Page 1: International Building Code Sections – 713.2 through 713.3.3 Section 716.6.63.

International Building International Building CodeCode

Sections – 713.2 through Sections – 713.2 through 713.3.3713.3.3

Section 716.6.63Section 716.6.63

Page 2: International Building Code Sections – 713.2 through 713.3.3 Section 716.6.63.

713.2 Installation details. Where sleeves are used, they shallbe securely fastened to the assembly penetrated. The spacebetween the item contained in the sleeve and the sleeve itselfand any space between the sleeve and the assembly penetratedshall be protected in accordance with this section. Insulationand coverings on or in the penetrating item shall not penetratethe assembly unless the specific material used has been testedas part of the assembly in accordance with this section.

Page 3: International Building Code Sections – 713.2 through 713.3.3 Section 716.6.63.

713.3.1.1 Fire-resistance-rated assemblies. Penetrationsshall be installed as tested in an approvedfire-resistance-rated assembly.713.3.1.2 Through-penetration firestop system.Through penetrations shall be protected by an approvedpenetration firestop system installed as tested in accordancewith ASTM E 814 or UL 1479, with a minimumpositive pressure differential of 0.01 inch (2.49 Pa) ofwater and shall have an F rating of not less than therequired fire-resistance rating of the wall penetrated.

Page 4: International Building Code Sections – 713.2 through 713.3.3 Section 716.6.63.

716.6.3 Nonfire-resistance-rated floor assemblies. Ductsystems constructed of approved materials in accordancewith the International Mechanical Code that penetratenonfire-resistance-rated floor assemblies shall be protectedby any of the following methods:

1. A shaft enclosure in accordance with Section 708.2. The duct connects not more than two stories, and theannular space around the penetrating duct is protectedwith an approvednoncombustible material thatresists the free passage of flame and the products ofcombustion.3. The duct connects not more than three stories, and theannular space around the penetrating duct is protectedwith an approvednoncombustible material thatresists the free passage of flame and the products ofcombustion and a fire damperis installed at each floorline.

Page 5: International Building Code Sections – 713.2 through 713.3.3 Section 716.6.63.

2009 Mechanical Code2009 Mechanical Code

Page 6: International Building Code Sections – 713.2 through 713.3.3 Section 716.6.63.

DUCT AND TRANSFER OPENINGS607.1 General. The provisions of this section shall govern theprotection of duct penetrations and air transfer openings inassemblies required to be protected.

607.1.1 Ducts that penetrate fire-resistance-ratedassemblies without dampers. Ducts that penetratefire-resistance-rated assemblies and are not required by thissection to have dampers shall comply with the requirementsof Sections 713.2 through 713.3.3 of the InternationalBuilding Code. Ducts that penetrate horizontal assembliesnot required to be contained within a shaft and not requiredby this section to have dampers shall comply with therequirements of Sections 713.4 through 713.4.2.2 of theInternational Building Code.

Page 7: International Building Code Sections – 713.2 through 713.3.3 Section 716.6.63.

607.1.1.1 Ducts that penetrate nonfire-resistance-rated assemblies. The space around a duct penetratinga nonfire-resistance-rated floor assembly shall comply with Section 716.6.3 of the International Building Code.

607.2 Installation. Fire dampers, smoke dampers, combinationfire/smoke dampers and ceiling radiation dampers locatedwithin air distribution and smoke control systems shall beinstalled in accordance with the requirements of this section,and the manufacturer's installation instructions and listing.

Page 8: International Building Code Sections – 713.2 through 713.3.3 Section 716.6.63.

607.2.1 Smoke control system. Where the installation of afire damper will interfere with the operation of a requiredsmoke control system in accordance with Section 909 oftheInternational Building Code, approved alternative protectionshall be used. Where mechanical systems includingducts and dampers used for normal building ventilationserve as part of the smoke control system, the expected performance of these systems in smoke control mode shall beaddressed in the rational analysis required by Section 909.4of the International Building Code.

Page 9: International Building Code Sections – 713.2 through 713.3.3 Section 716.6.63.

607.2.2 Hazardous exhaust ducts. Fire dampers for hazardousexhaust duct systems shall comply with Section 510.

510.6.1 Fire dampers and smoke dampers. Fire dampersand smoke dampers are prohibited in hazardous exhaust ducts.510.6.2 Floors. Hazardous exhaust systems that penetrate afloor/ceiling assembly shall be enclosed in a fire-resistance-rated shaft constructed in accordance with the InternationalBuilding Code.510.6.3 Wall assemblies. Hazardous exhaust duct systemsthat penetrate fire-resistance-rated wall assemblies shall beenclosed in fire-resistance-rated construction from the pointof penetration to the outlet terminal, except where the interiorof the duct is equipped with an approved automatic firesuppression system. Ducts shall be enclosed in accordancewith the International Building Code requirements for shaftconstruction and such enclosure shall have a minimumfire-resistance-rating of not less than the highest fire-resistance-rated wall assembly penetrated.510.6.4 Fire walls. Ducts shall not penetrate a fire wall.

Page 10: International Building Code Sections – 713.2 through 713.3.3 Section 716.6.63.

607.3 Damper testing, ratings and actuation. Damper testing,ratings and actuation shall be in accordance with Sections607.3.1 through 607.3.3.

607.3.1 Damper testing. Dampers shall be listed and bearthe label of an approved testing agency indicating compliancewith the standards in this section. Fire dampers shallcomply with the requirements of UL 555. Only fire damperslabeled for use in dynamic systems shall be installed in heating,ventilation and air-conditioning systems designed tooperate with fans on during a fire. Smoke dampers shallcomply with the requirements of UL 555S. Combinationfire/smoke dampers shall comply with the requirements ofboth UL 555 and UL 555S. Ceiling radiation dampers shallcomply with the requirements of UL 555C.

UNDERWRITERS LABORATORIES' STANDARD UL 555

Page 11: International Building Code Sections – 713.2 through 713.3.3 Section 716.6.63.

607.3.2 Damper rating. Damper ratings shall be in accordancewith Sections 607.3.2.1 through 607.3.2.3.

607.3.2.1 Fire damper ratings. Fire dampers shall havethe minimum fire protection rating specified in Table607.3.2.1 for the type of penetration.

607.3.2.2 Smoke damper ratings. Smoke damper leakageratings shall not be less than Class II. Elevated temperatureratings shall not be less than 250°F (121°C).607.3.2.3 Combination fire/smoke damper ratings.Combination fire/smoke dampers shall have the minimumfire protection rating specified for fire dampers inTable 607.3.2.1 for the type of penetration and shall alsohave a minimum Class II leakage rating and a minimumelevated temperature rating of 250°F (121°C).

Page 12: International Building Code Sections – 713.2 through 713.3.3 Section 716.6.63.

607.3.3 Damper actuation. Damper actuation shall be inaccordance with Sections 607.3.3.1 through 607.3.3.4 asapplicable.607.3.3.1 Fire damper actuation device. The firedamper actuation device shall meet one of the followingrequirements:1. The operating temperature shall be approximately50°F (28°C) above the normal temperature withinthe duct system, but not less than 160°F (71 DC).2. The operating temperature shall be not more than350°F (177°C) where located in a smoke controlsystem complying with Section 909 ofthe InternationalBuilding Code.

Page 13: International Building Code Sections – 713.2 through 713.3.3 Section 716.6.63.

607.3.3.2 Smoke damper actuation.

1. Where a smoke damper is installed within a duct, asmoke detector shall be installed in the duct within5 feet (1524 mm) of the damper with no air outletsor inlets between the detector and the damper. Thedetector shall be listed for the air velocity, temperatureand humidity anticipated at the point where itis installed. Other than in mechanical smoke controlsystems, dampers shall be closed upon fanshutdown where local smoke detectors require aminimum velocity to operate.2. Where a smoke damper is installed above smokebarrier doors in a smoke barrier, a spot-type detectorlisted for releasing service shall be installed oneither side of the smoke barrier door opening

Page 14: International Building Code Sections – 713.2 through 713.3.3 Section 716.6.63.

607.3.3.2 Smoke damper actuation. Continued.

3. Where a smoke damper is installed within anunducted opening in a wall, a spot-type detectorlisted for releasing service shall be installed within5 feet (1524 mm) horizontally of the damper.4. Where a smoke damper is installed in a corridorwall or ceiling, the damper shall be permitted to becontrolled by a smoke detection system installed inthe corridor.5. Where a total-coverage smoke detector system isprovided within areas served by a heating, ventilationand air-conditioning (HVAC) system, smokedampers shall be permitted to be controlled by thesmoke detection system.

Page 15: International Building Code Sections – 713.2 through 713.3.3 Section 716.6.63.

607.3.3.3 Combination fire/smoke damper actuation.Combination fire/smoke damper actuation shall be inaccordance with Sections 607.3.3.1 and 607.3.3.2. Combinationfire/smoke dampers installed in smoke controlsystem shaft penetrations shall not be activated by localarea smoke detection unless it is secondary to the smokemanagement system controls.607.3.3.4 Ceiling radiation damper actuation. Theoperating temperature of a ceiling radiation damper actuationdevice shall be 50°F (28°C) above the normal temperaturewithin the duct system, but not less than 160°F

Page 16: International Building Code Sections – 713.2 through 713.3.3 Section 716.6.63.

607.4 Access and identification. Fire and smoke dampersshall be provided with an approved means of access, largeenough to permit inspection and maintenance of the damperand its operating parts. The access shall not affect the integrityof fire-resistance-rated assemblies. The access openings shallnot reduce the fire-resistance rating of the assembly. Accesspoints shall be permanently identified on the exterior by a labelhaving letters not less than 0.5 inch (12.7 mm) in height reading:FIRE/SMOKE DAMPER, SMOKE DAMPER or FIREDAMPER. Access doors in ducts shall be tight fitting and suitablefor the required duct construction.

Page 17: International Building Code Sections – 713.2 through 713.3.3 Section 716.6.63.

607.5 Where required. Fire dampers, smoke dampers andcombination fire/smoke dampers shall be provided at the locationsprescribed in Sections 607.5.1 through 607.5.7. Where anassembly is required to have both fire dampers and smokedampers, combination fire/smoke dampers or a fire damperand smoke damper shall be required.

607.5.1 Fire walls. Ducts and air transfer openings permittedin fire walls in accordance with Section 705.11 of theInternational Building Code shall be protected with listedfire dampers installed in accordance with their listing.(This section given is a typo) Should be 706.11

706.11 Ducts and air transfer openings. Ducts and air transferopenings shall not penetrate fire walls.Exception: Penetrations by ducts and air transfer openingsof fire walls that are not on a lot line shall be allowed providedthe penetrations comply with Section 716. The sizeand aggregate width ofall openings shall not exceed the limitations of Section 706.8. (156 sq ft or 25% of wall )

Page 18: International Building Code Sections – 713.2 through 713.3.3 Section 716.6.63.

607.5.1.1 Horizontal exits. A listed smoke damper Idesigned to resist the passage of smoke shall be providedat each point that a duct or air transfer opening penetratesa fire wall that serves as a horizontal exit.

607.5.2 Fire barriers. Ducts and air transfer openings thatpenetrate fire barriers shall be protected with listed firedampers installed in accordance with their listing. Ductsand air transfer openings shall not penetrate exit enclosuresand exit passageways except as permitted by Sections 1022.4 and 1023.6, respectively, of the International BuildingCode.

1022.4 Penetrations. Penetrations into and openings through an exit enclosure are prohibited except for required exit doors,equipment and ductwork necessary for independent ventilation or pressurization…. 1023.6 except for exit passageway

Page 19: International Building Code Sections – 713.2 through 713.3.3 Section 716.6.63.

Exception: Fire dampers are not required at penetrationsof fire barriers where any of the following apply:

1. Penetrations are tested in accordance with ASTME 119 or UL 263 as part of the fire-resistance-rated assembly.

2. Ducts are used as part of an approved smoke controlsystem in accordance with Section 513 and where the fire damper would interfere with the operation of the smoke control system.

3. Such walls are penetrated by ducted HVAC systems,have a required fire-resistance rating of 1hour or less, are in areas of other than Group Hand are in buildings equipped throughout with an automatic sprinkler system

For the purposes of this exception, a ducted HVAC system shall be a duct system for the structure's HVAC system. Such a duct systemshall be constructed of sheet steel not less than 26 gage [0.0217 inch (0.55 mm)] thickness and shall be continuous from the air-handling appliance or equipment to the air outlet and inlet terminals.

Page 20: International Building Code Sections – 713.2 through 713.3.3 Section 716.6.63.

607.5.2.1 Horizontal exits. A listed smoke damper designed to resist the passage of smoke shall be provided at each point that a duct or air transfer opening penetrates afire barrier that serves as a horizontal exit.

607.5.3 Fire partitions. Ducts and air transfer openings that penetrate fire partitions shall be protected with listed fire dampers installed in accordance with their listing.Exception: In occupancies other than Group H, fire dampersare not required where any of the following apply:

1. Corridor walls in buildings equipped throughoutwith an automatic sprinkler system2. The partitions are tenant partitions in covered mall buildings where the walls are not required by provisions elsewhere in the International BuildingCode to extend to the underside of the floor or roof sheathing, slab or deck above.

Page 21: International Building Code Sections – 713.2 through 713.3.3 Section 716.6.63.

3. The duct system is constructed of approved materials in accordance with Section 603 and the duct penetrating the wall complies with all of the followingrequirements:3.1. The duct shall not exceed 100 squareinches (0.06 m2).3.2. The duct shall be constructed of steel aminimum of 0.0217 inch (0.55 mm) inthickness.

3.3. The duct shall not have openings that communicatethe corridor with adjacent spacesor rooms.3.4. The duct shall be installed above a ceiling.3.5. The duct shall not terminate at a wall registerin the fire-resistance-rated wall.

Page 22: International Building Code Sections – 713.2 through 713.3.3 Section 716.6.63.

3.6. A minimum 12-inch-Iong by 0.060-inch-thick steel sleeveshall be centered in each duct opening. The sleeve shall be secured to both sides of the wall and all four sides of the sleeve with minimum 11/ 2-inch by 11/ 2-inch by 0.060-inch steel retaining angles. The retaining angles shall be secured to the sleeve and the wall with No. 10 (M5) screws. The annularspace between the steel sleeve and the wall opening shall be filled with rock (mineral) wool batting on all sides.

Page 23: International Building Code Sections – 713.2 through 713.3.3 Section 716.6.63.

607.5.4 Corridors/smoke barriers. A listed smoke damperdesigned to resist the passage of smoke shall be provided ateach point a duct or air transfer opening penetrates a smokebarrier wall or a corridor enclosure required to have smokeand draft control doors in accordance with the InternationalBuilding Code. Smoke dampers and smoke damper actuationmethods shall comply with Section 607.5.4.1.Exceptions:1. Smoke dampers are not required in corridor penetrationswhere the building is equipped throughout with an approved smoke control system in accordance with Section 513 and smoke dampers are not necessary for the operation and control of the system.2. Smoke dampers are not required in smoke barrier penetrations where the openings in ducts are limited to a single smoke compartment and the ducts are constructed of steel.3. Smoke dampers are not required in corridor penetrationswhere the duct is constructed of steel notless than 0.019 inch (0.48 mm) in thickness andthere are no openings serving the corridor.

Page 24: International Building Code Sections – 713.2 through 713.3.3 Section 716.6.63.

607.5.4.1 Smoke damper. The smoke damper shall closeupon actuation of a listed smoke detector or detectorsinstalled in accordance with the International BuildingCode and one of the following methods, as applicable:

1. Where a damper is installed within a duct, a smoke detector shall be installed in the duct within 5 feet of the damper with no air outlets or inlets between the detector and the damper. Thedetector shall be listed for the air velocity, temperatureand humidity anticipated at the point where it is installed.2. Where a damper is installed above smoke barrier doors in a smoke barrier, a spot-type detector listed for releasing service shall be installed on either side of the smoke barrier door opening.

Page 25: International Building Code Sections – 713.2 through 713.3.3 Section 716.6.63.

3. Where a damper is installed within an unducted opening in a wall, a spot-type detector listed for releasing service shall be installed within 5 feet horizontally of the damper.4. Where a damper is installed in a corridor wall, the damper shall be permitted to be controlled by a smoke detection system installed in the corridor.5. Where a total-coverage smoke detector system is provided within all areas served by an HVAC system, dampers shall be permitted to be controlled by the smoke detection system.

607.5.5 Shaft enclosures. Shaft enclosures that are permittedto be penetrated by ducts and air transfer openings shall be protected with approved fire and smoke dampers installed in accordance with their listing.

Exceptions:1. Fire dampers are not required at penetrations ofshafts where:

Page 26: International Building Code Sections – 713.2 through 713.3.3 Section 716.6.63.

1.1. Steel exhaust subducts extend at least 22 inches vertically in exhaust shafts provided that there is a continuousairflow upward to the outdoors; or 1.2. Penetrations are tested in accordance withASTM E 119 or UL 263 as part of the fire-resistance-rated assembly; or1.3. Ducts are used as part of an approved smoke control system in accordance with Section 909 of the International BuildingCode, and where the fire damper will interfere with the operation of the smoke control system; or1.4. The penetrations are in parking garage exhaust or supply shafts that are separated from other building shafts by not less than 2-hour fire-resistance-rated construction.2. In Group Band R occupancies equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 of the International Building Code, smoke dampers are not required at penetrations of shafts where kitchen, clothes dryer, bathroom and toilet room exhaust openings with steel exhaust subducts, having a minimum thickness of 0.0187 inch (No. 26 gage), extend at least 22 inches

Page 27: International Building Code Sections – 713.2 through 713.3.3 Section 716.6.63.

vertically and the exhaust fan at the upper terminus is powered continuously in accordance with the provisions of Section 909.11 of the International Building Code, and maintains airflow upward to the outdoors.

3. Smoke dampers are not required at penetrations of exhaust or supply shafts in parking garages that are separated from other building shafts by not less than 2-hour fire-resistance-rated construction

4. Smoke dampers are not required at penetrations of shafts where ducts are used as part of an approved mechanical smoke control system designed in accordance with Section 909 of the International Building Code and where the smoke damper willinterfere with the operation of the smoke control system.

5. Fire dampers and combination fire/smoke dampers are not required in kitchen and clothes dryer exhaust systems installed in accordance with this code.

Page 28: International Building Code Sections – 713.2 through 713.3.3 Section 716.6.63.

607.5.5.1 Enclosure at the bottom. Shaft enclosuresthat do not extend to the bottom of the building or structureshall be protected in accordance with Section 708.11of the International Building Code.

607.5.6 Exterior walls. Ducts and air transfer openings infire-resistance-rated exterior walls required to have protectedopenings in accordance with Section 705.10 of theInternational Building Code shall be protected with listedfire dampers installed in accordance with their listing.607.5.7 Smoke partitions. A listed smoke damperdesigned to resist the passage of smoke shall be provided at each point where an air transfer opening penetrates a smoke partition. Smoke dampers and smoke damper actuation methods shall comply with Section 607.3.3.2.Exception: Where the installation of a smoke damperwill interfere with the operation of a required smoke controlsystem in accordance with Section 513, approvedalternate protection shall be used.

Page 29: International Building Code Sections – 713.2 through 713.3.3 Section 716.6.63.

607.6 Horizontal assemblies. Penetrations by air ducts of afloor, floor/ceiling assembly or the ceiling membrane of aroof/ceiling assembly shall be protected by a shaft enclosurethat complies with Section 708 and Sections 716.6.1 through716.6.3 of the International Building Code or shall complywith Sections 607.6.1 through 607.6.3.

607.6.1 Through penetrations. In occupancies other thanGroups 1-2 and 1-3, a duct constructed ofapproved materials in accordance with Section 603 that penetrates a fire-resistance- rated floor/ceiling assembly that connects not more than two stories is permitted without shaft enclosure protection provided that a listed fire damper is installed at the floor line or the duct is protected in accordance with Section 713.4 of the International Building Code. For air transfer openings, see Exception 7, Section 708.2 of the InternationalBuilding Code.

Exception: A duct is permitted to penetrate three floorsor less without a fire damper at each floor provided itmeets all of the following requirements.

Page 30: International Building Code Sections – 713.2 through 713.3.3 Section 716.6.63.

1. The duct shall be contained and located within thecavity of a wall and shall be constructed of steelhaving a minimum thickness of 0.0187 inch (No. 26 gage).2. The duct shall open into only one dwelling unit orsleeping unit and the duct system shall be continuousfrom the unit to the exterior of the building.3. The duct shall not exceed 4-inch nominal diameter and the total area of such ducts shall not exceed 100 square inches for any 100 squarefeet of the floor area.4. The annular space around the duct is protected with materials that prevent the passage of flame and hot gases sufficient to ignite cotton waste when subjected to ASTM E 119 or UL 263 time-temperature

5. Grille openings located in a ceiling of a fire-resistance-rated floor/ceiling or roof/ceiling assemblyshall be protected with a listed ceiling radiationdamper installed in accordance with Section607.6.2.1.

Page 31: International Building Code Sections – 713.2 through 713.3.3 Section 716.6.63.

607.6.2 Membrane penetrations. Ducts and air transferopenings constructed of approved materials, in accordancewith Section 603, that penetrate the ceiling membrane of afire-resistance-rated floor/ceiling or roof/ceiling assemblyshall be protected with one of the following:1. A shaft enclosure in accordance with Section 708 ofthe International Building Code.2. A listed ceiling radiation damper installed at the ceilingline where a duct penetrates the ceiling of a fireresistance-rated floor/ceiling or roof/ceiling assembly.3. A listed ceiling radiation damper installed at the ceilingline where a diffuser with no duct attached penetratesthe ceiling of a fire-resistance-rated floor/ceiling or roof/ceiling assembly.

Page 32: International Building Code Sections – 713.2 through 713.3.3 Section 716.6.63.

607.6.2.1 Ceiling radiation dampers. Ceiling radiation dampers shall be tested as part of a fire-resistance-rated floor/ceiling or roof/ceiling assembly in accordance with ASTME 119 or UL 263. Ceiling radiation dampers shall be installed in accordance with the details listed in the fire-resistance-rated assembly and the manufacturer's installation instructions and the listing. Ceiling radiation dampers are not required where either of the followingapplies:

1. Tests in accordance with ASTM E 119 or UL 263have shown that ceiling radiation dampers are notnecessary to maintain the fire-resistance rating ofthe assembly.2. Where exhaust duct penetrations are protected inaccordance with Section 713.4.1.2 of the InternationalBuilding Code, are located within the cavityof a wall and do not pass through another dwellingunit or tenant space.

Page 33: International Building Code Sections – 713.2 through 713.3.3 Section 716.6.63.

607.6.3 Nonfire-resistance-rated floor assemblies. Duct systems constructed of approved materials in accordance with Section 603 that penetrate nonfire-resistance-rated floor assemblies shall be protected by any of the following methods:1. A shaft enclosure in accordance with Section 708 ofthe International Building Code.2. The duct connects not more than two stories, and theannular space around the penetrating duct is protected with an approved noncombustible material that resists the free passage of flame and the products of combustion.3. The duct connects not more than three stories, and theannular space around the penetrating duct is protectedwith an approved noncombustible material thatresists the free passage of flame and the products ofcombustion, and a listed fire damper is installed ateach floor line.

Exception: Fire dampers are not required in ducts withinindividual residential dwelling units.

Page 34: International Building Code Sections – 713.2 through 713.3.3 Section 716.6.63.

607.7 Flexible ducts and air connectors. Flexible ducts andair connectors shall not pass through any fire-resistance-ratedassembly.