1. Technical Specifications Product type Independent DALI sensor (Daylight harvest) Operating voltage 120~277VAC 50/60Hz Switched power 2 x 2000W (resistive) 2 x 800W (capacitive) Power consumption < 1W Detection angle 360 o Detection range 10% / 50% / 100% Hold time 2s / 30s / 1min / 5min / 10min / 30min Stand-by time 0s / 10s / 1min / 10min / 30min / + Stand-by dimming level 10% / 20% / 30% Daylight threshold 2 ~ 50Lux , Disable Warmming-up time 20s Operating temperature -20 o C ~ +50 o C IP rating IP65 8 3. Functions Daylight sensor measures the available surrounding natural light, calculates how much electrical light is needed to reach the total lux expected. The demand is given to the LED driver by DALI signal, so as to deliver the needed amount of electric light. 3.1 Daylight Harvest (Daylight Regulating) Sometimes also know as “Potential-Free” or “Volt-Free” sensor, the dry contact sensors from Hytronik are designed to operate with external monitoring systems. They operate as conventional occupancy sensors, with the output available as shown in the table below: 3.2 Dry Contact Control Double “L” “N” terminal makes it easy for wire loop-in and loop-out, and saves the cost of terminal block and assembly time. 3.3 Loop-in and loop-out HF Aisle Sensor with DALI Control HCD450VDSRC Installation and Instruction Manual 2. Instruction and Dimension Warnings: 1. Installation of the sensor involves connecting it to the mains supply. This work must be carried out by a specialist in accordance with electrotechnical regulations. 2. Disconnect supply before installing. 4. Wiring Diagram 5. Detection Pattern 0 24 Light level Time (hrs) Normal Electric Light Daylight controlled light Energy Saving Zone Natural light Hold time Stand-by time HCD450VDSRC-20170109-A1 Wire out Infrared remote receiver Daylight sensor Installation rack Sensor Antenna LED indication 125.5 135 115.4 95 L L L N N N N N 1 2 C O COM + 1-10V+ DALI - DALI 1-10V- 25 46 65 112.9 50.6 82.3 114 56 Detection State Contacts Made Presence Absence Nc - Com No - Com LED Driver LED Driver HCD450VDSRC Power N N N N L L N L L 1 L 2 1-10V + 1-10V - 1-10V + 1-10V - + DALI - DALI + DALI - DALI N L 1-10V + 1-10V - + DALI - DALI N N C O COM 25m x 6m coverage @ 8m mounting height 25m x 6m coverage @ 15m mounting height 50m detection length @ 5m mounting height
2
Embed
Instruction manual for HCD450VDSRC - Hytronik · HCD450VDSRC-20170109-A1 Wire out Infrared remote receiver Daylight sensor Installation rack Sensor Antenna LED indication 125.5 135
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
1. Technical Specifications
Product type Independent DALI sensor (Daylight harvest)
Operating voltage 120~277VAC 50/60Hz
Switched power 2 x 2000W (resistive) 2 x 800W (capacitive)
Power consumption < 1W
Detection angle 360o
Detection range 10% / 50% / 100%
Hold time 2s / 30s / 1min / 5min / 10min / 30min
Stand-by time 0s / 10s / 1min / 10min / 30min / +
Stand-by dimming level 10% / 20% / 30%
Daylight threshold 2 ~ 50Lux , Disable
Warmming-up time 20s
Operating temperature -20oC ~ +50
oC
IP rating IP65
8
3. Functions
Daylight sensor measures the available surrounding natural light, calculates how much electrical light is needed to reach the total lux expected. The demand is given to the LED driver by DALI signal, so as to deliver the needed amount of electric light.
3.1 Daylight Harvest (Daylight Regulating)
Sometimes also know as “Potential-Free” or “Volt-Free” sensor, the dry contact sensors from Hytronik are designed to operate with external monitoring systems. They operate as conventional occupancy sensors, with the output available as shown in the table below:
3.2 Dry Contact Control
Double “L” “N” terminal makes it easy for wire loop-in and loop-out, and saves the cost of terminal block and assembly time.
3.3 Loop-in and loop-out
HF Aisle Sensor with DALI Control HCD450VDSRCInstallation and Instruction Manual
2. Instruction and DimensionWarnings: 1. Installation of the sensor involves connecting it to the mains supply. This work must be carried out by a specialist in accordance with electrotechnical regulations.2. Disconnect supply before installing.
Permanent ON/OFF [ ]1. Press button , to select permanent ON or permanent OFF mode.2. Press button to resume automatic operation. (Please refer to explanation below)
Auto Mode [ ]Press button to in initiate automatic mode.The sensor starts working and all settings remain as before the light was switched ON/OFF.
RESET [ ]
1
2
2 3 4
button 1
button 2
Press button , all settings go back to the values as below:Detection range: 100% Hold-time: 5min Stand-by period: 10min Stand-by dimming level: 10% Daylight sensor: disabled
3
button 3
Test 2s function [ ]1.Press button , the sensor goes into testmode (hold time 2s). N.B. the stand-by period and daylight sensor settings are disabled in test mode.2.Press button to exit from this mode, and the sensor settings are changed accordingly.
8
3 4 11
button 8
Ambient daylight threshold [ ]Press button , the latest surrounding lux value overwrites previous lux value learned, and is set as the daylight threshold. This feature enables the fixture to function well in any environment.
10
button 10
Power output [ ]Press button , the output shifts between 80% and 100%, for energysaving purposes.
5
button 5
Dim +/- [ ]Press button to adjust the light brightness between 10%~100% during hold-time. “+” increases the light level, “-” will decrease the light level.
9
button 9
Lux disable [ ]Press button , the built-in daylight sensor is disabled, the light will always operate upon detection regardless of ambient light level.
14
button 14
Button is disabled. 15
Manual override/ Semi-auto [ ]button 15
Detection range [ ]Press buttons in zone to set detection range at 100%/50%/10%.6
zone 6
Hold time [ ]Press buttons in zone to set hold time at 30s / 1min / 5min / 10min / 30min.
11
zone 11
Stand-by period [ ]Press buttons in zone to set the stand-by period at 0s / 10s / 1min / 10min / 30min / +∞.Note: “0s” means on/off control; “+∞” means bi-leve of dimming control, the light will never switch off. (i.e. the light remains at the stand-by dimming level until motion is detected.)
12
zone 12
Stand-by dimming level [ ]Press buttons in zone to set the stand-by dimming level at 10%/20%/30%.
7
zone 7
Daylight sensor [ ]Press buttons in zone to set daylight sensor at 2lux / 10lux / 50lux.13
zone 13
5
94
11
12
Stand-by dimming level
Detection range
ON/OFF Auto Mode Reset
Power80%
Test2s
10% 20%
30s 1min
100%
30min10min5min
0s 10s 1min
30%
SC1 SC2
SC3
Scene mode
10min
50% 10%
30min
Hold-time
Stand-by period
5min
LuxDisable
2Lux
10Lux
50Lux
Daylight Sensor
SC4
Power100% +
-Dim
M/A
312
7
8
6 10
13
14
15
HRC-05
Note: the buzzer beeps one time when RC receives signal successfully
There are 4 scene modes built into the remote control for different applications:
Scene mode options [ ]zone 4
Scene options
Detection range
Hold time
Stand-by period
Stand-by dimming leve
Daylight sensor
SC1 SC2 SC3 SC4
100% 100% 100% 100%
10% 10% 10% 10%
1min 5min 10min 10min
2Lux 2Lux 10Lux 50Lux
10min 10min 30min + 8
6 11
13
12
7
Note: the end-user can fine tune the settings by pressing buttons of detection range / hold time / stand-by period / stand-by dimming level /daylight sensor , the last setting will over-write that feature of the pre-set scene.