Top Banner

of 148

Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
  • Section 10 Overhead Lines and Underground Cables Overhead lines Overhead lines supports (towers and poles) Overhead lines conductors Fittings Representation of lines Underground cables Insulation, thermosetting and thermoplastic for cables

    1

  • Overhead Lines Overhead lines are usually suspended from insulators. The insulators are supported by towers or poles. The span between two towers depends upon the allowable sag

    in the line. Example: the span for steel towers with very-high voltage lines

    is normally 370-460 m. There are two main types of towers as follows:

    Those for straight runs, which are designed to withstand the stress due to the weight of line alone.

    Those for changes in route also known as deviation towers. They need to be able to withstand resultant forces due to line changing directions.

    2

  • Overhead Lines Overhead lines are, in essence, air-insulated cables suspended

    from insulated supports with a power transfer capacity approximately proportional to the square of the line voltage.

    The overhead lines components under IEC standards are as follows: conductors fittings vibration dampers supports.

    3

  • Overhead Lines Overhead lines versus underground cables Cables are more expensive than overhead lines, the higher

    ratios being found at higher voltages. For the transmission of equivalent power at 11 kV, a cable feeder would cost some 5 times the cost of a transmission line, at 132 kV 8 times and at 400 kV, 23 times.

    Overhead lines are a lot more forgiving when it comes to overloading than cables.

    Catastrophic failures due to short circuits are rare. Line damages can be discovered and repaired more easily than

    underground cables. Over head lines can be altered easily in situ to accommodate

    change.

    4

  • Overhead Lines Key elements: Transmission voltage evolution Voltage classification according to EN 60071 and General Use International and European standards Technical comparison of AC and DC transmission

    5

  • Transmission Voltage Evolution

    1910 1920 1930 1940 1950 1960 1970 1980 1990 20000

    200

    400

    600

    800

    1000

    1200

    Year of inauguration

    Tran

    smis

    sion

    vol

    tage

    (kV

    )

    6 Development of three-phase AC network transmission voltages

  • Voltage Classification According to EN 60071 and General Use Below 1 kV: Low Voltage (LV) Between 1 kV and 45 kV : Medium Voltage (MV) Between 45 kV and 300 kV : High Voltage (HV) Between 300 kV and 75 kV : Extra-High Voltage (EHV) Above 800 kV : Ultra-High Voltage (UHV)

    7

  • International and European Standards for Overhead Lines

    Standard Description IEC 60383 Insulators for overhead lines with a nominal voltage above 1000 V

    IEC 60471 Dimensions of clevis and tongue couplings on string insulator units

    IEC 60720 Characteristics of line post insulators

    IEC 60797 Residual strength of string insulator units of glass or ceramic material for overhead lines after mechanical damage to the dielectric

    IEC 60826 Design criteria for overhead transmission lines

    IEC/TR 60828 Loading and strength of overhead transmission lines

    IEC/TR 61774 Meteorological data for assessing climatic loads for overhead lines

    EN 12465 Wood poles for overhead lines durability requirements

    EN 12479 Wood poles for overhead lines signs, methods of measurement and densities

    EN 12510 Wood poles for overhead lines strength grading criteria

    EN 12511 Wood poles for overhead lines determination of characteristic values

    EN 12509 Timber poles for overhead lines determination of modulus of elasticity, binding strength, density and moisture content 8

  • International and European Standards for Overhead Lines Standard Description

    EN 14229 Wood poles for overhead lines requirements

    EN 12843 Precast concrete masts and poles

    EN 50341 Overhead electrical lines exceeding AC 45 k V

    EN 50423 Overhead lines AC 1 to 45 k V

    Eurocode 1 EN 1991 Basis of design and actions on structures; 1991-1-3 covers snow loads; 1991-2-4 covers wind loads

    Eurocode 2 EN 1992 Design of concrete structures 1992-3 covers concrete foundations

    Eurocode 3 EN 1993 Design of steel structures

    Eurocode 7 EN 1997 Geotechnical design

    Eurocode 8 EN 1998 Design provision for earthquake resistance of structures

    9

  • Technical Comparison of AC and DC Transmission Advantages of DC line towards AC lines DC lines present lower power losses. DC lines present lower switching overvoltage and therefore

    lower clearance to tower. DC lines introduce no problem of stability. DC lines have the ability to interconnect systems of different

    frequency through back-to-back converter stations. DC lines present lower levels of short circuit.

    10

  • Technical Comparison of AC and DC Transmission Disadvantages of DC line towards AC lines DC lines cannot directly supply loads. DC lines cannot be economically taped to supply consumers. The converter stations need a high ratio of reactive power to

    supply commutation equipments which reaches to 60% of active power.

    11

  • Support Types and their Applications Definition: Towers or poles are parts of support and consist of

    tower or pole body, earth wire peaks and cross arms. Transmission voltage, the number of circuits, the height of

    supports and other aspects determine the support design and materials.

    Self-supporting structures: Poles made of reinforced concrete, solid wall steel and wood as well as steel towers and portal structures.

    12

  • Support Types and their Applications Key elements: Pole structures Tower structures Tasks of supports in an overhead line Support design and application

    13

  • Pole Structures Pole structures are especially used for economic household

    distribution at voltage levels of 380/415 V and 20/11kV where planning permission allows such arrangements in place of buried cables.

    Pole structures are also used at the lower transmission voltage levels, typically at up to 145 kV but also with multipole and guyed (stayed) arrangements at voltages up to 330kV.

    Low-voltage designs are based on matching the calculated equivalent pole head load to the particular type and diameter of wood, steel or concrete to be employed.

    At higher voltages specific designs are used in order to select optimum size and relative cost.

    14

  • Typical Pole Structures

    15

    Low voltage Wood pole

    Low voltage thin wall steel pole

    Single circuit Single circuit Trient (no earth wire)

  • Typical Pole Structures

    16

    Single circuit twin earth wire

    Combined 3 wires 11 kV and 380 V

    Double circuit twin earth wire

  • Tower Structures In order to standardise, towers are categorized typically to fulfill the

    following duties: Suspension towers: straight line and deviation angles up to about 2 10 angle or section tower: angles of deviation up to 2 or at section

    positions also for heavy weight spans or with unequal effective negative weight spans

    30 angle: deviation angles up to 30 60 angle: deviation angles up to 60 90 angle: deviation angles up to 90 Terminal tower: terminal tower loading taking full line tension on one

    side of tower and none or slack span on other typically at substation entry

    17

  • Typical Tower Outlines

    18

    Single circuitSingle earth wire

    Double circuitSingle earth wire

  • Typical Tower Outlines

    19

    Single circuitdouble earth wire

    Double circuitdouble earth wire

  • Tasks of Supports in an Overhead Line 1. Suspension supports 2. Angle suspension supports 3. Angle supports 4. Strain and angle strain supports 5. Dead-end supports 6. Special supports

    20

  • Tasks of Supports in an Overhead Line 1. Suspension supports:

    Carry the conductors in a straight line.

    2. Angle suspension supports: Serve as suspension supports for conductors where the line

    changes the direction at line angle deflection. Important at voltages higher than 110 kV. The angle change is 0-20 degrees.

    3. Angle supports: Carry the resulting conductor tensile forces where the line

    changes direction at line angle deflections.

    21

  • Tasks of Supports in an Overhead Line 4. Strain and angle strain supports:

    Carry the conductor tensile force in line direction or in resultant direction.

    Serve as rigid points in the line. Secure the line against cascading failures.

    5. Dead-end supports: Carry the total conductor tensile forces in line direction on one

    side. Are additionally loaded by conductors leading to the substation

    portals. Act often under large angle to the horizon over a short distance.

    22

  • Tasks of Supports in an Overhead Line 6. Special supports:

    Supports that are used for several functions of individual supports. For example, a branch support which assumes the task of angle or angle-strain support concerning the circuit passing through.

    23

  • Support Design and Application 1. Selection of support design 2. Self supporting lattice steel towers 3. Self supporting steel poles 4. Steel reinforced concrete poles 5. Wood poles 6. Guyed supports 7. Cross-armless supports

    24

  • Support Design and Application 1. Selection of support design factors:

    Optimum utilization of right-of-way Environmental impact Prospected life time Location Terrain and its access Number of circuits to be installed on the same structure Mechanical and climetical load Required height of structure Land use for the line and its vicinity Keraunic level and arrangement of earth wires Required methods of construction and maintenance Investment

    25

  • Support Design and Application 2. Self supporting lattice steel towers

    The most traditional overhead lines. Suitable for local conditions demanding narrow tower locations

    and right of way Above 150 kV All kinds of conductor configuration Easy to be upgraded Easy to exchange cross arms Increasing of tower heights is possible Easy to repair Unnecessary towers can be scraped and recycled They are hot-dip galvanised for corrosion protection

    26

  • Self Supporting Lattice Steel Towers

    Self supporting lattice steel tower

    27

  • Support Design and Application 3. Self supporting steel poles:

    Used in congested urban areas Able to accommodate insulating crossarms Low visual impact Suspension poles made of H-beam sections can be adopted for

    medium voltage lines. H-beams: low torsional stiffness. Seamless tubular steel poles: Section by section differing diameter

    and canonical shape. Adjustable to bending momentum. Canonical steel poles: six, eight or more sides. Shape and cross

    section can be adjusted for loads. Used f or high voltage. 110 and 400 kV have been used.

    28

  • Self Supporting Steel Poles

    Self supporting steel pole

    29

    FILIP BRNADICFILIP BRNADIC 4 September 2013 2:01 PM

  • Support Design and Application 4. Steel reinforced concrete poles:

    Steel reinforced concrete poles are used as spun concrete poles for low and medium voltage installations, 110 and 132 kV double circuit lines

    Long service life with out any efforts for maintenance Low visual impact for residential area High weight is a disadvantage. Hard to be transported and erected

    30

  • Support Design and Application 5. Wood poles:

    Wood poles are the simplest and cheapest support structures. They have been made from larch, spruce, cedar, pine and fir trees, selected specially for height and straightness.

    They are very flexible and they can bend and give under sudden severe loads.

    Under severe forces, such as strong storm winds perpendicular to the line, the force on the pole may be dissipated in the ground. Usually, they can be straightened.

    Have been used for 100 kV and 220kV in North America and Australia.

    31

  • Support Design and Application

    Guyed V-tower

    6. Guyed supports: Types: H, V and Y Frequently used for long

    single-circuit lines Suitable for agricultural

    areas.

    32

  • Support Design and Application

    Crossarm-less support

    Mast

    Spacer cable Cross ropeEarth wire

    7. Cross-armless supports: Used to make compact lines First used for 735 kV line in Canada.

    33

  • Design Spans In order to design suitable tower dimensions for an overhead

    line it is necessary to calculate the conductor sags and tensions.

    The maximum conductor tension (which will occur at minimum temperature) is evaluated in order to ensure a sufficient mechanical strength margin for the particular conductor.

    The sag is calculated in order to fix the tower height. The ruling condition for the conductor has to be determined

    based on either the maximum working tension (MWT), the everyday stress (EDS) or, potentially, the maximum erection tension (MET).

    34

  • Design Spans Key elements: Basic span Wind span Weight span Equivalent span

    35

  • Basic Span

    36

    3O O A B C EH C S S S S S

    SE

    SA

    SA

    SA

    SC

    SB

    SO

    C

    H

    C : statutory clearance to ground SA : length of insulator suspension set SB, SC, SE : vertical distances between crossarms and conductor above or to earth wire SO : sag of conductor (proportional to square of span)

  • Wind Span The wind span is half the sum of the adjacent span lengths. At 230 kV this might be 400 m under normal conditions and 300

    m under broken wire conditions. At 132 kV typical values are 365 m and 274 m respectively.

    37

  • Weight Span The weight span is the distance between the lowest points on

    adjacent sag curves on either side of the tower. The ratio of weight span to wind span is also important since

    insulators on lightly loaded towers may be deflected excessively thus encroaching electrical clearances.

    A ratio of weight span to wind span of approximately 1.52 is often considered acceptable.

    38

    230 kV 132 kV

    Suspension towers 750 m Normal conditions 680 m Normal conditions

    565 m Broken wire Conditions 510 m Broken wire Conditions

    Tension towers 750 m Normal conditions 680 m Normal conditions

    750 m Broken wire Conditions 680 m Broken wire Conditions

    Typical weight span values at 230 kV and 132 kV

  • Weight Span

    39

    L1 L2 L3

    Cold sag temperature curve

    Weight span

  • Equivalent Span

    L1 L2 L3

    40

    The equivalent span is defined as a fictitious single span in which tension variations due to load or temperature changes are nearly the same as in the actual spans in a section.

    Equivalent span

    3 3 31 2 3

    1 2 3

    L L LL L L L Equivalent span :

  • Loads on Over-head Lines 1. Wind loading 2. Conductor loadings:

    Conductor tensions Short circuit loadings Ice loading Seismic loads Combined loads Broken wire conditions

    41

  • Loads on Over-head Lines Wind loading: It is normal practice to consider wind loads on structures due to a 3-second gust that occurs over a 50-year period. The wind load is related to the wind speed in accordance with the code of practice applicable to the country where the work is being carried out. In the EU the relevant information is set out in the NNAs of EN50341 and 50423. It describes procedures for calculating wind loads on both structures and conductors, with considerable variation in detail between individual countries.

    42

  • Conductor Tensions

    43

    2

    8W g LT NS

    The tension, T, in the conductor for a given sag, S, is given by the formula:

    W : weight of conductor per unit length (kg/m) L : span of the conductor (m) G : gravitational constant (1 kgf or 9.81 N) S : sag (m)

  • Short Circuit Loading Under short circuit conditions lateral mechanical attraction or repulsion forces will occur between the different phase conductors. The effect of conductor movement during short circuits is erratic and difficult to calculate. Such movement is taken into account in the overall design by allowing adequate clearances between the phase conductors. The conductor short circuit forces are usually ignored in the structural design of overhead line towers or substation gantries because of the very short durations of the faults.

    44

  • Loads on Over-head Lines Ice loading

    The build-up of ice on conductors will increase effective conductor weight, diameter and wind loading. Local experience must be used in the application of ice loads to structural design. As an example, EN 50341-3-9 calls for a uniform ice load on all spans of 5 kN/m3 to be considered for UK designs, or 9 kN/m3 in case of wind and ice.

    Seismic loads The acceleration due to a seismic event is categorized as a

    fraction of the gravitational constant, g. This may be given for both horizontal and vertical effects over a frequency spectrum.

    45

  • Loads on Over-head Lines Combined loads

    The simultaneous application of individual worst case loads is unlikely to occur in practice and the simple arithmetic addition of all such load cases would lead to an uneconomic and over-engineered solution. The individual loads are therefore factored to arrive at a sensible compromise.

    wind load plus ice load is often taken as full ice loading plus wind load at, say, 50% basic wind speed. Similarly, wind load plus seismic load is normally taken as full earthquake load plus 50% wind load.

    46

  • Broken Wire Condition The towers themselves are usually designed such that no

    failure or permanent distortion occurs when loaded with forces equivalent to 2 times the maximum simultaneous vertical, transverse or longitudinal working loadings for suspension towers and 2.5 times for tension towers.

    Under broken wire conditions the towers must be capable of withstanding typically 1.25 times the maximum simultaneous resulting working loadings.

    47

  • Overhead Line Conductor and Technical Specifications Key elements: Environmental conditions Environmental effects Connector selection Calculated electrical rating Conductor and earth wire spacing and clearances

    48

  • Environmental Conditions Temperature Wind velocity Solar radiation Rainfall Humidity Altitude Ice and snow Atmospheric pollution Soil characteristic Lightning Seismic factor General loadings

    49

  • Environmental Effects Corrosion Corona

    50

  • Corrosion Aluminum conductors have good corrosion behavior

    essentially resulting from the formation of an undisturbed protective surface oxide layer which prevents further corrosion attack.

    ACSR is known to suffer from bi-metallic corrosion which is noticeable as an increase in conductor diameter due to corrosion products in the steel core known as bulge corrosion.

    Early problems associated with deterioration of the steel cores used in ACSR conductors have been resolved over the years by the use of high temperature greases.

    AAAC will obviously offer superior corrosion resistance than ungreased ACSR.

    51

  • Corrosion For very aggressive environments the following order of

    preference is suggested: Aluminum conductor fully greased. Aluminum conductor with alumoweld core fully greased. ACSR fully greased. Aluminum alloy conductor fully greased. Aluminum conductor with alumoweld core ungreased. ACSR with greased core.

    52

  • Corona High voltage gradients surrounding conductors (above about

    18 kV/cm) will lead to a breakdown of the air in the vicinity of the conductor surface known as corona discharge.

    This effect is more pronounced at high altitudes. Generally, the breakdown strength of air is approximately 31 kV peak/cm or 22kV rms/cm.

    At higher voltage levels, and certainly at voltages of 400 kV and above, interferences due to the corona effect can be the dominant factor in determining the physical size of the conductor rather than the conductor thermal rating characteristic.

    53

  • Corona The corona effect is more severe around small conductors and

    at sharp points and corners. Corona absorbs energy from the line. Corona losses can be reduced by taking the following actions:

    Separating conductors with spacers placed periodically along the line.

    Bundling of high voltage conductors.

    54

  • Corona Practical formula to calculate voltage surface gradient (Vg)

    55

    [ / ]/ 2 log 2 /p

    ge

    UV kV cmd D d

    Up : phase voltage (kV) d : diameter of single conductor (cm) D : distance between phases for single phase line or equivalent spacing for three phase lines (cm)

  • Overhead line Conductor and Technical Specifications Connector selection: The selection of the most appropriate conductor

    size at a particular voltage level must take into account both technical and economic criteria as listed below:

    The maximum power transfer capability must be in accordance with system requirements.

    The conductor cross-sectional area should be such as to minimize the initial capital cost and the capitalized cost of the losses.

    The conductor should conform to standard sizes already used elsewhere on the network in order to minimize spares holdings and introduce a level of standardization.

    The conductor thermal capacity must be adequate. The conductor diameter or bundle size must meet recognized

    international standards for radio interference and corona discharge. The conductor must be suitable for the environmental conditions and

    conform to constructional methods understood in the country involved (such as IEC61089).

    56

  • Connector Selection Key elements: ACSR, AAAC, ACAR and AACSR Aerial bundled conductor (ABC) and BLX Conductor breaking strengths Bi-metal connectors

    57

  • ACSR, AAAC, ACAR and AACSR For 36 kV transmission and above both aluminum conductor steel

    reinforced (ACSR) and all aluminum alloy conductor (AAAC) are used. Aluminum conductor alloy reinforced (ACAR) and all aluminum alloy

    conductors steel reinforced (AACSR) are less common than AAAC and all such conductors may be more expensive than ACSR.

    ACSR has been widely used because of its mechanical strength, the widespread manufacturing capacity and cost effectiveness.

    Copper (BS 7884 applies) has a very high corrosion resistance and is able to withstand desert conditions under sand blasting but it is expensive.

    At larger conductor sizes, the AAAC option becomes more attractive. AAAC can achieve significant strength/weight ratios and for some constructions gives smaller sag and/or lower tower heights.

    AAAC is slightly easier to joint than ACSR.

    58

  • ACSR

    59

    Aluminum-based conductors have been referred to by their nominal aluminums area. Thus, ACSR with 54 Al strands surrounding seven steel strands, all strands of diameter d = 3.18 mm, was designated 54/7/3.18; aluminum area of 428.9 mm2, steel area of 55.6 mm2 and described as having a nominal aluminum area of 400 mm2.

    54/7/3.18 ASCR

  • Aerial Bundled Conductor (ABC) and BLX At low voltage levels aerial bundled conductor (ABC) is now

    becoming rapidly more popular because of improved reliability and the low installation and maintenance costs compared to conventional open wire pole distribution.

    For the 1014 kV distribution levels the use of ABC is more problematic due to the requirement of employing underground cable joining techniques at high level (especially difficult in maintenance situations).

    For medium voltage distribution lines, (10 kV to 25 kV) BLX conductors are now preferred in many countries.

    60

  • Aerial Bundled Conductor (ABC) and BLX There are two distinct ABC systems in use: 1. One system uses a self-supporting bundle of insulated

    conductors where all conductors are laid up helically and where tension is taken on all conductors which are of hard-drawn aluminum.

    2. An alternative system is where all conductors are insulated and the hard-drawn aluminum phase conductors are laid up around an aluminum alloy neutral which has greater tensile strength and acts as a catenary wire to support the whole bundle. The insulation material may be polyvinylchloride (PVC), linear polyethylene (PE) or cross-linked polyethylene (XLPE).

    61

  • Conductor Breaking Strengths for ACSR

    62

    Calculation standard ACSR conductor 50/8 breaking strength (kN) ACSR conductor 380/50 Breaking strength (kN)

    BS215, Pt. 2. 1970 16.81 120.96

    ASTM B2 32-74(Class A) 17.45 121.62

    ASTM B232-74 (Class B) 16.91 119.74

    ASTM B232-74 (Class C) 16.67 114.97

    NFC 34 120 1968 (R) - 144.21

    NFC 34 120 1968 (N) - 118.75

    DIN 48 204 (declared) 17.09 123.14

    DIN 48204 (theoretical area) 16.83 120.80

    DIN 48204 (calculated area) - 120.72

    CSA C49 175 17.19 123.40

    IEC 61089 16.87 120.71

    EN 50182 16.81 121.30

  • Bi-metal Connectors

    63

    Where an aluminum conductor is terminated on a copper terminal of an isolator a special copper/aluminum joint is necessary to prevent the formation of a corrosion cell. A termination of this type usually comprises of an aluminum sleeve compressed onto a copper stalk with an insulating disc separating the two surfaces which are exposed to the atmosphere

    Copper pin

    Anti corrosion varnish

    Aluminum Ferrule

    Bi-metal connectors

  • Calculated Electrical Rating 1. Heat balance equation 2. Power carrying capacity

    64

  • Heat Balance Equation

    65

    2 20 1 C R SI R t H H H

    0.448387CH V d

    4 4237 237R CH E s d t t S SH S d

    I : current rating, amps R20 : resistance of conductor at 20C : temperature coefficient of resistance per C (for ACSR at 20C, =0.00403) t : ambient temperature, C : temperature rise, C (t1 , initial temperature and, t2 , final temperature)

  • Heat Balance Equation S : solar absorption coefficient depends upon outward condition of the

    conductor and varies between 0.6 for new bright and shiny conductor to 0.9 for black conditions or old conductor.

    S : intensity of solar radiation, watts/m2

    d : conductor diameter, mm V : wind velocity normal to conductor, m/s. For design purposes 0.5 or 0.6

    m/s wind speeds are often taken.

    EC : emissivity of conductor differs with conductor surface brightness. Typical values are 0.3 for new bright and 0.9 for black aluminium, ACSR or AAAC conductor. Average value 0.6, say.

    66

  • Power Carrying Capacity

    67

    100

    200

    300

    400

    500

    600

    100000 200000 300000

    Line

    vol

    tage

    (kV

    )

    Power transfer (MW.km)

    Line voltages 66 kV-600 kV

    10

    70

    20

    30

    40

    50

    60

    100 200 300 400 500 600

    Power transfer (MW.km)Li

    ne v

    olta

    ge (k

    V)

    Line voltages 11 kV-66 kV

    Economic power transfer capacity trends for different line voltages based on power transfer are proportional to the square of the line voltage.

    Economical power transfer

  • Power Carrying Capacity

    68

    Line voltage

    (kV)

    Conductor equipment

    configuration spacing (mm)

    ASCR conductor

    code

    AAC conductor

    code MW capacity

    11 1400

    Sparrow Raven Linnet

    Iris Poppy Tulip

    8 (km) 0.95 1.4 3.00

    160 (km) 0.490 0.7 1.5

    24 (km) 0.33 0.47 1.00

    32 (km) 0.25 0.35 0.75

    33 1500

    Quail Penguin Linnet Hen

    Aster Oxlip Tulip Cosmos

    16 (km) 5.00 6.70 8.35 11.50

    32 (km) 2.50 3.35 4.18 5.75

    48 (km) 1.70 2.20 2.80 3.80

    64 (km) 1.25 1.70 2.10 2.90

    66 3000

    Quail Linnet Hen

    Aster Tulip Cosmos

    32 (km) 12.50 16.00 18.40

    64 (km) 6.25 8.00 9.18

    96 (km) 4.18 5.32 6.12

    128 (km) 3.14 3.99 4.59

  • Earth Wire Spacing and Clearances Electrical clearances Earth wires Distribution voltage level clearances Transmission voltage level clearances

    69

  • Earth Wire Spacing and Clearances According to EN 50314-1, there are five types if requirements to be considered for determining the minimum of electrical clearance distance: 1. Prevention of disruptive discharges between phase conductors

    and earth during fast and slow front over voltages. This clearance can be considered either internal clearance between earthed tower components or external clearance between conductor and an obstacle (Del).

    2. Prevention of disruptive discharges between phase conductors during fast and slow front over voltages. The minimum clearance is an internal nature in this case (Dpp).

    70

  • Earth Wire Spacing and Clearances 3. Prevention of disruptive discharges between a live conductor

    and objects with earth positional at power frequency (Dpf_pe). 4. Prevention of disruptive discharges between a live conductors

    at power frequency (Dpf_pp). 5. Setting of minimum air clearance distances to obstacles or

    cross objects in order to prevent discharges occur inside the overhead line.

    71

  • Electrical Clearances Clearances Del and Dpp corresponding to fast-front withstand voltages, of conductor-to-obstacle and conductor-to-conductor air gaps in altitudes up to 1000m above sea level, EN 50341-1.

    72

    Lightning surge withstand voltage (kV)

    Del_ff (m) Dpp_ff (m)

    400 0.77 .85

    600 1.14 1.26

    800 1.50 1.68

    1000 1.88 2.08

    1200 2.23 2.50

    1400 2.61 2.92

    1600 2.98 3.33

    1800 3.35 3.75

    2000 3.72 4.17

    2050 3.82 4.27

    2100 3.91 4.38

    2150 4.00 4.48

  • Electrical Clearances Clearance Del and Dpp corresponding to slow withstand voltages, of conductor-to-obstacle and conductor-to-conductor air gaps in altitudes up to 1000m above sea level, EN 50341-1.

    73

    Lightning surge withstand voltage (kV)

    Del_sf (m)

    Dpp_sf (m)

    400 0.88 1.02

    600 1.44 1.67

    800 2.07 2.45

    1000 2.84 3.41

    1200 3.71 4.57

    1400 4.77 5.97

    1600 6.02 7.66

    1800 7.50 9.70

  • Electrical Clearances Minimum clearances in air dependent on the highest voltage of equipment, EN 50341-1

    74

    Highest voltage of equipment (kV)

    Dpf-pe (m) Dpf-pp (m)

    52 0.11 0.17

    72.5 0.15 0.23

    82.5 0.16 0.26

    100 0.19 0.30

    123 0.23 0.37

    145 0.27 0.42

    170 0.31 0.49

    245 0.43 0.69

    300 0.51 0.83

    420 0.70 1.17

    525 0.86 1.47

    765 1.28 2.30

  • Electrical Clearances Empirical data for minimum clearance distances Del and Dpp, EN 50341-1.

    75

    Highest voltage of equipment (kV) Del (m) Dpp (m)

    52 0.60 0.70

    72.5 0.70 0.80

    82.5 0.75 0.85

    100 0.90 1.05

    123 1.00 1.15

    145 1.20 1.40

    170 1.30 1.50

    245 1.70 2.00

    300 2.10 2.40

    420 2.80 3.20

    525 3.50 4.00

    765 4.90 5.60

  • A Typical Overhead Line Clearances (based on maximum conductor temperature or the load EN 50341)

    Clearance (m) from line with highest system voltage of: Clearance consideration 52 kV 145 kV 245 kV

    To ground in unobstructed countryside 5.6 6.2 6.7

    To rockface or steep slope 3.1 3.2 3.7 To trees which cannot be

    climbed 0.6 1.2 1.7

    To trees which can be climbed 2.1 2.7 3.2

    To buildings with fire-resistant roofs and

    roofs with slope 15 to horizontal

    3.1 3.2 3.7

    To buildings with fire-resistant roofs and roofs with slope

  • Earth Wires Where there is a risk of a direct lightning strike to the phase

    conductors, transmission lines are provided with overhead earth (or ground) wires to shield them and also to provide a low impedance earth return.

    In the UK the original 132 kV overhead lines were designed with a 45 angle of protection and gave satisfactory cover.

    This angle was applied 400 kV overhead with the angle of 30 in order to reduce the number of strikes in UK.

    77

  • Distribution and Transmission Voltage Level Clearances Distribution voltage level clearance: for open wire

    construction at distribution voltage levels (380 V24 kV) the earth or neutral wire is normally placed at the bottom (nearest the ground) of the conductor set so as to minimize the danger caused by poles, ladders, etc. touching the wires from underneath.

    Transmission voltage level clearance: There are no universally agreed clearances as they depend upon insulation level, pollution, span, type of overhead line construction, etc.

    78

  • Overhead Line Fitting Definition: overhead line fittings serve for the mechanical

    attachment, for electric connection and the protection of conductors and insulators.

    Fittings for conductors serve to terminate, suspend or join the conductors and are directly connected to the conductors. Fittings for conductor include suspension and dead-end clamps, connectors, branch-off clamps, vibration protection fittings and bundle spacers.

    Fittings for insulator sets and other attachments serve to connect the tension or suspension components with the attachment points at the supports such as: Yoke plates, index-yoke plate corona protection fittings and grading rings.

    79

  • Fittings for Conductors 1. Conductor attachment at suspension insulator sets 2. Conductor attachments at dead-end terminations 3. Turn buckles 4. Connectors 5. Spacers for bundle conductors 6. Vibration dampers for single conductors 7. Sag adjusters 8. Miscellaneous fittings

    80

  • Conductor Attachment and Suspension Insulator Sets Articulated suspension clam: the most frequently used type of

    suspension clamp. Armor rod suspension (ARS) Wedge-type dead-end clamp Armor grip suspension Suspended dead end arrangement: to prevent static bending

    stress over long spans such as river crossing. Saddle-type clamp: which its suspension body can reach up to

    two meters. Release suspension clams: are adopted occasionally to protect

    not sufficiently proof suspension towers. Sliding suspension clamps: enable the conductor to slide

    through the clamp above a stipulated difference in conductor tensile forces between adjacent spans.

    81

  • Articulated Suspension Clam

    82

    Suspension strap

    Clamp cover

    Clamp body

  • Armor Rod Suspension (ARS)

    Suspension strap

    Clamp cover

    Clamp body Armor rods

    83

  • Armor Grip Suspension (AGS)

    84

    Armor rodsRubber elastic lining

    Suspension strap

    Clamp body

  • Suspended Dead End Arrangement

    85

    Dead end clampTriangular yoke plate Turn bcuket

  • Saddle-type Clamp

    86 Clamp body

    Armor rods Clamp cover

    Suspension insulator set using saddle-type clamp cover

  • Conductor Attachment and Suspension Insulator Sets Conductors can be terminated by dead-end clamps or by performed dead-ends. Wedge-type clamps: simple to install and can correct line sags,

    adopted for high and medium voltage lines. Compression dead-end clamps: suitable for all standard types

    of conductors in market. They are designed to achieve ultimate terminating forces up to rated tensile strength (RTS) of conductors, adopted for high and medium voltage lines.

    Performed dead-end rods: suitable for terminating metal-reinforced cables with optical fibers (OPGW) and other aerial cables. They can be installed bare hand.

    87

  • Wedge-type Clamps

    Clamp body

    Clamp wedge

    Terminal strap

    88

  • Compression Dead-end Clamps Clamp body with

    sleeve for steel core

    Lug for jumper loop

    Outer sleeve

    89

  • Turn Buckles and Connectors Turn buckles: are arranged in dead-end insulator sets to

    compensate tolerances in lengths of elements in parallel or sub-conductors in bundles.

    Connectors: including tension proof and non-tension proof are fitting jointing one or more phase conductors or earth-wires to each other or producing a branch-off. Performed splices: are used for medium-voltage. Protective patch rods or repair patch rods are frequently

    adopted to restore the electric and mechanical function after damage or strand failures at conductors, earth wires or aerial cables.

    90

  • Spacers for Bundle Conductors Spacers keep the sub-conductors within a span and in jumper loops at designed spacing to avoid damage caused by clashing, twisting or entwining. Rigid spacers: keep the sub-conductors at a constant distance

    at the location of installation. Flexible spacers: permit small relative displacements of the

    sub-conductors at the location of installation. Spacer dampers: reduce the vibration level by energy

    dissipation in rubber-elastic elements. Phase spacers: are adopted in spans of lines where

    conductor galloping occurs frequently due to topographical or climate peculiarities.

    91

  • Rigid Spacers

    Bar

    Clamping jaw

    92

  • Phase Spacer

    Clamping arrangement

    Central pivot

    Suspensionbracket Composite insulators

    Spacer sleeves

    Grading rings

    93

    Phase spacer for quadruple bundles

  • Vibration Dampers and Spacer Dampers for Bundle Conductors Vibration dampers: offer effective protection against vortex-

    induced vibrations. The most popular is Stockbridge-type. Spacer dampers for bundle conductors: suppress vortex-

    induced conductor vibrations

    94

  • Fittings for Insulator Sets Fittings for insulator set compromise: 1. Fittings to attach the insulator sets to the support. 2. Fittings to join the insulator of one string , e. g. ball and socket

    or clevis and tongue connections, yoke plates for multi-string insulator sets.

    3. Fittings for grading of electrical fields and arcing protection, e. g. coordinating spark gaps, arcing horns and rings, as well as grading fittings.

    4. Ball and socket connections are used for connecting long rod and cap-and-pin insulators, clevis and tongue connections for long rod and composite insulators. The dimensions of ball and socket connections are standardized by IEC 60120, for clevis and tongue connections by IEC 60471.

    5. Arcing protection fittings should safe-guard insulators sensitive to abrupt temperature changes which may occur due to power arcs.

    95

  • Sag Adjusters and Miscellaneous Fittings Sag adjusters: these consist of pivoted clamping plates with

    adjustment holes to allow the sag of the conductor to be regulated after the initial erection in steps of, say, 10 mm over a 300 mm range.

    Miscellaneous fittings: These include:

    Tower or pole anti-climbing guards Climbing steps Danger plates Tower or pole number plates Phase plates Line circuit identifications Aircraft warning spheres

    96

  • Representation of Lines The way in which lines and cables are represented with an

    equivalent circuit depends on the following: Length Type Accuracy needed

    There are three broad categories of length as follows: Short (up to 80 km or 50 miles). Medium (up to 240 km or 150 miles). Long (above 240 km or 150 miles).

    97

  • Representation of Lines The actual line or cable is a distributed constant circuit and it

    has: Resistance Inductance Capacitance Leakage resistance

    These are all distributed evenly along its length. Except the long lines, the total resistance, inductance,

    capacitance and leakage resistance of the line are concentrated to give a lumped constant circuit.

    The various distances quoted are used as a rough guide only.

    98

  • Voltage Drop Along a Line The various loads (customers) connected across the line draw

    current causing the voltage to drop. The farther one gets away from the substation, the higher the

    voltage drop. If the voltage at the substation is set at nominal value, the

    customers at the end of the line will not have enough voltage under heavy load.

    If the voltage is set so that the end customers have nominal value, the voltage near the substation is too high for light loading conditions.

    A compromise must be reached or maybe other methods can be employed for voltage regulation under various loading conditions.

    99

  • Substation

    1st customer 2nd customer last customer

    Other laterals

    Distribution Circuit

    100

  • Substation

    1st customer2nd customer last customer

    V

    VBase

    Voltage Drop Along a Line with Heavy Load

    101

  • Voltage Drop Along a Line with Light Load

    102

    Substation

    1st customer 2nd customer last customer

    V

    VBase

  • Reactance The magnetic flux produced by the AC current flowing in a

    conductor produces a series inductive reactance due to: Self inductance (which causes skin effect) along the conductor. Mutual inductance between conductors.

    The reactance does not dissipate real power, but results in a voltage drop along the line and also draws reactive volt-amperes.

    Any reactive power on the line must be supplied by the generator over and above to the reactive power the load will consume.

    103

  • Reactance Basic formula, geometric mean radius and geometric mean

    distance Three phase formula Positive and negative sequence reactance Zero sequence reactance

    104

  • Basic Formula, Geometric Mean Radius and Geometric Mean Distance

    105

    0.2 0.25 log / [ / ]eL d r mH km L : inductance d : separation between conductor axes (mm) r : radius of conductor (mm)

    d

    r

  • Three-phase Formula for Transmission Lines Inductance (L)

    106

    0.2 log / [ / ]eL GMD GMR K mH km

    K : correction factor GMD : geometric mean distance between the A, B and C phases (mm) GMR : geometric mean radius of conductors (mm)

    3 AB BC CAGMD d d d

    rdAB

    dAC dBC

    A B

    C

  • Three-phase Formula for Transmission Lines Inductance (L)

    107

    All aluminum or all copper conductor ACSR

    Number of strands GMR Number of Al strands

    GMR

    7 0.726 r 6 0.768 r

    19 0.758 r 12 0.859 r

    37 0.768 r 26 0.809 r

    61 0.772 r 30 0.826 r

    91 0.774 r 54 0.810 r

    127 0.776 r

    169 0.779 r

    Solid 0.779 r

    GMR values as function of conductor radius, r

  • Positive and Negative Sequence Reactance The positive and negative sequence inductive reactances (X1 , X2) of a three phase overhead line are equal and for a frequency, f Hz, become:

    108

    31 0.4 10 log /eX f GMD GMR K

  • Zero Sequence Reactance Zero sequence reactance (X0) is complicated to calculate. The value depends upon the position and materials used for the earth wires and the log of the square root of the ground resistivity.

    109

    Earth wire Overhead line X0/X1 - Single circuit 3.5

    - Double circuit 5.5

    Galvanized steel Single circuit 3.5

    Galvanized steel Double circuit 5.0

    Non-magnetic Single circuit 2.0

    Non-magnetic Double circuit 3.0

    Typical values for the ratio of zero-to-positive sequence reactance for double and single circuit overhead lines

  • Capacitance Conductors separated by a given distance have capacitance.

    The capacitance of a transmission line depends upon: Conductor size Spacing Height above the ground Voltage

    Transmission line capacitance must be charged initially before transfer of real power can occur.

    The expression for line-to-neutral capacitance, C, is:

    110

    1 [ / ]

    18log /eC F kmGMD r

  • Resistance The series resistance of a conductor depends on:

    Resistivity of the conductor material Length Temperature Skin effect

    Conductor resistance varies with temperature in a linear fashion.

    Losses occur because of the resistance of the lines, and these losses are kept minimum by using high voltages for transmission of bulk power.

    111

  • Power Factor Correction The term correction or compensation is used to describe the

    intentional insertion of reactive power devices, either capacitive or inductive, to achieve one or more desired effects in an electric power system.

    These effects include improved voltage profiles, enhanced stability and increased transmission capacity.

    The correcting devices are either in series or in shunt (parallel) with the load(s) at one or more points in the power circuit.

    112

  • Why do we bother? The motivations behind power factor correction equipment are: Increase the efficiency of the source i.e. the AC mains in two

    distinct ways as follows: Lower the source losses (harmonics are associated with undesired

    components and losses). Increase the power that can be taken out from a given source.

    Reduce the line harmonics and associated Electromagnetic Interference) (EMI) induced in the source (AC mains) by the load.

    Market expectations for modern equipment. The aim is to shape the line current so that it will be in phase

    with the input sinusoidal voltage.

    113

  • Shunt Capacitors for Voltage Regulation Capacitors have been effectively used to correct the power

    factor since most of the loads are inductive (lagging). This is achieved by supplying Var. The capacitors are installed as close to the loads as possible. There are two ways for the capacitances to become available

    for such function as follows: Fixed value: to cater for both light and heavy load conditions. Variable or switched capacitor banks in the case that the

    load variation is so large and one capacitor value will not be good enough to serve all cases.

    114

  • Shunt Capacitors for Voltage Regulation Switched capacitor banks are expensive mainly because they

    need sensing hardware to operate and appropriate control systems.

    All capacitor banks require protection with a fuse or circuit breaker.

    They can be connected either as delta or star. The underground start connection is preferred because if a

    capacitor is shorted in one leg, the other two will limit the fault current.

    Shunt capacitors are usually installed in radial feeders.

    115

  • Shunt Capacitors for Voltage Regulation

    116

    Without shunt capacitor

    Applying shunt capacitor

    Distance from the source (generator)

    Term

    inal

    vol

    tage

  • Capacitor Banks

    117

    Circuit breaker

    CT for protective relays

    PT PT PT

    Protevtive relay

    Fuses

  • Outdoor Regulator Bank

    118

  • Disconnect Switches for the Outdoor Regulator Bank for Maintenance

    119

  • Shunt Reactors Shunt reactors are usually installed to remedy utility company power-generation and transmission issues including: Overvoltages that occur during low load periods at utility

    substations served by long lines as a result of the inherent capacitance of the line.

    Leading power factors at generating plants resulting in lower transient and steady-state stability limits.

    Open-circuit line charging kVA requirements in extra-high-voltage systems that exceed the available generation capabilities.

    120

  • Shunt Reactors

    121

    Without shunt reactor

    Applying shunt reactor

    Distance from the source (generator)

    No-

    load

    term

    inal

    vo

    ltage

  • Skin Effect The skin effect phenomena refer to the fact that as the

    frequency of the AC current increases, the flow of current shifts towards the surface of the conductor.

    Since the AC current reverses direction in a periodic way, each reversal results in the magnetic flux produced by the current also reversing.

    The magnetic flux density is highest in the centre of the conductor, causing the inductive reactance of the conductor to also be highest in the centre.

    The higher inductive reactance in the centre forces the current towards the surface.

    The skin effect at a fixed frequency is proportional to the diameter of the conductor.

    The skin effect causes the AC resistance to be 10 to 20 per cent of the DC one.

    122

  • Representation of Transmission and Distribution Systems Modern electricity supply systems are three-phase systems. The design of distribution networks is such so that normal

    operation is reasonably close to balanced three-phase systems, i.e. one phase is usually sufficient to study and understand the systems full operation.

    Equal loading on all three phases is ensured by connecting as far as possible equal domestic loads to each phase of the low voltage distribution feeders.

    Industrial loads are most of the time three-phase ones.

    123

  • Reasons for Interconnection There are a number of reasons for interconnection as follows: The base load is satisfied by high efficiency generation plants

    that feed into the system and not into a particular load regardless of geographical location.

    To meet sudden increases, spinning reserve is available from generators running at normal speed and ready to supply power instantaneously.

    Interconnection allows for alternative paths to exist between generators and bulk supply point. This offers security of supply should a given path fails.

    124

  • Transmission It implies the bulk transfer of power from generators to load

    centers which is then distributed. The transmission network operates at high voltage. Generators usually produce voltages at around 11kV -25kV. Transformers increase this to the main transmission voltage

    levels. Large amounts of power is transmitted at voltage levels of 400

    kV and 275 kV in the UK. Slightly different in other countries. This network in many cases is called supergrid.

    125

  • MLine, cable or busbar (three-phase)

    Rotating machine-general

    Synchronous machine

    Two winding transformer

    Three winding transformer

    Current transformer

    BreakerThree-phase star connected with the star point solidly connected to earth or ground electrode

    Three-phase star connected

    Load

    Symbols of Power System Components

    126

  • Large high-efficiency station

    Substation (grid supply point)

    Generator transformers

    275 kV or 400 kV (345.5 0r 765 kV in U.S.A.) (busbars sectionalized)

    Load

    Substation

    Loads

    Load

    Load

    To the restof

    system

    Embedded generation(local generator)

    Typical Power System

    127

  • Large generators ( gas, coal, nuclear, hydro)

    Tie line to other systems

    CHP generators or small local independents

    Small embedded generators, e.g. wind,

    landfill gas

    132 kV(230/115 kV)

    400/275 kV(765 kV, 500/345 kV)

    Distribution

    Loads

    Constituent Networks of a Supply System

    128

  • Transmission Line Repair The time to repair a failed transmission line typically varies from

    2 to 10 days, depending upon: Type of line

    Overhead Underground cable in conduit Pipe-type of cable

    The time required to replace a failed bulk-power system transformer is typically 30 days.

    As a result of the previous points, emergency ratings for a transmission line or transformer may include, 2-hours emergency, 2-to-10 days emergency, and in some cases 30 days emergency ratings.

    129

  • Overhead Transmission Line Ratings The ratings of an overhead transmission line is based on the

    maximum temperature of the conductors. Conductor temperature affects the following:

    The conductor sag between towers The loss of conductor tensile strength due to annealing.

    If the temperature is too high the following may happen: Proscribed conductor-to-ground clearance may not be met. The elastic limit of the conductor may be exceeded such that it

    cannot shrink to its original length when cooled.

    130

  • Overhead Transmission Line Ratings Conductor temperature depends upon:

    Current magnitude and its time duration. Ambient temperature. Wind velocity. Solar radiation. Conductor surface conditions.

    There are standards that allow use of standards assumptions on ambient temperature, wind velocity, etc. and these are calculated conservatively (IEEE Std. 738-85, 1985).

    131

  • Overhead Transmission Line Ratings It is common practise to have summer and winter ratings,

    based on seasonal ambient temperature differences. In locations that higher winds prevail, such as coastal areas,

    larger than normal line ratings are used. Emergency line ratings vary between 110% to 120% of

    normal ratings. In many cases real time monitoring of actual conductor

    temperatures along a transmission line is used for on-line dynamic transmission line ratings.

    132

  • Stability Definitions System stability is the ability of all synchronous generators in

    operation to stay in synchronism with each other while moving from one operating condition to another.

    Steady-state stability refers to small changes in operating conditions, such as normal load changes.

    Transient stability refers to larger, abrupt changes, such as the loss of the largest generator or a short circuit followed by circuit breakers opening, where synchronism or loss of synchronism occurs within a few seconds.

    Dynamic stability refers to longer time periods, from minutes up to a half-hour following a large, abrupt change, where steam generators (boilers), automatic generation control and system operator actions affect stability.

    133

  • Planning Process and Stability Steady state stability is also evaluated during the planning

    process with the use of power-flow programs and by the systems ability to meet equipment loading criteria and transmission voltage criteria under steady state conditions.

    Transient stability is evaluated via stability programs by simulating the systems transient response for various types of disturbances, including short circuits and other abrupt network changes.

    134

  • Typical Disturbances and Stability Studies Scenario: All transmission lines in service, and a permanent

    three-phase fault (short-circuit) occurs on: Any transmission line Both transmission lines on any double circuit tower At any bus The fault is successfully cleared by primary relay

    Any one transmission line out of service, a permanent three-phase fault occurs on any other transmission line. The fault is successfully cleared by primary relaying.

    With all transmission lines in service, a permanent three-phase fault occurs on any transmission line; back up relaying clears the fault after a time delay due to a circuit breaker failure.

    135

  • Value-based Transmission Planning The method assigns a monetary value to various levels of

    reliability in order to balance reliability and cost. For each outage, the amount of money of unserved energy is

    determined and its value is calculated based on the type of customers and other information.

    If the cost of the transmission project required to eliminate the outage exceeds the value of service, then that project is given lower priority.

    This means that reliability is quantified, and benefit-to-cost ratios are used to compare and prioritise planning options.

    136

  • Cables Cables are use for low voltage, medium voltage and high

    voltage power systems. Besides there are many applications of using control,

    communication cable and fiber optic cables. International Electrotechnical Commission (IEC) standards for

    application and testing of cables are IEC 60055, 60096, 60141, 60183, 60227, 60228, 60229, 60230, 60287, 60331, 60332, 60364,60502, 60702, 60724, 60754, 60811, 60840, 60853, 60859, 60885, 61034, 61042, 61084, 61443 and 62067.

    137

  • Classification of Cables

    138

    Voltage level Usage Voltage range Insulation Low voltage (LV) Telephone 50 V PVC or PE

    Control 600/1000 V PVC

    Solid dielectric 600/1000 V PVC, XLPE, EPR

    MI or MIND 600/1000 V Paper

    Fire resistant 600 & 1000 V Mineral, Silicone Rubber

    Fire retardant 600/1000 V LSF, LSOH

    Medium voltage (MV) Solid dielectric 3 kV to 7.2 kV PVC, PE, XLPE, EPR MI or MIND 3 kV to 7.2 kV Paper

    XLPE : Cross-linked polyethylene PVC : Polyvinylchloride PE : Polyethylene EPR : Ethylene propylene rubber LSF : Low smoke and fume LSOH : Low smoke zero halogen MI : Mass impregnated MIND : Mass impregnated non-draining PPL : Polypropylene paper laminate

  • Classification of Cables

    139

    Voltage level Usage Voltage range Insulation High voltage (HV) Solid dielectric 10 kV to 150 kV XLPE, EPR

    MIND 10 kV to 36 kV Paper

    Oil- filled, gas pressure 80 kV to 150 kV Paper

    Gas insulated ducts 10 kV to 150 kV SF6

    Very high voltage (VHV) Solid dielectric

    150 kV to 300 kV XLPE

    Oil-filled 150 kV to 300 kV Paper, PPL

    Gas insulated ducts 150 kV to 300 kV SF6

    Extra high voltage (EHV) Solid dielectric Above 300 kV XLPE

    Oil-filled Above 300 kV Paper, PPL

    Gas insulated ducts Above 300 kV SF6

  • Insulation Synthetic insulation for wire and cable can be classified as

    follows: Thermosetting Thermoplastic

    The mixture of materials within each of these categories vary so much so that unlimited number of insulations are available to the power engineer.

    Most of insulation is composed of compounds made of synthetic rubber polymers (thermosetting) and from synthetic materials (thermoplastics).

    These synthetic materials are combined to prove specific physical and electrical properties.

    140

  • Thermosetting Insulation These materials are characterised by their ability to:

    be stretched compressed Deformed

    within reasonable limits under mechanical strain and then return to their original shape when the applied stress is removed.

    141

  • Thermoplastic Insulation Thermoplastic insulation materials have excellent electrical

    characteristics. They are relatively inexpensive. They are popular since they allow thinner insulation thickness to

    be used to obtain good electrical properties, especially at higher voltage levels.

    142

  • Cable Armouring In order to protect cables from mechanical damages such as

    pick or spade blows, ground subsidence or excessive vibrations cable armouring is employed.

    For three-core cables this consists of one or two layers of galvanized steel tapes, galvanized steel wire braid or galvanized steel wires helically wound over the cable.

    For single core cables aluminium is used instead of steel wire in order to avoid losses.

    143

  • Underground Cables It is quite difficult and in most cases impossible to obtain right

    of way in urban areas for overhead lines. Therefore, use of underground cables is usually confined to the

    short lengths required in heavily populated areas. The cost of underground cable is higher than the overhead

    cable. Technologies such as cryogenic cable and other types of cable

    using forced cooling techniques are used. In this case the cable uses three separate cables, each having a hollow centre for cooling purposes.

    The conductor is made of stranded aluminium. The conductors are wrapped with an insulating material that contains liquid nitrogen.

    144

  • Cryogenic Underground Cable

    145

    Outer covering

    Insulation containing liquid

    nitrogen

    Stranded aluminium conductors

    Hollow core

  • High-pressure Oil-filled Pipe-type High-voltage Cable

    146

    Steel pipe (filled with insulting oil)

    Skid wires

    Paper or oil insulation

    Screen

    Metallic tapes

    Conductor (stranded copper)

  • Submarine Cables Submarine cables require additional tensile strength to permit

    laying on or under the sea or river bed under high tension conditions.

    Paper, PVC or XLPE insulation is used together with additional protection measures against water ingress and mechanical damage and with special sheath compositions to repel worm attack.

    Such cables are manufactured in the longest possible lengths in order to minimize the number of underwater cable joints.

    When preparing the design for submarine cables an accurate knowledge of the prevailing currents and tidal variations is essential to assist in deciding the best cable route and most favourable times for the cable laying work.

    147

  • Summary Key points Competence required

    Overhead line towers Comparing towers and poles applications and structures

    Overhead line fittings Ability to choose suitable fittings

    Tower structure Differentiation between tower structures according to their applications

    Design span Calculating clearances and spans according to standards

    Transmission line model Describing transmission line model, overvoltage, voltage drop, reasons for connecting capacitors

    and inductors to transmission lines

    Cables Comparing different types of cables and ability to

    use standards to choose cables for specific applications

    148