Knowledge is Power Belimo Energy Valve™ CHW DELTA T MITIGATION STUDY 1 2014 AHR Expo Innovation Award” Winner in the Category of Building Automation The Belimo Energy Valve™ won the “Technical Innovation of the Year – Products” at the BCIA Building Controls Industry Association Awards. BOB RYBKA BELIMO AMERICAS 908 397 5960
43

Knowledge is Power Belimo Energy Valve™ CHW DELTA T · PDF file · 2016-09-28Knowledge is Power Belimo Energy Valve ... • Recommend implementing chilled wate r delta T...

Mar 26, 2018

Download

Documents

phamduong
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: Knowledge is Power Belimo Energy Valve™ CHW DELTA T · PDF file · 2016-09-28Knowledge is Power Belimo Energy Valve ... • Recommend implementing chilled wate r delta T improvement

Knowledge is Power Belimo Energy Valve™CHW DELTA T MITIGATION STUDY

1

2014 AHR Expo Innovation Award” Winner in the Category of Building Automation

The Belimo Energy Valve™ won the “Technical Innovation of the Year – Products” at the BCIA Building Controls Industry Association Awards.

BOB RYBKABELIMO AMERICAS908 397 5960

Page 2: Knowledge is Power Belimo Energy Valve™ CHW DELTA T · PDF file · 2016-09-28Knowledge is Power Belimo Energy Valve ... • Recommend implementing chilled wate r delta T improvement

Delta T Mitigation StrategiesEnergy Valve Site Study

• Dynamic Balancing Control Valve Technology• Chilled Water delta T Study• Chilled Water System Design• AHU Coil• Beta Site Study• Correcting Low delta T• Data Analysis and Optimization• Additional Applications

2

Page 3: Knowledge is Power Belimo Energy Valve™ CHW DELTA T · PDF file · 2016-09-28Knowledge is Power Belimo Energy Valve ... • Recommend implementing chilled wate r delta T improvement

Water exits valve

Pressure is P2 (low)

Water enters valve

Pressure is P1 (high)

Pressure Independent Control Valve

Water passes through regulator, disc, and ball

Pressure Drops

Ports sense pressure drop and transfer it below regulator

Low pressure pulls regulator down, against the spring force

Operational theory

Page 4: Knowledge is Power Belimo Energy Valve™ CHW DELTA T · PDF file · 2016-09-28Knowledge is Power Belimo Energy Valve ... • Recommend implementing chilled wate r delta T improvement

ELECTRONIC PRESSURE INDEPENDENT VALVE1/2’’– 6”, 1.65 thru 713 GPM

Actuator

Valve

Flow Sensor

Page 5: Knowledge is Power Belimo Energy Valve™ CHW DELTA T · PDF file · 2016-09-28Knowledge is Power Belimo Energy Valve ... • Recommend implementing chilled wate r delta T improvement

ELECTRONIC PRESSURE INDEPENDENT VALVE WITH WATER DELTA T MANAGMENT

½’’ – 2’’ NPT - 1.6 thru 76 GPM2.5” – 6” FLANGED - 90 thru 713 GPM

5

Page 6: Knowledge is Power Belimo Energy Valve™ CHW DELTA T · PDF file · 2016-09-28Knowledge is Power Belimo Energy Valve ... • Recommend implementing chilled wate r delta T improvement

6

Library Case Study

• Case Study Issues• Coil delta T reported as 6 Degree F• Over pumping• Low delta T Syndrome at Chiller Plant

6 AHU units, 153,000 sq-ft

Page 7: Knowledge is Power Belimo Energy Valve™ CHW DELTA T · PDF file · 2016-09-28Knowledge is Power Belimo Energy Valve ... • Recommend implementing chilled wate r delta T improvement

Chilled Water SystemPeak Load 26,000 Tons

• UNIVERSITY CAMPUS STUDY

7

* From 2008 Chilled Water Delta T Study

Page 8: Knowledge is Power Belimo Energy Valve™ CHW DELTA T · PDF file · 2016-09-28Knowledge is Power Belimo Energy Valve ... • Recommend implementing chilled wate r delta T improvement

8

Savings by Eliminating Causes of Low Delta T (30,000 Ton Plant)

• Recommend implementing chilled water delta T improvement projects across the campus.

Component Annual Energy Savings

Annual Cost Savings

Chiller Steam 10,887 Mlbs $181,000.00

Chiller Electric 2,576,000 kWh $412,000.00

CHW Pump Electric 2,334,000 kWh $373,000.00

CW Pump Electric 2,417,000 kWh $387,000.00

CT Fan Electric 740,000 kWh $118,000.00

TOTAL SAVINGS $1,471,000.00

25% of Total

Page 9: Knowledge is Power Belimo Energy Valve™ CHW DELTA T · PDF file · 2016-09-28Knowledge is Power Belimo Energy Valve ... • Recommend implementing chilled wate r delta T improvement

Design

• Flow and delta T are inversely proportional; for a given load, when delta T drops flow has to increases.

9

T24TonsGPM

T1224TonsGPM 800

2TonsGPM 800

Tons2GPM 800

400Tons

Page 10: Knowledge is Power Belimo Energy Valve™ CHW DELTA T · PDF file · 2016-09-28Knowledge is Power Belimo Energy Valve ... • Recommend implementing chilled wate r delta T improvement

10

Typical Chilled Water System

System DataChiller #1 Load = 90%Chiller #2 Load = 0%Loop Flow = 360 GPMChiller ∆T = 12˚F

Design: 400 Ton CHW System @ 12˚∆T

Chiller200 tonsVFD Pump

VFD Pump Chiller200 tons

180 Ton Load (45%)

42˚

360 GPM Loop Flow

CHWS

90% LoadIncrease flow by 15%

CHWR

54˚

Page 11: Knowledge is Power Belimo Energy Valve™ CHW DELTA T · PDF file · 2016-09-28Knowledge is Power Belimo Energy Valve ... • Recommend implementing chilled wate r delta T improvement

11

Typical Chilled Water System

System DataChiller #1 Load = 45%Chiller #2 Load = 45%Loop Flow = 414 GPMChiller ∆T = 10.4˚F

Design: 400 Ton CHW System @ 12˚∆T

Chiller200 tonsVFD Pump

VFD Pump Chiller200 tons

180 Ton Load (45%)

42˚

414 GPM Loop Flow

CHWS

45% LoadIncrease flow by 15%

CHWR

52.4˚

Chiller200 tons

45% Load

An additional pump and chiller were started to meet the flow demand, not cooling demand!

Page 12: Knowledge is Power Belimo Energy Valve™ CHW DELTA T · PDF file · 2016-09-28Knowledge is Power Belimo Energy Valve ... • Recommend implementing chilled wate r delta T improvement

Causes of Low Delta T

– Control valves oversized– Controlling the water valve using air temp– Inadequate balancing procedure– Non-dynamic balancing– Changes to piping system

12

Page 13: Knowledge is Power Belimo Energy Valve™ CHW DELTA T · PDF file · 2016-09-28Knowledge is Power Belimo Energy Valve ... • Recommend implementing chilled wate r delta T improvement

Not the Solution

• Deny or Choke Valve, will not allow a coil to run as designed. This application will negate proper de-humidification and comfort.

13

Page 14: Knowledge is Power Belimo Energy Valve™ CHW DELTA T · PDF file · 2016-09-28Knowledge is Power Belimo Energy Valve ... • Recommend implementing chilled wate r delta T improvement

14

Library Case Study

• Case Study Issues• Coil delta T reported as 6 Degree F• Over pumping• Low delta T Syndrome at Chiller Plant

6 AHU units, 153,000 sq-ft

Page 15: Knowledge is Power Belimo Energy Valve™ CHW DELTA T · PDF file · 2016-09-28Knowledge is Power Belimo Energy Valve ... • Recommend implementing chilled wate r delta T improvement

Case Study

• AHU-6, CHW delta T with Belimo SL System Globe Valve test delta T control deactivated.

15

Page 16: Knowledge is Power Belimo Energy Valve™ CHW DELTA T · PDF file · 2016-09-28Knowledge is Power Belimo Energy Valve ... • Recommend implementing chilled wate r delta T improvement

Case Study

• AHU-6, CHW delta T with delta T control active-Globe Valve test.

16

Page 17: Knowledge is Power Belimo Energy Valve™ CHW DELTA T · PDF file · 2016-09-28Knowledge is Power Belimo Energy Valve ... • Recommend implementing chilled wate r delta T improvement

Case Study Setup

• 5 Flow Meter/Delta T Control Valves• 1 Tandem Venturi Valve with Delta T Control• Chilled Water is designed to run through a coil at a

designed temperature drop to supply air conditioned cooling air and to de-humidify. i.e. Water delta T=12 degrees F.

17

Page 18: Knowledge is Power Belimo Energy Valve™ CHW DELTA T · PDF file · 2016-09-28Knowledge is Power Belimo Energy Valve ... • Recommend implementing chilled wate r delta T improvement

Delta T and GPM control valve2.5” – 6”, 90 thru 713 GPM

• The Valve is a pressure independent control valve that optimizes, documents and proves water coil performance by correcting low delta T.

18

Actuator

Valve

Magnetic Flow sensor

Temperature Sensors (for supply & return water)

Page 19: Knowledge is Power Belimo Energy Valve™ CHW DELTA T · PDF file · 2016-09-28Knowledge is Power Belimo Energy Valve ... • Recommend implementing chilled wate r delta T improvement

Valve Operation

• Pressure independent, Mag flow meter maintains proper flow.

• Delta-T Manager will maintain design Coil delta-T.• Delta T will stay constant eliminating overflow.• The Energy Valve’s GPM meter, and temperature

sensors add no additional DDC points to a system.

19

Page 20: Knowledge is Power Belimo Energy Valve™ CHW DELTA T · PDF file · 2016-09-28Knowledge is Power Belimo Energy Valve ... • Recommend implementing chilled wate r delta T improvement

New Definitions

• Power Saturation Point– Point beyond which coil cannot yield additional

heat transfer regardless of increased flow.• Waste Zone

– Range beyond the “Power Saturation Point”.

20

Page 21: Knowledge is Power Belimo Energy Valve™ CHW DELTA T · PDF file · 2016-09-28Knowledge is Power Belimo Energy Valve ... • Recommend implementing chilled wate r delta T improvement

AHU-6 Power Curve: July 4, 2011 (data is PI valve function only)

21

Page 22: Knowledge is Power Belimo Energy Valve™ CHW DELTA T · PDF file · 2016-09-28Knowledge is Power Belimo Energy Valve ... • Recommend implementing chilled wate r delta T improvement

AHU-6 DT Curve: July 4, 2011 (data is PI valve function only)

22

Page 23: Knowledge is Power Belimo Energy Valve™ CHW DELTA T · PDF file · 2016-09-28Knowledge is Power Belimo Energy Valve ... • Recommend implementing chilled wate r delta T improvement

Power Saturation & Waste Zone

23

Page 24: Knowledge is Power Belimo Energy Valve™ CHW DELTA T · PDF file · 2016-09-28Knowledge is Power Belimo Energy Valve ... • Recommend implementing chilled wate r delta T improvement

Energy Valve Delta-T Manager Operation

24

DDC SIGNAL

Page 25: Knowledge is Power Belimo Energy Valve™ CHW DELTA T · PDF file · 2016-09-28Knowledge is Power Belimo Energy Valve ... • Recommend implementing chilled wate r delta T improvement

Pump Savings Example24% Flow Savings = 56% Energy Savings

25

0.00

5.00

10.00

15.00

20.00

25.00

30.00

35.00

0.00 10.00 20.00 30.00 40.00 50.00 60.00 70.00 80.00 90.00

12.57, 43.0910.27, 56.60

Pump flow Savings= (56.6-43.09)/56.6 = 24% Mechanical Energy Savings

=1-((1-.24) power 3)=56%

T

Flow [GPM ]

∆TCurve

T

Page 26: Knowledge is Power Belimo Energy Valve™ CHW DELTA T · PDF file · 2016-09-28Knowledge is Power Belimo Energy Valve ... • Recommend implementing chilled wate r delta T improvement

Hours Delta T Manager Active(Summer 2011)

1

Page 27: Knowledge is Power Belimo Energy Valve™ CHW DELTA T · PDF file · 2016-09-28Knowledge is Power Belimo Energy Valve ... • Recommend implementing chilled wate r delta T improvement

MIT, Haden Library Whole Building Results

• 2011 vs. 2010 Flow• 8/9-10/9 2010 6.15 F T • 8/9-10/9 2011 12.14 F T• From whole building meters, Metering data PI archive• Tonsx24/GPM= Weighted Average delta T

2

6 AHU units, 153,000 sq-ft

Page 28: Knowledge is Power Belimo Energy Valve™ CHW DELTA T · PDF file · 2016-09-28Knowledge is Power Belimo Energy Valve ... • Recommend implementing chilled wate r delta T improvement

Case Study Findings

• The delta T limiting is especially effective on coils that display “power saturation”

• Overall reduction of chilled water flow.• Significant energy savings are realized in

mechanical pumping energy with Delta-T Manger.

3

Page 29: Knowledge is Power Belimo Energy Valve™ CHW DELTA T · PDF file · 2016-09-28Knowledge is Power Belimo Energy Valve ... • Recommend implementing chilled wate r delta T improvement

Library Saving Calculations

• Using Data supplied by the Campus Engineering, increasing water delta T from 6 to 12 degrees. The potential savings for calendar year 2011 are as follows:– 2011 had 1005 COOLING D-DAY»$12,529.00 CHW

PUMP ALONE (25% of total savings).– Plant savings, turning off chillers, condenser pumps

and fans would equal a potential savings of $50,116.00.

4

Page 30: Knowledge is Power Belimo Energy Valve™ CHW DELTA T · PDF file · 2016-09-28Knowledge is Power Belimo Energy Valve ... • Recommend implementing chilled wate r delta T improvement

Chilled Water Delta T management technology

• Technical Summary• Maximize coil performance• Monitor savings at the coil level• Documented commissioning of coil• 13 month data archive

5

Page 31: Knowledge is Power Belimo Energy Valve™ CHW DELTA T · PDF file · 2016-09-28Knowledge is Power Belimo Energy Valve ... • Recommend implementing chilled wate r delta T improvement

Belimo Energy Valve

6

• Features & Benefits

Page 32: Knowledge is Power Belimo Energy Valve™ CHW DELTA T · PDF file · 2016-09-28Knowledge is Power Belimo Energy Valve ... • Recommend implementing chilled wate r delta T improvement

Knowledge is Power

7

Process Order

1. Benchmarking

2. Data Acquisition

3. Analysis

4. Optimization

Page 33: Knowledge is Power Belimo Energy Valve™ CHW DELTA T · PDF file · 2016-09-28Knowledge is Power Belimo Energy Valve ... • Recommend implementing chilled wate r delta T improvement

BenchmarkingStep 1

• Building Design• The first iteration of benchmarking is the Engineer’s design

8

Page 34: Knowledge is Power Belimo Energy Valve™ CHW DELTA T · PDF file · 2016-09-28Knowledge is Power Belimo Energy Valve ... • Recommend implementing chilled wate r delta T improvement

Data AcquisitionStep 2• Delta T and Flow data

– Flow– Delta T– Energy Output– Power Output– Totalized Energy

9

Page 35: Knowledge is Power Belimo Energy Valve™ CHW DELTA T · PDF file · 2016-09-28Knowledge is Power Belimo Energy Valve ... • Recommend implementing chilled wate r delta T improvement

Data AcquisitionStep 2

• Data Export and the Excel Tool• Energy Valve

• Data Logging and Storage• Up to 13 Months of Data• Export to .csv file format

• Excel Tool • Import .csv in to Excel Tool• Power Curves• Charts, Graphs, Trending

10

Page 36: Knowledge is Power Belimo Energy Valve™ CHW DELTA T · PDF file · 2016-09-28Knowledge is Power Belimo Energy Valve ... • Recommend implementing chilled wate r delta T improvement

Data AcquisitionStep 2

• Web View – Live Trending View• Live Trending

• Temperature• Flow (GPM)• Power (kW)• Up to 1hr of Data

• Features• Real Time Data• Export to .csv

11

Page 37: Knowledge is Power Belimo Energy Valve™ CHW DELTA T · PDF file · 2016-09-28Knowledge is Power Belimo Energy Valve ... • Recommend implementing chilled wate r delta T improvement

Data AcquisitionStep 2

• Web View – Live Trending View• Network Communications

• BACnet MS/TP• BACnet IP• TCP/IP• MP-bus

12

Page 38: Knowledge is Power Belimo Energy Valve™ CHW DELTA T · PDF file · 2016-09-28Knowledge is Power Belimo Energy Valve ... • Recommend implementing chilled wate r delta T improvement

Data AcquisitionStep 2Supported BACnet Objects

13

Page 39: Knowledge is Power Belimo Energy Valve™ CHW DELTA T · PDF file · 2016-09-28Knowledge is Power Belimo Energy Valve ... • Recommend implementing chilled wate r delta T improvement

`

Data AnalysisStep 3Analyzing the Power Curve

© Belimo, 2012

Page 40: Knowledge is Power Belimo Energy Valve™ CHW DELTA T · PDF file · 2016-09-28Knowledge is Power Belimo Energy Valve ... • Recommend implementing chilled wate r delta T improvement

OptimizationStep 4

• Web View - Parameterization Settings View• Networked, Communicate via Web• Real Time Configuration• Real Time Data

15

Page 41: Knowledge is Power Belimo Energy Valve™ CHW DELTA T · PDF file · 2016-09-28Knowledge is Power Belimo Energy Valve ... • Recommend implementing chilled wate r delta T improvement

OptimizationStep 4

• ZTH-2 - Parameterization Tool

• Quick Programming• Quick Reconfiguration• Fast Commissioning• Hand Held Local Display

16

Page 42: Knowledge is Power Belimo Energy Valve™ CHW DELTA T · PDF file · 2016-09-28Knowledge is Power Belimo Energy Valve ... • Recommend implementing chilled wate r delta T improvement

Hot Water Applications

• High Efficiency Condensing Boilers• Boiler efficiency 98%• Combustion gas 18°F above return water temp• Return temperature should be below 110°F

17

Page 43: Knowledge is Power Belimo Energy Valve™ CHW DELTA T · PDF file · 2016-09-28Knowledge is Power Belimo Energy Valve ... • Recommend implementing chilled wate r delta T improvement

Thank You