PACKAGED ELECTRIC / ELECTRIC KC Landmark™ Rooftop Units 60 HZ Bulletin No. 210553 October 2010 Supersedes August 2010 ENGINEERING DATA MODEL NUMBER IDENTIFICATION 15 to 25 Tons Net Cooling Capacity − 176,000 to 270,000 Btuh Optional Electric Heat - 15 to 90 kW K C A 240 S 4 B N 1 Y Brand/Family K = Landmark™ Unit Type C = Packaged Electric Cooling w/ optional Electric Heat Major Design Sequence A = 1st Generation Nominal Cooling Capacity - Tons 180= 15 Tons 210 = 17.5 Tons 240 = 20 Tons 300 = 25 Tons Cooling Efficiency S = Standard Efficiency Refrigerant Type 4 = R-410A Blower Type B = Belt Drive Factory Installed Electric Heat N = No Heat Minor Design Sequence 1 = 1st Revision 2 = 2nd Revision 3 = 3rd Revision Voltage Y = 208/230V-3 phase-60hz G = 460V-3 phase-60hz J = 575V-3 phase-60hz ASHRAE 90.1 COMPLIANT
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
P A C K A G E D E L E C T R I C / E L E C T R I C
KCLandmark™ Rooftop Units
60 HZBulletin No. 210553
October 2010Supersedes August 2010
E N G I N E E R I N G D ATA
MODEL NUMBER IDENTIFICATION
15 to 25 TonsNet Cooling Capacity − 176,000 to 270,000 Btuh
Optional Electric Heat - 15 to 90 kW
K C A 240 S 4 B N 1 Y
Brand/Family K = Landmark™
Unit Type C = Packaged Electric Cooling w/ optional Electric Heat
Voltage Y = 208/230V-3 phase-60hz G = 460V-3 phase-60hz J = 575V-3 phase-60hz
ASHRAE 90.1COMPLIANT
Landmark™ Packaged Electric / Electric 15 to 25 Ton / Page 2
FEATURES AND BENEFITS
Landmark™ rooftop units from Lennox are the new standard for reliable, efficient rooftop units built for long-lastingperformance that can significantly improve indoor and outdoor environments. Landmark rooftop units feature:
• R-410A Refrigerant - Environmentally friendly• Scroll Compressors - Single speed scroll compressors are furnished on all models.• Crankcase Heaters - Protect compressors from refrigerant liquid migration in the off cycle improving product
reliability.• High Pressure Switches - Protect compressor.• Isolated Compressor Compartment - Allows performance check during normal compressor operation without
disrupting airflow.• Independent Motor Mounts - Allows for easy and efficient service access without removing the top panel.• Downflow Airflow - Horizontal airflow with optional horizontal curb.• Two Fork Lift Slots on Three Sides - Easy to pick up and transport units from almost any angle.• Corrosion-Resistant Removable, Drain Pan - Provides application flexibility, durability and improved serviceability.• Thermostatic Expansion Valves - Provide peak cooling performance across the entire application range.• MERV 8 or MERV 13 Filters - Available as field installed option, provide an enhanced level of indoor air quality, and
can help the building qualify for additional LEED credits.
APPROVALS
ETL listed.Efficiency rating CSA.Components bonded for grounding to meet safety standards for servicing required by UL, ULC and National and Canadian Electrical Codes.All models are certified in accordance with the ULE certification program, which is based on AHRI Standard 340/360-2007.All models are ASHRAE 90.1-2007 compliant.ISO 9001 Registered Manufacturing Quality System.
WARRANTY
Limited five years on compressors.Limited one year all other covered components.
COOLING SYSTEM
Designed to maximize sensible and latent cooling performance at design conditions.System can operate from 30°F to 125°F without any additional controls.R-410A RefrigerantNon-chlorine based, ozone friendly, R-410A.
A
B
C
G
D
F
EH
I
J
K
L
M
NO
Landmark™ Packaged Electric / Electric 15 to 25 Ton / Page 3
FEATURES AND BENEFITS
APPROVALS
ETL listed.Efficiency rating CSA.Components bonded for grounding to meet safety standards for servicing required by UL, ULC and National and Canadian Electrical Codes.All models are certified in accordance with the ULE certification program, which is based on AHRI Standard 340/360-2007.All models are ASHRAE 90.1-2007 compliant.ISO 9001 Registered Manufacturing Quality System.
WARRANTY
Limited five years on compressors.Limited one year all other covered components.
COOLING SYSTEM
Designed to maximize sensible and latent cooling performance at design conditions.System can operate from 30°F to 125°F without any additional controls.R-410A RefrigerantNon-chlorine based, ozone friendly, R-410A.
A
Scroll CompressorsScroll compressors on all models for high performance, reliability and quiet operation.Resiliently mounted on rubber grommets for quiet operation.Compressor Crankcase HeatersProtects against refrigerant migration that can occur during low ambient operation.Thermal Expansion ValvesAssures optimal performance throughout the application range.Removable element head.Filter/DriersHigh capacity filter/drier protects the system from dirt and moisture.High Pressure SwitchesProtects the compressor from overload conditions such as dirty condenser coils, blocked refrigerant flow, or loss of outdoor fan operation.FreezestatsProtects the evaporator coil from damaging ice build-up due to conditions such as low/no airflow, or low refrigerant charge.Coil ConstructionCopper tube construction, enhanced rippled-edge aluminum fins, flared shoulder tubing connections, silver soldered construction for improved heat transfer. Factory leak tested.
B
C
D
E
Evaporator CoilCross row circuiting with rifled copper tubing optimizes both sensible and latent cooling capacity.Condenser CoilAngled, slab design helps protect coil from possible contact or hail damage.Condensate Drain PanPlastic pan, sloped to meet drainage requirements of ASHRAE 62.1.Side or bottom drain connections.Outdoor Coil Fan MotorsThermal overload protected, totally enclosed, permanently lubricated ball bearings, shaft up, wire basket mount.Outdoor Coil FansPVC coated fan guard furnished.
REQUIRED SELECTIONS
Cooling CapacitySpecify nominal cooling capacity of the unit
OPTIONS/ACCESSORIES
Field InstalledCondensate Drain TrapAvailable in copper or PVC.Drain Pan Overflow SwitchMonitors condensate level in drain pan, shuts down unit if drain becomes cloggedLow Ambient KitCycles the outdoor fan while allowing compressor operation in the cooling cycle. This intermittent fan operation allows the system to operate without icing the evaporator coil and losing capacity. Designed for use in ambient temperatures no lower than 0°F.
Landmark™ Packaged Electric / Electric 15 to 25 Ton / Page 4
FEATURES AND BENEFITS
CABINET
ConstructionHeavy-gauge steel panels and full perimeter heavy-gauge galvanized steel base rail provides structural integrity for transportation, handling, and installation.Base rails have rigging holes.Three sides of the base rail have forklift slots.Raised edges around duct and power entry openings in the bottom of the unit provide additional protection against water entering the building.Airflow ChoiceUnits are available in downflow (vertical) or horizontal return air flow configuration.Horizontal air flow requires Horizontal Roof Curb.Horizontal Return Air Panel Kit is also required if converting a downflow configured unit to horizontal air flow.Power EntryElectrical lines can be brought through the unit base or through horizontal access knock-outsExterior PanelsConstructed of heavy-gauge, galvanized steel with a two-layer enamel paint finish.InsulationAll panels adjacent to conditioned air are fully insulated with non-hygroscopic fiberglass insulation.Unit base is fully insulated. The insulation also serves as an air seal to the roof curb, eliminating the need to add a seal during installation.Access PanelsAccess panels are provided for the economizer/filter section, heating/blower section, and the compressor/controls section.
G
OPTIONS/ACCESSORIES
Factory InstalledCorrosion ProtectionA completely flexible immersed coating with an electrodeposited dry film process. (AST ElectroFin E-Coat) Meets Mil Spec MIL-P-53084, ASTM B117 Standard Method Salt Spray Testing.Indoor Corrosion Protection: - Coated coil - Painted blower housing - Painted indoor baseOutdoor Corrosion Protection: - Coated coil - Painted outdoor baseHinged Access PanelsHinged access panels for the filter section, the blower section and compressor/controls section.All hinged panels have seals and quarter-turn latching handles to provide a tight air and water seal.Field InstalledCoil GuardsPainted, galvanized steel wire guards to protect outdoor coil.Not used with Hail Guards.Hail GuardsConstructed of heavy gauge steel, painted to match cabinet, helps protect outdoor coils from hail damage.Not used with Coil Guards.
Horizontal Return Air Panel KitRequired for horizontal applications with Horizontal Roof Curb, contains panel with return air opening for field replacement of existing unit panel and panel to cover bottom return air opening in unit, see dimension drawings.
BLOWER
A wide selection of supply air blower options are available to meet a variety of airflow requirements.MotorOverload protected, equipped with ball bearings. Belt drive motors are offered on all models and are available in several different sizes to maximize air performance.Supply Air BlowerForward curved blades, double inlet, blower wheel is statically and dynamically balanced. Equipped with ball bearings and adjustable pulley (allows speed change),.Blower assembly slides out of unit for servicing.
REQUIRED SELECTIONS
Order blower motor horsepower and drive kit number required when base unit is ordered, see Drive Kit Specifications Table.
H
Landmark™ Packaged Electric / Electric 15 to 25 Ton / Page 5
FEATURES AND BENEFITS
CONTROLS
Unit ControlAll control voltage is provided via a 24V (secondary) transformer with built-in circuit breaker protection.Heat/Cool Staging - Capable of up to 2 heat / 2 cool staging with a third party DDC control system or thermostat.Low Voltage Terminal Block - Provides screw terminal connections for thermostat or controller wiring.Night Setback Mode - Saves energy by closing outdoor air dampers and operating supply fan on thermostat demand only.
OPTIONS/ACCESSORIES
Field InstalledSmoke DetectorPhotoelectric type, installed in supply air section, return air section or both sections. Available with power board and single sensor (supply or return) or power board and two sensors (supply and return). Power board located in unit control compartment.Commercial Control SystemsL Connection® NetworkComplete building automation control system for single or multi-zone applications. Options include local interface, software for local or remote communication, and hardware for networking other control functions.See L Connection Network Engineering Handbook Bulletin for details.ThermostatsControl system and thermostat options. Aftermarket unit controller options. See page 22.
I
ELECTRICAL
All units include terminal block and fuse block in power entry junction box for single power entry application.
REQUIRED SELECTIONS
Voltage ChoiceSpecify when ordering base unit.
OPTIONS/ACCESSORIES
Factory or Field InstalledDisconnect SwitchAccessible from outside of unit, spring loaded weatherproof cover furnished.GFI Service Outlets (2)115V ground fault circuit interrupter (GFCI) type, field wired.Field InstalledElectric HeatHelix wound nichrome elements, individual element limit controls, wiring harness. Unit fuse block is furnished as standard. See Options / Accessories tables for ordering information
J
K
INDOOR AIR QUALITY
Air FiltersDisposable 2 inch filters furnished as standard.
OPTIONS/ACCESSORIES
Field InstalledHigh Efficiency Air FiltersDisposable MERV 8 or MERV 13 (Minimum Efficiency Reporting Value based on ASHRAE 52.2) efficiency 2 inch pleated filters.Healthy Climate® UVC Germicidal Lamps
Germicidal lamps emit ultra-violet (UV-C) energy, which has been proven to be effective in reducing microbes such as viruses, bacteria, yeasts, and molds. This process either destroys the organism or controls its ability to reproduce.UV-C energy greatly reduces the growth and proliferation of mold and other bioaerosols (bacteria and viruses) on illuminated surfaces (particularly coil and drain pan).Lamps are field installed in the blower/evaporator coil section.All necessary hardware for installation is included.Lamps operate on 208/230V power supply. Step-down transformer must be field supplied when used with 460V and 575V rooftop units.Magnetic safety interlock terminates power when access panels are removed.Approved by ETL.Indoor Air Quality (CO2) SensorsMonitors CO2 levels, reports to the Unit Controller which adjusts economizer dampers as needed.
L
Landmark™ Packaged Electric / Electric 15 to 25 Ton / Page 6
FEATURES AND BENEFITS
SERVICEABILITY
Designed to streamline general maintenance and decrease troubleshooting time.Marked & Color-Coded WiringAll electrical wiring is color-coded and marked to identify which components it is connecting.Electrical PlugsPositive connection electrical plugs are used to connect common accessories or maintenance parts for easy removal or installation.Access PanelsLarge access panels are provided for quick and easy access to maintenance areas.Blower AccessSupply air blower parts are located near the access door for easy servicing and adjustment.Thermal Expansion Valve AccessThermal expansion valves are located near the perimeter of the unit for easier access.Removable element head allows change out of element and bulb without removing the TXV.Coil CleaningSlab condenser coils provided for easier cleaning.Standard ComponentsA large number of common maintenance parts are standard throughout the entire range of sizes (3-25 tons), reducing the need to carry a lot of different parts to the job or maintain in inventory.Compressor CompartmentCompressors are located near the perimeter of the unit for easier access.Compressors are isolated from the condenser airflow allowing system operation checks to be done without changing the airflow across the outdoor coils.
Landmark™ Packaged Electric / Electric 15 to 25 Ton / Page 7
OPTIONS / ACCESSORIES
ECONOMIZER/EXHAUST OPTIONS
Factory or Field InstalledEconomizer - Downflow or Horizontal With Outdoor Air HoodParallel gear-driven action return air and outdoor air dampers, plug-in connections to unit, nylon bearings, neoprene seals, 24-volt, fully-modulating, spring return motor, adjustable minimum damper position. Outdoor air hood is furnished.Single sensible control is furnished with economizer. Outdoor air temperature sensor enables economizer if the outdoor temperature is less than the setpoint of the control.Outdoor Air Hood is included when economizer is factory installed and is furnished with economizer when ordered for field installation.Single Economizer Enthalpy ControlEnthalpy sensor enables the economizer when the outdoor air enthalpy is below the configured setpoint.Field InstalledDifferential (Dual) Economizer Enthalpy ControlOrder two single, enthalpy control kits. One is field installed in the return air section, the other in the outdoor air section. Allows the economizer control board to select between outdoor air or return air, whichever has lower enthalpy.
Downflow Barometric Relief Dampers With Exhaust HoodAllow relief of excess air.Aluminum blade dampers prevent blow back and outdoor air infiltration during off cycle.Exhaust hood with bird screen is furnished.
M
N
Horizontal Barometric Relief Dampers With Exhaust HoodFor use when unit is configured for horizontal applications requiring an economizer.Allows relief of excess airAluminum blade dampers prevent blow back and outdoor air infiltration during off cycle.Field installed in return air duct.Exhaust hood with bird screen is furnished.Power Exhaust FanInstalls internal to unit for downflow applications only with economizer option. Provides exhaust air pressure relief. Interlocked to run when supply air blower is operating, fan runs when outdoor air dampers are 50% open (adjustable), motor is overload protected. Requires Economizer with Outdoor Air Hood and Downflow Barometric Relief Dampers. Dual fans are 20 in. diameter with 5 blades with (2) 1/3 hp motors.
OUTDOOR AIR OPTIONS
Factory or Field InstalledOutdoor Air Damper - Downflow or Horizontal With Air HoodLinked mechanical dampers, 0 to 25% (fixed) outdoor air adjustable, installs in unit. Includes outdoor air hood.Automatic model features fully modulating spring return damper motor with plug-in connection.Manual model features parallel blade, gear-driven dampers with adjustable fixed position.Outdoor Air Hood is included when damper is factory installed and is furnished with damper when ordered for field installation.
O
ROOF CURBS
Nailer strip furnished, mates to unit, US National Roofing Contractors Approved, shipped knocked down.
DownflowClip Curbs - Uses interlocking tabs to fasten corners together. No tools required.Standard Curbs - Curb corners fasten together with furnished hardware.Adjustable Pitched Curb - Curbs are regionally sourced. Dimensions will vary based upon the source. Contact your Lennox sales representative for a detailed cut sheet with applicable dimensions.
HorizontalConverts unit from downflow to horizontal (side) air flow, return air is on unit, supply air is on curb, see dimension drawings. Curbs for rooftop applications meet National Roofing Code requirements. Requires Horizontal Return Air Panel Kit. Available in 26, 30, 37 and 41 inch heights. Optional Insulation Kit is available to help prevent sweating.
CEILING DIFFUSERS
Ceiling Diffusers (Flush or Step-Down)Aluminum grilles, large center grille, insulated diffuser box with flanges, hanging rings furnished, interior transition (even air flow), internally sealed (prevents recirculation), adapts to T-bar ceiling grids or plaster ceilings.Transitions (Supply and Return)Used with diffusers, installs in roof curb, galvanized steel construction, flanges furnished for duct connection to diffusers, fully insulated.
Landmark™ Packaged Electric / Electric 15 to 25 Ton / Page 8
OPTIONS / ACCESSORIES
Item Description Model Number
Catalog Number 180 210 240 300
COOLING SYSTEMCondensate Drain Trap PVC - C1TRAP20AD2 76W26 X X X X
Copper - C1TRAP10AD2 76W27 X X X XCorrosion Protection Factory O O O ODrain Pan Overflow Switch K1SNSR71C-1- 68W89 X X X XEfficiency Standard O O O OLow Ambient Kit K1SNSR33C-1 55W72 X X X XRefrigerant Type R-410A O O O OBLOWER - SUPPLY AIRMotors Belt Drive - 3 hp Factory O O
Belt Drive - 5 hp Factory O O O OBelt Drive - 7.5 hp Factory O O O OBelt Drive - 10 hp Factory O O
Drive KitsSee Blower Data Tables for usage and selection
Kit #1 535-725 rpm Factory O OKit #2 710-965 rpm Factory O OKit #3 685-856 rpm Factory O O O O
Kit #4 850-1045 rpm Factory O O O OKit #5 945-1185 rpm Factory O O O OKit #6 850-1045 rpm Factory O O O OKit #7 945-1185 rpm Factory O O O O
Kit #8 1045-1285 rpm Factory O O O OKit #10 1045-1285 rpm Factory O OKit #11 1135-1365 rpm Factory O O
CABINETCoil Guards C1GARD20C11 54W79 X X
C1GARD20C31 54W80 X XHail Guards C1GARD10C11 54W83 X X
C1GARD10C31 54W84 X XCONTROLSCommercial Controls L Connection® Building Automation System - - - X X X XSmoke Detector - Supply or Return (Power board and one sensor) C1SNSR44C-1 53W82 X X X XSmoke Detector - Supply and Return (Power board and two sensors) C1SNSR43C-1 53W83 X X X XINDOOR AIR QUALITYAir FiltersHealthy Climate® High Efficiency Air Filters24 x 24 x 2 (Order 6 per unit)
MERV 8 - C1FLTR15C-1- 54W67 X X X XMERV 13 - C1FLTR40C-1- 52W40 X X X X
Replacement Media Filter With Metal Mesh Frame (includes non-pleated filter media)
C1FLTR30C-1- 44N61 X X X X
Indoor Air Quality (CO2) SensorsSensor - Wall-mount, off-white plastic cover with LCD display C0SNSR50AE1L 77N39 X X X XSensor - Wall-mount, off-white plastic cover, no display C0SNSR52AE1L 87N53 X X X XSensor - Black plastic case with LCD display, rated for plenum mounting C0SNSR51AE1L 87N52 X X X XSensor - Wall-mount, black plastic case, no display, rated for plenum mounting
C0MISC19AE1 87N54 X X X X
CO2 Sensor Duct Mounting Kit - for downflow applications C0MISC19AE1- 85L43 X X X XAspiration Box - for duct mounting non-plenum rated CO2 sensors(87N53 or 77N39)
C0MISC16AE1- 90N43 X X X X
UVC Germicidal Light Kit1 Healthy Climate® UVC Light Kit (110/230v-1ph) C1UVCL10C-1 54W65 X X X X
1 Lamps operate on 110-230V single-phase power supply. Step-down transformer must be field supplied for field installation in 460V and 575V rooftop units (transformer is furnished for factory installed light kits). Alternately, a separate 110V power supply may be used to directly power the UVC ballast(s)
NOTE - Catalog and model numbers shown are for ordering field installed accessories. OX - Configure To Order (Factory Installed) or Field Installed O = Configure To Order (Factory Installed) X = Field Installed
Landmark™ Packaged Electric / Electric 15 to 25 Ton / Page 9
OPTIONS / ACCESSORIES
Item Description Model Number
Catalog Number 180 210 240 300
ELECTRICAL
Voltage 60 hz 208/230V - 3 phase Factory O O O O
460V - 3 phase Factory O O O O
575V - 3 phase Factory O O O O
Disconnect Switch (see Electric Heat Tables for usage, )
Barometric Relief Dampers with ExhaustHood LAGEDH18/24 16K99 X X X XNOTE - Catalog and model numbers shown are for ordering field installed accessories. OX - Configure To Order (Factory Installed) or Field Installed O = Configure To Order (Factory Installed) X = Field Installed
Landmark™ Packaged Electric / Electric 15 to 25 Ton / Page 10
OPTIONS / ACCESSORIES
Item Description Model Number
Catalog Number 180 210 240 300
OUTDOOR AIROutdoor Air DampersMotorized Dampers with Outdoor Air Hood K1DAMP20C-1 58W62 OX OX OX OXManual Dampers With Outdoor Air Hood C1DAMP10C-1 54W76 OX OX OX OXPOWER EXHAUSTStandard Static 208/230V - C1PWRE10C-1Y 54W70 X X X X
460V - C1PWRE10C-1G 54W71 X X X X575V - C1PWRE10C-1J 54W72 X X X X
ROOF CURBS - DOWNFLOWClip Curb8 in. height C1CURB40CD1 26W32 X X X X14 in. height LARMF18/30S-14 33K44 X X X X18 in. height LARMF18/30S-18 33K45 X X X X24 in. height LARMF18/30S-24 33K46 X X X XStandard14 in. height LARMF18/36-14 16K87 X X X X24 in. height LARMF18/36-24 16K88 X X X XAdjustable Pitched Curb14 in. height L1CURB55C 43W26 X X X XROOF CURBS - HORIZONTAL (REQUIRES HORIZONTAL RETURN AIR PANEL KIT)Standard26 in. height - slab applications LARMFH18/24-26 97J33 X X X37 in. height - rooftop applications LARMFH18/24-37 38K53 X X X30 in. height - slab applications LARMFH30/36-30 33K79 X41 in. height - rooftop applications LARMFH30/36-41 38K54 XInsulation Kit For Standard Horizontal Curbsfor LARMFH18/24-26 C1INSU11C-1- 73K32 X X Xfor LARMFH18/24-37 C1INSU13C-1- 73K34 X X Xfor LARMFH30/36-30 C1INSU12C-1- 73K33 Xfor LARMFH30/36-41 C1INSU14C-1- 73K35 XHorizontal Return Air Panel KitRequired for Horizontal Applications with Roof Curb C1HRAP10C-1- 87M00 X X X XCEILING DIFFUSERSStep-Down - Order one RTD11-185 29G06 X
RTD11-275-R 29G07 X X XRTD11-150/180S (Canada only) 13K63 X
RTD11-275S (Canada only) 13K64 X X XFlush - Order one FD11-185 29G10 X
FD11-275-R 29G11 X X XFD11-150/180S (Canada only) 13K58 X
FD11-275S (Canada only) 13K59 X X XTransitions (Supply and Return) - Order one LASRT18 19K01 X
LASRT21/24 19K02 X X XLASRT18S (Canada only) 33K48 X
LASRT21/24S (Canada only) 33K49 X X XNOTE - Catalog and model numbers shown are for ordering field installed accessories. OX - Configure To Order (Factory Installed) or Field Installed O = Configure To Order (Factory Installed) X = Field Installed
Landmark™ Packaged Electric / Electric 15 to 25 Ton / Page 11
SPECIFICATIONSGeneral Data Nominal Tonnage 15 Ton 17.5 Ton 20 Ton 25 Ton
Model Number KCA180S4B KCA210S4B KCA240S4B KCA300S4BEfficiency Type Standard Standard Standard Standard
Filters Type of filter Fiberglass, disposableNumber and size - in. (6) 24 x 24 x 2
Electrical characteristics 208/230V, 460V or 575V - 60 hertz - 3 phaseNOTE - Net capacity includes evaporator blower motor heat deduction. Gross capacity does not include evaporator blower motor heat deduction. 1 Certified in accordance with the ULE certification program, which is based on AHRI Standard 340/360; 95°F outdoor air temperature and 80°F db/67°F wb entering evaporator air; minimum external duct static pressure. 2 Integrated Energy Efficiency Ratio certified and tested according to AHRI Standard 340/360.3 Using total air volume and system static pressure requirements determine from blower performance tables rpm and motor output required. Maximum usable output of motors furnished are shown. In Canada, nominal motor output is also maximum usable motor output. If motors of comparable output are used, be sure to keep within the service factor limitations outlined on the motor nameplate.
Landmark™ Packaged Electric / Electric 15 to 25 Ton / Page 12
RATINGSNOTE - For Temperatures and Capacities not shown in tables, see bulletin - Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.
17.5 TON STANDARD EFFICIENCY KCA210S4 (1ST STAGE)
Entering Wet Bulb
Temper-ature
Total Air
Volume
Outdoor Air Temperature Entering Outdoor Coil65°F 75°F 85°F 95°F
Landmark™ Packaged Electric / Electric 15 to 25 Ton / Page 13
RATINGSNOTE - For Temperatures and Capacities not shown in tables, see bulletin - Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.
25 TON STANDARD EFFICIENCY KCA300S4 (1ST STAGE)
Entering Wet Bulb
Temper-ature
Total Air
Volume
Outdoor Air Temperature Entering Outdoor Coil65°F 75°F 85°F 95°F
Landmark™ Packaged Electric / Electric 15 to 25 Ton / Page 14
BLOWER DATA
BLOWER TABLE INCLUDES RESISTANCE FOR BASE UNIT ONLY WITH DRY INDOOR COIL & AIR FILTERS IN PLACE FOR ALL UNITS ADD:
1 - Wet indoor coil air resistance of selected unit. 2 - Any factory installed options air resistance (heat section, economizer, etc.) 3 - Any field installed accessories air resistance (duct resistance, diffuser, etc.)
Then determine from blower table blower motor output and drive required. See page 15 for wet coil and option/accessory air resistance data. See page 15 for factory installed drive kit specifications.MINIMUM AIR VOLUME REQUIRED FOR USE WITH OPTIONAL ELECTRIC HEAT
All units require 6000 cfm minimum air with electric heat.
NOTE - Using total air volume and system static pressure requirements determine from blower performance tables rpm and motor output required. Maximum usable output of motors furnished are shown. In Canada, nominal motor output is also maximum usable motor output. If motors of comparable output are used, be sure to keep within the service factor limitations outlined on the motor nameplate.
Landmark™ Packaged Electric / Electric 15 to 25 Ton / Page 16
BLOWER DATA
POWER EXHAUST FAN PERFORMANCE Return Air System Static Pressure Air Volume Exhausted
1 Throw is the horizontal or vertical distance an airstream travels on leaving the outletor diffuser before the maximum velocity is reduced to 50 ft. per minute. Four sides open.
1 Extremes of operating range are plus and minus 10% of line voltage.2 HACR type breaker or fuse.3 Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
Landmark™ Packaged Electric / Electric 15 to 25 Ton / Page 18
ELECTRICAL/ELECTRIC HEAT DATA 17.5 TON17.5 TON STANDARD EFFICIENCY KCA210S41 Voltage - 60hz 208/230V - 3 Ph 460V - 3 Ph 575V - 3 PhCompressor 1 Rated Load Amps 19 9.7 7.4
1 Extremes of operating range are plus and minus 10% of line voltage.2 HACR type breaker or fuse.3 Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.4 Disconnect must be field furnished.
Landmark™ Packaged Electric / Electric 15 to 25 Ton / Page 19
ELECTRICAL/ELECTRIC HEAT DATA 20 TON20 TON STANDARD EFFICIENCY KCA240S41 Voltage - 60hz 208/230V - 3 Ph 460V - 3 Ph 575V - 3 PhCompressor 1 Rated Load Amps 22.4 10.6 7.7
1 Extremes of operating range are plus and minus 10% of line voltage.2 HACR type breaker or fuse.3 Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.4 Disconnect must be field furnished.
Landmark™ Packaged Electric / Electric 15 to 25 Ton / Page 20
ELECTRICAL/ELECTRIC HEAT DATA 25 TON25 TON STANDARD EFFICIENCY KCA300S41 Voltage - 60hz 208/230V - 3 Ph 460V - 3 Ph 575V - 3 PhCompressor 1 Rated Load Amps 25 12.2 9
1 Extremes of operating range are plus and minus 10% of line voltage.2 HACR type breaker or fuse.3 Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.4 Disconnect must be field furnished.
Landmark™ Packaged Electric / Electric 15 to 25 Ton / Page 21
UNIT CLEARANCES - INCHES (MM)
1 Unit ClearanceA B C D Top
Clearancein. mm in. mm in. mm in. mmService Clearance 60 1524 36 914 36 914 66 1676
UnobstructedMinimum Operation Clearance 45 1143 36 914 36 914 41 1041NOTE - Entire perimeter of unit base requires support when elevated above the mounting surface.1 Service Clearance - Required for removal of serviceable parts. Minimum Operation Clearance - Required clearance for proper unit operation.
1 Remote sensors for C0STAT02AE1L can be applied in the following combinations: (1) C0SNZN01AE1-, (2) C0SNZN73AE1-, (2) C0SNZN01AE1- and (1) C0SNZN73AE1-, (4) C0SNZN01AE1-, (3) C0SNZN01AE1- and (2) C0SNZN73AE1.
DIGITAL NON-PROGRAMMABLE THERMOSTATSIntuitive Interface - Automatic Changeover - Simple Up and Down Temperature ControlTwo-stage heating / cooling conventional systems ....................................... C0STAT10AE1L
(13K98)Sensor For Digital Non-Programmable Thermostats AboveRemote wall mounted temperature sensor....................................................... C0SNZN00AE1-
(26K57)Intuitive Interface - Automatic Changeover - Backlit Display - Simple Up and Down Temperature ControlOne-stage heating / cooling conventional systems .......................................... C0STAT12AE1L
(51M32)Sensor For Digital Non-Programmable Thermostats AboveOutdoor temperature sensor ............................................................................ C0SNSR04AE1-
(X2658)Accessories For Digital Non-Programmable Thermostats AboveOptional wall mounting plate ............................................................................ C0MISC17AE1-
(X2659)
OUTDOOR SOUND DATA
Unit Model Number
Octave Band Sound Power Levels dBA, re 10-12 Watts Center Frequency - HZ 1 Sound RatingNumber (dB)125 250 500 1000 2000 4000 8000
180, 210 71 78 81 81 76 71 63 86
240, 300 80 83 87 88 84 80 71 93
Note - The octave sound power data does not include tonal corrections. 1 Sound Rating Number according to AHRI Standard 370-2001.
Landmark™ Packaged Electric / Electric 15 to 25 Ton / Page 23
WEIGHT DATA
Model Number Net Shippinglbs. kg lbs. kg
180 Base Unit 1705 773 1905 864180 Max. Unit 2025 919 2225 1009210 Base Unit 1850 839 2050 930210 Max. Unit 2180 989 2380 1080240 Base Unit 2120 962 2320 1052240 Max. Unit 2450 1111 2650 1202300 Base Unit 2120 962 2320 1052300 Max. Unit 2450 1111 2650 1202
OPTIONS / ACCESSORIES
Description Shipping Weightlbs. kg
CEILING DIFFUSERSStep-Down
RTD11-185 392 178RTD11-275 403 183
FlushFD11-185 289 131FD11-275 363 165
Transitions LASRT18 80 36
LASRT21/24 75 34ECONOMIZER / OUTDOOR AIR / EXHAUSTEconomizerEconomizer Dampers K1ECON20C-1 86 39Barometric Relief Dampers (downflow) C1DAMP50C 30 14Barometric Relief Dampers (horizontal) LAGEDH18/24 20 9Outdoor Air DampersOutdoor Air Damper Section (downflow) - Automatic E1DAMP20C-1 52 24Outdoor Air Damper Section (downflow) - Manual C1DAMP10C-1 49 22Outdoor Air Damper Hood (downflow) 65 29Power Exhaust 62 28ELECTRIC HEAT15 kW 59 2730 kW 59 2745 kW 76 3460 kW 76 3490 kW 84 38ROOF CURBS - CLIP CURBDownflow8 in. height C1CURB40CD1 132 6014 in. height LARMF18/30S-14 164 7418 in. height LARMF18/30S-18 187 8524 in. height LARMF18/30S-24 222 101Horizontal26 in. height LARMFH18/24S-26 335 15237 in. height LARMFH18/24S-37 445 20230 in. height LARMFH30/36S-30 456 20741 in. height LARMFH30/36S-41 480 218ROOF CURBS - STANDARDDownflow14 in. height LARMF18/36-14 160 7324 in. height LARMF18/36-24 220 100Horizontal26 in. height LARMFH18/24-26 420 19137 in. height LARMFH18/24-37 580 26330 in. height LARMFH30/36-30 445 20241 in. height LARMFH30/36-41 725 329PACKAGINGLTL Packaging (less than truck load) 310 141
Landmark™ Packaged Electric / Electric 15 to 25 Ton / Page 24
DIMENSIONS - INCHES (MM) KCA180, KCA210CORNER WEIGHTS CENTER OF GRAVITY
Model No. AA BB CC DD EE FFlbs. kg lbs. kg lbs. kg lbs. kg in. mm in. mm
KCA180 Std. Unit 427 201 387 183 495 234 546 258 51-1/4 1302 40 1016KCA180 Max. Unit 550 259 467 220 534 252 629 297 49-1/2 1257 42-1/2 1080KCA210 Std. Unit 454 214 408 192 539 254 600 283 51 1295 39-1/4 997KCA210 Max. Unit 578 273 487 230 576 272 684 323 49-1/4 1251 41-3/4 1060Std. Unit - The unit with NO OPTIONS. Max. Unit - The unit with ALL OPTIONS Installed. (Economizer, etc.)
4(102)
4-1/4 (108)
BOTTOM POWER ENTRY5 X 8 inches (127 X 203 mm)
BOTTOM SUPPLYAIR OPENINGS
BOTTOM RETURNAIR OPENING
28(711)
28(711)
4(102)
12-3/8(314)
12-3/8(314)
20 (508) 20 (508)
15 (381)60-1/2 (1537)
AA BB
CCDD
CENTER OFGRAVITY
EE
FF
TOP VIEW
4-1/2(114)
SIDE VIEW
FORKLIFT SLOTS(Front and Left Side Only)
LIFTING HOLES(For Rigging
Front and Back) 107-3/4 (2737)BASE
106-1/2(2705)
END VIEW
90-1/8(2289)
28-3/4(730)
CONDENSATEDRAIN
5-3/8(137)
3-1/4(83)
54-1/4(1378)
51(1295)
91-1/8 (2315)BASE
SIDE ELECTRICALINLETS
ALTERNATE (THRU THE BASE)CONDENSATE DRAIN LOCATION
1-5/8 in. (41 mm) Diameter
18 (457)
28-3/8(721)
5-5/8 (143)
Landmark™ Packaged Electric / Electric 15 to 25 Ton / Page 25
SIDE VIEW
FORKLIFT SLOTS(Front and Left Side Only)
132-5/8(3369)
LIFTING HOLES(For Rigging
Front and Back)25-3/8(645)
107-3/4 (2737)BASE
BOTTOM POWER ENTRY5 X 8 inches (127 X 203 mm)
BOTTOM SUPPLYAIR OPENINGS
BOTTOM RETURNAIR OPENING
28(711)
28(711)
20 (508)
15 (381)60-1/2 (1537)
AA BB
CCDD
CENTER OFGRAVITY
EE
FF
TOP VIEW
4-1/2(114)
20 (508)
4(102)
4-1/4 (108)
4(102)
12-3/8(314)
12-3/8(314)
END VIEW
90-1/8(2289)
28-3/4(730)
CONDENSATEDRAIN
5-3/8(137)
3-1/4(83)
54-1/4(1378)
51(1295)
91-1/8 (2315)BASE
SIDE ELECTRICALINLETS
ALTERNATE (THRU THE BASE)CONDENSATE DRAIN LOCATION
1-5/8 in. (41 mm) Diameter
18 (457)
28-3/8(721)
5-5/8 (143)
DIMENSIONS - INCHES (MM) KCA240, KCA300CORNER WEIGHTS CENTER OF GRAVITY
Model No. AA BB CC DD EE FFlbs. kg lbs. kg lbs. kg lbs. kg in. mm in. mm
KCA240 Std. Unit 462 218 472 223 676 319 660 312 54-1/2 1384 37-1/2 953KCA240 Max. Unit 577 272 548 259 716 338 754 356 52-1/2 1334 39-1/2 1003KCA300 Std. Unit 462 218 472 223 676 319 660 312 54-1/2 1384 37-1/2 953KCA300 Max. Unit 577 272 548 259 716 338 754 356 52-1/2 1334 39-1/2 1003Std. Unit - The unit with NO OPTIONS. Max. Unit - The unit with ALL OPTIONS Installed. (Economizer, etc.)
Landmark™ Packaged Electric / Electric 15 to 25 Ton / Page 26
ACCESSORY DIMENSIONS - INCHES (MM)
16(406)
FRONT VIEW SIDE VIEW
31−5/8 (803)
14-1/2(368)
1 13(330)
6-1/2(165)1 29−1/2 (749)
NOTE − Two furnished per order no. 1 NOTE − Opening size required in return air duct.
HORIZONTAL BAROMETRIC RELIEF DAMPERS(Field installed in horizontal return air duct adjacent to unit)
1 OPTIONALSTANDARD STATICPOWER EXHAUST
FANS HOOD(Field Installed)
OPTIONAL OUTDOOR AIR HOOD DETAILWITH STANDARD STATIC POWER EXHAUST FANS
OPTIONALOUTDOOR AIR HOOD
(Field Installed)Required with Economizer
or Outdoor Air Damper
1 Field Installed in Return Air Duct for Horizontal Applications.
Landmark™ Packaged Electric / Electric 15 to 25 Ton / Page 27
ACCESSORY DIMENSIONS - INCHES (MM)
CLIP CURB − DOUBLE DUCT OPENING
TYPICAL FLASHING DETAIL FOR ROOF CURB
ROOF CURB(Extends around entire
perimeter of unit)
FIBERGLASSINSULATION
(Furnished)COUNTER FLASHING(Field Supplied)
BASE BOTTOM
RIGID INSULATION(Field Supplied)
ROOFINGMATERIAL
CANT STRIP(Field Supplied)
PACKAGEDUNIT
NAILER STRIP(Furnished)
8−1/4(210)
8−1/4(210)
8 (203)14 (356)18 (457)24 (610)
61-1/2(1562)
CURBRETURN AIR
OPENING
61-1/2(1562)
81-1/2(2070)
17 (432)
21 (533)
16 (406)
86−1/4(2191)
82−5/8(2099)
1−13/16(46)
102-1/8(2594)
98-1/2(2502)
1−13/16(46)
DETAIL ROOF CURB
8 (203)14 (356)18 (457)24 (610)
FACTORY INSTALLEDPERIMETER WOODNAILER STRIP
1−13/16(46)
1−13/16(46)
1/2 (13)
CURBSUPPLY AIR
OPENING
Landmark™ Packaged Electric / Electric 15 to 25 Ton / Page 28
ACCESSORY DIMENSIONS - INCHES (MM)
STANDARD ROOF CURBS − DOUBLE DUCT OPENING
TYPICAL FLASHING DETAIL FOR ROOF CURB
ROOF CURB(Extends around entire
perimeter of unit)
FIBERGLASSINSULATION
(Furnished)COUNTER FLASHING(Field Supplied)
BASE BOTTOM
RIGID INSULATION(Field Supplied)
ROOFINGMATERIAL
CANT STRIP(Field Supplied)
PACKAGEDUNIT
NAILER STRIP(Furnished)
CURBSUPPLY AIR
OPENING
8−1/4(210)
1−13/16(46)
DETAIL ROOF CURB
14 (356)24 (610)
1 (25)
FACTORY INSTALLEDPERIMETER WOODNAILER STRIP
2 (51)
8−1/4(210)
17 (432)
21 (533)
16 (406)
102-1/8(2594)
61-1/2(1562)
98-1/2(2502)
86-1/4(2191)
82-5/8(2099)
3/4 (19) Typ.
14 (356)or24 (610)
CURBRETURN AIR
OPENING
1−13/16(46)
61-1/2(1562)
1−13/16(46)
Landmark™ Packaged Electric / Electric 15 to 25 Ton / Page 29
ACCESSORY DIMENSIONS - INCHES (MM)
ROOF CURBS WITH SUPPLY & RETURN AIR TRANSITIONS FOR CEILING DIFFUSERS
LASRT SUPPLY TRANSITION
LASRT RETURN TRANSITION
RETURN AIROPENING
SUPPLY AIROPENINGS
TOP VIEW
54(1372)
69-1/4 (1759)
3/4(19) Typ.
4-1/2(114)
SUPPORTANGLE
(Furnished withTransitions)
B
A
B
69-1/4(1759)
2(51)
8 (203)
26-1/2(673)
1-1/2(38) Typ.
TRANSITION DETAIL
A
AB
TRANSITION OPENING SIZES
Model A BModelNumber inch mm inch mmLASRT18 18 457 36 914
LASRT21/24 24 610 48 1219
Landmark™ Packaged Electric / Electric 15 to 25 Ton / Page 30
HORIZONTAL SUPPLY AND RETURN AIR OPENINGSWITH HORIZONTAL ROOF CURB
1 LARMFH18/24-26 2 LARMFH18/24-373 LARMFH30/36-30 (used with 300S Models Only)4 LARMFH30/36-41 (used with 300S Models Only)
1 LARMFH18/24-26 2 LARMFH18/24-37 3 LARMFH30/36-30 (used with 300S) 4 LARMFH30/36-41 (used with 300S)
NOTE LARMFH18/24-26 and LARMFH30/36-30are designed for horizontal dischargewhen unit is mounted on a slab.LARMFH18/24-37 and LARMFH30/36-41are designed for horizontal dischargewhen unit is mounted on a rooftop.
N(T
1,2 14 (356)3,4 18 (457)
102-1/2 (2604)
CURB SUPPLYAIR OPENING
With 1-1/2 in. (38 mm) FLANGE
75(1905)
5-1/2 (140)
102-1/8 (2594)
1,2 8-1/4 (210)3,4 13-1/4 (337)
1,3 6-1/2 (165)2,4 17-1/2 (445)
1 26 (660)2 37 (940)3 30 (762)4 41 (1041)
FRONT VIEW
Landmark™ Packaged Electric / Electric 15 to 25 Ton / Page 31
ACCESSORY DIMENSIONS - INCHES (MM)
COMBINATION CEILING SUPPLY AND RETURN DIFFUSERSRESUFFID GNILIEC HSULFRESUFFID GNILIEC NWOD-PETS
L
A
C
HJG
FE
B
M
N
K
DG
2 (51)
A
C
HJG
FE
B
K
DG
2 (51)
Model Number RTD11-185 RTD11-275A in. 47-5/8 59-5/8