Fundamentals of
Load Frequency Control (LFC)and
Automatic Generation Control(AGC)
5/20/2018 Lec-5 Fundamentals of AGC
2/16
The system frequency reaches steady-state at a value
that causes the sum of the on-line generator output
MW to be equal to the system load MW.
With this type of governor Control (Primary Control),when the system load increases, the system
frequency decreases and visa versa.
How do we control frequency to 50HZ, no matter whatthe load is?
We need Secondary Control also
Limitation of Governor Control (Pr. Control)
2
5/20/2018 Lec-5 Fundamentals of AGC
3/16
Governor with
Speed-droop
Feedback Loop
3
(Ref. W&W p. 337)
By changing the load
reference set pointThe generators governor
characteristics
can be set to give
reference frequency fo
at any desired unitoutput.
The bas ic con tro l input to th e
generat ing un it as far as generat ion
contro l is co ncerned is the load
reference set po int (Raise/Lower).By adjusting this set point on each
unit, a desired unit dispatch can be
maitained while holding system
frequency close to the desiredvalue
5/20/2018 Lec-5 Fundamentals of AGC
4/16
Speed-Changer Settings
4
5/20/2018 Lec-5 Fundamentals of AGC
5/16
Steady-state speed characteristic
with speed changer
50
5
5/20/2018 Lec-5 Fundamentals of AGC
6/16
Power output as a function of frequency
6
5/20/2018 Lec-5 Fundamentals of AGC
7/16
7
5/20/2018 Lec-5 Fundamentals of AGC
8/16
Primary Control
Secondary Control
8
5/20/2018 Lec-5 Fundamentals of AGC
9/16
How does the addition of the Raise/Lower Speed
Changer( Sec. Control) to the Governor Control (Pr.Control) facilitate the control of frequency?
Hint: It causes the sum of the on-line generator
output MW to be equal to the system load MWexactly at desired value of steady-state system
frequency.
Governor alone can not eliminate frequency errorcaused by load changes. Advantage of governor is its
quick response and reasonable frequency correction
9
Primary Control and Secondary Control
5/20/2018 Lec-5 Fundamentals of AGC
10/16
From a central control site, you increase or decrease
the no-load frequency set-points of generating unitsuntil the sum of the generated power is equal to the
present system load, then the frequency will stabilize
at 50HZ.
This form of supplemental control is called Automatic
Generation Control (AGC) and more specifically, Load
Frequency Control (LFC).
AGC, and LFC
10
5/20/2018 Lec-5 Fundamentals of AGC
11/16
Automatic Generation Control, AGC
AGC is usually implemented in EnergyManagement System(EMS) of Energy
Control Centers(ECC).
The components of AGC in modern powersystem are:
Load Frequency Control(LFC)
Economic Dispatch(ED)
Interchange Scheduling(IS)
11
5/20/2018 Lec-5 Fundamentals of AGC
12/16
5/20/2018 Lec-5 Fundamentals of AGC
13/16
13
To
50 Hz
5/20/2018 Lec-5 Fundamentals of AGC
14/16
14
ACE Calculation
5/20/2018 Lec-5 Fundamentals of AGC
15/16
15
Generation Allocation
5/20/2018 Lec-5 Fundamentals of AGC
16/16
Losses, Loads, Export PowerGenerated, Import
50 Hz, in ourcountry
16