Green Transformer for Data CentreJeff Ong, Data Center Solutions Day, 5 July 2013

Absolutely!

Page 2: Jeff Ong, Data Center Solutions Day, 5 July 2013 Green ... · PDF fileGreen Transformer for Data Centre Jeff Ong, Data Center Solutions Day, 5 July 2013 Absolutely! ... Askarel oils

Power Network OverviewTransformer in every data center? YES!!!

Transformers

Page 3: Jeff Ong, Data Center Solutions Day, 5 July 2013 Green ... · PDF fileGreen Transformer for Data Centre Jeff Ong, Data Center Solutions Day, 5 July 2013 Absolutely! ... Askarel oils

Base materials

Environment

Encouragement(CustomerBenefits)

ABB ApproachCreating right recipe for green transformer

Page 4: Jeff Ong, Data Center Solutions Day, 5 July 2013 Green ... · PDF fileGreen Transformer for Data Centre Jeff Ong, Data Center Solutions Day, 5 July 2013 Absolutely! ... Askarel oils

Dielectric insulating fluidsHistory

In 1890, five yearsafter the invention oftransformers, BrownBoveri & Cie wasthe first one to usemineral-based oil asa transformerinsulating andcooling media

Mineral-based dielectric insulating fluids havebeen in use in transformers since the late1800’s

Today’s escalation in power demand pushesan often aging network to its limit

In that situation, mineral-based dielectricinsulating fluids have shown costly limitations

Two Major Issues

Environmental unfriendliness

Combustibility

Page 5: Jeff Ong, Data Center Solutions Day, 5 July 2013 Green ... · PDF fileGreen Transformer for Data Centre Jeff Ong, Data Center Solutions Day, 5 July 2013 Absolutely! ... Askarel oils

Dielectric insulating fluidsAlternative fluids overview

Several past alternatives

Askarel oils (PCBs) – Fire resistant but toxic

Silicone oils and high temperature hydrocarbons(HTHs) – Fire resistant but low biodegradability

• Ester-based fluids - New alternative combining high biodegradability with excellent fire safetyproperties

• Esters are a broad class of organic compounds from organic precursors (synthetic esters)or available from agricultural products (natural esters), as BIOTEMP ©

• While synthetic esters high cost currently limits their use to specialty applications, naturalesters have lately matured into suitable and affordable dielectric insulating fluids

BIOTEMP was putin the firsttransformer unitsusing a naturalester-based fluidinto the field in 1999

Page 6: Jeff Ong, Data Center Solutions Day, 5 July 2013 Green ... · PDF fileGreen Transformer for Data Centre Jeff Ong, Data Center Solutions Day, 5 July 2013 Absolutely! ... Askarel oils

Natural ester-based dielectric insulating fluidsToday’s market trend

Natural esters are now recognized asenvironmentally friendly and “less flammable”dielectric insulating fluids by the industry

Classified non hazardous to water (NWG) bythe German Federal Environment Agency(Umweltbundesamt)

Verified by the US Environmental ProtectionAgency (EPA)

Meet the US National Electrical Code

Listed by Factory Mutual (FM Global) andUnderwriters Laboratories (UL)

Specified by Industry Standards ASTM D6871and IEEE C57.147 published since 2003 and2008 respectively

Page 7: Jeff Ong, Data Center Solutions Day, 5 July 2013 Green ... · PDF fileGreen Transformer for Data Centre Jeff Ong, Data Center Solutions Day, 5 July 2013 Absolutely! ... Askarel oils

BIOTEMP™ – ABB sensible solutionPreserving the environment

BIOTEMP is a natural ester-based dielectricinsulating fluid made out of sunflower seeds

Readily biodegradable, non toxic¹

Much larger oil volume allowed beforecontainment is required

Spills can be disposed through normalmeans³

Potential for relief from environmentalregulatory penalties

Minimized air pollution

Near neutral carbon footprint due to thenegative carbon footprint of a vegetable-based oil production

¹ Verified by the USEnvironmentalProtection Agencyand classified nonhazardous to waterby the GermanFederalEnvironmentAgency

² According to FMGlobal property losspreventiondatasheet fortransformers

³ Applicable locallaws andregulations willdetermine what isexactly required

Page 8: Jeff Ong, Data Center Solutions Day, 5 July 2013 Green ... · PDF fileGreen Transformer for Data Centre Jeff Ong, Data Center Solutions Day, 5 July 2013 Absolutely! ... Askarel oils

BIOTEMP™ – ABB sensible solutionBiodegradability

Listed as biodegradable and non-toxic dielectric insulating fluid by the US FederalEnvironmental Protection Agency (EPA)

Page 9: Jeff Ong, Data Center Solutions Day, 5 July 2013 Green ... · PDF fileGreen Transformer for Data Centre Jeff Ong, Data Center Solutions Day, 5 July 2013 Absolutely! ... Askarel oils

BIOTEMP® – ABB sensible solutionSGBC product certification

Page 10: Jeff Ong, Data Center Solutions Day, 5 July 2013 Green ... · PDF fileGreen Transformer for Data Centre Jeff Ong, Data Center Solutions Day, 5 July 2013 Absolutely! ... Askarel oils

BIOTEMP™ – ABB sensible solutionPreserving life and property

BIOTEMP has a flash and fire point of 340°Cand 360°C, respectively (vs. 160°C and180°C typically for mineral oil)Listed as a “less flammable” dielectric fluidby FM Global and Underwriters LaboratoriesTested in strict accordance with IEC standard61100 and meet the K2 classification

Eliminate active fire suppression and barrier walls

Meet fire safety requirements for indoor applications and outdoor areas of highsafety sensitivity without additional safety equipment

Reduce risk of transformer explosion and fire. hence mitigating collateraldamage and potentially lowering insurance premiums

¹ According to FMGlobal property losspreventiondatasheet fortransformers

Page 11: Jeff Ong, Data Center Solutions Day, 5 July 2013 Green ... · PDF fileGreen Transformer for Data Centre Jeff Ong, Data Center Solutions Day, 5 July 2013 Absolutely! ... Askarel oils

BIOTEMP™ – ABB sensible solutionPreserving life and property

Mineral oil

BIOTEMP

Note – Picturesshown here are notdirectly taken fromthe heat release testderived from ASTME1354, but are forillustration purposesonly

(derived from ASTM E1354)

Mineral oil BIOTEMP

Time to ignition (s) 57 723

Time to flameout (s) 1160 731

Smoke production rate (m2/s) 0.0495 0.0014

¹ The time to ignition,obtained from acone calorimetertest, is a strongindicator of amaterial’s fireresistance. Thelonger it takes for asample to ignite themore resistant thematerial is toburning

Time to ignition for BIOTEMP:- about 12 times longer than that of mineral

oil

Smoke production from BIOTEMP:-31 times less than that of the mineral oil

Page 12: Jeff Ong, Data Center Solutions Day, 5 July 2013 Green ... · PDF fileGreen Transformer for Data Centre Jeff Ong, Data Center Solutions Day, 5 July 2013 Absolutely! ... Askarel oils

BIOTEMP™ – ABB sensible solutionPreserving life and property

High energy arc fault test with mineral oil8000 A for up to 3 cycles (~106 Joule)Tank cover blew off with huge fire ball

High energy arc fault test with BIOTEMP8000 A for up to 3 cycles (~106 Joule)Tank cover vented only

Mineral oil

Page 13: Jeff Ong, Data Center Solutions Day, 5 July 2013 Green ... · PDF fileGreen Transformer for Data Centre Jeff Ong, Data Center Solutions Day, 5 July 2013 Absolutely! ... Askarel oils

BIOTEMP™ – ABB sensible solutionLess Flammable Fluids

BIOTEMP >340 >360 K2

Page 14: Jeff Ong, Data Center Solutions Day, 5 July 2013 Green ... · PDF fileGreen Transformer for Data Centre Jeff Ong, Data Center Solutions Day, 5 July 2013 Absolutely! ... Askarel oils

BIOTEMP™ – ABB sensible solutionEnhancing performance

BIOTEMP has a much higher water saturation limit than mineral oil at alltemperatures

BIOTEMP has a much greater affinity for water than mineral oil

Page 15: Jeff Ong, Data Center Solutions Day, 5 July 2013 Green ... · PDF fileGreen Transformer for Data Centre Jeff Ong, Data Center Solutions Day, 5 July 2013 Absolutely! ... Askarel oils

BIOTEMP™ – ABB sensible solutionEnhancing performance

The effect of moisture on the dielectric breakdown strength ofBIOTEMP is much less pronounced than for mineral oil

The allowable limit of moisture in BIOTEMP can be muchhigher than that allowed for mineral oil

¹ The acceptable limitaccording to ASTMD6871 is 30 kV min

Page 16: Jeff Ong, Data Center Solutions Day, 5 July 2013 Green ... · PDF fileGreen Transformer for Data Centre Jeff Ong, Data Center Solutions Day, 5 July 2013 Absolutely! ... Askarel oils

BIOTEMP™ – ABB sensible solutionEnhancing performance

• BIOTEMP-impregnated paper experiences much lower aging ratecompared to mineral oil-impregnated paper, increasing by a factor of 2 theinsulation system life

• BIOTEMP®-impregnated paper can alternatively operate at 8-10°C higherhotspot temperatures and attain the same life expectancy as mineral oil-impregnated paper

Page 17: Jeff Ong, Data Center Solutions Day, 5 July 2013 Green ... · PDF fileGreen Transformer for Data Centre Jeff Ong, Data Center Solutions Day, 5 July 2013 Absolutely! ... Askarel oils

BIOTEMP™ – ABB sensible solutionPaper condition after aging

Accelerated Aging Test@ 150ºC

Page 18: Jeff Ong, Data Center Solutions Day, 5 July 2013 Green ... · PDF fileGreen Transformer for Data Centre Jeff Ong, Data Center Solutions Day, 5 July 2013 Absolutely! ... Askarel oils

BIOTEMP® – ABB sensible solutionA proven solution

Over 3,500 transformers (up to 56 MVA and 145 kV) sold or retrofilled withBIOTEMP since 1999

AustraliaBrazilCanadaChinaColombiaCosta RicaEcuadorEgyptFranceHungaryItalyJapanMongoliaNorwaySingaporeSpainSwedenTaiwanUnited StatesVietnam

Page 19: Jeff Ong, Data Center Solutions Day, 5 July 2013 Green ... · PDF fileGreen Transformer for Data Centre Jeff Ong, Data Center Solutions Day, 5 July 2013 Absolutely! ... Askarel oils

BIOTEMP® – ABB sensible solutionReference list

Name of Project Qty & Rating

Woodland Data Centre 16 x 2,500kVA

Mediapolis2 x 500kVA1 x 1,000kVA2 x 2,500kVA

One North @ North Bouna Vista Dr 4 x 2,500kVA4 x 3,000kVA

Capitol Development Project4 x 1,500kVA3 x 2,000kVA2 x 2,500kVA

A&A works & New Blks of 5 Sty Teaching Facilities Bldg@ Temasek Poly

2 x 1,000kVA2 x 2,000kVA

Extension to TaTa Bldg @ Tai Seng Dr 2 x 3,000kVA2 x 4,000kVA

Page 20: Jeff Ong, Data Center Solutions Day, 5 July 2013 Green ... · PDF fileGreen Transformer for Data Centre Jeff Ong, Data Center Solutions Day, 5 July 2013 Absolutely! ... Askarel oils

BIOTEMP® – ABB sensible solutionReference list

Name of Project Qty & Rating

Red Dot @ Rolls Royce 4 x 1,500kVA4 x 2,000kVA

Farrer Mediplex Hospital Development @Farrer Park Station 8 x 2,500kVA

Cleantech One @ Nanyang Ave 6 x 2,000kVA

Replacement of Transformers @ PLAB 2 x 1,500kVA

New Substation 8 @ Ext'g S'pore Expo 2 x 1,500kVA

27 Sty Carlton Hotel @ Tanjong Pagar 2 x 3,000kVA

Page 21: Jeff Ong, Data Center Solutions Day, 5 July 2013 Green ... · PDF fileGreen Transformer for Data Centre Jeff Ong, Data Center Solutions Day, 5 July 2013 Absolutely! ... Askarel oils

BIOTEMP® – ABB sensible solutionCustomer benefits

Environmental – BIOTEMP® is 99% biodegradableHow much a major mineral oil spill clean up would cost you?How much would it cost you in revenue lost per day if you are not allowed tooperate one of your substations for environmental reasons?

Safety – BIOTEMP® has a 360°C fire pointHow much would you save in maintenance and rehabilitation costs if you didnot need a deluge system and/or fire barriers?How much would you lower your insurance premium by reducing the risk ofexplosion and fire?

Overload capacity – BIOTEMP® allows higher hotspotWhat would be the value to you of a 10% inherent increase in capacity oftransformer loading?What would happen to your capital budget if you gained 70% longer timesfor planned loading beyond nameplate?

Page 22: Jeff Ong, Data Center Solutions Day, 5 July 2013 Green ... · PDF fileGreen Transformer for Data Centre Jeff Ong, Data Center Solutions Day, 5 July 2013 Absolutely! ... Askarel oils

BIOTEMP® – ABB sensible solutionEcological benefits

Renewable sources:BIOTEMP® is completely derived from vegetable seed oil and is100% renewable

Non genetically modified organism:BIOTEMP® is made out of 100% natural High Oleic Sunflowergrowing mainly in Europe and in North America

Biodegradability:BIOTEMP® is 99% biodegradable

Non-toxic waste:BIOTEMP® is non-toxic so spills can often be disposed throughnormal means and not treated as hazardous waste

Low carbon-footprint:Near neutral carbon footprint due to the negative carbonfootprint of a vegetable-based oil production

Page 23: Jeff Ong, Data Center Solutions Day, 5 July 2013 Green ... · PDF fileGreen Transformer for Data Centre Jeff Ong, Data Center Solutions Day, 5 July 2013 Absolutely! ... Askarel oils

BIOTEMP® – ABB sensible solutionEconomical benefits

Reduced or delayed investments:Cellulose insulation lasts approximately two times as long in BIOTEMP® thanin mineral oil.

Reduced maintenance costs:Because of the “less-flammable” designation of BIOTEMP®, certaininstallations do not require fire-suppression systems or fire barriers. Thisprovides savings in installation and maintenance of such systems

Higher revenues (Overloadability – operational flexibility):Ability to overload BIOTEMP®-filled transformers could mean higherrevenues during peak demand periods without sacrificing transformer life

Reduced risk of environmental fines:Applicable laws and regulations will determine how fines are imposed.However, with 99% biodegradability and non-toxicity, BIOTEMP®

spills can often be disposed through normal means.

Page 24: Jeff Ong, Data Center Solutions Day, 5 July 2013 Green ... · PDF fileGreen Transformer for Data Centre Jeff Ong, Data Center Solutions Day, 5 July 2013 Absolutely! ... Askarel oils