Canopy Area excluded from GIA (2.20) Front Entrance Shutter Door Shutter Door Shutter Door Shutter Door Shutter Door Shutter Door Shutter Door Shutter Door Shutter Door Shutter Door Shutter Door Shutter Door Shutter Door Warehouse Canopy Area 162.79 sq m 1782 sq ft Copy Point Front Entrance Fire Exit Fire Exit Fire Exit Front Entrance Fire Exit Fire Exit Fire Exit Fire Exit Fire Exit Fire Exit Fire Exit Fire Exit Fire Exit Fire Exit Fire Exit Fire Exit L Twr TX EXT3 EXT4 EXT1 EXT2 LV01 Proposed DNO Substation Proposed 1MVA Transformer GRP transformer housing 3000 x 3000 x 2400 6xØ100 Ducts 1xØ100 Ducts 1xØ100 Ducts 2xØ100 Ducts 1xØ100 Ducts 450x450mm Draw Pit 1xØ100 Ducts 600x600mm Draw Pit 450x450mm Draw Pit 450x450mm Draw Pit 1xØ100 Ducts 1xØ100 Ducts 1xØ100 Ducts 1xØ100 Ducts 2xØ100 Ducts 4xØ100 Ducts 600x600mm Draw Pit 2xØ100 Ducts 1xØ100 Ducts 3xØ100 Ducts 4xØ100 Ducts 1xØ100 Ducts 1xØ100 Ducts 3xØ100 Ducts 3xØ100 Ducts 600x600mm Draw Pit 2xØ100 Ducts 1xØ100 Ducts 600x600mm Draw Pit RCD RCD RCD RCD RCD RCD RCD RCD RCD 450x450mm Draw Pit 450x450mm Draw Pit 450x450mm Draw Pit 1xØ100 Ducts 1xØ100 Ducts 8xØ150 Ducts 1xØ100 Ducts 1xØ100 Ducts Existing Private transformer 415V - 33KV 1xØ100 Ducts H EVC2 1xØ100 Ducts 1xØ100 Ducts 1xØ100 Ducts 1xØ100 Ducts 450x450mm Draw Pit 1xØ100 Ducts 1xØ100 Ducts Redundant incoming BT supply to be removed Redundant incoming MCW mains to be disconnected and removed L Redundant incoming LV supply to be disconnected and removed H 8xØ150 Ducts 450x450mm Draw Pit 450x450mm Draw Pit 450x450mm Draw Pit 450x450mm Draw Pit 1xØ100 Ducts 1xØ100 Ducts 1xØ100 Ducts 1xØ100 Ducts 600x600mm Draw Pit 10xØ150 Ducts 600x600mm Draw Pit L Incoming LV supply to be disconnected and removed BT M Incoming MCW mains to be retained Existing supply capacity to be confirmed New MCW meter to be installed Incoming LP Gas to be retained Existing supply capacity to be confirmed Incoming BT to be retained 10xØ150 Ducts DNO Substation MDPE Barrier Pipe Mains Cold Water proposed route. Medium Pressure Gas Main proposed route. BT ducts proposed route. Ducts proposed route (sized as shown) Low Pressure Gas Main proposed route. H Proposed Hydrant Position. TP+N isolator (rated as shown) SP+N isolator (rated as shown) SP+N distribution board TP+N distribution board HPPE Barrier Pipe Hydrant Main proposed route TX 3m x 3m Transformer compound. Proposed Precast Trench with composite lid. Precast Concrete Trench cable Feeder Pits FFP Proposed HV Turning Pit H L Potential Future LV Sub feeder Left as Turning Pit Indicative position of CCTV exterior camera mounted on column by end user's contractor. Main Contractor to provide containment, Twin 13A RCD metal clad socket, column & base to each location (column & base to be confirmed by end user). (Final number, type and direction to be decided by end user's Security contractor). Twin 13A Metalclad RCD Socket for CCTV media converter (exact position on column TBC). RCD Drawpit Size as noted 150mm underground LV Duct (No. INDICATED) Proposed MCW Valve Pit (Unless noted otherwise) Proposed Hydrant Valve Pit (Unless noted otherwise) Proposed Inspection Pit. (Size as noted) Proposed BT chamber. LEGEND:- BT M Proposed MCW Meter Proposed 13A Fused Spur Thrust Block T Column mounted light.(See drawing '10252-PL-100' for more information.) Feeder Pillar for EVC FP (EVC .NO) Notes: 1. Existing Incoming Utility services connection points for Gas/Water/Telecoms & Electricity to be confirmed by developer. 2. Location of Transformers and LV Panels to be carefully coordinated with MHE and operations layout. 3. Main Contractor to be responsible for any concrete bases/Builderswork required for Utility meters. 4. External Lighting to be carefully coordinated with HGV /Car parking and Landscaping layouts. 5. Transformer compound to be Fenced with Double Lockable gates. 6. Electrical Contractor to provide Lighting column details to Main Contractor to enable sleeves/concrete to be designed/installed. 7. Draw Pit to be included at all CCTV locations. 8. Main Contractor to allow additional 1x100mm duct from nearest Draw Pit to serve CCTV cameras on Lighting columns. 9. Main Contractor to provide power for CCTV camera media converters at positions indicated on drawing. 10. Main Contractor to confirm with End user's security contractor, suitability of lighting columns for camera mounting. TP&N ISOLATOR (Rated as shown) ??A TP&N 2x100mm Underground CCTV Duct 2xCOMPARTMENT CCTV CABLE TRUNKING SIZE AS INDICATED ON LAYOUT CCTV ELECTRICAL RISER CCTV STAINLESS STEEL CONDUIT 2x100mm UNDERGROUND CCTV DUCT 3 x 150mm Underground LV Generator Duct EARTH NEST 1000mm x 500mm Cable Trench complete with cover suitable for heavy vehicle crossing Active Charger Location CABLE TRAY UNDER CANOPY SIZE AS INDICATED 13A MASTERSEAL TSSO, 30mA RCD Column mounted light. (See drawing '10351-PL-100' for more information.) Passive Charger Location 2000 350 900 600 250 600 450 430 690 960 1255 1550 1720 280 430 260 270 295 295 170 Footpath(mm) 350 900 600 450 600 1. Carriageway(mm) 750 600 900 750 600 3. Gas Water BT Electric HV Electric LV Information Concerning Depth and line of existing infrastructure services has been extracted from relevant Statuatory Authority Ordinance Survey maps and is given without Obligation or warranty and its accuracy cannot be guaranteed. Exploration trial holes must be hand dug as must any excavation to relocate or otherwise modify existing live services. Adequate protection is to be provided during all site works. All new services to be installed to the following minimum depths of cover. Other Telecom Providers 600 350 4. Exact/final points of entry of all new incoming utility services to be agreed with the Employer. All incoming electricity & water services shall as/where applicable be ducted under all floor slabs & concrete service yards to meet the requirements of the particular utility company, with electricity cables also ducted under any road crossings. 5. All existing above or below ground redundant 'public/utility' or 'private' electrical, gas, telecom or water services within the site demise shall be identified & safely disconnected, removed and disposed off from site (or otherwise left abandoned underground) to meet Construction needs. 2. This information is issued for information purposes. No design intent is implied and the actual position of all new services and the construction sequence must be determined by the Contractor and/or his Highways Contractor. Contractor to provide coordination of all services with EVC services 6. NOTES: H A F 150 E D 350 150 65 C Base Door B G COLUMNS SPECIFICATION · Stepped tubular galvanised steel columns, to BS EN 40-2:2004 · Mounting accesories are hot dip galvanised to BS EN ISO 1461:2009 · Supplied with wooden baseboard for mounting cable connection accessories · Accessories are easily fixed with stainless steel grub screws and have an internal stop to ensure cable exit COLUMN RANGE NOMINAL HEIGHT CAT.No. PLANTING DEPTH BASE HEIGHT DOOR HEIGHT DOOR DIMENSIONS BASE DIAMETER SHAFT DIAMETER APPROX. kg BASEBOARD SIZE A B C D E F G H Single and Twin Starbeam Standard Columns 6m FC6 1000 925 300 500 100 140 76 44 89(w) x 500 (h) 8m FC8 1200 1200 400 600 115 168 114* 100 89(w) x 600 (h) 10m FC10 1500 1300 500 600 115 168 114* 142 89(w) x 600 (h) * Reduced at top to 101mm to accept accessories. 4m FC4 800 925 300 500 100 140 76 33 89(w) x 500 (h) Range of ornate arms available Conduit gland M25 threaded entry Tube to wiper spray nozzle Venting as standard Outline of customer CCTV camera Decorative banding Cabinet size options 325 / 400 / 500 Fan assisted cooling Double door access for partitioned cabinet Option Condensation drip tray with outlet pipe 400 Sq. cabinet Removable access door CCTV equipment mounted onto marine ply backboard Tamperproof micro switch Access door for wash bottle 5 litre wash bottle 342 746 x 312 Standard aperture Cable duct 325 x 325 Cable access 645 x 645 Ø219 MAIN CONTRACTOR TO PROVIDE FOLLOWING CONCRETE BASES TO SUB-CONTRACTOR DESIGN · TRANSFORMER · LIGHTING FEEDER PILLAR · MOBILE GENERATOR MAIN CONTRACTOR TO PROVIDE PROTECTION TO ALL INTERNAL DISTRIBUTION BOARDS & IDF BOARDS Typical Arrangement of 2 No. Water Connections to Site Meter Single Check Valve Sluice Valve Customers Potable Water Supply Customers Fire Main/Hydrant Supply Broken lines denote outline of valve/ meter pit sized to suit. Site Boundary Denotes R.W.C pipework installation Denotes Customer pipework installation Hydrant Washout Non-Return Valve Sluice valve (at site boundary) Suitably sized HPPE pipes connect to water main. RWC Water Main Suitably sized MDPE pipes connect to water main. GC8 Housing Base Typical Detail Typical Gas Meter/governor base detail for costing purposes only. Exact detail to be provided by Gas self lay contractor - 4 DETAIL TYPICAL TRANFORMER BUILDERSWORK WITH FULLY BUNDED PIT NTS BUNDED PIT TO SUIT TX SIZE BY CONTRACTOR EARTH PIT TRANSFORMER BUILDERSWORK WITH FULLY BUNDED PIT 3000 3000 TRANSFORMER ENCLOSURE EARTH TAPE CABLE IN CABLE OUT TO DRAINAGE SYSTEM TX PLAN VIEW SIDE VIEW PRECAST CONCRETE BASE TO LOAD 20 TONS GENERATOR CONNECTION BOARD CABLE ENTRY FROM MAIN LV PANEL Ø150 CABLE DUCT MOBILE GENERATOR CABLE ENTRY EARTH PIT - 3 DETAIL TYPICAL GENERATOR CONNECTION DETAIL FOR MAIN BUILDING MAIN LV PANEL NTS TYPICAL-1 TRANSFORMER DETAIL (TX) TYPICAL-2 MP/LP GAS METER HOUSING TYPICAL-3 PACKAGED ELECTRICAL SUBSTATION ADAPTABLE WAREHOUSE BOX FIXED WITH TAMPER PROOF SCREW BY MAIN CONTRACTOR MEDIA CONVERTOR BY SECURITY CONTRACTOR BY SECURITY CONTRACTOR - 2 DETAIL TYPICAL CCTV CABLING THROUGH CONVERTOR FROM TRUNKING NTS - 1 DETAIL TYPICAL CAMERA COLUMN WITH BASE NTS Drawing no. Scale Drawn by Rev. Date Checked by Drawing Title Project Address Architect Client The copyright of this document is vested solely in Kelly Taylor & Associates. Reproduction of this document, in whole or in part, is prohibited other than with the express permission of the above company. This drawing to be read in conjunction with all relevant architects, consultants, sub-contractors and specialist drawings, and should not be scaled from in any way. Rev. By Date Description Revisions E-MAIL [email protected] K E L L Y T A Y L O R & A S S O C I A T E S ENGINEERING & ENVIRONMENTAL CONSULTANTS 1 ASHLEIGH WAY, LANGAGE BUSINESS PARK, PLYMOUTH, DEVON, PL7 5JX. FAX. +44(0)1752 344282 TEL. +44(0)1752 332890 Authorised by Chk Size A0 THAMES ROAD, BARKING CDM DESIGNER RISK INFORMATION In addition to the hazards/risks normally associated with the types of work detailed on this drawing NOTE THE FOLLOWING: · CONSTRUCTION N/A · MAINTENANCE/CLEANING N/A · DECOMMISSIONING/DEMOLITION N/A It is assumed that all works will be carried out by a contractor competent under CDM 2015 working to an approved method statement External Services Layout 10365-EXT-100 - PLANNING 1:350 Feb '21 YJ YJ GPH