Top Banner

of 117

Liebert PEX - Compressor Models User Manual - AP11ENT-PEXCompModelsV1-UM

Jul 07, 2018

Download

Documents

Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
  • 8/18/2019 Liebert PEX - Compressor Models User Manual - AP11ENT-PEXCompModelsV1-UM

    1/117

    Next Generation Critical Coolingfor Room and Row

    Liebert PEXEfciency And Reliability For High Availability Cooling

    Compressor ModelsUser Manual

  • 8/18/2019 Liebert PEX - Compressor Models User Manual - AP11ENT-PEXCompModelsV1-UM

    2/117

    Liebert PEX Series Air Conditioner 

    User Manual

    Version V1.4

    Revision date July 27, 2010

    BOM 31011774

    Emerson Network Power provides customers with technical support. Users may contact the

    nearest Emerson local sales office or service center.

    Copyright © 2010 by Emerson Network Power Co., Ltd.

    All rights reserved. The contents in this document are subject to change without notice.

    Emerson Network Power Co., Ltd.

    Address: No.1 Kefa Rd., Science & Industry Park, Nanshan District 518057, Shenzhen China

    Homepage: www.emersonnetworkpower.com.cn

    E-mail: [email protected]

  • 8/18/2019 Liebert PEX - Compressor Models User Manual - AP11ENT-PEXCompModelsV1-UM

    3/117

  • 8/18/2019 Liebert PEX - Compressor Models User Manual - AP11ENT-PEXCompModelsV1-UM

    4/117

    Contents

    Chapter 1 Overview........................................................................................................................................................... 1

    1.1 Model Description............................................................................................................................................... 1

    1.2 Product Introduction ........................................................ ............................................................ ...................... 2

    1.3 Product Appearance........................................................................................................................................... 3

    1.4 Main Components............................................................................................................................................... 3

    1.4.1 Indoor Unit ............................................................ ............................................................ ....................... 4

    1.4.2 Outdoor Unit .......................................................... ............................................................ ...................... 4

    1.4.3 iCOM Controller ........................................................... ............................................................... ............. 5

    1.4.4 Remote Monitoring Software.................................................................................................................. 5

    1.5 Environmental Requirements .................................................... ........................................................... ............. 5

    1.5.1 Operating Environment........................................................................................................................... 51.5.2 Storage Environment ...................................................... ........................................................... ............. 5

    Chapter 2 Mechanical Installation ........................................................... ........................................................... ............. 6

    2.1 Movement, Unpacking And Inspection................ ........................................................... .................................. 6

    2.1.1 Transportation And Movement............................................................................................................... 6

    2.1.2 Unpacking ........................................................ ........................................................ ................................ 6

    2.1.3 Inspection................................................................................................................................................. 8

    2.2 Installation Notes................................................................................................................................................ 8

    2.3 System Installation Arrangement...................................................................................................................... 8

    2.3.1 Overall System Arrangement .......................................................... .................................................... ... 8

    2.3.2 System Installation Illustration........................................................... .................................................. 11

    2.3.3 Mechanical Parameters.......................................... .......................................................... ..................... 12

    2.4 Installing Indoor Unit ...................................................... ............................................................. ..................... 20

    2.4.1 Equipment Room Requirement......................................................... ................................................... 20

    2.4.2 Installation Space ........................................................ ..................................................... ..................... 20

    2.4.3 Requirement Of Maintenance Space ....................................................... ............................................ 21

    2.4.4 Installation Procedures............................................................. ........................................................ .... 22

    2.5 Installing Outdoor Unit ..................................................... ........................................................... ..................... 25

    2.6 Piping................................................................................................................................................................. 25

    2.6.1 Piping For Air-Cooled Unit.................................................... ............................................................ .... 25

    2.6.2 Piping For Water-Cooled Unit................................................... ........................................................... . 292.7 Lowering Fan And Removing Fixtures (Downflow EC Fan System) ....................................................... ..... 30

    2.7.1 Downflow Unit EC Fan Lowering............................................................................... ........................... 30

    2.7.2 Removing Transport Fastener And Vibration Absorber ..................................................... ............... 33

    2.8 Installation Inspection...................................................... .......................................................... ...................... 36

    Chapter 3 Electrical Installation................... ....................................................... ........................................................... 37

    3.1 Work Introduction And Installation Notes ............................................................... ....................................... 37

    3.2 Wiring Of Indoor Unit............................................. ............................................................ ............................... 37

    3.2.1 Locating Electrical Interface Of Indoor Unit.................. ........................................................... ........... 37

    3.2.2 Connecting Power Cable Of Indoor Unit ............................................................. ................................ 38

    3.2.3 Connecting Control Cables ...................................................... ......................................................... ... 39

  • 8/18/2019 Liebert PEX - Compressor Models User Manual - AP11ENT-PEXCompModelsV1-UM

    5/117

    3.2.4 Connecting Solenoid Valve Of Pipe Extension Kit (Options, For Site Installation) ......................... 40

    3.3 Wiring Of Outdoor Unit (For Air-Cooled Series)....................................................................... ...................... 40

    3.3.1 Connecting Control Signal Cables Of Outdoor Unit......................................... .................................. 40

    3.3.2 Connecting Power Cables Of Outdoor Unit ........................................................ ................................ 413.4 Installation Inspection...................................................... .......................................................... ...................... 41

    Chapter 4 System Power-On Commissioning ............................................................ .................................................. 42

    4.1 Location Of MCBs....................... ............................................................ ......................................................... . 42

    4.2 Power-On Commissioning Of Air-Cooled Series ..................................................... ...................................... 43

    4.2.1 Preparation Before Commissioning ....................................................... ............................................. 43

    4.2.2 Commissioning Procedures..................................................... .......................................................... .. 44

    4.2.3 Inspection After Commissioning ................................................... ...................................................... 45

    4.3 Power-On Commissioning Of Water-Cooled Series ...................................................... ................................ 46

    4.3.1 Preparation Before Commissioning ....................................................... ............................................. 46

    4.3.2 Commissioning Procedures..................................................... ........................................................... . 474.3.3 Inspection After Commissioning ........................................................ ................................................. 48

    Chapter 5 iCOM Controller ....................................................... ................................................................ ...................... 49

    5.1 LCD ................................................... ....................................................... .......................................................... 49

    5.2 Button And Indicator Panel.................................... ........................................................... ............................... 49

    5.3 Structure Chart Of Control Menu......................................................... ......................................................... ... 51

    5.4 Startup Interface ..................................................... .................................................................... ...................... 51

    5.5 Main Interface.......................................................... ........................................................... ............................... 51

    5.6 USER MENUS................................................................ .............................................................. ...................... 52

    5.6.1 PASSWORD ....................................................... ........................................................ ............................ 52

    5.6.2 SETPOINTS.................................................... ........................................................ ................................ 52

    5.6.3 EVENT LOG.............................. ............................................................ .................................................. 52

    5.6.4 GRAPHICS......................................... ........................................................... .......................................... 54

    5.6.5 SET ALARMS.................................................... ........................................................... .......................... 54

    5.6.6 SENSOR DATA ...................................................... ........................................................... ..................... 55

    5.6.7 DISPLAY SETUP............................................................ ........................................................... ............. 56

    5.6.8 TOTAL RUN HRS ............................................................ ........................................................... ............ 57

    5.6.9 SLEEP MODE......................................................... ........................................................... ..................... 58

    5.6.10 SERVICE INFO .......................................................... ............................................................... ............ 58

    5.6.11 ACTIVE ALARMS....... ....................................................... ............................................................... .... 58

    5.7 SERVICE MENUS....................................................... ................................................................. ...................... 585.7.1 PASSWORD LEVEL........................................................ ............................................................ ........... 59

    5.7.2 SETPOINTS......................................................... .............................................................. ..................... 59

    5.7.3 STANDBY.............................................................. ........................................................... ...................... 60

    5.7.4 WELLNESS........................................................................... ............................................................... ... 60

    5.7.5 DIAGNOSTICS............................................ ................................................................ ............................ 63

    5.7.6 SET ALARMS................................................ ....................................................... .................................. 65

    5.7.7 CALIBRATION....... ........................................................... ........................................................... ........... 67

    5.7.8 NETWORK SETUP ............................................................ ......................................................... ............ 67

    5.7.9 OPTIONS SETUP ............................................................ .......................................................... ............. 68

    5.7.10 SERVICE INFO ..................................................... ........................................................... .....................69

    5.8 ADVANCED MENUS........................................................ ............................................................. ..................... 69

  • 8/18/2019 Liebert PEX - Compressor Models User Manual - AP11ENT-PEXCompModelsV1-UM

    6/117

    5.8.1 PASSWORD LEVEL......................................................... ........................................................... ........... 69

    5.8.2 FACTORY SETUP ............................................................ .......................................................... ............ 70

    5.9 MBV Settings........................................ ........................................................... .................................................. 74

    5.10 EVENT NAME AND DEFINITION ............................................................... ..................................................... 75

    Chapter 6 Application Of INTELLISLOT............................................................ .......................................................... .. 79

    6.1 Introduction Of Host Communication Cards................................................................... ............................... 79

    6.2 Installation Of Host Communication Cards............................................................ ........................................ 79

    6.3 Commission Of Host Communication Component......................................................... ............................... 80

    6.3.1 Setting HyperTerminal ..................................................... ......................................................... ............ 80

    6.3.2 Setting 485 Communication Card ...................................................... .................................................. 82

    6.3.3 Setting TCP/IP Communication Card............................. ........................................................... ........... 83

    6.3.4 Setting SNMP Parameters Of TCP/IP Communication Card........................................................ ...... 85

    6.4 Host Communication Networking Diagram.............................................................. ...................................... 88

    Chapter 7 System Operation And Maintenance ......................................................... .................................................. 89

    7.1 System Diagnosing Test .......................................................... .................................................... .................... 89

    7.1.1 Self-diagnosis Function...................................................... ...................................................... ............ 89

    7.1.2 Electric Control Part................................................................. .......................................................... ... 89

    7.2 Filter ..................................................... ........................................................... ................................................... 91

    7.3 Fan Components............................................................................. ....................................................... ........... 91

    7.3.1 FC Fan ................................................... ........................................................... ...................................... 91

    7.3.2 EC Fan .......................................................... ............................................................ .............................. 91

    7.4 Infrared Humidifier.................................... ........................................................... ............................................. 91

    7.5 Electric Heater..................................... ........................................................... ................................................... 93

    7.6 Cooling System........................... ........................................................... .......................................................... . 94

    7.6.1 Suction Pressure................................................... ........................................................... ..................... 94

    7.6.2 Discharge Pressure...... ........................................................... .......................................................... .... 94

    7.6.3 Suction Superheat Degree.......................... ........................................................... ............................... 95

    7.6.4 Thermal Expansion Valve ......................................................... ........................................................... . 95

    7.6.5 Hot Gas Bypass Valve (For Single Compressor System) ............................................................ ...... 95

    7.6.6 Air-Cooled Condenser........................................................................................ ................................... 96

    7.6.7 Water-Cooled Condenser.............................................................................. ........................................ 96

    7.6.8 Compressor ................................................... ........................................................... ............................. 96

    Chapter 8 Troubleshooting ............................................................ .......................................................... ...................... 98

    Appendix 1 Composition Of Electrical Control Box.................................................................. ................................. 105

    Appendix 2 Circuit Diagram ................................................... ................................................................. ..................... 107

    Appendix 3 Menu Structure Of iCOM Controller ........................................................... ............................................. 108

  • 8/18/2019 Liebert PEX - Compressor Models User Manual - AP11ENT-PEXCompModelsV1-UM

    7/117

  • 8/18/2019 Liebert PEX - Compressor Models User Manual - AP11ENT-PEXCompModelsV1-UM

    8/117

  • 8/18/2019 Liebert PEX - Compressor Models User Manual - AP11ENT-PEXCompModelsV1-UM

    9/117

    2 Chapter 1 Overview

    Liebert PEX Series Air Conditioner User Manual

    1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25

    P 2 0 5 0 D A S 3 J H L 1 2 4 1 0 0 0 0 P 0 0 0 0

    Digit1 Model Range Digit16 Enclosure options

    P P EX 1 S tandard C olor Charcoal grey

    Digit2 Modules 2 C olo ur S pe cia l c olo r  

    2 Num ber of Modules/B ays 6 C olor C harcoal grey w /Double skin

    Digit3 Cooling Capacity kW Digit17 Mains Switch High Voltage Option

    Nom inal G ross Cooling C apacity - kW 0 N oneDigit4 Cooling Capacity kW D M a in n on -L oc ki ng D is co nn ec t

    Nominal Gross Cooling Capacity - kW Digit18 Lock Out Low Voltage Option

    Digit5 Cooling Capacity kW 0 N one

    Nom inal G ross C ooling C apacity - kW H R eheat & Hum idity Lockout

    Digit6 Air Discharge Digit19 Monitoring

    U Upflow 0 M onitoring - N o C ard

    D Dow nflow 1 M onitoring - IS W E B only

    Digit7 System Type 2 M on ito rin g - T wo IS W EB

     A Ai r c oo le d 3 Mo ni to rin g - I S4 85 on ly

    W W ate r co ole d 4 M on ito rin g - T wo IS 48 5

    G G lycol Cooled 5 M onitoring - IS W EB & IS485

    D D ua l C o ol - c hi lle d w at er + a ir c oo le d 6 M o ni to ri ng - i CO M D O

    H D u a l C o o l - c h il le d w a te r + w a te r c o ol ed D M o n it or in g - I SW E B & i C OM D O

    F Free cool E Monitoring - Two ISW EB & iC OM D O

    C C hilled W ater F Monitoring - IS485 & iCO M DO

    R C h il le d W a te r - D u al S o ur ce G M on it or in g T w o I S4 85 & iC O M D O

    Digit8 Airflow H M on it or in g - I SW E B & IS 4 85 & iC O M DO

    1 E C Plu g fa n - St an da rd St at ic Digit20 Sensors

    S Forward C urved fan - S tandard Static 0 None

    Digit9 Power Supply S Sm oke Senso r  

    3 400V / 3ph / 50H z+N H High Temperature

    T 3 80 V / 3 ph / 6 0H z N H ot a nd C old Is le S en so r A & S en so r B ( In addition to Standard Sensor)

     A 46 0V / 3 ph / 6 0H z F Sm ok e & Hi gh Te mp

    Digit10 Cooling System Digit21 Packaging

    C C om pliant S cro ll S ingle C ircu it R 407C P P ackaging - S tandard

    S Com pliant S cro ll D ual C ircu it R 407C C P ackag ing - W ooden crate Export

    E D ig it al S c ro ll S in g le C i rc u it R 4 07 C Digit22 Special Requirements

    D Digita l Scro ll D ual C ircu it R407C A S FA - none

    J C om pliant Scro ll S ingle C ircu it R 22 Z For Internal U se Only(For Austra lia and N ew zealand)

    F Com pliant S cro ll D ual C ircu it R22 T For Internal U se On ly(C hina Telecom )

    2 CW Tw o way Valves S tandard P ressure C For Internal U se O nly(C hat U nion)

    3 C W T hr e e w a y V a lv es St an d ar d P r es su re Digit23 Order Identifier 

    Digit11 Humidification 0 N one

    0 None 1 H igh ES P 100 P a

    H Infrared H um idifier 2 H igh ES P 200 P a

    S Electrode hum idifier 3 H igh A irflow/E SP other  

    Digit12 Display X S FA Included

    S S ma ll Dis pla y 1 TH S en so r   Digit24 Order Identifier 

    L Large D isplay 1 TH sensor 0 N one

    Digit13 Re-Heating L A ir Co o le d -L o n g P ip e Ru n Ki t> 3 0 m e te rs

    0 None X S FA Included

    1 E le ct ri c h ea ti ng S td 1 S ta ge Digit25 Order Identifier 

    2 E lectric heating O pt. 2 Stage U p 0 N one

    Digit14 Filtration X S FA Included

    2 G 4 ( EU 4 ) gr av im e tr ic ( re f M ER V 8 ) + C lo g g ed F i lt er  

    3 F 5 ( E U5 ) d u st s po t + Cl og g ed F il te r  

    Digit15 Coil and Valves

    S Standard DX Ai r Coo led Co i l

    4 Coi l DX - Al l va lves High Pressure MBV,DX - 2 way, CW co i l 2 way

    K Coi l DX - Al l va lves High Pressure MBV,DX - 3 way, CW co i l 3 way

    N Coi l DX - Al l va lves High Pressure MBV,DX - 2 way, CW co i l 3 way

    P Coi l DX - Al l va lves High Pressure MBV, DX - 3 way,CW co i l 2 way

    0- 9

    0- 9

    0- 9

     

    Figure 1-1 Model description

    1.2 Product Introduction

    The Liebert PEX series air conditioner is a medium-large sized precision environment control system, which

    is suitable for the environment control of the equipment room or computer room. It aims to provide a sound

    operating environment for precision equipment, such as sensitive equipment, industry processing equipment,

    communication equipment and computers.

    The Liebert PEX series air conditioner features high reliability, high sensible heat ratio and large airflow. It is

    configured with an infrared humidifier adjustable to different water qualities, and is compatible with R407C

    green refrigerant to meet the international requirement.

  • 8/18/2019 Liebert PEX - Compressor Models User Manual - AP11ENT-PEXCompModelsV1-UM

    10/117

    Chapter 1 Overview 3

    Liebert PEX Series Air Conditioner User Manual

    The unit is classified into dual cooling system, single source cooling system and free cool system in the light

    of the function module. All kinds of different function systems can use the forward centrifugal curved fan (FC

    fan for short) and the speed adjustable DC electronically commutated fan (EC fan for short).

    Dual cooling system

    The unit contains the compressor refrigerating system and the chilled-water system. The control board can

    select whether to run under the compressor refrigerating system or the chilled-water system flexibly

    according to the connected chilled-water condition and the indoor load, so as to achieve the energy-saving

    operation of the unit.

    Single source cooling system

    The unit contains the compressor refrigerating system only.

    Free cool system

    The unit contains the compressor refrigerating system and the free cool system. Free cool system can be

    connected with the special dry cooler. Under the conditions of the low outdoor temperature, the unit can

    select whether to run under the compressor refrigerating system or the free cool system flexibly according to

    the free cool medium condition provided by dry cooler and the indoor load, so as to achieve the

    energy-saving operation of the unit. According to the cooling mode of the refrigerant side, the unit contains

    the air-cooled series and the water-cooled series.

    Air-cooled series

    The Liebert PEX air-cooled series air conditioner comprises indoor unit and outdoor unit. With the standard

    configuration of Liebert PEX condenser unit, it can reduce noise pollution to the minimum while meeting

    system cooling requirement through the pressure regulating the fan speed. The Liebert PEX low temperature

    CS (D) F_S series outdoor unit can also be configured for it, qualifying the system to normally operate in

    cooling mode at the temperature down to -84.2°F. Please consult Emerson Network Power Co., Ltd. (Emerson

    for short) if the lower temperature is required.

    Water-cooled series

    The Liebert PEX water-cooled series air conditioner uses integrated structure and highly effective

    brazed-plate heat exchanger (BPHE), thus it is compact, efficient and quiet.

    1.3 Product Appearance

    Taking the two-bay unit of FC fan for example, the appearance of the Liebert PEX series air conditioner is

    shown in Figure 1-2.

    Downf lowUpf low

    Figure 1-2 Appearance (two-bay unit)

    1.4 Main Components

    The main components of Liebert PEX air conditioner include indoor unit, outdoor unit and iCOM controller.

  • 8/18/2019 Liebert PEX - Compressor Models User Manual - AP11ENT-PEXCompModelsV1-UM

    11/117

    4 Chapter 1 Overview

    Liebert PEX Series Air Conditioner User Manual

    1.4.1 Indoor Unit

    The indoor unit of the Liebert PEX air conditioner includes compressor, evaporator, thermal expansion valve,

    infrared humidifier, fan, electric heater, sight glass and filter drier. Besides these components, the

    water-cooled series indoor unit also includes BPHE and electric valve.

    Compressor

    The highly effective Copeland scroll compressor is used, featuring low vibration, low noise and high reliability.

    The Rotalock connection mode makes the maintenance easier.

    Evaporator

    The finned tube evaporator with high heat dissipation efficiency is used. The distributor is designed and

    validated according to specific model to ensure that the refrigerant is distributed evenly in each loop,

    improving the evaporator efficiency to a great extent.

    Thermal expansion valve

    The external equalizer type thermal expansion valve is used. It can collect temperature and pressure signals

    at the same time, so that it can regulate the refrigerant flow more accurately.

    Infrared humidifier

    The infrared humidifier is designed with a simple structure, which is easy for teardown, cleaning and

    maintenance. Application of the infrared humidifier can reduce the dependence on water quality. It also

    features fast startup, short humidifying time, large humidifying capacity and high humidifying efficiency.

    Fan

    The forward centrifugal fan with high efficiency and high reliability can be used. It features large airflow, long

    blowing distance, belt transmission and convenient maintenance. Users can also select the EC fan, which

    features high efficiency, energy-saving, space-saving and low noise. EC fan unit uses elaborate structure

    design, and the downflow unit uses the ‘in-floor’ design, which positions the fan unit below the floor to further

    improve the efficiency of air supply.

    Electric heater 

    The spiral fin U-type stainless steel heater is used. It features fast heating speed and even heat.

    Sight glass

    The sight glass is the window of the system cycle, for observing the refrigerant state, mainly the moisture

    content of the system. When the moisture content exceeds the standard, the color will be changed.

    Filter drier 

    The filter drier eliminates the moisture effectively in the system, and also filtrates the impurities generated

    during the long-term system operation so as to ensure normal system operation.

    BPHE (for water-cooled series)

    The brazed plate auto-cleansing BPHE is used. It features compact structure and high heat exchanging

    efficiency. Rotalock connections are provided for water and refrigerant sides.

    Electric valve (for water-cooled series and chilled water system)

    Water-cooled series: The precise electric valve is used. The water flow in the BPHE can be regulated through

    the intelligent valve position control of the control board, so as to ensure stable system operation.

    Chilled water system: The electric valve provides proportional regulation of chilled water flow according to

    the cooling requirement.

    Union mode is used to connect the electric valve to the system pipeline, which is convenient for installation at

    site and maintenance, reducing the project installation expenses.

    1.4.2 Outdoor Unit

    The outdoor unit is applicable to the Liebert PEX air-cooled series air conditioner. For details, refer to LiebertPEX Condenser User Manual .

  • 8/18/2019 Liebert PEX - Compressor Models User Manual - AP11ENT-PEXCompModelsV1-UM

    12/117

    Chapter 1 Overview 5

    Liebert PEX Series Air Conditioner User Manual

    1.4.3 iCOM Controller

    The iCOM controller of the Liebert PEX series air conditioner uses the LCD screen with blue backlight and 128

    × 64 pixels, or selects the large screen with 320 × 240 pixels. The user interface operation is simple. The

    multi-level password protection can effectively prevent unauthorized operation. It also provides power failure

    auto-restoration and high & low voltage protection functions. The operation time of components is available

    through the menus. The expert-level fault diagnosis system can automatically display the current faultinformation, facilitating the maintenance. It can store up to 400 historical event records. There are two kinds

    of panels for option: one with common screen and the other with large screen, as shown in Figure 1-3.

    Common screen  Large screen

    Figure 1-3 Panel of iCOM controller

    1.4.4 Remote Monitoring Software

    Through the configured RS485 port or TCP/IP port, the Liebert PEX air conditioner can communicate with the

    host computer and receive the control of the host software.

    1.5 Environmental Requirements

    1.5.1 Operating Environment

    See Table 1-1 for operating environment requirement.

    Table 1-1 Operating environment requirement

    Item Requirement

    Ambient temperatureIndoor 0°C ~ 40°C

    Outdoor Water-cooled series: 4°C ~ 45°C; Air-cooled series:-48°C~ +45°C

    Protection level (outdoor unit) IP55

    Altitude

  • 8/18/2019 Liebert PEX - Compressor Models User Manual - AP11ENT-PEXCompModelsV1-UM

    13/117

    6 Chapter 2 Mechanical Installation

    Liebert PEX Series Air Conditioner User Manual

    Chapter 2 Mechanical Installation

    This chapter introduces the mechanical installation of the Liebert PEX series air conditioner, including the

    transportation, movement, unpacking, inspection, installation notes, system installation arrangement,

    installing indoor unit, installing outdoor unit, piping for unit, lowering fan, removing fixtures and installation

    inspection.

    2.1 Movement, Unpacking And Inspection

    2.1.1 Transportation And Movement

    Railroad transportation and shipping are the recommended means of transportation. If truck transportation is

    unavoidable, choose roads that are less bumpy in order to protect the equipment.

    The Liebert PEX series air conditioner is heavy (see Table 2-1 for the weight). It is recommended to use

    mechanical equipment such as an electric forklift to unload and move the equipment to the place closest to

    the installation site. If an electric forklift is used, insert the tines of the forklift below the pallet, as shown in

    Figure 2-1. Align the tines with the center of gravity to prevent the equipment from falling over.

     

    Figure 2-1 Inserting and movement

    When moving the indoor unit, keep the obliquity within the range from 75° to 105°, as shown in Figure 2-2.

    1   0   5       7     5     

    Figure 2-2 Moving obliquity of indoor unit

    2.1.2 Unpacking

    Move the equipment to the place closest to the final installation site and then unpack it.

    Follow the procedures below for unpacking:

  • 8/18/2019 Liebert PEX - Compressor Models User Manual - AP11ENT-PEXCompModelsV1-UM

    14/117

    Chapter 2 Mechanical Installation 7

    Liebert PEX Series Air Conditioner User Manual

    1. Remove the side panels and top cover 

    Liebert PEX series air conditioner uses the international packaging. You can use a hammer or straight

    screwdriver to straighten the connection hook that connects the side panels to the top cover, as shown in

    Figure 2-3.

     

    Figure 2-3 Straightening the hook

    At first, straighten all the hooks that fix side panel I, and remove side panel I. Then straighten all the hooks

    that fix side panel II, and remove side panel II. At last remove top cover III, as shown in Figure 2-4.

    Kg

    1790 x 950 x 2020mm

    1816 x 976 x 2175mm

    I

    I

    III

    II

    II

    Figure 2-4 Removing side panels and top cover 

    2. Remove the base pallet.

    The unit is fixed onto the base pallet with M8 × 65 fixing bolts, as shown in Figure 2-5. You can use a 17mm

    open-end spanner, ratchet spanner or sleeve to remove the fixing bolts.

    Fixing bolt on base pallet M8 6 5

    Figure 2-5 Fixing bolt on the base pallet 

  • 8/18/2019 Liebert PEX - Compressor Models User Manual - AP11ENT-PEXCompModelsV1-UM

    15/117

    8 Chapter 2 Mechanical Installation

    Liebert PEX Series Air Conditioner User Manual

    2.1.3 Inspection

    After receiving the product, you should unpack it, and then check against the packing list that the fittings are

    complete and that the components are intact. If any parts are found missing, or damaged, please report to the

    carrier immediately. If any defects are found, please report to the local offices of the carrier and the distributor.

    2.2 Installation Notes

    To achieve the designed performance and maximize the product life, the correct installation is vital. This

    section should be applied in conjunction with the prevailing industry standards of mechanical and electrical

    installation.

    1. The Liebert PEX air-cooled series air conditioner is designed for split floor installation. The indoor unit

    must be installed on the floor of the equipment room or computer room, and the outdoor unit can be installed

    outdoors or on the floor of other rooms. The Liebert PEX water-cooled series air conditioner is designed for

    integrated floor installation. It should be installed on the floor of the equipment room or computer room.

    2. Before installation, make sure that the installation environment meets the requirements (see 1.5

    Environmental Requirements) and confirm whether the building needs to be transformed to accommodate the

    construction work of piping, wiring layout and ventilation ducts.3. Follow the design drawings strictly when installing the equipment, and reserve the space for routine

    maintenance and servicing. The manufacturer’s engineering dimension drawings can serve as a reference.

    2.3 System Installation Arrangement

    2.3.1 Overall System Arrangement

    The Liebert PEX series air conditioner includes air-cooled series and water-cooled series, and their overall

    system arrangements are shown in Figure 2-6 and Figure 2-7 respectively.

  • 8/18/2019 Liebert PEX - Compressor Models User Manual - AP11ENT-PEXCompModelsV1-UM

    16/117

    Chapter 2 Mechanical Installation 9

    Liebert PEX Series Air Conditioner User Manual

    Chil led

    water coi lEvaporator 

    EC/FC fan

    Expansion valve

    Sight glass

    Filter 

    drier 

    C om pressor C om pressor  

    Refr igerant

     Ai r- co ol ed co nd en se r 

    FA N

    Water-cooled or 

    glycol-cooled

    Low pressure

    H P

    sensor  

    iCOM control

    FA N

    iCOMcontrol

    B P H E

    iCOMcontrol

    Balancing valve o r isolat ion valve*

    Filter*

    Drain valve*

    Isolat ion valve*

    Hose port*

    Cool ing water o r glycol l iquid

    W elding port of chi l led water in/out port

    3-wayball valve

    Liquiddistributor 

    Chilled

    water coi lEvaporator 

    W elding port of chi l led water in/out port

    Hose port*

    Isolat ion valve*

    sensor  

    High pressuresensor  

    Refr igerantH P

    sensor  

    Sight glass

    Liquid

    distributor 

    EC/FC fan

    Low pressuresensor  

    High pressure

    sensor  Refr igerant Ai r- co ol ed co nd en se r 

     Ai r-c oo le d ou td oo r   Ai r-c oo le d ou td oo r 

    B P H E

    Refr igerant

    3-way bal l

    va lve3-way bal l

    va lve

    condenser water or glycol l iquid

    Water-cooled or 

    glycol-cooled

    Filter 

    dr ier  

    condenser water or glycol l iquid

    Figure 2-6 Dual system diagram of unit

    Note

    MUST ENSURE THAT MECHANICAL FILTER/STRAINER IS FITTED TO INLET OF BPHE CIRCUITS BY INSTALLER!

  • 8/18/2019 Liebert PEX - Compressor Models User Manual - AP11ENT-PEXCompModelsV1-UM

    17/117

    10 Chapter 2 Mechanical Installation

    Liebert PEX Series Air Conditioner User Manual

    Compressor  

    H Psensor  

    iCOM control

    FA N

    B P H E

    Balancing valve o r isolat ion valve*

    Filter*

    Isolat ion valve*

    Drain valve*

    Hose port*

    W elding port of chi l led water in/out port

    3-way bal l

    valve

    Chilled

    water coi l

    Low pressure sensor 

    High pressure sensor 

    Evaporator 

    Chilled

    water coi lEvaporator 

    Liquiddistributor 

    EC/FC fan

    Liquiddistributor 

    EC/FC fan

    Expansion valve

    Hot gas

    bypass valve

    Sight glass

    Filter drier 

    Refr igerant

    Refr igerant

     Ai r-c oo le d co nd en se r 

     Ai r-c oo le d ou td oo r 

    3-way bal l

    va lve

    iCOM cont ro l

    Condenser water 

    or glycol l iquid

    Water-cooled or 

    glycol-cooled

    Isolat ion valve*

    Hose port*

    W elding port of chi l led water in/out port

    Figure 2-7 Single system diagram of unit 

  • 8/18/2019 Liebert PEX - Compressor Models User Manual - AP11ENT-PEXCompModelsV1-UM

    18/117

    Chapter 2 Mechanical Installation 11

    Liebert PEX Series Air Conditioner User Manual

    Note

    1. The contents in the dotted line boxes are the water-cooled unit and air-cooled unit condenser schematic diagram that divided

     by the cooling mode of the refrigerant system. Select the corresponding pipe connection according to the actual type in use, thedashed lines are for pipe connection at site, * components can be selected according to the actual requirements.

    2. High pressure sensor is used for water-cooled or glycol-cooled unit only.

    3. Single source cooling system does not contain the chilled water pipe system, and meanwhile, the low pressure sensor isreplaced with the low pressure switch on the side of the refrigerant.

    2.3.2 System Installation Illustration

    The installation modes of the air-cooled series unit are shown in Figure 2-8 and Figure 2-9.

    Note

    1. If the condenser is installed higher than the compressor (see Figure 2-8), a back bend should be fitted to the discharge line andliquid line of the condenser, so as to prevent the liquid refrigerant from flowing back when the condenser stops.

    2. The top end of the back bend must be installed higher than the highest copper pipe of the condenser.

    Slope discharge

    Bac k bend (higher than the highest coppe r pipe of condenser)

    Liquid l ine (do not expo se liquid l ine to sunshine)

    Trap

    Heat insulation f loo r Sealed

    Outdoo r unit

    Indoor unit

    Floor  

    Condensed wate r ou t

    Hum idif ier water in

    Raised f loor  

          M

         a     x .

          7 .      5

         m

          M

         a     x .      2

          0     m

    supply

    Condensate drain

    Figure 2-8 Condenser installed higher than compressor

  • 8/18/2019 Liebert PEX - Compressor Models User Manual - AP11ENT-PEXCompModelsV1-UM

    19/117

    12 Chapter 2 Mechanical Installation

    Liebert PEX Series Air Conditioner User Manual

    Heat insulation f loo r 

    Sealed

    Outdoo r unit

    Floor  

    Condenser water out

    Humidif ier water in

          M

          i     n .

          5     m

    Slope liquid

    Indoor unit

    Condensed water out

    Raised f loor  Slope discharge

    supply

    Condensate drain

          M

         a     x .

    Figure 2-9 Compressor installed higher than condenser

    Figure 2-10 shows the arrangement of the cooling water system, which requires the water hotter than 4°C. Use

    heaters if the water source in site cannot meet this requirement. The cooling tower should be a closed loop

    system.

    Closed co ol ing tower  

    Exhaust water valve

    Strainer 

    Drain valve

    Ball

    Supplementary valve

    Manomete r  

    Expansion water tank

    F ilter P um p

     

           

     

           

    Temperaturegauge

    valve

    Liebert.PEX-T unitMunitLiebert PEX unit

    Figure 2-10 Arrangement of cooling water system

    2.3.3 Mechanical Parameters

    Indoor unit mechanical parameters

    The mechanical parameters of the indoor unit are shown in Figure 2-11, Figure 2-12, Figure 2-13 and Table 2-1.

  • 8/18/2019 Liebert PEX - Compressor Models User Manual - AP11ENT-PEXCompModelsV1-UM

    20/117

    Chapter 2 Mechanical Installation 13

    Liebert PEX Series Air Conditioner User Manual

        8    7   4

    8 5 3 

            1        9        7

            0

            1        9        7

            0

        8    7   4

    8 5 3 

    1  7   0  4  

            1        9        7        0

      8  7 4

    1  7   0  4  

            1        9        7        0

      8   7  4

    2  5   5   3  

            1        9        7        0

      8  7 4

    2  5   5   3  

      8   7  4

            1        9        7        0

    One-bay upf low

    8 5 3 

          1      9      7      0

       8    7   4

    One-bay downf low

          1      9      7

          0

    8 5 3 

       8    7   4

    1  7   0  4  1  7   0  4  

          1      9      7      0

          1      9      7      0

      8   7 4   8   7

     4

    Two-bay upf low Two-bay downf low

    2  5   5   3    2  5   5   3  

          1      9      7      0

          1      9      7      0

      8   7 4  8   7

     4

    Three-bay up flow Three-bay dow nflow

            1        9        7        0

      8  7 4

    2  5  5  3  2  5  5  3  

          1      9      7      0

      8   7 4

    Before instal l ing the f i l ter Three-bay downflow

    Figure 2-11 Mechanical parameters of the indoor FC fan unit (unit: mm)

  • 8/18/2019 Liebert PEX - Compressor Models User Manual - AP11ENT-PEXCompModelsV1-UM

    21/117

    14 Chapter 2 Mechanical Installation

    Liebert PEX Series Air Conditioner User Manual

    8  5  3  

            1        9        7        0

      8  7 4

            1        9        7        0

      8  7 4

    1  7   0  4  

            1        9        7        0

    2  5  5  3  

      8  7 4

    8  5  3  

    1  7   0  4  

          1      9      7      0

          1      9      7      0

      8   7 4

      8   7 4

          1      9      7      0

      8   7 4

    2  5  5  3  

    Two-bay upf low Two-bay upf low

    Three-bay upf low

    Figure 2-12 Mechanical parameters of the indoor EC fan upflow unit (unit: mm)

    Note

    The indoor unit mechanical parameters of EC fan downflow unit are the same as those of FC fan unit (except for P3100 and

    P2070 downflow dual cooling units, see Figure 2-13 for its mechanical parameters).

  • 8/18/2019 Liebert PEX - Compressor Models User Manual - AP11ENT-PEXCompModelsV1-UM

    22/117

    Chapter 2 Mechanical Installation 15

    Liebert PEX Series Air Conditioner User Manual

            1        9        7        0

      8  7 4

    2  5  5  3  

            2        0        7        0

      8  7 4

    2  5  5  3  2  5  5  3  

    2  5  5  3  

          2      0      7      0

          1      9      7      0

      8   7 4

      8   7 4

    Before install ing the fi lter   A fte r in st a lli ng th e fi lter 

    2  5   5   3  

      8   7  4

            1        9        7        0

    2  5   5   3  

          1      9      7      0

      8   7 4

    Three-bay downflowB efore installing the filter 

    Figure 2-13 Mechanical parameters of P3100 downflow dual cooling indoor unit (unit: mm)

    Note

    For P3100 and P2070 downflow dual cooling series units, the filter is delivered along with the unit accessory, therefore, the unit

    integral height can be increased to 100mm after installation. Taking P3100 for example, you can see the left figure of Figure 2-13for dimensions of the filter before the installation and see the right figure of Figure 2-13 for dimensions of the filter after theinstallation.

    Table 2-1 Mechanical parameters of indoor unit

    ModelDimensions (W × D ×

    H) (mm)

    Net weight (kg)

    Air-cooled series Water-cooled series

    Single source

    cooling system

    Dual cooling

    system

    Single source

    cooling system

    Dual cooling

    system

    P1020 853 × 874 × 1970 320 420 320 420

    P1025 853 × 874 × 1970 330 430 330 430

    P1030 853 × 874 × 1970 340 440 340 440

    P1035 853 × 874 × 1970 350 450 350 450

    P2035 1704 × 874 × 1970 550 700 550 700

    P2040 1704 × 874 × 1970 590 740 590 740

    P2045 1704 × 874 × 1970 560 710 560 710

    P2050 1704 × 874 × 1970 610 760 610 760

    P2055 1704 × 874 × 1970 570 720 570 720

    P2060 1704 × 874 × 1970 640 790 640 790

    P2070* 1704 × 874 × 1970 650 800 650 800

    P3070 2553 × 874 × 1970 890 1090 890 1090

    P3080 2553 × 874 × 1970 910 1110 910 1110

    P3090 2553 × 874 × 1970 930 1130 930 1130

    P3100* 2553 × 874 × 1970 950 1150 950 1150

    Note:

    The model with * means that the downflow dual cooling series units will be increased to 100mm after installation

    Note

    The weight of free cool system unit is the same as that of the dual cooling system unit.

  • 8/18/2019 Liebert PEX - Compressor Models User Manual - AP11ENT-PEXCompModelsV1-UM

    23/117

    16 Chapter 2 Mechanical Installation

    Liebert PEX Series Air Conditioner User Manual

    Plenum dimensions

     You can select the air supply plenum with grids for the upflow system according to the requirement. The

    appearance of the plenum is shown in Figure 2-14, Figure 2-15 and Figure 2-16. The dimensions are listed in

    Table 2-2.

    C

    B  A

    C

    B   A

    Figure 2-14 One-bay plenum Figure 2-15 Two-bay plenum

    C

      A

    Figure 2-16 Three-bay plenum

    Table 2-2 Plenum dimensions

    Type A B C

    One-bay plenum 867 853 400 (600, optional)

    Two-bay plenum 867 1704 400 (600, optional)

    Three-bay plenum 867 2553 400 (600, optional)

    Note

    If the height of the plenum selected for air conditioner unit exceeds 600mm, consult Emerson for non-standard production.

    Outdoor unit mechanical parameters

    See Liebert PEX Condenser User Manual for the dimensions and mechanical parameters of the outdoor unit.

  • 8/18/2019 Liebert PEX - Compressor Models User Manual - AP11ENT-PEXCompModelsV1-UM

    24/117

    Chapter 2 Mechanical Installation 17

    Liebert PEX Series Air Conditioner User Manual

    Base pallet cutout locations & dimensions

    Figure 2-17 and Figure 2-18 show the bases with the side panel removed.

          6      0

          1      4      9

          2      5      5

    58

    78.8

    10 0

    C /R

    P

          1      3      4      2

          3      0

    108.5

    134 .5

    126 1133

          6      0

    1 00 1 30

    D

    H

          1      3      4      2

          3      0

    108.5

    134.5

    126 1133

          6      0

    100 130

          6      0

          1      4      9

          2      5      5

    58

    78.8

    100

    One-bay series

    Two-bay ser ies

    Three-bay series

    C I

    128 .8

    128 .8

    8501700

    103.5

    78.8

          1      3      6 .      8

    C O

    C /R

    C I

    C /R C O

    P

    D

    H C /R C /R

    C IC O

    P

    D

    H

    P: Power cable entry hole D: Drain

    H: Humidifier water in CI: Chilled water in

    CO: Chilled water out C/R: Cooling water in or out/Refrigerant in or out  

    Figure 2-17 Base cutout location of upflow models (unit: mm)

  • 8/18/2019 Liebert PEX - Compressor Models User Manual - AP11ENT-PEXCompModelsV1-UM

    25/117

    18 Chapter 2 Mechanical Installation

    Liebert PEX Series Air Conditioner User Manual

    F C fa n E C fa n

    C /R

    H

    1 5 1 3

    Fan aperture

    C I

          1      7

          0

    6 5C /R

    CO

    93

          3      3      2

          2

          4      0

          1      4      0

    P

    CI

          1      7      0

    65C /R

    CO

    9 3

          3

          3      2

          2      4      0

          1      4      0P

    8 3

          3      5      0

          2      4      2

          1      4      0

    CI

    D C O

    C /R

    P  3

          3      2

          2      4      0

          1      4      0

    9 3

    C /RH

    1513

    8 3

          3      5      0

          2      4      2

          1      4      0

    C I

    COC/R

    P  3

          3      2

          2      4      0

          1      4      0

    9 3

    C I

    C /R

    H      3      5      0

          2      4      2

          1      4      0   3

          3      2

          2      4      0

          1      4      0

    C OC/R

    P

    93

    CI

    C /R

    H      3      5      0

          2      4      2

          1      4      0

      3      3      2

          2      4      0

          1      4      0

    C OC/R

    P

    9 3

    D

    9 4 1 5 13 850.2

    Fan aperture

    Fa n a pe rture Fa n a pe rture

    Fan ape rture Fan aperture Fan aperture

    One-bay ser ies

    FC fan

    EC fan

    Two-bay ser ies

    FC fan

    EC fan

    Three-bay ser ies

    Fan apertureFan ape rture

    Fan ape rtureFan apertureFan aperture

    D

    H

    P: Power cable entry hole D: Drain

    H: Humidifier water in CI: Chilled water in

    CO: Chilled water out C/R: Cooling water in or out/Refrigerant in or out  

    Figure 2-18 Base cutout location of downflow (unit: mm)

    Fan aperture locations & dimensions of top cover 

    The top cover fan aperture locations of upflow unit are shown in Figure 2-19.

  • 8/18/2019 Liebert PEX - Compressor Models User Manual - AP11ENT-PEXCompModelsV1-UM

    26/117

    Chapter 2 Mechanical Installation 19

    Liebert PEX Series Air Conditioner User Manual

    FC fan EC fan

    FC fan E C fan

    FC fan

    EC f a n

    40 0

    80 0

          5      0      9

          2      5      4

    80 0

    72 040   3      5

          7      2      4 .      8

          7      9      4 .      8

    210 400 430 400

          2      5      4

          5      0      9

    1650

    1650

          7      2      4 .      8

          7      9      4 .      8

    740.5 740.5      3      540

    210 400 430 400 498 400

          2      5      4

          5      0      9

    2498

          7      9      4 .      8

    40

    2498

    740.5 740.5 72012 889   3

          5

          7      2      4 .      8

    One-bay upflow series

    Two-bay upflow series

    Three-bay upflow series

    89

    Figure 2-19 Top cover fan aperture locations of upflow series (unit: mm)

  • 8/18/2019 Liebert PEX - Compressor Models User Manual - AP11ENT-PEXCompModelsV1-UM

    27/117

    20 Chapter 2 Mechanical Installation

    Liebert PEX Series Air Conditioner User Manual

    Side panel cutout locations & dimensions

    If piping and wiring from the base are difficult, connection from the side panel can be selected. The locations

    and dimensions of the knock-out holes are shown in Figure 2-20. You can select the in and out holes

    according to the actual needs, but must confirm that any two of the pipe, power cable and signal cable cannot

    use the same hole.

    31 9

    51 9673.68

    41 9

          8      7       1

          3      7

          1      8      7

    knock-out hole2- 25

    knock-out hole

    knock-out hole

    8- 80

    2- 35

    Figure 2-20 Cutout positions of side panel (unit: mm)

    2.4 Installing Indoor Unit

    2.4.1 Equipment Room Requirement

    The requirements of the equipment room are as follows:

    1. Damp proof and heat preservation work must be well done to make sure that the environment control

    system in the air conditioner room can operate normally.

    2. The equipment room should have good heat insulation and sealed damp proof layer. The damp proof layer

    of the ceiling and walls must use polyethylene film, and the coating of the concrete wall and the floor must be

    damp proof.

    3. The outdoor air that enters the equipment room should be reduced to a minimum, better below 5% of thetotal indoor airflow, as it may increase the load of heating, cooling, humidifying and dehumidification of the

    system.

    4. All the doors and windows should be closed and the openings should be as narrow as possible.

    2.4.2 Installation Space

    Note

    The air conditioner can generate condensate, which may be leakage due to the incorrect installation or use. Do not install it in the

    vicinity of any precision equipment so as to maintain the normal operation, and the installation site must provide drain pipes.

    1. To ensure normal operation, adequate installation space for the indoor unit must be provided.

    2. Avoid locating the indoor unit in confined areas, which can baffle the airflow, shorten the cooling cycle and

    result in down-draft and air noise.

    3. Avoid locating the indoor unit in a concave or at the end of a long and narrow room.

    4. Avoid locating multiple indoor units close to each other. That can result in crossing air patterns,

    unbalanced load and competitive operation.

    5. For the convenience of daily maintenance, do not install other devices (such as smoke detector) over the

    cabinet.

  • 8/18/2019 Liebert PEX - Compressor Models User Manual - AP11ENT-PEXCompModelsV1-UM

    28/117

    Chapter 2 Mechanical Installation 21

    Liebert PEX Series Air Conditioner User Manual

    2.4.3 Requirement Of Maintenance Space

    Leave a maintenance space of 850mm in front of the air conditioner unit normally, as shown in Figure 2-21.

      8  5  0  m

      m

    Figure 2-21 Maintenance space

    The minimal maintenance space is required as listed in Table 2-3.

    Table 2-3 Minimal maintenance space (unit: mm)

    Position Air-cooled Water-cooled

    Front 600 600

    Left 600* 600*

    Right 600* 600*

    Back 0 0

    Note :

    1. The space is provided for regular maintenance, such as replacing strainer, adjusting fan, cleaning infared humidifier.

    2 *. They are the maintenance space when the water-cooled unit connects water pipes on side or when the air-cooled unit

    connects the refrigerant pipes on side. If the water pipes or refrigerant pipes are laid on the bottom of the unit, no

    maintenance space is required

    Note

    For special applications, please consult Emerson.

  • 8/18/2019 Liebert PEX - Compressor Models User Manual - AP11ENT-PEXCompModelsV1-UM

    29/117

    22 Chapter 2 Mechanical Installation

    Liebert PEX Series Air Conditioner User Manual

    2.4.4 Installation Procedures

    The installation procedures of the indoor unit are as follows:

    1. Make a mounting base according to the dimensions in Figure 2-22, Figure 2-23 and Figure 2-24, and the

    requirements in Table 2-4. Emerson can supply a range of mounting bases to suit the required height.

    2. Lay a layer of rubber cushion on the top, lateral of the mounting base and on the bottom of the steel plate

    respectively. See Figure 2-22, Figure 2-23 and Figure 2-24 for their positions and see Table 2-4 for the

    thickness.

    3. Determine the installation position. Fix the mounting base onto the mounting position according to the site

    conditions and user’s requirement.

    4. Fix the air conditioner cabinet onto the mounting base with nuts, spring washers, flat washers and bolts.

    6  9  4  

    8  5  0  

    Installation hole of 4-M 8 60 sems screw

    4  0  

    H

       7  5  8

       7  6 4

       7  9  8

    8  9  3  9  2  6  

    7   8  

    1  0  0  

    Rubber cushion (top)

    Base

    Instal lation hole of 4-M 8 anchor bo lt

    Rubber cushion (bottom )

    Rubber cushion (lateral)

     A ng le st ee l

    Steel plate

    Front side of cabinet

    Rear s ide of cabinet

    Figure 2-22 Mounting base appearance and dimensions of one-bay series (unit: mm)

  • 8/18/2019 Liebert PEX - Compressor Models User Manual - AP11ENT-PEXCompModelsV1-UM

    30/117

    Chapter 2 Mechanical Installation 23

    Liebert PEX Series Air Conditioner User Manual

    1  5  4  4  

    1  7   0  0  

    4  0  

       7  6 4

       7  9  8

    H

    1  7   4  3  1  7   7   6  

       7  5  8

    7   8  

    1  0  0  

    Upf low

    Installat ion hole o f 4-M 8 60 sems screw

    Front side of cabinet

    Rubber cushion (top)

    Rubber cushion (bottom)

     A ng le st ee l

    Base

    Installat ion hole o f 4-M 8 anchor bo lt

    Rear side of cabinet

    Rubber cushion (lateral)

    Steel plate

    1  5  4  4  

    1  7   0  0  

    4  0  

       7  6 4

       7  9  8

    H

    1  7   4  3  1  7   7   6  

       7  5  8

    7   8  

    1  0  0  

    Downf low

    Installat ion hole o f 4-M 8 60 sems screw

    Front side of cabinet

    Rubber cushion (top)

    Rubber cushion (bottom)

     A ng le stee l

    Base

    Installat ion hole o f 4-M 8 anchor bo lt

    Rear side of cabinet

    Rubber cushion (lateral)Steel plate

    Figure 2-23 Mounting base appearance and dimensions of two-bay series (unit: mm)

  • 8/18/2019 Liebert PEX - Compressor Models User Manual - AP11ENT-PEXCompModelsV1-UM

    31/117

    24 Chapter 2 Mechanical Installation

    Liebert PEX Series Air Conditioner User Manual

    1  5  4  4  

    1  6  8  0  

    8  5  0  

    2  5  5  0  

    4  0  

    H

       7  5  8

    2  5  9  3  2  6  2  6  

    1  0  0  

    7   8  

       7  6 4

       7  9  8

    Upf low

    Installat ion hole of 6-M8 60 sems screw

    Installat ion hole o f 4-M 8 anchor bo lt

    Front side of cabinet

    Rear s ide o f cab inet

    Rubber cushion

    (lateral)

    Steel plate

    Rubber cushion

    (top)

    Rubber cushion

    (bot tom)

     A ng le st ee l

    Base

    1  5  4  4  

    1  6  8  0  

    8  5  0  

    2  5  5  0  

    4  0  

    H

       7  5  8

    2  5  9  3  2  6  2  6  

    1  0  0  

    7   8  

       7  6 4

       7  9  8

    Downf low

    Installat ion hole o f 6-M 8 60 sems screw

    Installat ion hole of 4-M8 anchor bo lt

    Front side of cabinet

    Rear s ide o f cab inet

    Rubber cushion

    (lateral)

    Steel plate

    Rubber cushion

    (top)

    Rubber cushion

    (bot tom)

     A ng le st ee l

    Base

     

    Figure 2-24 Mounting base appearance and dimensions of three-bay series (unit: mm)

  • 8/18/2019 Liebert PEX - Compressor Models User Manual - AP11ENT-PEXCompModelsV1-UM

    32/117

    Chapter 2 Mechanical Installation 25

    Liebert PEX Series Air Conditioner User Manual

    Table 2-4 Specifications of indoor unit mounting base

    Item Specification Remark

    Steel plate 100mm × 100mm × (5 ~ 6.5)mm -

    Angle steel 40mm × 40mm × 3mm -

    Rubber 

    cushion

    Top Thickness: 3mm ~ 5mm Supplied by others

    Lateral Thickness: 2mm ~ 3mm Supplied by others

    Bottom Thickness: 10mm ~ 12mm Supplied by others

    Installation hole of 

    anchor bolt- Install the bolts according to your requirement

    H

    One-bay H = 200mm (upflow unit)

    H   300mm (downflow unit of

    forward curved fan)

    H   325mm (downflow unit of EC

    fan)

    1. Only three-bay unit needs the middle support (front and

    rear).

    2. The upflow unit does not need the flow deflector.

    3. The H dimension here is only for reference, and should

    be determined according to user’s actual requirement while

    making the base

    Two-bay

    Three-bay

    Note:

    The external side boards of the unit cannot bear weight. Take the mounting base into consideration while selecting angle

    steels and fixing holes. For the downflow unit used EC fan, the minimum floor height requirement must be met

    2.5 Installing Outdoor Unit

    This outdoor unit is only applicable to the air-cooled series air conditioner. For detailed installation, refer to

    Liebert PEX Condenser User Manual .

    2.6 Piping

    2.6.1 Piping For Air-Cooled Unit

    All joints of the cooling pipes must be silver-brazed. Standard industry procedures must be followed in

    selecting, laying, and fixing the pipes, and evacuating the system and charging refrigerant. Take pipeline

    pressure drop, oil return to the compressor and minimization of noise and vibration into consideration during

    design and construction.

    General

    The recommended pipe sizes are ‘equivalent lengths’ (see Table 2-6 for equivalent lengths of partial

    components), with the resistance caused by bends taken into account. The installer should confirm that the

    sizes are appropriate for the site conditions.

    1. If the one-way equivalent length exceeds 30m, or if the vertical distance between indoor unit and outdoor

    unit exceeds the values in Table 2-5, consult Emerson before installation to confirm whether a pipe extension

    kit is needed.

    Table 2-5 Vertical distance between indoor unit and outdoor unit

    Relative position altitude differenceOutdoor unit higher than indoor unit Max.: +20m

    Outdoor unit lower than indoor unit Max.: -5m

    2. The pipe sizes recommended in Table 2-6 are ‘equivalent lengths’, with the resistance caused by bends and

    valves taken into account. The installer should confirm that the sizes are appropriate for the site conditions.

    Table 2-6 Equivalent lengths of partial components

    Outer Diameter (OD) of

    liquid pipe (inch)

    Equivalent length (m)

    90° bend 45° bend T type three-way

    3/8 0.21 0.10 0.76

    1/2 0.24 0.12 0.76

    5/8 0.27 0.15 0.76

    3/4 0.3 0.18 0.76

    7/8 0.44 0.24 1.1

    1-1/8 0.56 0.3 1.4

  • 8/18/2019 Liebert PEX - Compressor Models User Manual - AP11ENT-PEXCompModelsV1-UM

    33/117

    26 Chapter 2 Mechanical Installation

    Liebert PEX Series Air Conditioner User Manual

    Note

    A trap should be installed for every 7.5m of vertical distance. Please consult Emerson for details.

    Connecting pipes

    The pipes to be connected include:1. Condensate drain pipe of indoor unit

    2. Water inlet pipe for infrared humidifier 

    3. Connection copper pipe (discharge pipe and liquid pipe for air-cooled system) between indoor unit and

    outdoor unit

    4. Water inlet and outlet pipe of the chilled water (dual cooling unit)

    5. Pipe extension kit (optional)

    Connecting condensate drain pipe of indoor unit

    The condensate of infrared humidifier and evaporator is converged by a cross connector and drained through

    the drain pipe, as shown in Figure 2-25. The pipe OD is 25mm. If the drain pipe is used by three or more units,

    the minimal pipe OD should be 40mm.

    Note

    Because the infrared humidifier contains flowing hot water, the water pipe must be resistant to heat higher than 90°C.

    ater inlet pipe o f far 

    infrared humidif ier 

    Connector of co ndensed

    water drain pipe

    Connect ion of  

    condensa te drain pipe

    W ater in pipe of 

    infrared hum idifier  

    To inf rared hum idi fier  water pan

    Cross connec to r  H o s e c l a m p

    To condensed water  

    pan o f ev apora tor  o condensed water  

    pan of evaporator  

    To the condensedwater dra in p ipe

    To co ndensed

    To far infrared humidif ier 

    To condensatedrain pipe

    To condensatepan of evaporator 

    To condensatepan of evaporator 

    Figure 2-25 Connection of drain pipe

    Note

    1. A 25 hose clamp is delivered as an accessory to connect the drain pipe.

    2. When connecting the drain pipe, you must make sure that the U bend is installed vertically and the ‘U’ shape is not distorted,

    so as to ensure that the condensate can be drained immediately and effectively.

    Connecting water inlet pipe of infrared humidifier

    Water pipes should be connected for the infrared humidifier. To facilitate maintenance, an isolation valve

    should be fitted to the water inlet pipe. The infrared humidifier reserves a copper pipe (OD: 6.35mm), as

    shown in Figure 2-26. There is a 1/4” copper nut at the end of the copper pipe. Take out the 1/4” × 1/2”

    conversion copper thread connector from the accessory bag and connect it to the copper nut. You can also

    choose the connection method to connect pipes according to the site condition. Make sure that the

    connection is well sealed to prevent leakage. The main pipe pressure should be between 100kPa ~ 700kPa.

  • 8/18/2019 Liebert PEX - Compressor Models User Manual - AP11ENT-PEXCompModelsV1-UM

    34/117

    Chapter 2 Mechanical Installation 27

    Liebert PEX Series Air Conditioner User Manual

    Where the main pipe pressure may rise above 700kPa, a pressure reducer should be fitted. Where the main

    pipe pressure falls below 100kPa, a water tank and pump system should be used.

    Note

    Some product may include components required by local codes.

    Over- temperature

    protection switch

    W ater out le t

    Stainless steel stud

    Over- temperatureprotection relay

    Ceramic terminal socket

    W ater supply p ipe

    W ater pan (removable)

    W ater supply so lenoid valve

    W ater level sensor  

    Over-temperature protection

    W ater level regulator 

    W ater pan f ix ing screw

    W ater supply p ipeOD 6 .35mm  A d ire ct io n

     A di re ct io n

    W ater pan f ixing screw (left and right)

    switch (water pan bottom)

    OD 6 .35mm

    W ater high level sensor 

    switch (undre pan)

    Figure 2-26 Infrared humidifier

    Connecting connection copper pipes (discharge pipe and liquid pipe) between indoor unit and outdoor

    unit

    The indoor unit and outdoor unit are connected through welded copper pipes. The connection ball valves of

    the discharge pipe/liquid pipe of indoor unit are shown in Figure 2-27 and Figure 2-28. Note that the ball valve

    must be wrapped with a wet cloth before welding. In addition, many notes and instruction labels are pasted

    onto the base and side panel close to the ball valve. Protect them from heat burned during the welding

    operation.

    NoteThe exposure time of system pipes do not exceed 15min. Longer exposure will lead to the POE refrigeration oil being affected

    with moisture, which can affect the life of the key components and the stability of the system operation. Especially note that thecompressor and the corresponding expansion valve of the dual refrigerant system unit should be located at both sides of the unit.

    For example, you face the unit front door, No.1 system compressor is on the left hand side, while the expansion valve thatcorresponds to No.1 compressor is on the right hand side. Similarly No.2 system compressor is on the right hand side, while theexpansion valve that corresponds to the No.2 compressor is on the left hand side.

    Horizontal sections of the discharge pipes should be sloped downward from the compressor, with a slope of

    at least 1:200 (5mm down for each 1m run). The discharge pipes should be insulated where they are routed in

    the conditioned space (including under a raised floor).

    The pressure drop should not exceed 40kPa (5psi ~6psi), provided that there is no loss of refrigeration in the

    liquid return pipe. The pressure drop of the liquid return pipe is the sum of liquid flow resistance from thetubing and fitting (including filter drier), plus the loss of head pressure due to elevation above the condenser.

    If the liquid temperature is 38°C, the static pressure loss is 11kPa (1.6 psi) per meter of lift.

  • 8/18/2019 Liebert PEX - Compressor Models User Manual - AP11ENT-PEXCompModelsV1-UM

    35/117

    28 Chapter 2 Mechanical Installation

    Liebert PEX Series Air Conditioner User Manual

    System 1 p ipe

     A ir- co o led o f up flo w

    Sys tem 2expansion valve Sys tem 1

    System1 sight

    glass

    Sys tem 2

    System2 sight

    glass

    S ystem 2 p ipe S ystem 1expansion valve

    Sys tem 2expansion valve S y ste m 1 S y ste m 2

    Sys tem 1

    pipe

    System

    1 sightglass

    System2 sight

    glass

    System 2 p ipe Sys tem 1expansion valve

    Water-cooled of upf low

    Figure 2-27 Pipe connection of upflow unit 

    Sys tem 2expansion valve Sys tem 1 Sys tem 2

    System

    2 sightglass

    System 1 p ipe Sys tem 1

    expansion valve

    System

    1 sightglass

    Sys tem 2pipe

    System

    2 sightglass

    System 1 p ipe Sys tem 1expansion valve

    System

    1 sightglass

    Sys tem 2pipe

     A ir- co o led o f do wnflo w W at er -c o o led o f do wn flo w

    Sys tem 2expansion valve System 1 S ystem 2

    Figure 2-28 Pipe connection of downflow unit 

    Considering the effect of the pipe diameter on the system pressure drop, the pipe diameter of the indoor unit

    and outdoor unit should be determined according to the specifications listed in Table 2-7.

    Table 2-7 Recommended pipe sizes

    Recommended pipe sizes (unit: mm)

    Model P1020 P1025 P1030 P1035 P2035 P2040 P2045 P2050

    Eq.Lgt

    hD L D L D L D L D L D L D L D L

    10m 22 13 22 13 22 13 22 13 22 13 22 13 22 13 22 13

    20m 22 13 22 13 22 13 22 16 22 16 22 13 22 16 22 13

    30m 22 13 22 13 22 16 25 16 25 16 22 13 25 16 22 1340m* 22 13 22 13 22 16 25 16 25 16 22 13 25 16 22 13

    50m* 22 13 22 16 25 16 25 16 25 16 22 13 28 19 22 16

    60m* 22 16 22 16 25 16 25 19 25 19 22 16 28 19 22 16

    Model P2055 P2060 P2070 P3070 P3080 P3090 P3100

    Eq.Lgt

    hD L D L D L D L D L D L D L

    10m 22 16 22 13 22 13 22 13 22 13 22 13 22 16

    20m 25 16 22 13 22 16 22 16 22 16 25 16 25 16

    30m 28 19 22 16 25 16 25 16 25 16 25 16 28 19

    40m* 28 19 22 16 25 16 25 16 25 16 25 16 28 19

    50m* 28 19 25 16 25 16 25 16 28 19 28 19 28 19

    60m* 32 19 25 16 25 19 25 19 28 19 28 19 32 19Note

    1. A pipe extension kit is required for ‘Eq.Lgth’ marked with *.

  • 8/18/2019 Liebert PEX - Compressor Models User Manual - AP11ENT-PEXCompModelsV1-UM

    36/117

    Chapter 2 Mechanical Installation 29

    Liebert PEX Series Air Conditioner User Manual

    Recommended pipe sizes (unit: mm)

    2. D: discharge line, L: liquid line.

    3. Consult Emerson if the pipe length exceeds 60m

    Connecting water inlet and outlet pipe of the chilled water (dual cooling unit)

    The water inlet and outlet pipe of the chilled water is connected to the chilled water unit through welding. The

    inlet and outlet pipe of the chilled water should be welded according to the unit rack labelling, do not reversethe connection. The water inlet and outlet pipe of the chilled water can be connected from the base pallet or

    side panel, see the cutout positions schematic diagram of the base pallet and side panel for pipe entry

    position (see Figure 2-17, Figure 2-18, Figure 2-20). There should be a flexible connector for water inlet and

    outlet pipe and unit connection. The water inlet pipe must be installed with a strainer more than 60 mesh. The

    water inlet and outlet pipe of the chilled water should be installed more than one isolation valve, so as to cut

    off the power upon repair. One of the isolation valves can be a balancing valve. The chilled water system with

    a balancing valve has higher efficiency, and can control the water distribution more accurately.

    Installing pipe extension kit (for site installation)

    When the equivalent length of the one-way pipe exceeds 30m, the pipe extension kit should be installed.

    During the installation of the pipe extension kit, to avoid the pipe opening, it is recommended to install the

    solenoid valve of the pipe extension kit onto the outside project pipe of the ball valve on the liquid pipe. The

    outer side or the bottom of the unit is allowable.

    So, during installing the solenoid valve, you do not need to cut the indoor unit pipes. After the whole system

    is installed, you can open the ball valve to keep pressure and carry out the vacuum operation, avoiding the

    moisture absorption of the compressor refrigeration oil and ensuring the operation safety and life of the

    compressor. For the installation position of the check valve, refer to Figure 2-6.

    For the electrical connections of the pipe extension kit, refer to 3.2.4 Connecting Solenoid Valve Of Pipe

    Extension Kit (Options, For Site Installation).

    Charging refrigerant and adding refrigerant oil

    1. Charging refrigerant

    The Liebert PEX air-cooled series air conditioner has been charged in the factory with 2bar nitrogen.

    If the connection pipe between the indoor unit and the outdoor unit is longer than 10m, refill the refrigerant to

    the system to ensure normal system operation.

    The refilling amount of the refrigerant is calculated through the following formula:

    Refrigerant refilling amount (kg) = refrigerant refilling amount per unit length of liquid pipe (kg/m) × total

    length of extended liquid pipe (m)

    See Table 2-8 for refrigerant refilling amount of per meter liquid pipe.

    Total length of extended liquid pipe (m) = Total length of liquid pipe (m) - 10m

    Table 2-8 Refrigerant refilling amount per unit length of liquid pipe with different ODs

    Liquid pipe OD

    (mm)

    Refrigerant refilling amount of per

    meter liquid pipe (kg/m)

    Liquid pipe OD

    (mm)

    Refrigerant refilling amount of per

    meter liquid pipe (kg/m)

    9.52 0.060 19 0.261

    12.7 0.112 22 0.362

    16 0.181 28.6 0.618

    For the refrigerant charge quantity, refer to step 5 in 4.2.2 Commissioning Procedures.

    2. Adding POE refrigerant oil

    The refilled refrigerant will dilute the POE refrigerant oil in the system and affect the lubricating and cooling

    effects of the POE refrigerant oil. Therefore, the POE refrigerant oil should be added. See the formula below:

    Amount of refrigerant oil (ml) to be added = refrigerant refilling amount (kg) × 22.6

    2.6.2 Piping For Water-Cooled Unit

    Each cooling system uses a BPHE (or condenser) and an electric valve. The water supply (inlet) pipe and

    water return (outlet) pipe of the cooling water should be connected for the system. See Figure 2-29.

    A filter (filter mesh: 1mm) and multiple isolation valves should be mounted one side of the water supply pipe

    of the cooling water. One of the valves can be a balancing valve.

  • 8/18/2019 Liebert PEX - Compressor Models User Manual - AP11ENT-PEXCompModelsV1-UM

    37/117

    30 Chapter 2 Mechanical Installation

    Liebert PEX Series Air Conditioner User Manual

    The cooling water system with a balancing valve can control the water distribution more accurately and its

    pump has higher efficiency. On the other hand, the electric valve can keep the optimal condensing

    temperature by regulating the internal water flow.

    The electric actuator of the regulating valve features a manual override to allow water side balancing by the

    installer.

    It is recommended to arrange the cooling water pipes separately for different systems, so that repairing one

    pipe will not affect the operation of the other one.

    The water pressure should be high enough to counteract the pressure drops brought about by all the

    components of the water system. In addition, because the sediments and impurities cause more pressure

    drop after long term operation, you should arrange a redundancy of 20% ~ 25% when selecting the lifting part

    (such as pump).

    See Figure 2-6 and Figure 2-7 for the system arrangement of the water-cooled unit.

    Connecting pipes

    The pipes to be connected include:

    1. Condensate drain pipe of indoor unit

    2. Water inlet pipe of infrared humidifier 

    3. Water inlet and outlet pipe of cooling water 4. Water inlet and outlet pipe of chilled water (dual cooling unit)

    Connecting condensate drain pipe of indoor unit

    Refer to the corresponding content in 2.6.1 Piping For Air-Cooled Unit .

    Connecting water inlet pipe of infrared humidifier 

    Refer to the corresponding content in 2.6.1 Piping For Air-Cooled Unit .

    Connecting water inlet and outlet pipe of cooling water

    The water inlet and outlet pipe of cooling water of the indoor unit are copper pipes with 35mm outer diameter,

    as shown in Figure 2-29. Connect the pipes through direct welding at the site and make sure that the junction

    is well-sealed.

    W ater outlet

    W ater inlet

    B P H E

    Figure 2-29 Unit connections (water-cooled)

    Connecting water inlet and outlet pipe of chilled water (dual cooling unit)

    Refer to the corresponding content in 2.6.1 Piping For Air-Cooled Unit .

    2.7 Lowering Fan And Removing Fixtures (Downflow EC Fan System)

    2.7.1 Downflow Unit EC Fan Lowering

    After installation, you must lower all fans of the EC downflow unit before commissioning. You lower the fan

    using the supplied hand winch. Each EC downflow unit is only equipped with one lowering tool, so you

    should select the lowering mode according to the equipped lowering tool.

  • 8/18/2019 Liebert PEX - Compressor Models User Manual - AP11ENT-PEXCompModelsV1-UM

    38/117

    Chapter 2 Mechanical Installation 31

    Liebert PEX Series Air Conditioner User Manual

      Note

    Be careful when lowering the fan, avoid trapping your fingers and fan cables, and avoid foreign matter falling into the inlet ring

    of the fan.

    Lowering Fan Through Hand Winch Mode

    The downflow unit has been equipped with a set of fan elevator assembly before delivery, including a handwinch, a winch bracket, a hook, a sling, a winch limit and a handle in Figure 2-30, and also an L shaped lifting

    component in Figure 2-31.

    H o o k

    Handle

    W inch bracket

    Sling Winch

    Figure 2-30 Fan elevator assembly (winch mode)

    Lower the fan with the fan elevator assembly installed according to the following procedures:

    1. Open the unit maintenance cover, check the fixing bolts and washers II (see Figure 2-31, totally 2 pcs) of the

    L shaped lifting component to make sure that it is fixed properly, and then install the fixing bolts and washers

    IV (totally 4 pcs) of the winch bracket, as shown in Figure 2-31.

    Unit beam

    Unit beam

    Winch bracket

    L shaped lif t ing component

    M iddle round hole

    Fan

    Gaskets II

    Winch

    Handle

    Gaskets IV

    Sling

    W ashers IV

    W ashers II

    Figure 2-31 Installing winch bracket 

    2. Turn the handle and use the hook of the winch to hook the middle round hole (see Figure 2-31) of the L

    shaped lifting component. Adjust the handle until the sling is completely tight.

    3. Cut off the cable tie binding the fan cables to make the cables length satisfy fan lowering requirements, and

    then remove the fixing bolts and washers I (see Figure 2-32, totally 4 pcs) for fan transportation.

  • 8/18/2019 Liebert PEX - Compressor Models User Manual - A