Top Banner
Blas Hermoso Cartagena (Colombia) 6-8 April 2016 Lightning Protection of Structures BHA 1
23

Lightning Protection of Structures...Edition 2.0. 2010-12 - IEC 62305-4 Protection against lightning. Pat 4: Electrical and electronic systems within structures. Edition 2.0. 2010-12;

Mar 04, 2021

Download

Documents

dariahiddleston
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: Lightning Protection of Structures...Edition 2.0. 2010-12 - IEC 62305-4 Protection against lightning. Pat 4: Electrical and electronic systems within structures. Edition 2.0. 2010-12;

Blas Hermoso

Cartagena (Colombia)

6-8 April 2016

Lightning Protection of Structures

BHA1

Page 2: Lightning Protection of Structures...Edition 2.0. 2010-12 - IEC 62305-4 Protection against lightning. Pat 4: Electrical and electronic systems within structures. Edition 2.0. 2010-12;

MCR

110 kV

Data

TV

Telephone

400/230 V

ABC Company

Mobile phone

1320e.ppt / 07.03.02 / ESC1320e_c

Impact of Lightning

BHA 2

Page 3: Lightning Protection of Structures...Edition 2.0. 2010-12 - IEC 62305-4 Protection against lightning. Pat 4: Electrical and electronic systems within structures. Edition 2.0. 2010-12;

Standards - References

- IEC 62305-1 Protection against lightning. Pat 1: General principles. Edition 2.0. 2010-12

- IEC 62305-2 Protection against lightning. Pat 2: Risk management. Edition 2.0. 2010-12

- IEC 62305-3 Protection against lightning. Pat 3: Physical damage to structure and life hazard.

Edition 2.0. 2010-12

- IEC 62305-4 Protection against lightning. Pat 4: Electrical and electronic systems within structures.

Edition 2.0. 2010-12;

- IEC 62858 Lightning density based on lightning location systems (LLS) – General principles. Edition

1.0. 2015-08;

- EN 50536 Protection against lightning-Thunderstorm warning systems, May 2011

- IEC 61400-24 Wind turbines – Part 24: Lightning protection. 2010-6

BHA

3

Page 4: Lightning Protection of Structures...Edition 2.0. 2010-12 - IEC 62305-4 Protection against lightning. Pat 4: Electrical and electronic systems within structures. Edition 2.0. 2010-12;

Protection Measures IEC 62305-1

7.1 Protection measures may be adopted in order to reduce the type of damage

7.2 Protection measures to reduce injury of living being by electricshock;

7.3 Protection measures to reduce physical damage;

7.4 Protection measures to reduce failure of electrical and electronic systems

BHA

4

Page 5: Lightning Protection of Structures...Edition 2.0. 2010-12 - IEC 62305-4 Protection against lightning. Pat 4: Electrical and electronic systems within structures. Edition 2.0. 2010-12;

7.2 Protection measures to reduce injury of living being by electric shock;

- adequate insolation of exposed

conductive parts;

- equipotentialization by means of a

- mashed earthing system;

- physical restriction and warning notices;

- lightning equipotential bonding (EB)

BHA5

Page 6: Lightning Protection of Structures...Edition 2.0. 2010-12 - IEC 62305-4 Protection against lightning. Pat 4: Electrical and electronic systems within structures. Edition 2.0. 2010-12;

7.3 Protection measures to reduce physical damage;

Protection is achieved by the lightning protection system (LPS)

which includes the following features:

- air-termination system;

- down conductor system;

- earth termination system;

- lightning equipotential bonding (EB);

- electrical insulation (and hence

separation distancie) against the

external LPS

BHA6

Page 7: Lightning Protection of Structures...Edition 2.0. 2010-12 - IEC 62305-4 Protection against lightning. Pat 4: Electrical and electronic systems within structures. Edition 2.0. 2010-12;

7.4 Protection measures to reduce failure of electrical and electronic systems

Possible protection measures (SPM) include:

- earthing and bonding measures;

- magnetic shielding;

- line routing;

- Isolating interfaces;

- coordinated SPD systemsBHA 7

Page 8: Lightning Protection of Structures...Edition 2.0. 2010-12 - IEC 62305-4 Protection against lightning. Pat 4: Electrical and electronic systems within structures. Edition 2.0. 2010-12;

Protection measures shall be designed according with the

Lightning Protection Level (LPL)

- for the purposes of standard 62305 four LPL (I-IV) are

introduced;

- for each LPL a set of máximum and mínimum lightning

current parameters is fixed;

BHA8

Page 9: Lightning Protection of Structures...Edition 2.0. 2010-12 - IEC 62305-4 Protection against lightning. Pat 4: Electrical and electronic systems within structures. Edition 2.0. 2010-12;

BHA

Maximum values of lightning parameters according to LPL

LPL I shall be not exceded, with a probability of 99%;

LPL II probability of 75%;

LPL III and LPL IV probability of 50%;

used to design lightning protection components:

- cross-section of conductors;- thickness of metal sheets;- current capability of SPDs;- separation distancie against dangerous sparking;- to define test parameters simulating the effects of lightning on suchcomponents (see Annex D)

9

Page 10: Lightning Protection of Structures...Edition 2.0. 2010-12 - IEC 62305-4 Protection against lightning. Pat 4: Electrical and electronic systems within structures. Edition 2.0. 2010-12;

Maximum values of lightning parameters according to LPL

BHA10

Page 11: Lightning Protection of Structures...Edition 2.0. 2010-12 - IEC 62305-4 Protection against lightning. Pat 4: Electrical and electronic systems within structures. Edition 2.0. 2010-12;

BHA

Minimum values of lightning parameters and relatedrolling sphere radius corresponding to LPL

The mínimum values are used to derive the

rolling sphere radius in order to define the

lightning protection zone LPZ 0B which cannotbe riched by direct strike.

11

Page 12: Lightning Protection of Structures...Edition 2.0. 2010-12 - IEC 62305-4 Protection against lightning. Pat 4: Electrical and electronic systems within structures. Edition 2.0. 2010-12;

12

286,95m

72m

260m

225m

BHA

CRANE

Page 13: Lightning Protection of Structures...Edition 2.0. 2010-12 - IEC 62305-4 Protection against lightning. Pat 4: Electrical and electronic systems within structures. Edition 2.0. 2010-12;

13BHA

S1: flashes to the structure; S2: flashes near the structure

S3: flashes to the lines connectedto the structure

S4: flashes near the lines connectedto the structure.

According with IEC 62305-1, (5.1.2), the following situations shall be taken into account, depending on the position of the point of strike relative to the structure considered:

Page 14: Lightning Protection of Structures...Edition 2.0. 2010-12 - IEC 62305-4 Protection against lightning. Pat 4: Electrical and electronic systems within structures. Edition 2.0. 2010-12;

14

BHA

Producing three basic type of damage:

D1: injury to living beings by electric shock;

D2: physical damage (fire, explosión, mechanical destruction, chemicalrealise) due to lightning current effects, incluiding sparking;

D3: failure of internal systems due to LEMP.

Page 15: Lightning Protection of Structures...Edition 2.0. 2010-12 - IEC 62305-4 Protection against lightning. Pat 4: Electrical and electronic systems within structures. Edition 2.0. 2010-12;

15

And the following types of loss:

L1: loss of human life (incluiding permanent injury);

L2: loss of service to the public;

L3: loss of cultural heritage;

L4: loss of economic value (structure, its content, and loss of activity)

Page 16: Lightning Protection of Structures...Edition 2.0. 2010-12 - IEC 62305-4 Protection against lightning. Pat 4: Electrical and electronic systems within structures. Edition 2.0. 2010-12;

16BHA

Areas of probable lightning strike (red), LPL I, sphere 20m

Page 17: Lightning Protection of Structures...Edition 2.0. 2010-12 - IEC 62305-4 Protection against lightning. Pat 4: Electrical and electronic systems within structures. Edition 2.0. 2010-12;

17

72

m

225m

3x286,95m

260m

286,95m

75º

18,73m

879,58m

BHA

879,58m

Collection Area AD

AD =π.879,58m^2=2,43.10^6m^2

NG=2,2

CD=1 (Isolated structure:

no other objects in the vecinity)

ND = NGx ADx CD = 5,35

Number of dangerous events ND

IEC 62305-2 (A.2.4)

Page 18: Lightning Protection of Structures...Edition 2.0. 2010-12 - IEC 62305-4 Protection against lightning. Pat 4: Electrical and electronic systems within structures. Edition 2.0. 2010-12;

18

BHA

Collection Area AM: Flashes strinking near the structures (m^2)

879,58m

In this case Area AM (500m) is incluided in AD (879,58m)

IEC 62305-2 (A.3)

Page 19: Lightning Protection of Structures...Edition 2.0. 2010-12 - IEC 62305-4 Protection against lightning. Pat 4: Electrical and electronic systems within structures. Edition 2.0. 2010-12;

19

If applicable, by analogy, the Standard IEC 61400-24: Wind

Turbines - Part 24: Lightning Protection, the Collection Area AM

became a 250m wide circular crown

BHA

879,58

m250m

1129,58m

Page 20: Lightning Protection of Structures...Edition 2.0. 2010-12 - IEC 62305-4 Protection against lightning. Pat 4: Electrical and electronic systems within structures. Edition 2.0. 2010-12;

20

lvlvlr

D

Fundation

Crane

h

2a

Conections to ringEquipotentialbonding

BHA

Earthing System (LPS 1)

Has been adopted a

B configuration with a

ring diameter D =2re ≥

if not lr = l1 – relv =( l1 – re)/2

lr

l1

2l1

Page 21: Lightning Protection of Structures...Edition 2.0. 2010-12 - IEC 62305-4 Protection against lightning. Pat 4: Electrical and electronic systems within structures. Edition 2.0. 2010-12;

21BHA

CRANE

Power Supply

Page 22: Lightning Protection of Structures...Edition 2.0. 2010-12 - IEC 62305-4 Protection against lightning. Pat 4: Electrical and electronic systems within structures. Edition 2.0. 2010-12;

22BHA

30m<10m

Crane

Variable speed

Screened

cable

Page 23: Lightning Protection of Structures...Edition 2.0. 2010-12 - IEC 62305-4 Protection against lightning. Pat 4: Electrical and electronic systems within structures. Edition 2.0. 2010-12;

23

BHA

Conclusions

Has been selected:

- Lightning Protection Level I

- Air termination formed with wires

- Earthing System type B

- Power suply inside the structures

- DPS type I at the entry of variable speed

- DPS type II at the entry of motor