    Liebert

    C o s t E f f e c t i v e , F l e x i b l e A i r C o n d i t i o n i n g

    F o r U n m a n n e d T e l e c o m m u n i c a t i o n

    S h e l t e r s A n d O t h e r R e m o t e S t r u c t u r e s

    Heat Removal/Environmental ControI n t e l e C oo l2

    A REAL CHOICE FORTELECOM SHELTER PROTECTION

  • 8/12/2019 Intelecool2

    2/8

    AIR CONDITIONING DESIGNED FOR TODAYS

    TELECOMMUNICATIONS SHELTER NEEDS

    Even though they look the same on the outside, telecommunications shelters have very different requirements. Redundant city

    shelters can be produced inexpensively. Suburban and country shelters usually require greater reliability. And those sited well

    away from civilization need both high levels of reliability and remote communications capacity.

    So why is it that shelter air conditioners are all the same?

    Theyre not, thanks to Liebert. The first name in protection for sensitive systems for more than 30 years,

    Liebert has created the InteleCool 2 shelter air conditioning system.

    Its not just a shelter air conditioner...its a custom-configured model that fits your exact needs and budget. Want

    a bare-bones system at minimum cost? Consider the InteleCool 2, basic model. Want a top-of-the-line unit for that

    vital remote shelter? Try the InteleCool 2, advanced system. Need a field replacement/upgrade of a 3 ton air conditioner

    to 4 or 5 ton? Take the InteleCool 2 replacement/upgrade unit. Same name...very different shelter air conditioner.

    In the next few pages, well show you how to custom-configure an InteleCool 2 for every application.

    Liebert Means Legendary Reliability

    Liebert invented high-reliability, precision-controlled

    air conditioning for computers and computer rooms

    more than 30 years ago. Today, the telecommunicationsindustry worldwide relies on Liebert products to protect

    sensitive installations. Liebert air conditioning has more

    installations and has logged more hours of vital system

    protection than all of its competitors combined.

    And we not only build quality protection...we keep it

    running. Lieberts service network has maintenance and

    support offices around the world, and a 24-hour dispatch

    center. Many customers dont even know they had a

    problem until after it was diagnosed and fixed.

    A Perfe ct Ma tc h For

    Many Critical Applications

    In addition to a wide range of telecommunications

    shelter applications, the InteleCool 2 can beused at virtually any site that requires reliable cooling

    in a small, l ightweight package:

    Cellular

    Radio Paging

    Microwave/Satellite

    Earth Stations

    PCS Services

    Mobile/Modular

    Electronic Equipment

    Structures

  • 8/12/2019 Intelecool2

    3/8

    Basic Cooling

    For shelters that are less critical and located close to service capability,

    minimum seasonal air conditioning is usually sufficient. Depending on the

    application, single or redundant units may be used. A simple remote

    monitoring capability may also be added.

    Critical Shelters

    Shelters with highly sensitive equipment and limited site access must keep

    operating no matter what. These sites may require dual units, high-reliability

    components such as a scroll compressor, energy saving capabilities such

    as an economizer, heating, remote monitoring and switchover control.

    The InteleCool 2 T-Pack is designed for these types of common

    telecommunications shelters. This package includes the basic InteleCool 2

    system with all of the most popular options including high and low pressure

    switches, fan cycle control and low pressure bypass.

    Special Locations

    You dont always have a choice as to where to place a telecom shelter.

    It may be located in an urban environment where noise, appearance and

    other factors are important. Or it may be miles from nowhere on the side

    of a mountainmaking absolute reliability an important requirement.

    The InteleCool 2 is designed with the flexibility to match the multiple protection

    needs of todays telecommunications industry. You pick the level of protection your

    application requires and Liebert will configure an InteleCool 2 for you...

  • 8/12/2019 Intelecool2

    4/8

    Painted steel or

    aluminum cabinets

    Optional Economizer

    with spring-return

    actuator

    Copper-tube,

    aluminum fin coils

    Heavy-duty double

    width blower

    Choice of compressor

    on right or left side

    of unit

    NOW YOU CAN CUSTOM-CONFIGURE

    SHELTER AIR CONDITIONING TO YOUREX ACT NEEDS AND BUDGET

    Maximum Flexibility Designed To Meet

    Al l Your Sh el ter Co ol in g Requ ir em en ts

  • 8/12/2019 Intelecool2

    5/8

    No more wondering why you paid for all those features you dont use...or lamenting that you could have

    saved a lot of problems if you only added that one little feature when you had it installed.

    This simple, seven-step process can determine your needsand configure protection to match those needs exactly.

    1

    Step 1: Cooling Capacity

    The InteleCool 2 is offered in five

    capacities ranging from 1.5 to 5 tons,

    covering the needs of almost any

    shelter. Options and configurations

    are available so you can match the

    features you need to the cooling

    capacity that's required. 2

    Step 2: Cabinet

    The self-contained InteleCool 2

    cabinets come with your choice of

    painted steel or aluminum panels.

    Painted steel panels are available

    in a choice of four different colors.

    The evaporator supply and return

    openings match industry standard

    dimensions for ease of installation.

    3Step 3: CompressorThe InteleCool 2 offers a choice of compressors to match your specific reliability needs. A rugged

    hermetic compressor is standard on the 1.5, 2 and 3 ton units. For applications requiring the

    highest reliability and lower energy use, a scroll compressor is also available as an option on the

    1.5, 2 and 3 ton sizes and is standard equipment on the 4 and 5 ton capacity models. With fewer

    moving parts and continuous compression, the scroll compressor is 14% more efficient than

    hermetic units. It operates at an EER level of 11.3 one of the highest in the industry. The scroll

    compressor is also ideal in applications where noise is a factor thanks to its low noise and vibration.

    Compressors can also be located on either the right or left side of the u nit to make it easier to service dual installations.

    Almond

    Bright White

    Desert Brown

    HermeticScroll

    Aluminum

    Tan

  • 8/12/2019 Intelecool2

    6/8

    No EconomizerWhen outside

    temperatures are

    warmer than the inside

    air, the Economizer is

    closed and indoor air

    is recirculated to

    maintain proper cooling.

    Full EconomizerThe Economizer takes

    advantage of low

    outdoor ambients,

    drawing on this cool

    air to maintain indoor

    temperatures. The

    result is cooling at

    lower energy costs,

    also saving wear oncomponents.

    ModulatedIn Modulated mode,

    the Economizer draws

    cool outside air and

    recirculates indoor air,

    reducing compressor

    run time.

    5Step 5: Economizer Option

    The InteleCool 2 can be equipped with an economizer

    system that uses modulating dampers to draw in

    filtered, outside ambient air for cooling when the exterior

    temperature drops below a pre-set level. These outside air

    temperature settings are field adjustable. The economizer

    saves energy and reduces component wear.

    4Step 4: Fresh Air Damper

    If required by your application, this

    feature allows the introduction of

    outside air into the shelter by means

    of a field-adjustable damper.

    6

    7Step 7: Monitoring and Communications

    Many Liebert remote monitoring options are available

    ranging from relatively simple contact-closure sensing

    to the Liebert Tele 2 for more complete monitoring

    and control. Liebert also provides 24-hour monitoring

    and alarm dispatch capability from our Columbus, Ohio,

    command center.

    Step 6: Controls

    The high quality thermostat senses

    ambient temperature and compares it

    to your predetermined requirements.

    For the highest levels of reliability

    and to minimize site downtime critical shelters can be equipped with

    two InteleCool 2 units and an

    autochangeover system that balances

    runtime and automatically switches

    from one unit to another in case of a

    system failure. Dual operation can be

    accomplished with either the Dual

    Unit Control thermostat or the Tele2

    control and monitoring system.

    InteleCool 2 with optional common alarm feature

  • 8/12/2019 Intelecool2

    7/8

    Swift, Simple Installation

    When deadlines loom, a simple installation is worth

    almost anything...mostly because you cant get one at

    any price. The InteleCool 2 is the exception to the rule.

    However you configure the InteleCool 2, it comes

    from the Liebert factory wired, piped, charged with

    refrigerant and factory-tested as a complete system.

    Each standard unit is shipped with a Nationally

    Recognized Testing Laboratory (NRTL) listing. If the

    wall openings and electric service are in place, the

    InteleCool 2 can be installed in as little as 30 minutes.

    If you need to field replace/upgrade a 3 ton air conditioner

    to 4 or 5 ton, take the ET3 Series (ET3xx) of InteleCool 2

    Installation time is

    minimized with

    InteleCools

    self-contained

    packaging.

    Industry-standard

    evaporator supply

    and return openings

    allow the unit to be

    placed quickly.

    H

    G

    F

    E

    BRETURN

    Ws

    ASUPPLY

    Wu

    J

    The ET3 Series ofInteleCool 2 isdesigned as a fieldreplacement/upgradeof a 3 ton air conditionerto a 4 or 5 ton usingexisting air openings.This allows a unit withmore cooling capacityto be installed quicklyand easily. No cuttingor sawing of theshelter is required.

    Specifications

    60Hz Models 95F Outdoor

    Ambient ET018 ET024 ET036 ET048/ET348 ET060/ET360

    Compressor Type Hermetic Scroll Hermetic Scroll Hermetic Scroll Scroll Scroll

    80/67F 26.7/19.4C

    Total BTU/H 19300 19200 23200 22400 33800 34600 46900 56000

    Total kW 5.65 5.63 6.80 6.56 9.90 10.14 13.74 16.41

    Sensible BTU/H 17200 17200 19100 18800 26100 26400 38400 41900

    Sensible kW 5.04 5.04 5.60 5.51 7.65 7.74 11.25 12.28

    75/62.5F 23.9/16.9C

    Total BTU/H 17800 17900 21500 20900 31400 32300 43800 52400

    Total kW 5.22 5.24 6.30 6.12 9.20 9.46 12.83 15.35

    Sensible BTU/H 16600 16600 18400 18200 25300 25700 37300 40800

    Sensible kW 4.86 4.86 5.39 5.33 7.41 7.53 10.93 11.95

    Weight

    (Standard Unit) lbs.(kg) 330 (150) 330 (150) 330 (150) 470( 213) 470 (213)

    (Unit w/Economizer) lbs.(kg) 350 (159) 350 (159) 350 (159) 490( 222) 490 (222)

    50Hz Models 95F Outdoor

    Ambient ET017 ET023 ET035 ET047/ET347 ET059/ET359

    Compressor Type Hermetic Scroll Hermetic Scroll Hermetic Scroll Scroll Scroll

    80/67F 26.7/19.4C

    Total BTU/H 16500 19200 19900 21600 28800 27700 39800 49000

    Total kW 4.83 5.63 5.83 6.33 8.44 8.12 11.66 14.36Sensible BTU/H 14700 15800 16500 17100 22300 21900 32500 36000

    Sensible kW 4.31 4.63 4.83 5.01 6.53 6.42 9.52 10.55

    75/62.5F 23.9/16.9C

    Total BTU/H 15300 18000 18400 20100 26800 25900 37200 45900

    Total kW 4.48 5.27 5.39 5.89 7.85 7.59 10.90 13.45

    Sensible BTU/H 14200 15300 15900 16600 21700 21300 31600 35100

    Sensible kW 4.16 4.48 4.66 4.86 6.36 6.24 9.26 10.28

    Weight

    (Standard Unit) lbs.(kg) 330 (150) 330 (150) 330 (150) 470( 213) 470 (213)

    (Unit w/Economizer) lbs.(kg) 350 (159) 350 (159) 350 (159) 490( 222) 490 (222)

    Model Wu Ws Wf A B E F G H J

    1.5/2 Ton 37.1(943) 17.8(451) 38.8(984) 20.0(508) 20.0(508) 8.0(203) 20.8(527) 12.0(305) 25.1(638) 69.8(1772)

    3 Ton 37.1(943) 17.8(451) 38.8(984) 28.0(711) 28.0(711) 8.0(203) 18.0(457) 14.0(356) 26.0(660) 69.8(1772)

    4/5 Ton with 3 ton openings 4 1. 0( 10 41 ) 2 2. 5( 57 2) 4 2. 75 (1 08 6) 3 0. 3( 76 8) 2 8. 0( 71 1) 8 .0 (2 03 ) 1 8. 0( 45 7) 1 4. 0( 35 6) 3 7. 5( 95 2) 8 3. 0( 21 08 )

    Wu= unit width Wf=width to flange edges A=height to top of flange

    Shaded areas ina recommendeclearance of 34in front and 30each side or 36each side when adjacent to anotfor component arecommended mclearances referinstallation man

  • 8/12/2019 Intelecool2

    8/8

    The Liebert Experience

    L I E B E R T C O R P O R A T I O N

    1050 DEARBORN DRIVE

    P.O. BOX 29186

    COLUMBUS, OHIO 43229

    800.877.9222 PHONE (U.S. &

    CANADA ONLY)

    614.888.0246 PHONE (OUTSIDE U.S.)

    614.841.6022 FAX

    VIA LEONARDO DA VINCI 8

    ZONA INDUSTRIALE TOGNANA

    35028 PIOVE DI SACCO (PD)

    ITALY

    39 049 9719 111 PHONE

    39 049 5841 257 FAX

    EMERSON NETWORK POWER ASIA PACIFIC

    7/F., DAH SING FINANCIAL CENTRE

    108 GLOUCESTER RD, WANCHAI

    HONG KONG

    852 25722201 PHONE

    852 28029250 FAX

    L I E B E R T W E B S I T E

    http://www.liebert.com

    2 4 X 7 T E C H S U P P O R T

    800 222 5877 PHONE

    614 841 6755 (OUTSIDE U.S.)

    While every precaution has been taken to ensure accuracy andcompleteness in this literature, Liebert Corporation assumes noresponsibility, and disclaims all liability for damages resultingfrom use of this information or for any errors or omissions.

    2004 Liebert Corporation. All rights reserved throughoutthe world. Specifications subject to change without notice.

    All names referred to are trademarks or registered trademarksof their respective owners.

    Liebert and the Liebert logo are registered trademarksof the Liebert Corporation.

    Keeping Business in Business is a registered trademark

    of the Liebert Corporation.The Emerson logo is a trademark and service markof Emerson Electric Co.

    SL-19500 (R3/04)Printed in USA

    Heat Removal/Environmental Contro

    No organization in the world today has a better understanding of exactly what it takes to keep critical

    information and industrial processes operating continuously than Liebert.

    We are the only company in this business that maintains a strong local presence of

    Representatives, Distributors and Resellers. This resource, coupled with our broad product

    line, gives Liebert the ability to create a "tailored solution" that will meet your protection

    needs precisely and efficiently.

    There are Liebert systems designed for nearly every application from basic protection for

    network PCs, servers or point-of-sale terminalsto highly engineered systems for computerrooms, telecommunications centers, Internet hosting sites, colocation facilities and industrial

    control rooms. But no matter what the size or complexity, the availability of these critical

    electronic systems is Lieberts primary focus.

    With your purchase of a Liebert product, you are buying into a company that stands behind its

    products. You are also aligning yourself with an organization that has a reputation for quality

    and reliability that is second to none.

    After the sale, Liebert provides comprehensive support wherever and whenever it's needed,

    with the largest service organization in the industry.

    In the systems protection business it's when you need someone to count on that you find outwhether youve made the right choice. Liebert customers many of them with us for over three

    decades already know how good their decision was.

    TOTAL CONFIDENCE IN

    THE DECISION YOU'VE MADE.

    That Is

    I n t e l e C oo l2

    The day your critical operations arethreatened by excessive heat, powerproblems or other risks is no time tofind out if a "simple" solution to systemprotection will work. Let Liebert helpyou make the smart decision aboutassuring reliability in your highavailability facilities.