
–600
–400
–200
0
200
400
600
Cu
rre
nt (A
)
Time (μs)
Precursory Waves: Shield Coupling??
Precursory
Waves Main Flashover
Wave
Page 16
TW Fault Locator Design Concept
• Filter and sample currents
• Isolate desired mode
• Accurately measure time of arrival
• Exchange with other end, over same 87L
channel
• Calculate location using two-end equation
• Save data
Page 17
370 372 374 376 378 380 382 384
100
200
300
400
Cu
rre
nt (A
)
Time (μs)
Large Uncertainty
(2 μs = 600 m)
0
Simple Threshold Won’t Work
Page 18
Differentiator-Smoother Works Great Borrowed Idea From “Leading Edge Tracking”
t
di/dt
ta
t
i
i(t)is(t)
di/dt
Current Arrival
Timei(t) is(t)ta
di/dt
d/dtSmoother
(LPF)
DifferentiatorTime-of-
Peak
Estimator
Interpolate to
50 ns accuracy
Page 19
Relative Accuracy ~ 50 ns
Mean Error = 17 ns or 8′
Standard Deviation = 32 ns or 16′
R1 t1
R2 t2
Clock Dt = t1 – t2
Page 20
87L and TWFL Share 64 kb/s Channel
87L87L and TWFL
64 kb/s
network or point-to-point
87L
Wide-Area Time Reference (Network or GPS)
(for TWFL only)
Page 21
BPA Experience – 161 kV Line
DS1 Microwave Link
SEL-411L
SEL
SEL-411L
SEL
Page 22
Gunshot Phase Currents at Goshen and Drummond
Goshen Terminal
200
100
0
–100
Curr
en
t
36.832647 36.832697 36.832747
40
20
0
–20
Curr
en
t
36.832647 36.832697 36.832747
–40
Drummond Terminal
Page 23
“We Know Where Your Faults Are”
Nature of Fault Line Patrol (miles) TW (miles)
Flashover 67.91 68.19
Lead projectile 38.16 37.98
Lightning 66.86 67.25
Flashover 61.50 61.42
Flashover 50.18 50.56
Flashover 59.04 59.04
Accuracy within one to two tower spans
Page 24
BG Fault Located at 62/10…Irrigation
Closest
Tower
Page 25
BPA Experience – Tapped Lines
Red
mon
d
Bra
sada
Bro
ther
s Tap
Har
ney
Yew
Ave
. Tap
Ham
pton
Tap
Rile
y Tap
Page 26
Line Patrol – It Was Like
“Chasing Ghosts on This Line”
Nature of Fault Line Patrol (miles) TW (miles)
Flashover 36.65 36.33
Flashover 36.65 36.76
Flashover 6.92 6.92*
Flashover 91.62 91.76
Flashover 4.94 4.94*
Bird waste 47.1 47.35
*Single-ended fault location
Accuracy within one to two tower spans
Page 27
Line Patrol Found These
Flashed Insulators
Page 28
Summary of Typical Errors
Relay Error 50 ns 25′
Timing (clock) 50 ns 25′
Line Length (0.1% of 100 mi) 500′
Speed 0.05% 250′
Allowance for other errors 250′
…on the order of one span
Page 29
Traveling Wave Fault Locator
• Fits “hand-in-glove” into differential relay
• Easy to set up and use
• Not affected by series caps, mutual
coupling, or very fast clearing
• Complements impedance methods
• Adds to our understanding of lines
Page 30
TWFL on Cables In Service on 345 kV Underground Cables
Page 31
Waves Propagate Slower in
Underground Cables
Wave Velocity = 0.48 Times Speed of Light