Top Banner
Lagfæring eða tengli skipt út Leiðbeiningar varðandi lagfæringar á galla í tvöföldum tenglum frá Strömfors
7

Lagfæring eða tengli skipt út

Jan 14, 2016

Download

Documents

Jadzia

Lagfæring eða tengli skipt út. Leiðbeiningar varðandi lagfæringar á galla í tvöföldum tenglum frá Strömfors. Hafa samband við Ískraft Skrá þarf niður verkið og fá afhent beiðna númer. Verkfæri til verksins Íhluti til lagfæringar Nýja tengla ef skipta þarf út ónýtum tenglum - PowerPoint PPT Presentation
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: Lagfæring eða tengli skipt út

Lagfæring eða tengli skipt út

Leiðbeiningar varðandi lagfæringar á galla í tvöföldum

tenglum frá Strömfors

Page 2: Lagfæring eða tengli skipt út

Hafa samband við Ískraft Skrá þarf niður verkið og fá afhent beiðna númer

• Verkfæri til verksins• Íhluti til lagfæringar• Nýja tengla ef skipta þarf út ónýtum tenglum• Límmiða sem eru límdir inní rafmagnstöflu viðkomandi hæðar eða

byggingar að loknu verki.

• Gula límmiða sem eru límdir á hvern kassa með gölluðum tenglum

Rafverktakinn þarf að fá afhent :

Page 3: Lagfæring eða tengli skipt út

Special tools

markerTesting device for outletsThe testing device is loaded with a marker by turning and removing the handle,see picture on the right. The handle can befixed in both directions. When testing a badly broken outlet, the red marksof the testing device will stay visible. If this happens, the current has to be cut before continuing work!The marker makes a dot in the outlet, this shows that the outlet has been tested. The handle of this testing device is also used for removingThe feeding unit, in combination with below removing tool

NOTE! When you have a longer brake in the testing, please put the cap on the marker to avoid it from drying.

Removing toolThe removing tool is used for two different purposes:

1. Removing the outlets from the trunking.

2 Removing the feeding unit from an outlet - to do this you also need the above testing device for

pushing the feeding unit loose, see picture on the right.

”Dymo” or equivalent printerFor renewing markings on outlets that need to be replaced.

XXXXXXXX

Page 4: Lagfæring eða tengli skipt út

a

bc

ab

b4. Remove end pieces (a) and covers (b) 5. Remove outlets one by one with the removing tool.

BROKEN

2. Test: Push and keep pushed

OK

CUT POWER FROMTHE CENTRAL!

YOU MAY CONTINUEWITH CURRENT ON

3. Check result and continue accordingly. Test all outlet holes. When youhave a brake in testing, please put the cap on the marker

a

b

. .b

Repplace the broken outlets with new outlets, make new marking with ”Dymo” where needed.

The work may be done with current on if these instructions are followed:NOTE! Work must stop if you run out of securing parts or replaecement products!

23 395 double outlets repair/replacement instructions

NOTE! When working on poles, the end plate of the trunking portion may have to be removed to enable sliding of the outlets sideways to give room for the removing tool.

MINOR CRACKS

7.

a a

6. Check all outlets in the group for cracks: Do yo find any cracks? Follow instructions below

1. Identification of outlet 23 395: a.Holes are in a straight row b.End pieces are removable

ab

Fix the securing part (a) on all non-broken outlets.

8. Finalizing the work and general instructions:

Refit the secured or new outlets, covers and end pieces into the Trunking, keep these things in mind:-The rib of the feeding unit must be aligned with a notch in the trunk-Avoid big colour differences by renewing all outlets in the same group if necessary Put broken outlets into the same package as the replacement outlets were distributed in, close full 5-packs with the yellow ”DUCTEL PSA”stickes. Read more about the return procedure in our customer letter!

Finalize your work by marking all distribution boards with a sticker, on the sticker you should mark when work was finalized, name of the installation company and initials of the installer.

Check that the black dots(b) From testing (point 2) are visible. If needed, mark again manually.

CRACKS

Remove the feeding unit if needed like this: Refit the outlet with feeding unit to the trunking. Place removing tool (a) in the trunking, push with testing device (b) and push the feeding unit into the trunking by hand (c). Remove the outlet as described in point 5.

When pushed, red marksstay visible

When pushed, red marks are not visible

Installation company Installer

Company X / NN

Work done

XXXXXXXX

1.2.2008

a

example of a crack

For definition -See next slide!

Page 5: Lagfæring eða tengli skipt út

Corrective Action – Back Cover for Repair

• From November 2008 the repair/replace instruction was changed– Also outlets with minor cracks to be repaired– Validated in test lab + approved by authorities in FI, SE and NO

Page 6: Lagfæring eða tengli skipt út

Skil á gölluðum tenglum

DUCTEL PSAPalautusnumero/ Returnummer/ Return number:

Skrifa skal beiðna númer á gula miðann.

Setja skal brotnu tenglana í sömu pakkningar og útbýttu tenglarnir komu úr, lokið síðan heilum pakka með 5 tenglum með gulum ”DUCTEL PSA” límmiða. Pakkinn sendist eða skilast inn til Ískrafts

Page 7: Lagfæring eða tengli skipt út

Reikningur frá Rafverktaka

• Beiðna númer

• Fjöldi tengla lagfærðir

• Fjöldi tengla skipt út

• Fjöldi vinnustunda

Það sem þarf að koma fram á reikningnum er :