Top Banner
Kensa Heat Pumps Follow on training
33

Kensa Heat Pumps Follow on training. Agenda Introduction Heat Pump Operation Application Design/MCS/ Pricing Ground Arrays.

Dec 17, 2015

Download

Documents

Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: Kensa Heat Pumps Follow on training.  Agenda  Introduction  Heat Pump Operation  Application  Design/MCS/ Pricing  Ground Arrays.

Kensa Heat Pumps

Follow on training

Page 2: Kensa Heat Pumps Follow on training.  Agenda  Introduction  Heat Pump Operation  Application  Design/MCS/ Pricing  Ground Arrays.

www.kensaheatpumps.com

Agenda

Introduction

Heat Pump Operation

Application

Design/MCS/ Pricing

Ground Arrays – unrolling and purging

Simple diagnostics and fault finding

Q&A, product viewing

Lunch

Page 3: Kensa Heat Pumps Follow on training.  Agenda  Introduction  Heat Pump Operation  Application  Design/MCS/ Pricing  Ground Arrays.

www.kensaheatpumps.com

Heat Pump Cycle

3

Page 4: Kensa Heat Pumps Follow on training.  Agenda  Introduction  Heat Pump Operation  Application  Design/MCS/ Pricing  Ground Arrays.

www.kensaheatpumps.com

4

Heat Pump Performance

The efficiency of a heat pump

is mainly governed by

the outlet temperature

Page 5: Kensa Heat Pumps Follow on training.  Agenda  Introduction  Heat Pump Operation  Application  Design/MCS/ Pricing  Ground Arrays.

www.kensaheatpumps.com

Heat Pump Performance

Inlet temperature also can have an affect on COP

5

Page 6: Kensa Heat Pumps Follow on training.  Agenda  Introduction  Heat Pump Operation  Application  Design/MCS/ Pricing  Ground Arrays.

www.kensaheatpumps.com

Heat Pump Efficiency

Real-life efficiency is expressed as a SPF (Seasonal Performance Factor) which is a very complex calculation and is influenced by numerous factors quite distinct from the heat pump performance.

Kensa’s heat pumps use Copeland scroll compressors, the most advanced available, and capable of providing the best available performance.

Branding of the heat pump is not the critical factor in determining performance. Factors linked to the property and the site are far more influential.

Ability to highlight the impact of some of these factors is helpful in gaining credibility with the client.

6

6

Page 7: Kensa Heat Pumps Follow on training.  Agenda  Introduction  Heat Pump Operation  Application  Design/MCS/ Pricing  Ground Arrays.

www.kensaheatpumps.com

Domestic Heat Pumps

R407C R134a

Size Compressor Size Compressor

4kW Single 3.5 kW Single

6kW Single 4.3kW Single

8kW Single 6kW Single

10kW Single 7kW Single

12kW Single 8.5kW Single

12kW Twin 10kW Single

16kW Twin 12kW Twin

20kW Twin 17kW Twin

24kW Twin 20kW Twin

30kW Twin

Page 8: Kensa Heat Pumps Follow on training.  Agenda  Introduction  Heat Pump Operation  Application  Design/MCS/ Pricing  Ground Arrays.

www.kensaheatpumps.com

Single Compressor internals

Page 9: Kensa Heat Pumps Follow on training.  Agenda  Introduction  Heat Pump Operation  Application  Design/MCS/ Pricing  Ground Arrays.

www.kensaheatpumps.com

Twin Compressor Internals

Page 10: Kensa Heat Pumps Follow on training.  Agenda  Introduction  Heat Pump Operation  Application  Design/MCS/ Pricing  Ground Arrays.

www.kensaheatpumps.com

Hybrid Heat Pumps

10

Single Phase Twin Compressor

R407C and R134a

15kW and 21kW

Page 11: Kensa Heat Pumps Follow on training.  Agenda  Introduction  Heat Pump Operation  Application  Design/MCS/ Pricing  Ground Arrays.

www.kensaheatpumps.com

Shoebox Heat Pumps

11

Page 12: Kensa Heat Pumps Follow on training.  Agenda  Introduction  Heat Pump Operation  Application  Design/MCS/ Pricing  Ground Arrays.

www.kensaheatpumps.com

Plant Room Modules

15

20 to 75 kW per module.

Combinations up to 1 MW and beyond

Page 13: Kensa Heat Pumps Follow on training.  Agenda  Introduction  Heat Pump Operation  Application  Design/MCS/ Pricing  Ground Arrays.

www.kensaheatpumps.com

Application

Application is critical

If a heat pump fails we can fix it, but if the application is wrong........

Page 14: Kensa Heat Pumps Follow on training.  Agenda  Introduction  Heat Pump Operation  Application  Design/MCS/ Pricing  Ground Arrays.

www.kensaheatpumps.com

Application - Exercise

Points to consider when installing a GSHP

i.e. Type of fuel replacing

Page 15: Kensa Heat Pumps Follow on training.  Agenda  Introduction  Heat Pump Operation  Application  Design/MCS/ Pricing  Ground Arrays.

www.kensaheatpumps.com

Application

How well insulated is the building?

What type of heating?

What fuel are we displacing?

Floor Construction.

Amount of glazing.

Noise issues.

Available heat source.

Page 16: Kensa Heat Pumps Follow on training.  Agenda  Introduction  Heat Pump Operation  Application  Design/MCS/ Pricing  Ground Arrays.

www.kensaheatpumps.com

Insulation

19

The better you insulate your building : - The lower the flow temperature required by the underfloor

heating system to reach your target temperature

Therefore, the less the heat pump has to raise the temperature

And the more efficient the heat pump!

The better you insulate your building, the more efficiently the heat pump will operate.

Page 17: Kensa Heat Pumps Follow on training.  Agenda  Introduction  Heat Pump Operation  Application  Design/MCS/ Pricing  Ground Arrays.

www.kensaheatpumps.com

The better insulated the building

20

Smaller the heat pump required

The less the digging/drilling required

Lower the capital cost

Lower the building’s carbon emissions

Lower the energy bill

Page 18: Kensa Heat Pumps Follow on training.  Agenda  Introduction  Heat Pump Operation  Application  Design/MCS/ Pricing  Ground Arrays.

www.kensaheatpumps.com

21

Heating Distribution Methods

Underfloor

Ideal, large emitting area therefore low input temperatures.

Beware floor coverings and method of installation which might require the heat pump to operate at higher temperatures.

Page 19: Kensa Heat Pumps Follow on training.  Agenda  Introduction  Heat Pump Operation  Application  Design/MCS/ Pricing  Ground Arrays.

www.kensaheatpumps.com

22

Heating Distribution Methods

Radiators

Need a higher temperature than underfloor due to the lower heat emitting area.

Might need oversized radiators as maximum temperature from the heat pump is approx. 50C.

Page 20: Kensa Heat Pumps Follow on training.  Agenda  Introduction  Heat Pump Operation  Application  Design/MCS/ Pricing  Ground Arrays.

www.kensaheatpumps.com

Mixing radiators and underfloor

23

Some want radiators upstairs, and underfloor downstairs

Can this be done?Yes

Depending on the floor construction, the temperature required by the radiators can be the same as the underfloor system!

There is a delay between the radiators and underfloor feeling warm.

Zone valves are generally required.

Page 21: Kensa Heat Pumps Follow on training.  Agenda  Introduction  Heat Pump Operation  Application  Design/MCS/ Pricing  Ground Arrays.

www.kensaheatpumps.com

DHW Production

25

Page 22: Kensa Heat Pumps Follow on training.  Agenda  Introduction  Heat Pump Operation  Application  Design/MCS/ Pricing  Ground Arrays.

www.kensaheatpumps.com

Secondary Returns

26

Standard secondary returns cause the cylinder temperature to drop and due to the low temperature nature of heat pumps this temperature drop cannot be recovered

Page 23: Kensa Heat Pumps Follow on training.  Agenda  Introduction  Heat Pump Operation  Application  Design/MCS/ Pricing  Ground Arrays.

www.kensaheatpumps.com

DHW Cylinders

27

Single or Twin Coils(Coil designed and sized for Heat Pump applications)

3kW Immersion Heater

Expansion Vessel

G3 Kit

Stainless Steel tanks guaranteed for 25 years against leaks.

Page 24: Kensa Heat Pumps Follow on training.  Agenda  Introduction  Heat Pump Operation  Application  Design/MCS/ Pricing  Ground Arrays.

www.kensaheatpumps.com

Inverted houses

Bedrooms downstairs, living area upstairs.

Depends on floor construction.

Might need to run at higher temperatures and standard rate electricity.

Page 25: Kensa Heat Pumps Follow on training.  Agenda  Introduction  Heat Pump Operation  Application  Design/MCS/ Pricing  Ground Arrays.

www.kensaheatpumps.com

Glazing

Beware high areas of glazing.

(even triple glazing only retains 1/3rd of the heat a solid wall does)

Will be cool in winter when cold ambient conditions.

Additional heating such as log burners.

Page 26: Kensa Heat Pumps Follow on training.  Agenda  Introduction  Heat Pump Operation  Application  Design/MCS/ Pricing  Ground Arrays.

www.kensaheatpumps.com

Noise Issues

Keep the heat pump away from noise sensitive areas.

Similar noise to an oil fired boiler or running dishwasher.

Can install external to the building at the back of a garage or in a lean to.

Page 27: Kensa Heat Pumps Follow on training.  Agenda  Introduction  Heat Pump Operation  Application  Design/MCS/ Pricing  Ground Arrays.

www.kensaheatpumps.com

Buffer Vessels

Fitted to avoid short-cycling, i.e. which is where the heat generated during the minimum run time for the heating appliance (usually several minutes) cannot be absorbed by the buildings distribution system.

Page 28: Kensa Heat Pumps Follow on training.  Agenda  Introduction  Heat Pump Operation  Application  Design/MCS/ Pricing  Ground Arrays.

www.kensaheatpumps.com

Buffer Vessels2 connection buffer vessels are more efficient

If close control of all temperature zones is not required then ‘open’ zones of the underfloor can be used as the buffer vessel.

Page 29: Kensa Heat Pumps Follow on training.  Agenda  Introduction  Heat Pump Operation  Application  Design/MCS/ Pricing  Ground Arrays.

www.kensaheatpumps.com

Project Example – Sizing The Heat Pump

33

New Build Four Bedroom Detached Property with Garage

Page 30: Kensa Heat Pumps Follow on training.  Agenda  Introduction  Heat Pump Operation  Application  Design/MCS/ Pricing  Ground Arrays.

www.kensaheatpumps.com

Sizing

34

Internal area – Ground Floor & First Floor

Total Internal area = 224.6m2

Heat load =

224.6 x 40w/m (If New Build)

= 8984

= 8.98 kW

Page 31: Kensa Heat Pumps Follow on training.  Agenda  Introduction  Heat Pump Operation  Application  Design/MCS/ Pricing  Ground Arrays.

www.kensaheatpumps.com

Budget Pricing

Page 32: Kensa Heat Pumps Follow on training.  Agenda  Introduction  Heat Pump Operation  Application  Design/MCS/ Pricing  Ground Arrays.

www.kensaheatpumps.com

Budget Pricing

Page 33: Kensa Heat Pumps Follow on training.  Agenda  Introduction  Heat Pump Operation  Application  Design/MCS/ Pricing  Ground Arrays.

www.kensaheatpumps.com

SAP Report - Line 37

Heat Loss Coefficient x Temperature Difference -2°C (Min) to 21°C (Max) = 23°C rise

378.45 x 23 = 8704W = 10kW (39W/m)

SAP sizing – Line 37!