LOAD CENTERSMAIN LUG ONLY 1-PHASE 10,000 AIC
LC002GS
|HMM»
LC004NS
iHHM
Load Center Short CircuitCurrent RatingMurray load centers have
UL recognized shortcircuit current ratings up to 100,000 Amps,when
used with appropriate main or feeder(remote or internal)
overcurrent devices. Loadcenter ratings are shown below. For
loadcenter applications with residential orcommercial metering
equipment, refer to theappropriate catalog section.
Load CenterShort Circuit Load CenterCurrent Ratingil Main
Rating
Internal or RemoteMain or FeederCircuit Breaker Type
10,000 Amps22,000 Amps
42,000 Amps
65,000 Amps
100,000 Amps
Any100/125 Amps150/200/225
Amps100/125 Amps150/200/225
Amps100/125 Amps150/200/225
Amps100/125 Amps
150/200/225Amps
AnyMP-HT, MOM'S®MD-HTR, MQH®®,MPP-HT®MQL®®MQL®S
MP-MT, MPP-MT®MPP-MT®
100A, 300V AC, ClassT Fuse®200A, 300V AC, ClassT Fuse®
Single-phase, main lug only load centers areUnderwriters'
Laboratories Listed. They arefurnished with insulated, groundable
neutral andare suitable for use as service equipment wheneither of
the following conditions are met:1) 12-1" positions max: if not
more than
6 disconnecting means are used, and ifnot used as a lighting and
appliance branchcircuit panelboard (see 1996 NEC Art #384-14).
2) 200 Amp max: if a single back-fed mainbreaker is used.
Bonding means are provided. These loadcenters are UL Listed for
use with 60/75°Cconductors and accept Murray branch circuitbreakers
which are also UL Listed for use with60/75°C conductors. Type 3R
load centers arefurnished with a hub opening closure plate.
Accessories—See page LC-10.Lug Data—See page LC-11.Wiring
Diagrams—See pages LC-12
through LC-14.Knockout Data—See pages LC-15 and LC-16.
1 Remote Only
v? This information is based on use of 10,000 AIC ratedbranch
circuit breakers in load center (MP-T, MH-T,MP-GT, MG). Most series
ratings exclude MH-Tabove 40 Amp. Consult device wiring diagram
forspecific data.
STypes MQH & MQL may be mounted internal in 150-225amp 30
main breaker load centers, and in 225 amp 10main breaker load
centers.
Main Lug Panels 3-Wire 120/240V AC or 208Y/120V AC, Insulated
Groundable Neutral!See Interrupting Capacity Statement)
INDOOR ENCLOSURE— TYPEMax. #
r SingleAmps Spaces Poles Cat #'•'
2-8
6060
125125125125
125125125125125125125
ListEach
StdPkg
Approx.Wgt. KO
. Lbs. Fig
1 OUTDOOR ENCLOSURE— TYPE 3R®Dimensions — Inches3
Length Width Depth
CIRCUIT, 60-125 AMPERES
224466
6668888
44S8
1212
12121216161616
NO DOOR
LC002GF*LC002GS®LC004NF®®LC004NS6lff
LC006NFLC006NSS
WITH DOOR
LC006DF*LC006DS'5
LC006DFGsi)
LC008DFLC008DS1
LC008DFGS 'LC008DSG ! ""
45.0045.0055.0055.0075.0075.00
87.0087.0095.00
107.00107.00117.00117.00
555511
1111111
16.0016.0030.0030.0012.0012.00
12.0012.0012.0012.0012.0012.0012.00
112233
3333333
9%VA
12%12%14%i4/;
143/4
14%143/4U'A143/.14'/143/«
5'A5%6s/,6%
12%12%
12%12%12%12/^2a^12712%
2'/2%3143'/3%3%
3%3/-37-3%3%3',43%
Cat*ListEach
Std.Pkg
Approx.Wgt. KOLbs. Fig.
Dimensions — Inches'
Length Width Depth
2-8 CIRCUIT, 60-125 AMPERES
LW002GR®
LW004NR®®0
LW006NR4
LW008NR1
88.00
97.00
115.00
162.00
5
5
1
1
24.00 6
34.00 7
13.00 8
13.00 8
814
12'/4
143/4
143/«
5%
6%
12%
12K
Vk
4'/4
4/4
VA
I'Hub provision only. Closure plate included. Panelsthrough 225A
require HS type hub; panels over 225Arequire HV type hub. See
accessories, page LC-10,for hub selection.
SCover type is specified by character in 7th (usually
last)position, as follows:
S = SurfaceF -FlushC = Combination Surface/Flush
C?)Dimensions shown are representative of outside boxlength,
width & depth (±X") and do not includeallowance for mounting
bumps, endwalls, hubs orhardware protrusions. Allow approximately
1X"additional in length and width dimensions for surfaceor
combination overhang. Consult factory for specificdetails if
required.
'^Use of 60A GFCI requires use of 75°C copper wire.
®Use neutral lug kit DLK1 or DLK2 as required.See accessory page
LC-10 or CO-6.
®Panel includes factory-installed ground bar.ii'Maximum breaker
100A.©Accepts only grounding bar kit #LX068M. See page LC-10.
Discount Schedule "A"
-
LOAD CENTERSGENERAL DESCRIPTION
MurrayLoad Centers—the industry standard of
highestquality...designed to complement theMurray line of Circuit
Breakers.
Load centers are used for the protection anddistribution of
loads in residential, commercialand light industrial applications
operating at 240volts AC max. Load centers subdivide powerinto
branch circuits serving a variety of smallloads. They provide a
switching and protectivefunction for these load circuits. Typical
loadsare lighting, appliance, heating and small motorbranch
circuits.
Murray load centers feature a new split neutraldesign in all
single phase main lug and mainbreaker models from 100 Amp, 12
circuitthrough 225 Amp, 42 circuit. These neutralshave one
insulated and one uninsulated neutralbar. For service entrance
applications, use bothbars for neutral and ground conductors.For
non-service entrance applications, useinsulated bar for neutral
conductors anduninsulated bar for ground conductors.
Load centers are often referred to as servicepanels, circuit
breaker panels, or several othernames, however, they are officially
knownas panelboards.
Design/Performance Features• New insulated and bonded split
neutral for
faster neater wiring.
Two neutral bars, one bonded, one insulated,connected with a
cross strap and removablebonding strap, allowing maximum
versatility.For service entrance applications, connect thebonding
strap and wire neutral and grounds toboth bars. For non-service
entranceapplications, disconnect the bonding strapand use insulated
bar for neutral and bondedbar for grounds. No need to
purchaseaccessory ground bars.
Neutral bars provide two sizes of terminalsfor maximum wire
range usage.
• One-piece bus bar construction, through 200amps, eliminates
heat producing joints andprovides cooler operation with longer
life.Alstan® 88 plating with a copper strikeensures maximum
electrical conductivity andcorrosion prevention.
• Circuit breaker landing pads provide branchcircuit breakers
positive fit and alignment.
• 100 through 225 amp load centers are offeredwith combination
surface/flush covers forgreater inventory flexibility
substantiallyreducing inventory space and investment.
Covers are attractively styled one-piece trimand dead front
design featuring an easy toopen and close sliding latch.
• NEMA 3R enclosures are constructed of G90galvanized steel
painted with anelectrodeposition process providing uniformcoverage
for maximum protection againstcorrosive environments and an
attactiveappearance.
• Bus protectors to guard against contaminationduring
installation and finish constructionwork.
• Drywall gauge visibly embossed on fourcorners of enclosure to
facilitate proper flushmounting.
I!IJ/I/II1
LC002GS LC120DC
60 Amp 2 circuit load center, available inindoor enclosure,
surface and flush, andoutdoor surface enclosure.
100 Amp single phase load center, withinsulated and bonded split
neutral.
LC330SS LW020PR
'..*
400 Amp double main breaker load center,includes a 200 Amp
factory mounted mainbreaker controlling a 30 circuit load
center,and provision for a second 200A breakerfor a remote
load.
200 Amp outdoor load center withinsulated and bonded split
neutral.
• Interior is made with a rugged steel basepanto provide rigid
support for plug-in circuitbreakers. One-piece steel construction
withcaptive interior assembly hardware allowseasy removal of
interior to facilitate quick wirepulling.
1 Keyhole and nail slots provide fast and easyenclosure
mounting.
• New knockout patterns are ideally sized andlocated for maximum
wiring flexibility.
•Circuit identification labels preprinted forpopular circuits,
and number labels for crossreference with directory.
• Circuit directory is large and easy to read.
• Short circuit current rating is UL listed forseries ratings up
to 100.000A 1C usingstandard to 10.000A 1C branch current.
• Murray's Rock Solid Warranty guaranteescircuit breakers for a
lifetime and load centersfor up to 10 years!
-
LOAD CENTERSTECHNICAL INFORMATION LC
Load Center Short CircuitCurrent RatingMurray load centers have
UL recognized shortcircuit current ratings up to 100,000 Amps,when
used with appropriate main or feeder(remote or internal)
overcurrent devices. Loadcenter ratings are shown below. For
loadcenter applications with residential orcommercial metering
equipment, refer to theappropriate catalog section.
Load CenterShort CircuitCurrent Rating
Load Center2} Main Rating
Internal or RemoteMain or FeederCircuit Breaker Type
10,000 Amps22,000 Amps
42,000 Amps
65,000 Amps
100,000 Amps
Any100/125 Amps150/200/225Amps100/125 Amps150/200/225Amps100/125
Amps150/200/225Amps100/125 Amps
150/200/225Amps
AnyMP-HT, MQH®MD-HTR, MQH®,MPP-HT®MQL®MQL®
MP-MT, MPP-MT®MPP-MT®
100A, 300V AC, ClassT Fuse®200A, 300V AC, ClassT Fuse®
^'Remote Only
®This information is based on use of 10,000 AIC ratedbranch
circuit breakers in load center (MP-T, MH T, MP-GT, MG). Most
series ratings exclude MH-T above 40Amp. Consult device wiring
diagram for specific data.
'1;Types MQH & MQL may be mounted internal in 150-225amp 30
main breaker load centers, and in 225 amp 10main breaker load
centers.
Series RatingsSeries ratings allow two or three breakers tobe
connected in series, such that the 2nd and3rd breakers have an
interrupting capacity lessthan the system available fault current.
Suchcombinations must be tested, and onlybreakers of the type and
ampere rating testedmay be used in this combination. Typicalusage
of series ratings would be main andbranch circuit breakers in load
centers. Themain breaker must have an interruptingcapacity at least
equal to the available faultcurrent. However, the branch breaker
mayhave an interrupting capacity lower than theavailable fault
current, provided the pair havebeen tested together as a
series-rated pair.
LC230PC
I
200 Amp 30 Circuit 10,000 AIC LoadCenter, Indoor
Enclosure,Combination Cover.
Industry and GovernmentSpecificationsMurray load centers meet or
exceed the latestedition of the following industry standardsand
Government specifications, unlessnoted otherwise:
IndustryNEMA—Standard #PB1
UL—Standards #50 and #67
US GovernmentStandard # WP-115b, Type 1, Class 2 coversload
centers through 200 Amps.
Spaces Versus PolesThe number of "spaces" available in a
loadcenter is the maximum number of 1" singlepole circuit breakers
that can be installed inthat load center. Because most load
centerswill accept half-size breakers, the actualnumber of single
pole breakers that may beinstalled is often more than the number of
1"spaces provided. In compliance with therequirements of the
National Electrical Code,a physical means is provided to prevent
theinstallation of more circiut breakers than thenumber of breakers
for which the load centerwas designed. This means of circuit
limitingallows the load centers to be UL Listed as"Class CTL".
Circuit Breaker UL Type
§0o
m30CO
CATALOG #PREFIX UL
TYPE*MP(150-200A)MP05-125A)MP(Duplex)MP(Triplex)MPIQuad
Plex)MP(GFCI)
MD-TR OR MD-HTRMP-T, MP-HT, MP-MT
MH-TMH-TMH-T
MP-GT, MP-HGTf UL Type is shown on circuit breaker label.
-
LOAD CENTERSKNOCKOUT DATA INDOOR ENCLOSURES
Figure 1 Figure 2
•* W *-| D < u
,_. ® ^, ®® © ® (D ^9 CD
aCM) ^ CM)©: ;© ® ® ® ® :®i i 'i i i
' i Li i
^' '/^ ® ®Cy ; ® ® ; CL> ® ® , ®^a ® " r^ ®® © ® ® (a) @
Figure 4
©00© ^-^ ©00©_©© (SJ 0©© 0® Q-& © ®©
© © 9 A? © ©= © © =Pi ii©m© ©«®©B© ©K©©w ©©= © © =
© © © © © ©
0© © 99 ©0©0© (s) 0©
©©©© ̂ Q©0©
Knockout Code — Conduit Sizes
a = x. s = i, v/4, ix, 2, 2^A = !« T = 1 7,B = 'A, % U = 1 X 1
'Ac = x, y., i v = ix, IH, 2D = H, 1 W = 1 %, 2E = X. %, 1,1'X. X =
IX, 1)4, 2, 2!4 . >F = X, 1 '/», 1 !< Y = 1 H, 2G = % Z = 1
%, 2, 2 14H = «, 1 AA = 1 !«, 2, 2!4, 3J = 3/, 1,1 'X, BB = 1)4, 2,
2H, 3, 3!4K = 3X«, VX. CC = 2, 2H, 3, 3KL= X, 3X«, 1, U, VA EE = 2,
2)4, 3M = %, 1, IX, IX FF = 2)4, 3N = 3X., 1, 1'X., 114, 2 GG =
2!4, 3, 3KP = 1, IX HH = 2)4, 3, 314, 4Q=1, 1X,1!4 JJ = 3X, 4R = 1,
IX., 114, 2 LL = 3
W = 2
L
L
i_
Figure
®
©
0®
©
3
* W *
®@® fa. **. ®
@%@
@®T©
®
®
®o® (gj Q® ®^® ® ® ®
R77
®©®®
©
TI
i
T
LC
n
15
r-OA
D C
EN
TER
S