“Ratron” Loading Transformers Beyond Nameplate Rating
23

Loading Power Transformers Beyond Nameplate Ratings(1)

Apr 03, 2018

Download

Documents

Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: Loading Power Transformers Beyond Nameplate Ratings(1)

7/28/2019 Loading Power Transformers Beyond Nameplate Ratings(1)

http://slidepdf.com/reader/full/loading-power-transformers-beyond-nameplate-ratings1 1/23

“Ratron” 

Loading Transformers Beyond

Nameplate Rating

Page 2: Loading Power Transformers Beyond Nameplate Ratings(1)

7/28/2019 Loading Power Transformers Beyond Nameplate Ratings(1)

http://slidepdf.com/reader/full/loading-power-transformers-beyond-nameplate-ratings1 2/23

Outline

• Background

• IEEE C57.91-1995• Calculations

• Benefits and Applications

• Conclusions

Page 3: Loading Power Transformers Beyond Nameplate Ratings(1)

7/28/2019 Loading Power Transformers Beyond Nameplate Ratings(1)

http://slidepdf.com/reader/full/loading-power-transformers-beyond-nameplate-ratings1 3/23

• Background

 – Most utilities limit their transformers to

nameplate ratings

 – Emergency ratings do not exist

 – Usually a rating philosophy is not in place

 – Settings of overload relays is inaccurate

 – Dispatchers reroute loads or load shed

costumers

Page 4: Loading Power Transformers Beyond Nameplate Ratings(1)

7/28/2019 Loading Power Transformers Beyond Nameplate Ratings(1)

http://slidepdf.com/reader/full/loading-power-transformers-beyond-nameplate-ratings1 4/23

 – IEEE Guide for Loading Mineral-Oil-Immerse

transformers (Std C57.91-1995)

• Transformers can be loaded beyond nameplate

ratings during critical conditions and peak hours• Offers a method to calculate continuous, long term

emergency and short term emergency ratings

• Offers a method to calculate the loss of life of the

transformer 

Page 5: Loading Power Transformers Beyond Nameplate Ratings(1)

7/28/2019 Loading Power Transformers Beyond Nameplate Ratings(1)

http://slidepdf.com/reader/full/loading-power-transformers-beyond-nameplate-ratings1 5/23

• Using the IEEE C57.91 standard to

calculate:

 – Normal loading

 – Long term emergency

 – Short term emergency

 – Loss of life

Page 6: Loading Power Transformers Beyond Nameplate Ratings(1)

7/28/2019 Loading Power Transformers Beyond Nameplate Ratings(1)

http://slidepdf.com/reader/full/loading-power-transformers-beyond-nameplate-ratings1 6/23

• Normal Life expectancy loading

 – This results when the transformer is operated

continuously at a hottest spot conductor 

temperature of 110 deg C

 – The standard allows a maximum temperature

of 120 deg C only if the transformer has

operated below 110 deg C for longer periodsof time

Page 7: Loading Power Transformers Beyond Nameplate Ratings(1)

7/28/2019 Loading Power Transformers Beyond Nameplate Ratings(1)

http://slidepdf.com/reader/full/loading-power-transformers-beyond-nameplate-ratings1 7/23

• Planned Loading Beyond Nameplate

Rating

 – Transformers that do not work at a continuous

temperature of 110 deg C, can be loaded to a

maximum temperature of 120-130 deg

 – Loss of insulation life should be considered on

the length of time at this temperature

Page 8: Loading Power Transformers Beyond Nameplate Ratings(1)

7/28/2019 Loading Power Transformers Beyond Nameplate Ratings(1)

http://slidepdf.com/reader/full/loading-power-transformers-beyond-nameplate-ratings1 8/23

• Long Term Emergency Loading

 – During contingency conditions, transformers

hottest spot conductor temperature can reach

120-140 deg C

 – Time will depend on loss of life

 – It is expected that such occurrences happen

only 2-3 times during the life of thetransformer 

Page 9: Loading Power Transformers Beyond Nameplate Ratings(1)

7/28/2019 Loading Power Transformers Beyond Nameplate Ratings(1)

http://slidepdf.com/reader/full/loading-power-transformers-beyond-nameplate-ratings1 9/23

• Short Term Emergency Loadings

 – During second or third contingency problems,

the transformer can be allowed to reach a

maximum hot-spot conductor temperature of 

180 deg C

 – Maximum time of 2-3 hours and an

occurrence of once or twice during the life of the transformer 

Page 10: Loading Power Transformers Beyond Nameplate Ratings(1)

7/28/2019 Loading Power Transformers Beyond Nameplate Ratings(1)

http://slidepdf.com/reader/full/loading-power-transformers-beyond-nameplate-ratings1 10/23

• Calculations with Ratron:

 – Using the standard to calculate transformer 

ratings can be time consuming and difficult

 – Ratron makes it easier for the user to input

data he is familiar with and data that is

available to him

Page 11: Loading Power Transformers Beyond Nameplate Ratings(1)

7/28/2019 Loading Power Transformers Beyond Nameplate Ratings(1)

http://slidepdf.com/reader/full/loading-power-transformers-beyond-nameplate-ratings1 11/23

• Data Required

 – Top-Oil temperature rise above ambient (test

report)

 – Winding average temperature above ambient

(nameplate 65 or 55deg C) (nameplate)

 – Tank radiator oil capacity (nameplate)

 – Tank and fittings weight (nameplate)

 – Cooling mode (FOA,OA, FA) (nameplate)

 – Load and no load losses (test report)

Page 12: Loading Power Transformers Beyond Nameplate Ratings(1)

7/28/2019 Loading Power Transformers Beyond Nameplate Ratings(1)

http://slidepdf.com/reader/full/loading-power-transformers-beyond-nameplate-ratings1 12/23

 

Input Tab

Page 13: Loading Power Transformers Beyond Nameplate Ratings(1)

7/28/2019 Loading Power Transformers Beyond Nameplate Ratings(1)

http://slidepdf.com/reader/full/loading-power-transformers-beyond-nameplate-ratings1 13/23

Page 14: Loading Power Transformers Beyond Nameplate Ratings(1)

7/28/2019 Loading Power Transformers Beyond Nameplate Ratings(1)

http://slidepdf.com/reader/full/loading-power-transformers-beyond-nameplate-ratings1 14/23

 

Results

Page 15: Loading Power Transformers Beyond Nameplate Ratings(1)

7/28/2019 Loading Power Transformers Beyond Nameplate Ratings(1)

http://slidepdf.com/reader/full/loading-power-transformers-beyond-nameplate-ratings1 15/23

Page 16: Loading Power Transformers Beyond Nameplate Ratings(1)

7/28/2019 Loading Power Transformers Beyond Nameplate Ratings(1)

http://slidepdf.com/reader/full/loading-power-transformers-beyond-nameplate-ratings1 16/23

 

The Grid Tab

Here you can edit

load profile and

ambient temperature

Page 17: Loading Power Transformers Beyond Nameplate Ratings(1)

7/28/2019 Loading Power Transformers Beyond Nameplate Ratings(1)

http://slidepdf.com/reader/full/loading-power-transformers-beyond-nameplate-ratings1 17/23

Page 18: Loading Power Transformers Beyond Nameplate Ratings(1)

7/28/2019 Loading Power Transformers Beyond Nameplate Ratings(1)

http://slidepdf.com/reader/full/loading-power-transformers-beyond-nameplate-ratings1 18/23

 

Graphical tab

Page 19: Loading Power Transformers Beyond Nameplate Ratings(1)

7/28/2019 Loading Power Transformers Beyond Nameplate Ratings(1)

http://slidepdf.com/reader/full/loading-power-transformers-beyond-nameplate-ratings1 19/23

Page 20: Loading Power Transformers Beyond Nameplate Ratings(1)

7/28/2019 Loading Power Transformers Beyond Nameplate Ratings(1)

http://slidepdf.com/reader/full/loading-power-transformers-beyond-nameplate-ratings1 20/23

• Benefits and Applications

 – Transmission Planning•  Apply transformer emergency ratings for power 

flow and contingency analysis – Real time operations

• Prepare dispatching centers with emergencyratings until they mitigate power failures

 – Relay settings• Set overload relay settings based on the calculated

emergency ratings of the transformer 

Page 21: Loading Power Transformers Beyond Nameplate Ratings(1)

7/28/2019 Loading Power Transformers Beyond Nameplate Ratings(1)

http://slidepdf.com/reader/full/loading-power-transformers-beyond-nameplate-ratings1 21/23

• Benefits and Applications

 – When two transformers are in parallel, emergency

ratings can help you know how much the other 

transformer can be overloaded.• Rating Philosophies

 – Ratron offers an easy way to create transformer rating

philosophies

• NERC compliance – Ratron allows you to back up your methodology and

gets you ready for NERC auditing

Page 22: Loading Power Transformers Beyond Nameplate Ratings(1)

7/28/2019 Loading Power Transformers Beyond Nameplate Ratings(1)

http://slidepdf.com/reader/full/loading-power-transformers-beyond-nameplate-ratings1 22/23

Page 23: Loading Power Transformers Beyond Nameplate Ratings(1)

7/28/2019 Loading Power Transformers Beyond Nameplate Ratings(1)

http://slidepdf.com/reader/full/loading-power-transformers-beyond-nameplate-ratings1 23/23

 