LGE UK Multi V Spec SPECIFICATION FOR LG MULTI V VRF SYSTEMS BASIC DESIGN The mechanical services shall maintain the following conditions at the stated external parameters: Internal design conditions Summer 23 0 C db, 50% RH Winter 21 0 C, 40% RH External design conditions Summer 30 0 C db, 20 0 C wb Winter 0 0 C db, Saturated Noise criteria External noise criteria At 1 m in front of the plant NR60 Design noise criteria To the offices NR40 1
25

LG Multi V SPEC

Nov 12, 2014

Download

Documents

Javier Sordo
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: LG Multi V SPEC

LGE UK Multi V Spec

SPECIFICATION FOR LG MULTI V VRF SYSTEMS

BASIC DESIGN

The mechanical services shall maintain the following conditions at the stated external parameters:

Internal design conditions

Summer 230 C db, 50% RH Winter 210 C, 40% RH

External design conditions

Summer 300 C db, 200 C wb

Winter 00 C db, Saturated

Noise criteria

External noise criteria At 1 m in front of the plant NR60

Design noise criteriaTo the offices NR40

1

Page 2: LG Multi V SPEC

LGE UK Multi V Spec

GENERAL DESCRIPTION

The building shall be air conditioned via Variable Refrigerant Flow System with R410A refrigerant as manufactured by LG Electronics and as supplied by:

Insert details here

The systems shall comprise of one or a number of outdoor units connected via interconnecting refrigeration pipe work to multiple indoor units. The systems shall be complete with all the necessary electronic controls and control wiring to maintain the design room conditions.

Installation

The equipment must be installed in line with the manufacturer’s specification as listed below:Pipe sizing and wiring to be carried out as per manufacturers schematic drawings.

Warranty of LG Multi V units is subject to a complete and satisfactory commissioning report being made available to LGEUK

2

Page 3: LG Multi V SPEC

LGE UK Multi V Spec

REFRIGERATION PIPE WORK

The pipe work shall be of refrigerant quality copper to BS2871 Part 2, ASTM 280, DIN1754/8905 half hard tempered. Soft tempered pipe work may be used where the pipe diameter is 1/4” or 3/8”. Long radius bends shall be formed using pipe bender. The use of short radius pre formed bends and elbows should be avoided to minimise pressure drop and possibility of leaks.

Oxygen free nitrogen must be passed through the pipe work during all brazing of joints to prevent the formation of oxidisation scale on the inside surface of the pipes.

All pipe work shall be clean, de-hydrated and sealed. Pipe work shall be stored under dry conditions. Any pipe work found to be stored without the end caps should be rejected. Where sections are cut from a new coil any remaining lengths must be re-sealed. During the installation if the system has to be left unattended for any purpose whatsoever, the openings in the systems must be securely sealed.

Pipe work fittings for branching off to indoor units must be LG Branch joints as supplied by insert name here. No other fittings are acceptable. The positioning of these joints shall be strictly in accordance to the manufacturer’s specification. More detailed information can be found in installation manuals available from insert name here.

All pipe work shall be insulated with Armaflex Class-0 type insulation, 13 mm thick. Joints and headers shall be insulated with the pre formed insulation supplied with these fittings. Insulation exposed to atmospheric conditions shall be protected with two coats of insulation paint. All insulation joints shall be made using adhesive and care should be taken that the every part of insulation is sealed to maintain a vapour barrier.

The pipe work must be supported through its entire length according to good refrigeration practice. However the brackets must not be positioned directly on the joints or headers. On horizontal pipe work the bracketing should be over the insulation to allow pipe movement due to contraction and expansions. The vertical pipe work shall be bracketed at no more than 1000 mm centres. The horizontal pipe work shall be bracketed at no more than 1500 mm centres.

The pipe work layout and the pipe sizing shall be according to the diagrams supplied by insert name here.

All installed pipe work lengths are to be accurately measured and recorded on the commissioning form. This information is required for accurate calculation of the additional refrigerant charge for the system. The weight of the additional refrigerant must also be recorded for future reference.

PRESSURE TESTING, EVACUATION AND COMMISSIONING

After Installation of pipe work, and prior to sealing of insulation joints, pipe work should be pressure tested to 38 bar, held for 24 hours and checked for leaks, vacuumed/dehydrated to –752 mm Hg and held at that setting for 1 to 4 hours depending on the pipe length. The detailed information can be found in the installation and commissioning procedures available from insert name here

3

Page 4: LG Multi V SPEC

LGE UK Multi V Spec

A representative from insert name here shall carry out the final refrigerant charging and the commissioning of the system, a copy must be sent to LG EUK to qualify for warranty.

4

Page 5: LG Multi V SPEC

LGE UK Multi V Spec

WIRING

A fused 415 V - 3 Phase, N + E power supply with external isolator shall be made available for each outdoor unit. The fuse rating for the 5 hp outdoor unit shall be 20 Amps, the 8 and 10 hp outdoor units shall be 32 amps and the 12 and 14 hp units shall be 40 Amp. All fuses / circuit breakers should be motor rated.

A fused 240 V - 1 Phase, N + E Power supply shall be made available for each indoor unit, the HR box and the centralised control system. It is a normal practice to run a 15 amps ring main for the indoor units and HR boxes and a 5 Amp fused spur provided local to each item.

Control cable to the following specification shall be used:

2 core PVC shielded cable sized between 0.75 mm2 and 1.25 mm2.

Control and power cables must not be installed along side each other as interference in the signal wiring caused by electrostatic and electromagnetic coupling can occur.

The table below indicates manufacturer’s recommendation as to the appropriate spacing of control and power cables where these run side by side:

Current capacity of the power cables Spacing10 amp or less 300 mm

100 v or more 10 - 50 amps 500 mm50 -100 amps 1000 mm100 amp + 1500 mm

The control cables shall be installed on metal cable trays or conduits. Care must be taken to ensure that they are not tied together or packed tightly.

5

Page 6: LG Multi V SPEC

LGE UK Multi V Spec

OUTDOOR UNITS

All outdoor units are to be permanently marked with an identification number. The removable access panels are also to be marked with the same number.

The outdoor units are to be:

a) Heat pump Multi V Spaceb) Heat pump type c) Heat recovery type

The units shall be air-cooled type incorporating heat exchanger coils manufactured from copper tubes and aluminium fins, factory treated to reduce the effect of atmospheric corrosion. The unit casing shall be manufactured from (70µ) polyester powder coated baked enamel finish sheet steel in order to have a high corrosion resistance and to protect against salt laden environment close to where the units may be installed. The colour shall be manufacturer’s standard ‘off white’. The air outlet grilles shall have plastic coated guards.

The outdoor units shall have at least 1 inverter driven compressor electronically controlled and capable of changing speed linearly to follow the variation in cooling and heating requirements.

The capacity control of the outdoor units will be inverter controlled and shall be determined electronically by sensing operational temperatures, pressures and ambient temperature and monitoring requirements for the indoor units.

The units shall be complete with electronic expansion valve(s), oil separator(s), high pressure switches, fan motor safety devices, over current relay, inverter overload protection, fuses, necessary solenoid valves, refrigerant shutoff valves, re-cycling guard timer and all necessary sensors for a safe and trouble free operation.

The access to the internal components for maintenance purposes shall be by removable panels.

HEAT PUMP SPACE UNITS

It shall be possible to connect up to 16 indoor units, capacity permitting, to one outdoor unit.

The 5 hp units shall have a single inverter driven scroll compressor and an inverter driven variable speed scroll type fan offering 120Pa of static pressure.

The 8, & 10 hp units shall have two scroll compressors and will be capable of operating on one compressor under emergency condition in case the inverter other fails.

Both compressors shall be inverter driven. These units will incorporate two inverter driven variable speed scroll type fans, offering 120Pa of static pressure

The outdoor unit shall have full capacity control to meet the load fluctuation and indoor unit individual control.

6

Page 7: LG Multi V SPEC

LGE UK Multi V Spec

HEAT PUMP UNITS

It shall be possible to connect up to 40 indoor units, capacity permitting, to one outdoor unit.

The 5 hp units shall have a single inverter driven scroll compressor and an inverter driven variable speed propeller type fan.

The 8, & 10 12 and 14hp units shall have two scroll compressors and will be capable of operating on one compressor under emergency condition in case the inverter compressor fails.

One compressor shall be inverter driven capable of ‘Soft start’. The other compressor/s shall be on/ off type. These units will incorporate one inverter driven variable speed propeller type fan.The fan will be capable of overcoming a minimum of 58 Pascal of external static pressure.

The outdoor unit shall have full capacity control to meet the load fluctuation and indoor unit individual control.

7

Page 8: LG Multi V SPEC

LGE UK Multi V Spec

HEAT RECOVERY UNITS

It shall be possible to connect up to 40 indoor units capacity permitting and 10 PRHR heat recovery boxes, to one out door unit.

The 8, & 10 12 and 14hp units shall have two scroll compressors and will be capable of operating on one compressor under emergency condition in case the inverter compressor fails.

One compressor shall be inverter driven capable of ‘Soft start’. The other compressor/s shall be on/ off type. These units will incorporate one inverter driven variable speed propeller type fan.The fan will be capable of overcoming a minimum of 58 Pascal of external static pressure.

The outdoor unit shall have full capacity control to meet the load fluctuation and indoor unit individual control.

HEAT RECOVERY BOX PRHR

These boxes are to be supplied for heat-recovery type applications only to allow automatic/manual heat / cool change over control.

The unit casing shall be manufactured from galvanised sheet steel.

Each unit shall incorporate two solenoid valves, one for the suction and the other for the discharge line to allow for heating or cooling mode selection by the indoor unit control.

The Workings of the HR Box shall be encased in expanded foam and as such a condense drain connection shall not be required. The removable coils for the valves shall be accessible through a removable panel located on the top of the unit. During installation care must be taken to provide clear access on the top of the unit (Suggest minimum 125 mm) for service purposes.

The control PCB, the power and control wiring terminals shall be provided in an electrical box attached to the front of the unit.

It shall be possible to connect between 1 and 4 indoor units to one PRHR each capable of cooling or heating independently of any other unit.

8

Page 9: LG Multi V SPEC

LGE UK Multi V Spec

INDOOR UNITS

The units shall be:

One way discharge Cassette - Model reference

ARNU07GTJC0ARNU09GTJC0ARNU12GTJC0

The unit casing shall be manufactured from galvanised steel plate and shall be fully insulated.

The fan shall be statically and dynamically balanced to ensure low noise and vibration free operation.

The heat exchanger coils shall be manufactured from copper tubes and aluminium fins.It shall have electronic expansion valve to control refrigerant flow rate in response to the load variation in the conditioned space. The expansion valve shall be controlled by an integral computerised control system to maintain correct room temperature.

The low profile dedicated decoration panel ref shall be provided for each unit. The decoration panel shall incorporate the return air grille and supply air louvers. A facility shall be provided to automatically swing the supply air louvers or lock them at a desired angle between to ensure even distribution of the airflow.

A condensate lift pump shall be provided within the unit and shall be capable of discharging at a height of at least 310 mm above the drain outlet.

The condensate shall be drained from the unit using thermally insulated copper tube and run directly to the foul water drain as indicated.

The air filters shall be incorporated within the unit and shall be washable resin net type.

9

Page 10: LG Multi V SPEC

LGE UK Multi V Spec

Two way discharge Cassette - Model reference

ARNU07GTKC0ARNU09GTKC0ARNU12GTKC0ARNU18GTLC0ARNU24GTLC0

The unit casing shall be manufactured from galvanised steel plate and shall be fully insulated.

The fan shall be of the dual suction multi blade type, statically and dynamically balanced to ensure low noise and vibration free operation.

The heat exchanger coils shall be manufactured from copper tubes and aluminium fins.It shall have electronic expansion valve to control refrigerant flow rate in response to the load variation in the conditioned space. The expansion valve shall be controlled by an integral computerised control system to maintain correct room temperature.

The low profile dedicated decoration panel ref shall be provided for each unit. The decoration panel shall incorporate the return air grille and supply air louvers. A facility shall be provided to automatically swing the supply air louvers or lock them at a desired angle between to ensure even distribution of the airflow.

A condensate lift pump shall be provided within the unit and shall be capable of discharging at a height of at least 310 mm above the drain outlet.

The condensate shall be drained from the unit using thermally insulated copper tube and run directly to the foul water drain as indicated.

The air filters shall be incorporated within the unit and shall be washable resin net type.

10

Page 11: LG Multi V SPEC

LGE UK Multi V Spec

Four-way discharge ceiling Cassette - Model ref –

ARNU24GTHC0ARNU28GTHC0ARNU36GTDC0ARNU42GTDC0ARNU48GTDC0

The unit casing shall be manufactured from galvanised steel plate and shall be fully insulated. Facility shall be provided for duct connection for introduction of the fresh air in the unit and branch ductwork from the unit.

The fan shall be of the propeller type, statically and dynamically balanced to ensure low noise and vibration free operation.

The heat exchanger coils will be manufactured from copper tubes and aluminium fins.It shall have electronic expansion valve to control refrigerant flow rate in response to the load variation in the conditioned space. The expansion valve shall be controlled by an integral computerised control system to maintain correct room temperature.

The low profile dedicated decoration panel shall be provided for each unit. The decoration panel shall incorporate the return air grille and supply air louvers. A facility shall be provided to automatically swing the supply air louvers or lock them at a desired angle to ensure even distribution of the airflow.

A condensate lift pump shall be provided within the unit and shall be capable of discharging at a height of at least 500 mm above the drain outlet.

The condensate shall be drained from the unit using thermally insulated copper tube and run directly to the foul water drain as indicated.

The air filters shall be incorporated within the unit and shall be mould resistant washable resin net type.

11

Page 12: LG Multi V SPEC

LGE UK Multi V Spec

Four way discharge 600 mm square Cassette - Model ref –

ARNU09GTEC0ARNU12GTEC0ARNU18GTEC0

The unit casing shall be manufactured from galvanised steel plate and shall be fully insulated. Facility shall be provided for duct connection for introduction of the fresh air in the unit and branch ductwork from the unit.

The fan shall be of the propeller type, statically and dynamically balanced to ensure low noise and vibration free operation.

The heat exchanger coils will be manufactured from copper tubes and aluminium fins.It shall have electronic expansion valve to control refrigerant flow rate in response to the load variation in the conditioned space. The expansion valve shall be controlled by an integral computerised control system to maintain correct room temperature.

The low profile dedicated decoration panel shall be provided for each unit. The decoration panel shall incorporate the return air grille and supply air louvers. A facility shall be provided to automatically swing the supply air louvers or lock them at a desired angle to ensure even distribution of the airflow.

A condensate lift pump shall be provided within the unit and shall be capable of discharging at a height of at least 500 mm above the drain outlet.

The condensate shall be drained from the unit using thermally insulated copper tube and run directly to the foul water drain as indicated.

The air filters shall be incorporated within the unit and shall be mould resistant washable resin net type.

12

Page 13: LG Multi V SPEC

LGE UK Multi V Spec

Under Ceiling and Floor Mounted convertible unit - Model ref –

ARNU09GVEA0ARNU12GVEA0ARNU18GVJA0ARNU24GVJA0

The unit casing shall be manufactured from heat resistant plastic, the casing colour shall be white. The back plate and the support frames shall be manufactured from galvanised steel plate.

The fan shall be cross flow type, statically and dynamically balanced to ensure low noise and vibration free operation.

The heat exchanger coils will be manufactured from copper tubes and aluminium fins.It shall have electronic expansion valve to control refrigerant flow rate in response to the load variation in the conditioned space. The expansion valve shall be controlled by an integral computerised control system to maintain correct room temperature.

The condensate shall be drained from the unit using thermally insulated copper tube and run directly to the foul water drain as indicated.

The air filters shall be incorporated within the unit and shall be washable resin net type.

13

Page 14: LG Multi V SPEC

LGE UK Multi V Spec

Low Profile LOW ESP Ducted type – Mode l Ref –

ARNU07GB1G0ARNU09GB1G0ARNU12GB1G0ARNU18GB2G0ARNU24GB2G0

The unit casing shall be manufactured from galvanised steel plate and shall be fully insulated. Facility shall be provided for duct connection for introduction of the fresh air in the unit and branch ductwork from the unit. The return air to the unit shall be through the bottom of the unit as standard. A facility shall be provided for alternative return air position through the back of the unit.

The fan shall be inverter driven to allow variable static pressures to suit the installation it shall also be statically and dynamically balanced to ensure low noise and vibration free operation.

The indoor units shall discharge conditioned air to the offices via insulated galvanised mild steel ductwork. The final connection to the supply air diffusers are to be made in flexible ductwork which shall be pre-insulated and shall be no longer than 0.5 m in length with no bends or offsets. The supply air diffusers are to be supplied by the builder.

If required a low profile dedicated decoration panel shall be available as an option. The decoration panel shall incorporate the return air grille. Alternatively a return air grille properly sized for minimum pressure drop at rated air volume can be supplied by others. The return air should be ducted back to the indoor unit in insulated galvanised sheet steel ductwork for accurate temperature control. The ceiling light fittings should not be used for return air.

The heat exchanger coils will be manufactured from copper tubes and aluminium fins.It shall have electronic expansion valve to control refrigerant flow rate in response to the load variation in the conditioned space. The expansion valve shall be controlled by an integral computerised control system to maintain correct room temperature.

A condensate lift pump shall be provided within the unit and shall be capable of discharging at a height of at least 275 mm above the drain outlet.

The condensate shall be drained from the unit using thermally insulated copper tube and run directly to the foul water drain as indicated.

When using the bottom return air configuration the air filters shall be incorporated within the unit and shall be mould resistant washable resin net type.

When using the rear return air configuration a separate filter frame with 25 mm glass fibre throwaway type filter shall be provided for on site installation. A blanking plate shall be provided for the bottom opening. This blanking plate must be removable for access to the internal components of the unit.

14

Page 15: LG Multi V SPEC

LGE UK Multi V Spec 15

Page 16: LG Multi V SPEC

LGE UK Multi V Spec

High ESP ducted type –

ARNU18GBHA0ARNU24GBHA0ARNU28GBGA0ARNU36GBGA0ARNU42GBGA0ARNU48GBRA0

The unit casing shall be manufactured from galvanised steel plate and shall be fully insulated. Facility shall be provided for duct connection for introduction of the fresh air in the unit and branch ductwork from the unit. The return air to the unit shall be through the back of the unit as standard.

The fan shall be inverter driven to allow variable static pressures to suit the installation it shall also be statically and dynamically balanced to ensure low noise and vibration free operation.

The indoor units shall discharge conditioned air to the offices via insulated galvanised mild steel ductwork. The final connection to the supply air diffusers are to be made in flexible ductwork which shall be pre-insulated and shall be no longer than 0.5 m in length with no bends or offsets. The supply air diffusers are to be supplied by the builder.

A return air grille properly sized for minimum pressure drop at rated air volume must be supplied by others. The return air should be ducted back to the indoor unit in insulated galvanised sheet steel ductwork for accurate temperature control. The ceiling light fittings should not be used for return air.

The heat exchanger coils will be manufactured from copper tubes and aluminium fins.It shall have electronic expansion valve to control refrigerant flow rate in response to the load variation in the conditioned space. The expansion valve shall be controlled by an integral computerised control system to maintain correct room temperature.

The condensate shall be drained from the unit using thermally insulated copper tube and run directly to the foul water drain as indicated.

The air filters shall be incorporated within the unit and shall be mould resistant washable resin net type.

16

Page 17: LG Multi V SPEC

LGE UK Multi V Spec

Wall mounted type – Model ref –

ARNU07GSEL0ARNU09GSEL0ARNU12GSEL0ARNU18GS5L0ARNU24GS5L0

The unit casing shall be manufactured from heat resistant plastic. The casing colour shall be white. The back plate and the support frames shall be manufactured from galvanised steel plate.

The fan shall be cross flow type, statically and dynamically balanced to ensure low noise and vibration free operation.

The heat exchanger coils will be manufactured from copper tubes and aluminium fins.It shall have electronic expansion valve to control refrigerant flow rate in response to the load variation in the conditioned space. The expansion valve shall be controlled by an integral computerised control system to maintain correct room temperature.

The condensate shall be drained from the unit using thermally insulated copper tube and run directly to the foul water drain as indicated.

The air filters shall be incorporated within the unit and shall be washable resin net type.

Wall mounted Artcool type – Model ref –

ARNU07GSPM1ARNU09GSPM0ARNU12GSPM0ARNU18GSVM0

The unit casing shall be manufactured from heat resistant plastic. The facia panel shall be available in a number of colours to be specified. The back plate and the support frames shall be manufactured from galvanised steel plate.

The fan shall be, statically and dynamically balanced to ensure low noise and vibration free operation.

The heat exchanger coils will be manufactured from copper tubes and aluminium fins.It shall have electronic expansion valve to control refrigerant flow rate in response to the load variation in the conditioned space. The expansion valve shall be controlled by an integral computerised control system to maintain correct room temperature.

The condensate shall be drained from the unit using thermally insulated copper tube and run directly to the foul water drain as indicated.

17

Page 18: LG Multi V SPEC

LGE UK Multi V Spec

The air filters shall be incorporated within the unit and shall be washable resin net type.

18

Page 19: LG Multi V SPEC

LGE UK Multi V Spec

Wall mounted Artcool Mirror type – Model ref –

The unit casing shall be manufactured from heat resistant plastic. The facia panel shall be available in a number of colours to be specified. The

back plate and the support frames shall be manufactured from galvanised steel plate.

The fan shall be, statically and dynamically balanced to ensure low noise and vibration free operation.

The heat exchanger coils will be manufactured from copper tubes and aluminium fins.It shall have electronic expansion valve to control refrigerant flow rate in response to the load variation in the conditioned space. The expansion valve shall be controlled by an integral computerised control system to maintain correct room temperature.

The condensate shall be drained from the unit using thermally insulated copper tube and run directly to the foul water drain as indicated.

The air filters shall be incorporated within the unit and shall be washable resin net type.

ARNU07GSER0ARNU09GSER0ARNU12GSER0ARNU18GS3R0ARNU24GS3R0

19

Page 20: LG Multi V SPEC

LGE UK Multi V Spec

Floor standing cased type – Model ref –

ARNU07GCEA0ARNU09GCEA0ARNU12GCEA0ARNU18GCFA0ARNU24GCFA0

The unit casing shall be manufactured from galvanised steel plate fully insulated. The casing colour shall be white.

The fan shall be, statically and dynamically balanced to ensure low noise and vibration free operation.

The return air shall be through the bottom of the unit while the supply air shall be through the louvers situated on the top of the unit. These louvers shall be manually adjustable to select most suitable airflow pattern.The heat exchanger coils will be manufactured from copper tubes and aluminium fins.

It shall have electronic expansion valve to control refrigerant flow rate in response to the load variation in the conditioned space. The expansion valve shall be controlled by an integral computerised control system to maintain correct room temperature.

The condensate shall be drained from the unit using thermally insulated copper tube and run directly to the foul water drain as indicated.

The air filters shall be incorporated within the unit and shall be washable resin net type.

20

Page 21: LG Multi V SPEC

LGE UK Multi V Spec

Floor standing un-cased unit – Model ref -

ARNU07GCEU0ARNU09GCEU0ARNU12GCEU0ARNU18GCFU0ARNU24GCFU0

The unit casing shall be manufactured from galvanised steel plate, fully insulated and designed to be encased in decorative casing to suit the building decor.

The fan shall be statically and dynamically balanced to ensure low noise and vibration free operation.

The return air shall be through the bottom of the unit while the supply air shall be through the top of the unit. The supply and the return air grilles are to be provided by the builder and should be selected for minimum pressure drop. The return air grille is to be located at the bottom of the casing and the supply air grille is to be located on the top of the casing. These grilles must cover the full width and depth of the respective apertures provided on the unit. A short piece of ductwork must be installed between the discharge air spigot as provided on the unit and the supply air grille.

The heat exchanger coils will be manufactured from copper tubes and aluminium fins.It shall have electronic expansion valve to control refrigerant flow rate in response to the load variation in the conditioned space. The expansion valve shall be controlled by an integral computerised control system to maintain correct room temperature.

The condensate shall be drained from the unit using thermally insulated copper tube and run directly to the foul water drain as indicated.

The air filters shall be incorporated within the unit and shall be washable resin net type.

21

Page 22: LG Multi V SPEC

LGE UK Multi V Spec

CONTROLS

Computerised control shall be used to maintain a correct room temperature either at the fan coil or from a sensor in the remote controller. The system shall be equipped with a self-diagnostic feature for easy service and maintenance. The LCD remote controller shall be able to control up to 16 indoor units as a group. It shall also be possible to select cooling, heating, fan only or automatic change over mode for heat recovery systems.

Standard remote controller

The remote controller shall perform the following functions:

a) On / off control.b) Temperature set point control.c) Fan speed control.d) Operation mode control. (For Heat-Recovery systems only)e) Swing louver position control. (If fitted)f) Malfunction indication code display for ease of servicing and maintenance.g) 7 day time clocking

Deluxe touch screen remote controller

The remote controller shall perform the following functions:

a) On / off control.b) Temperature set point control.c) Fan speed control.h) Operation mode control. (For Heat-Recovery systems only)i) Swing louver position control. (If fitted)j) Malfunction indication code display for ease of servicing and maintenance.k) 7 day time clocking

The controller is to have a backlit touch screen display with no buttons.

Simplified remote controller

As full function controller but without swing louver and timer

Hotel remote controller

As full function controller but without swing louver, timer and operation mode control

22

Page 23: LG Multi V SPEC

LGE UK Multi V Spec

Deluxe centralised Controller

A multi functional centralised Controller shall be supplied.

It will provide the following features:

Start/stop operation, set point control, cool/heat mode selection, air volume setting, air flow direction setting and enabling/disabling operation of the remote.

Monitoring of operation status of the indoor units and error code of the group or the zone.

Comprehensive timer function to start/stop the air conditioning systems. This can be set for year, month, day of week, hour and minute. This will enable normal day-to-day time clock functions as well as yearly holiday set up..

Power proportional distribution with optional memory card DCS002A1 and external kW hour meters.

The controller shall have wide colour touch screen control colour display and can be wired by a non-polar 2-wire transmission cable to a distance of 200m away from the outdoor units.

23