NITIN CORPORATION 402, 4 th Floor, Bezzola Commercial Complex, Sion – Trombay Road, Chembur, Mumbai – 400071, India. WEB: www.corponit.com E – MAIL: [email protected][email protected]FAX : +91 - 22 - 25235386 PH (O) : +91 - 22 - 25234478/67973677 THE FOLLOWING NEW ALTERNATORS / GENERATOR ENDS ARE AVAILABLE FOR SALE WITH US WITH IMMEDIATE DELIVERY: 19 Nos. – NEW Leroy Somer & Stamford make Alternators / Generators Ends as per technical details below: LIST OF ALTERNATOR / GENERATOR ENDS AVAILABLE FOR SALE. Make Model KVA V KW RPM YOM Leroy Somer LSA51.2M60 2300 480 1968,6 1800 2012 Leroy Somer LSA51.2M60 2300 480 1968,6 1800 2012 Leroy Somer LSA51.2M60 2300 480 1968,6 1800 2012 Leroy Somer LSA51.2M60 2300 480 1968,6 1800 2012 Leroy Somer LSA51.2M60 2300 480 1968,6 1800 2012 Stamford PI734E1 2600 480 1840 1800 2012 Stamford PI734E1 2600 480 1840 1800 2012 Stamford PI734E1 2600 480 1840 1800 2012 Stamford PI734E1 2600 480 1840 1800 2012 Stamford PI734F1 2600 480 2080 1800 2012 Stamford PI734F1 2600 480 2080 1800 2012 Stamford PI734F1 2600 480 2080 1800 2012 Stamford PI734F1 2600 480 2080 1800 2012 Stamford PI734F1 2600 480 2080 1800 2012 Stamford PI734F1 2600 480 2080 1800 2012 Stamford PI734F1 2600 480 2080 1800 2012 Leroy Somer LSA51.2S55 1800 380 1440 1800 2009 Leroy Somer LSA51.2S55 1800 380 1440 1800 2009 Leroy Somer LSA51.2M60 2300 480 1600 1800 2012
28
Embed
LIST OF ALTERNATOR / GENERATOR ENDS … · 19 Nos. – NEW Leroy Somer & Stamford make Alternators / Generators Ends as per technical details below: LIST OF ALTERNATOR / GENERATOR
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
ELECTRICAL DATAInsulation class H Excitation system A R E P + PMIWinding pitch - Code 2/3 - (N° 6S) A.V.R. model R 449Leads 6 Voltage regulation (steady state) ± 0,5 %Drip proof IP 23 Sustained short-circuit current 300% (3 IN) : 10sAltitude ≤ 1000 m Total harmonic (*) TGH / THC < 2,5 %Overspeed 2250 min -1 Waveform : NEMA = TIF - (*) < 50Air flow 2,5 m3/s Waveform : I.E.C. = THF - (*) < 2 %(*) Total harmonic content line to line, at no load or full rated linear and balanced load
According to : I.E.C. 34.1/34.2 - U.T.E. : NF C 51.111 - V.D.E. 0530 - B.S. 4999 & 5000 - NEMA : MG 1.22 - ISO 8528 . 3 - CSA (C22.2 + UL 2200). Products and materials shown in this catalogue may, at any time, be modified in order to follow the latest technological developments, improve the design or change the conditions of utilisation.Their description cannot in any case engage Leroy-Somer's liability. The values indicated are typical values .
ALTERNATORS
RATINGS : kVA / kW - Power factor = 0,8 Duty/Ambiant T° Continuous / 40°C Stand-by / 40°C Stand-by / 27°CClass/T° rise H / 125° K F / 105° K H / 150° K H / 163° K
Phase 3 ph. 3 ph. 3 ph. 3 ph. Y ∆
380V220V
400V230V
415V240V
380V220V
400V230V
415V240V
380V220V
400V230V
415V240V
380V220V
400V230V
415V240V
51.2 S55 kVA 1800 1620 1890 1980
kW 1440 1296 1512 1584
51.2 M60 kVA 2000 1800 2100 2200
kW 1600 1440 1680 1760
51.2 L70 kVA 2150 1935 2255 2365
kW 1720 1548 1804 1892
51.2 VL 85 kVA 2250 2025 2360 2475
kW 1800 1620 1888 1980
EFFICIENCIES (%) - Class H / 40° C Three phase : 400 V
T'do Open circuit time constant 2660 2770 2910 3050X'd Direct axis transient reactance saturated 27,4 26,2 23,8 20,4T'd Short circuit transient time constant 237 245 254 263X"d Direct axis subtransient reactance saturated 14,2 13,6 12,4 10,6T"d Subtransient time constant 22 23 24 26X"q Quadrature axis subtransient reactance saturated 17,8 17 15,5 13,2Xo Zero sequence reactance unsaturated 3,4 3,2 2,9 2,5X2 Negative sequence reactance saturated 16 15,3 13,9 12Ta Armature time constant 38 41 44 48
OTHER DATA - CLASS H / 400 V io (A) No load excitation current 1,5 1,5 1,6 1,6ic (A) Full load excitation current 6 5,9 5,5 5uc (V) Full load excitation voltage 63 62 60 56
ms Recovery time (∆U = 20 % transient) < 700 < 700 < 700 < 700kVA Motor start. (∆U = 20% sust.) or (∆U = 50% Transient) 3600 4000 4300 4500% Transient dip (rated step load) - PF : 0,8 LAG 12 12 11 10
Products and materials shown in this catalogue may, at any time, be modified in order to follow the latest technological developments, improve the design or change the conditions of utilisation.Their description cannot in any case engage Leroy-Somer's liability. The values indicated are typical values .
0 500 1000 1500 2000 2500 3000 3500 400000
5
10
15
20
25
0
kVA at 0,8 power factor
% V
olta
ge d
ip
Load application
0 500 1000 1500 2000 2500 300000
5
10
15
20
25
0
kVA at 0,8 power factor
% V
olta
ge r
ise
Load rejection
1) For a starting P.F. differing from 0,6 the starting kVA have to be multiplied by (Sine Ø /0,8)2) If voltage is not 400V(Y) , 230V(∆) at 50 Hz then kVA must be multiplied by (400/U)2 or (230/U)2.
0 500 1000 1500 2000 2500 3000 3500 4000 450000
10
20
30
0
Locked rotor - kVA at 0,6 power factor
% V
olta
ge d
ip
Motors starting
ALTERNATORS
VL 85
LSA 51.2 - 4P 50 Hz - 1500 r.p.m.
TRANSIENT VOLTAGE VARIATION - 400V
L 70
M 60
S 55
VL 85
L 70
M 60 S 55
VL 85
L 70
M 60
S 55
NITIN
CORPORATIO
N
ELECTRICAL DATAInsulation class H Excitation system A R E P + PMIWinding pitch - Code 2/3 - (N° 6S) A.V.R. model R 449Leads 6 Voltage regulation (steady state) ± 0,5 %Drip proof IP 23 Sustained short-circuit current 300% (3 IN) : 10sAltitude ≤ 1000 m Total harmonic (*) TGH / THC < 2,5 %Overspeed 2250 min -1 Waveform : NEMA = TIF - (*) < 50Air flow 2,8 m3/s Waveform : I.E.C. = THF - (*) < 2 %(*) Total harmonic content line to line, at no load or full rated linear and balanced load
According to : I.E.C. 34.1/34.2 - U.T.E. : NF C 51.111 - V.D.E. 0530 - B.S. 4999 & 5000 - NEMA : MG 1.22 - ISO 8528 . 3 - CSA (C22.2 + UL 2200). Products and materials shown in this catalogue may, at any time, be modified in order to follow the latest technological developments, improve the design or change the conditions of utilisation.Their description cannot in any case engage Leroy-Somer's liability. The values indicated are typical values .
ALTERNATORS
RATINGS : kVA / kW - Power factor = 0,8 Duty/Ambiant T° Continuous / 40°C Stand-by / 40°C Stand-by / 27°CClass/T° rise H / 125° K F / 105° K H / 150° K H / 163° K
T'do Open circuit time constant 2660 2770 2910 3050X'd Direct axis transient reactance saturated 27,4 26,2 23,8 20,4T'd Short circuit transient time constant 237 245 254 263X"d Direct axis subtransient reactance saturated 14,2 13,6 12,4 10,6T"d Subtransient time constant 22 23 24 26X"q Quadrature axis subtransient reactance saturated 17,8 17 15,5 13,2Xo Zero sequence reactance unsaturated 3,4 3,2 2,9 2,5X2 Negative sequence reactance saturated 16 15,3 13,9 12Ta Armature time constant 38 41 44 48
OTHER DATA - CLASS H / 480 V io (A) No load excitation current 1,5 1,5 1,6 1,6ic (A) Full load excitation current 6 5,9 5,5 5uc (V) Full load excitation voltage 63 62 60 56
Products and materials shown in this catalogue may, at any time, be modified in order to follow the latest technological developments, improve the design or change the conditions of utilisation.Their description cannot in any case engage Leroy-Somer's liability. The values indicated are typical values .
1) For a starting P.F. differing from 0,6 the starting kVA have to be multiplied by (Sine Ø /0,8)2) If voltage is not 480V(Y), 277V(∆), 240V(YY ) at 60 Hz then kVA must be multiplied by (480/U)2 or (277/U)2 or (240/U)2.
ALTERNATORS LSA 51.2 - 4P 60 Hz - 1800 r.p.m.
TRANSIENT VOLTAGE VARIATION - 480 V
0 500 1000 1500 2000 2500 3000 3500 4000 450000
5
10
15
20
25
0
kVA at 0,8 power factor
% V
olta
ge d
ip
Load application
0 500 1000 1500 2000 2500 3000 350000
5
10
15
20
25
0
kVA at 0,8 power factor
% V
olta
ge r
ise
Load rejection
VL 85
L 70
M 60
S 55
VL 85
L 70
M 60 S 55
VL 85
L 70
M 60
S 55
NITIN
CORPORATIO
N
Cables
4 holes Ø 334 holes Ø 14,5
4 holes Ø M24
S DIA,XBG Eq. Sp. holes on M P.C.D.
AIR INLETAIR OUTLET
YD
IA, X
Eq.
Sp.
hol
es o
n U
P.C
.D.
LB
L
Xg
V
Ø B
X
Ø N
Ø 9
98
AH
895
50
0
1395
35
ß
0 - 0,
127
- 0,
050
- 0,
100
12
7
PMG Option +110
IP 23 Option
Opt
ion
26060
6040
150 150220
195B
Ø 8
71Ø
975
6801080
+1
0
220
750 80 80
910
610 140 140 140
Lr
Ø 2
25
Ø 1
70
Ø 1
40
Xr
Ø 2
40
Ø 2
20
FRAME DIMENSIONS (mm) Mass (kg)
TYPEL
without PMG LB B V Xg M
LSA 51.2 S55 1677 1655 900 744 735 3745
LSA 51.2 M60 1777 1755 1000 844 770 4040
LSA 51.2 L70 1877 1855 1100 944 825 4445
LSA 51.2 VL85 1977 1955 1200 1044 885 4995
ALTERNATORS LSA 51.2 - 4P Single bearing
DIMENSIONS
TORSIONAL ANALYSIS DATA
CENTRE OF GRAVITY : Xr (mm) - ROTOR LENGTH : Lr (mm) - MASS : M (kg) - MOMENTS OF INERTIA : J (kgm2) : (4J = MD2)
Products and materials shown in this catalogue may, at any time, be modified in order to follow the latest technological developments, improve the design or change the conditions of utilisation.Their description cannot in any case engage Leroy-Somer's liability. The values indicated are typical values .
Coupling
FlangeFlex plate
SAE00
SAE 0
SAE 24 •
SAE 21 •
SAE 18 • •
FLANGE DIMENSIONS (mm) FLEX PLATE DIMENSIONS (mm)S.A.E. N M XBG S ß S.A.E. BX U X Y AH
Products and materials shown in this catalogue may, at any time, be modified in order to follow the latest technological developments, improve the design or change the conditions of utilisation.Their description cannot in any case engage Leroy-Somer's liability. The values indicated are typical values .
FRAME DIMENSIONS (mm) Mass (kg)
TYPEL
wihout PMG LB B V Xg M
LSA 51.2 S55 1905 1655 900 744 735 3725
LSA 51.2 M60 2005 1755 1000 844 770 4020
LSA 51.2 L70 2105 1855 1100 944 825 4425
LSA 51.2 VL85 2205 1955 1200 1044 885 4975
CENTRE OF GRAVITY : Xr (mm) - ROTOR LENGTH : Lr (mm) - MASS : M (kg) - MOMENTS OF INERTIA : J (kgm2) : (4J = MD2)
TYPE Xr Lr M J
LSA 51.2 S55 605,6 1783,5 1281 38,9
LSA 51.2 M60 647,6 1883,5 1398 42,6
LSA 51.2 L70 698,8 1983,5 1553 47,8
LSA 51.2 VL85 763,3 2083,5 1766 55,1
NITIN
CORPORATIO
N
MOTEURS LEROY-SOMER 16015 ANGOULÊME CEDEX - FRANCE
http://www.leroy-somer.com
AP
PR
OV
ED
DO
CU
ME
NT
PI734E - Winding 312
Technical Data Sheet
NITIN
CORPORATIO
N
AP
PR
OV
ED
DO
CU
ME
NT
PI734ESPECIFICATIONS & OPTIONS
STANDARDSStamford industrial generators meet the requirements of BS EN 60034 and the relevant sections of other national and international standards such as BS5000, VDE 0530, NEMA MG1-32, IEC60034, CSA C22.2-100, AS1359.Other standards and certifications can be considered on request.
DESCRIPTIONThe STAMFORD PI range of synchronous ac generators are brushless with a rotating field. They are separately excited by the STAMFORD Permanent Magnet Generator (PMG). This is a shaft mounted, high frequency, pilot exciter which provides a constant supply of clean power via the Automatic Voltage Regulator (AVR) to the main exciter. The main exciter output is fed to the main rotor, through a full wave bridge rectifier, protected by surge suppression. VOLTAGE REGULATORSThe PI range generators, complete with a PMG, are available with one of two AVRs. Each AVR has soft start voltage build up and built in protection against sustained over-excitation, which will de-excite the generator after a minimum of 8 seconds. Underspeed protection (UFRO) is also provided on both AVRs. The UFRO will reduce the generator output voltage proportional to the speed of the generator below a pre-settable level.
The MX341 AVR is two phase sensed with a voltage regulation of ± 1 %. (see the note on regulation).
The MX321 AVR is 3 phase rms sensed with a voltage regulation of 0.5% rms (see the note on regulation). The UFRO circuit has adjustable slope and dwell for controlled recovery from step loads. An over voltage protection circuit will shutdown the output device of the AVR, it can also trip an optional excitation circuit breaker if required. As an option, short circuit current limiting is available with the addition of current transformers.
Both the MX341 and the MX321 need a generator mounted current transformer to provide quadrature droop characteristics for load sharing during parallel operation. Provision is also made for the connection of the STAMFORD power factor controller, for embedded applications, and a remote voltage trimmer.
WINDINGS & ELECTRICAL PERFORMANCEAll generator stators are wound to 2/3 pitch. This eliminates triplen (3rd, 9th, 15th …) harmonics on the voltage waveform and is found to be the optimum design for trouble-free supply of non-linear loads. The 2/3 pitch design avoids excessive neutral currents sometimes seen with higher winding pitches. A fully connected damper winding reduces oscillations during paralleling. This winding, with the 2/3 pitch and carefully selected pole and tooth designs, ensures very low levels of voltage waveform distortion.
TERMINALS & TERMINAL BOXStandard generators feature a main stator with 6 ends brought out to the terminals, which are mounted on the frame at the non-drive end of the generator. A sheet steel terminal box contains the AVR and provides ample space for the customers' wiring and gland arrangements. It has removable panels for easy access.
SHAFT & KEYSAll generator rotors are dynamically balanced to better than BS6861:Part 1 Grade 2.5 for minimum vibration in operation. Two bearing generators are balanced with a half key.
INSULATION/IMPREGNATIONThe insulation system is class 'H', and meets the requirements of UL1446.All wound components are impregnated with materials and processes designed specifically to provide the high build required for static windings and the high mechanical strength required for rotating components.
QUALITY ASSURANCEGenerators are manufactured using production procedures having a quality assurance level to BS EN ISO 9001.
NOTE ON REGULATIONThe stated voltage regulation may not be maintained in the presence of certain radio transmitted signals. Any change in performance will fall within the limits of Criteria 'B' of EN 61000-6-2:2001. At no time will the steady-state voltage regulation exceed 2%.
DE RATESAll values tabulated on page 8 are subject to the following reductions
5% when air inlet filters are fitted.10% when IP44 Filters are fitted.3% for every 500 metres by which the operating altitude exceeds 1000 metres above mean sea level.3% for every 5°C by which the operational ambient temperature exceeds 40°C. Note: Requirement for operating in an ambient temperature exceeding 60°C must be referred to the factory.
Note: Continuous development of our products entitles us to change specification details without notice, therefore they must not be regarded as binding.
Front cover drawing is typical of the product range.
2
NITIN
CORPORATIO
N
AP
PR
OV
ED
DO
CU
ME
NT
CONTROL SYSTEM SEPARATELY EXCITED BY P.M.G.
A.V.R. MX341 MX321
VOLTAGE REGULATION ± 1 % ± 0.5 % With 4% ENGINE GOVERNING
SUSTAINED SHORT CIRCUIT
INSULATION SYSTEM
PROTECTION
RATED POWER FACTOR
STATOR WINDING
WINDING PITCH
WINDING LEADS
MAIN STATOR RESISTANCE
MAIN ROTOR RESISTANCE
EXCITER STATOR RESISTANCE
EXCITER ROTOR RESISTANCE
R.F.I. SUPPRESSION BS EN 61000-6-2 & BS EN 61000-6-4,VDE 0875G, VDE 0875N. refer to factory for others
WAVEFORM DISTORTION NO LOAD < 1.5% NON-DISTORTING BALANCED LINEAR LOAD < 5.0%
MAXIMUM OVERSPEED 2250 Rev/Min
BEARING DRIVE END BALL. 6228 C3
BEARING NON-DRIVE END BALL. 6319 C3
1 BEARING 2 BEARING
WEIGHT COMP. GENERATOR
WEIGHT WOUND STATOR
WEIGHT WOUND ROTOR
WR² INERTIA
SHIPPING WEIGHTS in a crate
PACKING CRATE SIZE
TELEPHONE INTERFERENCE
COOLING AIR
VOLTAGE STAR 380/220 400/231 415/240 440/254 416/240 440/254 460/266 480/277
kVA BASE RATING FOR REACTANCE VALUES 1845 1900 1900 1865 2070 2210 2255 2300
3-phase 2-phase L-L 1-phase L-NVoltage Factor Voltage Factor x 1.00 x 0.87 x 1.30
380v x 1.00 416v x 1.00 x 1.00 x 1.80 x 3.20400v x 1.05 440v x 1.06 x 1.00 x 1.50 x 2.50415v x 1.09 460v x 1.10 10 sec. 5 sec. 2 sec.440v x 1.16 480v x 1.15
The sustained current value is constant irrespectiveof voltage level
Three-phase Short Circuit Decrement Curve. No-load Excitation at Rated SpeedBased on star (wye) connection.
Max. sustained durationAll other times are unchanged
Instantaneous
SustainedMinimum
50Hz 60Hz
PI734E
Sustained Short Circuit = 6,250 Amps
Sustained Short Circuit = 7,500 AmpsNote 1The following multiplication factors should beused to adjust the values from curve betweentime 0.001 seconds and the minimum currentpoint in respect of nominal operating voltage :
Note 2The following multiplication factor should be used to convert thevalues calculated in accordance with NOTE 1 to those applicableto the various types of short circuit :
Note 3Curves are drawn for Star (Wye) connected machines.
Cont. F - 105/40°C Cont. H - 125/40°C Standby - 150/40°C Standby - 163/27°C
Winding 312 / 0.8 Power Factor
RATINGS
50Hz
60Hz
8
NITIN
CORPORATIO
N
AP
PR
OV
ED
DO
CU
ME
NT
PI7E-312-TD-EN-SG-A
Head Office Address:Barnack Road, StamfordLincolnshire, PE9 2NB
United KingdomTel: +44 (0) 1780 484000Fax: +44 (0) 1780 484100
www.cumminsgeneratortechnologies.com
Copyright 2010, Cummins Generator Technologies Ltd, All Rights ReservedStamford and AvK are registered trade marks of Cummins Generator Technologies Ltd
Cummins and the Cummins logo are registered trade marks of Cummins Inc.
NITIN
CORPORATIO
N
AP
PR
OV
ED
DO
CU
ME
NT
PI734F - Winding 312
Technical Data Sheet
NITIN
CORPORATIO
N
AP
PR
OV
ED
DO
CU
ME
NT
PI734FSPECIFICATIONS & OPTIONS
STANDARDSStamford industrial generators meet the requirements of BS EN 60034 and the relevant sections of other national and international standards such as BS5000, VDE 0530, NEMA MG1-32, IEC60034, CSA C22.2-100, AS1359.Other standards and certifications can be considered on request.
DESCRIPTIONThe STAMFORD PI range of synchronous ac generators are brushless with a rotating field. They are separately excited by the STAMFORD Permanent Magnet Generator (PMG). This is a shaft mounted, high frequency, pilot exciter which provides a constant supply of clean power via the Automatic Voltage Regulator (AVR) to the main exciter. The main exciter output is fed to the main rotor, through a full wave bridge rectifier, protected by surge suppression. VOLTAGE REGULATORSThe PI range generators, complete with a PMG, are available with one of two AVRs. Each AVR has soft start voltage build up and built in protection against sustained over-excitation, which will de-excite the generator after a minimum of 8 seconds. Underspeed protection (UFRO) is also provided on both AVRs. The UFRO will reduce the generator output voltage proportional to the speed of the generator below a pre-settable level.
The MX341 AVR is two phase sensed with a voltage regulation of ± 1 %. (see the note on regulation).
The MX321 AVR is 3 phase rms sensed with a voltage regulation of 0.5% rms (see the note on regulation). The UFRO circuit has adjustable slope and dwell for controlled recovery from step loads. An over voltage protection circuit will shutdown the output device of the AVR, it can also trip an optional excitation circuit breaker if required. As an option, short circuit current limiting is available with the addition of current transformers.
Both the MX341 and the MX321 need a generator mounted current transformer to provide quadrature droop characteristics for load sharing during parallel operation. Provision is also made for the connection of the STAMFORD power factor controller, for embedded applications, and a remote voltage trimmer.
WINDINGS & ELECTRICAL PERFORMANCEAll generator stators are wound to 2/3 pitch. This eliminates triplen (3rd, 9th, 15th …) harmonics on the voltage waveform and is found to be the optimum design for trouble-free supply of non-linear loads. The 2/3 pitch design avoids excessive neutral currents sometimes seen with higher winding pitches. A fully connected damper winding reduces oscillations during paralleling. This winding, with the 2/3 pitch and carefully selected pole and tooth designs, ensures very low levels of voltage waveform distortion.
TERMINALS & TERMINAL BOXStandard generators feature a main stator with 6 ends brought out to the terminals, which are mounted on the frame at the non-drive end of the generator. A sheet steel terminal box contains the AVR and provides ample space for the customers' wiring and gland arrangements. It has removable panels for easy access.
SHAFT & KEYSAll generator rotors are dynamically balanced to better than BS6861:Part 1 Grade 2.5 for minimum vibration in operation. Two bearing generators are balanced with a half key.
INSULATION/IMPREGNATIONThe insulation system is class 'H', and meets the requirements of UL1446.All wound components are impregnated with materials and processes designed specifically to provide the high build required for static windings and the high mechanical strength required for rotating components.
QUALITY ASSURANCEGenerators are manufactured using production procedures having a quality assurance level to BS EN ISO 9001.
NOTE ON REGULATIONThe stated voltage regulation may not be maintained in the presence of certain radio transmitted signals. Any change in performance will fall within the limits of Criteria 'B' of EN 61000-6-2:2001. At no time will the steady-state voltage regulation exceed 2%.
DE RATESAll values tabulated on page 8 are subject to the following reductions
5% when air inlet filters are fitted.10% when IP44 Filters are fitted.3% for every 500 metres by which the operating altitude exceeds 1000 metres above mean sea level.3% for every 5°C by which the operational ambient temperature exceeds 40°C. Note: Requirement for operating in an ambient temperature exceeding 60°C must be referred to the factory.
Note: Continuous development of our products entitles us to change specification details without notice, therefore they must not be regarded as binding.
Front cover drawing is typical of the product range.
2
NITIN
CORPORATIO
N
AP
PR
OV
ED
DO
CU
ME
NT
CONTROL SYSTEM SEPARATELY EXCITED BY P.M.G.
A.V.R. MX341 MX321
VOLTAGE REGULATION ± 1% ± 0.5 % With 4% ENGINE GOVERNING
SUSTAINED SHORT CIRCUIT
INSULATION SYSTEM
PROTECTION
RATED POWER FACTOR
STATOR WINDING
WINDING PITCH
WINDING LEADS
MAIN STATOR RESISTANCE
MAIN ROTOR RESISTANCE
EXCITER STATOR RESISTANCE
EXCITER ROTOR RESISTANCE
R.F.I. SUPPRESSION BS EN 61000-6-2 & BS EN 61000-6-4,VDE 0875G, VDE 0875N. refer to factory for others
WAVEFORM DISTORTION NO LOAD < 1.5% NON-DISTORTING BALANCED LINEAR LOAD < 5.0%
MAXIMUM OVERSPEED 2250 Rev/Min
BEARING DRIVE END BALL. 6232 C3
BEARING NON-DRIVE END BALL. 6319 C3
1 BEARING 2 BEARING
WEIGHT COMP. GENERATOR
WEIGHT WOUND STATOR
WEIGHT WOUND ROTOR
WR² INERTIA
SHIPPING WEIGHTS in a crate
PACKING CRATE SIZE
TELEPHONE INTERFERENCE
COOLING AIR
VOLTAGE STAR 380/220 400/231 415/240 440/254 416/240 440/254 460/266 480/277
kVA BASE RATING FOR REACTANCE VALUES 2020 2080 2080 2040 2345 2500 2550 2600
REACTANCES ARE SATURATED VALUES ARE PER UNIT AT RATING AND VOLTAGE INDICATED
T'd TRANSIENT TIME CONST. 0.154sT''d SUB-TRANSTIME CONST. 0.02sT'do O.C. FIELD TIME CONST. 2.54s
Ta ARMATURE TIME CONST. 0.02s
SHORT CIRCUIT RATIO 1/Xd
REFER TO SHORT CIRCUIT DECREMENT CURVES (page 7)
WINDING 312
DOUBLE LAYER LAP
2.31 Ohms at 22°C
0.8
IP23
CLASS H
0.00076 Ohms PER PHASE AT 22°C STAR CONNECTED
6
TWO THIRDS
PI734F
2.69 m³/sec 5700 cfm 3.45 m³/sec 7300 cfm
50 Hz
THF<2%
60 Hz
TIF<50
3807 kg
48.424 kgm2
216 x 105 x 154(cm)
1565 kg1609 kg
216 x 105 x 154(cm)
49.3409 kgm2
3913kg 3876kg
1908 kg
3840 kg
1908 kg
17.5 Ohms at 22°C
0.063 Ohms PER PHASE AT 22°C
3
NITIN
CORPORATIO
N
AP
PR
OV
ED
DO
CU
ME
NT
Winding 312PI734F
THREE PHASE EFFICIENCY CURVES
50Hz
4
NITIN
CORPORATIO
N
AP
PR
OV
ED
DO
CU
ME
NT
Winding 312PI734F
THREE PHASE EFFICIENCY CURVES
60Hz
5
NITIN
CORPORATIO
N
AP
PR
OV
ED
DO
CU
ME
NT
PI734FWinding 312
Locked Rotor Motor Starting Curve
0
5
10
15
20
25
30
0 1000 2000 3000 4000 5000 6000 7000LOCKED ROTOR kVA
PER
CEN
T TR
AN
SIEN
T VO
LTA
GE
DIP
.
380V 416V 440V 460V 480V
0
5
10
15
20
25
30
0 1000 2000 3000 4000 5000 6000LOCKED ROTOR kVA
PER
CEN
T TR
AN
SIEN
T VO
LTA
GE
DIP
.
346V 380V 400V 415V 440V 50Hz
60Hz
6
NITIN
CORPORATIO
N
AP
PR
OV
ED
DO
CU
ME
NT
3-phase 2-phase L-L 1-phase L-NVoltage Factor Voltage Factor x 1.00 x 0.87 x 1.30
380v x 1.00 416v x 1.00 x 1.00 x 1.80 x 3.20400v x 1.05 440v x 1.06 x 1.00 x 1.50 x 2.50415v x 1.09 460v x 1.10 10 sec. 5 sec. 2 sec.440v x 1.16 480v x 1.15
Minimum
Winding 312
50Hz 60Hz
PI734F
The sustained current value is constant irrespectiveof voltage level
Three-phase Short Circuit Decrement Curve. No-load Excitation at Rated SpeedBased on star (wye) connection.
Max. sustained durationAll other times are unchanged
Instantaneous
Sustained
Sustained Short Circuit = 6,850 Amps
Sustained Short Circuit = 8,900 AmpsNote 1The following multiplication factors should beused to adjust the values from curve betweentime 0.001 seconds and the minimum currentpoint in respect of nominal operating voltage :
Note 2The following multiplication factor should be used to convert thevalues calculated in accordance with NOTE 1 to those applicableto the various types of short circuit :
Note 3Curves are drawn for Star (Wye) connected machines.
Cont. F - 105/40°C Cont. H - 125/40°C Standby - 150/40°C Standby - 163/27°C
Winding 312 / 0.8 Power Factor
RATINGS
50Hz
60Hz
8
NITIN
CORPORATIO
N
AP
PR
OV
ED
DO
CU
ME
NT
PI7F-312-TD-EN-SG-A
Head Office Address:Barnack Road, StamfordLincolnshire, PE9 2NB
United KingdomTel: +44 (0) 1780 484000Fax: +44 (0) 1780 484100
www.cumminsgeneratortechnologies.com
Copyright 2010, Cummins Generator Technologies Ltd, All Rights ReservedStamford and AvK are registered trade marks of Cummins Generator Technologies Ltd
Cummins and the Cummins logo are registered trade marks of Cummins Inc.