Large naphtha storage tank fire at Tomakomai, Japan (part 2) National Research Institute of Fire and Disaster, Japan Hiroshi Koseki
18

Large naphtha storage tank fire at Tomakomai, Japan (part 2) National Research Institute of Fire and Disaster, Japan Hiroshi Koseki.

Dec 15, 2015

Download

Documents

Efren Crane
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: Large naphtha storage tank fire at Tomakomai, Japan (part 2) National Research Institute of Fire and Disaster, Japan Hiroshi Koseki.

Large naphtha storage tank fire at Tomakomai, Japan (part 2)

National Research Institute of Fire and Disaster,

Japan  Hiroshi Koseki

Page 2: Large naphtha storage tank fire at Tomakomai, Japan (part 2) National Research Institute of Fire and Disaster, Japan Hiroshi Koseki.

Two fires occurred after the eathquake

Crude oil tank September 26, 2003, just after the

earthquake   Naphtha tank fire  September 28 , 10 : 49 AM Koseki was asked to help fire-fighting against

the second fire, who was in Tokyo. About 5 hours after fire, he was there.

Page 3: Large naphtha storage tank fire at Tomakomai, Japan (part 2) National Research Institute of Fire and Disaster, Japan Hiroshi Koseki.

Summary of Naphtha tank

No.30063 tank, floating roof, single roof Storage volume  32,779kl ,  

26,000kl exist ( Fuel height :about 18 m)

Diameter  42.7m  Height  24.4m

Built in 1974 as crude oil tank Then changed for storage of naptha

Page 4: Large naphtha storage tank fire at Tomakomai, Japan (part 2) National Research Institute of Fire and Disaster, Japan Hiroshi Koseki.

naphtha No posibility for boilover because of 71

C for 95 % distilation Similar to gasoline, but lower boiling poi

nt Flash point  ー20℃ Burning rate is very high ; 5-8 mm / m

in ( 0.36-0.50m / hour ) Due to strong wind, it was higher.

Page 5: Large naphtha storage tank fire at Tomakomai, Japan (part 2) National Research Institute of Fire and Disaster, Japan Hiroshi Koseki.

Distilation curves(Naptha, Crude oil and gasoline)

0

50

100

150

200

250

300

0 20 40 60 80 100

( 流出量 Vol.% )

(℃

)温

ガソリンナフサMurban

m

Crude oil

Naptha

gasoline

Volume %

Temperature C

Page 6: Large naphtha storage tank fire at Tomakomai, Japan (part 2) National Research Institute of Fire and Disaster, Japan Hiroshi Koseki.

Burning rate during the fire

Period Burning rate(m/hr)

Ignition - 4 hr 0.36

4 hr - 8 hr 0.50

These values are very large, normally 0.2-0.4m/hr for gasoline, keroseneBecause naphtha is very light

Page 7: Large naphtha storage tank fire at Tomakomai, Japan (part 2) National Research Institute of Fire and Disaster, Japan Hiroshi Koseki.

4 :0 5 AM, September 29Start of large fure fighting gun, 17 hours after start of the fire

Page 8: Large naphtha storage tank fire at Tomakomai, Japan (part 2) National Research Institute of Fire and Disaster, Japan Hiroshi Koseki.

9:32 AM Sep. 29

Page 9: Large naphtha storage tank fire at Tomakomai, Japan (part 2) National Research Institute of Fire and Disaster, Japan Hiroshi Koseki.

1:00 AM, September 29

Page 10: Large naphtha storage tank fire at Tomakomai, Japan (part 2) National Research Institute of Fire and Disaster, Japan Hiroshi Koseki.

Tank Fall down, at 1:23 PM, September

Page 11: Large naphtha storage tank fire at Tomakomai, Japan (part 2) National Research Institute of Fire and Disaster, Japan Hiroshi Koseki.

2:06 PM, Sep. 29

Page 12: Large naphtha storage tank fire at Tomakomai, Japan (part 2) National Research Institute of Fire and Disaster, Japan Hiroshi Koseki.

2:07 PM September 29

Strong heat flux damaged fire engine

Page 13: Large naphtha storage tank fire at Tomakomai, Japan (part 2) National Research Institute of Fire and Disaster, Japan Hiroshi Koseki.

About 6:30 AM September 30

Page 14: Large naphtha storage tank fire at Tomakomai, Japan (part 2) National Research Institute of Fire and Disaster, Japan Hiroshi Koseki.

Tanks after the fire

Page 15: Large naphtha storage tank fire at Tomakomai, Japan (part 2) National Research Institute of Fire and Disaster, Japan Hiroshi Koseki.

Oil storagety storage base near Idemitsu Refinary, very little damage by the same earthquake

Page 16: Large naphtha storage tank fire at Tomakomai, Japan (part 2) National Research Institute of Fire and Disaster, Japan Hiroshi Koseki.

Problems in fire-fightings Not enough extinguish agent,

because two fires occurred after the earthquake

Commanding system is not good, because so many fire departments came

Strong wind, tank height is high, so extinguish agent did not reach inside tank

Page 17: Large naphtha storage tank fire at Tomakomai, Japan (part 2) National Research Institute of Fire and Disaster, Japan Hiroshi Koseki.

Problems, use of foam extinguih agent

Each fire fighter group has different agent

Government: synthetic foam Idemitsu: AFFF, Protein Foam National storage base: Protein Foam USA military: AFFF

Page 18: Large naphtha storage tank fire at Tomakomai, Japan (part 2) National Research Institute of Fire and Disaster, Japan Hiroshi Koseki.

Conclusion To extinguish we need 44 hours,

and most fuel was burnt out. Naphtha is so difficult to be

extinguished Other problems, strong wind,

height of tank is 24 m However, no human damage